EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
INTRODUCTIONThe Everpure® Conserv HE-3 High Efficiency Reverse Osmosis System is a pre-engineered, pre-assembled system solution designed to provide high purity water for numerous applications, such as premium espresso, coffee, ice, blended beverages and steam. The system combines a number of water treatment technologies into one easy-to-install package. The system provides superior protection against taste- and odor-causing contaminants while removing dirt*, particulates* and dissolved solids that can foul or scale equipment.
* Protection against objectionable taste- and odor-causing contaminants and removal of dirt and particulates not performance tested or certified by NSF®. Everpure SEN+ and SEN Fine Filter Cartridges not performance tested or certified by NSF.
UNPACKING AND INSPECTIONInspect the carton for damage. Carefully unpack and inspect each item. Report any damage to freight carrier immediately and retain all packaging materials.
The Everpure® Conserv® HE-3 RO System includes all the necessary fittings for installation. Lengths of 3/8-inch and 1/2-inch tubing have been provided for connecting to the wastewater drain connection. Supply lines and distribution piping/tubing are not included.
The Conserv HE-3 RO System is packaged as a complete unit in two (2) cartons. You should have the following:
Parts Quantity
1. Plate Mounted Processor Assembly: RO Booster Pump Cartridge Heads Controller and Power Supply
1
2. Everpure MR-600F RO Membrane Cartridge 1
3. Everpure SEN+ Fine Filter Cartridges (Prefilter) 24. Everpure SEN Fine Filter Cartridge (Postfilter) 15. Parts Kit 1
6. Permeate Storage Tank with the Top Plate 1
7. Tank Booster Pump (Not shown) 1
8. 1/2 Gallon Accumulator (Not shown) 1
The MR-600F RO Heads and the SEN Postfilter Manifold will each have one port plugged. If the installation requires the use of a second MR-600F RO and the second SEN Postfilter, the plugs must be removed to install these cartridges.
Conserv HE-3 Processor (Tank Included) Conserv HE-3 15 Gallon Tank
1 3
4
5
2
6
CONSERV® HE-3 HIGH EFFICIENCY REVERSE OSMOSIS SYSTEM
ORIGINAL INSTRUCTIONS
2 WATER YOU CAN TRUST®
The system consists of seven (7) major components:• Everpure® SEN+ Fine Filter Cartridges*• Inlet Booster Pump• Everpure MR-600F Reverse Osmosis (RO) Membrane
Cartridge• Permeate Pump• Everpure SEN Fine Filter Cartridge*• Control System with Power Supply• 15 Gallon Storage Tank
The SEN+ Fine Filter Cartridges contain multiple medias. These medias filter out dirt and particles, reduce chlorine and provide scale control, to extend RO membrane life.*
The Inlet Booster Pump increases the inlet pressure to maintain consistent permeate production.
The MR-600F RO Membrane Cartridge contains a semi-permeable reverse osmosis membrane. It’s here that most of the dissolved impurities are separated from the water and flushed down the drain. The water that is able to pass through the membrane, which is very low in dissolved impurities, is referred to as permeate or RO water.
The Storage Tank minimizes back pressure on the permeate produced by the MR-600F RO Membrane Cartridge. This reduction of back pressure provides consistent permeate production and maximizes system efficiency for peak demand.
The SEN Fine Filter Cartridge acts as a postfilter, filtering the RO water and any tap water added via the blending system.* †
TOOLS, MATERIALS & SPECIAL EQUIPMENT REQUIREDIn most cases, common hand tools and plumbing materials suitable for use with RO water are all that is needed for system installation. The system setup and calibration requires special equipment:
• Two (2) - 32 ounce or 1,000 mL Graduated Containers• Ball Valve for 1/2-inch O.D. Tubing• Stopwatch• Pressure Gauge• Hardness Test Kit• Chlorine Test Strips• TDS Meter• Utility Knife• Eyedropper• 5.25% Household Bleach or Equivalent Disinfectant
NOTE: Please read this entire manual prior to installing and operating the system.
NOTE: Consult with your local building inspector for approval and required permits to install this system. Additional equipment, may be required. Installation must meet all local and national codes.
OPERATING SPECIFICATIONS
Influent Water Characteristics:Total Dissolved Solids: 0-1,000 ppm (0-1,000 mg/L)pH: 6-9Free Chlorine: 0-3 ppm (0-3 mg/L)Chloramines: 0-3 ppm (0-3 mg/L)Turbidity: 0-1 NTUSilica SiO2 < 20 ppmIron and Manganese: 0-1 ppm (0-1 mg/L)Bacterial Quality: PotableTotal Hardness: <1 grain
Dynamic Operating Pressure: 50–80 psi (3.5-5.5 bar, 0.35–0.55 MPa) Pressure below 65 psi (4.5 bar, 0.45 MPa) may affect blend system† performance
Maximum Static Pressure: 100 psi (6.9 bar, 0.69 MPa)Operating Temperature: 60-100°F (15.5–37.8°C)‡Daily Production Rate: 443.68 gpd (1,680.19 Lpd)Efficiency Rating: 74.23%Overall Reduction/Rejection 90.70%Recovery Rating: 74.63%Plumbing Connections:
Inlet/Outlet: 1/2-inch O.D. tube (“push-in” quick-connect)
Reject: 1/4-inch O.D. tube (“push-in” quick-connect)
Electrical - Rated Voltage and Power Cord Type
System Part No. EV9977-50: 100-120VAC/60Hz - NEMA 5-15P
Wattage:Standby: 25 WFlush: 300 WRun/Fill: 600 W
Branch Circuit Protection: 15 Amp minimum. To minimize personnel shock hazards, install on a GFI, RCD, or equivalent protected circuit.
Connectivity Connections:Ethernet Port: Type CAT5
Softener Port: Type 4 pin RJ11
* Protection against objectionable taste- and odor-causing contaminants and removal of dirt and particulates not performance tested or certified by NSF®. SEN+ and SEN Cartridges not performance tested or certified by NSF.
† Blend system not performance tested or certified by NSF.
‡ If the incoming soft water temperature is less than 60°F (15.5°C), a tempering valve should be used. Otherwise there will be a reduction in RO production.
3 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
NOTE: Incoming water supplies that do not meet the influent water characteristics requirements will require the addition of pretreatment equipment prior to the Conserv HE-3 RO System.
SELECTING A MOUNTING LOCATIONLocate the system in an area that is convenient to the inlet water supply and drain facilities, with access for routing the blended water tubing/piping to the equipment. Install in a dry location, away from all forms of corrosive and/or flammable materials. Consider ease of access for servicing when selecting a location. If the Conserv HE-3 RO System is replacing an existing Everpure® MRS-600HE-II High Efficiency RO System the mounting system may be reused. The Conserv HE-3 is designed to mount using the MRS-600 HE-II wall mount brackets. The Conserv HE-3 may also be mounted using a new design wall mount hinge system (sold separately).
If the Conserv HE-3 RO System is wall mounted on hinges be certain the unit has clearance to swing out for maintenance. Evaluate the mounting surface for its ability to properly support the weight of the processor when in operation [approximately 90 lbs (40.8 kgs)].
14.4”(36.5 cm)
18.4”(46.7 cm)
23.5”(59.7 cm)
14.4”(36.5 cm)
Figure 1 Left Swing Clearance
14.4”(36.5 cm)
18.4”(46.7 cm)
23.5”(59.7 cm)
14.4”(36.5 cm)
Figure 2 Right Swing Clearance
DIMENSIONS
14.4”(36.5 cm)
18.4”(46.7 cm)
39.6”(100.5 cm)
29.0”(73.6 cm)
Provide 3" clearance for changing cartridges
Figure 3 Conserv HE-3 RO System Dimensions
27.9”(70.8 cm)
18.62”(47.3 cm)
13.4”(34.0 cm)
Figure 4 Conserv HE-3 RO System Storage Tank Dimensions
PRE-INSTALLATION CHECKLIST1. Can the unit be mounted within a reasonable distance of
the water supply, electrical service and drain facilities?
2. Is there an unswitched receptacle available for powering the system?
3. Is there adequate clearance and support to install the unit and permit access for maintenance? The Conserv HE-3 RO System may be wall mounted on hinges. Be certain the unit has clearance to swing out for maintenance.
4. Does the inlet water supply meet the requirements listed in the table (on page 2) under Influent Water Characteristics?
5. Is there a minimum dynamic pressure of 50 psi (3.5 bar, 0.35 MPa) pressure at open flow?
4 WATER YOU CAN TRUST®
SAFETY INSTRUCTIONSNOTE: The appliance is only to be installed in locations
where its use and maintenance is restricted to trained personnel.
NOTE: Children should be supervised to ensure that they do not play with the appliance.
NOTE: Cleaning and user maintenance shall not be made by children without supervision.
NOTE: The appliance is not suitable for installation in an area where a water jet could be used.
NOTE: If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
NOTE: Substances listed as reduced are not necessarily in your water. System must be maintained according to manufacturer's instructions, including replacement of filter cartridges.
NOTE: Your water must be within required influent water characteristic limits for satisfactory operation. If not, the RO membrane cartridge’s life may be shortened and your warranty will be voided (see Operating Specifications).
NOTE: Install on cold water line only. NOTE: Do not install where system will be exposed to direct
sunlight. NOTE: Make certain that installation complies with all state
and local laws and regulations. Use only plumbers tape without adhesive backing to seal joints. Do not use pipe compound (“pipe dope”), sticks, or similar compounds with this unit; they contain petroleum derivatives which can cause crazing and cracking of the plastic in the filter housing.
WARNING: Installation shall comply with applicable local, state, and national plumbing and electrical regulations.
WARNING: This appliance must be grounded. This appliance is equipped with a cord having an appliance-grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is installed and grounded in accordance with all local codes and ordinances. If the supply cord is damaged, it must be replaced by the manu-facturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING: Improper connection of the appliance-grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative if you are in doubt whether the appliance is properly grounded. Do not modify the plug provided with the appliance; if it will not fit in the outlet, have a proper outlet installed by a qualified technician.
WARNING: The appliance is intended to be permanently connected to the water mains and not connected by a hose-set.
WARNING: Before installing the system, make certain your water supply complies with the following operating specifications. Failure to do so may reduce the effectiveness of the system and will void the warranty. Consult your local water treatment utility or a certified water testing lab to determine the quality of your water.
WARNING: Do not use with water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after the system. The Pentair Everpure® Conserv® HE-3 Reverse Osmosis System will not protect against disease-causing bacteria or remove naturally-occurring harmless bacteria.
WARNING: The Everpure® Conserv® HE-3 Reverse Osmosis System contains replaceable components that are critical to the efficiency of the system. Replacement of the reverse osmosis component should be with one of identical specifications, as defined by the manufacturer, to assure the same efficiency and contaminant reduction performance.
WARNING: The Everpure® Conserv® HE-3 Reverse Osmosis System contains filter cartridges and an RO membrane cartridge included with the system that have limited service lives which are critical for the effective reduction of total dissolved sol-ids. Product water should be tested periodically to verify that the system is working properly.
WARNING: The Everpure® Conserv® HE-3 Reverse Osmosis System shall only be used for arsenic reduc-tion on chlorinated water supplies containing detectable residual free chlorine at the system inlet. Water systems using an in-line chlorinator should provide one (1) minute of chlorine contact time before the unit.
CAUTION: The Everpure® Conserv® HE-3 Reverse Osmosis System must be protected against freezing which can cause the filter housing to crack, resulting in water leakage. Do not use electrical heating tape or propane torch on this unit.
5 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
EVERPURE® CONSERV® HE-3 RO SYSTEM QUICK START GUIDE
14.4”(36.5 cm)
18.4”(46.7 cm)
39.6”(100.5 cm)
29.0”(73.6 cm)
Provide 3" clearance for changing cartridges
27.9”(70.8 cm)
18.62”(47.3 cm)
13.4”(34.0 cm)
1 Wall Mounting 2
Tubing Locations
Approximately 90 lbs
(40.8 kgs)Operating
WeightNOTE: Shown without
cartridges installed.
Blended Water To Application
Soft Water Connection
Hard Water Connection
RO Waste To Drain
RO Water To Storage Tank
RO Water From Tank
Accumulator
Tank Relief To Drain
6 WATER YOU CAN TRUST®
3 Install Everpure® SEN+ and SEN Cartridges
Cartridge Positions
SEN
+
SEN
+
SEN
1
2Plug Open Head (Pre-installed)
Pump Motor
Switch Off
SEN
SEN+
Plugs
4 Flush Everpure SEN+ Cartridge
2
1Insert 1/2" Tubing O.D.
3
4
OPEN
OPEN
Flush for Five (5) Minutes 5
Close Soft Water Valve
7
6CLOSE
Remove Tubing
Bottom View
7 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
5 Install Everpure® MR-600F RO Cartridge 6 Flush Everpure® MR-600F RO Cartridge
1
2
SEN
SEN
+
MR-
600F Plug Open
Head (Pre-installed)
SEN
SEN+
MR-600F
Install Cartridge(s)
1
Connect 3/8" Tubing
2
Pump Switch Off
4
1
3
2
7
6
Turn Power Switch ON
8Turn System Switch OFF
Plug Power Cord Into
OutletDirect 1/4" and 3/8"
Lines to Drain
When Water Exits Both Tubes, Turn Pump Switch ON
Perform RO Rinse for 90 Minutes or
Until TDS < 50 PPM from 3/8" Line
(Production)
Open5
Install Correct Restrictor for Application
9
Bottom View
8 WATER YOU CAN TRUST®
7 Prepare Storage Tank
6
34
5
2
1
Flush Valve Closed
OpenClosed
Pump Switch Off
Power Switch Off
Cover Removed
Unplugged
Force Air Out
7Check
Precharge (40 psi)
8 Sanitize Storage Tank
1
2Add 8 Oz. (237 mL) of 5.25%
Bleach 15 gal (56.8 L) @ 200 ppm
Connect to Flush Valve
Insert 1/2" O.D. Tubing
CLOSE
3/8" O.D. Tubing
Adapter
1/2" O.D. Tubing
5
3
4
9 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
8 Sanitize Storage Tank - Continued
8
9
7
6Flush Valve
OPEN
Open
Pump Switch Off
Power Switch
Off
OPEN Valve Slowly
CLOSE Flush Valve Once Tank Is Filled
Tank Fills
Wait 15 Minutes
Plug Into Wall Outlet
Closed
Repeat Steps 6-12 Two (2) Times
When Empty, (Bladder Stops Compressing) Unplug and CLOSE Ball Valve
9Remove Ball Valve
10
12
11
13
9 Connect Tank Tubing and Fill Tank
When Tank Begins to Fill, Turn ON Pump
Power Switch ONRemove Tubing From Flush Valve
Closed
Connect Tank Accumulator to
Permeate Inlet: Insert 1/2" Tubing
Connect 3/8" Tubing to Permeate Water Out
Once Full, Remove Fitting, Install Cover and Re-insert
Fitting
8
3
1
2
Allow Tank to Fill6
5
4
Connect Tank Sensor7
10 WATER YOU CAN TRUST®
10 Flush Everpure® Postfilter Cartridge
SEN
4
5
7
1
3
Plug Storage Tank Power Cord into HE-3
System
CLOSE Hard Water Inlet Valve
2 OPEN Hard Water Inlet Valve
OPENHard Water Blend Valve
1/2" O.D. Tubing to Drain
OPEN Blended Water Outlet Valve and Flush for Five (5) Minutes.
6 CLOSE Outlet Valve
11 Adjust The Blending Valves
1
3
2 Hard Water Blend Valve CLOSE Fully Then OPEN One
(1) Rotation
NOTE: Tank Not Shown
OPEN Hard Water Inlet Valve
OPEN Blended Water Outlet
RO Permeate Blend Valve OPEN Fully
6
5
7
Test The TDS. Check Display for TDS Value
Run Water To Drain For Two (2) Minutes
8
10
CLOSE Outlet Valve
Repeat Steps 5 - 7 Until TDS Is At Target LevelTarget TDS
Hard Water Blending Valve
HI
LOW
Hard Water Blending Valve
4
Remove Drain Tube From Blended Water Outlet and Connect to Downstream Application
9
11 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
SYSTEM ASSEMBLYWARNING: Mounting surface may require reinforcement to
support the Processor Assembly safely. Hollow walls, drywall and other non-structural surfaces are not suitable for mounting unless reinforced.
WARNING: Do not use screws smaller than #12 (5.5 mm) for mounting the Processor Assembly.
The Everpure® Conserv® HE-3 Processor Cabinet is designed to wall mount using either of two (2) methods.
1. If an Everpure® MRS-600HE-II System is being replaced, the mounting brackets can be reused. The new Conserv HE-3 will not swing open when using these brackets.
2. A mounting kit may be purchased that includes two (2) hinges and a template with instructions. This mounting kit allows the Conserv HE-3 to swing open for access to the back of the cabinet.
1 Wall Mounting Using the Hinged Mounting Kit The Everpure® Conserv® HE-3 Processor Cabinet can have two (2) mounting hinges attached to one side of the cabinet. The second half of the hinge is separate and will be mounted to the wall. See Figure 5 for Dimensions. When this half of the hinge is correctly mounted to the wall, it allows the cabinet to be lifted and the hinge pieces to connect to each other.
NOTE: When the processor cabinet is hinge-mounted, it can swing away from the wall to allow servicing. Determine that the application site will allow the cabinet to swing in the desired direction.
CAUTION: Be certain that the holes are vertically level. Any deviation will cause the Conserv HE-3 RO System Cabinet to swing during servicing.
1. Place the two (2) hinges in position over the mounting holes with the pegs pointing up.
2. Secure the hinges with appropriate hardware.
1-5/8”1.63
25-45/64”25.70
27-21/64”27.32
52/64”.82
2-29/64”2.45
1-5/8”1.63
Figure 5 2 Tubing Locations1. Refer to Figure 6 Conserv HE-3 RO System Assembly
for a description of major components and connection points. These major components and connections will be referred to in the following steps.
2. Prepare the plumbing to accept the RO system.
NOTE: The blended water tubing/piping and associated fittings connecting the RO blended water outlet to the equipment being serviced should be food-grade material that meets NSF® Standard 51, 61, or similar, with a minimum pressure rating of 100 psi (6.9 bar, 0.69 MPa). The blended water may react with metal piping, creating a corrosive condition in addition to imparting an objectionable taste. Plastic pipe or reinforced beverage tubing are generally very good material choices for RO water distribution piping. The size of the blended water tubing/piping should be 1/2-inch (12.7 mm) O.D. minimum. Distances of 25 feet (7.6 m) or greater from the RO system to the equipment being serviced should be 1/2-inch (12.7 mm) O.D. minimum.
3. Locate an appropriate point in the hard water plumbing to tie in a new section of tubing/piping that can be routed to the RO system. CLOSE the nearest shut-off valve that is upstream from the tie-in point and relieve the pressure in the line. Tie in the new tubing/piping section and connect it to the Hard Water Inlet fitting. See Figure 6 Conserv HE-3 RO System Assembly.
12 WATER YOU CAN TRUST®
4. Locate an appropriate point in the soft water plumbing to tie in a new section of tubing/piping that can be routed to the RO system. CLOSE the nearest shut-off valve that is upstream from the tie-in point and relieve the pressure in the line. Tie in the new tubing/piping section and connect it to the Soft Water Inlet fitting. See Figure 6 Conserv HE-3 RO System Assembly.
5. Connect the appropriate size and type of tubing/piping and associated fittings to the Everpure® Conserv® HE-3 RO System. Route the line(s) to the equipment being serviced (i.e., steam, espresso, coffee, etc.). CLOSE the Hard and Soft Water Inlet Valves, and the Blended Water Outlet Valve on the RO system. Reapply pressure to the hard water and soft water distribution plumbing by slowly OPENING the shut-off valves that were closed in the previous steps.
6. Connect a 1/4-inch (6.3 mm) O.D. tube to the port located at the bottom of the processor labeled WASTE. Route the other end of the tubing to a drain nearby, securing it properly. Allow an air gap at the drain, following any applicable local and national codes. See Figure 6 Conserv HE-3 RO System Assembly.
Soft Water Inlet Valve
Hard Water Inlet Valve
RO Waste to Drain
Blended Water Outlet Valve
Tank Accumulator
To Storage Tank
From Storage Tank Pump
Figure 6 Conserv HE-3 RO System Assembly
ELECTRICAL AND CONNECTIVITY CONNECTIONSThe Everpure® Conserv® HE-3 RO System is pre-wired at the factory. Verify that the supply voltage matches the RO system operating voltage. Also verify that the supply is a GFI, RCD, or equivalent protected circuit rated at 15 amps minimum. Verify that the pump motor switch (Figure 8) is in the off position. Plug in the power cord.
The bottom of the Everpure Conserv HE-3 RO System has two electrical connections. The permeate Storage Tank sensor will plug into the white connector. The Storage Tank pump power cord will plug into the remaining female connection.
WARNING: For proper operation, do not plug Storage Tank pump into a wall receptacle.
IMPORTANT: Electrical brown-outs below 100 volts will require the Everpure Conserve HE-3 RO System must be turned OFF and back ON (power cycled).
To monitor the Everpure Conserv HE-3 RO System remotely, an Ethernet cable (type CAT5, not provided with the system) must be connected between the RO system and the Internet router.
To have connectivity between the Everpure Conserv HE-3 RO System and the CES-9100TS E-30C Softener, a phone cord (type 4 pin RJ11, not provided with the system) must be connected between the RO system and the softener.
Ethernet Port
Softener Port
Figure 7
PREFILTER AND RO CARTRIDGE INSTALLATION AND SYSTEM START-UPSwitch and Valve Starting Positions:
• System Power - Off• Pump (P1) Power - Off• Soft Water Inlet Valve - Closed• Hard Water Inlet Valve - Closed• Blended Water Outlet Valve - Closed
13 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
3 Install Everpure SEN+ and SEN Fine Filter Cartridges1. Remove the outer shrink wrap and protective caps from
all of the cartridges.
2. Align the lugs on the Everpure SEN+ Fine Filter Cartridges with the slots in the cartridge ports on the twin prefilter header. Holding the head/bracket and cartridge firmly, press the cartridge upward into the head fully, and then turn the cartridge to the right until it stops (Figure 8). Install the second SEN+ Fine Filter Cartridge and the SEN Postfilter Cartridge in the same manner.
NOTE: If a second SEN Cartridge is installed, the pre-installed plug must be removed.
SEN
+
SEN
+
SEN
1
2
Plug Open Head
(Pre-installed)
SEN Postfilter (installed after
tank flush)
Pump On/Off
Figure 8
4 Flush Everpure SEN+ Fine Filter Cartridge
Flushing Valve
Figure 9
1. Attach 1/2-inch O.D. tubing for a drain line to the Flushing Valve. The tubing should run to a drain.
2. OPEN the Flushing Valve.
3. The store soft water supply valve should be open. OPEN the Soft Water Inlet Valve on the Everpure® Conserv® HE-3 RO System.
4. Flush the prefilters for a minimum of five (5) minutes at 0.5 gpm (1.8 Lpm).
5. CLOSE the Soft Water Inlet Valve.
6. CLOSE the Flushing Valve.
7. Remove the drain tube.
5 Install Everpure MR-600F RO Membrane Cartridge1. Align the lugs on the Everpure MR-600F RO Membrane
Cartridge with the slots in the head. Holding the head and cartridge firmly, press the cartridge upward into the head fully, and then turn the cartridge to the right until it stops.
NOTE: If a second MR-600F RO Membrane Cartridge is installed, the pre-installed plug must be removed.
2. Attach a length of 3/8-inch O.D. tubing to the RO tube that delivers permeate water to the Storage Tank (Figure 10). The open end should run to a drain.
CAUTION: To prevent damage to the pump (P1), the pump head should be filled with water (primed) before the unit is turned on.
Soft Water Inlet Valve
Attach 3/8" O.D. Tubing to DrainRO Waste
to Drain
Pump (P1) On/ Off Switch
System On/Off Switch
Permeate Port
NOTE: Cartridges not shown.
Figure 10
14 WATER YOU CAN TRUST®
3. Ensure that the Pump Switch (P1) is in the Off position. Then turn the System On/Off Switch to ON. The solenoid valve will open to allow water flow at store pressure into the pump head.
6 Flush Everpure MR-600F RO Membrane Cartridge1. Pump switch should be off.
2. Plug the HE-3 Cabinet power cord into an outlet.
3. Use the User Interface screen and press System Settings. Enter the password to access the Air Purge/Flush menu.
NOTE: Passwords are available through Pentair Everpure Technical Support at 630.307.3000.
4. When the Air Purge/Flush menu is displayed, press Perform RO Rinse.
NOTE: Water will exit both the RO waste and permeate tubes Figure 10.
5. When water is exiting both tubes, turn ON the Pump (P1) Switch.
6. The MR-600F RO Cartridges should be flushed for 90 minutes or until the TDS is below 50 ppm.
WARNING: DO NOT USE THIS RO WATER! It will likely contain a preservative solution that should not be consumed.
NOTE: The SEN Fine Filter Cartridges will not be flushed until the Storage Tank has been flushed and sanitized.
7. Turn OFF the system.
8. Remove the grey restrictor. Replace it with the correct restrictor for the application. Refer to the Flow Restrictor Table in the System Recovery Rate section.
7 Prepare Storage Tank Switch and Valve Starting Positions:
• Power - Off• Pump Power Switch - Off• Soft Water Inlet Valve - Open• Hard Water Inlet Valve - Closed• Outlet Valve - Closed• Power to Tank - Off (Unplugged)• Prefilter Flush Valve - Closed
1. Place the Storage Tank in position. Allow for:
• Proximity to the Conserv HE-3 RO System.• Minimal tubing lengths.
CAUTION: Before operation, the Storage Tank must be sanitized and filled.
NOTE: The Storage Tank is shipped with the top cover removed. To reduce the amount of air that must be purged, push down on the bag, forcing air out of the air pressure relief valve. When water is added, the bag will expand and the trapped air will be purged out.
2. Locate the small accumulator tank (see Figure 11).
8 Sanitize Storage Tank1. Attach a length of 3/8-inch O.D. tubing to the Storage
Tank Inlet Tee fitting. The tubing should be long enough to reach the Prefilter Flush Port.
2. Use an air gauge to check the tank's precharge. It should be 40 psi (2.75 bar, 0.275 MPa).
3. Use an eye dropper or funnel to place 8 oz. (237 mL) of 5.25% bleach (200 ppm) into the tubing.
4. Connect the tubing to the Prefilter Flush Port (Figure 11). Use the 3/8" to 1/2" adapter and a short piece of 1/2" O.D. tubing.
Prefilter Flush Port
Tank Inlet
Tank Outlet
Air Pressure Relief Valve
To DrainBall Valve
3/8" O.D. to 1/2" O.D. Tubing
Adapter
1/2" O.D. Tubing
1/2" O.D. Tubing
Accumulator Tank
Figure 11
5. Attach a length of 1/2-inch O.D. tubing to the Storage Tank Outlet fitting. The other end will go to a drain.
6. Install a ball valve on the Storage Tank Outlet tubing and set the valve to CLOSED.
7. Set the Prefilter Flushing Port Valve to partially open. This will allow water and bleach to enter the Storage Tank.
15 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
Soft Water Inlet Valve
NOTE: Cartridges not shown.
Figure 12
NOTE: Any air in the Storage Tank will need to be released. The Air Pressure Relief Valve will open to remove trapped air.
8. When the Storage Tank is full, CLOSE the Prefilter Flushing Valve.
9. Allow the Storage Tank to sit for 15 minutes.
10. Drain the Storage Tank by OPENING the Drain Line Ball Valve and applying power to the Storage Tank. The Permeate Pump (P2) will turn on.
WARNING: When applying external power to the Storage Tank Pump, do not run the pump after the bladder is empty. When the bladder stops collapsing, it is empty. Failure to follow this instruction is likely to damage the pump.
11. Remove power to the Storage Tank and CLOSE the Drain Line Ball Valve.
12. Repeat Steps 6 through 10, two (2) times.
13. Check that power is off to the Everpure® Conserv® HE-3 RO System.
14. Remove the tubing from the Prefilter Flush Port and switch it to service (closed).
9 Connect Tank Tubing1. Remove the 3/8" to 1/2" Tubing Adapter and the 1/2" O.D.
tubing. Connect 3/8" tubing from the Storage Tank to the connection (RO water out) on the Conserv HE-3 RO System (Figure 13).
1/2" O.D. Tubing
From Tank to Permeate
Inlet
3/8" O.D. Tubing To Tank Inlet
NOTE: Cartridges not shown.
Sensor Adapter Cable
Plug Into Storage Tank
Figure 13
2. Remove the ball valve from the Storage Tank Drain Line.
CAUTION: A water pressure reducing valve has been included in the parts kit. This valve must be assembled into the 1/2" O.D. tubing from the Storage Tank to the permeate inlet. The directional arrow on the body must point towards the permeate inlet. Failure to install the water pressure reducing valve properly will likely cause damage to the Conserv HE-3 RO System.
3. Connect the tubing with the water pressure reducing valve from the Storage Tank Outlet (Storage Tank Drain Line) to the permeate inlet connection on the Conserv HE-3 RO System (Figure 13). The water pressure reducing valve has a directional arrow molded into the body. This arrow must point towards the Conserv HE-3 Cabinet.
4. Use the Sensor Adapter Cable to connect the electrical port on the bottom of the Storage Tank to the white connector from the Conserv HE-3 Cabinet.
5. Install the Storage Tank cover by removing the fitting at the top. Position the cover and replace the fitting.
16 WATER YOU CAN TRUST®
NOTE: The Storage Tank will have a minor amount of pressure. Some water will exit the hole when the fitting is removed.
6. CLOSE the Soft Water Inlet Valve.
10 Flush Everpure Postfilter CartridgeSwitch and Valve Starting Positions:
• System Power - Off• Storage Tank Power - Off• Soft Water Inlet Valve - Closed• Hard Water Inlet Valve - Closed• Hard Water Blend Valve - Open• Blended Water Outlet Valve - Closed
1. Connect 1/2-inch O.D. tubing to the Blended Water Outlet Valve. Route this tubing to a drain.
2. OPEN the Hard Water Inlet Valve (Figure 14).
Hard Water Inlet Valve Blended Water
Outlet Valve
Hard Water Blend Valve
NOTE: Cartridges not shown.
Figure 14
3. OPEN the Blended Water Outlet Valve (Figure 14). Flush the SEN Postfilter Cartridge(s) to drain for five (5) minutes.
4. CLOSE the Hard Water Inlet Valve.
5. Remove the tubing from the Blended Water Outlet Valve.
6. Plug the Storage Tank Permeate Pump into the connection at the bottom of the HE-3 System frame.
11 Adjust The Blending Valves There are two (2) valves that are adjustable to provide a blend of RO permeate and incoming water to suit the application.
RO Blend Valve
Blended Water Outlet
Valve
Hard Water Blend Valve
Hard Water Inlet Valve
Soft Water Inlet Valve
Figure 15
To adjust the blend:
1. Determine the desired TDS for the application.
2. Locate the two (2) Blend Valves above the filter manifolds.
3. OPEN the RO Blend Valve fully, see Figure 15. This allows maximum flow of the RO permeate water.
4. CLOSE the Hard Water Blend Valve, see Figure 15.
NOTE: This configuration provides only RO permeate water with no hard water blend.
5. OPEN the Hard Water Blend Valve one (1) full rotation.
6. OPEN the Soft Water and the Hard Water Inlet Valves.
7. With the system turned ON, run water out of the Blended Water Outlet Valve for two (2) minutes.
8. Test the TDS or check the post-filter status screen.
9. If the TDS is too high, then CLOSE the Hard Water Blend Valve in small increments and retest. If the TDS is too low, then OPEN the Hard Water Blend Valve in small increments and retest. Allow water to flow for two (2) minutes between tests.
10. When the blend is correct, mount and secure the HE-3 Processor Cover. Place the system into full operation.
17 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
USER INTERFACE (UI)The operator of the Conserv HE-3 RO System can use the touch screen display to access real-time performance data. Operating parameters and calibration settings may be reviewed and changed.
Navigation
ButtonPress once to access the item shown.
Item Name Individual item usually followed by a value.
Value The real time value of the individual item. Also used for calibration values.
Setting The up/down arrows are used to change the setting value.Cancel any changes on the current screen.Confirm and save any changes on the current screen.Jump back one screen.
Jump to the top level home page.
Previous screen, cycles between screens within each section shown.Next screen, cycles between screens within each section shown.
Sleep ModeThe user interface will enter sleep mode after five (5) minutes of inactivity. The screen will become blank, but all the functions continue to operate. To wake the screen from sleep mode, press anywhere on the screen for two (2) seconds.
12 Place Into Operation When the cartridges are flushed and the blend is set, the Everpure® Conserv® HE-3 RO System is ready to begin operation.
All of the tubing should be properly connected (Figure 6).• OPEN the Hard Water Inlet Valve.• OPEN the Soft Water Inlet Valve.• CLOSE the Blended Water Outlet Valve.• Turn ON the Pump Switch.• Turn ON the System Switch.
Perform the following procedure to start up the HE-3 RO System using basic settings.
The User Interface will display the top level Home Screen.
Conserv® HE-3
SystemStatus
CalibrateSensors
SystemSettings
ContactInfo
Date and Time
Reset Filter Life
Clear Lockout
Figure 16
1. Press System Settings and enter the password to access the Air Purge/Flush menu.
NOTE: Passwords are available through Pentair Everpure Technical Support at 630.307.3000.
2. Press the Perform Tank Fill button to set the water level in the tank.
Air Purge/Flush Menu
Perform Air Purge
Perform RO Flush
Perform Tank Fill
Perform RO Rinse
Figure 17
Tank Fill Cycle
Tank Fill in progress.
0Tank Fill %
Figure 18
When the Tank Fill Cycle is complete, the Tank Fill % window indicates the percent full.
If the Tank Fill % is over 80%, the Conserv HE-3 RO System is ready for operation.
3. OPEN the Blended Water Outlet Valve.
If the Tank Fill % is under 80%, an Air Purge/Flush Cycle must be performed.
4. Return to the Air Purge/Flush menu, press Perform Air Purge and record the Set value. Select Start.
18 WATER YOU CAN TRUST®
NOTE: The Air Purge is used to push out any air that may have entered the Storage Tank. Pressure will build in the Storage Tank until air is forced out of the Pressure Relief Valve.
SetSTART
Air Purge/Flush Cycle
Set value then press START.
Cnt1400 420
Figure 19
5. Begin the Air Purge by pressing Start. Observe the tank relief valve. When the Air Purge Cycle is over, if no water has exited the valve then increase the Set value by 25. Press Start and run another Air Purge. Continue to increase the Set value and perform an Air Purge until water exits the Tank Relief Valve.
6. When the Air Purge is complete, press the Arrow button at the bottom of the screen. The System Settings menu should be showing.
System Settings Menu
Date and Time
StoreSettings
Air Purge/Flush
Units of Measure
Figure 20
7. Next, press the Store Settings button to display the Store Settings menu. Next select Customer Number. The display will show a screen to enter the customer and location information for the installation.
Contact Pentair® Everpure® Technical Support to obtain the customer ID and location numbers.
Set Customer Number
Customer #01
Location #01234
1 2 3 4 5 6
7 8 9 0 X
Figure 21
Remote monitoring must be enabled to allow a Pentair CES-9100TS E-30C Water Softener to communicate with the Everpure Conserv HE-3 RO System. To have connectivity beween the Everpure® Conserv® HE-3 RO System and the CES-9100TS E-30C Softener, a phone cord (Type 4 pin RJ11, not provided with the system) must be connected between the RO system and the softener.
Connection Port
Figure 22
8. On the Store Settings menu, press the Softener In Use button to enter a Yes or No setting, Figure 23.
NOTE: Only the Pentair CES-9100TS E-30C Water Softener may be used with the Conserv HE-3 Controller.
Set Softener In Use
CES-9100TS E-30CWater Softener In Use
no
Figure 23
9. Return to the top level home screen.
SYSTEM RECOVERY RATEThe amount of incoming water that becomes RO water should be 80%. This recovery percentage may be changed by replacing the flow restrictor in the black waste tubes located in the RO waste tubing connectors. There is one Flow Restrictor for each RO head. They are accessed from the top of the manifold tray.
CAUTION: The system should be run on 80% recovery when tempered, softened, and under 1,000 ppm TDS water is available. Any deviation from an 80% recovery rate will affect the system's production rate and/or life of the RO membrane. Please consult Pentair Everpure for a recommendation of any installation that does not meet this water specification.
19 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
Flow Restrictors
Tubes
NOTE: Some tubing has been removed from this illustration for clarity
Figure 24
Select the reject flow control assembly based on the flow restrictor table below. Insert the reject flow control assembly into the 1/4" (6.4 mm) O.D. tube, Figure 24. Insert the 1/4" (6.4mm) O.D. tube with reject flow control assembly into the elbow fitting on RO head.
Flow Restrictor Table
% Recovery Part Number Restrictor Description
90 EV3128-30 Red80 EV3128-31 Brown70 EV3128-32 Green60 EV3128-27 Blue50 EV3128-28 White Fully Trimmed40 EV3128-29 Grey
NOTE: Everpure® Conserv® HE-3 RO System is supplied with 40% and 80% recovery restrictors.
For the appropriate selection of flow restrictors for your application, please consult with Pentair Technical Service at 630.307.3000.
20 WATER YOU CAN TRUST®
EVERPURE® CONSERV® COMPLETE HE-3 USER INTERFACE The User Interface allows the integration with several features on the Conserv HE-3 RO System. A complete explanation of the interface is provided in this manual.
The top level User Interface (UI) Home screen is accessed by pressing the blank screen for two (2) seconds. This action will bring the UI out of sleep mode. All other screens will display a "Home" icon at the lower right corner. Pressing the Home button will take the UI to the Home screen.
This screen normally will have five (5) buttons. Each button will access user information.
SystemStatus
Displays a set of six (6) buttons that, when pressed, will show the status of that item.
Settings accessed via this button are:• Inlet• Prefilter• RO Membrane • RO Water Tank• Postfilter• History
Reset Filter Life
After replacing filters, the percentages for filter life should be reset to 100%.
SystemSettings
This is a password-protected button. These settings are critical to the operation of the system. Contact Pentair Everpure Technical Support, at 630.307.3000 for more information about this setting.
Settings accessed by this button are:• Date/Time• Store Settings• Air Purge/Flush• Units of Measure• Reset Filter Life
CalibrateSensors
This is a password-protected button. These settings are critical to the operation of the system. Contact Pentair Everpure Technical Support, at 630.307.3000 for more information about this setting.
Settings accessed by this button are:• Pressure Sensors• Pressure 4 Threshold• Tank Level• TDS Sensors• Flow Meters
ContactInfo
Pentair Everpure contact information.
Conserv® HE-3
SystemStatus
CalibrateSensors
SystemSettings
ContactInfo
Date and Time
Reset Filter Life
Clear Lockout
21 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
Clear Lockout
This button will only display under the following conditions:
• The Main Pump (P1) is running.• The system conditions are such that the
Storage Tank should be receiving RO water.
• The Storage Tank is not filling.• The Storage Tank Pump (P2) is not
running.• 20 minutes have elapsed.
If the above conditions are true, then it is likely there is a water leak in the system. In this condition, the Conserv HE-3 RO System will stop all incoming water flow. The Home Screen buttons will turn to red and the Clear Lockout button will be displayed. When the leak is repaired, and no other faults are found, press the Clear Lockout button to resume operation.
CAUTION: Any repair on the Everpure® Conserv® HE-3 RO System may compromise water flow and/or water quality. After repairing the water system, a thorough review must be made of the areas affected. Change filters, flush or sanitize as needed to restore water quality.
Date and Time
Displays the date as mm/dd/yy and the time as HH:MM am/pm.
System Status Menu InterfaceThe System Status Menu Displays:
InletPress to display inlet water conditions.
PreFilter
Press to display prefilter life.
RO Membrane
Press to display RO process information.
RO Water Tank
Press to display tank status.
PostFilter
Press to display postfilter life.
History Used for filter life, system statistics, and performance information.
The Inlet Status screen is displayed when the Inlet button is pressed. All of the values represent real-time information.
• Inlet flow rate in gallons per minute (gal/min) or Liters per minute (L/min).
• Inlet pressure as psi (MPa).• Inlet TDS as ppm.• Inlet water temperature in °F (°C).
Conserv® HE-3
SystemStatus
CalibrateSensors
SystemSettings
ContactInfo
Date and Time
Reset Filter Life
Clear Lockout
System Status Menu
Inlet PreFilter
PostFilter
RO Membrane
RO Water Tank
History
0.00 gpmInlet Flow RateInlet Pressure
Inlet TDSInlet Water Temp
0 psi0 ppm32 °F
Inlet Status
22 WATER YOU CAN TRUST®
100 %Pre-Filter LifePressure Drop 0 psi
Prefilter Status
0 ppmRO Water TDSRO Pump Pressure
Waste TDSRecovery
0 psi0 ppm80 %
RO Membrane Status
Rejection 90 %
IdleTank StatusTank Level 0 %
Water Tank Status
0 psiOutlet PressurePressure Drop
Blend Flow RateBlend TDS
0 psi1.57 gpm200 ppm
Post-Filter Status
Post Filter Life 100 %
The Prefilter Status screen is displayed when the Prefilter button is pressed.
• Pre-Filter Life is shown as a percentage remaining based on the volume of water used.
• Pressure Drop represents the pressure difference as measured before and after the prefilters.
The RO Membrane Status screen is displayed when the RO Membrane button is pressed. All of the values represent real-time information.
• RO Water TDS level measured as ppm.• RO Pump Pressure (P1) of the RO inlet water
measured as psi (MPa).• Waste TDS level of the water rejected by the RO
cartridge measured as ppm.• Recovery is the real-time percentage, of the feed water
that becomes blended water.• Rejection is the real-time percentage, of the minerals
in the water that are sent to waste or drain.
The Water Tank Status screen is displayed when the RO Water Tank button is pressed.
• Tank Status is an indicator of the water level (filling/emptying/idle).
• Tank Level is the real-time percentage of the volume of water in the Storage Tank.
The Post-Filter Status screen is displayed when the Postfilter button is pressed. All of the values represent real-time information.
• Outlet Pressure of the filtered water in psi (MPa).• Pressure Drop represents the real-time pressure
difference as measured before and after the postfilter(s).
• Blend Flow Rate is a measure of the water flow out of the system to the application. It is measured in gallons per minute (gal/min) or Liters per minute (L/min).
• Blend TDS is a real-time measurement in ppm of the water going to the application.
• Post Filter Life is shown as a percentage remaining based on the volume of water used.
23 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
100 %Pre-Filter LifePost-Filter Life
RO Membrane LifeMax Recovery
100 %100 %80 %
History Page 1
Min Recovery 90 %
1234567RO Pump CyclesRO Pump Hours
Tank Pump CyclesTank Pump Hours
123451234567
12345
History Page 2
# of Air Purge 0# of Flushes 0
1234.5 galsInlet Flow TotalMax Inlet TDSMin Inlet TDS
Blend Flow Total
1234.5 gals809 ppm
1234.5 gals
History Page 3
Max Blend TDS 0 ppmMin Blend TDS 0 ppm
Press the History button to display the first page of the system's history. Use the Left/Right arrow buttons to move to pages 2 and 3.
NOTE: Most of these values cannot be reset in the History menus, with the exception of filter life percentages. All of the values are real-time unless listed as Max or Min.
The maximum and minimum inlet TDS values reflect the highest and lowest TDS readings over the life of the system.
NOTE: Recovery and Rejection percentages will not total 100%. Recovery is the percentage of water that becomes RO permeate and is sent to the Storage Tank. Rejection is the percentage of minerals in the water that do not pass through the RO filter membrane.
24 WATER YOU CAN TRUST®
Reset Filter Life
Carbon Pre-Filter
Carbon Post-Filter
RO Membrane
RESET# of RO
1 2
System Settings Menu
Date and Time
StoreSettings
Air Purge/Flush
Units of Measure
System Settings Menu
Set Date and Time
Set DST and UTC
Date And Time
fri
01 jan 16
12 00 am
Reset Filter Life Menu InterfaceOn the Top Level Menu, press the Reset Filter Life button to display buttons that are used to reset the life percentages of the individual filters. These buttons are used when the cartridges are changed. Press to reset. The word "RESET" will display when the filter life has been reset.
Carbon Prefilter life is displayed on the Prefilter Status screen and the History Page 1 screen.
RO Membrane Life is displayed on the History Page 1 screen.
Carbon Post-Filter Life is displayed on the History Page 1 screen.
The # of RO is used to select the number of RO membrane cartridges that are installed on the system.
System Settings Menu InterfaceOn the top level menu, accessing the System Settings Menu requires a password. Contact Pentair Everpure Technical Support at 630.307.3000 to acquire the password.
Enter the password at the Home screen. The System Settings Menu displays:
Date and Time
Used to enter/change the date and time.
Units of Measure
Press to make changes to the units and values shown in the User Interface.
StoreSettings
Press to make changes to settings for the application.
Air Purge/Flush
Press to perform a manual tank air purge, a flush, RO rinse, or a tank fill.
Production Test
Press to view troubleshooting and sensor information.
Date and Time
Press the Set Date and Time Button to display a screen for setting the Day/Month/Year and Time.
DST and UTC
Press the Set DST and UTC button to display a screen for setting Daylight Savings Time and the time zone.
DST: Daylight Savings Time UTC: Coordinated Universal Time
Adjust the settings and press the Check Mark to confirm and change.
25 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
Choose Yes or No for Daylight Savings Time. Set the Coordinated Universal Time (UTC) to match the location of the installation:
- 5 for East Coast
- 6 for Central Time
- 7 for Mountain Time
- 8 for West Coast
Press the Check Mark to confirm and change.
Press the Units of Measure button to show the measurement units displayed in the user interface. Press the unit shown to change:
• PSI to MPa• Gallons to Liters• Fahrenheit to Celcius
Press the Store Settings Menu button to display:
Air Purge Frequency
Used to view and change the number of hours between air purgings.
Customer Number
Customer number and customer location are entered. This information is supplied by Pentair Everpure.
Softener In Use
The Pentair CES-9100TS E-30C Water Softener has the ability to communicate with the Pentair Everpure Conserv HE-3 RO System. If this feature is used, select this screen and set to YES.
On the Store Settings Menu, press the Air Purge Frequency button to display the number of hours to the next automatic air purge. The hours between air purgings may be changed.
Interval System Parameters6 Hrs 1 RO membrane and cold water (below 70°F
[21°C])5 Hrs 1 RO membrane and warm water (above 70°F
[21°C])4 Hrs 2 RO membranes and cold water (below 70°F
[21°C])3 Hrs 2 RO membranes and warm water (above 70°F
[21°C])
DST and UTC Time Zone
DST Active yes-6UTC Time Zone
Units of Measure
Pressure PSIGALSFlow Rates/Totals
Temperature ºF
Store Settings Menu
Air Purge Frequency
Customer Number
Softener in Use
Air Purge Frequency
# Of Hours To Next Air Purge6
26 WATER YOU CAN TRUST®
Set Customer Number
Customer #01
Location #01234
1 2 3 4 5 6
7 8 9 0 X
Set Softener In Use
CES-9100TS E-30CWater Softener In Use
no
Air Purge/Flush Menu
Perform Air Purge
Perform RO Flush
Perform Tank Fill
Perform RO Rinse
Air Purge/Flush Cycle
Flush Cycle in progress.
To enable remote monitoring on this unit, a customer ID and location number must be entered.
On the Store Settings menu, press the Customer Number button to enter the customer's ID number and location number. These are supplied by Pentair Everpure.
NOTE: The fields must be green to enter numbers.Contact Pentair® Everpure® Technical Support to obtain the customer ID and location number.
When the HE-3 is connected with the Pentair CES-9100TS E-30C, the HE-3 will sense low salt and no salt conditions from the softener. On the Store Settings Menu, press the Softener In Use button to enter a Yes or No setting.
To have connectivity beween the Everpure® Conserv® HE-3 RO System and the CES-9100TS E-30C Softener, a phone cord (Type 4 pin RJ11, not provided with the system) must be connected between the RO system and the softener.
NOTE: Only the Pentair CES-9100TS E-30C Water Softener may be used with the Pentair Everpure Conserv HE-3 Controller.
On the System Settings Menu, pressing the Air Purge/Flush Menu button will provide four (4) selections: Perform Air Purge, Perform Tank Fill, Perform RO Flush and Perform RO Rinse.
Selecting Perform Air Purge will fill the Storage Tank and force air out. This cycle is based on tank level settings entered in the System Settings Menu.
Selecting the Perform RO Flush will begin a flush cycle. The flush will push RO water from the storage tank into the RO cartridge(s). This forces the inlet water with high mineral content out and surrounds the RO membrane(s) with RO water on both sides.
The Flush Cycle is used to preserve the RO membrane during periods of inactivity, such as overnight. The system will resume normal operation when there is a demand for RO water.
The system will automatically perform a Flush Cycle if there has not been any flow for two (2) hours. If inactivity continues, another Flush Cycle will be performed after 12 hours.
NOTE: The Everpure Conserv HE-3 RO System will perform an automatic flush after 90 minutes of operation or every 12 hours if it is idle.
27 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
Press the Perform Tank Fill Button to display the Tank Fill Progress screen. This will show the tank percentage full and the current action.
Select Perform RO Rinse will pass water over a new RO cartridge to initialize it.
At the start of an Air Purge, the Storage Tank must be above 80% full (as shown on the Tank Fill Cycle screen) for the Air Purge to finish properly. If the Storage Tank is below 80% full, navigate to the System Settings Menu and select Air Purge/Flush. When the four (4) choices appear, press the Perform Tank Fill button. A forced manual Storage Tank fill will occur. When the Storage Tank fill is completed, return to the Air Purge/Flush Cycle menu and record the Set value. Move back to the Air Purge/Flush Menu and select Perform Air Purge.
NOTE: The Air Purge is used to push out any air that may have entered the storage tank. Pressure will build in the tank until air is forced out of the pressure relief valve.
Observe the Storage Tank Pressure Relief Valve. When the Air Purge cycle is over, if no water has exited the valve then increase the Set value by 25. Press Start and run another Air Purge. Continue to increase the Set value followed by an Air Purge until water exits the Storage Tank Pressure Relief Valve.
During an Automatic Air Purge, the status will be filling. The Storage Tank level will be increasing.
IMPORTANT: The Storage Tank Air Purge cycle is based on a setting that was established from the Air Purge settings screen. If a manual Air Purge was performed or excess water is leaking from the Storage Tank Pressure Relief Valve, the Storage Tank water level setting should be reset.
Tank Fill Cycle
Tank Fill in progress.
0Tank Fill %
Air Purge/Flush Cycle
RO Rinse in progress.
System Settings Menu
Date and Time
StoreSettings
Air Purge/Flush
Units of Measure
Air Purge/Flush Menu
Perform Air Purge
Perform RO Flush
Perform Tank Fill
Perform RO Rinse
SetSTART
Air Purge/Flush Cycle
Set value then press START.
Cnt1400 420
28 WATER YOU CAN TRUST®
Calibrate Sensors Menu InterfaceOn the top level menu, accessing the Calibrate Sensors Menu requires a password. Contact Pentair Everpure to acquire the password.
CAUTION: Incorrect sensor settings will result in improper operation of the Everpure® Conserv® HE-3 RO System. Sensor calibration has been set at the factory and should only be changed if a new sensor has been installed. Use the calibration data listed on the new sensor.
At the Home Screen, enter the password. The Calibrate Sensors Menu displays:
Pressure Sensors
Used to enter pressure sensor calibration settings.
Pump 2 Threshold
Used to enter permeate pump (P2) threshold calibration settings.
TankLevel
Used to enter Storage Tank level sensor calibration settings. Also used to enter offset percentages for tank fill and tank empty.
TDS Sensors
Used to enter calibration settings for the four (4) TDS sensors.
Flow Meters
Used to enter sensor calibration settings for flow meters F1 and F2.
Production Test
Select Production Test from the System Settings Menu to access troubleshooting and sensor information. The tank sensor has a preset value and will not be shown.
CAUTION: The Storage Tank will be in fill mode as long as the Production Test screen is displayed. When this screen has been exited, the Storage Tank will stop filling.
Press the Pressure Sensors button to display the Pressure Calibration screen. Use the "c" value that is provided with the new sensor.
To change the settings:
1. Press the window for the "c" value of the sensor.
2. Use the Up and Down arrows to enter the value listed on sensor packaging.
3. When finished, press the Check Mark to save the changes.
Press the Pump 2 Threshold button to display the Threshold Calibration screen. This screen sets the pressure value for the permeate pump (P2).
To properly set this value:
After blend is set, unplug tank pump. Allow system to normalize, then record Run value. Enter Run value +5 into Set box, confirm input, then re-plug in the pump.
Calibrate Sensors Menu
Pressure Sensors
TankLevel
Flow Meters
TDSSensors
Pump 2 Threshold
ProductionTest
Pressure Calibration
m cSensor#Sensor 1 -
----
Sensor 2Sensor 3Sensor 4Sensor 5
Pump 2 Threshold Calibration
RunLow 030
Set
After blend is set, unplug tank pump. Allow system to normalize, then record Run value. Enter Run value +5 into Set box, confirm input, then re-plug in pump.
29 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
Press the Tank Level button to display the Tank Level Calibration screen. Use the "m" and "b" values that are shown on the Storage Tank sensor packaging.
CAUTION: If the High setting is above the value displayed in the Run window, (refer to Pump 2 Threshold Calibration screen) the (P1) pump will not turn off. If the Low setting is below the value displayed in the Run window, the (P1) pump will not turn on.
To calibrate the tank level sensor:
1. Press the window for the "m" value.
2. Use the Up and Down arrows to enter the value listed on the sensor.
3. Press the window for the "b" value.
4. Use the Up and Down arrows to enter the value listed on the sensor.
5. When finished, press the Check Mark to save the changes.
NOTE: The Counts window is used by Pentair Everpure Customer Service as a diagnostic tool.
Press the TDS Sensors button to display the TDS Calibration screen. Use the calibration setting (C) that is shown on the sensor packaging.
To change the TDS calibration setting:
1. Press the window for the "C" value of the sensor.
2. Use the Up and Down arrows to enter the value listed.
3. When finished, press the Check Mark to save the changes.
Tank Level Calibration
m bTank Level67 28
18Counts
TDS Calibration
TDS 1 3.303.30TDS 2
TDS 3 3.303.30TDS 4
C
30 WATER YOU CAN TRUST®
Flow Meter Calibration
m bFMeter#F10.00 0.00F2 0.000.00
Conserv® HE-3
Pentair1040 Muirfield Dr
Hanover Park, IL 60133(630) 307-3000
Press the Flow Meters button to display the Flow Meter Calibration screen. Use the "m" and "b" settings that are shown on the flow meter packaging.
NOTE: System comes calibrated from the factory. Flow meter calibration is only required when replacing a flow meter.
To change the settings:
1. Press the window for the "m" value of the flow meter.
2. Use the Up and Down arrows to enter the value listed.
3. Press the window for the "b" value of the flow meter.
4. Use the Up and Down arrows to enter the value listed.
5. When finished, press the Check Mark to save the changes.
Contact Info Press the Contact Info button to display Pentair's address and phone number.
31 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
MAINTENANCE SECTIONPerformance Log
Test Date Run Hours
Outlet Flow RO Water
Only ounce/min
or mL/min
Reject Flow ounce/min
or mL/min
Inlet Pressure/
Temp. psi/°F
or MPa/°C
Inlet TDS mg/L
Hard Water TDS mg/L
RO Outlet TDS mg/L
Percent TDS Reduction
NOTES:
32 WATER YOU CAN TRUST®
TROUBLESHOOTING GUIDE
Problem Possible Cause Remedy
1. Insufficient blended water volume during normal operating periods.
Cartridge(s) plugged. Replace cartridge(s).
MR-600F RO Membrane Cartridge plugged. Replace MR-600F RO Membrane Cartridge.
Insufficient system inlet pressure. Check/repair booster pump and inlet line.
2. Insufficient blended water volume during peak periods.
Refer to Problem 1. Refer to Problem 1.
System output too low for application. Verify system output. If output is within specification, increase output if applicable.
3. Low quality RO water. Refer to Problem 1. Refer to Problem 1.
MR-600F RO Membrane Cartridge failure. Replace MR-600F RO Membrane Cartridge.
4. Low water pressure at water-using equipment.
Restrictive tubing/piping run to equipment. Increase tubing/piping diameter. Refer to "System Installation" section for recommendations.
5. Objectionable blended water odor.
Prefiltration cartridge(s) exhausted. Replace prefiltration cartridge(s).
6. Waste water flow too low or decreases over time.
Drain line restricted. Check/correct any restrictions in drain line tubing. Make sure to allow for an air gap at the drain. Disconnect reject line at quick-connect fitting and inspect for obstruction or damage. Remove obstruction. Replace if required.
Insufficient system inlet pressure. Check/repair booster pump and inlet line.
7. Pressure limit warning error.
Electrical connector at the pressure transducer not fully engaged.
Check electrical connector engagement with pressure transducer.
RO permeate pressure exceeds 114 psi (0.79 MPa). Check for restriction/blockage in permeate line causing abnormally high pressure. Relieve pressure in permeate line and correct restriction/blockage condition.
RO cartridge bypassing. Measure RO permeate flow and TDS, then compare to previously recorded values or system specifications. High permeate flow and/or poor TDS reduction indicates excessive passage of water around or within the RO cartridge. Remove the RO cartridge and check the integrity of all three (3) o-ring seals and correct as needed. If seals appear OK, replace the RO cartridge. After making the repairs, press any key on controller to clear the fault, then recheck RO permeate flows and TDS, then compare to previously recorded value or system specifications. If the fault reappears after returning to normal operation, replace controller and/or pressure transducer or contact Pentair® Everpure® Technical Support for further assistance.
33 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE
REPLACEMENT PARTS - CONSERV HE-3 RO SYSTEMContact your local Pentair Everpure Dealer for replacement and spare parts.
1 2
3
47
10
11
8
5
9
6
Number Part Number Description
1 EV3148-51 Manifold Tray Assy2 EV3145-01 Flotec® Pump3 EV3111-61 Valve, Needle, PVC, 3/8"4 EV3146-64 Controller5 EV3119-75 Union Tee, 1/2" Tube6 EV3149-69 Screen7 EV3148-02 Valve, 1/2" x 1/2" Pl QC8 EV3148-10 Check Valve, 1/2" x 1/2" Pl QC9 EV3103-90 Reducing Elbow, 1/2" x 3/8"10 EV3103-91 Check Valve11 EV3128-08 Flush Valve, Solenoid, 24 VDC* EV9692-66 Everpure SEN+ Fine Filter Cartridge, 1 PK* EV9692-65 Everpure SEN Fine Filter Cartridge, 1 PK* EV9627-22 Everpure MR-600F RO Membrane Cartridge
*Not Shown
34 WATER YOU CAN TRUST®
REPLACEMENT PARTS - PERMEATE STORAGE TANK
15
12
1713
1
5
24
18
25 6
10
716
26
18
21
22
7
3
27 16
2315
14
1911
18
911
8
2
11
27
4
Number Part Number Description
1 EV3145-33 PU Bladder, 15 gal.2 EV3150-66 Vane/Delivery Pump3 EV3145-74 Tank Shell Assy4 EV3145-73 SM Tank Bottom/Top5 EV3145-75 Accumulator, 0.5 gal6 EV3112-51 Endcap, 3/4" NPT 1/2" JG Fitting7 EV3119-75 Union Tee, 1/2" Tube8 EV3148-01 Elbow, 1/2" QC x 3/8" NPT QC9 EV3148-10 Check Valve 1/2 x 1/2 Pl QC10 EV3146-12 Fitting, 1/2" NPT x 1/2 QC11 EV3146-11 Elbow, 1/2" Stem x 1/2 QC12 EV3148-03 Connector, 1/2" NPT x 3/8" QC13 EV3144-24 Tee, Stem 3/8"14 EV3144-99 Transducer, 0-15 psi15 EV3145-61 Pressure Valve16 EV3146-14 Elbow, 1/2" QC x 1/2" QC17 EV3128-43 White PE Tube, 3/8" OD, 1.75" L18 EV3148-11 White PE Tube, 1/2" OD, 2.0" L
Number Part Number Description
19 EV3145-19 Tank Base20 EV3149-02 Male Connector21 EV3148-11 White PE Tube, 1/2" OD, 3.0" L22 EV3148-00 Elbow, 3/8" x 1/2" PI QC23 EV3128-43 White PE Tube, 3/8" OD, 2.5" L24 EV3149-77 Strap, HE-3 Accumulator25 EV3148-11 White PE Tube, 1/2" OD, 4.750" L26 EV3148-11 White PE Tube, 1/2" OD,27 EV3148-11 White PE Tube, 1/2" OD
35 EVERPURE® CONSERV® HE-3 RO SYSTEM INSTALLATION AND OPERATION GUIDE 35
MAINTENANCEThe Everpure® Conserv® HE-III System requires very little maintenance. Regular cartridge replacement, system recovery verification, and sanitization are the only normal maintenance requirements. Typical service schedules are as listed below.
Every 12 Months (Recommended)Replace all of the cartridges and sanitize the permeate storage tank.
Switch and valve starting positions:• Power - OFF• Soft Water Inlet Valve - CLOSED• Hard Water Inlet Valve - CLOSED• Blended Water Outlet Valve - CLOSED
1. Remove the cover on the Conserv HE-3 RO System.
NOTE: When the cartridges are removed, water will leak from the heads. Be prepared to catch or clean up any spills.
2. OPEN the outlet valve. Use the application equipment to release water pressure. CLOSE the outlet valve.
3. Have the new replacement cartridges ready to install. Remove all the old cartridges by grasping the outside of the cartridge. Push up and turn it to the left until it stops. The cartridge will then pull straight down and out.
4. Refer to "Prefilter and RO Cartridge Installation and System Start-up" on page 12. Perform Steps 1 through 14.
5. Refer to the section " 7 Prepare Storage Tank" on page 14. Perform Steps 2 through 17.
6. Refer to the section "10 Flush Everpure Postfilter Cartridge" on page 16, Perform Steps 1 through 10.
The system is ready to run. Use application blended water for five (5) minutes and test the TDS. If the measured TDS reading is not within the required specification of the application, then the blend should be adjusted.
7. To adjust the TDS of the blended application water, refer to the " 11 Adjust The Blending Valves" on page 16.
COMPLIANCE STATEMENTSCheck for compliance with state and local laws and regulations.
Do not use with water that is microbiologically unsafe, or of unknown quality without adequate disinfection before or after the system.
Substances reduced are not necessarily in your water. System must be maintained according to manufacturer’s instruction, including replacement of filter cartridges.
This system contains a replaceable mineral reduction (RO) module critical for the effective reduction of total dissolved solids.
Blended water should be tested periodically to verify that the system is working properly.
This reverse osmosis system contains a replaceable component critical to the efficiency of the system. Replacement of the reverse osmosis component should be with one of identical specifications, as defined by the manufacturer, to assure the same efficiency and containment reduction performance.
Recovery rating refers to the percentage of the influent water to the membrane portion of the system that is available to the user as reverse osmosis treated water when the system is operated without a storage tank or when the storage tank is bypassed.
Efficiency rating means the percentage of the influent water to the system that is available to the user as reverse osmosis treated water under operating conditions that approximate typical daily usage.
Pentair® Everpure® Technical Support:
Tel: 800.942.1153 (US Only) • 630.307.3000 Main •
Email: [email protected]
Water Treatment
Applicance - E359339
System Tested and Certified by NSF International against NSF/ANSI Standards 42, 53 and 58 for the reduction of:
Standard No. 42 — Aesthetic Effects Standard No. 53 — Health Effects
Standard No. 58
Chemical ReductionTaste and OdorChlorineChloramines
Mechanical FiltrationTurbidityCyst
Mechanical FiltrationTotal Dissolved Solids (TDS)
Mechanical FiltrationNominal Particulate Class I
World Headquarters 1040 Muirfield Drive Hanover Park, IL 60133 United States 800.942.1153 (US Only) 630.307.3000 Main [email protected]
Australia 1-21 Monash Drive Dandenong South, Vic 3175 Australia 011.1300 576 190 Tel [email protected]
China 21F Cloud 9 Plaza, N0 1118 Shanghai, 200052 China 86.21.3211.4588 Tel [email protected]
India Boulevard, B-9/A, 7th Floor - Tower B Sector 62 Noida - 201301 91.120.419.9444 Tel [email protected]
Europe Pentair Water Belgium BVBA Industriepark Wolfstee, Toekomstlaan 30, B-2200 Herentals Belgium +32.(0).14.283.504 Tel [email protected]
Japan Inc. Hashimoto MN Bldg. 7F, 3-25-1 Hashimoto, Midori-ku, Sagamihara-shi Kanagawa 252-0143 Japan 81.(0)42.775.3011 Tel [email protected]
Southeast Asia 390 Havelock Road, #04-01 King’s Centre Singapore 169662 65.6768.5800 Tel [email protected]
All Pentair trademarks and logos are owned by Pentair. All other brands or product names are trademarks or registered marks of their respective owners. Because we are continuously improving our products and services, Pentair reserves the right to change specifications without prior notice.
Pentair is an equal opportunity employer.
EV3149-34 Rev D SE18 ©2018 Pentair. All Rights Reserved.
LIMITED WARRANTYCOMMERCIAL WATER TREATMENT EQUIPMENT
You have just purchased one of the finest water treatment units made. As an expression of confidence in this product, Pentair Filtration Solutions, LLC (“PFS”) offers the following product warranty. This product is warranted against material defects in materials and workmanship to the original end-user when installed in accordance with the PFS specifications. The warranty period commences on the date of installation and is administered as follows:
For a period of ONE (1) YEAR Replaceable elements (i.e., filter & water treatment cartridges)* For a period of ONE (1) YEAR The entire system (excluding replaceable elements)The unit must be used in operating conditions that conform to PFS’s recommended guidelines. This warranty will not apply if the unit has been modified, repaired or altered by someone not authorized by PFS.
If a part described above is found to have a material defect in materials or workmanship within the specified warranty period, you should notify Pentair® Everpure technical service at the phone number listed below. Any part found materially defective within the terms of this warranty will be repaired or replaced (at PFS’s discretion) by your local dealer or Pentair Everpure technical service. You pay only freight from our factory and local dealer charges. Any item repaired or replaced pursuant to this warranty will be covered under the original warranty terms of the system.
PFS is not responsible for damage caused by accident, fire, flood, freezing, Act of God, misuse, misapplication, neglect, oxidizing agents (such as chlorine, ozone, chloramines and other related components), alteration, installation or operation contrary to our printed instructions, or by the use of accessories or components which do not meet PFS’s specifications. Refer to the specifications section in the Installation and Operating manual for approved application parameters.
Our product performance specifications are furnished with each water treatment unit. TO THE EXTENT PERMITTED BY LAW, EVERPURE DISCLAIMS ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE; TO THE EXTENT REQUIRED BY LAW, ANY SUCH IMPLIED WARRANTIES ARE LIMITED IN DURATION TO THE PERIOD SPECIFIED ABOVE FOR THE ENTIRE WATER TREATMENT UNIT.
As a manufacturer, we do not know the characteristics of your water supply or the purpose for which you are purchasing this product. The quality of water supplies may vary seasonally or over a period of time, and your water usage rate may vary as well. Water characteristics can also differ considerably if this product is moved to a new location. For these reasons, we assume no liability for the determination of the proper equipment necessary to meet your requirements, and we do not authorize others to assume such obligations for us. Further, we assume no liability and extend no warranties, express or implied, for the use of this product with a non-potable water source or a water source which does not meet the conditions for use described in the owner’s guide or performance data sheet for this product.
OUR OBLIGATIONS UNDER THIS WARRANTY ARE LIMITED TO THE REPAIR OR REPLACEMENT (AT PFS’S DISCRETION) OF THE FAILED PARTS OF THE WATER TREATMENT UNIT, AND WE ASSUME NO LIABILITY WHATSOEVER FOR DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, SPECIAL, GENERAL OR OTHER DAMAGES.
Some states do not allow the exclusion of implied warranties or limitations on how long an implied warranty lasts, so the above limitation may not apply to you. Similarly, some states do not allow the exclusion of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
*Warranty applies to material defects in materials & workmanship only.
EPA No. 002623-IL-002