Installation Instructions CompactLogix EtherNet/IP Web Server Module Catalog Number 1768-EWEB Topic Page Important User Information 2 Minimum Spacing 7 What You Need 8 Install the Modules 8 Wire the Module 14 Connect the Module 15 Configure the Module 16 Confirm Your Installation 16 Remove the EtherNet/IP Web Server Module 17 Troubleshoot the Module 18 Status Indicators 19 Specifications 20 Additional Resources 23

CompactLogix EtherNet/IP Web Server Module Installation ......CompactLogix EtherNet/IP Web Server Module 5 Rockwell Automation Publication 1768-IN007B-EN-P - August 2010 Environment

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

  • Installation Instructions

    CompactLogix EtherNet/IP Web Server Module

    Catalog Number 1768-EWEB

    Topic Page

    Important User Information 2

    Minimum Spacing 7

    What You Need 8

    Install the Modules 8

    Wire the Module 14

    Connect the Module 15

    Configure the Module 16

    Confirm Your Installation 16

    Remove the EtherNet/IP Web Server Module 17

    Troubleshoot the Module 18

    Status Indicators 19

    Specifications 20

    Additional Resources 23

  • 2 CompactLogix EtherNet/IP Web Server Module

    Important User Information

    Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

    In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

    The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

    No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

    Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

    Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

    WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

    ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

    SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.

    BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.

    IMPORTANT Identifies information that is critical for successful application and understanding of the product.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 3

    North American Hazardous Location Approval

    The following information applies when operating this equipment in hazardous locations.

    Informations sur l’utilisation de cet équipement en environnements dangereux.

    Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

    Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

    WARNING:Explosion Hazard -•Do not disconnect equipment

    unless power has been removed or the area is known to be nonhazardous.

    •Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

    •Substitution of components may impair suitability for Class I, Division 2.

    • If this product contains batteries, they must only be changed in an area known to be nonhazardous.

    AVERTISSEMENT:Risque d’Explosion – •Couper le courant ou s'assurer que

    l'environnement est classé non dangereux avant de débrancher l'équipement.

    •Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

    •La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

    •S'assurer que l'environnement est classé non dangereux avant de changer les piles.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 4 CompactLogix EtherNet/IP Web Server Module

    European Hazardous Location ApprovalThis equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC.

    Intertek certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in confidential report No.100014190DAL-001.

    Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15.

    WARNING: This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments.

    Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 5

    Environment and Enclosure

    ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

    This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.

    This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

    In addition to this publication, see:

    • Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional installation requirements.

    • NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 6 CompactLogix EtherNet/IP Web Server Module

    Prevent Electrostatic Discharge

    ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

    • Touch a grounded object to discharge potential static.• Wear an approved grounding wriststrap.• Do not touch connectors or pins on component boards.• Do not touch circuit components inside the equipment.• If available, use a static-safe workstation.• When not in use, store the equipment in appropriate static-safe

    packaging.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 7

    Minimum Spacing Plan for this minimum spacing from enclosure walls, wireways, and other equipment.

    See Specifications on page 20 for the temperature range.

    Item Description

    1 105 mm (4 in.)

    2 90 mm (3.54 in.)

    31609-M

    PowerOUT

    L1

    L2/N

    2

    1

    2

    1

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 8 CompactLogix EtherNet/IP Web Server Module

    What You Need

    Install the Modules

    Item Cat. No. or Size

    1768 CompactLogix power supply 1768-PA3

    1768 CompactLogix controller 1768-L43

    1769 end capConnects to the controller as the last module, either:• without any 1769-series

    modules attached to the controller (1768-series only)

    • with a combination of 1768-series and 1769-series modules attached to the controller

    1769-ECR

    RJ45 Ethernet connector See Wire the Module on page 14

    DIN rail or mounting screws (one or the other but not both)

    DIN rail Either of these sizes:

    • 35 x 7.5 mm (EN 50 022 - 35 x 7.5)• 35 x 15 mm (EN 50 022 - 35 x 15)

    Screws M4 or #8 panhead screws

    ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.87 in.) and use end-anchors appropriately.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 9

    If You Are Using Screws to Mount Your Modules

    The steps in these instructions show how to mount the modules on DIN rail. If you are using screws instead of DIN rail, make these changes to the instructions.

    1. Follow the steps in Mount the Controller on the DIN Rail on page 10 to connect the modules together.

    2. Use the modules as a template and mark pilot holes on your panel.

    3. Drill the pilot holes for M4 or #8 screws.

    4. Use M4 or #8 screws to mount the modules to your panel. Use 1.16 N•m (10 lb•in) of torque.

    5. Ground the module on a ground bus with a dedicated earth ground stake.

    6. Connect the ground bus to a functional earth ground on the DIN rail or panel.

    7. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional information.

    IMPORTANT Do not use screws and DIN rail to mount the modules. It is possible to break the mounting tabs off if you screw the modules to the panel while they are on DIN rail

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 10 CompactLogix EtherNet/IP Web Server Module

    Install the DIN RailMount the DIN rail in a suitable location.

    Mount the Controller on the DIN Rail

    1. Close the DIN rail latches on the controller.

    ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 11

    2. Align and press the controller onto the DIN rail until the latches snap closed.

    Mount the EtherNet/IP Web Server Module on the DIN Rail

    1. Open the DIN rail latches on the module.

    2. Align and press the module onto the DIN rail to the left of the controller.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 12 CompactLogix EtherNet/IP Web Server Module

    3. Slide module snugly against the controller.

    Mount the Power Supply on the DIN Rail

    1. Close the DIN rail latches on the power supply.

    2. Align and press the power supply onto the DIN rail until the latches snap closed.

    3. Slide the power supply snugly against the module.

    Mount the I/O Modules on the DIN Rail

    1. Close the DIN rail latches on the module.

    2. Align the tongue-and-groove slots of the module with the tongue-and-groove slots of the controller and slide the module back towards the DIN rail.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 13

    When the module is in place, the DIN rail latches snap closed.

    3. Slide the locking tab of the module to the left to lock the module in place.

    4. Align the tongue-and-groove slots of the end-cap with the tongue-and-groove slots of the module.

    5. Slide the end-cap back towards the DIN rail.

    Item Description

    1 Locking tab

    2 Tongue-and-groove slot

    2

    2

    1

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 14 CompactLogix EtherNet/IP Web Server Module

    6. Move the lock latch to the left to lock the endcap on the module.

    Wire the ModuleUse an RJ45 connector to connect to the EtherNet/IP network.

    Item Description

    1 Lock latch

    1

    8

    1

    8 ------ NC7 ------ NC6 ------ RD-5 ------ NC4 ------ NC3 ------ RD+2 ------ TD-1 ------ TD+

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 15

    Connect the Module

    Attach the RJ45 connector to the Ethernet port on the bottom of the module.

    WARNING: If you connect or disconnect the cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

    IMPORTANT We recommend connecting the module to the network via a100 MB Ethernet switch, which will reduce collisions and lost packets and increase network bandwidth. For detailed EtherNet/IP connection information, see the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001.

    Item Description

    1 Ethernet port

    1

    31611-M

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 16 CompactLogix EtherNet/IP Web Server Module

    Configure the ModuleTo configure your module, refer to the configuration chapter of the Web Server Modules User Manual, publication ENET-UM527.

    Confirm Your InstallationVerify the following status indicators’ states.

    See Troubleshoot the Module on page 18 if the status indicators are in other states.

    Item Description

    1 Solid or flashing green

    2 Solid green

    31608-M

    PowerOUT

    L1

    L2/N

    2 2

    1

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 17

    Remove the EtherNet/IP Web Server Module

    1. Turn off power.

    2. Open the DIN rail latches of the EtherNet/IP Web Server Module and the module directly left of the EtherNet/IP Web Server module.

    3. Slide the EtherNet/IP module to the right with other modules.

    4. Slide the controller away from the EtherNet/IP module.

    5. Pull the EtherNet/IP module forward off the DIN rail.

    IMPORTANT When you turn the CompactLogix power supply off, make sure you wait for all status indicators on the power supply and controller to turn off before disconnecting any part from the system.

    If you disconnect the CompactLogix system while the controller is still writing its program to memory, the program write will not be completed and you will lose your program.

    PowerOUT

    L1

    L2/N

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 18 CompactLogix EtherNet/IP Web Server Module

    Troubleshoot the ModuleThe three bi-color (red/green)status indicators on the module provide diagnostic information about the module and its connections to the network. If the alphanumeric display and status indicators do not sequence through the expected states, refer to the troubleshooting tables.

    Item Description

    1 Link status indicator

    2 OK status indicator

    3 Network status indicator

    3 2

    1

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 19

    Status IndicatorsThe module status indicators provides the following information:

    Indicator Status Description

    NET Off Module is not powered, or does not have an IP address.• Verify there is chassis power and the module is

    completely inserted into the chassis and backplane.• Make sure the module has been configured.

    Flashing Green Module has obtained an IP address, but has no established connections.

    Green Module has an IP address and at least one established connection.

    Flashing Red One or more of the connections in which the module is the target has timed out.

    Red Module has detected that its IP address is already in use. Assign a unique IP address to the module.

    Link Off No data transmission.Module is not ready to communicate.

    Green Module is ready to communicate.

    Flashing Green Data transmission in progress.Module is communicating over the network.

    OK Off Module does not have 5V DC power. Verify there is power and the module is properly installed.

    Flashing Green Standby mode. Module is not configured.

    Green Module is operating correctly.

    Flashing Red A minor, recoverable fault has been detected. This could be caused by an error in the configuration.

    Red A major, unrecoverable fault has been detected. Recycle power to the module. If this does not clear the fault, replace the module.

    Flashing Red and Green

    Module performing power-up self-test.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 20 CompactLogix EtherNet/IP Web Server Module

    Specifications

    Technical Specifications - 1768-EWEB

    Attribute 1768-EWEB

    Backplane current 834 mA at 5.2V DC

    Power consumption 4.34 W

    Power dissipation 4.38 W

    Isolation (continuous-voltage rating)

    30V, Functional Insulation Type, Ethernet network to systemType tested at 710V DC for 60 s

    Wire Size Ethernet network connections:RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702

    Wiring category(1)

    (1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

    2 - on communication ports

    North American temp code T4A

    IEC temp code T4

    Mounting screw torque 1.16 N•m (10 lb•in), using M4 or #8 screws

    Dimensions (HxWxD), approx. 132 x 56.7 x 105.1 mm (5.20 x 2.23 x 4.12 in.)

    Weight, approx. 0.213 kg (7.5 oz)

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 21

    Environmental Specifications - 1768-EWEB

    Attribute 1768-EWEB

    Temperature, operating • IEC 60068-2-1 (Test Ad, Operating Cold)• IEC 60068-2-2 (Test Bd, Operating Dry

    Heat)• IEC 60068-2-14 (Test Nb, Operating

    Thermal Shock)

    0…60 °C (32...140 °F)

    Temperature, nonoperating• IEC 60068-2-1 (Test Ab, Unpackaged

    Nonoperating Cold)• IEC 60068-2-2 (Test Bb, Unpackaged

    Nonoperating Dry Heat)• IEC 60068-2-14 (Test Na, Unpackaged

    Nonoperating Thermal Shock)

    -40…85 °C (-40...185 °F)

    Relative humidity• IEC 60068-2-30 (Test Db, Unpackaged

    Damp Heat)

    5…95% noncondensing

    Vibration• IEC 60068-2-6 (Test Fc, Operating)

    5 g @ 10…500 Hz

    Operating shock• IEC 60068-2-27 (Test Ea, Unpackaged

    Shock)

    30 g

    Nonoperating shock• IEC 60068-2-27 (Test Ea, Unpackaged

    Shock)

    50 g

    Emissions• CISPR 11

    Group 1, Class A

    ESD immunity• IEC 61000-4-2

    4 kV contact discharges8 kV air discharges

    Radiated RF immunity• IEC 61000-4-3

    10V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz1V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

    EFT/B immunity• IEC 61000-4-4

    ±2 kV at 5 kHz on communication ports

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • 22 CompactLogix EtherNet/IP Web Server Module

    Surge transient immunity• IEC 61000-4-5

    ±2 kV line-earth(CM) on communication ports

    Conducted RF immunity• IEC 61000-4-6:

    10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

    Enclosure type rating None (open-style)

    Certifications

    Certification (when product is marked)(1)

    Value

    c-UL-us • UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

    • UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

    CE European Union 2004/108/EC EMC Directive, compliant with:

    • EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A &

    B)

    C-Tick Australian Radiocommunications Act, compliant with:• AS/NZS CISPR 11; Industrial Emissions

    Ex European Union 94/9/EC ATEX Directive, compliant with:• EN 60079-15; Potentially Explosive Atmospheres,

    Protection "n"• EN 60079-0; General Requirements

    II 3 G Ex nA IIC T4

    EtherNet/IP • ODVA conformance tested to EtherNet/IP specifications

    (1) See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

    Environmental Specifications - 1768-EWEB

    Attribute 1768-EWEB

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • CompactLogix EtherNet/IP Web Server Module 23

    Additional ResourcesThese documents contain additional information concerning related Rockwell Automation products.

    You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.

    Resource Description

    EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001

    Provides information about how to use EtherNet/IP modules with vrious Logix5000 controllers.

    1768 CompactLogix Controller Installation Instructions, publication 1768-IN004

    Provides information for installing a 1768 CompactLogix controller.

    1769 CompactLogix Power Supplies Installation Instructions, publication 1768-IN001

    Provides information about how to install CompactLogix power supplies.

    Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

    Provides general guidelines for installing a Rockwell Automation industrial system.

    Product Certifications website, http://ab.com

    Provides declarations of conformity, certificates, and other certification details.

    Rockwell Automation Publication 1768-IN007B-EN-P - August 2010

  • Rockwell Automation Support

    Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

    Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

    For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

    Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.

    New Product Satisfaction ReturnRockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

    Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

    United States or Canada 1.440.646.3434

    Outside United States or Canada

    Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.

    United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

    Outside United States Please contact your local Rockwell Automation representative for the return procedure.

    Publication 1768-IN007B-EN-P - August 2010 PN-83489

    Allen-Bradley, Allen-Bradley, CompactLogix, RSLogix5000, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.

    Trademarks not belonging to Rockwell Automation are property of their respective companies.

    Supersedes Publication 1768-IN007A-EN-P - September 2006 Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    1768-IN007B-EN-P, CompactLogix EtherNet/IP Web Server Module Installation InstructionsImportant User InformationNorth American Hazardous Location ApprovalEuropean Hazardous Location ApprovalEnvironment and EnclosurePrevent Electrostatic DischargeMinimum SpacingWhat You NeedInstall the ModulesIf You Are Using Screws to Mount Your ModulesInstall the DIN RailMount the Controller on the DIN RailMount the EtherNet/IP Web Server Module on the DIN RailMount the Power Supply on the DIN RailMount the I/O Modules on the DIN Rail

    Wire the ModuleConnect the ModuleConfigure the ModuleConfirm Your InstallationRemove the EtherNet/IP Web Server ModuleTroubleshoot the ModuleStatus IndicatorsSpecificationsAdditional ResourcesBack Cover

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice

    Introduction_Catagory Types

    This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.

    Publication Type and Print Category

    Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder MinOrder MaxLife Cycle Usage / Release Option

    ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal

    APA3D2Application Solution or Customer Success Story5100Presale / External

    ARNANAArticle/Editorial/BylineNANAPresale / Internal

    /News Release (press releases should not be checked into DocMan or printed)

    ATB3, B4D5Application Techniques5100Presale / External

    BRA2 Primary, A1NABrochures5100Presale / External

    CAC2 Primary, C1NACatalogue150Presale / External

    CGNANACatalogue Guide150Presale / External

    CLNANACollection550Presale / External

    COA5, A6, A9D5Company Confidential InformationNANANA / Confidential

    CPE-onlyE-only, D5Competitive Information550NA / Confidential

    DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal

    DIA1, A3NADirect Mail5100Presale / Internal

    DMNANAProduct Demo550Presale / Internal

    DSB3D5Dimensions Sheet15Post / External

    DUB3D5Document Update15Post / External

    GRB2D6Getting Results15Post / External

    INB3D5Installation instructions15Post / External

    LMNANALaunch KitMaterials550Presale / Internal

    PCB3D5Packaging Contents

    PLE-only Primary, B3E-onlyPrice List550Presale / Internal

    PMB2D6Programming Manual15Post / External

    PPA3D1Product Profile NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External

    QRB2 Primary, B3, B5D5, D6Quick Reference15Post / External

    QSB2 Primary, B3, B5D5, D6Quick Start15Post / External

    RMB2D5, D6Reference Manual15Post / External

    RNB3D5Release Notes15Post / External

    SGB1 Primary, B4D5, D6Selection Guide Colour550Presale / External

    SGB2D5, D6Selection Guide B/W550Presale / External

    SPA1, A2, A3, A4NAService ProfileSales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal

    SRB2, B3D5, D6Specification Rating Sheet5100Presale / External

    TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / External

    TGB2, B3D6Troubleshooting Guide15Post / External

    UMB2 Primary, B4D6User Manual B/W15Post / External

    WDB3D5Wiring Diagrams / Dwgs15Post / Internal

    WPB3 Primary, B5D5White Paper550Presale / External

    Pre-sale / MarketingAll paper in this category is White Brightness, 85% or better. Opacity 87% or better

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    A14 color170gsm 2pp100# gloss cover, 100# gloss text

    A24 color170gsm, folded, 4pp100# gloss cover, 80# gloss text

    A34 colorCover 170gsm with Body 120gsm, > 4pp80# gloss cover, 80# gloss text

    A42 color80# gloss cover, 80# gloss text

    170gsm Silk – 120gsm Silk

    A52 color80# gloss cover, 80# matt sheet text

    170gsm Silk – 120gsm Silk

    A61 color170gsm Silk – 120gsm Silk80# gloss cover, 80# matt sheet text

    A74 color cover10 Point Cover C2S

    2 color textCategory being deleted50# matte sheet text

    Selection Guide

    A84 color coverCategory being deleted50# matte sheet text, self cover

    2 color text

    Selection Guide

    A92 color100gsm bond50# matte sheet text, self cover

    Selection Guide

    Post Sale / Technical Communication

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S

    2 color text50# matte sheet text

    B21 color60# Cover

    160gsm Colortech & 100gsm Bond50# matte sheet text

    B31 color50# matte sheet text, self cover

    100gsm bond

    B42 color60# Cover

    160gsm Colortech & 100gsm Bond50# matte sheet text

    B52 color50# matte sheet text, self cover

    100gsm bond

    Catalogs

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S

    4 color text45# Coated Sheet

    C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S

    2 color text32#-33# Coated Sheet

    JIT / POD

    CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

    D14 color170gsm white silk80# gloss cover, coated 2 sides

    D24 color120gsm white silk80# gloss text, coated 2 sides, self cover

    D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides

    D41 color160gsm tab90# index

    D51 color80gsm bond20# bond, self cover

    D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D72 color160gsm tab90# index

    D82 color80gsm bond20# bond, self cover

    D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

    D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond

    Print Spec Sheet

    JIT Printing SpecificationsRA-QR005E-EN-P - 5/19/2009

    Printing SpecificationYOUR DATA HEREInstructionsNO

    (required) Category:D5Select Print Category A,B,C or D from category list, on "Introduction_Catagory Types" tab11” x 17”LOOSE -Loose LeafYESPre-sale / MarketingTOP

    (required) Finished Trim Size Width:4.75” x 7” (slightly smaller half-size)8.5” x 11”PERFECT - Perfect BoundA1LEFT

    (required) Publication Number :1768-IN007B-EN-PSample: 2030-SP001B-EN-P3” x 5”SADDLE - Saddle StitchA2RIGHTCORNER

    Use Legacy NumberNOYES or NO18” x 24” PosterPLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE

    Legacy Number if applicable:Sample Legacy Number: 0160-5.3324” x 36” PosterSTAPLED1 -1 positionA3

    Publication Title:CompactLogix EtherNet/IP Web Server Module Installation InstructionsSample: ElectroGuard Selling Brief36” x 24” PosterSTAPLED1B - bottom 1 positionA5

    (required) Business Group:Marketing CommercialAs entered in DocMan4” x 6”STAPLED2 - 2 positionsA6

    (required) Cost Center:CMKMKE CM Integrated Arch - 19021As entered in DocMan - enter number only, no description. Example - 19021CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 191054.75” x 7” (slightly smaller half-size)THERMAL - Thermal bound (Tape bound)A7

    Binding/Stitching:SADDLE - Saddle StitchReview key on right...Saddle-Stitch Items All page quantities must be divisible by 4.20 sheets max. on 20# (text and cover); 20 sheets = 80-page pub16 sheets max. on 20# (text) and 90# (cover); 16 sheets = 64-page pub

    Perfect Bound Items475 sheets max. on 20# no cover; 475 sheets = 950-page pub470 sheets max. w/cover / 90# index unless indicated otherwise); 470 sheets = 940-page pub

    Coil Bound Items400 sheets max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 400 sheets = 800-page pub

    Tape Bound Items125 sheets max. on 20# no cover; 125 sheets = 250-page pub120 sheets max. w/cover (90# index unless indicated otherwise); 120 sheets = 240-page pub

    Double Wire Bound Items250 sheets max. on 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 250 sheets = 500-page pub4.75” x 7.75”THERMALO - Thermal Bound (Tape bound - offline)A8

    (required) Page Count of Publication:24Total page count including cover5.5” x 8.5” (half-size)Wire O - Double Wire Bound (offline)A9

    Paper Stock Color:White is assumed. For color options contact your vendor.6” x 4”Post Sale / Technical Communication

    Number of Tabs Needed:5 tab in stock at RR Donnelley7.385” x 9” (RSI Std)B1

    Stitching Location:Blank, Corner or Side8.25” x 10.875”B2

    Drill Hole YES/NOYESAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of ¼ inch from the inner page border.8.25” x 11” (RA product profile std)B3

    Glue Location on Pad:Glue location on pads8.375” x 10.875B4

    Number of Pages per Pad:Average sheets of paper.. 25, 50 75,100 Max9” x 12” (Folder)B5

    Ink ColorOne color assumes BLACK / 4 color assume CMYK / Indicate PMS number here…A4 (8 ¼” x 11 ¾”) (210 x 297 mm)Catalogs

    Used in Manufacturing:YESA5 (5.83” x 8.26”) (148 x 210 mm)C1

    Comments:1756-EWEBC2

    Part Number:PN-83489JIT / POD

    D1

    D2

    D3

    D4

    D5

    D6

    D7

    D8

    D9