31007118.01 www.telemecanique.com ConneXium Ethernet Cabling System TCSESM Managed Switch Installation Manual 12/2006

Connexium TCSESM Managed Switch Installation Manual

Embed Size (px)

DESCRIPTION

tcs

Citation preview

Page 1: Connexium TCSESM Managed Switch Installation Manual

e.com

310

0711

8.01

www.telemecaniqu

ConneXium Ethernet Cabling SystemTCSESM Managed Switch Installation Manual12/2006

Page 2: Connexium TCSESM Managed Switch Installation Manual

Safety Information

NOTICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

© 2006 Schneider Electric. All Rights Reserved.

The addition of this symbol to a Danger or Warning safety label indicatesthat an electrical hazard exists, which will result in personal injury if theinstructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personalinjury hazards. Obey all safety messages that follow this symbol to avoidpossible injury or death.

DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.

DANGER

WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.

WARNING

CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.

CAUTION

2 31007118 12/2006

Page 3: Connexium TCSESM Managed Switch Installation Manual

31007118 12/2006

1

Device Description

At a Glance

Overview This chapter describes the ESM switches and their different versions.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

General Switch Description 6

The Switch Versions 7

3

Page 4: Connexium TCSESM Managed Switch Installation Manual

Device Description

General Switch Description

Overview An ESM switch is a compact, heavy-duty device suitable for industrial applications which can be installed on a standard DIN Rail. The switches are available in 4, 8, 10, 16 and 24 ports combinations. Two of these ports, uplinks, usually used to implement the ring architectures, could be available in Copper or Fiber (multimode, single mode or mixed) and in 10/100 Mbps or Gigabit speeds.

The 10-60VDC/18-30VAC operating voltage is supplied via a plug-in terminal block with two connections to wire primary and redundant voltage if necessary. An alarm relay allows reporting diagnostic information (P/S, Link signal, Redundancy health) to Control systems. Integrated LEDs allow fast on-site installation and troubleshooting.

The HIPER-Ring redundancy concept allows single and fast implementation of redundant architectures (simple and coupling rings). The diagnostics and operating parameter display functions as well as the labeling field for the IP address provide a quick overview.

You can configure or diagnose the switch using a Web browser, Telnet, or the V.24 serial interface of the switch.

The ConneXium ESM switches allow you to set up in a line, star or ring structure switched industrial ETHERNET networks in accordance with the IEEE 802.3 and 802.3u standards using copper technology or fibre optic conductors. End devices and other infrastructure components can be connected using twisted pair cables or multi and single mode fiber optic cables. The twisted pair ports support autocrossing, autonegotiation and autopolarity.

The devices offer a wide variety of functions:

redundancy functions: (Rapid Spanning Tree, redundant ring structure, ring coupling, redundant power supply)security: Unauthorized messages (MAC or IP based) are blocked.synchronization of the system network time (SNTP)traffic controlfunctional diagnosticspriority (message or port-based)VLANtopology detectionWeb-based interfaceCommand Line Interface (CLI)SNMP

4 31007118 12/2006

Page 5: Connexium TCSESM Managed Switch Installation Manual

Device Description

The Switch Versions

Switch Versions

Part Number Part Number Description

4 Port Version TCSESM043F23F0 4 10/100 TX Managed

TCSESM043F1CU0 3 10/100 TX 1 100 FX-MM Managed

TCSESM043F2CU0 2 10/100 TX 2 100 FX-MM Managed

TCSESM043F1CS0 3 10/100 TX 1 100 FX-SM Managed

TCSESM043F2CS0 2 10/100 TX 2 100 FX-SM Managed

8 Port Version TCSESM083F23F0 8 10/100 TX Managed

TCSESM083F1CU0 7 10/100 TX 1 100 FX-MM Managed

TCSESM083F2CU0 6 10/100 TX 2 100 FX-MM Managed

TCSESM083F1CS0 7 10/100 TX 1 100 FX-SM Managed

TCSESM083F2CS0 6 10/100 TX 2 100 FX-SM Managed

TCSESM083F2CX0 6 10/100 TX 1 100 FX-MM 1 100 FX-SM Managed

16 Port Version TCSESM163F23F0 16 10/100 TX Managed

TCSESM163F2CU0 14 10/100 TX 2 100 FX-MM Managed

24 Port Version TCSESM243F2CU0 22 10/100 TX 2 100 FX-MM Managed

Gigabit - 10 Port Version

TCSESM103F23G0 8 10/100 TX 2 10/100/1000 TX Managed

TCSESM103F2LG0 8 10/100 TX 2 1000 SFP (fiber) Managed

Note: This product ships with open sockets (SFP) on the fiber ports. In order to use these ports, order 1 or 2 fiber modules in any combination (see below).

Fiber Media Modules for Gigabit

TCSEAAF1LFU00 fiber module SFP-SX/LC

TCSEAAF1LFS00 fiber module SFP-LX/LC

TCSEAAF1LFH00 fiber module SFP-LH/LC

Accessories TCSEAM0100 Adapter

Memory Back-up Adapter

31007118 12/2006 5

Page 6: Connexium TCSESM Managed Switch Installation Manual

Device Description

Examples of Switch Versions

The figure below shows the 4-port versions of the ESM.

1 Pluggable 6-pin terminal block2 LED display elements3 2-pin DIP switch4 MAC address field5 USB interface6 V.24 access, external management7 IP address field8 Ports in accordance with 10/100 BASE-T(X)9 Protective earth ground

1LNK

ACT

2LNK

ACT

3LNK

ACT

4LNK

ACTIP

Add

ress

MA

C-A

ddre

ss

ConneXium Switch

V.24

ONRM

FAULTRM

PStand

USB

FaultOVO

+24V(P1)

+24V(P2)

Telemecanique

TCSESM043F23F0

1LNK

ACT

2LNK

ACT

3LNK

ACT

4LNK

ACT

IP A

ddre

ss

MA

C-A

ddre

ss

ConneXium Switch

V.24

ONRM

Stand by

FAULT

RM

P

Stand by

USB

Fault

OVOV+24V(P1)

+24V(P2)

Telemecanique

TCSESM043F2CU0/CS0

2

1

1LNK

ACT

2LNK

ACT

3LNK

ACT

4LNK

ACT

IP A

ddre

ss

ConneXium Switch

V.24

ONRMStand by

FAULT

RM

P

Stand by

USB

Fault

OVOV+24V(P1)

+24V(P2)

Telemeca-

TCSESM043F1CU0/CS0

1

MA

C-A

ddre

ss

Twisted pair TX, RJ45, 10/100 Mbit Multimode FX, DSC, 100 MbitSingle mode FX, DSC, 100 Mbit

Port 1 + port 2, freely selectable

1

2

3

45

6

7

8

9

6 31007118 12/2006

Page 7: Connexium TCSESM Managed Switch Installation Manual

Device Description

The figure below shows the 8-port versions of the ESM.

The figure below shows the 16-port versions of the ESM.

Twisted pair TX, RJ45, 10/100 Mbit Multimode FX, DSC, 100 MbitSingle mode FX, DSC, 100

Port 1 + port 2

TCSESM083F23F0

3 4

5 6

7 8

IP A

ddre

ss

MA

C-A

ddre

ss

ConneXium Switch

V.24

ONRM

FAULRM

PStand

USB

FaultOO

+24 +24

Telemecanique

TCSESM083F1CU0/CS0

ACTLNK

LNK

ACT2

3 4

5 6

7 8

IP A

ddre

ss

MAC

-Add

ress

ConneXium Switch

V.24

ONRM

FAULRM

PStand

USB10

FaultOO

+24 +24

Telemecanique

TCSESM083F2CU0/CS0/CX0

ACTLNK

1

ACTLNK

1

3 4

5 6

7 8

IP A

ddre

ss

MA

C-A

ddre

ss

ConneXium Switch

V.24

ONRM

FAULRM

PStand

USB

FaultOO

+24 +24

Telemecanique

1 2

1

2

3

4

5

6

7

8

9

Twisted pair TX, RJ45, 10/100 Mbit Multimode FX, DSC, 100 Mbit

Port 1 + port 2

11 12

13

15

IP A

ddre

ss

MA

C-A

ddre

ss

ConneXium Switch

V.24

ONRM

FAULTRM

PStand

USB

FaultOO

+24V(P1)

+24V

Telemecanique

TCSESM163F2CU0

3 4

5 6

7 8

9 10

ACTLNK

1

ACTLNK

1

11 12

13 14

15 16

IP A

ddre

ss

MA

C-A

ddre

ss

ConneXium Switch

V.24

ONRM

FAULTRM

PStand by

USB

FaultOVOV

+24V +24V

Telemecanique

TCSESM163F23F0

1 2

3 4

5 6

7 8

9 10

9

1

2

3

4

5

6

7

8

31007118 12/2006 7

Page 8: Connexium TCSESM Managed Switch Installation Manual

Device Description

The figure below shows the 24-port version of the ESM.

The figure below shows the 10-port (gigabit) versions of the ESM.

Multimode FX, DSC, 100 MbitPort 1 + Port 2, freely selectable

19

21

23

IP A

ddre

ss

MA

C-A

ddre

ss

ConneXium Switch

V.24

ONRM

FAULRM

PStand

USB10

FaultOO

+24 +24

Telemecanique

TCSESM243F2CU0

3 4

5 6

7 8

9 10

11

13

15

17

ACTLNK

1

ACTLNK

1

1

2

3

4

5

6

7

8

9

5 6

7 8

9 10

IP A

ddre

ss

MAC

-Add

ress

ConneXium Switch

V.24

ONRM

FAULTRM

PStand

USB

Fault

OO+24V(P1)

+24V

Telemecanique

TCSESM103F23G0

3 4

LNK

ACT1

LNK

ACT2

5 6

7 8

9 10

IP A

ddre

ss

MA

C-A

ddre

ss

ConneXium Switch

V.24

ONRM

FAULTRM

PStand by

USB

FaultOVO

+24V +24

Telemecanique

TCSESM103F2LG0

3 4

ACTLNK

2

ACTLNK

1

Twisted pair TX, RJ45, 10/100/1000 MbitFX, SFP-shaft, 1000 Mbit

Port 1 + Port 2

1

2

3

4

5

6

7

8

9

8 31007118 12/2006

Page 9: Connexium TCSESM Managed Switch Installation Manual

31007118 12/2006

2

Installation and Startup

At a Glance

Overview This chapter describes installation and startup of the product.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Safety Instructions 12

Configurations 13

Installation and Startup 15

9

Page 10: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Safety Instructions

Staff Qualification Requirements

Only appropriately qualified staff should work on or near this equipment. Such staff must be thoroughly acquainted with all the warnings and maintenance measures contained in these operating instructions.The proper and safe operation of this equipment assumes proper transport, appropriate storage and assembly, and careful operation and maintenance.Qualified staff according to these operating instructions or the warning notes are persons familiar with setting up, assembling, starting up, and operating this product and who have appropriate qualifications to cover their activities, such as:

training or instruction/entitlement to switch circuits and equipment/systems on and off, ground them, and identify them in accordance with current safety standards,

training or instruction in accordance with current safety standards in looking after and using appropriate safety equipment,

first aid training.

Recycling Note After has been put out of use, it must be disposed of properly as electronic waste in accordance with the effective local, state and national disposal regulations.

Note: Electricity is used to operate this equipment. Comply in every detail with the safety requirements specified in the operating instructions regarding the voltages to apply.

10 31007118 12/2006

Page 11: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Configurations

Line Structure The ESM switches enable backbones in line structures to be built up. Cascading is carried out using the backbone ports:

Redundant Ring Structure

With the redundancy manager function of the ESM modules you can close the two ends of a line structured backbone to a redundant ring, as shown in the figures below. The ESM switches are integrated into the ring via the backbone ports (ports 6 and 7). If one section fails the reaction time comes to less than 0.5 s at up to 50 ESM modules being cascaded.

The following figure describes a redundant ring structure.

ConneXiumTCSESM

PremiumQuantum

ConneXium499NEH10410

ConneXium499NES25100

Optical fiber or copper

Shielded twisted paircrossed cord (490NTC000ll)

Shielded twisted paircord (490NTW000ll)

line structure

ConneXium499NEH10410

PremiumQuantum ConneXium

499NEH10410

ConneXium499NEH14100

ConneXium499NES25100

ConneXiumTCSESM

Shielded twisted paircord (490NTW000••)

Shielded twisted paircord (490NTC000••)

Configured redundancy manager Optical fiberredundant ringor copper

31007118 12/2006 11

Page 12: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Redundant Coupling of Network Segments

The built-in control intelligence of the ESM allows the redundant coupling of network segments. The connection of two network segments is realized via two separate paths. The ESM switches in the redundant line get the redundancy function assigned by the DIP switch setting standby.

The ESM modules in the redundant line and the ESM switches in the main line share their operating states via the control line (crossover Ethernet cable).

After the failure of the main line the redundant ESM modules enable the redundant line within 0.5 s. If the main line is operational again, the ESM switches in the main line inform the redundant ESM modules about this. The main line will be enabled and the redundant line will be disabled within 0.5 s.

The following figure describes a redundant coupling of optical rings structure:

ConneXiumTCSESM

ring 1configured redundancy manager

Master Slave

control line control line

mai

n lin

e

redu

ndan

t lin

e

OpticalShielded twisted pair

crossed cord (490NTC000)Fiber

mai

n lin

e

redu

ndan

t lin

e

redu

ndan

t co

uplin

g of

rin

g1

and

ring

3

redu

ndan

t co

uplin

g of

rin

g1

and

ring

2

ConneXium499NOH10510

ConneXiumTCSESM

configured redundancy manager

ring 2

Optical Fiber Optical Fiber

ring 3

12 31007118 12/2006

Page 13: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Installation and Startup

Overview of Installation

On delivery, a switch is always ready for operation.

The following installation procedure has been tried and tested in service:

unpacking and checkingfilling in the labeling fieldadjusting the DIP switch settingsconnecting the terminal block for supply voltage and signal contactfitting the device onto the snap-on rail, groundingfitting the terminal block, startupconnecting the data lines

Controls The standby and redundancy management functions can be switched on and off with the two-pin DIP switches on the front panel of the ESM.

The default setting is Off for both switches. The standby switch must be on for redundant coupling of 10/100 Mbit/s segments where the ESM is operated in redundant sections in standby mode.

The RM (Redundancy Manager) switch must be On to implement this functionality on the ESM switch. The default settings are as follows: switch position 0 (Off), i.e., RM function not active.

Two-Pin DIP Switch

The figure shows the DIP switch.

DUPLICATE ADDRESS HAZARDHaving two or more devices with the same IP address can cause unpredictable operation of your network. Ensure that you will be assigning a unique IP address to the switch.

Failure to follow this instruction can result in death, serious injury, or equipment damage.

WARNING

Note: Activate just one of the two functions: standby or RM. Activating both functions simultaneously causes the device to be reset.

ONRM

Stand by

31007118 12/2006 13

Page 14: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

DIP Switch Settings

The table shows the DIP switch settings you can make.

Supply Voltage

The supply voltage can be connected redundantly. Both inputs are decoupled. There is no distributed load. With redundant supply, the transformer supplies the ESM alone with the higher output voltage. The supply voltage is electrically isolated from the housing.

The figure illustrates how to connect the supply voltage on the 6-pin terminal block.

DIP Switches Switch State

RM Switch

Stand-By Switch

Ring Redundancy

Ring Coupling

Redundancy Manager

Ring Port

Control Port

Coupling Port

OFF OFF on off off 1+2

ON OFF on off on 1+2

OFF ON on on off 1+2 3 4

ON ON off off off

HAZARD OF ELECTRIC SHOCK OR BURNWhen the module is operated with direct plug-in power units, use only:

SELV supply units that comply with IEC 60950/EN 60950 and(in USA and Canada) Class 2 power units that comply with applicable national or regional electrical codes

Connect the ground wire to the PE terminal before you establish any further connections. When you remove connections, disconnect the ground wire last.

Failure to follow this instruction can result in death, serious injury, or equipment damage.

WARNING

FAULT

+24V(P1) OV OV +24V(P2)

+ +- -9,6...60 VDC 9,6...60 VDC

FAULT

+24V(P1) OV OV +24V(P2)

G~

G~

18...30 VAC 18...30 VAC

14 31007118 12/2006

Page 15: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Class 1, Division 2 Wiring Notes

Ground Connection

The front panel of ConneXium switch modules is grounded via a separate ground connection. The grounding screw is located on the front panel of the switches. The Ethernet RJ-45 socket casings are electrically connected to the front panel of the switch.

Signal Contact The signal contact monitors proper functioning of the switch and thus enables remote diagnostics.

The configuration Web pages also allow you to switch the signal contact manually and thus to control external devices.

If the potential-free signal contact (relay contact, open circuit connection) is opened, the following events are reported:

At least one of the two supply voltages (supply voltage 1 or 2<9.6 V) has failed. There is a permanent malfunction in the device (internal 3.3 VDC voltage).The link status of at least one port is faulty. Link status messages for individual ports can be can be masked in the configuration of the switch. In the default state, connections are not monitored.Redundancy is no longer provided for.An error has occurred during self-testing.

In the Redundancy Manager mode, the following state is also reported:

Ring redundancy is provided for. In the default state, ring redundancy is not monitored.

Note: Power, input and output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods [Article 501-4(b) of the National Electrical Code, NFPA 70] and the authority having jurisdiction.

Note: Use 60/75 or 75° C copper (CU) wire only.

Note: Peripheral equipment must be suitable for the location in which it is used.

Note: Make sure that the electrical installation meets local or nationally applicable safety regulations.

31007118 12/2006 15

Page 16: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Installation Install the device as follows:

Step Action

1 Check whether the DIP switch pre-settings suit your application.

2 Unplug the six-pin terminal block and remove it from the switch module and wire up the supply voltage and indicator lines.

3 Fit the switch on a 35 mm standard DIN EN 50 022 rail:

4 Attach the upper snap-on slide bar on the module to the DIN rail and press it down until it locks in position.

5 Connect the ground wire to terminal block.

6 Reattach the six-pin terminal block to the switch.

7 Turn the power on.

8 Install the Ethernet cables.

8 Start up the switch.

Note: Do not open the module housing.

Note: The ventilation slits must not be covered, inhibiting free air circulation. The distance to the ventilation slots of the housing has to be a minimum of 10 cm.

Note: This is a Class A device. This equipment may cause radio interference if it is used in a residential area. It is the operator´s responsibility to take appropriate preventative measures.

Note: For use in Class 2 circuits.

Note: Use 60/75 or 75 degree C copper (CU) wire only.

16 31007118 12/2006

Page 17: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Interfaces 10/100 Mbit/s Twisted Pair Connection

10/100 Mbit/s ports (R45 socket) enable the connection of end devices or independent network segments in compliance with the IEEE 802.3 100BASE-TX/10BASE-T standards. These ports support:

autonegotiation (Speed and Duplex mode)autocrossing (when autonegotiation is switched on)autopolarity100 Mbit/s half duplex mode, 100 Mbit/s full duplex mode10 Mbit/s half duplex mode, 10 Mbit/s full duplex mode

The default setting is as follows: autonegotiation is activated with the exception of port 1 and 2 (configured by default for Hiper-Ring use): 100 Mbit/s full duplex.

The socket housings are galvanically connected to the front panel.

The figure below describes the pin assignment of a TP/TX interface.

10/100/1000 Mbit/s Twisted Pair Connection

1000 Mbit/s twisted pair connection 1000 Mbit/s twisted pair ports (R45 sockets) allow you to connect end devices or independent network segments in accordance with the IEEE 802.3-2000 (ISO/IEC-3:2000 1000BASE-T standard. These ports support:

autonegotiation (Speed and Duplex mode)autocrossing (when autonegotiation is switched on)autopolarity1000 Mbit/s full duplex mode100 Mbit/s half duplex mode, 100 Mbit/s full duplex mode10 Mbit/s half duplex mode, 10 Mbit/s full duplex mode

Default setting: autonegotiation

The socket housings are galvanically connected to the front panel.

Pin 8Pin 7Pin 6Pin 5Pin 4Pin 3Pin 2Pin 1

n.c.n.c.TD-n.c.n.c.TD+RD-RD+

31007118 12/2006 17

Page 18: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

The pin assignment corresponds to MDI-X.

100 Mbit/s F/0 Connection

100 Mbit/s F/O ports (SC Duplex) allow you to connect end devices or independent network segments in accordance with the IEEE 802.3 100BASE-FX standard. These ports support full and half duplex mode.

Default setting: full duplex

1 Gigabit/s F/0 Connection

Gbit/s F/O ports (SFP sockets and LC fiber modules) enable the connection of end devices or independent network segments in accordance with the IEEE 802.3-2000 (ISO/IEC 8802-3:2000) 1000BASE-SX or 1000BASE-LX standard. These ports support: autonegotiation and full duplex mode. Default setting: autonegotiation

Note: Make sure you connect SM ports only to SM ports and MM ports only to MM ports.

Note: Make sure, that you connect LH ports only to LH ports, SX ports only to SX ports and LX ports only to LX ports.

Pin 8Pin 7Pin 6Pin 5Pin 4Pin 3Pin 2Pin 1

BI_DC-

BI_DC+BI_DA-BI_DD-BI_DD+BI_DA+BI_DB-

BI_DB+

18 31007118 12/2006

Page 19: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Laser Light

Displays After applying the operating voltage, the software starts and initializes itself. The device then performs a self-test. Various LEDs light up in the process. The process lasts approximately 60 seconds.

POTENTIAL INJURY OR EQUIPMENT DAMAGELED OR LASER components in accordance with IEC 60825-1 (2001):LASER CLASS 1 - CLASS 1 LASER PRODUCTLaser lightDo not look into the beam or view the beam directly with optical instruments (magnifying glasses, microscope).At a distance of less than 100 mm, failure to observe this precaution can cause injury to your eyes.Light is emitted from the optical connections or from the ends of the connected optical fibers that are connected to the optical connections. LIGHT EMITTING DIODE CLASS 2 M, wave length 650 nm, power <2 mW in accordance with DIN EN 60825-1:2003-10LIGHT EMITTING DIODE CLASS 1 - CLASS 1 LED PRODUCT

Failure to follow this instruction can result in injury or equipment damage.

CAUTION

Device status

FAULTRM

PStand by Green

Yellow

Port Status

31007118 12/2006 19

Page 20: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Device Status These LEDs provide information about conditions concerning the operating status of the entire device.

Port Status The green and the yellow LEDs on the individual ports display port-related information. During booting, those LEDs display the status of the boot procedure.

LED Status Meaning

P - Power(Green/Yellow LEDs)

lit green both supply voltages on

Iit yellow only one supply voltage on

not lit supply voltage is too low

Fault - Error it red the signal contact is open, i.e. error

not lit the signal contact is closed, i.e. no error

Note: If the manual adjustment is active on the signal contact, the error display is independent of the signal contact setting.

RM - Redundancy Manager(Green/Yellow LEDs)

lit green RM function active, redundant port not active

lit yellow RM function active, redundant port active

not lit RM function not active

flashes green

incorrect configuration of HIPER-Ring (e.g. ring not connected to ring port)

Stand By lit green stand-by operation active

lit yellow stand-by operation not active

LED Status Meaning

LNK (Link Status, Green LED) not lit no valid connection

lit green valid connection

flashes green (1 time/s) port is switched to stand by

flashes green (3 times/s) port is disabled

ACT (Data, Yellow LED) not lit no data reception at port

flashes yellow data reception at port

20 31007118 12/2006

Page 21: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Making Basic Settings

You must enter IP parameters when the switch is installed for the first time. The switch provides five configuration options:

the V.24 interfacethe Ethernet Switch Configurator softwareBOOTPDHCPthe Memory Back Up Adapter (TCSEAM0100)

For detailed information, refer to the chapter Entering the IP Parameters of the Configuration Manual.

Default Settings:

IP address: the device searches the IP address using DHCP.password for management:

public (write access only, just for the Web-based interface)private (read and write access)

V.24 data rate: 9,600 baudring redundancy: activatedring ports on 100 Mbit full duplex or 1000 Mbit autonegotiationEthernet ports: The link status is not evaluated.optical 100 Mbit ports: 100 Mbit full duplexAll other ports: autonegotiationRedundancy Manager switched off (DIP switch RM: OFF)stand-by coupling is switched off (DIP switch: stand-by is switched off)port 4 = control port, port 3 = coupling port for redundant ring coupling

The USB Interface

The USB socket is an interface which allows you to connect a Memory Back Up Adapter (EAM) locally. The EAM is a device which allows you to save and load the configuration and to load the software.

The V.24 Interface (External Management)

RJ11 socket (V.24 interface) is a serial interface which allows you to connect the following devices locally:

an external management station (VT100 terminal or PC with appropriate terminal emulation). (The serial cable that allows external management is part number 490NTRJ11.) This allows you to establish a connection to the Command Line Interface and the System Monitor.Memory Back Up Adapter (EAM)

Pin Number Signal Name

1 VCC

2 - data

3 + data

4 ground

31007118 12/2006 21

Page 22: Connexium TCSESM Managed Switch Installation Manual

Installation and Startup

Settings VT100 Terminal:

The figure below describes the pin assignment of the V24 interface.

Removal The following table shows how to remove the switch from the snap-on rail.

Speed: 9600 Baud (EMS)

Data: 8 bit

Stopbit: 1 bit

Handshake: off

Parity: none

Note: The socket housing is not galvanically insulated from the front panel of the switch.

Note: The V.24 interface is electrically connected to the supply voltage.

Note: You can order the terminal cable separately (ref #: 490NTRJ11).

Pin 6

Pin 1Pin 1

Pin 5

Pin 8

CTSnot connected

TXGND

RXRTS

Step Action

1 Move the screwdriver horizontally under the chassis in the locking slide.

2 Pull this down — without tilting the screwdriver.

3 Pull the switch off the rail.

22 31007118 12/2006

Page 23: Connexium TCSESM Managed Switch Installation Manual

31007118 12/2006

A

Technical Data

At a Glance

Overview This chapter contains the technical data and the order numbers of the product.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

General Technical Hardware Data 26

Dimension Drawings 27

Electromagnetic Compatibility (EMC) and Physical Resistance 29

Network Expansion 30

Power Input and Output 31

Switches and Accessories 32

Underlying Standards 33

Agency Approvals 34

Certifications 34

23

Page 24: Connexium TCSESM Managed Switch Installation Manual

Technical Data

General Technical Hardware Data

Dimensions: W x H x D TCSESM04 47 x 131 x 111 mm1.85 x 5.16 x 4.3 in

TCSESM08 and TCSESM10

74 x 131 x 111 mm2.91 x 5.16 x 4.37 in

TCSESM16 and TCSESM24

111 x 131 x 111 mm4.37 x 5.16 x 4.37 in

Weight TCSESM04 400 g

TCSESM08 410 g

TCSESM10

TCSESM16 600 g

TCSESM24 650 g

Voltage Supply operating voltage 9.6 to 60 VDC or 18 to 30 VAC safety extra-low voltage (SELV), redundant input decoupledRelevant to North America:Nec Class 2 power source 5 A max

Overload Protection at the Input non-exchangeable fuse

Insulation Voltage between Operating Voltage and Housing

800 V

Ambient Conditions operating temperature

0° C (+32° F) to +60° C (+140° F)

storage temperature

ambient air: -40° C (-40° F) to +80° C (+176° F)

humidity 10% to 90% (non-condensing)

atmospheric pressure

up to 2000 m (795 hPa), higher altitudes on demand

Pollution Degree 2

Protection Classes laser protection Class 1 in accordance with EN 60825-1 (2001)

protection class IP 20

24 31007118 12/2006

Page 25: Connexium TCSESM Managed Switch Installation Manual

Technical Data

Dimension Drawings

4 and 8 Port Versions

111 13,7330,48

4613

13,

6

0.544.37

5.16

0.14

1.2

1.8

mminch

111 13,7330,48

74

131

3,6

4.37 0.541.2

2.91

5.16

0.14

31007118 12/2006 25

Page 26: Connexium TCSESM Managed Switch Installation Manual

Technical Data

16 and 24 Port Versions

110,3 13,7330,48

110

130

3,6

1.20

4.33

4.34 0.54

5.12

0.14

mminch

26 31007118 12/2006

Page 27: Connexium TCSESM Managed Switch Installation Manual

Technical Data

Electromagnetic Compatibility (EMC) and Physical Resistance

EMC Immunity The product complies with the standards concerning EMC immunity listed below:

EMC Interference The product complies with the standards concerning EMC interference listed below:.

Physical Resistance

The product complies with the standards concerning physical resistance listed below:.

EMC Immunity Kind of Interference Levels

EN 61000-4-2 discharge of static electricity, contact discharge: test level 3 8 kV

EN 61000-4-3 electromagnetic fields, test level 3 (80 -2000 MHz 20 V/m

EN 61000-4-4 fast transients (burst), test level 3:

power line 4 kV

data line 4 kV

EN 61000-4-5 surge voltages:

EN 61000-4-5 power line: line/line: test level 2 1 kV

power line: line/earth, test level 3 2 kV

data line: test level 3 2 kV

EN 61000-4-6 immunity to conducted disturbances induced by radio frequency fields, test level 3:

10 - 150 kHz 3 V

150 kHz - 80 MHz 10 V

EN 61000-4-9 pulse magnetic fields, test level 4 300 A/m

EMC Interference Classes

EN 55022 Class A

FCC 47 CFR Part 15 Class A

Germanischer Lloyd Classification and Building Regulations VI-7-3 Part 1

Resistance to Standards concerning Resistance

Vibration IEC 60068-2-6, test FC, test levels in accordance with IEC 61131-2Guidelines for the Execution of Prototype Tests, part 1

Shock IEC 60068-2-27, Test EA, test level in accordance with IEC 61131-2

31007118 12/2006 27

Page 28: Connexium TCSESM Managed Switch Installation Manual

Technical Data

Network Expansion

TP Port A twisted pair cable segment is typically 100 m long (cat5e cable for 1000BASE-TX).

100BASE-FX Fiber Optic Port

The table below lists the network expansion data concerning 100BASE-FX fiber optic ports.

1000BASE-FX Fiber Optic Port

The table below lists the network expansion data concerning 1000BASE-FX fiber optic ports.

Description Wave Length

Fiber System Attenuation

Expansion Fiber Data

Multimode FX, DSC, 10/100 Mbit 1300 nm 50/125 μm 0-8 dB 0-5 km 1.0 dB/km, 800 MHz*km

Multimode FX, DSC, 10/100 Mbit 1300 nm 62.5/125 μm 0-11 dB 0-4 km 1.0 dB/km, 500 MHz*km

Single Mode FX, DSC, 10/100 Mbit 1300 nm 9/125 μm 0-16 dB 0-30 km 0.4 dB/km; 3.5 ps/(nm*km)

Description Wave Length

Fiber System Attenuation

Example of Fiber Optic Line Length

Fiber Data

M-SFP-SX/LC (MM) 850 nm 50/125 μm 0-7.5 dB 0-550 m 3.0 dB/km, 400 MHz*km

M-SFP-LX/LC (MM) 1310 nm (1) 50/125 μm 0-11 dB 0-550 m 1.0 dB/km, 800 MHz*km

M-SFP-SX/LC (MM) 850 nm 62.5/125 μm 0-7.5 dB 0-275 m 3.2 dB/km, 200 MHz*km

M-SFP-LX/LC (MM) 1310 nm (1) 62.5/125 μm 0-11 dB 0-550 m 1.0 dB/km, 500 MHz*km

M-SFP-LX/LC (SM) 1310 nm 9/125 μm 0-11 dB 0-20 km 0.4 dB/km; 3.5 ps/(nm*km)

M-SFP-LH/LC (LH) 1550 nm 9/125 μm 6-22 dB 24-72 km 0.25 dB/km; 19 ps/(nm*km)

Note: (1) with fiber optic adapter in accordance with IEEE 802.3-2002 clause 38 (single-mode fiber offset-launch mode conditioning patch cord)

28 31007118 12/2006

Page 29: Connexium TCSESM Managed Switch Installation Manual

Technical Data

Power Input and Output

Power Input and Output List

The table shows power input and output for the different switch versions.

Version Power Input Power Output

TCSESM04, 2 TX Ports 5.3 W 18.1 Btu (IT)/h

TCSESM04, 1 FX Port, 1 TX Port 6.5 W 22.2 Btu (IT)/h

TCSESM04, 2 FX Ports 7.7 W 26.3 Btu (IT)/h

TCSESM08, 2 TX Ports 5.3 W 18.1 Btu (IT)/h

TCSESM08, 1 FX Port, 1 TX Port 6.5 W 22.2 Btu (IT)/h

TCSESM08, 2 FX Ports 7.3 W 26.3 Btu (IT)/h

TCSESM10 (with Gigabit Ports), 2 TX Ports 8.9 W 30.4 Btu (IT)/h

TCSESM10 (with Gigabit Ports), 2 FX Ports 8.3 W 28.4 Btu (IT)/h

TCSESM16, 2 TX Ports 9.4 W 32.1 Btu (IT)/h

TCSESM16, 2 FX Ports 11.8 W 40.3 Btu (IT)/h

TCSESM24, 2 FX Ports 15.5 W 52.9 Btu (IT)/h

31007118 12/2006 29

Page 30: Connexium TCSESM Managed Switch Installation Manual

Technical Data

Switches and Accessories

Scope of Delivery

The delivery comprises:

selected switch versionterminal block for supply voltage and signal contactdescription and manualsCD ROM

Order Numbers

Part Number Description

4 Port Version TCSESM043F23F0 4 10/100 TX Managed

TCSESM043F1CU0 3 10/100 TX 1 100 FX-MM Managed

TCSESM043F2CU0 2 10/100 TX 2 100 FX-MM Managed

TCSESM043F1CS0 3 10/100 TX 1 100 FX-SM Managed

TCSESM043F2CS0 2 10/100 TX 2 100 FX-SM Managed

8 Port Version TCSESM083F23F0 8 10/100 TX Managed

TCSESM083F1CU0 7 10/100 TX 1 100 FX-MM Managed

TCSESM083F2CU0 6 10/100 TX 2 100 FX-MM Managed

TCSESM083F1CS0 7 10/100 TX 1 100 FX-SM Managed

TCSESM083F2CS0 6 10/100 TX 2 100 FX-SM Managed

TCSESM083F2CX0 6 10/100 TX 1 100 FX-MM 1 100 FX-SM Managed

16 Port Version TCSESM163F23F0 16 10/100 TX Managed

TCSESM163F2CU0 14 10/100 TX 2 100 FX-MM Managed

24 Port Version TCSESM243F2CU0 22 10/100 TX 2 100 FX-MM Managed

Gigabit - 10 Port Version

TCSESM103F23G0 8 10/100 TX 2 10/100/1000 TX Managed

TCSESM103F2LG0 8 10/100 TX 2 1000 SFP (fiber) Managed Note: These products ship with open sockets (SFP) on the fiber ports, so in order to use these ports, you must order 1, or 2, media modules shown below.

Fiber Media Modules

TCSEAAF1LFU00 SFP-SX/LC fiber module for Gigabit

TCSEAAF1LFS00 SFP-LX/LC fiber module for Gigabit

TCSEAAF1LFH00 SFP-LH/LC fiber module for Gigabit

Accessories TCSEAM0100 Memory Backup Adapter

30 31007118 12/2006

Page 31: Connexium TCSESM Managed Switch Installation Manual

Technical Data

Underlying Standards

Standard Contents of Standard

EN 61000-6-2:2001 Generic standard: immunity for industrial environments

EN 55022:1998 + A1 2000 + A2-2003 Radio interference characteristics of information technology equipment

EN 60950:2001 Safety of information technology equipment

EN 61131-2:200 Programmable logic controllers

EN 50121-4:2000 Railroad applications—EMC: interference and immunity of signal and telecommunications equipment

FCC 46 CFR Part 15:2003 Code of Federal regulations

EN 10155 Declaration (railroad)

EN 61850-3 Communication networks and systems in stations

IEEE 1613 Standard environment and testing requirements for communication networking devices in electric power substations

31007118 12/2006 31

Page 32: Connexium TCSESM Managed Switch Installation Manual

Technical Data

Agency Approvals

Certifications

The ESM switches have CE certification.

Standards Contents of Standard

UL 508 / CSA C22.2 No. 142 Safety of industrial control equipment

ISA 12.12.01 / CSA C22.2 No. 213 Electrical equipment for use in Class I and Class II, Div. 2 and Class III hazardous (classified) locations

Germanischer Lloyd Classification and construction VI-7-3, part 1, 2003 edition

32 31007118 12/2006