Community-Scale Solar Plus Thermal Storage and Demand-Response

A Modeling Study of Local Grid Benefits

Community Solar Value Project September 2017

Santiago Sena, Public Service Company of New Mexico

Jon Hawkins, PNM Resources

Page 2: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

Summary

WorkingwiththeteamfromtheCommunitySolarValueProject(CSVP),aprogramco-fundedbytheU.S.DOESunShotprogram,PublicServiceCompanyofNewMexico(PNM)hasexaminedtheideaofcombiningcommunity-scalesolarwithstorageanddemand-response(DR)measures.Thisstrategyhasbeendiscussedintheutilityindustry,asameansofcapturingnumerousbenefits,frommanagingsystempeakstoofferingcustomersmoreclean-energychoices,asrenewable-energypenetrationincreases.Anotherbenefitmightbetheopportunitytositesolarandsolar-plusmeasurestocapturegridbenefits.Thus,thisstudyexaminesanopportunitytomitigatelow-voltageissuesonafeedercomprisedprimarilyofresidentialloads.MightdistributedsolargenerationplusthermalstorageandDRbenefitthiscircuit,ormighttheycreatenewproblems?

PNMmodeledtheimpactonadistributionfeederofmultiplecombinationsofsolararraysofvaryingsizeswithcontrolofresidentialairconditionersandelectricwaterheaters.Ineachscenario,PNMevaluatedtheresultingimprovementinvoltagelevelsoneachdistributiontransformerduringtheperiodoflowvoltage(primarily,lateafternoonandearlyevening).WhileneitherDRalonenorasolararrayalonecouldmitigatealllow-voltageissues,thecombinationofamid-sizedsolararrayandsimpleDRcontrolstrategiesonthermalstorageeliminatedallinstancesoflowvoltage.ThemodelingapproachusedheremaybeextendedandappliedinotherstudiesatPNMorotherutilities,inevaluatingnovelcombinationsofrenewablesandloadflexibilitytoaddressdistributionissues.

Page 3: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

1

Introduction

PNMisNewMexico’slargestelectricutility,servingover525,000customersinastatewithrelativelylowpopulationandalargeamountofnaturalresources.Giventhenaturalresourcesinthestate,itisnotsurprisingthatPNM’scustomershaveahighinterestinrenewableenergy.Infact,AlbuquerquewasnotedinarecentU.S.DepartmentofEnergySunShotSolarIndustryUpdateasbeinginthetop5citiesinthenationintermsofpercapitaPVinstalled.1Inaproactiveprojectthatbeganin2010andwascompletedin2011,PNMwasaveryearlypioneerinstudyinghowenergystoragemaybeabletoworktogetherwithdistributedrenewablestohelpimprovetheirvalue.Thateffort,calledtheProsperityEnergyStorageproject,hasbeendevelopedaspartoftheU.S.DepartmentofEnergy(U.S.DOE)SmartGridDemonstrationGrantsintheEnergyStorageProgram.

TheProsperityprojectwasdesignedandbuiltasa500-kW/1MWhutility-scalebatterystoragesystemthatinteracteddirectlywithaco-located500kWPVsolararray.Inthisproject,PNMresearcherslookedatmultiplevaluestreams.Onesuchvaluestreamisrelatedtosmoothingpoweroutput,inresponsetochangesinPVsystemoutpute.g.,fromintermittentcloudcover;ThesystemalsohasthecapabilityofstoringPVsystemoutputathighsolarproductiontimesforuseattimesthataremorealignedwithutilitysystempeakusagetimes.

Whilebatteryenergystorageisanextremelyflexibleresource,inmanymarketsitisstillacostlysolution.Thus,PNM’sexperiencewithProsperitypromptedaninvestigationintootherresourcesthatcouldcombinewithPVtoprovidesimilarbenefitsatalowercost.Inparticular,mighttherebealternativeresourcesforbalancingshortertermfluctuations,allowingthebatterysystemtofocusonitsenergyapplications,andhowsuchalternativeresourcescouldhelpmitigatesomeofthelocationalissuesthatarisewithdistributedgeneration.Aspartofthisinvestigation,PNMmodeledsomescenariosutilizingacommunity-scalesolar(CS)projectcoupledwithdemand-response(DR)resources.Thescenariocouldbeextendedtoimplementationthroughamodelthatpromotescommunitysolarwithcompanionmeasures(utility-sidestorageplusDR);however,thismodelingexercisewasfocusedonlyontechnicalimpacts.

PNMhadidentifiedafeederinitsserviceterritorythatalreadywasdisplayingvoltagesatcertaintimesofthedaythatwerebelowPNM’sdesigncriteria(ANSIRange-AVoltageLimits).Thelowvoltageswereidentifiedduringroutineplanningevaluationandtraditionalsystemimprovementapproacheswereimplementedtomitigatethelowvoltages.However,thegoalofthisanalysiswastoinvestigatethepossibilityofusingDRandCSresources,asopposedtothetraditionalapproachestomitigatelowvoltagesthatoccurasaresultofnormalloadgrowth.2TheanalysispresentedinthisreportassumesallavailableDRresourcesparticipatedintheprogram.TwoDRresourceswereevaluatedin1RobertMargolis,DavidFeldman,DanielBoff,“Q42016/Q12017SolarIndustryUpdate”,page33,U.S.DepartmentofEnergySunShot,April25,20172TheanalysisandconclusionshighlightedinthisreportwerenotfullyvettedthroughPNM’sDistributionPlanningDepartment.ThefindingsandconclusionsinthisreportarethoseoftheauthorsanddonotrepresenttheofficialpositionofPNM.

Page 4: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

2

thisanalysis,controlledHVACunits(residentialairconditioning)andcontrolledelectrichotwaterheaters(EHWH).Thecircuitmodeledisprimarilyresidential,buttheseCSandDRmeasuresmayalsobetargetedtoacommercialmarket.

Asindicatedbelow,thescenarioutilizedforthisstudyrepresentsafirst-stepinthetechnicalassessmentofpossibleCSgridbenefits.Theresearchquestionsaresimplythese:

1)Wouldadistributioncircuitthatisexperiencinglowvoltagebeacandidateforasolar-plus-DR(withthermalstorage)strategy?

2)Ifasolar-plus-DRstrategyweresuggestedforacircuitexperiencingperiodiclow-voltagecharacteristics,isthereanidealconfiguration,intermsofsolar-projectscale?

3)Whatarethelikelysynergisticeffectsinthesituationdescribed,ofaddingoneormoreDRmeasures,plusthermalstorage,alongwiththeadditionofdistribution-scalesolargeneration?

Inpreparingthisanalysis,theauthorsworkedwiththeCommunitySolarValueProject(CSVP),whichisaU.S.DOESunShotawardee.CSVPhasworkedwithutilitiesonarangeofDRandstorageoptionsthatcouldbeusedascompanionmeasureswithcommunity-scalesolar,primarilyintherangeof500-kWto10MW.SomeoftheapproachesdiscussedinthisanalysisweredevelopedbasedinpartonCSVP’sworkwithotherutilities,andtheauthorshopetheseresultswillbeofusetoutilitiesconsideringsimilaroptions.Asnotedbelow,CSVPhasidentifiednumerousDRtechnologiesandcustomer-sidestorageoptionsthatarereadilyavailableandhavevarious,flexiblecontrolcharacteristics,aswellascustomer-appeals.CSVPalsohasrecommendedfullyutilizinginvertertechnologyandaddingstrategicsolar-designimprovements.Notalloftheseavailablehigh-valueoptionsaremodeledforthisstudy.Ineffect,thisstudyrepresentsa“firstgate”inthepathtoestablishingacommunity-scalesolar-plusstrategy

Thefollowingcasesweremodeled:

• BaseCaseo Demandresponseandcommunitysolarresourcesnotevaluated

• CommunitySolarOnlyo Onlycommunitysolarresourcesevaluated.o ThesizeofthePVgeneratorwasincreasedfrom1MW-9MWat1MW

increments.o Thelocationofthecommunitysolarsitewasstatic.

• DemandResponseOnlyo Onlydemandresponseresourcesevaluated.o OperationoftheHVACunitswereadvancedordeferredinaneffortto

mitigatevoltageissues.o TheoperationsoftheEHWHunitswereshiftedoutsidepeakloadingperiods.

• CommunitySolarplusDemandResponse

Page 5: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

3

o Demandresponseresourcesevaluatedinconjunctionwithcommunitysolarresources

o TheoperationoftheHVACunitswereadvancedordeferredinanefforttomitigatelowvoltageissues.

o TheoperationsoftheEHWHweredeferredbetweenpeakloadingperiods.

DemandResponseResources

Company-sponsoredthirdpartyloadresearchidentifiedHVACsaturationat32.3%andEHWHsaturationat9.1%.ForthepurposesofthisanalysisitwasassumedallavailableHVACandEHWHunitsparticipatedintheDRprogram.Thisresultedin763customerswithHVACunitsand212customerswithEHWHunits.HVACandEHWHunitswererandomlyassignedtodistributiontransformersaccordingtothepreviouslyidentifiedsaturationlevels.HypotheticalloadprofilesfortheDRresourcewererandomlygeneratedand24-hourloadprofilesforresidentialloadsweredeveloped.ForthepurposeofthisanalysisDRloadswereshiftedfromon-peaktooff-peakperiods.ThetotalbaselineDRloadprofiledevelopedforthisanalysisishighlightedinFigure1.

Figure1-TotalDRBaselineLoadProfile

HVACUnits

MeteredcustomerHVACloaddatawasnotavailableforuseinthisanalysis.Therefore,baselinehypotheticalHVACloadprofilesweregenerated.AnexampleofageneratedHVACloadprofileishighlightedinError!Referencesourcenotfound..AllHVACunitsweresimulatedusinga5.6kWdemand.TheONdurationtimeforHVACunitswassetfor15minutesandtheOFFdurationtimewasrandomlygeneratedbetween30-90minutes.

Page 6: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

4

Figure2-GeneratedHVACBaseline15MinuteLoadProfile

HVACloadswerecontrolledinoneoftwoways:(1)forthetimeintervalbetween12:00PM-6:30PMindividualHVACloadswereadvanced15minutescomparedtothebaselineprofile,ensuringdistributionvoltagesremainwithintheplanningcriteria,(2)fortimeintervalsbetween6:30PM-12AMindividualHVACloadsweredelayed15minutes,ensuringdistributionvoltagesremainwithintheplanningcriteria.Forexample,forthebaselineHVACloaddepictedinFigure2thecorrespondingcontrolledHVACloadprofileisidentifiedinFigure3.

Figure3-ControlledHVACLoadProfileExample

EHWHUnits

MeteredcustomerEHWHloaddatawerenotavailableforuseinthisanalysis.Therefore,baselinehypotheticalEHWHloadprofilesweregenerated.AnexampleofageneratedEHWHloadprofileishighlightedinFigure4.TheEHWHloadsweregeneratedusingademandof3.9kW.TheONdurationtimefortheEHWHwassetfor15minutesandtheOFFdurationtimewassetfor75minutes.TheinitialONoperationfortheEHWHwererandomlygenerated.FortheDRcontrolledcasesevaluatedinthisanalysisEHWHloads

Page 7: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

5

werecompletelycurtailedbetweenthehoursof5:00PM–10PM.Forexample,forthebaselineEHWEloaddepictedinFigure4thecorrespondingcontrolledEHWHloadprofileisidentifiedinFigure5.

Notethattoday’sgrid-interactiveelectricwaterheatertechnologiescansupportamoreflexible,load-responsivecontrolscenariothanthosemodeledhere.Asafirst-stepanalysis,thisstudyreliedonbasictime-of-daytypecontrolstrategiesandassumedonlyexistingwaterheaters,retrofittedwithcontrolsthatdonotrequirecustomerstohaveadvancedelectronicmeters.Similarly,theHVACcontrolstrategyselectedforthismodelingeffortwasintendedtobereadilyachievable,usingexistingtechnologiesandsimplechangestoexistingprotocols.(SeeadditionalCSVPresourcesformoreonDRandcustomer-sidestorageoptions.)

Figure4-BaselineEHWHLoadProfile

Figure5-ControlledEHWHLoadProfileExample

FeederDistributionVoltage

Thecompany-acceptedcriteriaforappropriatedistributionvoltageistheAmericanNationalStandardInstitute(ANSI)StandardC84.1.Thestandardspecifiesvoltageranges

Page 8: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

6

fornormal(Range-A)andemergency(RangeB)conditions.Range-Adefinestheservicevoltageasaminimumof114voltsandamaximumof126volts.

Amaximumvoltagedropof4%isthecompanydesignlimitfromthedistributiontransformerprimarytothecustomerservicemeter.Furthermore,PNMtypicallysetssubstationtransformersecondaryvoltagesat2.0%-2.5%above120voltsnominal.ApplyingthecompanyvoltagedropdesignlimitstotheANSIC84.1Range-Alimitsresultsinaminimumvoltagerequirementof118.7voltsattheprimarydistributiontransformerhighsidetoensureautilizationvoltageof114voltsatthecustomermeter.Furthermore,PNMgenerallydoesnotmodeldistributiontransformersandcustomerservicedrops.Forthepurposeofthisanalysis,distributiontransformersprimaryvoltagesbelow118.7voltsandabove126voltsareconsideredoutsideRange-A.

FeederModel

ThefeederusedinthisanalysisisidentifiedasHAMI13.Duringroutineplanningevaluation,theSynergifeedermodelidentifiedlowvoltagesbelowtheANSIC84.1Range-Alowerlimitduringpeakloadingconditions.ThelowvoltageswereconcentratedtoA-phaseandB-phaselateralslocatedattheendofthefeeder.TheSynergivoltageheatmapisidentifiedinFigure6.Mitigatingthelowvoltagesrequiredthefollowingsystemimprovements:

• Relocatinganoverhead1200kVARfixedcapacitor• Installinganewpad-mounted1800kVARswitchedcapacitorbank• TransferringasinglephaseloopfromtheB-phasetotheA-phase.

Page 9: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

7

Figure6-SynergiHAMI13FeederModelVoltageProfile

OpenDSSModelDevelopment

TheSynergifeedermodelwasconvertedtoOpenDSSformatusingscriptsdevelopedinVisualBasicforApplication(VBA).Aone-to-oneconversionwasperformedbetweentheSynergifeedermodelandtheOpenDSSequivalentformat.AvisualcomparisonbetweenofthecircuitplotmodelsisshowninFigure7.PowerflowanalysiswasdoneusingOpenDSS,drivenbyVBAthroughtheCOMinterface.

Page 10: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

8

Figure7-OpenDSSandSynergiFeederCircuitPlots

OpenDSSBaseModel

SupervisoryControlandDataAcquisition(SCADA)feederloaddatacorrespondingtothepeakloadingdaywasusedtodevelopresidentialloadprofiles.TheresidentialtransformerloadprofilesweredevelopedbytreatingtheEHWHandHVACunitsasspotloadsandallocatingSCADA15minutefeederloaddataaccordingtoconnectedKVA.ModelingtheDRloadasspotloadsensuredthatonlynon-deferrableloadswerecapturedintheallocationfactors.TheresultingOpenDSSmodelfeederloadprofile,withDRresourcesandnon-deferrableloadsidentifiedisshowninFigure8.

Figure8-OpenDSSFeederLoadProfile

ThebasecaseOpenDSSfeedermodeldevelopedforthisanalysisidentifiedmultiplesingle-phaselateralswithprimarydistributionvoltagesbelowtheANSIC84.1Range-Alimit.TheSynergiandOpenDSSdistributionvoltageprofileresultsareidentifiedinFigure9.Both

Page 11: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

9

modelsidentifysystemiclowvoltage,clusteredonsinglephaselateralsattheendofthefeeder.

Figure9-Synergi&OpenDSSVoltageCircuitPlots

TheBaseCaseOpenDSSminimumtransformerprimaryvoltageandfeederloadprofilearegraphedinFigure10.Thefeederpeakof9.4MWoccurredat6:30PM.OpenDSSanalysisresultsidentifytransformerprimaryvoltagesbelowtheANSIC84.1Range-Alowerlimitbetweenthehoursor4:00PMand8:00PM.TheidentifiedtimeintervalalsocorrespondstothepeakfeederloadingintervalasidentifiedinFigure10.

Page 12: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

10

Figure10-OpenDSSFeedLoadingandMinimumTransformerPrimaryVoltages

ThetotalnumberoftransformerswithprimaryvoltagesbelowtheANSIC84.1Range-Alowerlimitof118.7voltsishighlightedinFigure11.ThenumberoftransformerswithprimaryvoltagesbelowtheANSIC84.1Range-Alowerlimitspeaksat6:45PMwith58transformers.Themajorityoflowvoltagesoccurbetween5:15PM-7:30PM.ThelocationoftransformerswithvoltagesbelowRange-AareidentifiedinFigure12.Thetransformersarelocatedattheendofthefeederonsinglephaselaterals.

Figure11-BaseCase:TransformerswithPrimaryVoltagebelow118.7volts

Page 13: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

11

Figure12-BaseCase:LocationofTransformerswithLowVoltages

Analysis

DemandResponseOnly

ControllingDRresourcesmarginallydecreasesthenumberoftransformerswithprimaryvoltagesbelowtheANSIC84.1Range-Alowerlimitof118.7volts.AcomparisonbetweenthenumbersoftransformerswithvoltagesbelowthedesigncriteriaforboththeDRcontrolledcaseandtheBaseCasesarehighlightedinFigure13.ControllingDRresourcesresultsinvoltagesabovethedesigncriteriaforinstancesbefore4:00PMandafter7:15PM.

Figure13-DRControlledCase:TransformerswithVoltagesbelow118.7Volts

Page 14: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

12

TheminimumtransformervoltagesforthecontrolledanduncontrolledcasesarehighlightedinFigure14.ThelocationsoftransformerswithprimaryvoltagesbelowRange-AlowerlimitsareidentifiedinFigure15.ComparedtotheBaseCaseanalysisresults,controllingDRresourcesresultsinmitigatingalltransformerprimaryvoltageslocatedontheB-phaselaterattheendofthefeeder.

Figure14-MinimumTransformerPrimaryVoltage:ControlledDRvs.BaseCase

Figure15-ControlledDRCase:LocationofTransformerswithLowVoltage

CommunitySolarOnly

InthisanalysistheCSresourcewasmodeledusingaunitypowerfactorandassuminganidealPVgenerationoutputforboththeCSfacilityandexistingdistributivegeneration.Furthermore,theCSresourcewasmodeledusingastaticfacilitylocation.TheCSfacilitycapacitywasincrementedfrom1MWto9MWat1MWintervals.Considerable

Page 15: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

13

improvementintransformerprimaryvoltagesresultinCSoutputsof3-6MW.However,transformerprimaryvoltagesremainbelowtheANSIC84.1Range-Alowerlimit.TheminimumtransformerprimaryvoltagesresultingfromvariousCSfacilityoutputsaregraphedinFigure16.

Figure16-CSOnlyCase:MinimumTransformerPrimaryVoltage

PeakCSoutputandpeakfeederloadingareoffsetby5hourswithpeakCSoutputoccurringat1:30PMandpeakloadingoccurringat6:30PM.ACSoutputof9MWresultsinthemajorityoftransformerprimaryvoltageswithintheANSIC84.1Range-Alowerlimits.However,theoutputofa9MWCSfacilityprovidesinsufficientvoltagesupporttomitigatelowvoltagesbetween7:00PM-8:00PM.Forvisualizationthe9MWCSoutput,feederloadprofileandremainingnumberoftransformerswithvoltagesbelowtheANSIC84.1Range-Avoltagelimitof118.7voltsaregraphedinFigure17andthelocationofthosetransformersareidentifiedonFigure18.Theremaininglowvoltagesareclusteredattheendofthefeeder.

Figure17-BaseCaseFeederProfilewith9MWCSOutput&AssociatedXFMRSbelowRange-A

Page 16: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

14

Figure18-9MWCSCase:LocationofTransformerswithVoltagesbelow118.7volts

CommunitySolar&DemandResponse

AcombinationofCSandcontrolledDRresourcessignificantlyimprovedprimarytransformervoltages.TransformerprimaryvoltagesforvariouscasesofCSoutputsareshowninFigure19.UtilizingaCSoutputof4.5MWincombinationwithcontrollingDRresourcesensuredalltransformerprimaryvoltagesarewithintheANSIC84.1Range-Avoltagelimitrequirements.

Figure19-DR&CSCase:MinimumPrimaryTransformerVoltageProfile

Page 17: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

15

AllDRloads,roughly1.2MW,areshiftedoffpeakwithaCSoutputof4.5MW.

Figure20–DR&CSCase:ResuktingDRLoadProfile

Conclusion

TheanalysisidentifiedthatutilizingacombinationofCSandDRresourcesimprovedvoltagessignificantly.ACSoutputof4.5MWandleveragingDRresourcesensuredallprimarytransformervoltageswerewithinplanningcriterialowerlimits.UtilizingCSresourcesexclusivelydidprovidemarginalimprovementsinfeedervoltageathighCSpenetrationlevelsbutdidnotensureallprimarytransformervoltageswerewithinplanningcriterialowerlimits.Furthermore,controllingDRresourcesexclusivelyresultedinmarginalimprovementinprimarytransformervoltagesbutdidnotcompletelyensureallprimarytransformersvoltageswerewithinplanningcriterialowerlimits.

ThisanalysisutilizedverysimpleDRcontrolalgorithmstoshiftHVACandEHWHloadsoutsideofpeakloadingperiods.InthisanalysisitwasassumedthatallavailableHVACandEHWHunitsparticipatedinthedemandresponseprogram.Furthermore,CSresourcesanddistributivegenerationweremodeledusingidealPVgenerationoutputs.

Analysisidentifiedthefollowingresults:

• AcombinationofDRandCSresourcessignificantlyimprovestransformerprimaryvoltagescomparedtothebasecase.

• UtilizingDRresourcesandaCSfacilityof4.5MWensuredalltransformerprimaryvoltageswereaboveRange-Alowerlimits.

• ACSfacilitywithanoutputof9MWmarginallydecreasesthenumberoftransformerswithlowvoltagesbelowRange-Alimitsbefore7:00PM.However,theoutputof9MWCSfacilityprovidesinsufficientvoltagesupporttomitigatelowvoltagesafter7:00PM.

Page 18: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

16

• ControllingDRresourcesmarginallydecreasesthenumberoftransformerswithprimaryvoltagesbelowtheRange-Alowerlimit.ControllingDRresourcesresultsinvoltagesabovethedesigncriteriaforinstancesbefore4:00PMandafter7:15PM.

Thesimplicityofthecontrolalgorithmsusedinthemodelingisencouragingandmayindicatethatmoreautomatedandcoordinatedcontrolstrategiesusingintra-dayfeedbackcouldyieldimprovedresults,comparedtothedeterministictime-of-daycontrolstrategiesmodeledinthispaper.Thistypeofscenariosuggestsananalysisforfutureinvestigation.

WhiletheanalysisdidprovidesomeveryinterestingresultsregardingthecombinationofcommunitysolarplusDR,andtheircapabilitytoworkinconcerttomitigatefeederissues,thereisstilladoseofrealitythatmustbeconsidered.SomehypothesesaroundPVinstallationsbelievethatsolaralonecouldbeapossibleresourcetopossiblydeferfeederupgrades.Inthismodel,thesolarinstallationdidmitigatesomelowvoltageissues,butfellshortasthesunwassettingwhenwebegantoagainseethevoltageissuesweweretryingtomitigate.Alsodemandresponse,traditionallyusedasapeakingresourceforthebulkelectricsystem,onlydidamarginaljobonmitigatingvoltageissuesonthedistributionfeederitself.Additionalengineeringandsolar-plusmeasurescouldachieveagriddeferralinsomecases,butasthisanalysissuggests,thatwouldnotbeasimpleundertaking,atbest.

ThepurposeofthisstudywastoinvestigatethefeasibilityofutilizingCSandDRresourcestomitigatelowvoltagesresultingfromnormaldistributionfeederloadgrowth.Forthecircuitthatprovidedthebasisforthisstudy,actualmeasuretakentomitigatevoltageissuesincluded:

• Relocatinganexistingoverhead1200kVARcapacitorbank• Installinganewpad-mounted1800kVARcapacitorbank• Transferringasingle-phasefromtheB-phasetotheC-phase.

Asidefromtheinstallationofthe1800kVARvoltagecontrolledcapacitor,theidentifiedsystemimprovementsrepresentmarginable,inexpensivesolutions.Itwouldbehighlyunrealistictousethisproblemaloneasanargumenttoinstallamulti-milliondollarcommunitysolararrayandimplementacustomer-facingDRprogramwithtechnologyandprogramadministrationassociatedcosts.Additionally,whilethe4.5-MWarrayseemsidealforthisapplication,thereareseveralotherconsiderationsprerequisitetoanyconstructiondecision.Forexample,thesizeofthearraymight,fromatechnicalstandpoint,alsobedependentonthefeedertowhichitisinterconnected,andpossiblyevenonthehostingcapacityofthatfeeder.Landuseandbusinessfactors,marketing,andprogramdesignconsiderationsalsowouldcomeintoplaypriortoanysolardevelopmentdecision.

WouldaddingalargesolararrayandDRprogrambeacosteffectivesolutionforthevoltageimbalancesonthiscircuit?Inaword,no.However,theevidenceisclearthatasolar-plusstrategywouldnot,inthiscase,beatechnicalimpediment.Rather,itcouldsupporttheutility’scommitmenttosystemreliability.Itisimportanttolookatprogramssuchascommunitysolar,DRandenergyefficiencyholistically,andoutsidethetraditionaloperationalandplanningsilosthatexistatmanyutilities.

Page 19: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

17

Relevantquestionsforfurtherconsiderationinclude:

! Doestheutilitydesiremorecommunity-scalesolar,inthe500-kW-to10-MWrange?

! Wouldacommunitysolarimplementationmodelhelpmovemorecustomersolarfromtherooftop(whereitisgenerallyinvisibleandnon-strategic)totheutility’spreferredscaleandlocations?

! Doestheutilityhaveenergyefficiencyorloadmanagementdesiresorrequirements?

! ArethereprogramobjectivesthatneedtobemetforStaterequirements?

! Doestheutilityhaveacleanelectrificationinitiative?TheintroductionofDRandstoragemeasures,suchasgrid-interactiveelectricwaterheaters,controlledHVAC,icestorage,andstrategicelectricvehicle(EV)programscouldsupportgreateruseofelectricity,inanageofrisingrenewable-energypenetration.

! Doestheutilityforeseehavingagreenhousegasmitigationplan?

! DoestheutilityIntegratedResourcePlan(IRP)callformoreDRorrenewableresources?

Alltheseareimportantconsiderationsinlookingforopportunitiestoimplementnewdistributedresourceprojectsandprograms,whilemaintainingreliabilityandoptimizationoftheutility’sdistributionsystem,toensurequalityservicetoallcustomers.

Page 20: Community-Scale Solar Plus Thermal Storage and Demand …solarmarketpathways.org/wp-content/uploads/2018/05/... · Applying the company voltage drop design limits to the ANSI C84.1

18

About the Authors Santiago Sena is a distribution system engineer with PNM in Albuquerque, NM. Jon Hawkins is manager of advanced technology and strategy for PNM Resources, and has participated with the Community Solar Value Project (CSVP) as a member of its Utility Forum, leading the exploration of opportunities to create greater net benefits from solar-plus storage and demand response measures. Jill Cliburn is the Principal Investigator of the CSVP. John Powers is the Project Officer of the CSVP. About the Community Solar Value Project The Community Solar Value Project aims to increase the scale, reach, and value of utility-based community solar programs by using strategic solar technologies, siting, and design, improving procurement strategies, target marketing, and integrating suitable companion measures, such as demand-response and storage into broad program designs. The project is led by the San Francisco-area energy consulting and analytics firm Extensible Energy, LLC, with support from Cliburn and Associates, LLC, Olivine, Inc., and Navigant Consulting. Utility participants include the Sacramento (California) Municipal Utility District (SMUD), Public Service of New Mexico, and other utilities nationwide. The project is powered by SunShot, under the Solar Market Pathways program of the U.S. Department of Energy. Contact: http://www.communitysolarvalueproject.com; [email protected] Acknowledgment The information, data, or work presented herein was funded in part by the Office of Energy Efficiency and Renewable Energy (EERE), U.S. Department of Energy, under Award Number DE-EE0006905. Disclaimer This modeling project report a product of the Community Solar Value Project. As such, it is intended for review by project stakeholders and as a means to further the development of the technical and market strategies proposed herein. This work is not expressly endorsed or accepted by PNM. The information, data, or work presented herein was funded in part by an agency of the United States Government. Neither the United States Government nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the United States Government or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the United States Government or any agency thereof.