Click here to load reader
Upload
vudang
View
212
Download
0
Embed Size (px)
Citation preview
1
Abstract—This paper studies the use of a voltage source
converter (VSC) with DC capacitors as energy storage medium
for the compensation of pulsating active and reactive power of
CERN’s proton synchrotron (PS) particle accelerator. The PS
accelerator load demands periodic, active and reactive power
pulses of about 2s duration and a magnitude of up to 45MW and
65Mvar. The proposed compensator is able to control both
reactive and active power exchange with the network in order to
eliminate network disturbances. The controllability study reveals
that the best control strategy is to use q-axis converter input for
active power and d-axis input for reactive power regulation. An
analytical system model is created to study the system dynamics
and to aid the controller design. The eigenvalue study with the
MATLAB model reveals that, with large energy storage units and
small converter losses, there is only a small interaction between
the control channels. The final testing is done with a detailed
non-linear model in PSCAD/EMTDC. The simulation results
show that it is possible to fully compensate the active power
exchange with the network during typical accelerator cycles, and
at the same time to achieve excellent AC voltage control.
Index Terms— State space methods, Root Loci, Eigenvalues.
Accelerator power supply, Proton accelerators, Energy storage,
Pulse width modulated power converters.
I. INTRODUCTION
CERN, the European Organization for Nuclear Research, is
an international organisation with 20 Member States. It’s
objective is to provide for collaboration among the European
States in the field of high-energy particle physics research.
CERN designs, constructs and operates the necessary particle
accelerators and the associated support equipment.
For a power system, particle accelerators represent heavily
pulsating electric loads with a variable power factor, which is
mainly caused by the twelve-pulse and six-pulse thyristor
converters. Because of the large magnitudes and short rise
times of the pulsating power, rapid reactive power
compensation and voltage control is necessary. In addition,
dedicated filtering is required to eliminate the harmonics
generated by the power converters. For this purpose, CERN is
currently operating nine 18kV Static Var Compensators (SVC)
with an installed total power of more than 500Mvar [1].
The Proton Synchrotron (PS) is the oldest and the most
versatile of CERN's accelerators, which has diameter of 200
meters and reaches a final energy of 28GeV. At present, the PS
D. Jovcic is with University of Aberdeen, Aberdeen, AB24 3UE, UK [email protected]
K. Kahle is with CERN’s Electric Power Systems Group, CH-1211 Geneva
23, Switzerland. [email protected]
complex can accelerate all stable and electrically charged
particles (electrons, protons), their antiparticles (positrons,
antiprotons), and different kinds of heavy ions (oxygen, sulfur,
lead), which are then injected into the larger rings for further
acceleration.
The PS accelerator is continuously pulsating with a cycle
time of about 2s. The largest cycles (pulse 1) require power of
up to 45MW and 65Mvar at the cycle peak, and have a rise
time of 600ms, as seen in Figure 1.
In order to limit disturbances to other loads, the PS is
decoupled from the network using a motor-generator supply.
An integrated large rotating mass serves as a storage medium
for smoothing the power pulses. The 6MW supply motor
represents a stable load to the 18kV CERN network.
By now, the rotating machines have been in service for over
34 years, and CERN has initiated an investigation of
compensation options based on FACTS [2] technology.
Initially, the option of a conventional thyristor-based SVC
and a more modern STATCOM [2] for reactive power
compensation was explored, confirming that good 18kV AC
voltage regulation is possible. However, the remaining steep
pulses of active power gave concern related to periodic torque
variations at the small generators in the local supply network.
This initiated the study of a technical solution with active and
reactive power compensation.
This paper presents the study of the use of a Voltage Source
Converter (VSC) with DC energy storage elements for the
compensation of pulsating active and reactive power.
A STATCOM is also able to regulate active power
exchange if an energy storage medium is connected to the DC
side. Various options exist for the storage media, including
batteries, fuel cells, capacitors, supercapacitors and Super-
conducting Magnetic Energy Storage (SMES) [3].
Considering the fast power dynamics and high number of the
PS accelerator operating cycles, batteries or fuel cells would
not provide optimal dynamics and long-term reliability [3],
and the adequate medium would be only SMES,
supercapacitors or DC capacitors. STATCOM with SMES is
suggested [4],[5] as a possible solution for larger energy
storage (mainly over 50MJ) with fast dynamic response. On
the downside, such an element incorporates the main converter
with a bi-directional DC-DC chopper which increases
compensator losses. Also, because of the SMES technology
and the converter capital investment, at present such an
element may not be an economically viable solution for the
required energy storage level. As an outcome, DC capacitors
are selected as the storage medium.
A STATCOM with large DC capacitors will require
different design approaches and much different control
Compensation of Particle Accelerator Load
Using Converter Controlled Pulse Compensator D. Jovcic, Member IEEE and K. Kahle
2
strategies from the conventional STATCOM. This
compensation element is labeled Converter Controlled Pulse
Compensator (CCPC) to distinguish from the name
STATCOM with energy storage, which is frequently used
with SMES. The aim of this study is to investigate using a
CCPC for the PS particle accelerator compensation.
The paper firstly describes the modeling of the PS particle
accelerator. The design section briefly describes calculations
of main compensator parameters and the control strategy in
more detail. Simulation results with a non-linear digital
simulation are presented in the last section.
-45
-35
-25
-15
-5
5
15
25
35
45
55
65
0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6
Time [sec]
Active P. [MW], Reactive P. [MVAr] Pulse 1
Pulse 2
P -[MW]
P -PSCAD
Q -[MVAr]
Q -PSCAD
Figure 1 PSCAD/EMTDC model verification for two typical Proton
Synchrotron pulses. The P and Q curves are obtained by measurements on the
actual system.
II. PROTON SYNCHROTRON MODELING
The PS accelerator supply consists of two twelve-pulse
thyristor converters that supply DC power to the accelerator
magnets. The main electrical circuit is shown in Figure 2,
together with the proposed future supply configuration. The
PS control system consists of two control levels. The inner,
fast level has two DC voltage feedback control loops, one for
each twelve-pulse group. At the outer control level, there is a
DC current control loop, which has the role of keeping the
firing angle within the operating range. It also prevents a
commutation failure in the inversion operating mode. The
external input signal for PS control is the DC current
reference, which has the shape of square pulses. These
reference pulses are pre-calculated in the technical control
room on the basis of the accelerator cycle demand.
The system model is developed with a PSCAD/EMTDC [6]
simulator. Some control circuit parameters are not known;
thus they are estimated to match the measured power curves.
Figure 1 shows that the PSCAD/EMTDC model achieves
excellent matching against the power measurements.
In addition, a MATLAB-based small signal linear model is
developed to enable dynamic studies, as discussed below.
III. CCPC DESIGN
The simplified circuit of the CCPC compensator is
presented in Figure 2. The element consists of a two-level
VSC and large DC capacitors. It is connected to the 18kV
network using a reactor Ls, without the need for a transformer.
Based on the load power demand in Figure 1, a rating of
35MVA for the harmonic filters and ±55MVA for the converter is chosen to enable adequate control margin.
The reactor Ls is selected on the basis of the maximum
harmonic current and the maximum DC voltage deviations.
Sinusoidal PWM control is assumed with the pulse number of
27 (ratio between triangular career frequency and the sine
wave frequency). According to converter theory [7] the 25th
harmonic will have the largest magnitude. The harmonic
current through the converter can be determined using basic
circuit equations and assuming AC filters (zf) are tuned to this
harmonic frequency. Figure 3 shows the 25th harmonic current
as a function of reactor size. A reactor size of Ls=6mH is
chosen to keep the harmonic current below 7% of the
fundamental value. Note that this current is not injected in the
network since it is eliminated by the filters. Higher value for
Ls would improve the harmonic profile but it would also lead
to larger DC voltage variations. A higher DC voltage
requirement, on the other hand, implies reduced voltage range
available for the energy storage, resulting in increased
capacitor rating.
The DC capacitor size is determined considering the
energy storage requirements. With reference to Figure 1, the
positive and negative energy requirement for the largest power
pulse is determined as the surface under the active power
curve:
zac400
~
18/2.12kV
Y/Y
Y/Y DC
filters
main
magnets
Proton synchrotron
Supply network
Compensator
DC
filters
18/2.12kV400/18kV
18kV
4km cable CB
Y/
Y/
Vdc1
Vdc2
z f
ac
ps
s
dc
LR
I
I
I ,
I
α
α
P ,Q
I
I
V
I
V
V
VSC
C
C
ss
s
dc
ls ls
psdc
ps2
ps1
ls
f
c
s
s
Figure 2 Proton synchrotron with the proposed supply configuration.
3
MJE
MJE
pulse
pulse
112/55.040
5.19154.02/6.045
1
1
=×=
=×+×=
−
+ (1)
The aim is to develop a compensator that can fully supply
and absorb the pulse energy and in this way eliminate any
power variation from the supply network. In an ideal
compensation case, the network supplies only the PS power
consumed and losses over a cycle. Taking the difference
between Epulse1+ and Epulse1- we obtain the energy consumed
during one pulse. The average power supplied from the
network can be calculated as Pav=5.5MW, which does not
include the converter losses. Subtracting the energy supplied
from the network, and assuming some margin for converter
losses we obtain the maximum energy demand for the
compensator of Emax=16.0MJ.
DC capacitors exchange energy on the basis of their
voltage variations as:
( )2min
2max
2DCDC
totCCPC VV
CE −= (2)
At present, commercially available VSC’s have maximum
DC voltages of about VDCmax=60kV. The minimum DC voltage
is limited by the requirement for reactive power control. At
any level of stored energy, full reactive power exchange must
be possible to enable AC voltage control. Therefore, the
minimum voltage VDCmin must be greater than the maximum
DC voltage required for reactive power control. Figure 4
shows the reactive power control operating curve for the
CCPC assuming the reactor size as discussed above. The
lowest Vdc curve is the DC voltage variation across reactive
power exchange range assuming that control magnitude is
Mm=1. The PWM magnitude input (Mm) regulates the AC
voltage as presented below. The maximum voltage in the
curve with maximum Mm determines the minimum DC
voltage for storage range, which is VDCmin=36kV.
The converter AC voltage curve in Figure 4 (Vs) is
uniquely determined on the basis of the reactive power
exchange requirement. The AC voltage regulation at higher
DC voltage levels is achieved by reducing the control signal
magnitude Mm as shown with the curves in the storage region.
As the basic energy storage units we are considering the
commercially available DC capacitors C1=2.4mF and
V1dc=6kV. A total of 580 of these units (10 in series by 58
parallel) would have Ctot=Cs/2=13.92mF and according to (2)
their stored energy is just above the required value of 16MJ.
IV. CONTROLLABILITY ANALYSIS
A. Controller based on dynamic decoupling
This section investigates the control strategy for the
CCPC. Since there is a requirement for two control loops, one
for AC voltage control and the other for active power control,
the main design challenge is to develop high gain controllers
without cross-coupling between the control channels.
A decoupled control method has been suggested as the
control strategy for VSC converters in [5] and [8], which is
discussed firstly. The basic electrical equations for the CCPC
Ls
Figure 3. Series inductance Ls selection on the basis of harmonic current.
Vdc (Mm
=1)
Vs
storage
region
Vdc (Mm
=0.8)Vd
c (Mm
=0.67
)
Vdc (Mm
=0.4)
Figure 4. Operating curve for reactive power compensation.
in Figure 2 can be obtained by applying the rules for d-q
transformation [5],[9], since the AC voltage with a PWM
controlled converter is Vsd=0.5MdVdc, Vsq=0.5MqVdc,:
acddcdsqosdssd
s VVMIIRdt
dIL +−−−= 5.0ω (3)
acqdcqsdosqs
sq
s VVMIIRdt
dIL +−+−= 5.0ω (4)
where ωo=2π50[rad/s], and subscripts d and q denote corresponding components. Md and Mq are the rectangular
frame components of the control signal M (Mm and Mϕ are polar components) for the two-level PWM controller
converter. Rs represents the internal losses in the converter.
Assuming that the co-ordinate frame is attached to the AC
voltage (Vacm=Vacd), active and reactive power are controlled
using the respective converter currents:
sdacmIVP 3= , sqacmIVQ 3= (5)
where Vacm is the magnitude of the 18kV bus voltage.
It is evident that a control signal (Md or Mq) will affect both
Id and Iq in either of the equations. If however, the control
signal is made to linearise and decouple the currents in
equations (3) and (4) we have [5],[8]:
dcdxsqod VMIM /)(2 += ω (6)
dcqxsdoq VMIM /)(2 +−= ω (7)
4
where Mdx and Mqx are the external inputs for PI control.
Substituting (5-6) in (3-4) we obtain:
acddxsdssd
s VMIRdt
dIL +−−= (8)
acqqxsqs
sq
s VMIRdt
dIL +−−= (9)
In (8-9) it is seen that we have a decoupled controller that
enables independent control along the two channels with no
cross-interactions. In [8], a more advanced version is proposed
with internal predictive control that relies to a lesser degree on
the external current measurements. Although this controller
showed good results in our PSCAD/EMTDC simulation, it
gave inferior performance to the controller presented in
section B below. The weak performance is attributed to the
following:
• The controller requires the variables Id and Iq at a high
bandwidth in order to enable effective linearization. In
practice this is difficult to achieve because of the high
noise content on the AC signals as well as the PLL
dynamics, which affect the accuracy of measurements.
The predictive controller [8] improves responses by
calculating currents internally using the controller
outputs, but in case of external disturbances (Vac changes)
the currents can still have large transient peaks. As
simulation results below show, the Vac disturbances can
be large because of presence of PS converters with pulsed
operation.
• The coefficients (ωo) with the terms that we are canceling are much larger than the terms Rs and Ls. Even
small error (or delay) in the decoupling circuit will cause
large interactions.
• The controller has three control levels just for current
control, and additional two levels are required for DC
voltage and power control which would make it overly
complex.
The above issues limit the magnitude of feedback gains and
this deteriorates performance.
B. Controller based on static equations
In the alternative strategy, we analyse the steady-state
controllability by neglecting the dynamic terms. The CCPC
current and voltage equations are:
( ) ssacms zVVI −= (10)
jVVV sqsds += , ( soss LjRz ω+= ) (11)
Substituting (11) in (10) the converter current components
are obtained as:
( )
( )22sos
sqsossdacm
sdLR
VLRVVI
ω
ω
+
−−= (12)
( )( )( )22
sos
acmsdsosqs
sqLR
VVLVRI
ω
ω
+
−+−= (13)
In the above equations we have cross-coupling, i.e. one
control voltage (Vsd or Vsq) affects both current components.
Assuming now 0=sR , from (12,13) we obtain:
sosqsd LVI ω/−= , ( ) soacmsdsq LVVI ω/−= (14)
Substituting (14) in the basic equations for VSC power (5)
we obtain:
sosqacm LVVP ω/3−= , ( ) sosdacm LVVVQ ω/3 18−= (15)
Equation (15) shows that it is possible to independently
control P or Q by controlling q or d components of the VSC
voltage in the following manner:
Active power control using q voltage component,
Reactive power control using d voltage component.
The interactions are therefore low for small Rs. In addition,
the gain is larger in the desired direction in (15) if Ls is
smaller.
The above-considered ideal case (Rs=0) would lead to
completely decoupled control, implying no interactions
between the two control channels. However, in practice there
will be a small resistance Rs, which depends on the converter
topology, the pulse number, type of switches and the snubber
circuit. For the selected topology in our system a conservative
value for the resistance is Rs=0.24Ω (assuming 650kW losses at the average current of 0.95kA). This resistance value is now
used to analyze the realistic steady-state control and the extent
of the unwanted cross-coupling between the channels.
Assuming a typical operating point at Q=-25Mvar, P=-
2MW (results are similar for other operating points), we
analyse interactions between the channels as shown in Figure
5. In Figure 5 a), which is obtained for a ±20% change in the d-component of the CCPC AC voltage Vsd, it is seen that Q
changes approximately 60% and P changes 10% of its full
range, and therefore the interaction between channels is small.
Ideally P should remain at zero for this input. Similar analysis
is performed with Vsq changed by a factor of 5 (the gain is
lower along q axis), and the results are shown in Figure 5 b).
We observe that the active power P will change 25% of the
full range while reactive power Q changes only by 3-4%. It is
concluded that there is no need to use control compensation
for interactions of such small magnitude.
The above study only covers the steady-state operation,
whereas during transient conditions there will still be cross-
coupling between the control channels as seen in (3) and (4).
The dynamic control analysis is presented in the next section.
P
Q
P
Q
Figure 5. CCPC active and reactive power change a) as Vsd changes by
±20%., b) as Vsq changes by a factor of 5.
5
ki1*1/s
kp1
KPfPload
Qload
d(Qload)/dt
KQf
KQdf
+ +
+
+
+
+
++
Vacmref
feedforward
signal
control signal
components
PS load
measurements
18kV AC voltage controller
Power controller DC voltage controller
Vacm
MdMd Mm
Mq
Mϕ
ki2*1/s
kp2
++
+Vdcref
Vdcrefm
Plref
Vdc
Vdc
Vdc
Pls
Mq
ki3*1/s
P/Vdc
kp3
+
+1/s+
Hzn 180
1
=ω
Hzn 80
1
=ω
Hzn 20
1
=ω
a/b
b
a
a/b
b
a
Figure 6. Converter Controlled Pulse Compensator control system.
V. CONTROLLER STRUCTURE
The controller structure is shown in Figure 6. The
controller consists of two independent units: the AC voltage
controller and the active power controller.
The AC voltage controller is a conventional PI type
controller with a feedback of the 18kV AC voltage magnitude
Vacm. Because of the fast power variations of the PS
accelerator, we use additional direct compensation of the
disturbances by measuring PS reactive power Qload, reactive
power differential dQload/dt and the active power Pload.
These three signals could be directly measured on the AC side,
at the 18kV substation, however the following difficulties
might arise:
The measurement of AC variables has a low bandwidth
since vector transformation is employed and resulting
harmonics must be filtered,
The actual disturbance originates on the DC side of the
load (the DC voltage reference for PS), and measuring
the AC variables gives only a filtered disturbance.
The basic converter equations [9] are used to achieve
estimation of the above AC side variables by measuring the
DC side variables of the PS. Figure 7 outlines the principle of
this estimation, enabling much wider bandwidth feed-forward
signals. The input signals in Figure 7 are the PS converter
firing angle (αps) and the PS DC current (Ipsdc), whereas it is assumed that the AC voltage is constant since DC variables
undergo larger changes.
The active power controller consists of two stages: DC
voltage controller and power controller. The DC voltage
controller is required for two main reasons:
In case of no load, the VSC operates as an AC voltage
controller only, and DC voltage is kept at the constant
minimum value to minimize losses.
The DC voltage controller safeguards the DC voltage
limits and overrides the power controller if these are
violated.
The power controller is of PI type regulating the total
power exchange with the network (Pls). This controller also
includes an additional integrator to enable tracking of DC
voltage ramps.
It should be noted that special anti wind-up feedback
circuits (not shown in Figure 6) are also required to eliminate
winding up of the series connected integrators.
VI. CONTROLLER DESIGN
A. Small signal linear model
In order to analyze the dynamics of the above system and to
determine the controller parameters, a small-signal analytical
model is created. This is a state-space linearized model with
the structure presented in Figure 8. The model consists of two
state-space represented subunits, which are coupled together
using the interaction matrices and variables as presented in
[10]. The AC system model includes the cable and filters, and
the state-space VSC converter modeling follows the modeling
approaches presented in [11]. The load is not included in this
model (it is a disturbance in Figure 8), because of complexity.
Also the feed-forward control gains are not considered; they
are introduced at the latest testing stage in PSCAD/EMTDC.
α α
Ipsdc IpsdcPload
Qload
dQ/dtP=F1(Ipsdc,α ) Q=F2(Ipsdc,α )
ps ps
psps
Figure 7. The principle of estimation of PS active and reactive power by measuring the DC side variables. The AC voltage Vac is assumed constant.
DC voltage
controller
AC voltage
controller
Power
controller
CCPC AC
systemVdcref
VdcMq
Vac
Is
Ips
disturbance
Md
Pls
Plsref
Vacmref
Vacm
DC co-ordinate frame
D-Q rotating
co-ordinate
frame Figure 8. Structure of the simplified linear model.
6
PSCAD
MATLAB
time [s] time [s]
AC voltage [pu]
DC voltage [kV]
a) b)
PSCAD
MATLAB
Figure 9. System model response after a) +5% on AC voltage reference
(Vacmref), and b) -10% step input on DC voltage reference (Vdcref). (The gains are those used in final design with PS load and PSCAD simulation).
The model is coded in MATLAB and it enables the
eigenvalue and frequency domain design techniques, which do
not exist in PSCAD/EMTDC. Figure 9 is the verification test
of the analytical model against non-linear PSCAD/EMTDC
simulation, where very good accuracy is observed.
B. AC voltage and DC voltage control
This section studies the system dynamics using the root
locus method and assuming that only the DC voltage
controller is active on q-control input. In the study, the gains
of one controller are varied whereas the gains on the other
controller(s) are fixed at the optimum values. Also, only the
dominant eigenvalues are observed considering that the model
is of high order.
In all root-locus Figures diamonds represents the open loop
system. The selected location is the optimal value of the gains,
determined in the final simulations in PSCAD/EMTDC.
Studying solely the root locus much larger gains could be
adopted in many cases. However the noise and non-linearities
in the practical system will impose lower limits on the gains.
Figure 10 shows the root locus for the AC voltage
controller, assuming that the controller zero (-ki1/kp1) is pre-
selected. A larger controller zero will move the locus branch
to the left increasing the response speed, but wide-bandwidth
control is difficult in a practical system because of the
converter harmonics. The open loop eigenvalues on branch B
are those selected with q-input controller, as presented later in
Figure 11. It can be observed that the AC voltage controller
affects predominantly the eigenvalue branch A.
Figure 11 shows a similar root-locus analysis with the DC
voltage controller. The open-loop eigenvalues on branch A are
those selected in the design stage in Figure 10. It is seen that
the DC voltage controller moves only the eigenvalues on
branches B and C, where the C branch limits the achievable
speed of response.
From Figures 10 and 11 it is deduced that the two control
channels (along d and q axis) have largely decoupled
dynamics. These are important conclusions since as the
consequence:
• It is possible to use independent and sequential
controller design,
• If one control loop is broken, the other loop is not
much affected.
Figure 11 also shows the root locus when the CCPC
reactance Ls increases 5 times (B’,C’ branches), and evidently
in this case the system is more difficult to control. Therefore a
balance must be achieved since large Ls would be beneficial in
reducing the harmonic level.
Re
Im
C
A
Bselected
location
Figure 10. Root locus for the AC voltage controller. The open loop system
consists of the DC voltage controller.
Re
Im
A
CC’
B’B
selected
location
B’, C’ locus with Ls increased 5 times
Figure 11. Root locus for the DC voltage controller. The open loop system consists of the AC voltage controller.
C. AC voltage and Power controller
This section studies the dynamics in case that a power
controller is used in addition to the DC voltage controller with
the q axis control. During normal operation, the CCPC is
expected to frequently change between DC voltage and power
control modes and therefore both modes should have
satisfactory performance.
Figure 12 shows the root locus for the power controller
where the open loop system has DC voltage and AC voltage
controller gains as selected in Figures 10 and 11. It is seen that
the eigenvalues on branches B and C change position whereas
branch A is very short and very little interactions will result
with the d-axis controller. Comparing with the Figure 11, it is
seen that adding the power control mode has similar effect as
increasing the DC voltage gains.
Figure 13 shows the AC voltage controller root locus with
the power controller gains from Figure 12. There is only
marginal interaction with d-axis control as evident by the short
branch C. It is also seen that AC voltage control has faster
dynamics than the DC voltage control (as also confirmed in
Figure 9), which is the result of the large DC capacitance with
CCPC. The final controller gains are obtained by tuning in
PSCAD/EMTDC and their values are shown in the Appendix.
Note that the feed-forward gains have relatively small values
and minimal influence on the system dynamics, however they
contribute reducing the AC voltage peaks during PS cycles.
The converter losses Rs in our model cannot be accurately
determined. Since this parameter depends also on the
converter topology it would be meaningful to investigate
7
Re
Im
A B
C
selected
location
Figure 12. Root locus for the power controller. The open loop system consists of the DC voltage controller and AC voltage controller.
Im
C’ C
A
A’ B’
B
Re
A’,B’,C’ locus with 3 times increased Rs
Figure 13. Root locus for the AC voltage controller. The open loop system
consists of the DC voltage controller and the power controller.
the dynamic cross-coupling for different Rs. Figure 13 also
shows the AC voltage controller root locus with converter
resistance increased by a factor of 3. It is observed that branch
B’ is significantly longer implying stronger interactions
between the two control channels. In addition, the root locus
for the AC voltage controller (A’) moves towards Im axis and
it is less favorable in terms of stability and performance. This
indicates potential control problems with high-loss converter
concepts or with higher switching frequencies.
In our studies the following factors are found to negatively
influence the system stability:
• Increased converter losses Rs,
• Increased connecting reactance Ls,
• Reduced converter DC capacitance Cs.
• The power control mode shows slightly more
interactions than DC voltage control.
In case of the above system parameters which result in
more control interactions, the decoupling method from section
IV A) might offer the best performance. It is also mentioned
that even wide variations in the AC system impedance show
only minimal changes in the system dynamics.
VII. SIMULATION RESULTS
Figure 14 shows the PSCAD/EMTDC simulation of a
single PS cycle (pulse 1) when compensated with CCPC. The
first part of the simulation (between 0.7s and 1.9s), is the
capacitor charging period which is shown for completeness.
Figure 14a) shows that the active power exchange with the
network (Pls) remains approximately constant at 7MW. Note
that the power reference of 7MW accounts for the PS
accelerator and converter losses over the particular cycle. For
ideal compensation it should be adjusted individually for each
PS cycle. The reactive power exchange (Qls) is almost zero.
In Figure 14b) we observe excellent control of the AC
voltage. There is a 2.5% peak-to-peak deviation at the instant
of power reversal, which is very difficult to eliminate.
-45-40-35-30-25-20-15-10-505101520253035404550
0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1 2.3 2.5 2.7 2.9 3.1 3.3 3.5 3.7 3.9
Time [s]
Active Power [MW]
P -PSCAD
Pls Plsref
Charging period Pulse operation
P -PSCAD
Plsref
Pls
Qls
a) Active and reactive power exchange.
0.98
0.985
0.99
0.995
1
1.005
1.01
1.015
1.02
0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1 2.3 2.5 2.7 2.9 3.1 3.3 3.5 3.7 3.9
Time [s]
AC Voltage [pu]
Vac rms
Vref
b) 18kV AC voltage.
-14
-12
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
16
18
0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1 2.3 2.5 2.7 2.9 3.1 3.3 3.5 3.7 3.9
Time [s]
Control angle [deg]
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
Control magnitude
control angle
control magnitude
c) Converter control variables (control magnitude Mm, control angle Mϕ).
25
30
35
40
45
50
55
60
65
0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1 2.3 2.5 2.7 2.9 3.1 3.3 3.5 3.7 3.9
Time [s]
DC Voltage [kV]
0.8
0.9
1
1.1
1.2
1.3
1.4
1.5
1.6
current [kA]
CCPC AC current
CCPC DC voltage
Vdc ref
d) CCPC DC voltage and AC current. Figure 14. PSCAD simulation responses for a single PS cycle assuming
compensation with CCPC and 580 capacitors.
8
-45-40-35-30-25-20-15-10-50510152025303540455055
1.2 1.6 2 2.4 2.8 3.2 3.6 4 4.4
Time [s]
Power [MW]
P -PSCAD
Pls
Plsref
Figure 15. PSCAD simulation responses for two PS cycles assuming
compensation with CCPC and 430 capacitors.
Figure 14c) is the simulation of CCPC control variables
Mm and Mϕ. It is important to observe that Mm stays close to, but it does not exceed the saturation limit of Mm=1,
confirming that an appropriate design approach is used.
The compensator DC voltage profile is shown in Figure
14d). At the beginning of the cycle the capacitors are fully
charged at 60kV. The DC voltage is decreasing when CCPC
delivers energy to the network and increasing when absorbing
energy. At the end of the positive half-cycle the DC voltage is
close to the minimum limit Vdcmin=36kV indicating optimum
component sizing. The transitions between active power and
DC voltage control are without noticeable overshootings.
CERN has also indicated potential benefits in using a
compensator with reduced storage capacity. In this case the
DC capacitor rating is determined solely by the amount of
energy returned to the network during the negative half-cycle.
Using (1-2) it is found that 430 capacitor units would be
required to enable storage of approximately 11MJ during the
negative half-cycle. Figure 15 shows that there is an
incomplete compensation during the positive half-cycle but it
is possible to fully recover the energy returned during the
negative half-cycle of the PS pulse. This figure demonstrates
that a compensator with reduced energy storage capacity
would also be a feasible technical option.
Note that the CCPC compensator element could be used
with renewable sources and a range of other industrial loads
like: traction drives, large induction motors or arc furnaces.
VIII. CONCLUSIONS
CERN’s Proton Synchrotron particle accelerator demands
very short and steep pulses of active and reactive power that
have a negative impact on the network power quality. A
compensating device, Converter Controlled Pulse
Compensator, consisting of a parallel connected VSC
converter with large DC capacitors, is found to be a suitable
compensation option.
The controllability analysis shows that active power control
can be achieved using q-axis of the PWM converter input, and
AC voltage control is obtained through d-axis converter input.
By analyzing the eigenvalue location it is shown that the
dynamic interactions between the two control channels are
small and large gains can be employed with simple PI
controllers. Further studies with wider range of parameters
show that the above results are primarily applicable to systems
with a large DC capacitance and low converter losses. The
PSCAD/EMTDC simulations of the PS accelerator cycles
show that reactive power compensation with CCPC achieves
excellent AC voltage control and the energy storage capability
enables that the active power exchange with the network
remains constant throughout the entire load cycle.
IX. REFERENCES
[1] K. Kahle. J. Pedersen, T. Larsson, M. de Oliveira, “The new 150 Mvar, 18 kV Static Var Compensator at CERN: Background, Design and
Commissioning,” CIRED 2003 [2] N. G. Hingorani, L. Gyugyi: “Understanding FACTS: Concepts and
Technology of Flexible AC Transmission Systems,” IEEE Press, 2000
[3] J. N. Baker, A. Collinson, “Electrical Energy storage at the turn of the millennium,” Power Engineering Journal Volume: 13, Issue: 3, pp: 107
– 112, June 1999.
[4] A. B. Arsoy, Y. L.iu, P.F.Ribeiro, F.Wang,: “StatCom – SMES,” Industry Applications Magazine, IEEE ,Volume: 9 ,Issue: 2, pp:21 – 28,
March-April 2003.
[5] C. Shen, Z. Yang; M. L. Crow, S. Atcitty: “Control of STATCOM with energy storage device,” Power Engineering Society Winter Meeting,
2000. IEEE , Volume: 4, pp:2722 – 2728, 23-27 Jan. 2000
[6] Manitoba HVDC Research Center “PSCAD/EMTDC users manual,” Winnipeg 2003.
[7] N. Mohan, T. M. Undeland, W. P. Robbins “Power Electronics Converters, Applications and Design,” John Wiley & Sons, 1995
[8] Papic, I.; Zunko, P.; Povh, D.; Weinhold, M.; “Basic control of unified power flow controller,” IEEE Transactions on Power Systems,
Vol. 12, no 4, Nov. 1997 Pp: 1734 - 1739. [9] P. Kundur: “Power System Stability and Control,” McGraw Hill, Inc.
1994.
[10] D. Jovcic N. Pahalawaththa, M. Zavahir “Analytical Modelling of HVDC Systems.” IEEE Trans. on PD, Vol. 14, No 2, pp. 506-511, April
1999
[11] D. Jovcic L. A. Lamont, L. Xu: “VSC Transmission model for analytical studies," Power Engineering Society General Meeting, 2003, IEEE,
Volume: 3, pp:1737 – 1742, 13-17 July 2003.
X. APPENDIX
CCPC CONTROLLER GAINS
Comment Gain value
Kp2 1.4 [1/kV] DC voltage control
Ti2 0.02 [skV]
Kp3 1 [1/kV] Power control
Ti3 0.04 [skV]
Kp1 45 [1/kV] AC voltage control
Ti1 0.00014 [skV]
KPf 0.1 [1/MW]
KQf 1.3 [1/MVA]
Feedforward control
KQdiff 0.01 [s/MVA]
XI. BIOGRAPHIES
Dragan Jovcic (S’97, M’00) obtained a B.Sc. in Control Engineering from
the University of Belgrade, Yugoslavia in 1993 and a Ph.D. degree in Electrical Engineering from the University of Auckland, New Zealand in
1999. He is currently a lecturer with the University of Aberdeen, Scotland where
he has been since 2004. He also worked as a lecturer with University of
Ulster, in period 2000-2004 and as a design Engineer in the New Zealand power industry in period 1999-2000. His research interests lie in the areas of
FACTS, HVDC and control systems.
Karsten Kahle studied Electrical Power Engineering at the FHTW Berlin, Germany, and received his M.Sc. degree from the University of Manchester,
UK, in 1995. He is currently studying part-time towards his Ph.D. degree at
the University of Vienna, Austria. K. Kahle jointed the Electric Power Systems Group of CERN in 1997,
where he is now responsible for project management, system design and
power system analysis. His main interest is on the application of FACTS for particle accelerators.