Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Part I General information on the block library EXTENDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Chapter 1 Parameterizing functions and function blocks . . . . . . . . . . . . 15Parameterizing functions and function blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Part II EFB-descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Chapter 2 AVE_***: Averaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Chapter 3 AVGMV: Floating mean with fixed window size . . . . . . . . . . .27Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Detailed description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Runtime error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Chapter 4 AVGMV_K: Floating mean with frozen correction factor . . . .33Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Detailed description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

3

Page 4: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Chapter 5 BCD_TO_INT: Conversion from 16 Bit BCD to INT. . . . . . . . . 37Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Chapter 6 BIT_TO_BYTE: Type conversion . . . . . . . . . . . . . . . . . . . . . . . 39Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Chapter 7 BIT_TO_WORD: Type conversion . . . . . . . . . . . . . . . . . . . . . . 43Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Chapter 8 BYTE_AS_WORD: Type conversion . . . . . . . . . . . . . . . . . . . . 47Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Chapter 9 BYTE_TO_BIT: Type conversion . . . . . . . . . . . . . . . . . . . . . . . 49Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

Chapter 10 CTD_***: Down counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Chapter 11 CTU_***: Up counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Chapter 12 CTUD_***: Up/Down counter . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

Chapter 13 DBCD_TO_DINT: Conversion from 32 Bit BCD to DINT . . . . . 59Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

4

Page 5: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Chapter 14 DBCD_TO_INT: Conversion from 32 Bit BCD to INT. . . . . . . .61Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

Chapter 15 DEAD_ZONE_REAL: Dead zone . . . . . . . . . . . . . . . . . . . . . . . .63Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64Detailed description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

Chapter 16 DINT_AS_WORD: Type conversion . . . . . . . . . . . . . . . . . . . . . 67Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Chapter 17 DINT_TO_DBCD: Conversion from DINT to 32 Bit BCD . . . . .69Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

Chapter 18 DIVMOD_***: Division and Modulo . . . . . . . . . . . . . . . . . . . . . .71Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72Runtime error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Chapter 19 HYST_***: Indicator signal for maximum value delimiter with hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74Detailed Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

Chapter 20 INDLIM_***: Indicator signal for delimiters with hysteresis . .77Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78Detailed description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

Chapter 21 INT_TO_BCD: Conversion from INT to 16 Bit BCD . . . . . . . . .81Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

5

Page 6: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Chapter 22 INT_TO_DBCD: Conversion from INT to 32 Bit BCD . . . . . . . 83Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

Chapter 23 LIMIT_IND_***: Limit with indicator . . . . . . . . . . . . . . . . . . . . . 85Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

Chapter 24 LOOKUP_TABLE1: Traverse progression with 1st degree interpolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90Detailed description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

Chapter 25 NEG_***: Negation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94Runtime error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

Chapter 26 REAL_AS_WORD: Type conversion . . . . . . . . . . . . . . . . . . . . 97Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

Chapter 27 SAH: Detecting and holding with rising edge . . . . . . . . . . . . . 99Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Chapter 28 SIGN_***: Sign evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

Chapter 29 TIME_AS_WORD: Type conversion . . . . . . . . . . . . . . . . . . . . 105Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

6

Page 7: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Chapter 30 TOF_P: Off Delay with Pause . . . . . . . . . . . . . . . . . . . . . . . . .107Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109Detailed description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

Chapter 31 TON_P: On Delay with Pause . . . . . . . . . . . . . . . . . . . . . . . . .111Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113Detailed description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

Chapter 32 TRIGGER: Detection of all types of edges . . . . . . . . . . . . . . . 117Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118

Chapter 33 UDINT_AS_WORD: Type conversion . . . . . . . . . . . . . . . . . . .119Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

Chapter 34 WORD_AS_BYTE: Type conversion . . . . . . . . . . . . . . . . . . . .121Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

Chapter 35 WORD_AS_DINT: Type conversion . . . . . . . . . . . . . . . . . . . . 123Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

Chapter 36 WORD_AS_REAL: Type conversion. . . . . . . . . . . . . . . . . . . .125Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126

Chapter 37 WORD_AS_TIME: Type conversion . . . . . . . . . . . . . . . . . . . . 127Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128

Chapter 38 WORD_AS_UDINT: Type conversion . . . . . . . . . . . . . . . . . . .129Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129Brief description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130

7

Page 8: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Chapter 39 WORD_TO_BIT: Type conversion . . . . . . . . . . . . . . . . . . . . . 131Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131Brief description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132Representation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159

8

Page 9: Concept 2.6 IEC Block Library Part ... - Schneider Electric

§

Safety Information

Important Information

NOTICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of this symbol to a Danger or Warning safety label indicatesthat an electrical hazard exists, which will result in personal injury if theinstructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personalinjury hazards. Obey all safety messages that follow this symbol to avoidpossible injury or death.

DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.

DANGER

WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.

WARNING

CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.

CAUTION

33002214 9

Page 10: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Safety Information

PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

© 2007 Schneider Electric. All Rights Reserved.

10 33002214

Page 11: Concept 2.6 IEC Block Library Part ... - Schneider Electric

About the Book

At a Glance

Document Scope This documentation is designed to help with the configuration of functions and function blocks.

Validity Note This documentation applies to Concept 2.6 under Microsoft Windows 98, Microsoft Windows 2000, Microsoft Windows XP and Microsoft Windows NT 4.x.

Related Documents

You can download these technical publications and other technical information from our website at www.telemecanique.com

User Comments We welcome your comments about this document. You can reach us by e-mail at [email protected]

Note: There is additional up to date tips in the README data file in Concept.

Title of Documentation Reference Number

Concept Installation Instructions 840 USE 502 00

Concept User Manual 840 USE 503 00

Concept EFB User Manual 840 USE 505 00

Concept LL984 Block Library 840 USE 506 00

33002214 11

Page 12: Concept 2.6 IEC Block Library Part ... - Schneider Electric

About the Book

12 33002214

Page 13: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

I

General information on the block library EXTENDED

Overview

Introduction This section contains general information on the block library EXTENDED.

What's in this Part?

This part contains the following chapters:

Chapter Chapter Name Page

1 Parameterizing functions and function blocks 15

13

Page 14: Concept 2.6 IEC Block Library Part ... - Schneider Electric

General information

14 33002214

Page 15: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

1

Parameterizing functions and function blocks

15

Page 16: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Parameterization

Parameterizing functions and function blocks

General Each FFB consists of an operation, the operands needed for the operation and an instance name or function counter.

Operation The operation determines which function is to be executed with the FFB, e.g. shift register, conversion operations.

Operand The operand specifies what the operation is to be executed with. With FFBs, this consists of formal and actual parameters.

FFB(e.g. ON-delay)

Item name/Function counter(e.g. FBI_2_22 (18))

Operation(e.g. TON)

Operand

Actual parameterVariable, element of a

multi-element variable, literal, direct

address(e.g. ENABLE, EXP.1, TIME, ERROR, OUT,

%4:0001)

Formal parameter

(e.g. IN,PT,Q,ET)

TON

ENABLE

EXP.1

TIME

EN

IN

PT

ENO

Q

ET

ERROR

OUT

%4:00001

FBI_2_22 (18)

16 33002214

Page 17: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Parameterization

Formal/actual parameters

The formal parameter holds the place for an operand. During parameterization, an actual parameter is assigned to the formal parameter.

The actual parameter can be a variable, a multi-element variable, an element of a multi-element variable, a literal or a direct address.

Conditional/ unconditional calls

"Unconditional" or "conditional" calls are possible with each FFB. The condition is realized by pre-linking the input EN.� Displayed EN

conditional calls (the FFB is only processed if EN = 1)� EN not displayed

unconditional calls (FFB is always processed)

Calling functions and function blocks in IL and ST

Information on calling functions and function blocks in IL (Instruction List) and ST (Structured Text) can be found in the relevant chapters of the user manual.

Note: If the EN input is not parameterized, it must be disabled. Any input pin that is not parameterized is automatically assigned a "0" value. Therefore, the FFB should never be processed.

Note: For disabled function blocks (EN = 0) with an internal time function (e.g. DELAY), time seems to keep running, since it is calculated with the help of a system clock and is therefore independent of the program cycle and the release of the block.

33002214 17

Page 18: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Parameterization

18 33002214

Page 19: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

II

EFB-descriptions

Overview

Introduction These EFB descriptions are documented in alphabetical order.

Note: The number of inputs of the EFBs can be increased to a maximum of 32 by changing the size of the FFB symbols vertically. Please consult the individual EFB descriptions to know which EFBs are concerned.

19

Page 20: Concept 2.6 IEC Block Library Part ... - Schneider Electric

EFB-descriptions

What's in this Part?

This part contains the following chapters:

Chapter Chapter Name Page

2 AVE_***: Averaging 23

3 AVGMV: Floating mean with fixed window size 27

4 AVGMV_K: Floating mean with frozen correction factor 33

5 BCD_TO_INT: Conversion from 16 Bit BCD to INT 37

6 BIT_TO_BYTE: Type conversion 39

7 BIT_TO_WORD: Type conversion 43

8 BYTE_AS_WORD: Type conversion 47

9 BYTE_TO_BIT: Type conversion 49

10 CTD_***: Down counter 51

11 CTU_***: Up counter 53

12 CTUD_***: Up/Down counter 55

13 DBCD_TO_DINT: Conversion from 32 Bit BCD to DINT 59

14 DBCD_TO_INT: Conversion from 32 Bit BCD to INT 61

15 DEAD_ZONE_REAL: Dead zone 63

16 DINT_AS_WORD: Type conversion 67

17 DINT_TO_DBCD: Conversion from DINT to 32 Bit BCD 69

18 DIVMOD_***: Division and Modulo 71

19 HYST_***: Indicator signal for maximum value delimiter with hysteresis

73

20 INDLIM_***: Indicator signal for delimiters with hysteresis 77

21 INT_TO_BCD: Conversion from INT to 16 Bit BCD 81

22 INT_TO_DBCD: Conversion from INT to 32 Bit BCD 83

23 LIMIT_IND_***: Limit with indicator 85

24 LOOKUP_TABLE1: Traverse progression with 1st degree interpolation

89

25 NEG_***: Negation 93

26 REAL_AS_WORD: Type conversion 97

27 SAH: Detecting and holding with rising edge 99

28 SIGN_***: Sign evaluation 101

29 TIME_AS_WORD: Type conversion 105

30 TOF_P: Off Delay with Pause 107

31 TON_P: On Delay with Pause 111

32 TRIGGER: Detection of all types of edges 117

33 UDINT_AS_WORD: Type conversion 119

20 33002214

Page 21: Concept 2.6 IEC Block Library Part ... - Schneider Electric

EFB-descriptions

34 WORD_AS_BYTE: Type conversion 121

35 WORD_AS_DINT: Type conversion 123

36 WORD_AS_REAL: Type conversion 125

37 WORD_AS_TIME: Type conversion 127

38 WORD_AS_UDINT: Type conversion 129

39 WORD_TO_BIT: Type conversion 131

Chapter Chapter Name Page

33002214 21

Page 22: Concept 2.6 IEC Block Library Part ... - Schneider Electric

EFB-descriptions

22 33002214

Page 23: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

2

AVE_***: Averaging

Overview

Introduction This chapter describes the AVE_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 24

Representation 25

23

Page 24: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVE_***: Averaging

Brief description

Function description

The Function calculates the mean of weighted input values, and the result is then given at the output.

Each two successive inputs (K_Xn) represent one pair of values. The first K_Xn input corresponds to K1, the next to X1, the one after that to K2, etc.

The number of K_Xn inputs can be increased to 32 by vertically modifying the size of the block frame. This corresponds to a maximum of 16 value pairs.

The number of inputs must be even.

Data types of the ANY_NUM group can be processed.

The data types of all input and output values must be identical. A specific function is available to process each of the different data types.

It is possible to project EN and ENO as additional parameters.

24 33002214

Page 25: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVE_***: Averaging

Representation

Symbol Block representation:

Formula Block formula:

Parameter description

Block parameter description:

AVE_***

***K_X1***K_X2***::K_Xn***K_Xm***

*** = INT, DINT, UINT, UDINT, REAL

OUTΣ Ki Xi×( )

Σ Ki( )---------------------------=

Parameters Data type Meaning

K_X1 INT, DINT, UINT, UDINT, REAL

Factor (K1) for first value

K_X2 INT, DINT, UINT, UDINT, REAL

First value (X1)

K_X3 INT, DINT, UINT, UDINT, REAL

Factor (K2) for second value

K_X4 INT, DINT, UINT, UDINT, REAL

Second value (X2)

:

K_Xn INT, DINT, UINT, UDINT, REAL

Factor (Km/2) for m/2 value

K_Xm INT, DINT, UINT, UDINT, REAL

m/2 value (Xm/2)

OUT INT, DINT, UINT, UDINT, REAL

Mean value

33002214 25

Page 26: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVE_***: Averaging

26 33002214

Page 27: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

3

AVGMV: Floating mean with fixed window size

Overview

Introduction This chapter describes the AVGMV block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 28

Representation 29

Detailed description 31

Runtime error 32

27

Page 28: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVGMV: Floating mean with fixed window size

Brief description

Function description

The function block forms a floating mean from a fixed number of input values (Input X). The output is the mean of all values between the current X value and the oldest X-value (N-1). It is possible to save up to 100 input values (N).

The function block can operate in manual and automatic mode.

It is possible to project EN and ENO as additional parameters.

28 33002214

Page 29: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVGMV: Floating mean with fixed window size

Representation

Symbol Block representation:

Formula With RDY = 1:

or

Explanation of variables

AVGMV

REALY

BOOLRDY

MANBOOLXREALNINT

YMANREAL

Variable Meaning

Y (new) Y value in current program cycle

Y (old) Y value from last program cycle

N Window size (number of values in buffer)

X(N-1) oldest X value in buffer

Y new( )

Xi

i 0=

N 1–

N-----------------=

Y new( ) Y old( )XN----

X N 1–( )N

----------------------–+=

33002214 29

Page 30: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVGMV: Floating mean with fixed window size

Parameter description

Block parameter description:

Parameter Data type Meaning

MAN BOOL "0" = automatic operating mode"1" = manual operating mode

X REAL Input

N INT Window size (number of input values that are loaded into the buffer; 100 max.)

YMAN REAL Manual value

Y REAL Mean value

RDY BOOL "1" = n values in buffer, i.e. buffer ready "0" = buffer not ready

30 33002214

Page 31: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVGMV: Floating mean with fixed window size

Detailed description

Automatic operating mode

In N program cycles, N X-values are read into an internal buffer. The arithmetic mean of these values is calculated, and is delivered at the Y output. From the N+1 program cycle onwards, the oldest X-value in the buffer is deleted and replaced with the current x-value.

After a modification of the N value or after a cold/warm start, the internal buffer is deleted. The output is set to the input value X and RDY to "0". The buffer is filled during the next N cycles. The Y output contains an mean of the values accumulated so far. RDY remains "0" until the buffer is filled with correct X values after N program cycles then RDY becomes "1".

Manual operating mode

The value YMAN is transferred to the Y output. The buffer is completely filled with the value YMAN and marked as full (RDY = 1).

Diagram Floating mean with limited memory of N = 50 values

Note: As long as RDY = 0, the mean is not derived from N values but from the current updated read-in number (n < N).

RDY

0

0

1

X

Y

33002214 31

Page 32: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVGMV: Floating mean with fixed window size

Runtime error

Runtime error An Error message appears if,� N = 0 or N>100

32 33002214

Page 33: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

4

AVGMV_K: Floating mean with frozen correction factor

Overview

Introduction This chapter describes the AVGMV_K block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 34

Representation 34

Detailed description 35

33

Page 34: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVGMV_K: Floating mean with frozen correction factor

Brief description

Function description

The function block establishes a floating mean (with frozen correction factor) of up to 10 000 input values.

The function block can operate in manual and automatic mode.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Formula Block formula:

Explanation of variables

Parameter description

Block parameter description:

AVGMV_K

REALY

MANBOOLXREALKINTYMANREAL

Variable Meaning

Y (new) Y value in current program cycle

Y (old) Y value from last program cycle

K Correction factor

X X value in current program cycle

Y new( ) Y old( )X Y old( )–

K----------------------------+=

Parameter Data type Meaning

MAN BOOL "0" = Automatic Mode; "1" = Manual Mode

X REAL Input

K INT Correction factor (max. 10 000)

YMAN REAL Manual value

Y REAL Mean value

34 33002214

Page 35: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVGMV_K: Floating mean with frozen correction factor

Detailed description

Automatic operating mode

One X value is read in every program cycle. 1/N is deducted from the Y value of the last program cycle, and then 1/N of the current X value is added. The result is delivered at the Y output.

After a cold or warm (re)start, the X value is assigned to output Y.

Manual operating mode

The value YMAN is transferred to the Y output.

Diagram Floating mean with frozen correction factor (K = 50)

0

X

Y

33002214 35

Page 36: Concept 2.6 IEC Block Library Part ... - Schneider Electric

AVGMV_K: Floating mean with frozen correction factor

36 33002214

Page 37: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

5

BCD_TO_INT: Conversion from 16 Bit BCD to INT

Overview

Introduction This chapter describes the BCD_TO_INT block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 38

Representation 38

37

Page 38: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Conversion from 16 Bit BCD to INT

Brief description

Function description

This function converts a 16 Bit BCD input value (8-4-2-1-Code) into an INT data type output value.

If no valid BCD coded value is created at input, a runtime error is reported and the input value passes unchanged to the output.

EN and ENO can be configured as additional parameters.

Example Example of a BCD -> INT conversion

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Data type Dec. value Hex. value (= BCD-value)

Input value INT -26 797 9753

Output value INT 9 753 -

BCD_TO_INT

INTVALUEINT BCD_VAL

Parameter Data type Meaning

BCD_VAL INT 16 Bit BCD input value

VALUE INT INT output value

38 33002214

Page 39: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

6

BIT_TO_BYTE: Type conversion

Overview

Introduction This chapter describes the BIT_TO_BYTE block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 40

Representation 41

39

Page 40: Concept 2.6 IEC Block Library Part ... - Schneider Electric

BIT_TO_BYTE: Type conversion

Brief description

Function description

The Function converts 8 input values of the Data type BOOL to an output of the data type BYTE.

The input values are assigned to the individual bits of the byte at the output according to the input names.

It is possible to project EN and ENO as additional parameters.

BIT0 (2 )

BIT7 (2 )

0

7

BIT1 (2 )1

BIT6 (2 )6

27 21 2026

BYTE

40 33002214

Page 41: Concept 2.6 IEC Block Library Part ... - Schneider Electric

BIT_TO_BYTE: Type conversion

Representation

Symbol Block representation:

Formula Block formula:

Parameter description

Block parameter description:

BIT_TO_BYTE

BYTEBIT0BOOLBIT1BOOLBIT2BOOLBIT3BOOLBIT4BOOLBIT5BOOLBIT6BOOLBIT7BOOL

OUT BIT7 BIT6 … BIT0,,,{ }=

Parameter Data type Meaning

BIT0 BOOL Input bit 0

BIT1 BOOL Input bit 1

: : :

BIT7 BOOL Input bit 7

OUT BYTE Output value

33002214 41

Page 42: Concept 2.6 IEC Block Library Part ... - Schneider Electric

BIT_TO_BYTE: Type conversion

42 33002214

Page 43: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

7

BIT_TO_WORD: Type conversion

Overview

Introduction This chapter describes the BIT_TO_WORD block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 44

Representation 45

43

Page 44: Concept 2.6 IEC Block Library Part ... - Schneider Electric

BIT_TO_WORD: Type conversion

Brief description

Function description

The Function converts 16 input words from Data type BOOL to an output value of data type WORD.

The input values are assigned to the individual bits of the word at the output according to the input names.

It is possible to project EN and ENO as additional parameters.

BIT0 (2 )

BIT15 (2 )

0

15

BIT1 (2 )1

BIT14 (2 )14

215 21 20214

WORD

44 33002214

Page 45: Concept 2.6 IEC Block Library Part ... - Schneider Electric

BIT_TO_WORD: Type conversion

Representation

Symbol Block representation:

Formula Block formula:

Parameter description

Block parameter description:

BIT_TO_WORD

WORDDATABIT0BOOLBIT1BOOL

BIT2BOOLBIT3BOOLBIT4BOOLBIT5BOOLBIT6BOOLBIT7BOOLBIT8BOOLBIT9BOOLBIT10BOOLBIT11BOOLBIT12BOOLBIT13BOOLBIT14BOOLBIT15BOOL

OUT BIT15 BIT14 … BIT0,,,{ }=

Parameter Data type Meaning

BIT0 BOOL Input bit 0

BIT1 BOOL Input bit 1

: : :

BIT15 BOOL Input bit 15

OUT WORD Output value

33002214 45

Page 46: Concept 2.6 IEC Block Library Part ... - Schneider Electric

BIT_TO_WORD: Type conversion

46 33002214

Page 47: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

8

BYTE_AS_WORD: Type conversion

Overview

Introduction This chapter describes the BYTE_AS_WORD block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 48

Representation 48

47

Page 48: Concept 2.6 IEC Block Library Part ... - Schneider Electric

BYTE_AS_WORD: Type conversion

Brief description

Function description

The Function converts 2 input words from Data type BYTE to an output value of data type WORD.

The input values are assigned to the word at the output according to the input names.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Formula Block formula:

Parameter description

Block parameter description:

BYTE_AS_WORD

WORDDATALOWBYTE

HIGHBYTE

OUT = {HIGH, LOW}

Parameter Data type Meaning

LOW BYTE less significant byte

HIGH BYTE more significant byte

OUT WORD Output value

48 33002214

Page 49: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

9

BYTE_TO_BIT: Type conversion

Overview

Introduction This chapter describes the BYTE_TO_BIT block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 50

Representation 50

49

Page 50: Concept 2.6 IEC Block Library Part ... - Schneider Electric

BYTE_TO_BIT: Type conversion

Brief description

Function description

Thisfunction block converts one input word from Data type BYTE into 8 output values of data type BOOL.

The individual bits of the byte at the input are assigned to the outputs according to the output names.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

BIT0 (2 )

BIT7 (2 )

0

7

BIT1 (2 )1

BIT6 (2 )6

27 2 1 2 026

BYTE

BYTE_TO_BIT

BOOLBIT0

BOOLBIT1

BOOLBIT2

BOOLBIT3

BOOLBIT4

BOOLBIT5

BOOLBIT6

BOOLBIT7

INBYTE

Parameter Data type Meaning

IN BYTE Input

BIT0 BOOL Output bit 0

BIT1 BOOL Output bit 1

: : :

BIT7 BOOL Output bit 7

50 33002214

Page 51: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

10

CTD_***: Down counter

Overview

Introduction This chapter describes the CTD_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 52

Representation 52

51

Page 52: Concept 2.6 IEC Block Library Part ... - Schneider Electric

CTD_***: Down counter

Brief description

Function description

The Function block is used for counting down.

A "1" signal at the LD input causes the value of the PV input to be allocated to the CV output. With each transition from "0" to "1" at the CD input, the value of CV is reduced by 1.

When CV is ≤ 0, the output Q becomes "1".

The Data types of the PV input and the CV output must be identical. A specific function block is available to process each of the different data types.

The parameters EN and ENO can additionally be projected.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Note: The counter only works up to the minimum values of the data type being used. No overflow occurs.

CTD_***

BOOLQ

***CV

CDBOOLLDBOOLPV*** *** = INT, DINT, UINT, UDINT

Parameter Data type Meaning

CD BOOL Trigger input

LD BOOL Load data

PV INT, DINT, UINT, UDINT

Presettings value

Q BOOL Output

CV INT, DINT, UINT, UDINT

Count value (actual value)

52 33002214

Page 53: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

11

CTU_***: Up counter

Overview

Introduction This chapter describes the CTU_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 54

Representation 54

53

Page 54: Concept 2.6 IEC Block Library Part ... - Schneider Electric

CTU_***: Up counter

Brief description

Function description

The Function block is used for counting up.

A "1" signal at the R input causes the value "0" to be allocated to the CV output. With each transition from "0" to "1" at the CU input, the value of CV is increased by 1. When CV ≥ PV, the Q output is set to "1".

The Data types of the PV input and the CV output must be identical. A specific function block is available to process each of the different data types.

The parameters EN and ENO can additionally be projected.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Note: The counter only works up to the maximum values of the data type being used. No overflow occurs.

CTU_***

BOOLQ

***CV

CUBOOL

RBOOLPV*** *** = INT, DINT, UINT, UDINT

Parameter Data type Meaning

CU BOOL Trigger input

R BOOL Reset

PV INT, DINT, UINT, UDINT

Presettings value

Q BOOL Output

CV INT, DINT, UINT, UDINT

Count value (actual value)

54 33002214

Page 55: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

12

CTUD_***: Up/Down counter

Overview

Introduction This chapter describes the CTUD_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 56

Representation 57

55

Page 56: Concept 2.6 IEC Block Library Part ... - Schneider Electric

CTUD_***: Up/Down counter

Brief description

Function description

The Function block is used for counting up and down.

A "1" signal at the R input causes the value "0" to be allocated to the CV output. A "1" signal at the LD input causes the value of the PV input to be allocated to the CV output. With each transition from "0" to "1" at the CU input, the value of CV is increased by 1. With each transition from "0" to "1" at the CD input, the value of CV is reduced by 1.

If there is a simultaneous "1" signal at input R and input LD, input R has precedence.

When CV ≥ PV, output QU is "1".

When CV is ≤ 0, output QD is "1".

The Data types of input PV and input CV must be identical. A specific Function block is available to process each of the different data types.

The parameters EN and ENO can additionally be projected.

Note: The down counter only works up to the minimum values of the data type being used, and the up counter only up to the maximum values of the data type being used. No overflow occurs.

56 33002214

Page 57: Concept 2.6 IEC Block Library Part ... - Schneider Electric

CTUD_***: Up/Down counter

Representation

Symbol Block representation:

Parameter description

Block parameter description:

CTUD_***

BOOLQU

BOOLQD

***CV

CUBOOLCDBOOLRBOOL

LDBOOLPV*** *** = INT, DINT, UINT, UDINT

Parameter Data type Meaning

CU BOOL Up counter trigger input

CD BOOL Down counter trigger input

R BOOL Reset

LD BOOL Load data

PV INT, DINT, UINT, UDINT

Presettings value

QU BOOL Up display

QD BOOL Down display

CV INT, DINT, UINT, UDINT

Count value (actual value)

33002214 57

Page 58: Concept 2.6 IEC Block Library Part ... - Schneider Electric

CTUD_***: Up/Down counter

58 33002214

Page 59: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

13

DBCD_TO_DINT: Conversion from 32 Bit BCD to DINT

Overview

Introduction This chapter describes the DBCD_TO_DINT block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 60

Representation 60

59

Page 60: Concept 2.6 IEC Block Library Part ... - Schneider Electric

DBCD_TO_DINT: Conversion from 32 Bit BCD to DINT

Brief description

Function description

This function converts a 32 Bit BCD input value (8-4-2-1-Code) into a DINT data type output value.

If no valid BCD coded value is created at input, a runtime error is reported and the input value passes unchanged to the output.

EN and ENO can be configured as additional parameters.

Example Example of a DBCD -> DINT conversion

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Data type Dec. value Hex. value (= BCD-value)

Input value DINT -2 023 406 815 8765 4321

Output value DINT 87 654 321 -

DBCD_TO_DINT

DINTVALUEDINT BCD_VAL

Parameter Data type Meaning

BCD_VAL DINT 32 Bit BCD input value

VALUE DINT DINT output value

60 33002214

Page 61: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

14

DBCD_TO_INT: Conversion from 32 Bit BCD to INT

Overview

Introduction This chapter describes the DBCD_TO_INT block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 62

Representation 62

61

Page 62: Concept 2.6 IEC Block Library Part ... - Schneider Electric

DBCD_TO_INT: Conversion from 32 Bit BCD to INT

Brief description

Function description

This function converts a 32 Bit BCD input value (8-4-2-1-Code) into an INT data type output value.

The valid input value range is 0 32 767 (BCD.).

The following runtime errors are generated:� If no valid BCD coded value is created at input, a runtime error is reported and

the input value passes unchanged to the output.� If the BCD format is correct, but too large (> 32 767) a runtime error is reported

and the output value is set to -1.

EN and ENO can be configured as additional parameters.

Example Example of a DBCD -> INT conversion

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Data type Dec. value Hex. value (= BCD-value)

Input value DINT 22 083 0000 5643

Output value INT 5 643 -

DBCD_TO_INT

INTVALUEDINT BCD_VAL

Parameter Data type Meaning

BCD_VAL DINT 32 Bit BCD input value (valid value range 0 - 32767)

VALUE INT INT output value

62 33002214

Page 63: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

15

DEAD_ZONE_REAL: Dead zone

Overview

Introduction This chapter describes the DEAD_ZONE_REAL block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 64

Representation 64

Detailed description 65

63

Page 64: Concept 2.6 IEC Block Library Part ... - Schneider Electric

DEAD_ZONE_REAL: Dead zone

Brief description

Function description

The Function is used to specify a deadzone for control variables.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Formula Block formula:

Assuming: DZ≥0

Y = GAIN x X for -DZ ≤ X ≤ DZ

Y = (X - DZ) + GAIN x DZ for X > DZ

Y = (X + DZ) - GAIN x DZ for X < DZ

Parameter description

Block parameter description:

DEAD_ZONE_REAL

REALXREAL

DZREALGAINREAL

Parameter Data type Meaning

X REAL Input variable

DZ REAL Half width of the deadzone

GAIN REAL Gradient within deadzone

Y REAL Output variable

64 33002214

Page 65: Concept 2.6 IEC Block Library Part ... - Schneider Electric

DEAD_ZONE_REAL: Dead zone

Detailed description

Characteristic Curves

The function block has the following characteristic curve:

Deadzone with 0 < GAIN < 1

Deadzone with GAIN > 1

GAIN

X

Y

DZ

-DZ

GAIN

X

Y

DZ

-DZ

33002214 65

Page 66: Concept 2.6 IEC Block Library Part ... - Schneider Electric

DEAD_ZONE_REAL: Dead zone

Deadzone with GAIN < 0

Note: Outside the dead zone, a gradient of 1 has been specified.

GAIN

X

Y

DZ

-DZ

66 33002214

Page 67: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

16

DINT_AS_WORD: Type conversion

Overview

Introduction This chapter describes the DINT_AS_WORD block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 68

Representation 68

67

Page 68: Concept 2.6 IEC Block Library Part ... - Schneider Electric

DINT_AS_WORD: Type conversion

Brief description

Function description

This function block converts one input value of Data type DINT to 2 output values of data type WORD.

The individual words of the DINT input are assigned to the outputs corresponding to the output names.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

DINT_AS_WORD

WORDLOW

WORDHIGH

INDINT

Parameter Data type Meaning

IN DINT Input

LOW WORD less significant word

HIGH WORD more significant word

68 33002214

Page 69: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

17

DINT_TO_DBCD: Conversion from DINT to 32 Bit BCD

Overview

Introduction This chapter describes the DINT_TO_DBCD block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 70

Representation 70

69

Page 70: Concept 2.6 IEC Block Library Part ... - Schneider Electric

DINT_TO_DBCD: Conversion from DINT to 32 Bit BCD

Brief description

Function description

This function converts a DINT data type input value into a 32 Bit BCD output value (8-4-2-1-Code).

The valid input value range is 0 99 999 999 (Dec.).

If no valid value is created at input, a runtime error is reported and the input value passes unchanged to the output.

EN and ENO can be configured as additional parameters.

Example Example of a DINT -> DBCD conversion

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Data type Dec. value Hex. value (= BCD-value)

Input value DINT 87 654 321 -

Output value DINT -2 023 406 815 8765 4321

DINT_TO_DBCD

DINTBCD_VALDINT VALUE

Parameter Data type Meaning

VALUE DINT DINT input value (valid value range 0 - 99 999 999)

BCD_VAL DINT 32 Bit BCD output value

70 33002214

Page 71: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

18

DIVMOD_***: Division and Modulo

Overview

Introduction This chapter describes the DIVMOD_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 72

Representation 72

Runtime error 72

71

Page 72: Concept 2.6 IEC Block Library Part ... - Schneider Electric

DIVMOD_***: Division and Modulo

Brief description

Function description

This function block divides the value at input IN1 by the value at input IN2. The result of the division (quotient) is delivered at output DV. The remainder of the division (Modulo) is delivered at output MD.

If there is a decimal place in the division result, the division will truncate it.

Data types of the ANY_INT group can be processed.

The data types of all input and output values must be identical. A specific function is available to process each of the different data types.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Formula Block formula:

DV = IN1 / IN2

MD = IN1 mod IN2

Parameter description

Block parameter description:

Runtime error

Runtime error An Error message appears, when� IN2=0

DIVMOD_***

***DV

***MD

IN1***

IN2*** *** = INT, DINT, UINT, UDINT

Parameter Data type Meaning

IN1 INT, DINT, UINT, UDINT Dividend

IN2 INT, DINT, UINT, UDINT Divisor

DV INT, DINT, UINT, UDINT Quotient

MD INT, DINT, UINT, UDINT Modulo

72 33002214

Page 73: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

19

HYST_***: Indicator signal for maximum value delimiter with hysteresis

Overview

Introduction This chapter describes the HYST_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 74

Representation 74

Detailed Description 75

73

Page 74: Concept 2.6 IEC Block Library Part ... - Schneider Electric

HYST_***: Indicator for maximum value delimiter with hysteresis

Brief description

Function description

The function block monitors the input variable X for violation of the upper threshold.

Data types of the ANY_NUM group can be processed.

The data types of all input values must be identical. A specific function is available process each of the different data types.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Note: If the lower threshold should be monitored as well, use the INDLIM function block.

HYST_***

BOOLINDX***

HIGH***LOW***

*** = INT, DINT, UINT, UDINT, REAL

Parameter Data type Meaning

X INT, DINT, UINT, UDINT, REAL

Input variable

HIGH INT, DINT, UINT, UDINT, REAL

Maximum upper threshold

LOW INT, DINT, UINT, UDINT, REAL

Minimum upper threshold

IND BOOL Anzeige: reached upper threshold

74 33002214

Page 75: Concept 2.6 IEC Block Library Part ... - Schneider Electric

HYST_***: Indicator for maximum value delimiter with hysteresis

Detailed Description

Parameter description

If X violates the upper HIGH limit, the function block reports this condition with IND = 1.

If, subsequently, X violates the LOW threshold, IND will be reset to "0".

Function Function description

INDi = 1, if X > HIGH

INDi = 0, if X < LOW

otherwise

INDi = INDi-1

If LOW is greater than HIGH, there is no hysteresis, and IND shows X is greater than HIGH.

Diagram Maximum value delimiter with hysteresis

IND

X

LOW

HIGH

X

Time

33002214 75

Page 76: Concept 2.6 IEC Block Library Part ... - Schneider Electric

HYST_***: Indicator for maximum value delimiter with hysteresis

76 33002214

Page 77: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

20

INDLIM_***: Indicator signal for delimiters with hysteresis

Overview

Introduction This chapter describes the INDLIM_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 78

Representation 78

Detailed description 79

77

Page 78: Concept 2.6 IEC Block Library Part ... - Schneider Electric

INDLIM_***: Indicator signal for delimiters with hysteresis

Brief description

Function description

The function block monitors the input variable X for violation of the upper threshold and violation of the lower threshold.

It is possible to process data types of the ANY_NUM group.

The data types of all input values must be identical. A specific function is available to process each of the different data types.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Note: If only the upper threshold should be monitored as well, use the HYST function block.

INDLIM_***

BOOLMX_IND

BOOLMN_IND

X***MX_HIGH***MX_LOW***MN_LOW***

MN_HIGH*** *** = INT, DINT, UINT, UDINT, REAL

Parameter Data type Meaning

X INT, DINT, UINT, UDINT, REAL Input variable

MX_HIGH INT, DINT, UINT, UDINT, REAL Maximum upper limit

MX_LOW INT, DINT, UINT, UDINT, REAL Minimum lower limit

MN_LOW INT, DINT, UINT, UDINT, REAL Minimum lower limit

MN_HIGH INT, DINT, UINT, UDINT, REAL Minimum upper limit

MX_IND BOOL Display: reached upper limit

MN_IND BOOL Display: reached lower limit

78 33002214

Page 79: Concept 2.6 IEC Block Library Part ... - Schneider Electric

INDLIM_***: Indicator signal for delimiters with hysteresis

Detailed description

Parameter description

If X exceeds the upper limit MX_HIGH, the function block reports this condition with MX_IND = 1.

If, subsequently, X is less than the limit MX_LOW, MX_IND will be reset to "0".

Function Function description:

MX_INDi = 1, if X > MX_HIGH

MX_INDi = 0, if X < MX_LOW

otherwise

MX_INDi = MX_IND(i-1)

If X is less than the lower limit MN_HIGH, the function block reports this condition with MN_IND =1.

If, subsequently, X exceeds the limit MN_LOW, MX_IND is reset to "0".

Function Function description:

MX_INDi = 1, if X < MX_HIGH

MX_INDi = 0, if X > MX_LOW

otherwise

MX_INDi = MX_IND(i-1)

If MX_LOW is greater than MX_HIGH, there will be no hysteresis, and MX_IND displays the fact that X is greater than MX_HIGH.

If MN_HIGH is greater than MN_LOW, there will be no hysteresis, and MN_IND displays the fact that X is smaller than MN_HIGH.

33002214 79

Page 80: Concept 2.6 IEC Block Library Part ... - Schneider Electric

INDLIM_***: Indicator signal for delimiters with hysteresis

Diagram Delimiters with hysteresis INDLIM

MN_IND

MX_IND

X

MX_LOW

MX_HIGH

MN_LOWMN_HIGH

X

Time

80 33002214

Page 81: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

21

INT_TO_BCD: Conversion from INT to 16 Bit BCD

Overview

Introduction This chapter describes the INT_TO_BCD block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 82

Representation 82

81

Page 82: Concept 2.6 IEC Block Library Part ... - Schneider Electric

INT_TO_BCD: Conversion from INT to 16 Bit BCD

Brief description

Function description

This function converts an INT data type input value into a 16 Bit BCD output value (8-4-2-1-Code).

The valid input value range is 0 9 999 (Dec.).

If no valid BCD coded value is created at input, a runtime error is reported and the input value passes unchanged to the output.

EN and ENO can be configured as additional parameters.

Example Example of an INT -> BCD conversion

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Data type Dec. value Hex. value (= BCD-value)

Input value INT 9 753 -

Output value INT -26 797 9753

INT_TO_BCD

INTBCD_VALINT VALUE

Parameter Data type Meaning

VALUE INT INT input value (valid value range 0 - 9 999)

BCD_VAL INT 16 Bit BCD output value

82 33002214

Page 83: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

22

INT_TO_DBCD: Conversion from INT to 32 Bit BCD

Overview

Introduction This chapter describes the INT_TO_DBCD block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 84

Representation 84

83

Page 84: Concept 2.6 IEC Block Library Part ... - Schneider Electric

INT_TO_DBCD: Conversion from INT to 32 Bit BCD

Brief description

Function description

This function converts an INT data type input value into a 32 Bit BCD output value (8-4-2-1-Code).

The valid input value range is 0 32 767 (Dec.).

If no valid value is created at input, a runtime error is reported and the input value passes unchanged to the output.

EN and ENO can be configured as additional parameters.

Example Example of an INT -> DBCD conversion

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Data type Dec. value Hex. value (= BCD-value)

Input value INT 13 579 -

Output value DINT 79 225 0001 3579

INT_TO_DBCD

DINTBCD_VALINT VALUE

Parameter Data type Meaning

VALUE INT INT input value (valid value range 0 - 32767)

BCD_VAL DINT 32 Bit BCD output value

84 33002214

Page 85: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

23

LIMIT_IND_***: Limit with indicator

Overview

Introduction This chapter describes the LIMIT_IND_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 86

Representation 87

85

Page 86: Concept 2.6 IEC Block Library Part ... - Schneider Electric

LIMIT_IND_***: Limit with indicator

Brief description

Function description

This function block transfers the unchanged input value (IN) to the output OUT, if the input value is not less than the minimum value (MN) and does not exceed the maximum value (MX). If the input value (IN) is less than the minimum value (MN), the minimum value will be transferred to the output. If the input value (IN) exceeds the maximum value (MX), the maximum value is transferred to the output.

Furthermore, a signal indicates the violation of a minimum or maximum value. If the value at input IN is less than the value at input MN, output MN_IND becomes "1". If the value at input IN exceeds the value at input MX, the output MX_IND becomes "1".

Data types of the ANY_ELEM group can be processed.

The data types of the input values MN, IN, MX as well as of the output value OUT must be identical. A specific function is available to process each of the different data types.

It is possible to project EN and ENO as additional parameters.

86 33002214

Page 87: Concept 2.6 IEC Block Library Part ... - Schneider Electric

LIMIT_IND_***: Limit with indicator

Representation

Symbol Block representation:

Formula Block formula:

OUT = IN, if (IN ≤ MX) & IN ≥ MN

OUT = MN, if (IN < MN)

OUT = MX, if (IN > MX)

MN_IND = 0, if IN ≥ MN

MN_IND = 1, if IN < MN

MX_IND = 0, if IN ≤ MX

MX_IND = 1, if IN > MX

Parameter description

Block parameter description:

LIMIT_IND_***

BOOLMN_IND

***OUT

BOOLMX_IND

MN***IN***

MX***

*** = INT, DINT, UINT, UDINT, REAL, TIME,BOOL, BYTE, WORD

Parameter Data type Meaning

MN INT, DINT, UINT, UDINT, REAL, TIME, BOOL, BYTE, WORD

Limit of minimum value

IN INT, DINT, UINT, UDINT, REAL, TIME, BOOL, BYTE, WORD

Input

MX INT, DINT, UINT, UDINT, REAL, TIME, BOOL, BYTE, WORD

Limit of maximum value

MN_IND BOOL Display of minimum value violation

OUT INT, DINT, UINT, UDINT, REAL, TIME, BOOL, BYTE, WORD

Output

MX_IND BOOL Display of maximum value violation

33002214 87

Page 88: Concept 2.6 IEC Block Library Part ... - Schneider Electric

LIMIT_IND_***: Limit with indicator

88 33002214

Page 89: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

24

LOOKUP_TABLE1: Traverse progression with 1st degree interpolation

Overview

Introduction This chapter describes the LOOKUP_TABLE1 block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 90

Representation 90

Detailed description 91

89

Page 90: Concept 2.6 IEC Block Library Part ... - Schneider Electric

LOOKUP_TABLE1: Traverse progression with 1st degree interpolation

Brief description

Function description

This function block linearizes characteristic curves by means of interpolation. The function block works with variable width.

The number of XiYi inputs can be increased to 30 by modifying the size of the block frame vertically. This corresponds to a maximum of 15 support point pairs.

The number of inputs must be even.

The X values must be in ascending order.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

LOOKUP_TABLE

REALY

BOOLQXHI

BOOLQXLO

XREAL

XiYi1REALXiYi2REAL::XiYinREALXiYimREAL

Parameter Data type Meaning

XiYi1 REAL X-coordinate 1st support point

XiYi2 REAL Y-coordinate 1st support point

XiYin REAL X-coordinate mth support point

XiYim REAL Y-coordinate mth support point

X REAL Input variable

Y REAL Output variable

QXHI BOOL Display: X > Xm

QXLO BOOL Indicator signal X < X1

90 33002214

Page 91: Concept 2.6 IEC Block Library Part ... - Schneider Electric

LOOKUP_TABLE1: Traverse progression with 1st degree

Detailed description

Parameter description

Each two sequential inputs (XiYi) represent a support point pair. The first input XiYi corresponds to X1, the next one to Y1, the one after that to X2, etc.

For all types of input value in X found between these support points, the corresponding Y output value is interpolated, while the traverse progression between the support points is viewed linearly.

For X < X1 Y is = Y1

For X > X1 is Y = Y1

If the value at input X is higher than the value of the last support point Xm, the output QXHI becomes "1".

If the value at input X is less than the value of the first support point X1, the output QXLO becomes "1".

Principle of interpolation

Traverse progression with 1st degree interpolation

Y

0 X

Ym

Yi+1Ym-1Y

Yi

Xi X Xi+1 Xm-1Xm

33002214 91

Page 92: Concept 2.6 IEC Block Library Part ... - Schneider Electric

LOOKUP_TABLE1: Traverse progression with 1st degree interpolation

Interpolation The following algorithm applies to a Point y:

for Xi ≤ X ≤ Xi+1 and i = 1 ... (m-1)

Assuming: X1 ≤ X2 ≤ ... ≤ Xi ≤ Xi+1 ≤ ... ≤ Xm-1 ≤ Xm

The X values must be in ascending order.

Two consecutive X values can be identical. This could cause a discrete curve progression.

In this instance, the special case applies:

Y = 0.5 x (Yi + Yi+1)

for

Xi = X = Xi+1 und i = 1 ... (m-1)

Y YiY j 1+( ) Yj–

X j 1+( ) Xj–---------------------------- X Xi–( )×+=

92 33002214

Page 93: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

25

NEG_***: Negation

Overview

Introduction This chapter describes the NEG_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 94

Representation 94

Runtime error 95

93

Page 94: Concept 2.6 IEC Block Library Part ... - Schneider Electric

NEG_***: Negation

Brief description

Function description

The Function negates the input value and delivers the result at the OUT output.

Data types of the ANY_NUM group can be processed.

The negation causes a sign reversal, e.g.

6 -> -6

-4 -> 4

The data types of the input and output values must be identical. A specific function is available to process each of the different data types.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

Note: When the data types are processedDINT and INT it is not possible to convert very long negative values into positive ones. However, the ENO output is not set to 0 when this error occurs.

Note: When the data types are processedUDINT and UINT there is always an Error message.

NEG_***

********* = INT, DINT, UINT, UDINT, REAL

Parameter Data type Meaning

IN INT, DINT, UINT, UDINT, REAL

Input

OUT INT, DINT, UINT, UDINT, REAL

Negated output

94 33002214

Page 95: Concept 2.6 IEC Block Library Part ... - Schneider Electric

NEG_***: Negation

Runtime error

Runtime error A violation of the value range at the input during the execution of the function will cause an error message to appear.

An Error message appears, when� the value range of the input is exceeded or� an input value of the data type UDINT or UINT is to be converted.

33002214 95

Page 96: Concept 2.6 IEC Block Library Part ... - Schneider Electric

NEG_***: Negation

96 33002214

Page 97: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

26

REAL_AS_WORD: Type conversion

Overview

Introduction This chapter describes the REAL_AS_WORD block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 98

Representation 98

97

Page 98: Concept 2.6 IEC Block Library Part ... - Schneider Electric

REAL_AS_WORD: Type conversion

Brief description

Function description

This function block converts one input word from Data type REAL to 2 output values of data type WORD.

The individual words of the REAL input are assigned to the outputs according to the output names.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

REAL_AS_WORD

WORDLOW

WORDHIGH

INREAL

Parameter Data type Meaning

IN REAL Input

LOW WORD less significant word

HIGH WORD more significant word

98 33002214

Page 99: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

27

SAH: Detecting and holding with rising edge

Overview

Introduction This chapter describes the SAH block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 100

Representation 100

99

Page 100: Concept 2.6 IEC Block Library Part ... - Schneider Electric

SAH: Detecting and holding with rising edge

Brief description

Function description

The function block transfers the input value PV to the OUT output when first called up. With a rising edge (0 to 1) at input CLK, the input value IN is transferred to the OUT output. This value remains at the output until the next rising edge causes a new value to be loaded from IN to OUT.

The data types of the input values IN, PV and of the output value OUT must be identical.

The parameters EN and ENO can additionally be projected.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

SAH

INANYCLKBOOL

PVANY

ANYOUT

Parameter Data type Meaning

IN ANY Input value

CLK BOOL Clock input

PV ANY Preset value

OUT ANY Output value

100 33002214

Page 101: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

28

SIGN_***: Sign evaluation

Overview

Introduction This chapter describes the SIGN_*** block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 102

Representation 103

101

Page 102: Concept 2.6 IEC Block Library Part ... - Schneider Electric

SIGN_***: Sign evaluation

Brief description

Function description

The function is used to detect negative signs.

Data types of the ANY_NUM group can be processed.

With a value ≥ 0 at the input, the output becomes "0". With a value < 0 at the input, the output becomes "1".

A specific function is available to process each of the different data types.

EN and ENO can be configured as additional parameters.

Note: Different processing of REAL and INT values results in the following behavior for signed 0 (+/-0):-0.0 -> SIGN_REAL -> 1-0 -> SIGN_INT/DINT -> 0+0.0 -> SIGN_REAL -> 0+0 -> SIGN_INT/DINT -> 0

102 33002214

Page 103: Concept 2.6 IEC Block Library Part ... - Schneider Electric

SIGN_***: Sign evaluation

Representation

Symbol Block representation:

Formula Block formula:

OUT = 1, if IN < 0

OUT = 0, if IN ≥ 0

Parameter description

Block parameter description:

SIGN_***

BOOL***

*** = INT, DINT, UINT, UDINT, REAL

Note: Different processing of REAL and INT values results in the following behavior for signed 0 (+/-0):-0.0 -> SIGN_REAL -> 1-0 -> SIGN_INT/DINT -> 0+0.0 -> SIGN_REAL -> 0+0 -> SIGN_INT/DINT -> 0

Parameter Data type Meaning

IN INT, DINT, UINT, UDINT, REAL

Signed input

OUT BOOL Sign evaluation

33002214 103

Page 104: Concept 2.6 IEC Block Library Part ... - Schneider Electric

SIGN_***: Sign evaluation

104 33002214

Page 105: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

29

TIME_AS_WORD: Type conversion

Overview

Introduction This chapter describes the TIME_AS_WORD block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 106

Representation 106

105

Page 106: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TIME_AS_WORD: Type conversion

Brief description

Function description

The function block converts one input word from Data type TIME to 2 output values of data type WORD.

The individual words of the TIME input are assigned to the outputs according to the output names.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

TIME_AS_WORD

WORDLOW

WORDHIGH

INTIME

Parameter Data type Meaning

IN TIME Input

LOW WORD less significant word

HIGH WORD more significant word

106 33002214

Page 107: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

30

TOF_P: Off Delay with Pause

Overview

Introduction This chapter describes the TOF_P block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 108

Representation 109

Detailed description 110

107

Page 108: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TOF_P: Off Delay with Pause

Brief description

Function description

The function block is used as Off delay.

A 0 -> 1 edge on input IN triggers a reset.

A 1 -> 0 edge on input IN starts the timer function.

If the elapsed time (output ET) reaches the value defined on input PT, output Q is set to "0".

When the function block is first called the initial state of ET is "0".

With a "1" signal on input PAUSE, the timer is stopped and all values are frozen. If the input PAUSE becomes "0" again, the timer continues.

PAUSE has the highest priority. With a 1 -> 0 edge on input PAUSE, the block is no longer processed in this cycle. The block continues processing in the next cycle.

EN and ENO can be configured as additional parameters.

Note: Input EN cannot be used as pause function for the function block.The elapsed time is still measured even when input EN becomes "0". If input EN becomes "1" again, output ET is updated and executes a jump.However, if PAUSE is "1" when EN becomes "0", the pause is continued after EN becomes "1" until PAUSE becomes "0". In this case, there is no jump on output ET.

108 33002214

Page 109: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TOF_P: Off Delay with Pause

Representation

Symbol Block representation:

Parameter description

Block parameter description:

TOF_P

INBOOLPTTIMEPAUSEBOOL

BOOLQ

TIMEET

Parameter Data type Meaning

IN BOOL 0 -> 1: Reset1 -> 0: Start timer

PT TIME Preset delay time

PAUSE BOOL 1: The timer values are frozen.

Q BOOL Output

ET TIME Elapsed time

33002214 109

Page 110: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TOF_P: Off Delay with Pause

Detailed description

Timing diagram Representation of the Off delay TOF_P:

t0 If IN becomes "1" and PAUSE is "1", Q remains "0" and the internal time is not started (PAUSE has priority above IN).

t1 If IN becomes "0" while PAUSE is "1", the block remains inactive.t2 If PAUSE becomes "0" while IN is "0", the block remains inactive.t3 If IN becomes "1", Q becomes "1".t4 If IN becomes "0", the internal time (ET) is started.t5 If IN becomes "1" before the internal time has reached the value of PT, the internal time is

reset without Q becoming "0".t6 If PAUSE becomes "1", Q remains "1" (the block is inactive).t7 If IN and PAUSE become "0", the internal time is started in the next cycle.t8 If the internal time reaches the value of PT, Q becomes "0". t9 If IN becomes "1", Q becomes "1" and the internal time is reset.t10 If IN becomes "0", the internal time is started.t11 If PAUSE becomes "1" before the internal time has reached the value of PT, the internal

time is stopped without Q becoming "0".t12 If PAUSE becomes "0", the internal time (ET) continues.t13 If the internal time reaches the value of PT, Q becomes "0". t14 If IN becomes "1", Q becomes "1" and the internal time is reset.

PAUSE

time

IN

Q

PT

t0 t2t1 t4t3 t5 t6 t7 t9t8 t10 t11 t13 t14t12

ET

110 33002214

Page 111: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

31

TON_P: On Delay with Pause

Overview

Introduction This chapter describes the TON_P block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 112

Representation 113

Detailed description 114

111

Page 112: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TON_P: On Delay

Brief description

Function description

The function block is used as On delay.

A 1 -> 0 edge on input IN triggers a reset.

A 0 -> 1 edge on input IN starts the timer function.

If the elapsed time (output ET) reaches the value defined on input PT, output Q is set to "1".

When the function block is first called the initial state of ET is "0".

With a "1" signal on input PAUSE, the timer is stopped and all values are frozen. If the input PAUSE becomes "0" again, the timer continues.

PAUSE has the highest priority. With a 1 -> 0 edge on input PAUSE, the block is no longer processed in this cycle. The block continues processing in the next cycle.

EN and ENO can be configured as additional parameters.

Note: Input EN cannot be used as pause function for the function block.The elapsed time is still measured even when input EN becomes "0". If input EN becomes "1" again, output ET is updated and executes a jump.However, if PAUSE is "1" when EN becomes "0", the pause is continued after EN becomes "1" until PAUSE becomes "0". In this case, there is no jump on output ET.

112 33002214

Page 113: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TON_P: On Delay

Representation

Symbol Block representation:

Parameter description

Block parameter description:

TON_P

INBOOLPTTIMEPAUSEBOOL

BOOLQ

TIMEET

Parameter Data type Meaning

IN BOOL 0 -> 1: Start timer1 -> 0: Reset

PT TIME Preset delay time

PAUSE BOOL 1: The timer values are frozen.

Q BOOL Output

ET TIME Elapsed time

33002214 113

Page 114: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TON_P: On Delay

Detailed description

Timing diagram Representation of the On delay TON_P:

t0 If IN becomes "1" and PAUSE is "1", Q remains "0" and the internal time is not started (PAUSE has priority above IN).

t1 If IN becomes "0" while PAUSE is "1", the block remains inactive.t2 If PAUSE becomes "0" while IN is "0", the block remains inactive.t3 If IN becomes "1", the internal time (ET) is started.t4 If IN becomes "0" before the internal time has reached the value of PT, the internal time is

reset without Q becoming "1".t5 If IN becomes "1", the internal time (ET) is started.t6 If PAUSE becomes "1" before the internal time has reached the value of PT, the internal

time is stopped without Q becoming "1".t7 If IN and PAUSE become "0", the internal time is reset in the next cycle without Q

becoming "1".t8 If IN becomes "1", the internal time (ET) is started.t9 If PAUSE becomes "1" before the internal time has reached the value of PT, the internal

time is stopped without Q becoming "1".t10 If PAUSE becomes "0", the internal time (ET) continues.t11 If the internal time reaches the value of PT, Q becomes "1". t12 If IN becomes "0", Q becomes "0" and the internal time is reset.

PAUSE

time

IN

Q

PT

t0 t2t1 t4t3 t5 t6 t7 t9t8 t10t11 t13 t14 t15t12

ET

t17t16

114 33002214

Page 115: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TON_P: On Delay

t13 If IN becomes "1", the internal time (ET) is started.t14 If the internal time reaches the value of PT, Q becomes "1". t15 If PAUSE becomes "1", Q remains "1".t16 If IN becomes "0" while PAUSE is "1", Q remains "1" and ET is not reset (the block is

inactive).t17 If PAUSE becomes "0" while IN is "0", Q becomes "0" in the next cycle and the internal

time is reset.

33002214 115

Page 116: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TON_P: On Delay

116 33002214

Page 117: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

32

TRIGGER: Detection of all types of edges

Overview

Introduction This chapter describes the TRIGGER block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 118

Representation 118

117

Page 118: Concept 2.6 IEC Block Library Part ... - Schneider Electric

TRIGGER: Detection of all types of edges

Brief description

Function description

The Function block recognizes all types of edges (1 -> 0 and 0 -> 1) at input CLK.

Output EDGE becomes "1" if there is a transition from "0" to "1" or from "1" to "0" at CLK; otherwise it remains on "0".

If there is a transition from "0" to "1" at input CLK, output RISE becomes "1"; if there is a transition from "1" to "0" at input CLK, output FALL becomes "1"; if neither of these two instances occurs, both outputs become "0".

The parameters EN and ENO can additionally be projected.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

TRIGGER

BOOLRISE

BOOLEDGE

BOOLFALL

CLKBOOL

Parameter Data type Meaning

CLK BOOL Clock input

RISE BOOL Indicator signal of rising edge

EDGE BOOL Indicator of all types of edges

FALL BOOL Indicator signal of falling edge

118 33002214

Page 119: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

33

UDINT_AS_WORD: Type conversion

Overview

Introduction This chapter describes the UDINT_AS_WORD block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 120

Representation 120

119

Page 120: Concept 2.6 IEC Block Library Part ... - Schneider Electric

UDINT_AS_WORD: Type conversion

Brief description

Function description

The function block converts one input word from Data type UDINT to 2 output values of data type WORD.

The individual words of the UDINT input are assigned to the outputs according to the output names.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

UDINT_AS_WORD

WORDLOW

WORDHIGH

INUDINT

Parameter Data type Meaning

IN UDINT Input

LOW WORD less significant word

HIGH WORD more significant word

120 33002214

Page 121: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

34

WORD_AS_BYTE: Type conversion

Overview

Introduction This chapter describes the WORD_AS_BYTE block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 122

Representation 122

121

Page 122: Concept 2.6 IEC Block Library Part ... - Schneider Electric

WORD_AS_BYTE: Type conversion

Brief description

Function description

The function block converts one input word from Data type WORD to two output values of data type BYTE.

The individual bytes of the word at the input are assigned to the outputs according to the output names.

The parameters EN and ENO can additionally be projected.

Representation

Symbol Block representation:

Parameter description

Block parameter description:

WORD_AS_BYTE

BYTELOW

BYTEHIGH

INWORD

Parameter Data type Meaning

IN WORD Input

LOW BYTE less significant byte

HIGH BYTE more significant byte

122 33002214

Page 123: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

35

WORD_AS_DINT: Type conversion

Overview

Introduction This chapter describes the WORD_AS_DINT block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 124

Representation 124

123

Page 124: Concept 2.6 IEC Block Library Part ... - Schneider Electric

WORD_AS_DINT: Type conversion

Brief description

Function description

The Function converts 2 input words from Data type WORD to an output value of data type DINT.

The input values are assigned to the word at the output according to the input names.

The parameters EN and ENO can additionally be projected.

Representation

Symbol Block representation:

Formula Block formula:

Parameter description

Block parameter description:

WORD_AS_DINT

DINTLOWWORDHIGHWORD

OUT HIGH LOW,{ }=

Parameter Data type Meaning

LOW WORD less significant word

HIGH WORD more significant word

OUT DINT Output value

124 33002214

Page 125: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

36

WORD_AS_REAL: Type conversion

Overview

Introduction This chapter describes the WORD_AS_REAL block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 126

Representation 126

125

Page 126: Concept 2.6 IEC Block Library Part ... - Schneider Electric

WORD_AS_REAL: Type conversion

Brief description

Function description

The Function converts 2 input words from Data type WORD to an output value of data type REAL.

The input values are assigned to the word at the output according to the input names.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Formula Block formula:

Parameter description

Block parameter description:

WORD_AS_REAL

REALLOWWORDHIGHWORD

OUT HIGH LOW,{ }=

Parameter Data type Meaning

LOW WORD less significant word

HIGH WORD more significant word

OUT REAL Output value

126 33002214

Page 127: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

37

WORD_AS_TIME: Type conversion

Overview

Introduction This chapter describes the WORD_AS_TIME block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 128

Representation 128

127

Page 128: Concept 2.6 IEC Block Library Part ... - Schneider Electric

WORD_AS_TIME: Type conversion

Brief description

Function description

The Function converts 2 input words from Data type WORD to an output value of data type TIME.

The input values are assigned to the word at the output according to the input names.

The parameters EN and ENO can additionally be projected.

Representation

Symbol Block representation:

Formula Block formula:

Parameter description

Block parameter description:

WORD_AS_TIME

TIMELOWWORDHIGHWORD

OUT HIGH LOW,{ }=

Parameter Data type Meaning

LOW WORD less significant word

HIGH WORD more significant word

OUT TIME Output value

128 33002214

Page 129: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

38

WORD_AS_UDINT: Type conversion

Overview

Introduction This chapter describes the WORD_AS_UDINT block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 130

Representation 130

129

Page 130: Concept 2.6 IEC Block Library Part ... - Schneider Electric

WORD_AS_UDINT: Type conversion

Brief description

Function description

The Function converts 2 input words from Data type WORD to an output value of data type UDINT.

The input values are assigned to the word at the output according to the input names.

It is possible to project EN and ENO as additional parameters.

Representation

Symbol Block representation:

Formula Block formula:

Parameter description

Block parameter description:

WORD_AS_UDINT

UDINTLOWWORDHIGHWORD

OUT HIGH LOW,{ }=

Parameter Data type Meaning

LOW WORD less significant word

HIGH WORD more significant word

OUT UDINT Output value

130 33002214

Page 131: Concept 2.6 IEC Block Library Part ... - Schneider Electric

33002214

39

WORD_TO_BIT: Type conversion

Overview

Introduction This chapter describes the WORD_TO_BIT block.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Brief description 132

Representation 133

131

Page 132: Concept 2.6 IEC Block Library Part ... - Schneider Electric

WORD_TO_BIT: Type conversion

Brief description

Function description

The function block converts one input word from Data type WORD to 16 output values of data type BOOL.

The individual bits of the word at the input are assigned to the outputs according to the output names.

The parameters EN and ENO can additionally be projected.

BIT0 (2 )

BIT15 (2 )

0

15

BIT1 (2 )1

BIT14 (2 )14

215 21 20214

WORD

132 33002214

Page 133: Concept 2.6 IEC Block Library Part ... - Schneider Electric

WORD_TO_BIT: Type conversion

Representation

Symbol Block representation:

Parameter description

Block parameter description:

WORD_TO_BIT

BOOLBIT0

BOOLBIT1

BOOLBIT2

BOOLBIT3

BOOLBIT4

BOOLBIT5

BOOLBIT6

BOOLBIT7

BOOLBIT8

BOOLBIT9BOOLBIT10

BOOLBIT11

BOOLBIT12

BOOLBIT13

BOOLBIT14

BOOLBIT15

WORD

Parameter Data type Meaning

IN WORD Input

BIT0 BOOL Output BIT0

BIT1 BOOL Output BIT1

: : :

BIT15 BOOL Output BIT15

33002214 133

Page 134: Concept 2.6 IEC Block Library Part ... - Schneider Electric

WORD_TO_BIT: Type conversion

134 33002214

Page 135: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

active Window The window, which is currently selected. Only one window can be active at any given time. When a window is active, the color of the title bar changes, so that it is distinguishable from the other windows. Unselected windows are inactive.

Actual Parameters

Current connected Input / Output Parameters.

Addresses (Direct) addresses are memory ranges on the PLC. They are located in the State RAM and can be assigned Input/Output modules.The display/entry of direct addresses is possible in the following formats:� Standard Format (400001)� Separator Format (4:00001)� Compact format (4:1)� IEC Format (QW1)

ANL_IN ANL_IN stands for the "Analog Input" data type and is used when processing analog values. The 3x-References for the configured analog input module, which were specified in the I/O component list, are automatically assigned to the data type and should therefore only be occupied with Unlocated Variables.

ANL_OUT ANL_OUT stands for the "Analog Output" data type and is used when processing analog values. The 4x-References for the configured analog output module, which were specified in the I/O component list, are automatically assigned to the data type and should therefore only be occupied with Unlocated Variables.

ANY In the present version, "ANY" covers the BOOL, BYTE, DINT, INT, REAL, UDINT, UINT, TIME and WORD elementary data types and related Derived Data Types.

A

33002214 135

Page 136: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

ANY_BIT In the present version, "ANY_BIT" covers the BOOL, BYTE and WORD data types.

ANY_ELEM In the present version, "ANY_ELEM" covers the BOOL, BYTE, DINT, INT, REAL, UDINT, UINT, TIME and WORD data types.

ANY_INT In the present version, "ANY_INT" covers the DINT, INT, UDINT and UINT data types.

ANY_NUM In the present version, "ANY_NUM" covers the DINT, INT, REAL, UDINT and UINT data types.

ANY_REAL In the present version, "ANY_REAL" covers the REAL data type.

Application Window

The window contains the workspace, menu bar and the tool bar for the application program. The name of the application program appears in the title bar. An application window can contain several Document windows. In Concept the application window corresponds to a Project.

Argument Synonymous with Actual parameters.

ASCII-Mode The ASCII (American Standard Code for Information Interchange) mode is used to communicate with various host devices. ASCII works with 7 data bits.

Atrium The PC based Controller is located on a standard AT board, and can be operated within a host computer in an ISA bus slot. The module has a motherboard (requires SA85 driver) with two slots for PC104 daughter-boards. In this way, one PC104 daughter-board is used as a CPU and the other as the INTERBUS controller.

Backup file (Concept-EFB)

The backup file is a copy of the last Source coding file. The name of this backup file is "backup??.c" (this is assuming that you never have more than 100 copies of the source coding file). The first backup file has the name "backup00.c". If you have made alterations to the Definitions file which do not cause any changes to the EFB interface, the generation of a backup file can be stopped by editing the source coding file (Objects → Source). If a backup file is created, the source file can be entered as the name.

B

136 33002214

Page 137: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Base 16 literals Base 16 literals are used to input whole number values into the hexadecimal system. The base must be denoted using the prefix 16#. The values can not have any signs (+/-). Single underscores ( _ ) between numbers are not significant.

Example16#F_F or 16#FF (decimal 255) 16#E_0 or 16#E0 (decimal 224)

Base 2 literals Base 2 literals are used to input whole number values into the dual system. The base must be denoted using the prefix 2#. The values can not have any signs (+/-). Single underscores ( _ ) between numbers are not significant.

Example 2#1111_1111 or 2#11111111 (decimal 255) 2#1110_0000 or 2#11100000 (decimal 224)

Base 8 literals Base 8 literals are used to input whole number values in the octosystem. The base must be denoted using the prefix 8#. The values can not have any signs (+/-). Single underscores ( _ ) between numbers are not significant.

Example 8#3_77 or 8#377 (decimal 255) 8#34_0 or 8#340 (decimal 224)

Binary Connections

Connections between FFB outputs and inputs with the data type BOOL.

Bit sequence A data element, which consists of one or more bits.

BOOL BOOL stands for the data type "boolean". The length of the data element is 1 bit (occupies 1 byte in the memory). The value range for the variables of this data type is 0 (FALSE) and 1 (TRUE).

Bridge A bridge is a device which connects networks. It enables communication between nodes on two networks. Each network has its own token rotation sequence - the token is not transmitted via the bridge.

BYTE BYTE stands for the data type "bit sequence 8". Entries are made as base 2 literal, base 8 literal or base 16 literal. The length of the data element is 8 bits. A numerical value range can not be assigned to this data type.

33002214 137

Page 138: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Clipboard The clipboard is a temporary memory for cut or copied objects. These objects can be entered in sections. The contents of the clipboard are overwritten with each new cut or copy.

Coil A coil is a LD element which transfers the status of the horizontal connection on its left side, unchanged, to the horizontal connection on its right side. In doing this, the status is saved in the relevant variable/direct address.

Compact format (4:1)

The first digit (the Reference) is separated from the address that follows by a colon (:) where the leading zeros are not specified.

Constants Constants are Unlocated variables, which are allocated a value that cannot be modified by the logic program (write protected).

Contact A contact is a LD element, which transfers a status on the horizontal link to its right side. This status comes from the boolean AND link of the status of the horizontal link on the left side, with the status of the relevant variable/direct address. A contact does not change the value of the relevant variable/direct address.

Data transfer settings

Settings which determine how information is transferred from your programming device to the PLC.

Data Types The overview shows the data type hierarchy, as used for inputs and outputs of functions and function blocks. Generic data types are denoted using the prefix "ANY".� ANY_ELEM

� ANY_NUMANY_REAL (REAL)ANY_INT (DINT, INT, UDINT, UINT)

� ANY_BIT (BOOL, BYTE, WORD)� TIME

� System Data types (IEC Extensions)� Derived (from "ANY" data types)

C

D

138 33002214

Page 139: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

DCP I/O drop A remote network with a super-ordinate PLC can be controlled using a Distributed Control Processor (D908). When using a D908 with remote PLC, the super-ordinate PLC considers the remote PLC as a remote I/O drop. The D908 and the remote PLC communicate via the system bus, whereby a high performance is achieved with minimum effect on the cycle time. The data exchange between the D908 and the super-ordinate PLC takes place via the remote I/O bus at 1.5Mb per second. A super-ordinate PLC can support up to 31 D908 processors (addresses 2-32).

DDE (Dynamic Data Exchange)

The DDE interface enables a dynamic data exchange between two programs in Windows. The user can also use the DDE interface in the extended monitor to call up their own display applications. With this interface, the user (i.e. the DDE client) can not only read data from the extended monitor (DDE server), but also write data to the PLC via the server. The user can therefore alter data directly in the PLC, while monitoring and analyzing results. When using this interface, the user can create their own "Graphic Tool", "Face Plate" or "Tuning Tool" and integrate it into the system. The tools can be written in any language, i.e. Visual Basic, Visual C++, which supports DDE. The tools are invoked when the user presses one of the buttons in the Extended Monitor dialog field. Concept Graphic Tool: Configuration signals can be displayed as a timing diagram using the DDE connection between Concept and Concept Graphic Tool.

Declaration Mechanism for specifying the definition of a language element. A declaration usually covers the connection of an identifier to a language element and the assignment of attributes such as data types and algorithms.

Definitions file (Concept-EFB)

The definitions file contains general descriptive information on the selected EFB and its formal parameters.

Defragmenting With defragmenting, unanticipated gaps (e.g. resulting from deleting unused variables) are removed from memory.

Derived Data Type

Derived data types are data types, which are derived from Elementary Data Types and/or other derived data types. The definition of the derived data types is found in the Concept data type editor.A distinction is made between global data types and local data types.

33002214 139

Page 140: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Derived Function Block (DFB)

A derived function block represents the invocation of a derived function block type. Details of the graphic form of the invocation can be found in the "Functional block (instance)". In contrast to the invocation of EFB types, invocations of DFB types are denoted by double vertical lines on the left and right hand side of the rectangular block symbol.The output side of a derived function block is created in FBD language, LD language, ST language, IL language, but only in the current version of the programming system. Derived functions can also not be defined in the current version.A distinction is made between local and global DFBs.

DFB Code The DFB code is the section's DFB code which can be executed. The size of the DFB code is mainly dependent upon the number of blocks in the section.

DFB instance data

The DFB instance data is internal data from the derived function blocks used in the program.

DINT DINT stands for the data type "double length whole number (double integer)". Entries are made as integer literal, base 2 literal, base 8 literal or base 16 literal. The length of the data element is 32 bits. The value range for variables of this data type reaches from -2 exp (31) to 2 exp (31) -1.

Direct Representation

A method of displaying variables in the PLC program, from which the assignment to the logical memory can be directly - and indirectly to the physical memory - derived.

Document Window

A window within an application window. Several document windows can be open at the same time in an application window. However, only one document window can ever be active. Document windows in Concept are, for example, sections, the message window, the reference data editor and the PLC configuration.

DP (PROFIBUS) DP = Remote Peripheral

Dummy An empty file, which consists of a text heading with general file information, such as author, date of creation, EFB designation etc. The user must complete this dummy file with further entries.

DX Zoom This property enables the user to connect to a programming object, to monitor and, if necessary change, its data value.

140 33002214

Page 141: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

EFB code The EFB code is the executable code of all EFBs used. In addition the used EFBs count in DFBs.

Elementary functions/function blocks (EFB)

Identifier for Functions or Function blocks, whose type definitions are not formulated in one of the IEC languages, i.e. whose body for example can not be modified with the DFB editor (Concept-DFB). EFB types are programmed in "C" and are prepared in a pre-compiled form using libraries.

EN / ENO (Enable / Error signal)

If the value of EN is equal to "0" when the FFB is invoked, the algorithms that are defined by the FFB will not be executed and all outputs keep their previous values. The value of ENO is in this case automatically set to "0". If the value of EN is equal to "1", when the FFB is invoked, the algorithms which are defined by the FFD will be executed. After the error-free execution of these algorithms, the value of ENO is automatically set to "1". If an error occurs during the execution of these algorithms, ENO is automatically set to "0". The output behavior of the FFB is independent of whether the FFBs are invoked without EN/ENO or with EN=1. If the EN/ENO display is switched on, it is imperative that the EN input is switched on. Otherwise, the FFB is not executed. The configuration of EN and ENO is switched on or off in the Block Properties dialog box. The dialog box can be invoked with the Objects → Properties...menu command or by double-clicking on the FFB.

Error If an error is recognized during the processing of a FFB or a step (e.g. unauthorized input values or a time error), an error message appears, which can be seen using the Online → Event Viewer...menu command. For FFBs, the ENO output is now set to "0".

Evaluation The process, through which a value is transmitted for a Function or for the output of a Function block during Program execution.

Expression Expressions consist of operators and operands.

FFB (Functions/Function blocks)

Collective term for EFB (elementary functions/function blocks) and DFB (Derived function blocks)

E

F

33002214 141

Page 142: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Field variables A variable, which is allocated a defined derived data type with the key word ARRAY (field). A field is a collection of data elements with the same data type.

FIR Filter (Finite Impulse Response Filter) a filter with finite impulse answer

Formal parameters

Input / Output parameters, which are used within the logic of a FFB and led out of the FFB as inputs/outputs.

Function (FUNC) A program organization unit, which supplies an exact data element when processing. a function has no internal status information. Multiple invocations of the same function using the same input parameters always supply the same output values.Details of the graphic form of the function invocations can be found in the definition "Functional block (instance)". In contrast to the invocations of the function blocks, function invocations only have a single unnamed output, whose name is the same as the function. In FBD each invocation is denoted by a unique number via the graphic block, this number is automatically generated and can not be altered.

Function block (Instance) (FB)

A function block is a program organization unit, which correspondingly calculates the functionality values that were defined in the function block type description, for the outputs and internal variable(s), if it is invoked as a certain instance. All internal variable and output values for a certain function block instance remain from one function block invocation to the next. Multiple invocations of the same function block instance with the same arguments (input parameter values) do not therefore necessarily supply the same output value(s).Each function block instance is displayed graphically using a rectangular block symbol. The name of the function block type is stated in the top center of the rectangle. The name of the function block instance is also stated at the top, but outside of the rectangle. It is automatically generated when creating an instance, but, depending on the user's requirements, it can be altered by the user. Inputs are displayed on the left side of the block and outputs are displayed on the right side. The names of the formal input/output parameters are shown inside the rectangle in the corresponding places.The above description of the graphic display is especially applicable to the function invocations and to DFB invocations. Differences are outlined in the corresponding definitions.

Function Block Dialog (FBD)

One or more sections, which contain graphically displayed networks from Functions, Function blocks and Connections.

Function block type

A language element, consisting of: 1. the definition of a data structure, divided into input, output and internal variables; 2. a set of operations, which are performed with elements of the data structure, when a function block type instance is invoked. This set of operations can either be formulated in one of the IEC languages (DFB type) or in "C" (EFB type). A function block type can be instanced (invoked) several times.

142 33002214

Page 143: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Function Number

The function number is used to uniquely denote a function in a program or DFB. The function number can not be edited and is automatically assigned. The function number is always formed as follows: .n.m

n = Number of the section (consecutive numbers) m = Number of the FFB object in the section (current number)

Generic Data Type

A data type, which stands in place of several other data types.

Generic literals If the literal's data type is not relevant, simply specify the value for the literal. If this is the case, Concept automatically assigns the literal a suitable data type.

Global Data Global data are Unlocated variables.

Global derived data types

Global derived data types are available in each Concept project and are occupied in the DFB directory directly under the Concept directory.

Global DFBs Global DFBs are available in each Concept project. The storage of the global DFBs is dependant upon the settings in the CONCEPT.INI file.

Global macros Global macros are available in each Concept project and are stored in the DFB directory directly under the Concept directory.

Groups (EFBs) Some EFB libraries (e.g. the IEC library) are divided into groups. This facilitates locating the EFBs especially in expansive libraries.

Host Computer Hardware and software, which support programming, configuring, testing, operating and error searching in the PLC application as well as in a remote system application, in order to enable source documentation and archiving. The programming device can also be possibly used for the display of the process.

G

H

33002214 143

Page 144: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

I/O Map The I/O and expert modules from the various CPUs are configured in the I/O map.

Icon Graphical representation of different objects in Windows, e.g. drives, application programs and document windows.

IEC 61131-3 International standard: Programmable Logic Controls - Part 3: Programming languages.

IEC Format (QW1)

There is an IEC type designation in initial position of the address, followed by the five-figure address.� %0x12345 = %Q12345� %1x12345 = %I12345� %3x12345 = %IW12345� %4x12345 = %QW12345

IEC name conventions (identifier)

An identifier is a sequence of letters, numbers and underscores, which must begin with either a letter or underscore (i.e. the name of a function block type, an instance, a variable or a section). Letters of a national typeface (i.e.: ö,ü, é, õ) can be used, except in project and DFB names.Underscores are significant in identifiers; e.g. "A_BCD" and "AB_CD" are interpreted as two separate identifiers. Several leading and multiple successive underscores are not allowed.Identifiers should not contain any spaces. No differentiation is made between upper and lower case, e.g. "ABCD" and "abcd" are interpreted as the same identifier.Identifiers should not be Keywords.

IEC Program Memory

The IEC program memory consists of the program code, EFB code, the section data and the DFB instance data.

IIR Filter (Infinite Impulse Response Filter) a filter with infinite impulse answer

Initial step The first step in a sequence. A step must be defined as an initial step for each sequence. The sequence is started with the initial step when first invoked.

Initial value The value, which is allocated to a variable when the program is started. The values are assigned in the form of literals.

I

144 33002214

Page 145: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Input bits (1x references)

The 1/0 status of the input bits is controlled via the process data, which reaches from an input device to the CPU.

Input parameter (Input)

Upon invocation of a FFB, this transfers the corresponding argument.

Input words (3x references)

An input word contains information, which originates from an external source and is represented by a 16 bit number. A 3x register can also contain 16 sequential input bits, which were read into the register in binary or BCD (binary coded decimal) format. Note: The x, which follows the initial reference type number, represents a five-figure storage location in the user data memory, i.e. the reference 300201 signifies a 16-bit input word at the address 201 in the State RAM.

Instance Name An identifier, which belongs to a certain function block instance. The instance name is used to clearly denote a function block within a program organization unit. The instance name is automatically generated, but it can be edited. The instance name must be unique throughout the whole program organization unit, and is not case sensitive. If the name entered already exists, you will be warned and you will have to choose another name. The instance name must comply with the IEC name conventions otherwise an error message appears. The automatically generated instance name is always formed as follows: FBI_n_m

FBI = Function Block Instance n = Number of the section (consecutive numbers) m = Number of the FFB object in the section (current number)

Instancing Generating an Instance.

Instruction (IL) Instructions are the "commands" of the IL programming language. Each instruction begins on a new line and is performed by an operator with a modifier if necessary, and if required for the current operation, by one or more operands. If several operands are used, they are separated by commas. A character can come before the instruction, which is then followed by a colon. The comment must, if present, be the last element of the line.

Note: The x, which follows the initial reference type number, represents a five-figure storage location in the user data memory, i.e. the reference 100201 signifies an output or marker bit at the address 201 in the State RAM.

33002214 145

Page 146: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Instruction (LL984)

When programming electrical controls, the user must implement operation-coded instructions in the form of picture objects, which are divided into a recognizable contact form. The designed program objects are, on a user level, converted to computer usable OP codes during the download process. The OP codes are decoded in the CPU and processed by the firmware functions of the controller in a way that the required control is implemented.

Instruction (ST) Instructions are "commands" of the ST programming language. Instructions must be completed by semicolons. Several instructions can be entered in one line (separated by semicolons).

Instruction list (IL)

IL is a text language according to IEC 1131, which is shown in operations, i.e. conditional or unconditional invocations of Functions blocks and Functions, conditional or unconditional jumps etc. through instructions.

INT INT stands for the data type "whole number (integer)". Entries are made as integer literal, base 2 literal, base 8 literal or base 16 literal. The length of the data element is 16 bits. The value range for variables of this datatype reaches from -2 exp (15) to 2 exp (15) -1.

Integer literals Integer literals are used to input whole number values into the decimal system. The values can have a preceding sign (+/-). Single underscores ( _ ) between numbers are not significant.

Example-12, 0, 123_456, +986

INTERBUS (PCP) The new INTERBUS (PCP) I/O drop type is entered into the Concept configurator, to allow use of the INTERBUS PCP channel and the INTERBUS process data pre-processing (PDV). This I/O drop type is assigned the INTERBUS switching module 180-CRP-660-01.The 180-CRP-660-01 differs from the 180-CRP-660-00 only in the fact that it has a clearly larger I/O range in the control state RAM.

Invocation The process by which the execution of an operation is initiated.

Jump Element of the SFC language. Jumps are used to skip zones in the sequence.

J

146 33002214

Page 147: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Keywords Keywords are unique combinations of characters, which are used as special syntactical components, as defined in Appendix B of the IEC 1131-3. All keywords which are used in the IEC 1131-3 and therefore in Concept, are listed in Appendix C of the IEC 1131-3. These keywords may not be used for any other purpose, i.e. not as variable names, section names, instance names etc.

Ladder Diagram (LD)

Ladder Diagram is a graphic programming dialog according to IEC1131, which is optically oriented to the "rung" of a relay contact plan.

Ladder Logic 984 (LL)

The terms Ladder Logic and Ladder Diagram refer to the word Ladder being executed. In contrast to a circuit diagram, a ladder diagram is used by electrotech-nicians to display an electrical circuit (using electrical symbols), which should show the course of events and not the existing wires, which connect the parts with each other. A usual user interface for controlling the actions of automation devices permits a Ladder Diagram interface, so that electrotechnicians do not have to learn new programming languages to be able to implement a control program.The structure of the actual Ladder Diagram enables the connection of electric elements in such a way that generates a control output, which is dependent upon a logical power flow through used electrical objects, which displays the previously requested condition of a physical electrical device.In simple form, the user interface is a video display processed by the PLC programming application, which sets up a vertical and horizontal grid in which programming objects are classified. The diagram contains the power grid on the left side, and when connected to activated objects, the power shifts from left to right.

Landscape Landscape means that when looking at the printed text, the page is wider than it is high.

Language Element

Every basic element in one of the IEC programming languages, e.g. a step in SFC, a function block instance in FBD or the initial value of a variable.

Library Collection of software objects, which are intended for re-use when programming new projects, or even building new libraries. Examples are the libraries of the Elementary function block types.EFB libraries can be divided up into Groups.

K

L

33002214 147

Page 148: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Link A control or data flow connection between graphical objects (e.g. steps in the SFC Editor, function blocks in the FBD Editor) within a section, represented graphically as a line.

Literals Literals are used to provide FFB inputs, and transition conditions etc with direct values. These values can not be overwritten by the program logic (write-protected). A distinction is made between generic and standardized literals.Literals are also used to allocate, to a constant, a value or a variable, an initial value. Entries are made as base 2 literal, base 8 literal, base 16 literal, integer literal, real literal or real literal with exponent.

Local derived data types

Local derived data types are only available in a single Concept project and the local DFBs and are placed in the DFB directory under the project directory.

Local DFBs Local DFBs are only available in a single Concept project and are placed in the DFB directory under the project directory.

Local Link The local network is the network, which connects the local nodes with other nodes either directly or through bus repeaters.

Local macros Local macros are only available in a single Concept project and are placed in the DFB directory under the project directory.

Local network nodes

The local node is the one which is currently being configured.

Located variable A state RAM address (reference addresses 0x, 1x, 3x,4x) is allocated to located variables. The value of these variables is saved in the state RAM and can be modified online using the reference data editor. These variables can be addressed using their symbolic names or their reference addresses.

All inputs and outputs of the PLC are connected to the state RAM. The program can only access peripheral signals attached to the PLC via located variables. External access via Modbus or Modbus Plus interfaces of the PLC, e.g. from visualization systems, is also possible via located variables.

148 33002214

Page 149: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Macro Macros are created with the help of the Concept DFB software.Macros are used to duplicate frequently used sections and networks (including their logic, variables and variable declaration).A distinction is made between local and global macros.

Macros have the following properties:� Macros can only be created in the FBD and LD programming languages.� Macros only contain one section.� Macros can contain a section of any complexity.� In programming terms, there is no difference between an instanced macro, i.e. a

macro inserted into a section and a conventionally created section.� DFB invocation in a macro� Declaring variables� Using macro-specific data structures� Automatic transfer of the variables declared in the macro.� Initial values for variables� Multiple instancing of a macro in the entire program with differing variables� The name of the section, variable names and data structure names can contain

up to 10 different exchange marks (@0 to @9).

MMI Man-Machine-Interface

Multi element variables

Variables to which a Derived data type defined with STRUCT or ARRAY is allocated.A distinction is made here between field variables and structured variables.

Network A network is the collective switching of devices to a common data path, which then communicate with each other using a common protocol.

Network node A node is a device with an address (1...64) on the Modbus Plus network.

Node Node is a programming cell in a LL984 network. A cell/node consists of a 7x11 matrix, i.e. 7 rows of 11 elements.

M

N

33002214 149

Page 150: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Node Address The node address is used to uniquely denote a network node in the routing path. The address is set on the node directly, e.g. using the rotary switch on the back of the modules.

Operand An operand is a literal, a variable, a function invocation or an expression.

Operator An operator is a symbol for an arithmetic or boolean operation which is to be executed.

Output parameter (output):

A parameter, through which the result(s) of the evaluation of a FFB is/are returned.

Output/Marker bits (0x references)

An output/marker bit can be used to control real output data using an output unit of the control system, or to define one or more discrete outputs in the state RAM. Note: The x, which follows the initial reference type number, represents a five-figure storage location in the user data memory, i.e. the reference 000201 signifies an output or marker bit at the address 201 in the State RAM.

Output/marker words (4x references)

An output / marker word can be used to save numerical data (binary or decimal) in the state RAM, or to send data from the CPU to an output unit in the control system. Note: The x, which follows the initial reference type number, represents a five-figure storage location in the user data memory, i.e. the reference 400201 signifies a 16 bit output or marker word at the address 201 in the State RAM.

Peer CPU The Peer CPU processes the token execution and the data flow between the Modbus Plus network and the PLC user logic.

PLC Memory programmable controller

Portrait Portrait means that the sides are larger than the width when printed.

Program The uppermost program organization unit. A program is closed on a single PLC download.

O

P

150 33002214

Page 151: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Program organization unit

A function, a function block, or a Program. This term can refer to either a type or an instance.

Program redundancy system (Hot Standby)

A redundancy system consists of two identically configured PLC machines, which communicate with one another via redundancy processors. In the case of a breakdown of the primary PLC, the secondary PLC takes over the control check. Under normal conditions, the secondary PLC does not take over the control function, but checks the status information, in order to detect errors.

Project General description for the highest level of a software tree structure, which specifies the super-ordinate project name of a PLC application. After specifying the project name you can save your system configuration and your control program under this name. All data that is created whilst setting up the configuration and program, belongs to this super-ordinate project for this specific automation task.General description for the complete set of programming and configuration information in the project database, which represents the source code that describes the automation of a system.

Project database The database in the host computer, which contains the configuration information for a project.

Prototype file (Concept-EFB)

The prototype file contains all the prototypes of the assigned functions. In addition, if one exists, a type definition of the internal status structure is specified.

REAL REAL stands for the data type "floating point number". The entry can be real-literal or real-literal with an exponent. The length of the data element is 32 bits. The value range for variables of this data type extends from +/-3.402823E+38.

Real literals Real literals are used to input floating point values into the decimal system. Real literals are denoted by a decimal point. The values can have a preceding sign (+/-). Single underscores ( _ ) between numbers are not significant.

Example-12.0, 0.0, +0.456, 3.14159_26

R

Note: Dependent on the mathematical processor type of the CPU, different ranges within this permissible value range cannot be represented. This applies to values that are approaching ZERO and for values that approach INFINITY. In these cases NAN (Not A Number) or INF (INFinite) will be displayed in the animation mode instead of a number value.

33002214 151

Page 152: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Real literals with exponents

Real literals with exponents are used to input floating point values into the decimal system. Real literals with exponents are identifiable by a decimal point. The exponent indicates the power of ten, with which the existing number needs to be multiplied in order to obtain the value to be represented. The base can have a preceding negative sign (-). The exponent can have a preceding positive or negative sign (+/-). Single underscores ( _ ) between numbers are not significant. (Only between characters, not before or after the decimal point and not before or after "E", "E+" or "E-")

Example-1.34E-12 or -1.34e-12 1.0E+6 or 1.0e+6 1.234E6 or 1.234e6

Reference Every direct address is a reference that begins with an indicator, which specifies whether it is an input or an output and whether it is a bit or a word. References that begin with the code 6, represent registers in the extended memory of the state RAM. 0x range = Output/Marker bits 1x range = Input bits 3x range = Input words 4x range = Output registers 6x range = Register in the extended memory

Register in the extended memory (6x-reference)

6x references are holding registers in the extended memory of the PLC. They can only be used with LL984 user programs and only with a CPU 213 04 or CPU 424 02.

Remote Network (DIO)

Remote programming in the Modbus Plus network enables maximum performance when transferring data and dispenses with the need for connections. Programming a remote network is simple. Setting up a network does not require any additional ladder logic to be created. All requirements for data transfer are fulfilled via corresponding entries in the Peer Cop Processor.

RIO (Remote I/O) Remote I/O indicates a physical location of the I/O point controlling devices with regard to the CPU controlling them. Remote inp./outputs are connected to the controlling device via a twisted communication cable.

RTU-Mode Remote Terminal Unit The RTU mode is used for communication between the PLC and an IBM compatible personal computer. RTU works with 8 data bits.

Note: The x, which follows each initial reference type number, represents a five-digit storage location in the user data memory, i.e. the reference 400201 signifies a 16 bit output or marker word at the address 201 in the State RAM.

152 33002214

Page 153: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Runtime error Errors, which appear during program processing on the PLC, in SFC objects (e.g. Steps) or FFBs. These are, for example, value range overflows for numbers or timing errors for steps.

SA85 module The SA85 module is a Modbus Plus adapter for IBM-AT or compatible computers.

Scan A scan consists of reading the inputs, processing the program logic and outputting the outputs.

Section A section can for example be used to describe the functioning mode of a technological unit such as a motor.A program or DFB consists of one or more sections. Sections can be programmed with the IEC programming languages FBD and SFC. Only one of the named programming languages may be used within a section at any one time.Each section has its own document window in Concept. For reasons of clarity, however, it is useful to divide a very large section into several small ones. The scroll bar is used for scrolling within a section.

Section Code Section Code is the executable code of a section. The size of the Section Code is mainly dependent upon the number of blocks in the section.

Section Data Section data is the local data in a section such as e.g. literals, connections between blocks, non-connected block inputs and outputs, internal status memory of EFBs.

Separator Format (4:00001)

The first digit (the reference) is separated from the five-digit address that follows by a colon (:).

Sequence language (SFC)

The SFC Language Elements enable a PLC program organization unit to be divided up into a number of Steps and Transitions, which are connected using directional Links. A number of actions belong to each step, and transition conditions are attached to each transition.

Serial Connections

With serial connections (COM) the information is transferred bit by bit.

S

Note: Data which appears in the DFBs of this section is not section data.

33002214 153

Page 154: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Source code file (Concept-EFB)

The source code file is a normal C++ source file. After executing the Library → Create files menu command, this file contains an EFB-code frame, in which you have to enter a specific code for the EFB selected. To do this invoke the Objects → Source menu command.

Standard Format (400001)

The five-digit address comes directly after the first digit (the reference).

Standardized literals

If you would like to manually determine a literal's data type, this may be done using the following construction: ’Data type name’#’value of the literal’.

ExampleINT#15 (Data type: integer, value: 15), BYTE#00001111 (Data type: byte, value: 00001111) REAL#23.0 (Data type: real, value: 23.0)

To assign the data type REAL, the value may also be specified in the following manner: 23.0. Entering a comma will automatically assign the data type REAL.

State RAM The state RAM is the memory space for all variables, which are accessed via References (Direct representation) in the user program. For example, discrete inputs, coils, input registers, and output registers are located in the state RAM.

State RAM overview for uploading and downloading

Overview:

Status Bits For every device with global inputs or specific inputs/outputs of Peer Cop data, there is a status bit. If a defined group of data has been successfully transferred within the timeout that has been set, the corresponding status bit is set to 1. If this is not the case, this bit is set to 0 and all the data belonging to this group is deleted (to 0).

Variables-Editor

RDEEditor

Concept Project database

Variables(Initial values)

State RAM-

Mirror (Image)

for loading fromand/or loading in Signal-memory

PLC-State RAM 0x / 1x / 3x / 4x

U3 D3 D2 U1

U2

D1

154 33002214

Page 155: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Step SFC-language element: Situation, in which the behavior of a program, in reference to its inputs and outputs, follows those operations which are defined by the actions belonging to the step.

Step name The step name is used to uniquely denote a step in a program organization unit. The step name is generated automatically, but it can be edited. The step name must be unique within the entire program organization unit, otherwise an error message will appear. The automatically generated step name is always formed as follows: S_n_m

S = step n = Number of the section (consecutive numbers) m = Number of the step in the section (current number)

Structured text (ST)

ST is a text language according to IEC 1131, in which operations, e.g. invocations of Function blocks and Functions, conditional execution of instructions, repetitions of instructions etc. are represented by instructions.

Structured variables

Variables to which a Derived data type defined with STRUCT (structure) is allocated.A structure is a collection of data elements with generally different data types (elementary data types and/or derived data types).

SY/MAX In Quantum control devices, Concept includes the preparation of I/O-map SY/MAX-I/O modules for remote controlling by the Quantum PLC. The SY/MAX remote backplane has a remote I/O adapter in slot 1, which communicates via a Modicon S908 R I/O System. The SY/MAX-I/O modules are executed for you for labeling and inclusion in the I/O map of the Concept configuration.

Template file (Concept-EFB)

The template file is an ASCII file with layout information for the Concept FBD Editor, and the parameters for code creation.

TIME TIME stands for the data type "time". The entry is time literal. The length of the data element is 32 bits. The value range for variables of this data type extends from 0 to 2exp(32)-1. The unit for the data type TIME is 1 ms.

T

33002214 155

Page 156: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Time literals Permissible units for times (TIME) are days (D), hours (H), minutes (M), seconds (S) and milliseconds (MS) or combinations of these. The time must be marked with the prefix t#, T#, time# or TIME#. The "overflow" of the unit with the highest value is permissible, e.g. the entry T#25H15M is allowed.

Examplet#14MS, T#14.7S, time#18M, TIME#19.9H, t#20.4D, T#25H15M, time#5D14H12M18S3.5MS

Token The network "token" controls the temporary possession of the transfer right via a single node. The token passes round the nodes in a rotating (increasing) address sequence. All nodes follow the token rotation and can receive all the possible data that is sent with it.

Total IEC memory

The total IEC memory consists of the IEC program memory and the global data.

Traffic Cop The traffic cop is an IO map, which is generated from the user-IO map. The traffic cop is managed in the PLC and in addition to the user IO map, contains e.g. status information on the I/O stations and modules.

Transition The condition, in which the control of one or more predecessor steps passes to one or more successor steps along a directed link.

UDEFB User-defined elementary functions/function blocksFunctions or function blocks, which were created in the C programming language, and which Concept provides in libraries.

UDINT UDINT stands for the data type "unsigned double integer". Entries are made as integer literal, base 2 literal, base 8 literal or base 16 literal. The length of the data element is 32 bits. The value range for variables of this data type extends from 0 to 2exp(32)-1.

UINT UINT stands for the data type "unsigned integer". Entries are made as integer literal, base 2 literal, base 8 literal or base 16 literal. The length of the data element is 16 bits. The value range for variables of this data type extends from 0 to (2exp 16)-1.

U

156 33002214

Page 157: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

Unlocated variable

Unlocated variables are not allocated a state RAM address. They therefore do not occupy any state RAM addresses. The value of these variables is saved in the internal system and can be changed using the reference data editor. These variables are only addressed using their symbolic names.

Signals requiring no peripheral access, e.g. intermediate results, system tags etc., should be primarily declared as unlocated variables.

Variables Variables are used to exchange data within a section, between several sections and between the program and the PLC.Variables consist of at least one variable name and one data type.If a variable is assigned a direct address (reference), it is called a located variable. If the variable has no direct address assigned to it, it is called an unlocated variable. If the variable is assigned with a derived data type, it is called a multi element variable.There are also constants and literals.

Warning If a critical status is detected during the processing of a FFB or a step (e.g. critical input values or an exceeded time limit), a warning appears, which can be seen using the Online → Event Viewer...menu command. For FFBs, the ENO remains set to "1".

WORD WORD stands for the data type "bit sequence 16". Entries are made as base 2 literal, base 8 literal or base 16 literal. The length of the data element is 16 bits. A numerical value range can not be assigned to this data type.

V

W

33002214 157

Page 158: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Glossary

158 33002214

Page 159: Concept 2.6 IEC Block Library Part ... - Schneider Electric

CBAIndex

AArithmetic

AVE_***, 23NEG_***, 93SIGN_***, 101

AVE_***, 23Averaging, 23AVGMV, 27AVGMV_K, 33

BBCD_TO_INT, 37BCDConverter

BCD_TO_INT, 37DBCD_TO_DINT, 59DBCD_TO_INT, 61DINT_TO_DBCD, 69INT_TO_BCD, 81INT_TO_DBCD, 83

BIT_TO_BYTE, 39BIT_TO_WORD, 43BYTE_AS_WORD, 47BYTE_TO_BIT, 49

CConversion from 16 Bit BCD to INT, 37Conversion from 32 Bit BCD to DINT, 59Conversion from 32 Bit BCD to INT, 61Conversion from DINT to 32 Bit BCD, 69Conversion from INT to 16 Bit BCD, 81

33002214

Conversion from INT to 32 Bit BCD, 83Converter

BIT_TO_BYTE, 39BIT_TO_WORD, 43BYTE_AS_WORD, 47BYTE_TO_BIT, 49DINT_AS_WORD, 67REAL_AS_WORD, 97TIME_AS_WORD, 105UDINT_AS_WORD, 119WORD_AS_BYTE, 121WORD_AS_DINT, 123WORD_AS_REAL, 125WORD_AS_TIME, 127WORD_AS_UDINT, 129WORD_TO_BIT, 131

CounterCTD_***, 51CTU_***, 53CTUD_***, 55DIVMOD_***, 71

CTD_***, 51CTU_***, 53CTUD_***, 55

DDBCD_TO_DINT, 59DBCD_TO_INT, 61Dead zone, 63DEAD_ZONE_REAL, 63Detecting and holding with rising edge, 99

159

Page 160: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Index

Detection of all types of edges, 117DINT_AS_WORD, 67DINT_TO_DBCD, 69Division and Modulo, 71DIVMOD_***, 71Down counter, 51

EEdge detection

TRIGGER, 117EXTENDED

TOF_P, 107TON_P, 111

ExtendedAVE_***, 23AVGMV, 27AVGMV_K, 33BCD_TO_INT, 37BIT_TO_BYTE, 39BIT_TO_WORD, 43BYTE_AS_WORD, 47BYTE_TO_BIT, 49CTD_***, 51CTU_***, 53CTUD_***, 55DBCD_TO_DINT, 59DBCD_TO_INT, 61DEAD_ZONE_REAL, 63DINT_AS_WORD, 67DINT_TO_DBCD, 69DIVMOD_***, 71HYST_***, 73INDLIM_***, 77INT_TO_BCD, 81INT_TO_DBCD, 83LIMIT_IND_***, 85LOOKUP_TABLE1, 89NEG_***, 93REAL_AS_WORD, 97SAH, 99SIGN_***, 101TIME_AS_WORD, 105TRIGGER, 117UDINT_AS_WORD, 119

160

WORD_AS_BYTE, 121WORD_AS_DINT, 123WORD_AS_REAL, 125WORD_AS_TIME, 127WORD_AS_UDINT, 129WORD_TO_BIT, 131

FFloating mean with fixed window size, 27Floating mean with frozen correction factor, 33Function

Parameterization, 15, 16Function block

Parameterization, 15, 16

HHYST_***, 73

IIndicator signal for delimiters with hysteresis, 77Indicator signal for maximum value delimiter with hysteresis, 73INDLIM_***, 77INT_TO_BCD, 81INT_TO_DBCD, 83

LLimit with indicator, 85LIMIT_IND_***, 85LOOKUP_TABLE1, 89

33002214

Page 161: Concept 2.6 IEC Block Library Part ... - Schneider Electric

Index

MMeasurement

AVGMV, 27AVGMV_K, 33DEAD_ZONE_REAL, 63HYST_***, 73INDLIM_***, 77LOOKUP_TABLE1, 89SAH, 99

NNEG_***, 93Negation, 93

OOff Delay with Pause, 107On Delay with Pause, 111

PParameterization, 15, 16

RREAL_AS_WORD, 97

33002214

SSAH, 99Selection

LIMIT_IND_***, 85Sign evaluation, 101SIGN_***, 101

TTIME_AS_WORD, 105Timer

TOF_P, 107TON_P, 111

TOF_P, 107TON_P, 111Traverse progression with 1st degree interpolation, 89TRIGGER, 117Type conversion, 39, 43, 47, 49, 67, 97, 105, 119, 121, 123, 125, 127, 129, 131

UUDINT_AS_WORD, 119Up counter, 53Up/down counter, 55

WWORD_AS_BYTE, 121WORD_AS_DINT, 123WORD_AS_REAL, 125WORD_AS_TIME, 127WORD_AS_UDINT, 129WORD_TO_BIT, 131

161