29
User Manual GALILEO 05/2011 MN04802059Z-EN replaces M000935-02, 10/2005 Communication Simatic S7

Communication Simatic S7 - Eaton

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Communication Simatic S7 - Eaton

User Manual GALILEO 05/2011 MN04802059Z-EN

replaces M000935-02, 10/2005

Communication

Simatic S7

Page 2: Communication Simatic S7 - Eaton

Imprint

2 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

Manufacturer Eaton Automation AG Spinnereistrasse 8-14 CH-9008 St. Gallen Schweiz www.eaton-automation.com www.eaton.com

Support Region North America Eaton Corporation Electrical Sector 1111 Superior Ave. Cleveland, OH 44114 United States 877-ETN-CARE (877-386-2273) www.eaton.com

Other regions Please contact your supplier or send an E-Mail to: [email protected]

Original instructions The German version of this document is the original instructions.

Editor A. Schmid

Brand and product names All brand and product names are trademarks or registered trademarks of the owner concerned.

Copyright © Eaton Automation AG, CH-9008 St. Gallen

All rights reserved, also for the translation.

None of this document may be reproduced or processed, duplicated or distributed by electronic sytems in any form (print, photocopy, microfilm or any other process) without the written permission of Eaton Automation AG, St. Gallen.

Subject to modifications.

Page 3: Communication Simatic S7 - Eaton

Proper use

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 3

Proper use Hardware, software, operating systems and drivers must only be used for the applications specified and only in conjunction with the components recommended by Eaton Automation AG.

Warning No warranty claims will be recognised for faults arising from the improper handling of devices and modules. The devices, even by means of communication, should not be used for the implementation of any safety functions relating to the protection of personnel and machinery. No liability is accepted for claims for damages arising from a failure or functional defect in the device. All data specified in this document does not represent warranted properties in the legal sense.

Page 4: Communication Simatic S7 - Eaton

Imprint

4 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

Page 5: Communication Simatic S7 - Eaton

Contents

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 5

Contents 1 General .................................................................................................................7

1.1 Aim and purpose of this document...........................................................................7 1.2 List of documents .....................................................................................................7

2 Operating Principle .............................................................................................9 2.1 Overview ..................................................................................................................9 2.2 MICRO PANEL in the MPI network..........................................................................9 2.3 MICRO PANEL in the Industrial Ethernet network .................................................10 2.4 Addressing .............................................................................................................11 2.5 Data block size .......................................................................................................12 2.6 Memory alignment..................................................................................................13 2.7 Status refresh .........................................................................................................13 2.8 Default Slot.............................................................................................................13

3 Siemens – MPI ...................................................................................................15 3.1 Hardware requirements..........................................................................................15 3.2 Select PLC .............................................................................................................15

3.2.1 Baud rate .................................................................................................................16 3.2.2 MMI station number.................................................................................................16 3.2.3 Highest station address (HSA) ................................................................................16 3.2.4 Driver version ..........................................................................................................16

4 Siemens – MPI (OnBoard).................................................................................17 4.1 Hardware requirements..........................................................................................17 4.2 Select PLC .............................................................................................................17

4.2.1 Baud rate .................................................................................................................18 4.2.2 MMI station number.................................................................................................18 4.2.3 Highest station address (HSA) ................................................................................18

5 Siemens – Industrial Ethernet ..........................................................................19 5.1 General...................................................................................................................19 5.2 Hardware requirements..........................................................................................19 5.3 Select PLC .............................................................................................................20

5.3.1 Startup delay ...........................................................................................................20 5.3.2 MPI/PROFIBUS station number..............................................................................21 5.3.3 MPI/PROFIBUS S7 subnet ID.................................................................................23 5.3.4 IP address ...............................................................................................................24

6 Siemens – S7 Profibus Standard Profile (OnBoard).......................................25 6.1 General...................................................................................................................25 6.2 Hardware requirements..........................................................................................25 6.3 SIMATIC Network Settings.....................................................................................26 6.4 Select PLC .............................................................................................................27

6.4.1 Baud rate .................................................................................................................27 6.4.2 MMI station number.................................................................................................27 6.4.3 Highest station address (HSA) ................................................................................28 6.4.4 Target rotation time (TTR).......................................................................................28

7 Communication Errors......................................................................................29 7.1 Error messages ......................................................................................................29 7.2 Rectification............................................................................................................29

Page 6: Communication Simatic S7 - Eaton

Contents

6 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

Page 7: Communication Simatic S7 - Eaton

1 General

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 7

1 GENERAL

1.1 AIM AND PURPOSE OF THIS DOCUMENT

This documentation describes the connection of a MICRO PANEL to a SIMATIC S7 PLC via the MPI or Ethernet interface.

Refer to the MICRO PANEL user manual for further information on connecting, commissioning and operating the MICRO PANEL.

You must be familiar with the use of the following software which must already be installed:

• SIMATIC STEP 7 PLC programming software from Siemens

• Galileo HMI programming software

Refer to the Galileo documentation or the online help for further information on Galileo and GRS.

The Galileo dialogs shown are from version 5.2.3.

1.2 LIST OF DOCUMENTS

Document Doc. No.

[1] System Description Networks in Brief MN05010009Z

[2] System Description Windows CE MN05010007Z

[3] User Manual Communication module MPB1-TP / MPB2-TP MN04802030Z

[4] User Manual Simatic S7 PG router MN04802060Z

(this list of documents is not final)

Page 8: Communication Simatic S7 - Eaton

1 General

8 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

Page 9: Communication Simatic S7 - Eaton

2 Operating Principle

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 9

2 OPERATING PRINCIPLE

2.1 OVERVIEW

This documentation describes the following three possible communication methods:

• Siemens – MPI for MICRO PANELs using the MPB2-TP communication card.

• Siemens – MPI (OnBoard) for MICRO PANELs with an OnBoard MPI interface.

• Siemens – Industrial Ethernet for MICRO PANELs with an Ethernet interface.

2.2 MICRO PANEL IN THE MPI NETWORK

A direct connection to the SIMATIC S7 is made at the programming port of the CPU (MPI). No parameter settings or function blocks are required for this connection. As soon as the MICRO PANEL is connected to the MPI network, this is indicated with the configured MPI station number in the PG device under Accessible Nodes. However is not possible to make a connection to this station using the programming device. If this is nevertheless attempted, the MICRO PANEL will refuse the connection and the programming device will indicate “Station refuses connection establishment”.

The MICRO PANEL can establish an active connection simultaneously with up to 42 MPI stations (SIMATIC S7 PLCs).

The SIMATIC PLC only supports a limited number of MPI connections, depending on the CPU in use. Each MICRO PANEL uses one OP (operator panel) connection.

The following are the standard address settings in the MPI network:

• MPI address 0 is reserved for the SIMATIC PG.

• MPI address 1 is the default setting for an Operator Panel (MMI)

• MPI address 2 is the default setting for a PLC

• MPI address 3 up to HSA (highest station address) available as required

MICRO PANEL

ST5 ST4 ST2

ST1 ST0 ST3

PG

Page 10: Communication Simatic S7 - Eaton

2 Operating Principle

10 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

2.3 MICRO PANEL IN THE INDUSTRIAL ETHERNET NETWORK

A direct connection to the SIMATIC S7 is made at the Ethernet port of the CPU or the CP. No additional parameter settings or function blocks are required for this connection. It is also possible to use a router to communicate with other PLCs in the MPI/PROFIBUS network. This requires a station in the Ethernet network to carry out this router function, and a SIMATIC S7 station with an Ethernet and MPI/PROFIBUS interface or a MICRO PANEL with Ethernet and MPI-OnBoard interface can be used for this purpose.

Further information on using a MICRO PANEL as a router is available in the “S7 PG Router” manual 4T[5]T).

The MICRO PANEL can establish an active connection simultaneously with several stations (SIMATIC S7 PLC).

The SIMATIC S7 PLC only supports a limited number of connections, depending on the CPU in use. Each MICRO PANEL uses one OP connection.

Station and IP addresses are given as examples. It is essential that every station has a unique and unambiguous station and/or IP address.

Ethernet

192.168.0.39

192.168.0.2

ST 2

MPI/PROFIBUS ST 31

192.168.0.4 192.168.0.3

ST 4

Router ST 5 or

192.168.0.40

MPI/PROFIBUS

Page 11: Communication Simatic S7 - Eaton

2 Operating Principle

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 11

2.4 ADDRESSING

The addressing is implemented using the SIMATIC syntax and all commonly available data types are supported.

Addressing format without station number Data area

AB %d.%d Output

EB %d.%d Input

MB %d.%d Marker

DB %d.DBX %d.%d

DB %d.DBB %d

DB %d.DBW %d

DB %d.DBD %d

Data access in data block

Addressing format with station number Data area

ST %d:AB %d.%d Output

ST %d:EB %d.%d Input

ST %d:MB %d.%d Marker

ST %d:DB %d.DBX %d.%d

ST %d:DB %d.DBB %d

ST %d:DB %d.DBW %d

ST %d:DB %d.DBD %d

Data access in data block

The placeholder %d represents a decimal number which must be entered for addressing the individual tags. The ST entry defines the station number in the MPI/PROFIBUS network. If no station number is specified in the address, the standard station number from the Select PLC dialog is used.

Driver version * 2.00 is required when using the MPB2-TP communication card and the addressing format without station number.

Page 12: Communication Simatic S7 - Eaton

2 Operating Principle

12 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

If a station number is specified in the address, the standard station number from the Select PLC dialog is not relevant for this tag.

The tag import of the symbol file is supported from Galileo V5.1.3. Further information is provided in the Galileo documentation.

2.5 DATA BLOCK SIZE

The smallest possible format is 8-bit or 1-byte format. Single bit communication is therefore not possible. The maximum size of a data block depends on the type of communication selected. The structure and array size defined in Galileo is therefore restricted to this maximum value.

The PLC Data tab in the Select PLC... dialog shows all the data block sizes that are supported.

Data types >8 bits can only be set on even addresses.

Page 13: Communication Simatic S7 - Eaton

2 Operating Principle

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 13

2.6 MEMORY ALIGNMENT

The memory alignment defines how the individual tags of a structure are stored in the memory of a PLC. Siemens data blocks are normally defined with a 2-byte memory alignment. Refer to the Galileo documentation or the Galileo Online Help for further information on memory alignment.

2.7 STATUS REFRESH

The Status refresh defines the maximum refresh time in seconds of the status structure. If the MMI status does not change within the refresh time, the status structure is transferred to the PLC anyway. This is necessary if bit 0 is used in the status structure in order to monitor the connection to the MMI. A default setting of 10s is recommended. Further information on this subject is provided in the Galileo documentation.

The shorter the refresh time, the more this will burden communication between the panel and the PLC. This may create a situation in which only the status structure is transferred.

2.8 DEFAULT SLOT

If a direct connection to the SIMATIC S7 is made at the programming port of the CPU (MPI), the value can be set to 0. Otherwise the slot number of the target CPU in the rack is to fill in. Rack 0 corresponds to 1..31, rack 1 corresponds to 33… 63 etc.

This setting has validity for all stations of a connection.

Page 14: Communication Simatic S7 - Eaton

2 Operating Principle

14 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

Page 15: Communication Simatic S7 - Eaton

3 Siemens – MPI

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 15

3 SIEMENS – MPI

3.1 HARDWARE REQUIREMENTS

This communication method requires the use of the MPB2-TP communication card and therefore requires the use of a MICRO PANEL with a communication slot.

Refer to the User Manual Communication module MPB1-TP / MPB2-TP for information on configuring and commissioning the MPB2-TP communication card 5T[3]T.

Refer to the document “System Description Networks in Brief” for information on the communication cable 5T[1]T.

3.2 SELECT PLC

The MPB2-TP communication card supports only one connection. Several connections cannot therefore be configured on the same interface. Communication with several PLCs is possible in the MPI network, however addressing the system structures is limited to one PLC in the MPI subnet.

For this, select “Siemens MPI” in the Select PLC... dialog. The dialog shown will then appear for setting the parameters required for this communication.

Parameter setting for Status Refresh ( chap. 2.7)

Parameter setting for Default Station Number ( chap. 2.4)

Parameter setting for Default Slot ( chap.2.8)

Page 16: Communication Simatic S7 - Eaton

3 Siemens – MPI

16 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

3.2.1 BAUD RATE

Only a baud rate of 187.5kB is supported. The baud rate must correspond to the baud rate setting of the MPI subnet in the SIMATIC Manager of STEP 7.

3.2.2 MMI STATION NUMBER

Station number of the MICRO PANEL in the MPI subnet. This must be set between 1 and the HSA. It must also be ensured that each station in the MPI subnet is assigned a unique MPI address.

In all cases check with the SIMATIC PG device under Accessible Nodes which addresses have already been assigned.

3.2.3 HIGHEST STATION ADDRESS (HSA)

The highest MPI address setting is used to optimise the MPI subnet. This setting must correspond to the highest MPI address setting of the MPI subnet in the SIMATIC Manager of STEP 7. The following values are possible: 15,31,63,126.

3.2.4 DRIVER VERSION

The name and version of the driver file are displayed in the PLC Data tab of the Select PLC ... dialog.

The driver file must be loaded on the MPB2-TP communication card. The version of the driver loaded on the MPB2-TP communication card is indicated when the application is started up on the MICRO PANEL. The loaded driver version is also displayed in a system message ( chap. 6.1).

Refer to the User Manual Communication module MPB1-TP / MPB2-TP for information on loading the driver file and other settings required for the MPB2-TP communication card [3].

Page 17: Communication Simatic S7 - Eaton

4 Siemens – MPI (OnBoard)

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 17

4 SIEMENS – MPI (ONBOARD)

4.1 HARDWARE REQUIREMENTS

This communication method requires a MICRO PANEL with an MPI OnBoard interface. Refer to the document "Installation instructions, General wiring instructions" for information on the communication cable 5T[1]T.

At least 40 additional license points must be available on the device, regardless of the number of connections!

If you have any questions on license products, please contact your local MICRO PANEL sales distributor.

4.2 SELECT PLC

The OnBoard interface supports several connections, i.e. several connections can therefore be configured on the same interface. This makes it possible to address the tags including the system structures on several PLCs in the MPI network. Baud rate, MMI station number and HSA must be identical on all connections.

For this, select Siemens MPI (OnBoard) in the Select PLC... dialog. The dialog shown will then appear for setting the parameters required for this communication method.

Parameter setting for Status refresh ( chap. 2.7)

Parameter setting for Default Station Number ( chap. 2.4)

Parameter setting for Default Slot ( chap.2.8)

Page 18: Communication Simatic S7 - Eaton

4 Siemens – MPI (OnBoard)

18 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

4.2.1 BAUD RATE

187.5kB and 1.5MB are supported. The baud rate must correspond to the baud rate setting of the MPI subnet in the SIMATIC Manager of STEP 7.

4.2.2 MMI STATION NUMBER

Station number of the MICRO PANEL in the MPI network. This must be set between 1 and the HSA. It must also be ensured that each station in the MPI subnet is assigned a unique MPI address. In all cases check with the SIMATIC PG device under Accessible Nodes which addresses have already been assigned.

4.2.3 HIGHEST STATION ADDRESS (HSA)

The highest MPI address setting is used to optimise the MPI subnet. This setting must correspond with the highest MPI address of the MPI subnet in the SIMATIC Manager of STEP 7. The following values are possible: 15,31,63,126.

Page 19: Communication Simatic S7 - Eaton

5 Siemens – Industrial Ethernet

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 19

5 SIEMENS – INDUSTRIAL ETHERNET

5.1 GENERAL

At least one of the following versions of the SIMATIC Manager is required in order to use the Industrial Ethernet:

a) STEP 7 V5.2 + Net driver

b) STEP 7 V5.3

Further information on creating and configuring a SIMATIC network is provided in the Help system of the SIMATIC Manager and SIMATIC NetPro.

Before creating a connection with a MICRO PANEL to a SIMATIC S7 PLC, you should ensure that the SIMATIC S7 PLC is accessible from the SIMATIC PG on the network.

5.2 HARDWARE REQUIREMENTS

This communication method requires a MICRO PANEL with an Ethernet interface.

Refer to Ethernet in the document “Installation instructions, General wiring instructions” for information on the communication cable 5T[1] T.

At least 80 additional license points must be available on the device, regardless of the number of connections!

If you have any questions on license products, please contact your local MICRO PANEL sales distributor.

Page 20: Communication Simatic S7 - Eaton

5 Siemens – Industrial Ethernet

20 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

5.3 SELECT PLC

The Ethernet interface supports several connections, i.e. several connections can therefore be configured on the same interface. This makes it possible to address the tags including the system structures on several PLCs in the MPI/PROFIBUS network.

For this, select Siemens Industrial Ethernet in the Select PLC... dialog. The dialog shown will then appear for setting the parameters required for this communication.

Parameter setting for Status refresh ( chap. 2.7)

Parameter setting for Default Station Number ( chap. 2.4)

Parameter setting for Default Slot ( chap.2.8)

5.3.1 STARTUP DELAY

During this time, error messages concerning communication are suppressed. This is useful if the startup of the SIMATIC S7 station takes longer than the startup of the MICRO PANEL. After startup, the MICRO PANEL immediately tries to start communication. An error message, however, is only generated after the set time has elapsed.

If a startup delay of >0 is set, a green system message will appear as soon as communication is successful started.

If there is no communication to the CP/CPU established, check the accessibility of the CP/CPU with the PING command.

Page 21: Communication Simatic S7 - Eaton

5 Siemens – Industrial Ethernet

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 21

5.3.2 MPI/PROFIBUS STATION NUMBER

This is where the station number is entered for the station defined as the router in the MPI/PROFIBUS subnet. This can be a MICRO PANEL or a SIMATIC S7 station.

The following example shows communication with a SIMATIC S7 station used as the router. Station number 31 must be entered for communication with station 2 and 31.

The following example shows communication with a MICRO PANEL station used as the router. Station number 31 must be entered for communication with station 2.

Page 22: Communication Simatic S7 - Eaton

5 Siemens – Industrial Ethernet

22 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

In the following example with a PLC directly on the Ethernet network, communication with station number 5 consequently requires 5 to be entered.

Page 23: Communication Simatic S7 - Eaton

5 Siemens – Industrial Ethernet

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 23

5.3.3 MPI/PROFIBUS S7 SUBNET ID

The MPI/PROFIBUS S7 subnet ID only has to be entered if a PLC in the MPI/PROFIBUS subnet is to be accessed via a router. In the following example, this would be required for station number 2. If the PLC is accessible directly via the Ethernet network, no subnet ID has to be entered. The MPI/PROFIBUS S7 subnet ID is shown in the SIMATIC network configuration, and must not be confused with the Ethernet S7 subnet ID.

(Dialog is from the SIMATIC Manager of STEP 7)

Page 24: Communication Simatic S7 - Eaton

5 Siemens – Industrial Ethernet

24 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

5.3.4 IP ADDRESS

The IP address entry must match the setting of the SIMATIC station or the MICRO PANEL with a PG router function. This is the IP address of the router and the station on the Ethernet network.

The following example requires the configuration of 2 connections:

1. Connection to station number 2 and 31, 192.168.0.39 must be entered.

2. Connection to station number 5, 192.168.0.40 must be entered.

(Dialog is from the SIMATIC Manager of STEP 7)

The subnet mask of the MICRO PANEL must be suitable for the subnet mask of the SIMATIC S7 station. For further information on setting the IP address of the MICRO PANEL refer to the " System Description Windows CE " TT[2] TH.

Page 25: Communication Simatic S7 - Eaton

6 Siemens – S7 Profibus Standard Profile (OnBoard)

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 25

6 SIEMENS – S7 PROFIBUS STANDARD PROFILE (ONBOARD)

6.1 GENERAL

In order to use this communication you need a SIMATIC CPU/CP which supports S7 communication via PROFIBUS at least as a slave.

Each MICRO PANEL is assigned to at least one OP connection.

Further information on creating and configuring a SIMATIC network is provided in the Help system of the SIMATIC Manager and SIMATIC NetPro.

6.2 HARDWARE REQUIREMENTS

This communication requires a MICRO PANEL with an OnBoard MPI/DP interface. Information on the communication cable is provided in the section on Profibus in the document "System Description Network in brief" [1].

The device must have 40 license points available, irrespective of the number of connections.

If you have any questions on license products, please contact your MICRO PANEL sales distributor.

Page 26: Communication Simatic S7 - Eaton

6 Siemens – S7 Profibus Standard Profile (OnBoard)

26 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

6.3 SIMATIC NETWORK SETTINGS

Select the Standard profile in the Profile list box. The Options... button provided with this profile enables other bus stations that cannot be configured with STEP 7 to be included in the calculation of the bus parameters.

Please contact our Support if you cannot operate Profibus with the bus parameters of the standard profile.

Precisely one active station with S7 communication load must be added for each MICRO PANEL. The share of communication in the entire bus load must be set to ‘Low’.

Page 27: Communication Simatic S7 - Eaton

6 Siemens – S7 Profibus Standard Profile (OnBoard)

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 27

6.4 SELECT PLC

Galileo supports several connections for the OnBoard interface, i.e. several connections can be connected on the same interface. This makes it possible to address the tag variables including the system structures on several PLCs. Baud rate, MMI station number, HSA and TTR must be identical on all connections.

Select Siemens – S7 Profibus Standard Profile (OnBoard) in the Select PLC ... dialog. The dialog shown above will then appear for setting the parameters required for this communication.

Parameter setting for Status Refresh ( chap. 2.7)

Parameter setting for Default Station No. ( chap.2.4)

Parameter setting for Default Slot ( chap. Fehler! Verweisquelle konnte nicht gefunden werden.)

6.4.1 BAUD RATE

Baud rates of 9.6kB, 19.2kB, 45.45kB, 93.75kB, 187.5kB, 500kB and 1.5MB are supported. The baud rate must correspond to the setting of the baud rate of the PROFIBUS network in the SIMATIC Manager of STEP 7.

The baud rate of 45.45kB is designed for segment couplers and links to PROFIBUS-PA.

6.4.2 MMI STATION NUMBER

Station number of the MICRO PANEL in the PROFIBUS network. This must be set between 1 and the HSA. It must also be ensured that each station in the PROFIBUS subnet is assigned a unique PROFIBUS address.

Page 28: Communication Simatic S7 - Eaton

6 Siemens – S7 Profibus Standard Profile (OnBoard)

28 Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com

6.4.3 HIGHEST STATION ADDRESS (HSA)

The highest PROFIBUS address is used to optimize the PROFIBUS subnet. This must correspond to the setting of the highest PROFIBUS address of the PROFIBUS subnet in the SIMATIC Manager of STEP 7. Permissible values are 15, 31, 63 and 126.

6.4.4 TARGET ROTATION TIME (TTR)

The TTR in t_Bit is calculated in the STEP 7 network configuration and must be used accordingly. Be aware that changes to the SIMATIC network settings can affect the TTR.

Page 29: Communication Simatic S7 - Eaton

7 Communication Errors

Communication Simatic S7 05/2011 MN04802059Z-EN www.eaton.com 29

7 COMMUNICATION ERRORS

7.1 ERROR MESSAGES

Different system error messages are generated in response to any communication errors that occur. These system error messages provide different information:

• The tag name indicates the tag in which a problem was found.

• The interface information indicates the MICRO PANEL interface on which the problem was found.

• The driver version indicates which communication driver is active.

• The station number after ST# corresponds to the MPI address of the affected PLC (CPU).

• The additional information may indicate the possible cause of an error in plain text. This information can, however, also be generated from lower software layers. Its content can therefore only be interpreted with an in-depth knowledge of the system. The troubleshooting procedure is nevertheless the same in all cases.

7.2 RECTIFICATION

Checking the following points is recommended:

• Check the cabling and the connections on the MICRO PANEL and the PLC.

• When using a communication card, check the jumper settings and driver loaded with the version on the card ( chap.3.2.4).

• Check the baud rate and HSA settings. These settings must be the same on all stations. Check all other parameters in the Select PLC... dialog.

• Check the MPI addresses in the network. Is the station number indicated in the system error message present or available in the MPI/PROFIBUS network? An address must only be present once.

• Is the address of the tag indicated in the system error message present in the corresponding station? (is the corresponding DB present?)

• Is the Ethernet communication overloaded?

• Is the PLC (CPU) accessible via the SIMATIC PG device?

• Is the PLC (CPU/CP) accessible via Ethernet via PING command?

If the problem continues, contact our Customer Support at [email protected].

Tag name

Interface

Driver version Station number

Additional error information