Upload
nabaroon-goswami
View
21
Download
2
Embed Size (px)
Citation preview
SGI Earthing Design – A Concept Note
An earthing system basically provides a drain path to all kinds of faults that may develop
in an electrical system comprising of power circuits, control circuits, EMP and statics.
These faults may be caused by surges or transients from indirect lightning strikes, or
spikes, or harmonics, or faults emanating from within your own electrical system. The
nature of these faults is varied with respect to frequency, amplitude and time. Therefore,
the earthing system of any installation needs to be thoughtfully designed to handle all
such faults effectively.
Generally an earthing installation consists of an elaborate system of earth grid comprising
of earth rods or electrodes, tapes or strips, and pipes that are connected to the electrical
earth terminal. The entire grid acts as a carrier of such faults. However, the grid by itself
is not capable of discharging theses fault currents into the ground. It is the electrical
resistance property of the surrounding ground that helps to absorb and dissipate the fault
currents from the carrier grid it to the earth mass. Hence, while designing an earth grid,
one should consider the following points in great detail.
1. The grid should be capable of conducting such fault currents for a given time
duration taking current density absorption capacity for continuous and
instantaneous duty of the soil.
2. The neighboring groundmass should be capable of absorbing such fault currents
and dissipating it to the larger earth mass taking dangerous potentials developed,
into consideration.
IEEE 80-2000, IEEE 665, IEEE 142, IEEE 81-993, BS 7430, IS 3043 are the standards
which provide detailed procedures for designing such a grid.
If the soil resistivity is high, the penetration of the charges into the earth mass would be
poor. The concentration of charges in the vicinity of the earth grid will thus be high and
create high voltage. Further, in a high resistive soil, the concentration of charges dips
steeply as you move away from the earth grid. This results in a steep drop in voltage. The
presence of high voltage in the vicinity of the grid & its neighboring areas is a matter of
concern and a serious hazard to the safety of human life and livestock. Therefore, while
designing the earth grid and its various components, we need to be cautious of the
following parameters:
Step Voltage: It is the difference in voltage between the right & the left foot
when a person is standing in the vicinity of the grid.
Touch Voltage: It is the difference in voltage between the point at which a man
stands & the object he touches, which is connected to the grid.
Mesh Voltage: Maximum touch voltage within a mesh of a ground grid.
Grid Potential Rise: The maximum potential a grid may attain relative to a
distant grounding point, which is at the potential of the remote earth.
Human heart fibrillates if more than 0.116 ampere current flows through it. Thus any
earth grid should necessarily have the following parameters.
The earth grid should have the minimum cross section to carry the maximum fault
current for particular time duration without fusing.
The superficial area of the conductor in touch with the soil should be more than
continuous or instantaneous duty ratings based on soil resistivity and time of
clearance of fault.
The actual step potential should be lower than the allowable step potential.
The actual mesh potential should be lower than the allowable touch potential.
The grid potential rise should be as low as design permits.
It is also observed that lower soil resistivity reduces the earth grid size. The grid thus
becomes more compact and economical. In situations where soil resistivity is high, or in
installations where the grid resistance is desired to be very low, it is always desirable to
treat the soil with artificial treatment compounds in order to bring down the soil
resistivity.
Correction of Old Earth Grid :
In an old live substation , it is not possible to take a shutdown for days and relay the earth
grid. This old earth grid can be enhanced by creating a peripheral grid of the desired
length around the existing grid. The length of the conductor required , should be
calculated as per IEEE 80 2000. The total conductor required should be arranged in
multiple tiers such that desired length as per IEEE 80 2000 is achieved. The multi tier
conductors have to be linked to each other at a distance of 20 mtrs. The parallel length of
conductors should be minimum 1-metre apart. The parallel conductor rings should be
alternately treated with artificial compounds (TEREC+ & Earthcon combination) as per
clause 14.5.d , IEEE 80 2000 to achieve permanency of the earthing system. This
ingenious and modern way of peripheral grid correction is termed as Tier-earth. The
design is tailor made for each soil type and has to be handled by authorized agency.
As ELV systems in sub stations is prone to GPR (Grid Potential Rise) at time of fault and
it is impossible to develop a full proof surge protection system through existing power ,
data, control lines ,it is advisable to create a separate electronic earth at a distance from
the tier earth in accordance to IEEE 142. An earthing system with minimum reflection
factor in which the fault current travels progressively into soils of higher resistivity has to
be created such that the resistance of SIGMA Earth is below 0.5 ohms. The calculation
of SIGMA Earth depends on volume dissipation of earth using plate conductor of micro-
ohm meter, TEREC+ of < 0.12 ohm meter, earthcon of <2.5 ohm meter, soil < 25 ohm
meter and virgin surrounding soil. The design is tailor made for each soil type and has to
be handled by authorized agency. The usage of these patented products ensures quicker
transfer of fault current to surrounding soil within a given time.
Modern concepts of New Earth Grid design:
A new earth grid has the flexibility to be designed with Terec+ to achieve permanency.
The substation earth grid design has to be as per IEEE 80 2000 with desired spacing such
that the application of permanent artificial treatment (Terec+) as per clause 14.5.d gives
the desired reduction in soil resistivity. The choice of combination of artificial compound
has to be advised by a specialist. The earth grid for body and lightning can be connected
to each other using an earth coil.
The electronic earth needs to be separate as thousands of control, data and power cables
cannot be practically fitted with SPDs. The electronic earth has to be separate from main
earth pit as per IEEE 142. An earthing system with minimum reflection factor in which
the fault current travels progressively into soils of higher resistivity has to be created such
that the resistance of SIGMA Earth is below 0.5 ohms. The calculation of SIGMA Earth
depends on volume dissipation of earth using plate conductor of micro-ohm meter,
TEREC+ of < 0.12 ohm meter, earthcon of <2.5 ohm meter, soil < 25 ohm meter and
virgin surrounding soil. The design is tailor made for each soil type and has to be handled
by authorized agency.
Advantages of modern concepts of earth grid :
1. There is a limited choice in terms of grid location, usually in un-fertile/
wastelands wherein there maybe pockets of high resistance underground and
inadequate land mass available for construction.
2. Usage of micro-chip and control cards necessitates more careful handling of
earthing for modern transformers and control panels.
3. In case of a new grid the adoption of new technology is simple for design and
installation compared to old grid.
4. The practical issues in proper installation of salt& charcoal /watering both during
construction and also in periodic maintenance are removed. The issues of proper
compaction, uniform dispersion and water retention are a significant improvement
over conventional techniques used over the years.
5. The grid resistance of every point in the grid and earth pits attached to the grid is
identical
6. The actual step potential and touch potential across the grid is constant due to
identical resistivity of the artificial treatment compound around the conductor.
7. GPR, actual step potential , actual touch potential are below permissible limits.
8. The grid resistance and dangerous potentials calculated at the time of design will
remain constant permanently even with varying moisture conditions in the infinite
earth mass.
9. The SIGMA earth provides a constant resistance to the protection devices and a
prefect reference earth to the control system permanently
10. New grids will require comparatively lesser investments and ROI will be far
sooner and the best in class.