27
2018 Texas A&M Relay Conference Craig Palmer Hubbell Power Systems Communications Assisted Islanding Detection

Communications Assisted Islanding Detection

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Communications Assisted Islanding Detection

2018 Texas A&M Relay Conference

Craig Palmer

Hubbell Power Systems

Communications Assisted Islanding Detection

Page 2: Communications Assisted Islanding Detection

Communications Assisted Anti-Islanding

Agenda

• What is a power system island?

• Islanding detection – Local

• Islanding detection – Communications Assisted

• Direct Transfer Trip & Phase Comparison Analysis

• Phase Comparison Islanding Detection Details and Critical Functionality

• Summary

Page 3: Communications Assisted Islanding Detection

A power system island occurs when distributed generation becomes isolated from the power system grid and continues to provide power to a portion of the grid.

What is a Power System Island?

Utility Substation

Island

Page 4: Communications Assisted Islanding Detection

• Intentional

• Where an island is desired in certain circumstances (example: micro-grids)

• Unintentional

• Where an island is not desired

Unintentional islands are considered a risk to personnel safety, power quality, equipment, and

reliable grid operation.

Intentional and Unintentional Islands

What is a Power System Island?

Page 5: Communications Assisted Islanding Detection

• Personal Safety

• Generator may back feed power to disconnected lines

• Maintenance risk for utility personnel working on lines

• Public safety risk for downed lines

• System Coordination

• Reclosing into islands can cause issues and also affect coordination between inverters

• Power Quality

• Power regulation may be reduced while islanded

• Power disruptions and instability more likely

• Equipment Damage

• Resulting voltage fluctuations may cause damage to utility and customer equipment

Unintentional islanding risks

What is a Power System Island?

Page 6: Communications Assisted Islanding Detection

Islanding Detection - Local

Advantages

• Lower equipment cost

• Less maintenance

Disadvantages

• Non-detection zone (NDZ)

• Resiliency during system disturbances

Local Detection - Advantages and Disadvantages

Page 7: Communications Assisted Islanding Detection

Islanding Detection – Communications Assisted

• Direct Transfer Trip (DTT)

• Phase Comparison

Communications Assisted Methods

Communications assisted methods effectively eliminate the NDZ found in local methods.

As a result protection elements may be set less sensitively, reducing false operations during

system disturbances.

Page 8: Communications Assisted Islanding Detection

Islanding Detection – Communications Assisted

• Uses teleprotection channel to send signal to generator to open local breaker

• Can be initiated from any device which can cause an island

• Substation breaker

• Recloser

• Switch

Direct Transfer Trip (DTT)

G

GeneratorUtility Station

DTT TX DTT RX

Page 9: Communications Assisted Islanding Detection

Islanding Detection – Communications Assisted

Communications Channels:

• Direct Fiber

• Digital Network (owned or leased)

• Power Line Carrier (PLC)

• Audio tone circuit (phone line)

• Wireless radio

Communications for DTT

should emphasize security.

Direct Transfer Trip (DTT)Advantages

• No NDZ given a good communications channel

• Speed

• Reduced false tripping as a result of system disturbances

Disadvantages

• Initial and/or recurring communications cost

• Requires one comms channel for each interruption device

Page 10: Communications Assisted Islanding Detection

Islanding Detection – Communications Assisted

Phase Comparison

Phase Comparison TX

Phase Comparison RX

System Voltage

Communications Channel

Substation

GeneratorGen Voltage

Trip

OutputG

>90°

Phase Comparison Logic

The complexity of the connection does not matter

Page 11: Communications Assisted Islanding Detection

Islanding Detection – Communications Assisted

Communications Channels:

• Direct Fiber

• Digital Network (owned or leased)

• Audio tone circuit (phone line)

• Power Line Carrier (PLC)

Communications for

Phase Comparison should

emphasize dependability

Phase ComparisonAdvantages

• No NDZ given a good communications channel

• Simplicity when multiple line interruption sources exist

• Only one communications channel required per generator

• Reduced false tripping as a result of system disturbances

Disadvantages

• Initial and/or recurring communications cost

Page 12: Communications Assisted Islanding Detection

DTT & Phase Comparison Analysis

Distribution Line with Reclosers

Direct Transfer Trip Method

DTT anti-islanding requires separate DTT transmitters and receivers at the Station and at each Recloser

in order to trip for each islanding case

G

GeneratorUtility Station

DTT TX DTT RX

R R

DTT TX

DTT TX

DTT RX

DTT RX

Page 13: Communications Assisted Islanding Detection

DTT & Phase Comparison Analysis

Distribution Line with Reclosers

Phase Comparison Method

Phase Comparison anti-islanding requires only one comms channel and one transmitter / receiver pair, regardless of the number of in-line reclosers

G

GeneratorUtility Station

Phase Comparison

TX

Phase Comparison

RX

R R

Page 14: Communications Assisted Islanding Detection

DTT & Phase Comparison Analysis

Looped System Example

Direct Transfer Trip Method

Multiple comms channels and transmitter/receiver pairs between the Generator and each Station.

Complex logic design to determine the island condition

G

GeneratorUtility Station

DTT TX DTT RX

DTT TX

DTT TX DTT RX

DTT RX

DTT TX

DTT TX

DTT TX

DTT RX

DTT RX

DTT RX

Page 15: Communications Assisted Islanding Detection

DTT & Phase Comparison Analysis

Looped System Example

Phase Comparison Method

Phase Comparison anti-islanding requires only one comms channel between the Generator and Source

Station to determine the island condition, and no complex logic

G

GeneratorUtility Station

Phase Comparison

TX

Phase Comparison

RX

Page 16: Communications Assisted Islanding Detection

Phase Comparison Islanding Detection - Details

• Located at the Utility Substation

• System voltage phase input (120VAC)

• Optional DTT input for backup control

Transmit Device

Phase Comparison TX

System Voltage

Communications Channel

Substation

Page 17: Communications Assisted Islanding Detection

Phase Comparison Islanding Detection - Details

• Located at the Generator

• Receives system phase square wave

• Local voltage phase input (120VAC)

• Phase comparison logic for islanding detection

• Optional DTT output for backup control

Receive Device

Phase Comparison

RX

Communications ChannelGen Voltage

Trip Output

>90°

Phase Comparison Logic

Page 18: Communications Assisted Islanding Detection

Phase Comparison Islanding Detection - Details

• Delay inherent in communications must be compensated for

• Without compensation a fair comparison cannot be achieved

Analog Communications

• Local generator phase square wave is delayed to match received system phase

• Manual adjustment at the time of commissioning

Receiver – Delay Compensation

Page 19: Communications Assisted Islanding Detection

Phase Comparison Islanding Detection - Details

Digital Communications

• Digital circuits do not always have fixed delays as a result of circuit switching and re-routing

Dynamic Delay Compensation

• Local generator phase square wave is delayed by a fixed amount

• Active ping pong delay measurements are used to delay received system phase to match the generator phase

Receiver – Delay Compensation

Page 20: Communications Assisted Islanding Detection

Phase Comparison Islanding Detection - Details

• Compares the received system phase with the local generator phase

• Negates local generator phase (180° out of phase)

• Prevents false tripping under loss of communications

• Calculates phase difference by the amount of time in phase (coincidence)

• Quarter of a cycle or 4.25ms for 90° (60Hz)

Receiver – Phase Comparison Logic

Page 21: Communications Assisted Islanding Detection

What is a Power System Island?

IEEE 1547 – Standard for Interconnecting Distributed Resources with Electric Power Systems, recommends that an island be detected and removed within two seconds of an occurrence

IEEE 1547 Recommendations

Page 22: Communications Assisted Islanding Detection

Phase Comparison Islanding Detection - Details

• Detection time is a function of the difference in frequency at the time of separation and the set trip angle

Example:

Typical set point = 90° (4.25ms)

Generator frequency sags to 59.5Hz when islanded while the system remains at 60Hz.

Receiver – Islanding Detection Time

Detection time = 𝑆𝑒𝑡 𝑇𝑟𝑖𝑝 𝐴𝑛𝑔𝑙𝑒

360× |

1(𝑆𝑦𝑠 𝐹𝑟𝑒𝑞 −𝐺𝑒𝑛 𝐹𝑟𝑒𝑞)

|

Page 23: Communications Assisted Islanding Detection

0.000

0.500

1.000

1.500

2.000

2.500

3.000

Op

era

te T

ime

(se

con

ds)

Difference in Frequency (Hz)

Operate Time vs Delta-F for AT = 30, 60, 90

30

60

90

Operate Time Detection time = 𝑆𝑒𝑡 𝑇𝑟𝑖𝑝 𝐴𝑛𝑔𝑙𝑒

360× |

1(𝑆𝑦𝑠 𝐹𝑟𝑒𝑞 −𝐺𝑒𝑛 𝐹𝑟𝑒𝑞)

|

Phase Comparison Islanding Detection - Details

Page 24: Communications Assisted Islanding Detection

0.000

0.200

0.400

0.600

0.800

1.000

1.200

1.400

1.600

1.800

Op

era

te T

ime

(se

con

ds)

Rate of Change of Frequency (ROCOF) (Hz/s)

Operate Time vs ROCOF for AT = 30, 60, 90 Setpoints

30

60

90

𝑑𝑓

𝑑𝑡= |

𝑆𝑒𝑡 𝑇𝑟𝑖𝑝 𝐴𝑛𝑔𝑙𝑒

360∗ 𝑇𝑜𝑝𝑒𝑟𝑎𝑡𝑒

2 |Operate Time

Phase Comparison Islanding Detection - Details

Page 25: Communications Assisted Islanding Detection

Summary

• Eliminates NDZ as found with local methods

• Performance relies on the quality of the communications channel and equipment

• Performance measurements

• Security

• Dependability

• Latency

• Allows passive protection to be less sensitive reducing false tripping during system disturbances

Communications Assisted Methods

Page 26: Communications Assisted Islanding Detection

Summary

Direct Transfer Trip (DTT)

• Trip signal initiated by interruption/switching devices

• Requires one communications channel for each interruption device

Phase Comparison

• Substation voltage phase information sent to the generator for comparison with the generator phase

• Generator is tripped when phase difference reaches a preset level

• Requires only one communications link per generator

• Requires no complex DTT logic as a result of in-line reclosers, switches or multi-line connections

Communications Assisted Methods

Page 27: Communications Assisted Islanding Detection

Q & A