Configuration of Class 300 Transmitters

  • Upload
    pat

  • View
    222

  • Download
    0

Embed Size (px)

Citation preview

  • 7/30/2019 Configuration of Class 300 Transmitters

    1/44

    User Manual

    Configuration of TransmittersClass 300

    Keypad Remote control Modbus network

    weN

    TH300 >Remote probe

    TemperatureHumidity

    Pressure

    CP300 >

    TH300 >Standard probe

    Temperature

    < TT300

    Remote probe

    TT300 >Standard probe

    Air velocity

    CTV310 >Standard probe

  • 7/30/2019 Configuration of Class 300 Transmitters

    2/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    3/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    4/44

    Summary

    10. Air velocity measurement configuration (CP300 + SQR) F600 . . . . . . . . P 2410.a - Temperature compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 2410.b - Air velocity coefficient selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 26

    10.c - Air velocity correction coefficient input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 27

    11. Airflow measurement configuration F600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 28

    12. Other functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 3112.a - Activation / Deactivation of the RS 232 and home bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 3112.b - Serial number display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 3112.c - Modification of Modbus communication speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 3212.d - Purge Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 33

    13. Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 36

    14. Functions recap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P 37

    Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    5/44

    1. Prerequisite

    Page 1Class 300 transmitter configuration via keypad / remote control / Modbus

    1.a - Working principleUsing keypad / remote control / Modbus configuration, you can activate (or deactivate) a channel, change themeasuring range, set the set points and time-delay...

    Principle: the configuration options are accessed via folders and sub-folders (similar to Windows ). Access ismade via a numerical code (full details in this manual).

    Meaning of the keys

    To increment a value or a level

    To decrement a value or a level

    To validate an input

    To cancel an input or to return to the previous step

    AL1 AL2

    CODE:

    0000

    Visual alarm LED

    Graphic display

    Keypad

    Infrared receiver

    1.a.1 - Keypad

    AL1 AL2

    CODE:

    0000

  • 7/30/2019 Configuration of Class 300 Transmitters

    6/44

    Page 2 Class 300 transmitter configuration via keypad / remote control / Modbus

    1. Prerequesite

    1.a.2 - Infrared remote control

    The remote control works like the keypad and the configuration method remains exactly the samewhichever you use (keypad or remote control).

    =

    Meaning of the remote control keys

    To increment a value or a level

    To decrement a value or a level

    To validate an inputTo cancel an input or to return to the previous step

    Channel selectorWith this selector, you can swap the transmission channel so that itmatchs with the transmitter reception channel. See page 6 to configurethe transmitter reception channel.

    The Class 300 can output either a voltage or a current signal.Voltage or Current ?

    Down

    0-10 V

    Up

    4-20 mA

    1.b - Output signal selection

    With the on-off switch located onthe left top of the transmitter(when open), you can chooseanalogue output 0-10V (voltage)or 4-20 mA (current)

    It's extremely unwise to remove the protection tip of our hygrometryprobes as the sensitive element is very fragile even to light contacts.However, if you have to remove the protection tip, take all possible

    precautions and avoid any contact with the sensitive element.

    To remove the protection tip, unscrew it or unclip it.

    1.c - Protection tip of the sensor

    Sensitiveelement

    !

    Protection tipto unscrew

    Protection tipto unscrew

    Sensitive

    element

  • 7/30/2019 Configuration of Class 300 Transmitters

    7/44

    Values formatting -Modbus code :1444 (channel 2)1448 (channel 3 or value 1 of the external transmitter)1452 (channel 4 or value 2 of the external transmitter)

    1440 (channel 1)

    Page 3Class 300 transmitter configuration via keypad / remote control / Modbus

    2. Modbus parameters

    2.a - Configuration parameters Communication speed. . . . . . . . . . . . . . . . . . . . . 19200 Bauds (see page 33 to configure the speed) Data bits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 bits Stop bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 bit

    Parity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . None Flow control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . None Transmitter addressing . . . . . . . . . . . . . . . . . between 1 and 255

    default address 0 for single ended bus configurationto change the addressing, see page 8.

    2.b - Functions Register reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function 03 Register writing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function 16 Communication loop test . . . . . . . . . . . . . . . . . . . . . Function 08

    2.c - Access codes to Registers Registers type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Signed long integer (32 bits), permuted (LSB, MSB)

    Alarms status -Modbus code : 1436

    Relay 1Relay 2

    0 1 0 1Ex. The value sent by the transmitter is 5Alarm condition 1and relay 1 excited

    Values -Modbus code : 1438 (channel 1)1442 (channel 2)

    1446 (channel 3 or value 1 of the external transmitter)1450 (channel 4 or value 2 of the external transmitter)Ex. the value sent by the transmitter is 6321

    ... b4 b3 b2 b1 b0b31

    b31 ... b12 b11 b10 b9 b8 b7 b5 b4 b3 b2 b1 b0b60 0 0 1 0 0 0 0 1 1 0 0

    Unit of measurement (see chart)

    Nr of digits after the comma

    Value sign (0=>+, 1=> -)

    Ex. The formatting displayed is 268.Unit of measurement => 12 (see chart)Figure(s) after the comma => 1Sign => positive

    If the value measured is equal to 6231 :

    Result => 623,1 mmH O2

    Alarm 1Alarm 2

    1 m/s 12 mmH O2

    2 fpm 13 inWg

    3 m3/h 14 Kpa

    4 L/s 15 mmHg

    5 cfm 16 mbar

    6 m3/s 17 g/kg (absolute humidity.

    7 C 18 C (dew temp. Td)

    8 F 19 F (dew temp. Td)

    9 %RH 20 C (wet temp.Tw)

    10 PSI 21 F (wet temp. Tw)

    11 Pa 22 KJ/Kg (Enthalpy i)

    )

    Units of measurement

  • 7/30/2019 Configuration of Class 300 Transmitters

    8/44

    2. Modbus parameters

    Page 4 Class 300 transmitter configuration via keypad / remote control / Modbus

    2.c - Access code to Registers (sequel)

    Serial number of sensing element (SPI - CP300 / Humidity - TH300)Modbus code: 1402

    Other access codes to different registers are indicated on each function at stage n2.Shown as this pictogram: dbuo sM

    202

  • 7/30/2019 Configuration of Class 300 Transmitters

    9/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    10/44

    4.b - BacklightWith the backlight, the reading is easier with more contrast, if the ambient light is weak.You can activate or deactivate it.

    1

    Step Go into the configuration mode (see page 5). The folder number displayedcorresponds to the last folder used.

    2

    StepSelect the folder 100 and validate with .

    Select the sub-folfer 101 and validate with .The cursor> goes to the line of available choices.

    3

    Step With and keys, select 00 to deactivate the backlit or01 to activate.

    Validate with .01F 101

    >

    014F 101

    Step The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to select another folder. with and keys, you can choose another sub-folder from the folder 100.

    >

    01

    F 101>

    100

    100

    4. Display and keypad configurationF100

    dbuo sM

    202

    4.a - Transmitter channel for infrared remote controlYou can change the channel number for receiving the signal from the infrared remote control.The advantage is that only one remote controlis required to drive several transmitters, and that thereis no interference if 2 transmitters are located side by side.

    1

    Step Go into the configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    2

    StepSelect the folder 100 and validate with .

    Select the sub-folder 100 and validate with .The cursor> goes to the line of available choices.

    3

    Step With and keys, select the channel number (from 00 to 09). Validate

    with .03F 100

    >

    034F 100Step The cursor> returns to sub-folders line.

    press twice to return to reading mode

    press once to select another folder.

    with and keys, you can choose another sub-folder from the folder 100.

    >

    00

    F 100>

    100

    100

    dbuo sM

    200

    By default, the channel number is 0.

    Page 6 Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    11/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    12/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    13/44

    CP 301, 302 et 303 CP 304 TH 300

    00 Inactive channel

    01 Pa Pa C C m/s

    02 mmH O mmH O F F fpm2

    03 inWg inWg %HR C

    04 mbar mbar g/Kg (Hygro. absolue F

    305 C mmHg C (Temp. de rose Td) m /h

    06 F C F (Temp. de rose Td) L/s

    07 m/s F C (Temp. humide Tw) cfm

    308 fpm m/s F (Temp. humide Tw) m /s

    309 m /h fpm KJ/Kg (Enthalpie i)

    310 L/s m /h

    11 cfm L/s

    312 m /s cfm

    313 m /s

    TT 300 CTV 310

    Inactive channel Inactive channel Inactive channel Inactive channel

    2

    )

    5. Configuring channels and units of measurementF200

    Class 300 transmitters have 4 measuring channels. You can activate 1, 2, 3 or 4 channels and select each unit ofmeasurement.

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 200 and validate with .

    Channel 1 Channel 2 Channel 3 Channel 4Select sub-folder 200 201 202 203

    With and keys, select the unit of measurement (see chart below).

    Validate with .

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys to choose another sub-folder from the folder 200.

    and validate with . The

    cursor>goes to choices line.

    For a CP 300 transmitter (301, 302, 303 and 304),the SQR option is required in order to activate theunits of air velocity and airflow.

    1

    Step

    2

    Step

    3

    Step

    06F 201

    >

    04

    F 200>

    200

    200

    dbuo sM

    400

    dbuo sM dbuo sM d

    buo sM

    402 404 406

    064F 201Step >

    Page 9Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    14/44

    6. Analogue output managementF300

    6.a - Output diagnosticsWith this function, you can check with a multimeter (or a regulator/display, or a PLC/BMS) if the transmitter outputsare working properly. The transmitter generates a voltage of 0 V, 5 V and 10 V or a current of 4 mA, 12 mA and 20mA.

    6.a.1 - Multimeter connection configuration

    Before carrying out the output diagnostics, all connections and configurations of the transmitter must beenabled, to avoid any damage on the transmitter and the multimeter !

    1

    Step First, select a channel for the output diagnostics.Selection of the channelto be checked

    The channel numbers are indicated on theboard located below the terminal block.

    Channel n1 Channel n2

    2

    Step Example of

    connection

    On the photo alongside, the multimeter isconnected to the 0-10 V output and channeln1.

    NO....

    .........n

    ormall

    yope

    n

    COM

    ..........

    com

    mon

    NC....

    ........

    .normal

    lyclo

    sed

    Relay 1

    NO....

    .........n

    ormall

    yope

    n

    COM

    ..........

    com

    mon

    NC....

    ........

    .normal

    lyclo

    sed

    Relay 2

    B

    -

    A

    +

    0-10V

    ........

    ......volt

    age

    GN

    D.....

    ........

    ....gro

    und

    4-20m

    A .....

    ......curr

    ent

    Analogue output 1

    0-10V

    ........

    ......volt

    age

    GN

    D.....

    ........

    ....gro

    und

    4-20m

    A .....

    ......curr

    ent

    Analogue output 2

    The ticked box showsthe power supply typeof the transmitter(230 Vac shown above).

    230 Vac

    115 Vac

    [24 Vdc / ac

    Page 10 Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    15/44

    6.a.2 - Output diagnostics

    Once the connection of the transmitter to the multimeter (or regulator or PLC/BMS is complete, (see page6), you can carry out the analogue output diagnostics on several check points.

    6. Analogue output management

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 300 and validate with .

    Channel n 1 outputSelect sub-folder 300

    and validate with .

    The cursor> goes to available choices.

    Channel n 2 outputSelect sub-folder 303

    Diagnostic Output

    00 0 V

    01 5 V

    02 10 V

    03 4 mA

    04 12 mA

    05 20 mA

    F300

    With and keys, select the signal that the transmitter must output (see

    chart below). Note : no need to validate with .

    1

    Step

    2

    Step

    3

    Step

    01F 300

    >

    00

    F 300>

    300

    100

    !

    If the deviations are too big (>0,05V or >0,05mA) between the signal issued and thevalue displayed on the multimeter, we recommend that you return the transmitter to

    our factory.

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys to choose another sub-folder from the folder 300.

    4

    Step > F 300

    01

    Page 11Class 300 transmitter configuration via keypad / remote control / Modbus

    dbuo sM dbuo sM

    600 606

  • 7/30/2019 Configuration of Class 300 Transmitters

    16/44

    +500F 302

    6. Analogue output managementF300

    6.b - Analogue output settingsWith this function, you can modify the measuring range of the transmitter, and you can equate the new limits to theanalogue output (0-10V or 4-20mA).You can enter the measuring range required on your own !

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 300 and validate with .

    Minimum of Channel n1output

    Select sub-folder 301

    With and keys, select the value sign: negative or positive, validate with

    . Then, enter the minimum limit value and validate with .

    and validate with . The cursor> returns to the input line.

    of Channel n2output

    Select sub-folder 304

    Minimum

    Maximumof Channel n1output

    Select sub-folder 302

    Etape

    With and keys, select the value sign: negative or positive, validate with

    .

    Then, enter the maximum limit value and validate with .

    and validate with . The cursor> goes to the input line.

    Maximumof Channel n2output

    Select sub-folder 305

    !You must enter the values according to the units of measurement selected, notaccording to the measuring range of the transmitter.

    Eg. on a CP 303 pressure transmitter (0 to 1000 Pa) with a reading in mmH2O, the minimum and maximum ranges must beconfigured on measuring range of 0 to 102 mmH2O. See conversion chart on following page.

    6

    Step The cursor> goes to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys you can choose another sub-folder from the folder300.

    >

    After an analogue output setting, if the unit of measurement is modified (see page 5), you have to reconfigure theoutputs according to the new unit of measurement.

    ! We recommend that the interval between the minimum and maximum is > 5% of the measuring range.

    1

    Step

    2

    Step

    3

    Step

    -000100

    F 301

    >

    -100

    F 301>

    300

    100

    4

    Step

    5

    Step

    +000500F 302

    >

    +500

    F 302

    >

    dbuo sM

    602

    dbuo sM

    608

    dbuo sM

    604

    dbuo sM

    610

    Page 12 Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    17/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    18/44

    7. Alarm / relay settingsF400

    7.a - Activation / Deactivation of BEEP alarm

    Go into configuration mode (page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 400 and validate with .

    Select sub-folder 400 and validate with .

    The cursor> goes to available choices.

    With and keys, select 01 to activate the BEEP alarm or00to

    disactivate. Validate with .

    The cursor> goes to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys you can choose another sub-folder from the folder 400.

    7.b - Relay security

    Enter in configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select folder 400 and validate with .

    Select sub-folder 401 and validate with .

    The cursor> goes to available choices.

    With the keys and , select 01 for a positive security or00for a

    negative security. Validate with .

    The cursor> returns to sub-folders line. press twice on to return to reading mode.

    press once on to return to another folder selection.

    with and keys, you can choose another sub-folder from the folder 400.

    The relay outputs are by default, in negative security: the relay is energizedwhen a set point is reached.With the keypad, you can swap the relays inpositive security: then, the relay is de-energizedwhen a set point isreached or during a power outage.

    The beep alarm (audible alarm) is activated when a set point is reached.For more details on the setpoint settings, see page 20.

    1

    Step

    2

    Step

    3

    Step

    01F 400

    >

    014F 400Step >

    01

    F 400>

    400

    100

    1

    Step

    2

    Step

    3

    Step

    01F 401

    >

    014F 401Step >

    01

    F 401>

    400

    100

    dbuo sM

    800

    dbuo sM

    802

    Page 14 Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    19/44

    7. Alarm / relay settingsF400

    7.c - Alarm / relay functions and LED colour codes

    7.c.1 - Visual / audible alarms

    Class 300 transmitters have 2 visual / audible alarms located in front of the transmitter, allowing to know the

    condition of the setpoints.

    Alarm n2Alarm n1Alarm LED colour codes

    Green The alarm function is activated andthe set point is not reached

    Red The alarm function is activated andthe setpoint is reached

    None The alarm function is not activated

    The red LED appears when the setpoint is reached,taking into account the time-delay and the action type(falling or rising).

    See page 17 for more details.

    7.c.2 - The relaysClass 300 transmitters have 2 relays visible on the transmitter board. These 2 relays each have one LED to

    allowreal-time checking.

    Audible alarm

    Once the alarm is activated, an alarm soundswhilst the setpoint is reached.

    Relay LED colour codes

    Red The relay is

    None The relay is not energizedorhas not been configured

    energized

    The relay is energized when the setpoint is reached, takinginto account the time-delay, the action type and also thealarms security mode.Set points, time-delay and action type setting: see page 20Alarm security settings : see page 14

    Relayn2LED

    Relayn1LED

    Relayn2Relay n1

    The BEEP alarm function must be activated to use theaudible alarm. See page 14.

    Page 15Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    20/44

    7.d - Selection of the channel for visual and relays alarms

    7. Alarm / relay settingsF400

    Class 300 transmitters have 4 alarms: 2 visual (LED) and audible alarms and 2 relay alarms. The transmitter can beconfigured with 4 different alarms setups.

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 400 and validate with .

    With and keys, select the channel number for which you want to

    configure an alarm. Validate with .

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys, you can choose another sub-folder from the folder 400(i.e. for example to configure another alarm / relay)

    402 407 412 417Alarm 1 Alarm 2 Relay 1 Relay 2(LED 1) (LED 2)

    Select sub-folder

    and validate with .

    1Step

    2Step

    3

    Step

    014F 402Step

    >

    01

    F 402>

    400

    100

    01

    F 402>

    dbu

    os

    M

    804

    dbuos

    M

    814

    dbuos

    M

    824

    dbuos

    M

    834

    Page 16 Class 300 transmitter configuration via keypad / remote control / Modbus

    Before any alarm setup, check that the corresponding channel(s) is activated.!

  • 7/30/2019 Configuration of Class 300 Transmitters

    21/44

    7.e - Alarm mode details

    7. Alarm / relay settingsF400

    7.e.1 - DefinitionsSetpointThe setpoint is a limit which, on being reached and/or exceeded , activates an alarm or energizes a relay (in negative

    security, see page 14 for more details).

    Time-delay

    Once the setpoint is reached and/or exceeded, the time-delay postpones the alarm activation (or relay excitation) for ashort period (in seconds). Once this period is elapsed, and if the setpoint is still exceeded, then the alarm is activated orthe relay is energized (in negative security).

    Action type

    For alarm activation or relay excitation, you can choose the action type: rising or falling action. Rising action: the alarm is activated once the measurement goes overthe setpoint Falling action: the alarm is activated once the measurement goes below the setpoint

    7.e.2 - Available configurations

    Configuration N1 : 2 setpoints and time-delay activated (Control Mode)

    Setpoint 1

    Setpoint 2

    Time

    Measurement

    Energized

    Not energized

    Relay statusNegative security

    Energized

    Not energized

    Relay statusPositive security

    Alarm set

    Time-delay

    Setpoint 1 > Setpoint 2

    Setpoint 2

    Setpoint 1

    Time

    Measurement

    Energized

    Not energized

    Relay status

    Negative securityEnergized

    Not energized

    Status relayPositive security

    Alarm set

    Time-delay

    Setpoint 2 > Setpoint 1

    Page 17Class 300 transmitter configuration via keypad / remote control / Modbus

    Control mode (or

    regulation mode)=>you can regulate themeasurement within arange determined by 2setpoints.

  • 7/30/2019 Configuration of Class 300 Transmitters

    22/44

    7. Alarm / relay settingsF400

    Configuration N2 : 1 setpoint, time-delay and rising action activated

    Setpoint 1

    Time

    Measurement

    Energized

    Not energized

    Relay statusNegative security

    Energized

    Not energized

    Relay statusPositive security

    Alarm set

    Time-delay

    Configuration N3 : 1 setpoint, time-delay and falling action activated

    Setpoint 1

    Time

    Energized

    Not energized

    Relay statusNegative security

    Energized

    Not energized

    Relay statusPositive security

    Alarm set

    Time-delay

    Page 18 Class 300 transmitter configuration via keypad / remote control / Modbus

    Measurement

  • 7/30/2019 Configuration of Class 300 Transmitters

    23/44

    7.f - Alarm mode selection

    7. Alarm / relay settingsF400

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 400 and validate with .

    With and keys, select the code relative to the alarm mode (see chart

    below). Validate with .

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys, you can choose another sub-folder from the folder400.

    Code Alarm mode Drawing

    00 No alarm

    01 2 setpoints with time-delay (control mode) N 1 page 17

    02 1 setpoint with time-delay and rising action

    03 1 setpoint with time-delay and falling action N 3 page 18

    N 2 page 18

    1

    Step

    2

    Step

    3

    Step

    01F 403

    >

    014F 403Step >

    01

    F 403>

    400

    100

    403 408 413 418Alarm 1 Alarm 2 Relay 1 Relay 2

    Select sub-folder

    and validate with .

    dbuo sM

    806

    dbuo sM

    816

    dbuo sM

    826

    dbuo sM

    836

    Page 19Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    24/44

    7.g - Setpoints and time-delay setting

    7. Alarm / relay settingsF400

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 400 and validate with .

    With and keys, select the value sign: negative or positive. Validate with

    .

    Then, enter the setpoint value and validate with .

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection. with and keys, you can choose another sub-folder from the folder400.

    7.g.1 - Setpoints

    !You must enter values according to the units of measurement selected, notaccording to the measuring range of the transmitter.

    Ex. on a CP 303 pressure transmitter (0 to 1000 Pa) with a reading in mmH2O, the minimum and maximum ranges must beconfigured on measuring range of 0 to 102 mmH2O. See conversion chart on page 13.

    If after having set up a setpoint, the unit of measurement is modified (see page 9), then you have to reconfigurethe setpoints according to this new unit of measurement.

    1

    Step

    2

    Step

    3

    Step

    -00100

    F 404

    >

    -1004F 404Step >

    02

    F 404>

    400

    100

    404 409 414 419Alarm 1 Alarm 2 Relay 1 Relay 2

    To configure the setpoint 1, select sub-folder

    and validate with .

    dbuo sM

    808

    dbuo sM

    818

    dbuo sM

    828

    dbuo sM

    838

    405 410 415 420Alarm 1 Alarm 2 Relay 1 Relay 2

    To configure the setpoint 2b-folder

    (alarm in control mode, see p17),select su

    and validate with .

    dbuo sM

    810

    dbuo sM

    820

    dbuo sM

    830

    dbuo sM

    840

    Page 20 Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    25/44

    7. Alarm / relay settingsF400

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 400 and validate with .

    With and keys, set the required time-delay: from00 to60seconds.If you do not need the time-delay, enter00.

    Validate with .

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys , you can choose another sub-folder from the folder 400.

    7.g.2 - Time-delay

    1

    Step

    2

    Step

    3

    Step

    15F 406

    >

    154F 406Step >

    02

    F 406>

    400

    100

    406 411 416 421Alarm 1 Alarm 2 Relay 1 Relay 2

    Select sub-folder

    and validate with .

    dbuo sM

    812

    dbuo sM

    822

    dbuo sM

    832

    dbuo sM

    842

    Page 21Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    26/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    27/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    28/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    29/44

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 600 and validate with .

    Select the sub-folder 602 , validate with .

    The cursor> returns to available choices.

    With and keys, choose 01. Validate with .

    10.a.1 - Automatic compensation

    1Step

    2

    Step

    3

    Step

    01

    F 602>

    014

    F 602Step >

    01

    F 602>

    600

    100

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys, you can choose another sub-folder from the folder 500

    10. Air velocity measurement configurationF600

    !Once the automatic temperature compensation configuration is complete, check carefullythe connection of the thermocouple K probe.

    dbuo sM

    1204

    Page 25Class 300 transmitter configuration via keypad / remote control / Modbus

    Before configuring the automatic compensation in temperature, you must connect thethermocouple K probe on the transmitter.!

  • 7/30/2019 Configuration of Class 300 Transmitters

    30/44

    10. Air velocity measurement configurationF600

    10.b - Air velocity coefficient selection (CP 300)Since the air velocity is calculated from the pressure (on a CP 300) and from a differential probe, you must enter thecoefficient value of the differential probe. For Pitot tubes and Debimo blades, the coefficient is already includedin the transmitter.

    ! Function only available on the pressure transmitters: CP 300 + SQR option

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 600 and validate with .

    Select the sub-folder 603 and validate with .

    The cursor> goes to available choices.

    With and keys, select the differential probe type. Validate with .

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys, you can choose another sub-folder from the folder600.

    If you use Other differential probe please carefully follow the instructions below.

    Code Differential probe Coef.

    00 Pitot tube L (ISO 3966) 1

    01 DEBIMO blade 0.8165

    02 Other differential probe To be entered

    Select the folder 600 and validate with .

    Select the sub-folder 604 and validate with .

    The cursor> goes to available choices.

    With and keys, enter the coefficient relative to your differentialprobe. This coefficient is given by the manufacturer (from 0.0001 to 9.9999).Validate with .

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys , you can choose another sub-folder from the folder 600.

    10.b.1 - Manual coefficient input

    1

    Step

    2

    Step

    3

    Step

    01

    F 603

    >

    014F 603Step >

    00

    F 603>

    600

    100

    1Step

    2

    Step

    0.8165

    F 604

    >

    0.81653

    F 604Step >

    00

    F 604>

    600

    dbuo sM

    1206

    dbuo sM

    1208

    Page 26 Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    31/44

    10. Air velocity measurement configurationF600

    10.c- Air velocity coefficient inputWith this correction coefficient, you can adjust the transmitter according to the air velocity in your installation.

    ! Function only available on the transmitter : CP 300 + SQR option and CTV 310.

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 600 and validate with .

    Select the sub-folder 605 and validate with .

    The cursor> goes to available choices.

    With and keys, enter the coefficient value calculated (from 0.200 to

    2.000). Validate with .

    The cursor> returns to the sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with et keys, you can choose another sub-folder from the folder 600.

    10.c.1 - How to calculate it ?If the air velocity in your duct is equal to 17 m/s, and if the transmitter indicates 16.6 m/s, then the

    coefficient to apply is 17 / 16,6, ie 1.024

    10.c.2 - Coefficient input

    1Step

    2

    Step

    3

    Step

    1.024

    F 605

    >

    1.0244F 605Step >

    00

    F 605>

    600

    100

    dbuo sM

    1210

    Page 27Class 300 transmitter configuration via keypad / remote control / Modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    32/44

    11. Airflow measurement configurationF600

    11.a - Selection of duct section type or airflow coefficient

    ! Function only available on transmitters: CP 300 + SQR option and CTV 310

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 600 and validate with .

    Select the sub-folder 606 and validate with .The cursor> goes to available choices.

    With and keys, select the section type (00 or01).

    Validate with .

    The cursor> returns to sub-folders line.

    press twice to return to reading mode. press once to return to another folder selection.

    with and keys to choose another sub-folder from the folder 600.

    Code Section type

    00 Rectangular

    01 Circular

    02 Airflow coefficient (to be entered, see p 29)

    11.a.1 - Working from the section type

    Section sizes input

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 600 and validate with .

    Length Width Diameter

    mm 607 608 609

    inch 610 611 612

    Select sub-folder

    and validate with .

    Rectangularsection Circularsection

    1

    Step

    2

    Step

    3

    Step

    00

    F 606

    >

    004

    F 606Step

    >

    00

    F 606>

    600

    100

    1

    Step

    2

    Step

    1500

    F 607>

    600

    100

    dbuo sM

    1212

    dbuo sM

    1214

    Page 28 Class 300 transmitter configuration via keypad / remote control / Modbus

    dbuo sM

    1216

    dbuo sM

    1218

    dbuo sM

    1220

    dbuo sM

    1222

    dbuo sM

    1224

  • 7/30/2019 Configuration of Class 300 Transmitters

    33/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    34/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    35/44

    12. Other functions

    12.a- Activation / deactivation of the RS232 and home busClass 300 transmitters have one RS232 and one RS 485 digital output (Modbus protocol) - optional.With the RS 232, you can display 1 or 2 parameters which are measured by other Class 200 and 300 transmitters, oryou can send measurements to be displayed on another Class 300 transmitters.

    Go into configuration mode (see page 5). The folder numberdisplayed corresponds to the last configurationfolder used.

    Select the folder 100 and validate with .

    Select the sub-folder 103 and validate with

    .

    With and keys, select 00 to receive data from another

    transmitter or select01 to send data via RS 232. Validate withCAUTION !!

    When the transmitter is configured to receive data, then the RS485 Modbus is active). When the transmitter is configured tosend data via RS 232, then the RS 485 Modbus is inactive.

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys, you can choose another sub-folder from the folder 100.

    12.b- Serial number display

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 100 and validate with .

    Select the sub-folder 105

    The serial number of the transmitter is displayed.The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys to choose another sub-folder from the folder 100.

    !If you set up your transmitter to send measurements to another transmitter via RS 232, then you willnot be able to use the RS 485 digital output anymore (Modbus - optional).

    1

    Step

    2

    Step

    3

    Step

    00

    F 103

    >

    004

    F 103Step >

    00F 103>

    100

    100

    dbuo sM

    206

    1

    Step

    2

    Step

    3

    Step

    03.12.2004

    F 105>

    100

    100

    03.12.2004

    F 105>

    Page 31Class 300 transmitter configuration via keypad / remote control / Modbus

    dbuo sM

    210

  • 7/30/2019 Configuration of Class 300 Transmitters

    36/44

    12. Other functions

    Page 32 Class 300 transmitter configuration via keypad / remote control / Modbus

    12.c- Modification of Modbus communication speed

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 100 and validate with .

    Select the sub-folder 107 and validate with .

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys, you can choose another sub-folder from the folder 100.

    1

    Step

    2

    Step

    3

    Step

    05

    F 107

    >

    054F 107Step >

    03

    F 107>

    100

    100

    dbuo sM

    214With and keys, select a communication speed

    (see chart below). Validate with .

    00 2400 bauds 03 19200 bauds (speed by default)

    01 4800 bauds 04 38400 bauds

    02 9600 bauds 05 115200 bauds

  • 7/30/2019 Configuration of Class 300 Transmitters

    37/44

    12. Other functions

    12.d- Purge mode

    Page 33Class 300 transmitters configuration via keypad / remote control / modbus

    The purge mode enables to freeze the measurement when being displayed, enables to lock the analogue outputs,and to activate the relay 1, in order to actuate a de-dust system of an air movement conditions system and to activatethe relay 2 in order to isolate the transmitter.

    ! This function is only available on CP 300 pressure transmitters.

    Here is the detailed process of purge mode :1 - Measurement is frozen.2 - Wait for three seconds.3 - Activation of relay 2 (isolation of the transmitter)4 - Wait for time-delay (e.g : 10 seconds).5 (sending compressed air

    into the network to clean the installation)6 - Purge duration (

    - Activation of relay 1

    (e.g : 30 seconds)

    7 - Deactivation of relay 1 (stop sendingcompressed air).

    8 - Wait for time-delay .9 - Deactivation of relay 210 - Wait for three second.11 - Recovery of measurement

    (e.g : 10 seconds)

    Frozen measurement

    3 seconds of time delay

    Protection duration ofthe transmitter

    Time-delay of advance of triggering oft h e r e l a y 2 c o r r e s p o n d i n g :Temporisation of 10 seconds bydefault

    Time-delay of triggering of the relay 2corresponding : Temporisation of 10seconds by default

    Purge time :30 secondsby default

    Relay 1 : Command ofpurge electro-valve

    Relay 2 : Command ofisolation electro-valve

    To modify purge time and temporisation delay, see page 34-35.

  • 7/30/2019 Configuration of Class 300 Transmitters

    38/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    39/44

    12. Other functions

    12.d- Mode Purge

    Go into configuration mode (see page 5). The folder number displayedcorresponds to the last configuration folder used.

    Select the folder 300 and validate with .

    Select the sub-folder 308 and validate with .

    The cursor> returns to sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and , choose another sub-folder from the folder 300.

    1

    Step

    2

    Step

    3

    Step

    60

    F 308

    >

    604F 308

    Step>

    00

    F 308>

    300

    100

    dbuo sM

    616With keys and , enter the value in minutes of the frequency

    of each purge (from 01 to 9999). Validate with .

    12.d.3 -Frequency

    Go into configuration mode (see page 5).corresponds to the last configuration folder used.

    The folder number displayed

    Select the folder 300 and validate with .

    Select the sub-folder 309 and validate with .

    The cursor> returns to the sub-folders line. press twice to return to reading mode.

    press once to return to another folder selection.

    with and keys, choose another sub-folder from the folder 300.

    1

    Step

    2

    Step

    3

    Step

    10

    F 309

    >

    104F 309Step >

    00

    F 309>

    300

    100

    dbuo sM

    618With and keys, enter the value in seconds of the time-delay

    required (from00 to60). Validate with .

    12.d.4 - Time-delayTime-delay corresponds to the advanced and retardation lead time of triggering of the relay 2 relative tothe relay 1.

    Page 35Class 300 transmitters configuration via keypad / remote control / modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    40/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    41/44

    00 2400 bds 02 9600 bds 04 38400 bds

    01 4800 bds 03 19200 bds 05 115200 bds

    14. Functions recap

    Code Description Available settings

    100 Channel n for IR remote control 0 to 9

    101Backlight 0 or 1

    102 Display contrast control from 0 to 10

    103 Sending data via RS232 0 or 1

    104 Keypad locking 0 or 1

    105 Serial number display

    106 Modbus slave number 1 to 255

    107 Modbus communication speed

    200

    202204

    206

    208

    210

    212

    214

    F100

    Code Description

    200 Unit of channel 1

    201 Unit of channel 2

    202 Unit of channel 3

    203 Unit of channel 4

    Available settings

    400

    402

    404

    406

    F200

    bd uo sMxxx

    bd uo sMxxx

    CP301, 302 et 303 CP 304 TH300 CTV310

    00 I

    01 Pa Pa C m/s

    02 mmH O mmH O F fpm2

    03 inWg inWg %HR C

    04 mbar mbar g/Kg (absolute humd. F3

    05 C mmHg C (dew temperature Td) m /h

    06F C F (dew temperature Td) L/s

    07 m/s F C (wet temperature Tw) cfm3

    08 fpm m/s F (wet temperature Tw) m /s3

    09 m /h fpm KJ/Kg (Enthalpy i)3

    10 L/s m /h

    11 cfm L/s3

    12 m /s cfm3

    13 m /s

    Inactive channel Inactive channel nactive channel Inactive channel

    2

    )

    Page 37Class 300 transmitters configuration via keypad / remote control / modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    42/44

    14. Functions recap

    Code Description

    300 Analogue output setting on channel 1 0=>0V, 1=>5V, 2=>10V3=>4mA, 4=>12mA, 5=>20mA

    301 Analogue output minimum on channel 1

    302 Analogue output maximum on channel 1

    303 Analogue output setting on channel 1 0=>0V, 1=>5V, 2=>10V3=>4mA, 4=>12mA, 5=>20mA

    304 Analogue output minimum on channel 2

    305 Analogue output maximum on channel 2

    306 Activation / Deactivation of purge mode 00 or 01

    307 Working time of each purge from 01 to 60 seconds

    308 Frequency of each purge from 01 to 9999 minutes

    309 Time-delay before and after purge from 00 to 60 seconds

    Available settings

    600

    602

    604

    606

    608

    610

    612

    614

    616

    618

    F300

    channel2

    channe

    l1

    bd uo sMxxx

    CP

    300

    Code Model Description

    500 CP300 Measurement integration from 0 to 9

    500 TH300 Offset in humidity -50,0 to +50,0

    501 CP300 Self-calibration for time-delay from 0 to 60 minutes

    501 TH200 Offset in temperature (C) from -50,0 to +50,0

    502 TH200 Offset in temperature (F) from -90,0 to +90,0

    Available settings

    1000

    1000

    1002

    1002

    1004

    F500dbuo

    sM xxx

    Page 38 Class 300 transmitters configuration via keypad / remote control / modbus

  • 7/30/2019 Configuration of Class 300 Transmitters

    43/44

  • 7/30/2019 Configuration of Class 300 Transmitters

    44/44

    14. Functions recap

    Code Description

    600 Compensation temperature in C* -

    601 Compensation temperature in F* -602 Compensation type* manual =>00 or automatic=>01

    603 Air velocity measurement mean*

    604 Air velocity coefficient value* from 0.0001 to 9.9999

    605 Air velocity correction coefficient from 0.200 to 2.000606 Section type selection

    607 Section length in mm from 0 to 3000 mm

    608 Section width in mm from 0 to 3000 mm

    609 Section diameter in mm from 0 to 3000 mm

    610 Section length in inch from 0 to 118.11 inch

    611 Section width in inch from 0 to 118.11 inch

    612 Section diameter in inch from 0 to 118.11 inch

    613 Airflow coefficient* from 0.1 to 9999.9

    614 Units of pressurefor the pressure calculation*

    Available settings

    1200

    12021204

    1206

    1208

    12101212

    1214

    1216

    1218

    1220

    1222

    1224

    1226

    1228

    F600

    Code Differential probe

    00 Pitot tube

    01 DEBIMO blade

    02 Other differential probe

    Code Section type

    00 Rectangular

    01 Circular

    02 Airflow coefficient

    bd uo sMxxx

    CP301/302/303 CP304

    01 Pa Pa

    02 mmH O2

    03 inWg inWg

    04 mbar mbar

    05 - mmHg

    mmH O2

    Ref.NTAng-Classe300-13/07/10-

    RCS(24)349282095Non-contractualdocume

    nt-Wereservetherighttomodifythecharacteristicsofourproductswithoutpriornotice.

    CP

    300-CTV3

    10

    * : only for CP300 transmitter