Compatibility Report Comtrol IO-Link Master Contrinex DW-AD-603-03

Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

Compatibility Report

Comtrol IO-Link Master

Contrinex DW-AD-603-03

Page 2: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 2

Contents

Contents .................................................................................................................................................................................. 2

Test Report Overview ............................................................................................................................................................. 3

IO-Link Master - IO-Link Diagnostics Page ............................................................................................................................. 3

Configuring IO-Link Settings ................................................................................................................................................... 4

After Configuring Port-Friendly Names ................................................................................................................................... 5

Setting Up Passwords ............................................................................................................................................................. 6

DW-AD-603-03 Configuration ................................................................................................................................................. 7

Loading IODD Files ............................................................................................................................................................. 7

Verifying that the Correct IODD Files Are Loaded ............................................................................................................ 10

Changing Parameters on the DW-AD-603-03 with the GUI ................................................................................................. 11

Using the Device Validation Feature ..................................................................................................................................... 13

Incompatible Device Attached to Port ............................................................................................................................... 13

Page 3: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 3

Test Report Overview

The Contrinex inductive, DW-AD-603-03 sensor operates properly with the Comtrol IO-Link Master. This report contains the following topics:

• IO-Link Master – IO-Link Diagnostics page

• Configuring IO-Link settings

• Setting up passwords

• Configuring the sensor with the IODD file

• Using the Device Validation feature

The sensor was tested using Application Base v1.4.14 on the IO-Link Master DR-8-EIP (machine mountable IP67). This report does not illustrate all Comtrol IO-Link Master features, such as: EtherNet/IP and Modbus/TCP configuration, uploading the latest software, or network configuration. In addition, it does not discuss data storage as this is an IO-Link v1.0 sensor.

IO-Link Master - IO-Link Diagnostics Page

Upon connection to the IO-Link Master, the DW-AD-603-03 immediately displays in the IO-Link Diagnostics page without any configuration.

Page 4: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 4

Configuring IO-Link Settings

There is no configuration required to getting the IO-Link device operating. It is not even necessary to configure the Minimum Cycle Time, as the IO-Link Master negotiates the required Cycle Time with each IO-Link device.

This example shows configuring friendly port names. The Device Validation feature is discussed later in the report.

Page 5: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 5

After Configuring Port-Friendly Names

The IO-Link Diagnostics page now displays friendly the Port Name.

Page 6: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 6

Setting Up Passwords

The IO-Link Master ships from the factory without passwords and administrative permissions are granted. You can use the Advanced | Accounts page to set up passwords for the IO-Link Master. Admin, Operator, and User permissions are defined in the help system on the Accounts page.

Page 7: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 7

DW-AD-603-03 Configuration

You can use the Comtrol IO-Link Master to configure the IO-Link device. When an IODD file is loaded on the IO-Link Master, you can use the GUI on the top of the IO-Link Device – Port page to change parameter settings. If an IODD file is not loaded, you can use the ISDU Interface on the bottom of the IO-Link Device – Port page

This section discusses the following topics:

• Loading IODD files

• Verifying that the correct IODD file is loaded

• Changing IO-Link device parameters using the GUI

Loading IODD Files

IODD file packages must be unzipped and the appropriate files located and re-zipped or loaded individually.

1. Click Attached Devices | IODD Files.

2. Click the UPLOAD FILE button.

3. Click the CHOOSE FILE button.

Page 8: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 8

4. Select the file set (zip) or xml file to upload and click the UPLOAD button. If there are files in the IODD file set that are not required by the associated xml file, the IO-Link Master does not load the files, and displays an Ignored Files message, click Ok.

5. The IODD Files page now displays the IODD files loaded on the IO-Link Master.

Page 9: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 9

6. If you want to view the xml file, click the corresponding IODD FILENAME in the table.

7. Optionally, click the hyperlink to view the xml file in your browser.

Page 10: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 10

Verifying that the Correct IODD Files Are Loaded

Use the IO-Link Device Configuration Summary page to verify that the correct IODD files for the attached IO-Link devices have been loaded on the IO-Link Master. The correct file is loaded if an xml file name displays in the IODD Name field.

Page 11: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 11

Changing Parameters on the DW-AD-603-03 with the GUI

1. The DW-AD-603-03 displays as expected in the PORT page.

2. Click the EDIT button to make parameter changes. In this example, these parameters were changed:

• Index 1 Sub-index 1 and 2 = 2

• Index 1 Sub-index 5 = 0

Page 12: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 12

3. Click the SAVE button, observe that the settings were changed.

Page 13: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 13

Using the Device Validation Feature

The DW-AD-603-03 supports Compatible Device Validation.

This report does not illustrate Identical Device Validation because a serial number is required for identical device validation.

Incompatible Device Attached to Port

1. In the IO-Link Configuration page, click EDIT, set Device Validation mode to Compatible.

2. Click the GET ATTACHED button.

3. Click SAVE.

4. Remove the DW-AD-603-03 and connect another IO-Link device (not a DW-AS-733-M12).

Page 14: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 14

5. The IO-Link LED on the IO-Link Master is now flashing red to indicate that an incompatible device is connected to the port. In addition, the IO-Link Diagnostics page displays that an incompatible device is attached to the port.

Page 15: Comtrol IO-Link Master and ifm TN25314/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 Page | 7 DW-AD-603-03 Configuration You can use the Comtrol IO-Link Master to configure

4/26/2016 Comtrol IO-Link Master | Contrinex LLR-C23PA-NMS-404 P a g e | 15

6. Re-attach the DW-AD-603-03 and notice that it immediately begins operating.