Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
FUJITSU StorageETERNUS AF series, ETERNUS DX200F All-Flash Arrays,ETERNUS DX S5/S4/S3 series Hybrid Storage Systems, ETERNUS DX60 S2/DX80 S2/DX90 S2 Disk Storage Systems
Configuration Guide (Power Synchronized Unit)
Instructions for using power synchronized units
P3AM-8012-14ENZ0
Table of Contents
1. Overview 20
External View ............................................................................................................................. 20
Features ..................................................................................................................................... 21
Specifications ............................................................................................................................. 22
Components ............................................................................................................................... 23Power Synchronized Unit .................................................................................................................................... 23AC Sensor Unit (Optional) ................................................................................................................................... 25
System Configuration ................................................................................................................. 26
Power Management for Power Synchronization ......................................................................... 28
2. Installation 32
Package Contents Check ............................................................................................................ 32
Preparation ................................................................................................................................ 32Installation Area ................................................................................................................................................. 32Checking Power Sockets and Server UPS Unit Outlets .......................................................................................... 33Preparing Power Cords ........................................................................................................................................ 33
Installing in a Rack .................................................................................................................... 34Installing a Power Synchronized Unit .................................................................................................................. 35Installing an AC Sensor Unit ................................................................................................................................ 38
3. Powering On and Off 42
4. Connection and Settings 43
Setting the ETERNUS DX/AF ........................................................................................................ 44
Turning on the Power Synchronized Unit ................................................................................... 48
Connecting Cascade Cables ........................................................................................................ 51
Connecting to the Server UPS Unit ............................................................................................. 53Connecting the Server UPS Unit to the Power Synchronized Unit ........................................................................ 54Connecting the AC Sensor Unit ............................................................................................................................ 55
Connecting to the ETERNUS DX/AF ............................................................................................. 57
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
2
Table of Contents
Checking after Connection ......................................................................................................... 61
5. Adding a Connecting Device 62
Connection Procedure When Adding a Server ............................................................................ 62
Connection Procedure When Adding an ETERNUS DX/AF ............................................................ 64
6. Operation and Maintenance 68
Checking the Power Synchronized Unit Status ........................................................................... 68
Device Replacement After Operation Startup ............................................................................. 68Replacing a Server .............................................................................................................................................. 68Replacing a Power Synchronized Unit ................................................................................................................. 69Replacing an AC Sensor Unit ............................................................................................................................... 70
Troubleshooting ......................................................................................................................... 71Check List ............................................................................................................................................................ 71Trouble Record .................................................................................................................................................... 73
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
3
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
4
List of Figures
Figure 1 External view of a power synchronized unit ................................................................................................ 20Figure 2 External view of an AC sensor unit .............................................................................................................. 20Figure 3 Components (power synchronized unit) ...................................................................................................... 23Figure 4 Components (AC sensor unit) ...................................................................................................................... 25Figure 5 System configuration example (power synchronization with two server UPS units) .................................... 26Figure 6 System configuration example (power synchronization with three or more server UPS units) .................... 27Figure 7 Power on using a power synchronized unit ................................................................................................. 28Figure 8 Operation timing chart when using a power synchronized unit (powering on) ........................................... 29Figure 9 Power off using a power synchronized unit ................................................................................................. 30Figure 10 Operation timing chart when using a power synchronized unit (powering off) ........................................... 31Figure 11 ETERNUS AF series, ETERNUS DX S5/S4/S3 series (excluding ETERNUS DX900 S5, ETERNUS DX8900 S4,
and ETERNUS DX8700 S3/DX8900 S3), and ETERNUS DX200F setup (Setup Power Management screen) ... 44Figure 12 ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3 setup
(Setup Power Management screen) ............................................................................................................ 45Figure 13 ETERNUS DX80 S2/DX90 S2 setup (Setup Power Management screen)........................................................ 46Figure 14 ETERNUS DX60 S2 setup (Setup Power Management screen)...................................................................... 47Figure 15 Cascade cable connection............................................................................................................................ 51Figure 16 Connection for the server UPS units and the AC sensor units ....................................................................... 53Figure 17 Trouble record ............................................................................................................................................. 73
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
5
List of Tables
Table 1 Specifications .............................................................................................................................................. 22Table 2 Status and meanings of each LED (for power synchronized units) .............................................................. 24Table 3 Status and meanings of each LED (for AC sensor units)............................................................................... 25Table 4 List of package contents (power synchronized unit).................................................................................... 32Table 5 List of package contents (AC sensor unit).................................................................................................... 32
Preface
Fujitsu would like to thank you for purchasing our power synchronized unit for the ETERNUS AF/DX storage sys-tems.
The power synchronized unit is a device that synchronizes power operations of the ETERNUS AF/DX storagesystems with servers.
Please carefully review the information outlined in this manual.This manual introduces the user to the power synchronized unit, and explains the regular checks and mainte-nance that are required.
This manual is designed for use with the following ETERNUS AF/DX storage systems:
• ETERNUS AF150 S3/AF250 S3 All-Flash Arrays• ETERNUS AF650 S3 All-Flash Arrays• ETERNUS AF250 S2 All-Flash Arrays• ETERNUS AF650 S2 All-Flash Arrays• ETERNUS AF250 All-Flash Arrays• ETERNUS AF650 All-Flash Arrays• ETERNUS DX200F All-Flash Arrays• ETERNUS DX60 S5/DX100 S5/DX200 S5 Hybrid Storage Systems• ETERNUS DX500 S5/DX600 S5 Hybrid Storage Systems• ETERNUS DX900 S5 Hybrid Storage Systems• ETERNUS DX60 S4/DX100 S4/DX200 S4 Hybrid Storage Systems• ETERNUS DX500 S4/DX600 S4 Hybrid Storage Systems• ETERNUS DX8900 S4 Hybrid Storage Systems• ETERNUS DX60 S3/DX100 S3/DX200 S3 Hybrid Storage Systems• ETERNUS DX500 S3/DX600 S3 Hybrid Storage Systems• ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems• ETERNUS DX60 S2/DX80 S2/DX90 S2 Disk Storage Systems
Fourteenth EditionOctober 2019
Applicable Environment
The power synchronized unit was designed and manufactured with user safety for general office environments inmind. When using the power synchronized unit, follow the handling instructions, placement and cautionarynotes listed in this manual. If used beyond the limits described, the users may be at risk of personal injury and/ormaterial damage.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
6
Preface
Using This Manual
This manual contains important information regarding safe usage.Please read this manual carefully before using the power synchronized unit. Pay special attention to"Safety Precautions" (page 13), and understand the contents thoroughly before using the power synchronizedunit. Keep this manual in a safe place for future reference.Fujitsu pays careful attention to the safe use of its products to prevent user injury and/or material damage. To usethe power synchronized unit properly, please follow the instructions in this manual.
Compliance with Standards
The power synchronized unit is compliant with the following standards.
Type Standard
Product safety UL60950-1, CSA-C22.2 No. 60950-1, EN60950-1, IEC60950-1
Electromagnetic Compatibility FCC CFR47 part 15 Class A, ICES-003 Class A, EN55022 Class A, VCCI Class A
Electromagnetic Immunity EN55024
CE certificationElectromagnetic Compatibility Directive 2004/108/EC
Low Voltage Directive 2006/95/EC
Environmental complianceRoHS-compliant (Restriction of hazardous substances)
WEEE-compliant (Waste electrical and electronic equipment)
The power synchronized unit is designed, developed and manufactured as contemplated for general use, including without limitation, general office use, personal use, household use, and ordinary industrial use, but is not designed, developed and manufactured for use in situations with accompanying fatal risks or dan-gers that, unless extremely high safety is secured, could lead directly to death, personal injury, severe physi-cal damage or other loss (hereinafter "High Safety Required Use"), including without limitation, nuclear reaction control in nuclear facility, aircraft flight control, air traffic control, mass transport control, medical life support system, and missile launch control in weapon systems. Do not use the power synchronized unit for High Safety Required Use without securing the sufficient safety level required. If you wish to use the power synchronized unit for High Safety Required Use, please consult with our sales representative before such use.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
7
Preface
● Simplified Chinese
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
8
Preface
● Traditional Chinese
Trademarks
Third-party trademark information related to this product is available at:
https://www.fujitsu.com/global/products/computing/storage/eternus/trademarks/
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
9
About This Manual
Intended Audience
This manual is intended for field engineers who use power synchronized units or for system administrators.
Warning Notations
Warning signs are shown throughout this manual in order to prevent injury to the user and/or material damage.These signs are composed of a symbol and a message describing the recommended level of caution. The follow-ing section explains the symbols, their levels of caution, and their meanings as used in this manual.
The following symbols are used to indicate the type of warnings or cautions being described.
WARNINGThis symbol indicates the possibility of serious or fatal injury if the power synchro-nized unit is not used properly.
CAUTIONThis symbol indicates the possibility of minor or moderate personal injury, as well as damage to the power synchronized unit and/or to other users and their prop-erty, if the power synchronized unit is not used properly.
This symbol indicates IMPORTANT information for the user to note when using the power synchronized unit.
Electric ShockThe triangle emphasizes the urgency of the WARNING and CAUTION contents.
Inside the triangle and above it are details concerning the symbol (e.g. Electric Shock).
No DisassemblyThe barred "Do Not..." circle warns against certain actions.
The action which should be avoided is both illustrated inside the barred circle and written above it (e.g. No Disassembly).
UnplugThe black "Must Do..." circle indicates actions that must be taken.
The required action is both illustrated inside the black circle and written above it (e.g. Unplug).
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
10
About This Manual
How Warnings Are Presented in This Manual
A message is written beside the symbol indicating the caution level. This message is marked with a vertical rib-bon in the left margin, to distinguish this warning from ordinary descriptions.An example is shown here.
About Document Conventions
■ Notice Symbols
The following notice symbol is used in this manual:
■ Naming Conventions
Warning level indicator
Warning type indicator
Warning details
• To avoid damaging the ETERNUS storage system, pay attention to the following points when cleaning the ETERNUS storage system:
Warning layout ribbon
Example warning
- Make sure to disconnect the power when cleaning.- Be careful that no liquid seeps into the ETERNUS storage system when using cleaners, etc.- Do not use alcohol or other solvents to clean the ETERNUS storage system.
CAUTIONDo
Indicates information that supplements the descriptions in this manual, such as functions and knowhow which can be useful when power synchronized units are being set up or used.
ETERNUS storage system models Naming conventions
ETERNUS AF150 S3/AF250 S3, ETERNUS AF650 S3, ETERNUS AF250 S2, ETERNUS AF650 S2, ETERNUS AF250, ETERNUS AF650, ETERNUS DX200F All-Flash Arrays,ETERNUS DX60 S5/DX100 S5/DX200 S5, ETERNUS DX500 S5/DX600 S5/DX900 S5, ETERNUS DX60 S4/DX100 S4/DX200 S4, ETERNUS DX500 S4/DX600 S4, ETERNUS DX8100 S4/DX8900 S4, ETERNUS DX60 S3/DX100 S3/DX200 S3, ETERNUS DX500 S3/DX600 S3, ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems, ETERNUS DX60 S2/DX80 S2/DX90 S2, ETERNUS DX60/DX80/DX90 Disk Storage Systems
ETERNUS AF series,ETERNUS DX series
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
11
About This Manual
About the Latest Version of This Manual and Contact Details
The information in this manual is subject to change without notice for improvement and functionality expansionof the power synchronized unit.The latest version of this manual, and important service and support contacts (see "Contact Fujitsu") for FujitsuCustomer Service in your country of purchase are available at the following website:
https://www.fujitsu.com/global/support/products/computing/storage/disk/manuals/manual.html
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
12
Safety Precautions
This section describes safety precautions.Make sure to follow the instructions described below to ensure the safe use of the power synchronized unit.
■ If you detect an unusual occurrence during operation
■ Instructions for installation
WARNINGDo Not
• If the power cord and/or power plug is damaged, do not use the power synchro-nized unit and contact your sales representative or your maintenance engineer. Never attempt to repair the power synchronized unit by yourself. Not doing so may cause electric shock or fire.
Unplug
• If the power synchronized unit overheats, gives off smoke or an unusual odor, makes an unusual sound, or shakes abnormally, immediately disconnect the power plug from the socket. After the problem has subsided, contact your sales representative or your maintenance engineer. Never attempt to repair the power synchronized unit by yourself. Not doing so may cause electric shock or fire.
• If any liquids such as water or foreign objects like metal fragments get into the power synchronized unit, immediately disconnect the power plug from the socket. Then, contact your sales representative or your maintenance engineer. Do not attempt to repair the power synchronized unit by yourself. Doing so may cause electric shock or fire.
• If the power synchronized unit is dropped or covers are damaged, immediately disconnect the power plug from the socket. Then, contact your sales representa-tive or your maintenance engineer. Do not attempt to repair the power synchro-nized unit by yourself. Doing so may cause electric shock or fire.
WARNINGDo Not
• Do not place the power synchronized unit in an area with bad ventilation or where anything that may cause a fire, or flammable gases are generated. Doing so may cause a fire and damage the power synchronized unit.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
13
Safety Precautions
WARNINGDo Not
• Do not place the power synchronized unit in locations subject to oil smoke, steam, humidity and dust, or in places where the power synchronized unit may come into contact with water. Doing so may lead to electric shock, fire, and/or damage the power synchronized unit.
• Do not place any objects containing water such as vases and cups on or near the power synchronized unit. Doing so may cause water to get into the power syn-chronized unit and lead to electric shock, fire, and/or damage the power synchro-nized unit.
• Do not place the power synchronized unit on an unstable floor. Doing so may cause the power synchronized unit to fall, resulting in injury or damage to the power synchronized unit.
• Do not connect power cords or any other cables to the power synchronized unit during thunderstorms. Doing so may lead to electric shock and/or fire.
Unplug
• When the power synchronized unit is installed or moved, disconnect the power plug from the socket. Remove all the connected cables. Watch your step during the operation. Not doing so may damage the power cords and cause electric shock or fire. Failure to do so may also cause the power synchronized unit to fall and injure others.
CAUTIONDo Not
• Do not use the power synchronized unit in an area affected by corrosive gas or in a salty environment. Doing so may cause device failure.
• Do not knock or place heavy objects on the power synchronized unit or optional products. Doing so may cause injury or damage the power synchronized unit.
• Do not place the power synchronized unit in areas with strong magnetic fields, such as in the vicinity of TVs or speakers. Doing so may damage the power syn-chronized unit and cause the power synchronized unit to malfunction.
• Do not place power cords and other cables in locations where they may become trip hazards. Doing so may cause injury or damage the power synchronized unit .
• Do not place the power synchronized unit on a slanted or unstable surface or in areas that tend to shake. Doing so may cause it to tip over and injure others. Also, do not place the power synchronized unit in high traffic areas such as in a hall-way. Passersby can shake the unit, damage it or cause malfunction.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
14
Safety Precautions
■ Handling the power synchronized unit
CAUTIONDo
• Place the power synchronized unit in an environment in which the temperature and humidity satisfy the environmental conditions described in "Specifications" (page 22).
- For 24-hour operation, ensure that the schedule for air conditioning is able to maintain the required temperature. Failure to do so may result in damage to the device.
- During the winter, control the heating system to limit ambient temperature rises to less than 15C per hour to prevent condensation. Failure to do so could lead to electric shock and damage the power synchronized unit.
WARNINGNo Disassembly
• Do not attempt to repair, disassemble, or remodel the power synchronized unit by yourself. Doing so may cause electric shock or fire.
Do Not
• Do not use a voltage other than that indicated. Doing so may cause electric shock or fire.
• Do not handle the power plug with wet hands. Doing so may cause electric shock.
• Do not wind power cords too tightly at the root of the power cord. Doing so stresses the cords and may expose or snap the inner wires, which can lead to elec-tric shock or fire.
• Do not damage or modify the power cord or the power plug. Heating, forced bending, twisting, pulling, or placing heavy objects on the power cord or the power plug will damage it, causing electric shock or fire.
• Do not plug all the power cords into a single outlet. Doing so may cause electric shock or fire.
• Do not use a power cord that does not satisfy the specifications of the power syn-chronized unit and the AC sensor unit. Doing so may cause electric shock, fire, or device failure.
• Do not use any products other than the optional products for the power synchro-nized unit. Doing so may cause electric shock, fire, or device failure.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
15
Safety Precautions
WARNINGDo Not
• Do not insert or drop foreign objects such as metals or flammable objects into openings in the power synchronized unit such as air vents. Doing so may cause electric shock, fire, or device failure.
• Do not obstruct the openings in the power synchronized unit such as air vents. Doing so may cause overheating that leads to fire and device failure.
• Do not use any flammable type cleaning sprays. Doing so may cause fire or device failure.
Do
• Use only power sockets that have a ground. Failure to do so may cause electric shock, fire, or malfunction.
• Disconnect the power plug from the socket during thunderstorms. Failure to do so may lead to electric shock, fire, or device failure.
• Ensure the power plug is fully inserted into the socket. Failure to do so may cause electric shock or fire.
• Install optional products for the power synchronized unit by following the instruc-tions described in this manual. If an optional product is installed in any other way, device failure or electric shock may occur.
Do Not Wet
• Do not pour or spill water on the power synchronized unit. Doing so may cause electric shock, fire, or device failure.
Unplug
• When unplugging the power plug, do not pull on the cable, hold the plug. Pulling the cable may expose or snap the inner wires, which can lead to electric shock or fire.
• Use a dry cloth to remove all dust from plugs and sockets. Not doing so may cause electric shock or fire.
• When the power synchronized unit is not used for a long period of time, unplug all power plugs. Failure to do so may lead to fire.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
16
Safety Precautions
■ Instructions for rack installation
CAUTIONDo Not
• When the power synchronized unit is pulled out from the rack, make sure not to hit your head if you are operating devices under the power synchronized unit. Not doing so may cause injury.
• Do not put your finger into the inlet/outlet. Doing so may cause injury or device failure.
• Do not remove the cover from the power synchronized unit inlet/outlet unless necessary. Doing so may cause device failure.
• Do not use devices such as mobile phones that emit radiation in the vicinity of the power synchronized unit. Doing so may cause malfunction.
Do
• Before applying insecticides for pest control, turn off the power synchronized unit and cover it with a plastic sheet. Not doing so may damage the power synchro-nized unit.
• Note the following points when cleaning the power synchronized unit. Failure to do so may cause device failure.
- Make sure the power synchronized unit is turned off.- Do not allow liquids such as cleaner to get into the power synchronized unit.- Never use organic solvents such as alcohol or thinner to clean the power syn-
chronized unit.
CAUTIONDo
• Especially for an enclosed rack with doors, or when multiple devices are to be mounted and running, it is important to realize that the temperature inside the cabinet will be considerably higher than that of the room. Make sure the rack internal ambient temperatures do not exceed the environmental conditions for temperature described in "Specifications" (page 22). Failure to do so may damage the power synchronized unit.
• When installing the power synchronized unit with other devices into the same rack, the airflow of the device installed on and under the power synchronized unit may interfere with each other and reduce the effect of device cooling. Make sure to leave plenty of room between the devices if required. Failure to do so may dam-age the power synchronized unit and lead to malfunction.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
17
Safety Precautions
■ Handling cables
CAUTIONDo
• When installing the power synchronized unit in a rack, be careful not to pinch your fingers in the rack. Doing so may cause injury.
• Install the blank panels provided with the rack where no other devices are installed. Failure to do so may cause the power synchronized unit to overheat, resulting in damage to the device.
• When moving the rack after installing the power synchronized unit, make sure to contact your sales representative or your maintenance engineer. Do not move the rack by yourself. Doing so may cause injury and/or damage the power synchro-nized unit.
CAUTIONDo Not
• Do not damage or modify the cables such as heating, forced bending, twisting, pulling, or placing heavy objects on them. Doing so may damage the cables and cause the power synchronized unit to malfunction.
• Do not forcibly bend or fold the cable. Doing so may damage the cable and cause the power synchronized unit to malfunction.
Do
• Firmly insert cable connectors into inlets, outlets, or sockets. Failure to do so may cause the power synchronized unit to malfunction.
• When inserting or removing the cable, only hold the connector. Do not hold the cable. Doing so may damage the cable and cause the power synchronized unit to malfunction.
• Remove any dirt, dust, oil, grease, etc on cable connectors. Failure to do so may cause the power synchronized unit to malfunction.
90
Do not bend more than 90 degrees
Do not fold
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
18
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
19
Labels
Warning labels and manufacturer's labels are found in various places of the power synchronized unit, as shown inthe example below.Never remove these labels from the equipment or allow them to become dirty.
■ Power synchronized unit
■ AC sensor unit
Manufacturer’s labelIndicates the model, serial number, etc.This label is attached to the plate in the label holder on the bottom of the power synchronized unit. It can be checked by pulling out the plate when the power synchronized unit is installed in a rack.
Manufacturer’s labelIndicates the model, serial number, etc.
1. Overview
This chapter provides external views, features, specifications, and system configuration examples of the powersynchronized unit and the AC sensor unit (optional). The names and usages of the various components of thepower synchronized unit and the AC sensor unit are also described.
External View
Figure 1 and Figure 2 show the external views of the power synchronized unit and the AC sensor unit.
■ Power synchronized unit
Figure 1 External view of a power synchronized unit
■ AC sensor unit
Figure 2 External view of an AC sensor unit
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
20
1. Overview Features
Features
This section explains the features of the power synchronized unit and the AC sensor unit.
• Powering the ETERNUS DX/AF on and off can be synchronized with a server by connecting to the Uninterrupt-ible Power Supply (UPS) unit to which the server is connected.As well as the UPS unit to which the server is connected (referred to as "server UPS unit" in the remainder of this manual), the power synchronized unit can be connected to a unit that can control the output of an AC out-let.
• The sizes of the power synchronized unit and the AC sensor unit are 1U. These units can be installed in a 19-inch rack for the server or the ETERNUS DX/AF.
• Two server UPS units can be connected to manage power synchronization in a standard configuration. By add-ing an AC sensor unit, up to 16 server UPS units can be connected.
• By serially connecting each AC sensor unit, the distance between a server UPS unit and a power synchronized unit can be extended by up to 100m.
• By cascading power synchronized units, the power of up to eight ETERNUS DX/AF storage systems can be con-trolled.
• A redundant configuration is available by using two power synchronized units.
• Power synchronization starts when the power synchronized unit is connected to the server UPS unit and the ETERNUS DX/AF by cables. Connection procedures can be performed while the server UPS unit and the ETER-NUS DX/AF are operating.
• The status of the power synchronized unit and the status of the AC power output from the server UPS unit are displayed on the LED. If an error occurs, tracking the error and error recovery can be performed based on the LED information.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
21
1. Overview Specifications
Specifications
Table 1 shows the specifications of the power synchronized unit and the AC sensor unit.
Table 1 Specifications
Item Specifications
Dimensions (W D H)Power synchronized unit 440 230 40 (mm) [1U]
AC sensor unit 100 150 40 (mm) [1U]
WeightPower synchronized unit 4.0kg
AC sensor unit 1.3kg
Power
Voltage AC100 - 120V, AC200 - 240V
Phase Single
Frequency 50Hz/60Hz
Maximum power requirementsAC100 - 120V 3W
AC200 - 240V 7W
Maximum heat generationAC100 - 120V 11kJ/h
AC200 - 240V 26kJ/h
Connection interfaceFor ETERNUS DX/AF storage systems RS232C 4
For AC detection AC sensor 2
Number of con-nectable devices
Server UPS unitBasic 2
Maximum (when AC sensor units are connected)
16
ETERNUS DX/AFBasic 4
Maximum (when a cascade connec-tion is used)
8
Cable length
Between a power synchronized unit and an AC sensor unit (total)
Max. 100m
Between a power synchronized unit and the ETERNUS DX/AF
Max. 5m
Between power synchronized units Max. 10m
Conditions to detect AC output
Power consumption0.1A or less AC output for one second or
more is detected.
Voltage AC100V / AC200V
Phase Single
Support for a duplicated configuration Yes
Environmental conditionTemperature
5 - 40C (during operation)0 - 50C (during non-operation)
Humidity20 - 80%RH (during operation)
8 - 80%RH (during non-operation)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
22
1. Overview Components
Components
This section describes the names and usage of the various components for the power synchronized unit and theAC sensor unit.
Power Synchronized Unit
Figure 3 shows the names and usage of the various components for the power synchronized unit.
Figure 3 Components (power synchronized unit)
AC IN portFor power cord (for AC power input) connection
RCI portNot used
PWC ports (#0, #1, #2, #3 from left)For ETERNUS DX/AF connection with RS232C cables to a power synchronized unit
AC SENSOR port- For AC sensor unit connection with an AC sensor port connection cable to a power synchronized unit- For cascading two power synchronized units with a cascade cable to the AC SENSOR port on the second power synchronized unit
CASCADE portFor cascading two power synchronized unitswith a cascade cable to the CASCADE porton the first power synchronized unit
SENSOR ports (left: #0, right: #1)For power cord (for AC sensor) connectionto detect the power status of a server UPS unit
POWER LEDDisplays the power status of a power synchronized unit
POWER SENSOR LEDDisplays the detection status of AC output from a server UPS unit
POWER CONTROL LEDDisplays the power status of the connected ETERNUS DX/AF
CHECK LEDDisplays the starting status of a power synchronized unit
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
23
1. Overview Components
Table 2 shows details about LEDs and the status of a power synchronized unit.
Table 2 Status and meanings of each LED (for power synchronized units)
LED name FunctionLED
statusPower synchronized unit status
POWER(green)
Displays the power sta-tus of the power syn-chronized unit.
(off) The power synchronized unit is off.
(on)
After the power synchronized unit is turned on, the following condition for powering on the ETERNUS DX/AF is detected.
• AC output from server UPS units using the SENSOR port, the AC SENSOR port, or the CASCADE port
(blinks)
• Even though the power synchronized unit is turned on, the following condition for powering on the ETERNUS DX/AF is not detected.
- AC output from server UPS units using the SENSOR port, the AC SENSOR port, or the CASCADE port
• The power synchronized unit is starting up.
POWER SEN-SOR(green)
Displays that the power synchronized unit has commanded the ETER-NUS DX/AF to turn on or off.
(off)
The following condition is not detected and the power syn-chronized unit commands the ETERNUS DX/AF to turn off.
• AC output from server UPS units using the SENSOR port, the AC SENSOR port, and the CASCADE port
(on)
The following condition is detected and the power synchro-nized unit commands the ETERNUS DX/AF to turn on.
• AC output from server UPS units using the SENSOR port, the AC SENSOR port, or the CASCADE port
POWER CON-TROL(green)
Displays the power sta-tus of the ETERNUS DX/AF.
(off) All of the ETERNUS DX/AF storage systems are off.
(on) The ETERNUS DX/AF is on.
(blinks)The ETERNUS DX/AF is still on even after the power synchro-nized unit commands the ETERNUS DX/AF to turn off (such as when shutting down the ETERNUS DX/AF).
CHECK (Yellow)
Displays the starting status of the power synchronized unit.
(off) The power synchronized unit is operating normally.
(on) The power synchronized unit is starting up.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
24
1. Overview Components
AC Sensor Unit (Optional)
Figure 4 shows the names and usage of the various components for the AC sensor unit.
Figure 4 Components (AC sensor unit)
Table 3 shows details about LEDs and the status of an AC sensor unit.
Table 3 Status and meanings of each LED (for AC sensor units)
LED name FunctionLED
statusAC sensor unit status
LED(green)
Displays the AC out-put status of the con-nected server UPS unit.
(off)AC output from server UPS units using the AC In port is not detected.
(on) AC output from server UPS units using the AC In port is detected.
AC In portFor server UPS unit connection with a power cord (for AC sensor) to an AC sensor unit
AC sensor output portFor power synchronized unit connection with an AC sensor port connection cableto an AC sensor unit
LEDLights up green when AC output froma server UPS unit is detected
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
25
1. Overview System Configuration
System Configuration
System configuration examples when the power synchronized unit is used are shown below.
■ Power synchronization with two server UPS units
The following configuration is an example of power synchronization with two server UPS units.One power synchronized unit can connect up to two server UPS units and four ETERNUS DX/AF storage systems.
Figure 5 System configuration example (power synchronization with two server UPS units)
The server UPS unit must have a function in the management software (PowerChute plus, etc.) that controls the AC power output according to when the server powers on and off.
Server#0UPS unit forServer#0
UPS unit forServer#1
Server#1
SENSOR#0 SENSOR#1
PWC#0
ETERNUS DX/AFPWC
Power synchronized unit#0#0 #1 #2 #3
Power cord (for AC sensor)
Power cord (for AC power input)
RS232C cable
Provided cables are indicated by solid lines.Optional cables that can be added are indicated by dotted lines.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
26
1. Overview System Configuration
■ Power synchronization with three or more server UPS units
The following configuration is an example of power synchronization with three or more server UPS units.Up to 16 server UPS units can be connected by using optional AC sensor units. By cascading two power synchro-nized units, up to eight ETERNUS DX/AF storage systems can be connected.
Figure 6 System configuration example (power synchronization with three or more server UPS units)
Server#0
Server#1 Server#3 -
Server#2
CASCADE
AC SENSOR
Power synchronized unit#1 (*2)#0 #1 #2 #3
SENSOR#0 SENSOR#1AC SENSOR
AC sensor unit#0
AC sensor unit#1
PWC
~~
Power synchronized unit#0#0 #1 #2 #3
UPS unit forServer#1
UPS unit forServer#0
UPS unit for Server#3 -
UPS unit forServer#2
*1: Do not attach a termination resistor to the branch connector on the AC sensor unit.*2: For a cascade connection, do not connect the server UPS unit to power synchronized unit#1.
(*1)
ETERNUS DX/AF#0
PWC
ETERNUS DX/AF#1
PWC
ETERNUS DX/AF#2
PWC
ETERNUS DX/AF#3
PWC
ETERNUS DX/AF#4
PWC
ETERNUS DX/AF#5
PWC
ETERNUS DX/AF#6
PWC
ETERNUS DX/AF#7
PWC
PWC
Cascade cable
AC sensor port connection cable
RS232C cable
Provided cables are indicated by solid lines.Optional cables that can be added are indicated by dotted lines.
Power cord (for AC sensor)
Power cord (for AC power input)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
27
1. Overview Power Management for Power Synchronization
Power Management for Power Synchronization
This section explains power management with a power synchronized unit.
The power synchronized unit detects the AC power output of the target devices for power synchronization andcommands the ETERNUS DX/AF to synchronize the power with the target devices.When the power synchronized unit detects the AC power output of any server UPS unit, the power synchronizedunit commands the ETERNUS DX/AF to turn on.When the power synchronized unit does not detect AC power output in any of the server UPS units, the power syn-chronized unit commands the ETERNUS DX/AF to turn off.The server UPS unit must have a function in the management software that controls the AC power output accord-ing to when the server powers on and off. The server UPS unit must have one unused outlet to connect to thepower synchronized unit.
Connect the power cords of the ETERNUS DX/AF and the power synchronized unit to a UPS (UPS for the ETERNUSDX/AF) that uses a power line that is not the same as the server UPS unit. This enables power to be supplied orstopped according to the scheduled operations and the power failure settings of the server.
■ Powering on sequence for turning on power or power recovery
Figure 7 Power on using a power synchronized unit
1 Power on of an ETERNUS DX/AF UPS unit
2 Issuance of command to turn on the server (power on of the server UPS units)
3 Server startup (OS startup is suspended)The server OS startup is suspended until the ETERNUS DX/AF startup is complete. For the set suspend timeof the server, refer to "Figure 8 Operation timing chart when using a power synchronized unit (poweringon)" (page 29).
ETERNUS DX/AF
PWC
Power synchronized unit
PWC
UPS unit forServer#0
Server#0
UPS unit forServer#1
4
5
3, 6 3, 62 2
UPS managementsoftware
Server#1
UPS managementsoftware
ETERNUS DX/AFUPS unit
UPS settingUPS setting
RS232C cable
An instruction is issued to turn on the ETERNUS DX/AF when AC output is detected.
1
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
28
1. Overview Power Management for Power Synchronization
4 Issuance of command to turn on the ETERNUS DX/AF from the power synchronized unit
5 ETERNUS DX/AF startup
6 Server OS startup
The following figure shows the timing chart of power on operations for scheduled operations and power recovery.For details about setting items and values, refer to the manual of the expansion card that is installed in the UPSunit and the manual of the UPS management software that is used.
Figure 8 Operation timing chart when using a power synchronized unit (powering on)
3 OS startup suspensionShutdown state Operating6 OS startup
ONOFF
ONOFF
ETERNUS DX/AF
Server UPS unit
Server
ETERNUS DX/AF UPS unit
2 Issuance of command to turn on the server
2 Power on of the server UPS unit (Power supply starts)
4 Issuance of command to turn on the ETERNUS DX/AF from the power synchronized unit
S1 (>E1)
5 Startup Operating
E1
1 Power on of an ETERNUS DX/AF UPS unit (Power supply starts)
S1: Waiting time interval starting from when the command is issued to turn on the server to the beginning of the OS startup process. Set a longer time than the time that is required to complete ETERNUS DX/AF startup (E1).E1: Time that is required to complete ETERNUS DX/AF startup from the start of powering on of the ETERNUS DX/AF. For details, refer to the manual that is provided with the connected ETERNUS DX/AF.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
29
1. Overview Power Management for Power Synchronization
■ Powering off sequence for turning off power or power recovery
Figure 9 Power off using a power synchronized unit
(0 Power failure occurred (commercial power is stopped))
1 Shutdown of all the servers
2 Shutdown of all the server UPS units
3 Issuance of command to turn off the ETERNUS DX/AF from the power synchronized unit
4 ETERNUS DX/AF shutdown
5 Shutdown of the ETERNUS DX/AF UPS unit
ETERNUS DX/AF
PWC
Power synchronized unit
PWC
UPS unit forServer#0
Server#0
UPS unit forServer#1
3
4
1 12 2
5
UPS managementsoftware
Server#1
UPS managementsoftware
ETERNUS DX/AF UPS unit
UPS settingUPS setting
RS232C cable
An instruction is issued to turn off the ETERNUS DX/AF when no AC output is detected.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
30
1. Overview Power Management for Power Synchronization
The following figure shows the timing chart of power off operations for scheduled operations or for when a powerfailure occurs. For details about setting items and values, refer to the manual of the expansion card that isinstalled in the UPS unit and the manual of the UPS management software that is used.
Figure 10 Operation timing chart when using a power synchronized unit (powering off)
Shutdown stateOperating
ON
OFF
OFF
ON OFF
ETERNUS DX/AF
Server UPS unit
Server
ETERNUS DX/AF UPS unit
1 Shutdown of the server (Server shutdown starts)
3 Issuance of command to shut down the ETERNUS DX/AF from the power synchronized unit
S3 (>S2)
S2
E3 (>S3+E2)
Operating (Power is on)
E2
5 UPS shutdown (Power supply stops)
S2: Processing time for server shutdown.
E2: Required time to turn off the ETERNUS DX/AF. For details, refer to the manual that is provided with the connected ETERNUS DX/AF.
S3: Battery operation time until server UPS unit shutdown when a power failure occurs.
E3: Battery operation time until ETERNUS DX/AF UPS unit shutdown when a power failure occurs.
Shutdown process
4 Shutdown process
2 UPS shutdown (Power supply stops)
(0 Power failure occurred (commercial power is stopped))
Shutdown stateOperating
ON
OFF
OFF
ON OFF
ETERNUS DX/AF
Server UPS unit
Server
ETERNUS DX/AF UPS unit
1 Shutdown of the server (Server shutdown starts)
3 Issuance of command to shut down the ETERNUS DX/AF from the power synchronized unit
S3 (>S2)
S2
E3 (>S3+E2)
Operating (Power is on)
E2
5 UPS shutdown (Power supply stops)
S2: Processing time for server shutdown.
E2: Required time to turn off the ETERNUS DX/AF. For details, refer to the manual that is provided with the connected ETERNUS DX/AF.
S3: Battery operation time until server UPS unit shutdown when a power failure occurs.
E3: Battery operation time until ETERNUS DX/AF UPS unit shutdown when a power failure occurs.
Shutdown process
4 Shutdown process
2 UPS shutdown (Power supply stops)
(0 Power failure occurred (commercial power is stopped))
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
31
2. Installation
This chapter describes the installation procedures for the power synchronized unit and the AC sensor unit.
Make sure to check "Safety Precautions" (page 13) before installation.
Package Contents Check
Check the list of package contents in Table 4 and Table 5 to confirm that there are no missing parts.
If there are missing parts, contact your sales representative.
Table 4 List of package contents (power synchronized unit)
Table 5 List of package contents (AC sensor unit)
Preparation
Installation Area
■ Placement area
Refer to the placement area of the rack to install the power synchronized unit and the AC sensor unit.
■ Installation condition
Install the power synchronized unit and the AC sensor unit in an area that meets all the conditions described in"Instructions for installation" (page 13) of "Safety Precautions".
Package contents Quantity Note
Power synchronized unit 1 —
RS232C cable 21mFor ETERNUS DX/AF connection
Rack mount kit One set —
Safety Precautions 1 —
Read Me First 1 —
Package contents Quantity Note
AC sensor unit 1 —
AC sensor port connection cable 14mFor power synchronized unit connection
Branch connector 1 —
Rubber foot 4This is not used when the AC sensor unit is installed in a rack.
Rack mount kit One set —
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
32
2. Installation Preparation
Checking Power Sockets and Server UPS Unit Outlets
Check the required number and specifications of power sockets and server UPS unit outlets.
• One power socket is required for each power synchronized unit. Make sure to check the plug type of the power socket. Connect the power synchronized unit to the same power socket line as the ETERNUS DX/AF.
• Make sure each server UPS unit has an unused outlet for connecting a power synchronized unit or an AC sensor unit. In addition, make sure to check the plug type of the outlet.
Preparing Power Cords
Note that power cords (for AC power input) for power synchronized units and power cords (for AC sensor) to con-nect server UPS units to power synchronized units or AC sensor units are not supplied with power synchronizedunits.
The IEC 60320-C14 port type is used for the AC IN ports and the SENSOR ports of the power synchronized units.This port type is also used for the AC IN ports of the AC sensor units. Check the specifications of the power sockets and server UPS unit outlets that are to be used for the power syn-chronized units and AC sensor units. Prepare the required number of appropriate power cords.
• Power cord (for AC power input)- Each power synchronized unit requires one power cord. - The voltage for the AC IN port is 10A 250V or less.
• Power cord (for AC sensor)- Each server UPS unit that is to be connected to the power synchronized unit requires one power cord.- Each AC sensor unit requires one power cord.
Be sure that the power cords have the approval of the appropriate safety agencies of the country where theequipment will be used.
WARNINGDo Not
• Do not use a power cord that does not satisfy the specifications of the power syn-chronized unit and the AC sensor unit. Doing so may cause failure, fire, or electric shock.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
33
2. Installation Installing in a Rack
Installing in a Rack
This section explains how to install a power synchronized unit and an AC sensor unit in a rack.
Make sure to check "Safety Precautions" (page 13) before installing the power synchronized unit and the AC sen-sor unit in a rack. Also refer to the manual that is provided with the racks.
CAUTIONDo
• If the power synchronized unit and the AC sensor unit are installed or disassem-bled other than as described in this manual, device failure or electric shock may occur.
• The power synchronized unit contains delicate components, and should be han-dled gently. Do not drop or knock the power synchronized unit against the rack during installation.
• Install the blank panels provided with the rack where no other devices are installed.
• Especially for an enclosed rack with doors, or when multiple devices are to be mounted and running, it is important to realize that the temperature inside the cabinet will be considerably higher than that of the room. Make sure the rack internal ambient temperatures do not exceed the environmental conditions for temperature described in "Specifications" (page 22). Failure to do so may damage the power synchronized unit.
• When installing the power synchronized unit with other devices into the same rack, the airflow of the device installed on and under the power synchronized unit may interfere with each other and reduce the effect of device cooling. Make sure to leave plenty of room between the devices if required. Failure to do so may dam-age the power synchronized unit and lead to malfunction.
• Do not obstruct the air vents in the power synchronized unit.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
34
2. Installation Installing in a Rack
Installing a Power Synchronized Unit
This section describes how to install a power synchronized unit in a rack.
■ Checking the package contents of the rack mount kit
Check the following package contents to confirm that there are no missing parts. If there are missing parts, con-tact your sales representative.
■ Procedure for installing a power synchronized unit
Procedure
1 Open the front and rear doors of the rack.
2 Attach the M6 cage nuts to the rear rack pillar.
• Attachment positionsInsert four M6 cage nuts in the 1st and 3rd holes above the power synchronized unit base line.
❏ L-shaped bracket: 2
Same for right and left.
❏ M3 flat head screw: 4For attaching L-shaped brack-ets
❏ M6 cage nut: 4
Used when the holes in the rack pillars are square
❏ M6 cross recessed head screw with captive washer: 4
❏ Blank panel: 1
(Rear rack pillars)
Base line ofpower synchronized unit
1st position3rd position
1U (power synchronized unit size)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
35
2. Installation Installing in a Rack
• Attachment procedure
Clip the M6 cage nut tabs into the desired hole from the inside.
3 Attach the L-shaped brackets to the power synchronized unit.Use four M3 flat head screws to attach the L-shaped brackets to the power synchronized unit on both sides.
4 Install the power synchronized unit in the rack.Use four M6 cross recessed head screws with captive washer to fasten the power synchronized unit in therack.
Top view
M6 cage nut
Rack pillar (square)
M3 flat head screws
L-shaped bracket
M3 flat head screws
L-shaped bracket
(Rear rack pillars)
M6 cross recessed head screws with captive washer
M6 cross recessed head screws with captive washer
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
36
2. Installation Installing in a Rack
5 Attach the blank panel to the rack front.The blank panel should be attached at the same height as the power synchronized unit.
End of procedure
(Front rack pillars)
(Rear rack pillars)
Blank panel
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
37
2. Installation Installing in a Rack
Installing an AC Sensor Unit
This section describes how to install an AC sensor unit in a rack.
■ Checking the package contents of the rack mount kit
Check the following package contents to confirm that there are no missing parts. If there are missing parts, con-tact your sales representative.
Install the AC sensor unit in the same rack as the server UPS unit. When installing the AC sensor unit, the length of the power cord (for AC sensor) that connects the AC sensor unit and the server UPS unit must be taken into consideration.
❏ Shelf plate: 1 ❏ L-shaped bracket: 2
Same for right and left.
❏ M4 cross recessed head screw with captive washer: 2
❏ M3 cross recessed head screw with captive washer: 4
❏ M6 cage nut: 4
Used when the holes in the rack pillars are square
❏ M6 cross recessed head screw with captive washer: 4
❏ Blank panel: 1
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
38
2. Installation Installing in a Rack
■ Procedure for installing an AC sensor unit
Procedure
1 Open the front and rear doors of the rack.
2 Attach the M6 cage nuts to the rear rack pillar.
• Attachment positionsInsert four M6 cage nuts in the 1st and 3rd holes above the AC sensor unit base line.
• Attachment procedure
Clip the M6 cage nut tabs into the desired hole from the inside.
3 Attach the L-shaped brackets to the AC sensor unit.Use four M3 cross recessed head screws with captive washer to attach the L-shaped brackets to the AC sen-sor unit on both sides.
(Rear rack pillars)
Base line of AC sensor unit
1st position3rd position
1U (AC sensor unit size)
Top view
M6 cage nut
Rack pillar (square)
M3 cross recessed head screwswith captive washerL-shaped bracket
L-shaped bracketM3 cross recessed head screws with captive washer
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
39
2. Installation Installing in a Rack
4 Attach the shelf plate to the AC sensor unit.Use two M4 cross recessed head screws with captive washer to attach the shelf plate to the AC sensor unit.
5 Attach the shelf plate to the rack.Use four M6 cross recessed head screws with captive washer to fasten the shelf plate in the rack.
Up to two AC sensor units can be attached to the same shelf plate. Attach the first AC sensor unit on the right side when facing the shelf plate as shown in the figure above.
M4 cross recessed head screws with captive washer
Shelf plate
(Rear rack pillars)
M6 cross recessed head screws with captive washer
M6 cross recessed head screws with captive washer
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
40
2. Installation Installing in a Rack
6 Attach the blank panel to the rack front.The blank panel should be attached at the same height as the AC sensor unit.
End of procedure
(Front rack pillars)
(Rear rack pillars)
Blank panel
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
41
3. Powering On and Off
This chapter explains how to turn on and off the power synchronized unit.
■ Powering on
When a power cord (for AC power input) is connected to the AC IN port and the power socket, the power synchro-nized unit turns on.For details about how to connect a power cord (for AC power input), refer to "Turning on the Power SynchronizedUnit" (page 48).
■ Powering off
When a power cord (for AC power input) is disconnected from the AC IN port, the power synchronized unit turnsoff.
For normal operation, there is no need to turn the power off.If the power synchronized unit must be turned off, such as before any inspections of power supply devices are performed, check that the power synchronized unit and the devices that connect the power synchronized unit are all turned off before disconnecting the power cords (for AC power input).
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
42
4. Connection and Settings
This chapter describes the installation and setting procedures for a power synchronized unit and an AC sensorunit.
If your sales representative or maintenance engineer does not perform the settings of the power synchronizedunit and the AC sensor unit, perform the settings yourself.
For the connection and setting details of a device that is connected to the power synchronized unit, refer to themanual that is provided with the connected device.
■ Workflow
Perform the following procedure for connection and settings:
Procedure
1 Set the ETERNUS DX/AF.For details, refer to "Setting the ETERNUS DX/AF" (page 44).
2 Turn on the power synchronized unit.For details, refer to "Turning on the Power Synchronized Unit" (page 48).
3 When five or more ETERNUS DX/AF storage systems are installed, connect the cascade cables.For details, refer to "Connecting Cascade Cables" (page 51).
4 Connect the power synchronized unit to the server UPS unit.For details, refer to "Connecting the Server UPS Unit to the Power Synchronized Unit" (page 54).
5 When three or more server UPS units are connected, connect the AC sensor unit.For details, refer to "Connecting the AC Sensor Unit" (page 55).
6 Connect the power synchronized unit to the ETERNUS DX/AF.For details, refer to "Connecting to the ETERNUS DX/AF" (page 57).
End of procedure
Attach labels to each cable that is to be connected and make a note of the connection source and destination. This helps with cable management and prevents incorrect connections.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
43
4. Connection and Settings Setting the ETERNUS DX/AF
Setting the ETERNUS DX/AF
Perform the necessary settings for power synchronization by using the setting and maintenance program of theETERNUS DX/AF.
■ ETERNUS AF series, ETERNUS DX S5/S4/S3 series (excluding ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3), and ETERNUS DX200F
This section explains the setting items on the power synchronization setting screen.
Figure 11 ETERNUS AF series, ETERNUS DX S5/S4/S3 series (excluding ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3), and ETERNUS DX200F setup (Setup Power Management screen)
• Auto PowerSelect "Disable".
• Power ResumeSelect "Disable".
If the power synchronized unit and the ETERNUS DX/AF storage system are connected with a redundant configu-ration, the operations during a power down are as follows:
• For the ETERNUS AF series and ETERNUS DX series (excluding the ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3)When the controllers for CM#0 and CM#1 both receive shutdown instructions, the shutdown process starts.
• For the ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3When the Service Controllers (SVC) for SVC#0 and SVC#1 both receive shutdown instructions, the shutdown process starts.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
44
4. Connection and Settings Setting the ETERNUS DX/AF
• Connection CMSelect the controllers (CM#0 and/or CM#1) of the ETERNUS DX/AF that are connected to the power synchro-nized unit with the RS232C cable.Select "CM#0" when the power synchronized unit is connected to the PWC port on controller 0. Select "CM#1"when the power synchronized unit is connected to the PWC port on controller 1.When different power synchronized units are connected to controller 0 and controller 1 in a duplicated config-uration, select both "CM#0" and "CM#1".
• Delay until ShutdownDo not change the default setting (0 minute).
• Set management unit interfaceSelect "Power Synchronized Unit".
• Power Failure Signal"Positive" (positive logic) is automatically set.
• Low Battery Signal"Negative" (negative logic) is automatically set.
• UPS Shutdown SignalDo not select the "Enable" checkbox."Positive" (positive logic) is set by default.
■ ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX900 S5,ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3.
Figure 12 ETERNUS DX900 S5, ETERNUS DX8900 S4, and ETERNUS DX8700 S3/DX8900 S3 setup (Setup Power Management screen)
• Auto PowerSelect "Disable".
• Power ResumeSelect "Disable".
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
45
4. Connection and Settings Setting the ETERNUS DX/AF
• Connection SVCSelect the SVCs (SVC#0 and/or SVC#1) of the ETERNUS DX900 S5, ETERNUS DX8900 S4, or ETERNUS DX8700 S3/DX8900 S3 that are connected to the power synchronized unit with the RS232C cable.Select "SVC#0" when the power synchronized unit is connected to the PWC port on SVC#0. Select "SVC#1" whenthe power synchronized unit is connected to the PWC port on SVC#1.When different power synchronized units are connected to SVC#0 and SVC#1 in a duplicated configuration,select both "SVC#0" and "SVC#1".
• Delay until ShutdownDo not change the default setting (0 minute).
• Set management unit interfaceSelect "Power Synchronized Unit".
• Power Failure Signal"Positive" (positive logic) is automatically set.
• Low Battery Signal"Negative" (negative logic) is automatically set.
• UPS Shutdown SignalDo not select the "Enable" checkbox."Positive" (positive logic) is set by default.
■ ETERNUS DX80 S2/DX90 S2
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX80 S2/DX90 S2.
Figure 13 ETERNUS DX80 S2/DX90 S2 setup (Setup Power Management screen)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
46
4. Connection and Settings Setting the ETERNUS DX/AF
• EnableSelect the controllers (CM#0 and/or CM#1) of the ETERNUS DX80 S2/DX90 S2 that are connected to the powersynchronized unit with the RS232C cable.Select "CM#0" when the power synchronized unit is connected to the PWC port on controller 0. Select "CM#1"when the power synchronized unit is connected to the PWC port on controller 1.When different power synchronized units are connected to controller 0 and controller 1 in a duplicated config-uration, select both "CM#0" and "CM#1".
• Delay until Shutdown (min.)Do not change the default setting (0 minute).
• Set management unit interfaceSelect "Power Synchronized Unit".
• Power Failure Signal"Positive" (positive logic) is automatically set.
• Low Battery Signal"Negative" (negative logic) is automatically set.
• UPS Shutdown SignalDo not select the "Enable" checkbox."Positive" (positive logic) is set by default.
• Auto PowerSelect "Disable".
• Power ResumeSelect "Disable".
■ ETERNUS DX60 S2
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX60 S2.
Figure 14 ETERNUS DX60 S2 setup (Setup Power Management screen)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
47
4. Connection and Settings Turning on the Power Synchronized Unit
• EnableSelect the controllers (CM#0 and/or CM#1) of the ETERNUS DX60 S2 that are connected to the power synchro-nized unit with the RS232C cable. Select "CM#0" when the power synchronized unit is connected to the PWCport on controller 0. Select "CM#1" when the power synchronized unit is connected to the PWC port on control-ler 1.When different power synchronized units are connected to controller 0 and controller 1 in a duplicated config-uration, select both "CM#0" and "CM#1".
• Delay until Shutdown (min.)Do not change the default setting (0 minute).
• Set management unit interfaceSelect "Power Synchronized Unit".
• Power Failure Signal"Positive" (positive logic) is automatically set.
• Low Battery Signal"Negative" (negative logic) is automatically set.
• UPS Shutdown SignalDo not select the "Enable" checkbox."Positive" (positive logic) is set by default.
Turning on the Power Synchronized Unit
Connect the power cord (for AC power input) to the power synchronized unit to turn on the power synchronizedunit.
Each power synchronized unit requires a power cord (for AC power input). Power cords (for AC power input) must be obtained by customers.
WARNINGDo Not
• Do not handle the power plug with wet hands. Doing so may cause electric shock.
• Do not damage or modify the power cord or the power plug. Heating, forced bending, twisting, pulling, or placing heavy objects on the power cord or the power plug will damage it, causing electric shock or fire.
• Do not wind power cords too tightly at the root of the power cord. Doing so stresses the cords and may expose or snap the inner wires, which can lead to elec-tric shock or fire.
• Do not use the power cord or the power plug if it is damaged or the plug does not snugly fit into the socket. Doing so may cause electric shock or fire.
• Do not use a power cord that does not satisfy the specifications of the power syn-chronized unit and the AC sensor unit. Doing so may cause electric shock, fire, or device failure.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
48
4. Connection and Settings Turning on the Power Synchronized Unit
■ Procedure for powering on
The procedure for turning on a power synchronized unit is described below.
Procedure
1 Connect the power cord (for AC power input) to the power synchronized unit.
1-1 Connect the power plug of the power cord (for AC power input) to the AC IN port.
1-2 Attach the release tie to the plug of the power cord (for AC power input) to firmly fix the power plug to ensure it does not become unplugged.
Unplug
• Use a dry cloth to remove all dust from plugs and power sockets. Not doing so may cause electric shock or fire.
CAUTIONGround
• Use only power sockets that have a ground. Failure to do so may cause electric shock, fire, or malfunction.
AC IN port
Power cord (for AC power input)
Release tie
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
49
4. Connection and Settings Turning on the Power Synchronized Unit
2 Connect the power plug at the other end of the power cord to the power socket.When the power plug is connected to the power socket, the power synchronized unit is turned on.Check that the CHECK LED is off and the POWER LED is blinking green on the power synchronized unit.
End of procedure
Connect the power plug to the power socket that belongs to the same power line as the ETERNUS DX/AF. Do not connect the power plug to a server UPS unit.
CAUTIONDo
• Ensure the power plug is fully inserted into the socket. Failure to do so may cause electric shock or fire.
• Do not use the server service outlet to connect the power cord for the power synchronized unit.
• Do not overload electrical sockets. Doing so may cause electric shock or fire.
Unplug
• When unplugging the power cord, hold the plug. Do not pull on the cord. Pulling the cord may expose or snap the inner wires, which may cause electric shock or fire.
• When the power synchronized unit is not used for a long period of time, unplug all power plugs. Failure to do so may lead to fire.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
50
4. Connection and Settings Connecting Cascade Cables
Connecting Cascade Cables
When two power synchronized units are cascaded, use the cascade cable to connect the power synchronizedunits.Cascade cables must be purchased separately.
A connection figure for the cascade cable is shown below.
Figure 15 Cascade cable connection
• When the power synchronized units are cascaded, the unit that is connected to the server UPS unit is "power synchronized unit#0".
• Do not attach a branch connector or a termination resistor to the CASCADE port or the AC SENSOR port. Doing so makes operations unstable.
CAUTIONDo
• When connecting external (signal, power, etc.) cables, avoid placing stress on them. Not doing so may damage the cables.
Do Not
• Do not forcibly bend or fold the cable. Doing so may damage the cable and cause the power synchronized unit to malfunction.
Power synchronized unit#1
Power synchronized unit#0
Server#0UPS unit for Server#0
Server#1UPS unit for
Server#1
Cascade cable(optional)
Power cord (for AC sensor)
AC SENSOR port
CASCADE port
SENSOR ports
90
Do not bend more than 90 degrees
Do not fold
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
51
4. Connection and Settings Connecting Cascade Cables
■ Procedure for cascade cable connection
The procedure for connecting a cascade cable is described below.
Procedure
1 Connect the cascade cable to power synchronized unit#0.Connect the cascade cable connector to the CASCADE port.
2 Check that power synchronized unit#1 is turned on.Check that the CHECK LED is off and the POWER LED is blinking green on the power synchronized unit.
3 Connect the connector at the other end to power synchronized unit#1.Connect the connector at the other end of the cascade cable to the AC SENSOR port.
End of procedure
When connecting the cascade cable, check the direction of the connector tab and firmly insert it all the way in.When disconnecting a cascade cable, hold the tab of the connector while pulling it out.
Power synchronized unit#0 CASCADE port
Cascade cable
Power synchronized unit#1
Cascade cable
AC SENSOR port
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
52
4. Connection and Settings Connecting to the Server UPS Unit
Connecting to the Server UPS Unit
Connect the server UPS unit to the power synchronized unit.
When three or more server UPS units are connected or when the server UPS unit is placed beyond the reach of apower cord (for AC sensor), use the AC sensor unit.
The following figure shows server UPS unit and AC sensor unit connection.
Figure 16 Connection for the server UPS units and the AC sensor units
For details about settings for a server UPS unit that is connected to the power synchronized unit, refer to the man-ual that is provided with the server UPS unit and perform the appropriate settings.
The power cord (for AC sensor) that is connected to a server UPS unit is a cable for detecting the AC output status of a server UPS unit. This cable does not supply AC power to the power synchronized unit.
Power synchronized unit
Server#3
Server#2UPS unit for Server#2
UPS unit for Server#3
Server#1
Server#0
UPS unit for Server#1
UPS unit for Server#0
AC sensor unit
Power cord (for AC sensor)(Must be obtained by customers)
Power cord (for AC sensor)(Must be obtained by customers)
AC sensor port connection cable(provided with an AC sensor unit)
....
SENSOR#0 port SENSOR#1 port
AC In port Branch connector
AC SENSOR port
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
53
4. Connection and Settings Connecting to the Server UPS Unit
Connecting the Server UPS Unit to the Power Synchronized Unit
This section describes the procedure for connecting a power synchronized unit to a server UPS unit with the powercord (for AC sensor).Power cords (for AC sensor) must be obtained by customers.
Procedure
1 Connect the power cords (for AC sensor) to the power synchronized unit.
1-1 Connect the plugs of the power cords (for AC sensor) to SENSOR#0 port and SENSOR#1 port on the power synchronized unit.
CAUTIONDo
• When connecting external (signal, power, etc.) cables, avoid placing stress on them. Not doing so may damage the cables.
Do Not
• Do not forcibly bend or fold the cable. Doing so may damage the cable and cause the power synchronized unit to malfunction.
90
Do not bend more than 90 degrees
Do not fold
SENSOR#0 port SENSOR#1 portPower cord
(for AC sensor)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
54
4. Connection and Settings Connecting to the Server UPS Unit
1-2 Attach the release ties to the plugs of the power cords (for AC sensor) to firmly fix the power plugs to ensure they do not become unplugged.
2 Connect the plugs at the other ends to the server UPS units.Connect the plugs of the power cords (for AC sensor) at the other ends to the output outlets of the serverUPS units.
End of procedure
Connecting the AC Sensor Unit
To use the AC sensor unit, connect the server UPS unit and the AC sensor unit with the power cord (for AC sensor),and connect the AC sensor unit and the power synchronized unit with the AC sensor port connection cable.
One AC sensor port connection cable (4m) is provided with each AC sensor unit. Each AC sensor unit requires a power cord (for AC sensor) that must be obtained by customers.
Procedure
1 Connect the AC sensor unit and the server UPS unit with the power cord (for AC sensor).
1-1 Connect the plug of the power cord (for AC sensor) to the AC In port on the AC sensor unit.
1-2 Connect the plug at the other end of the power cord (for AC sensor) to the outlet of the server UPS unit.
Release ties
AC In port
Power cord (for AC sensor)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
55
4. Connection and Settings Connecting to the Server UPS Unit
2 Connect the AC sensor unit to the power synchronized unit with the AC sensor port connection cable.
2-1 Attach the branch connector to the AC sensor output port of the AC sensor unit.A branch connector is provided with the AC sensor unit.
2-2 Connect the AC sensor port connection cable to one of the ports on the branch connector that was attached in Step 2-1.
2-3 Connect the connector at the other end of the AC sensor port connection cable to the AC SENSOR port on the power synchronized unit.
When connecting the AC sensor port connection cable, check the connector orientation and then firmly push it all the way in.When disconnecting the AC sensor port connection cable, hold the tab of the connector while pulling it out.
AC sensor output port
Branch connector
AC sensor port connection cable
Branch connector
AC sensor port connection cable
AC SENSOR portPower synchronized unit
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
56
4. Connection and Settings Connecting to the ETERNUS DX/AF
3 When two or more AC sensor units are connected, connect the AC sensor units with the AC sen-sor port connection cables.
3-1 Connect the AC sensor port connection cable to the other port on the branch connector.
3-2 Connect the connector at the other end of the AC sensor port connection cable to another AC sensor unit.
End of procedure
Connecting to the ETERNUS DX/AF
Connect the power synchronized unit to the ETERNUS DX/AF with the RS232C cable.
Two RS232C cables (1m) are provided with a power synchronized unit. If the length of the cable is too short orthree or more cables are required, purchase more RS232C cables.
• Up to 14 AC sensor units can be connected.• Do not attach a termination resistor to the branch connector on the AC sensor unit. Doing so makes
operations unstable.
AC sensor port connection cable
AC sensor port connection cable
Branch connector
Up to four ETERNUS DX/AF storage systems can be connected to each power synchronized unit. When power syn-chronized units are cascaded, up to eight ETERNUS DX/AF storage systems can be connected.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
57
4. Connection and Settings Connecting to the ETERNUS DX/AF
■ Procedure for RS232C cable connection
The procedure for connecting an RS232C cable is described below.
Procedure
1 Connect the RS232C cable to the power synchronized unit.Connect the RS232C cable connector to the PWC port on the power synchronized unit.
CAUTIONDo
• When connecting external (signal, power, etc.) cables, avoid placing stress on them. Not doing so may damage the cables.
Do Not
• Do not forcibly bend or fold the cable. Doing so may damage the cable and cause the power synchronized unit to malfunction.
90
Do not bend more than 90 degrees
Do not fold
• Connecting the power synchronized unit to the ETERNUS DX8900 S4 and ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 must be performed by your maintenance engineer. Do not attempt to connect the power synchro-nized unit by yourself.
• When connecting the RS232C cable, check the connector orientation and then firmly push it all the way in. When disconnecting the RS232C cable, hold the tab of the connector while pulling it out.
PWC portsRS232C cable
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
58
4. Connection and Settings Connecting to the ETERNUS DX/AF
2 Connect the connector at the other end to the ETERNUS DX/AF.Connect the connector at the other end of the RS232C cable to the PWC port on the ETERNUS DX/AF.
Connect the RS232C cable to the PWC port on the controller or SVC that was selected in the Setup PowerManagement screen.The locations of the PWC ports for various models of ETERNUS DX/AF storage systems are shown below.
• ETERNUS DX60 S5
• ETERNUS AF150 S3/AF250 S3, ETERNUS AF250 S2, ETERNUS AF250, ETERNUS DX100 S5/DX200 S5, ETER-NUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3, ETERNUS DX200F
• ETERNUS AF650 S3, ETERNUS DX500 S5/DX600 S5
The direction of the connector that is connected to the PWC port on the ETERNUS DX/AF is upside down to the connector that is connected to the PWC port on the power synchronized unit.
Controller 1 (CM#1)Controller 0 (CM#0)
Controller 0 (CM#0) Controller 1 (CM#1)
Controller 1(CM#1)
Controller 0(CM#0)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
59
4. Connection and Settings Connecting to the ETERNUS DX/AF
• ETERNUS DX900 S5
• ETERNUS DX60 S4/DX60 S3
• ETERNUS AF650 S2, ETERNUS AF650, ETERNUS DX500 S4/DX600 S4, ETERNUS DX500 S3/DX600 S3
• ETERNUS DX80 S2/DX90 S2
Service Controller 1 (SVC#1)
Service Controller 0 (SVC#0)
Controller 0 (CM#0) Controller 1 (CM#1)
Controller 0 (CM#0)
Controller 1 (CM#1)
Controller 0 (CM#0) Controller 1 (CM#1)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
60
4. Connection and Settings Checking after Connection
• ETERNUS DX60 S2
End of procedure
Checking after Connection
After connecting all the devices, check that the POWER LED on the power synchronized unit is green or blinkinggreen. Perform a test to check that the ETERNUS DX/AF turns on/off with the server as necessary.
Check the following operations when performing a test.For details about LEDs and the status of power synchronized units that are on, refer to "Table 2 Status and mean-ings of each LED (for power synchronized units)" (page 24). If a power synchronized unit is not operating properly, refer to "Troubleshooting" (page 71).
(1) Check the connection statusTurn on/off each server, and check that the linked ETERNUS DX/AF also turns on/off.
(2) Check scheduled operations and power outage settingsCheck that the ETERNUS DX/AF turns on/off in accordance with the linked server for the scheduled operations and the power outage settings.
- Power on by scheduled operationsCheck that the ETERNUS DX/AF turns on in accordance with the linked server for the scheduled operations.
- Power off by scheduled operationsCheck that the ETERNUS DX/AF turns off after all of the linked servers are turned off by a scheduled opera-tion.
- Power off due to power outagesSimulate a power outage and check that the ETERNUS DX/AF turns off after all of the linked servers are turned off according to the power outage settings.
- Power on after power recoverySimulate power recovery and check that the ETERNUS DX/AF turns on in accordance with the linked server by the power recovery settings.
Controller 0 (CM#0) Controller 1 (CM#1)
For the status of power on/off requests from a power synchronized unit to an ETERNUS DX/AF, check the POWER SENSOR LED on the power synchronized unit.
• OnThe ETERNUS DX/AF is requested to be turned on after detecting AC output from a server UPS unit.
• OffThe ETERNUS DX/AF is requested to be turned off after detecting no AC output from all of the server UPS units.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
61
5. Adding a Connecting Device
Devices (servers, power synchronized units, and ETERNUS DX/AF storage systems) that are to be power synchro-nized can be added during system operation.
This chapter explains how to connect a power synchronized unit when these devices are added.
Make sure to check "Safety Precautions" (page 13) or the manual provided with the server or the ETERNUS DX/AFbefore adding a device.
Connection Procedure When Adding a Server
This section describes how to connect the power synchronized unit to synchronize power with an added server.
For details about server installation, connection, and settings, refer to the manual provided with the server.
Procedure
1 Connect the server UPS unit for the added server to the power synchronized unit.An example of a connection between server UPS units and a power synchronized unit is shown below.
For details about how to connect a server UPS unit to the power synchronized unit, refer to "Connecting theServer UPS Unit to the Power Synchronized Unit" (page 54).
2 When two or more servers are added, use the AC sensor units to connect the server UPS units for the added servers to the power synchronized unit.An example of connecting AC sensor units, server UPS units, and a power synchronized unit is shownbelow.
1 Connect the server UPS units and the AC sensor units.
2 Connect the AC sensor units and the power synchronized unit.
3 When two or more AC sensor units are used, connect the AC sensor units.
For details about the connection procedure when using an AC sensor unit, refer to "Connecting the AC Sen-sor Unit" (page 55).
Power synchronized unit
Server#0
Server#1UPS unit forServer#1
UPS unit for Server#0
Power cord (for AC sensor)(Must be obtained by customers)
Added server
SENSOR#1 port
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
62
5. Adding a Connecting Device Connection Procedure When Adding a Server
End of procedure
After the procedure is complete, check that power synchronization performs normally if necessary.
Power synchronized unit
Server#1
Server#2UPS unit forServer#2
Server#3UPS unit forServer#3
Server#0
UPS unit for Server#1
UPS unit for Server#0
AC sensor unit
Power cord (for AC sensor)(Must be obtained by customers)
AC sensor port connection cable(provided with an AC sensor unit)
Added server
Added server AC In port
Branch connector
AC SENSOR port
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
63
5. Adding a Connecting Device Connection Procedure When Adding an ETERNUS DX/AF
Connection Procedure When Adding an ETERNUS DX/AF
This section describes how to connect the power synchronized unit when an ETERNUS DX/AF is added.
For details about ETERNUS DX/AF installation, connection, and settings, refer to one of the following manuals:• ETERNUS AF S3 series All-Flash Arrays Configuration Guide (Basic)• ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays Configuration Guide (Basic)• ETERNUS AF650 S2, ETERNUS AF650 All-Flash Arrays Configuration Guide (Basic)• ETERNUS DX200F All-Flash Arrays Configuration Guide (Basic)• ETERNUS DX S5 series Hybrid Storage Systems Configuration Guide (Basic)• ETERNUS DX60 S4/DX60 S3 Hybrid Storage Systems Configuration Guide (Basic)• ETERNUS DX100 S4/DX200 S4, ETERNUS DX100 S3/DX200 S3 Hybrid Storage Systems Configuration Guide
(Basic)• ETERNUS DX500 S4/DX600 S4, ETERNUS DX500 S3/DX600 S3 Hybrid Storage Systems Configuration Guide
(Basic)• ETERNUS DX80 S2/DX90 S2 Disk storage system User's Guide -Installation-• ETERNUS DX60 S2 Disk storage system User's Guide -Installation-
■ Adding up to four ETERNUS DX/AF storage systems
The connection procedure when up to four ETERNUS DX/AF storage systems are added is described below.
Procedure
1 Set the required settings for power synchronization of the ETERNUS DX/AF storage systems that are to be added.For details about the ETERNUS DX/AF settings, refer to "Setting the ETERNUS DX/AF" (page 44).
2 Connect the ETERNUS DX/AF storage systems to the power synchronized unit.An example of a connection between ETERNUS DX/AF storage systems and a power synchronized unit isshown below.
For details about how to connect an ETERNUS DX/AF to the power synchronized unit, refer to "Connecting tothe ETERNUS DX/AF" (page 57).
Adding the ETERNUS DX8900 S4 or ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 must be performed by your maintenance engineer. Do not attempt to add the ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 by yourself.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
64
5. Adding a Connecting Device Connection Procedure When Adding an ETERNUS DX/AF
End of procedure
Power synchronization starts when the connection is complete. Check that power synchronization performs nor-mally.
■ Adding five or more ETERNUS DX/AF storage systems
To add five or more ETERNUS DX/AF storage systems, cascade the power synchronized units by adding anotherpower synchronized unit.
The procedure is described below.
Procedure
1 Set the required settings for power synchronization of the ETERNUS DX/AF storage systems that are to be added.For details about the ETERNUS DX/AF settings, refer to "Setting the ETERNUS DX/AF" (page 44).
2 Install the power synchronized unit that is to be added in the rack.For details about how to install a power synchronized unit, refer to "Installing a Power Synchronized Unit"(page 35).
3 Turn on the added power synchronized unit.For details about how to turn on a power synchronized unit, refer to "Turning on the Power SynchronizedUnit" (page 48).
Power synchronized unit
ETERNUS DX/AF #0
PWC
ETERNUS DX/AF #1
PWC
ETERNUS DX/AF #2
PWC
ETERNUS DX/AF #3
PWC
Added ETERNUS DX/AF
Added ETERNUS DX/AF
Added ETERNUS DX/AF
Server#0UPS unit forServer#0
Server#1UPS unit for
Server#1
RS232C cables(optional)
RS232C cable(provided with apower synchronized unit)
PWC#0 PWC#1 PWC#2 PWC#3
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
65
5. Adding a Connecting Device Connection Procedure When Adding an ETERNUS DX/AF
4 Cascade two power synchronized units.A cascade connection example is shown below.
For details about cascade connection, refer to "Connecting Cascade Cables" (page 51).
Power synchronized unit#1
Power synchronized unit#0
Server#0UPS unit forServer#0
Server#1UPS unit for
Server#1
Cascade cable(optional)
AC SENSOR port
CASCADE port
ETERNUS DX/AF #0
PWC
ETERNUS DX/AF #1
PWC
ETERNUS DX/AF #2
PWC
ETERNUS DX/AF #3
PWC
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
66
5. Adding a Connecting Device Connection Procedure When Adding an ETERNUS DX/AF
5 Connect the ETERNUS DX/AF storage systems to the power synchronized units.An example of a connection between five or more ETERNUS DX/AF storage systems and power synchronizedunits is shown below.
For details about how to connect an ETERNUS DX/AF to the power synchronized unit, refer to "Connecting tothe ETERNUS DX/AF" (page 57).
End of procedure
Power synchronization starts when connection is complete. Check that power synchronization performs normally.
Power synchronized unit#1
Power synchronized unit#0
Added ETERNUS DX/AF storage systems
Server#0UPS unit for Server#0
Server#1UPS unit for
Server#1
PWC#0 PWC#1 PWC#2 PWC#3
RS232C cables(optional)
RS232C cables(provided with a power synchronized unit)
ETERNUS DX/AF #4
PWC
ETERNUS DX/AF #5
PWC
ETERNUS DX/AF #6
PWC
ETERNUS DX/AF #7
PWC
ETERNUS DX/AF #0
ETERNUS DX/AF #1
ETERNUS DX/AF #2
ETERNUS DX/AF #3
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
67
6. Operation and Maintenance
This chapter describes maintenance and troubleshooting after starting system operation.
Checking the Power Synchronized Unit Status
Check the LEDs on the power synchronized unit regularly.
Device Replacement After Operation Startup
This section explains the procedure to replace devices after starting system operation.
• Replacing a Server
• Replacing a Power Synchronized Unit• Replacing an AC Sensor Unit
Replacing a Server
The following procedure provides an overview of the required work to replace a server, such as when a server fails.Refer to the relevant manuals for more details.
Procedure
1 Replace the server.
2 Perform the necessary settings for the replacement server.
3 Connect the replacement server to the server UPS unit.
End of procedure
After the procedure is complete, check that power synchronization performs normally if necessary.
CAUTIONDo
• Ask your maintenance engineer to replace devices.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
68
6. Operation and Maintenance Device Replacement After Operation Startup
Replacing a Power Synchronized Unit
The following procedure provides an overview of the required work to replace a power synchronized unit, such aswhen a power synchronized unit fails.
Procedure
1 Remove the RS232C cable from the power synchronized unit.For cascade connections, remove all the RS232C cables from the cascade destination (power synchronizedunit#1).
2 Remove the power cords (for AC sensor), the AC sensor port connection cables, and the cascade cables from the power synchronized unit.
3 Remove the power cord (for AC power input) from the power synchronized unit and turn off the power synchronized unit.
4 Remove the power synchronized unit from the rack.
5 Install the new power synchronized unit and connect the required cables.To connect the cables, perform the procedure for disconnecting cables in reverse. Connect the RS232Ccables last.
End of procedure
After completing cable connection, check that power synchronization performs normally if necessary.
Make sure to use the following procedure to replace a power synchronized unit.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
69
6. Operation and Maintenance Device Replacement After Operation Startup
Replacing an AC Sensor Unit
The following procedure provides an overview of the required work to replace an AC sensor unit, such as when anAC sensor unit fails.
Procedure
1 Remove the RS232C cable from the power synchronized unit.For cascade connections, remove all the RS232C cables from the cascade destination (power synchronizedunit#1).
2 Remove the AC sensor port connection cable from the AC sensor unit.
3 Remove the power cord (for AC sensor) from the AC sensor unit.
4 Remove the AC sensor unit from the rack.
5 Install the new AC sensor unit and connect the required cables.To connect the cables, perform the procedure for disconnecting cables in reverse. Connect the RS232Ccables last.
End of procedure
After completing cable connection, check that power synchronization performs normally if necessary.
Make sure to use the following procedure to replace an AC sensor unit.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
70
6. Operation and Maintenance Troubleshooting
Troubleshooting
If you notice anything unusual during operation such as the conditions listed below, refer to "Check List" (page71) to check the power synchronized unit status, accurately record the status on the form provided in "TroubleRecord" (page 73), and contact your maintenance engineer.
• Unusual phenomena occurs during operation of the power synchronized unit
• The power synchronized unit does not turn on• The ETERNUS DX/AF does not turn off with the power synchronized server• The ETERNUS DX/AF does not turn on with the power synchronized server
Check List
■ Unusual phenomena occurs during operation of the power synchronized unit
If any of the following conditions apply to the power synchronized unit, remove the power cords of the power syn-chronized unit and contact your maintenance engineer.
• Abnormally hot
• Unusual odor• Emission of smoke• Unusual noise• Abnormal shaking
■ The power synchronized unit does not turn on
Check the following points: If you still have trouble, leave the power synchronized unit as it is and contact your sales representative or main-tenance engineer.
• The power cord (for AC power input) is not correctly connected to the AC IN port.
• The CHECK LED is left on.The power synchronized unit must be replaced. Contact your sales representative or maintenance engineer.
Remove the power cord (for AC power input) that is connected to the AC IN port first, then remove the power cords (for AC sensor) that are connected to the ports of SENSOR#0 and SENSOR#1.
WARNINGUnplug
• If the power synchronized unit overheats, gives off smoke or an unusual odor, makes an unusual sound, or shakes abnormally, or is likely to be damaged by a power abnormality, immediately remove the power cords.After waiting a while, check that the unusual phenomena has disappeared, and then contact your sales representative or maintenance engineer.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
71
6. Operation and Maintenance Troubleshooting
■ The ETERNUS DX/AF does not turn off with the power synchronized server
Check the following points: If you still have trouble, leave the power synchronized unit as it is and contact your sales representative or main-tenance engineer.
• The power synchronized unit is not turned on.
• A CM or an SVC is in a failed state.
• The POWER LED and POWER SENSOR LED are on.
- Check the status for the SENSOR#0 port and SENSOR#1 port on the power synchronized unit and the status for the AC output of the server UPS unit to which the AC sensor unit is connected.The AC output of all the connected server UPS units needs to be off to turn off the ETERNUS DX/AF.
- Check the status for the SENSOR#0 port and SENSOR#1 port on the power synchronized unit and the status of the cable connection for the AC sensor unit.
- When the power synchronized units are cascaded, check the connection status of the cascade cables.
• The POWER LED is on and the POWER CONTROL LED is blinking.
- Check that the ETERNUS DX/AF is not being turned off.It may take time for the ETERNUS DX/AF to turn off. Wait for a while and check that the status of the LEDsdoes not change.
- When different power synchronized units are connected to CM#0 and CM#1, or SCV#0 and SVC#1 on the ETERNUS DX/AF, the ETERNUS DX/AF must be turned off by both power synchronized units.
- Check that power synchronization with the power synchronized unit is correctly set for the ETERNUS DX/AF.
■ The ETERNUS DX/AF does not turn on with the power synchronized server
• The power synchronized unit is not turned on.
• The POWER LED and POWER SENSOR LED are on.
- Check that power synchronization with the power synchronized unit is correctly set for the ETERNUS DX/AF.- Check the connection status of the RS232C cable that connects the power synchronized unit and the ETER-
NUS DX/AF.
• When the POWER LED is on.
- Check the status for the SENSOR#0 port and SENSOR#1 port on the power synchronized unit and the status for the AC output of the server UPS unit to which the AC sensor unit is connected.The AC output of at least one of the connected server UPS units need to be on to turn on the ETERNUS DX/AF.
- Check the status for the SENSOR#0 port and SENSOR#1 port on the power synchronized unit and the status of the cable connection for the AC sensor unit.
- When the power synchronized units are cascaded, check the connection status of the cascade cables.
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
72
6. Operation and Maintenance Troubleshooting
Trouble Record
If trouble occurs, record the power synchronized unit and AC sensor unit conditions in Figure 17, and contact yourmaintenance engineer.
Figure 17 Trouble record
Trouble Record1: Please identify your power synchronized unit: (Check the Manufacturer’s label) MODEL SER.NO.
2: Please enter the following information: No. of connected server UPS units Model names of connected server UPS units No. of connected AC sensor units No. of connected storage systems Is the power synchronized unit cascaded?
3: Check the state of the following LEDs on the power synchronized unit: POWER POWER SENSOR POWER CONTROL CHECK 4: Is the LED on the AC sensor unit on?
5: Other
(On, Off, Blinking)(On, Off)(On, Off, Blinking)(On, Off, Blinking)
(Yes, No)
(Yes, No)
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
73
FUJITSU Storage ETERNUS AF series, ETERNUS DX200F All-Flash Arrays,ETERNUS DX S5/S4/S3 series Hybrid Storage Systems,
ETERNUS DX60 S2/DX80 S2/DX90 S2 Disk Storage Systems
Configuration Guide (Power Synchronized Unit)
P3AM-8012-14ENZ0
Date of issuance: October 2019Issuance responsibility: FUJITSU LIMITED
• The content of this manual is subject to change without notice.
• This manual was prepared with the utmost attention to detail. However, Fujitsu shall assume no responsibility for any operational problems as the result of errors, omissions, or the use of information in this manual.
• Fujitsu assumes no liability for damages to third party copyrights or other rights arising from the use of any information in this manual.
• The content of this manual may not be reproduced or distributed in part or in its entirety without prior permission from Fujitsu.