Island canopy style ventilator for use over medium duty equipment suitable for interior ceiling heights less than 8’6” by recessing into false ceiling.
These SW(DI) Series models are low velocity ceiling-mounted canopy ventilators which are U.L. Listed under the category of “Exhaust Hood Without Exhaust Damper.” Units are available in custom depths depending on particular cooking battery layout. All models include a full array of U.L. classified grease removing filters and a grease col-lecting gutter sloped to a removeable grease cup at either end.
When properly operated and maintained, the liquefied grease is drained off into a con-tainer for periodic removal and cleaning.
At periodic intervals (such as the end of each cooking day) the filters are to be re-moved and cleaned. They may be washed in a dishwasher, hand washed or soaked and rinsed.
Appropriately conditioned supply air must be mechanically delivered to the space to replace exhausted air. Generally 80% is so delivered through the HVAC system with the remaining 20% flowing naturally from adjoining areas.
Exhaust fan(s) and supply fan(s) are available. See fan section of catalog or web site for design information. Fans must be designed for Hood Depot air volumes and static pres-sure drop for the entire system and must be in compliance with local codes.• Exhaust fan(s) should be properly sized and include UL762 listings• Discharge ducts should be vertical when possible and located away from air intakes• Supply fan(s) should be equipped with throw-away or cleanable type filters• Exhaust and supply fans require a magnetic starter switch with 120 Volt holding coil and should be electrically interlocked for simultaneous operation• Exhaust/supply fans should be operated through a listed kitchen hood control panel
NFPA 96 and most other codes require a fire extinguishing system for protection of both the duct collar and plenum areas of ventilators and for the protection of cooking equip-ment such as fat fryers, griddles, ranges and broilers which may be source of ignition of grease. Check with local fire authorities for exact requirements.
Consult Hood Depot regarding custom services addressing:• Exhaust Fans, Supply Fans and rooftop units• Fire protection systems• Heat Recovery Units• Reduced Throat (low air volume) Ventilators• Utility Distribution Systems (UDS)• Air Purification Systems• Listed Control Panels• Demand Ventilation• HEPA Intake Units• ASTM 2519 High Efficiency Filters
Model SW(DI)Island Style Exhaust Canopy
ITEM NO.__________
PRODUCT SPECIFICATIONS
APPLICATION
DESCRIPTION
OPERATION
MAINTENANCE
AIR SUPPLY GUIDELINES
EXHAUST/SUPPLY FAN UNITS
FIRE PROTECTION
OPTIONAL EQUIPMENT
Furnish Hood Depot’s ventilator model SW(DI) (ventilator without fire damper at the inlet slot) as shown on plans, with a depth of _______ and an overall length of _______ and to meet the following requirements:
GENERAL DESCRIPTION: Ventilator is a conventional filter-type hood with continuous array of baffle U.L. Classified filters along the entire ventilator length. Ventilators up to 12’ to include semi-concealed pitched gutter which slopes to removable grease cup. Ventilators over 12’ include two pitched gutters that slope to removable grease cups located at each extreme end. Ventilator shall include means for hanging.
CONSTRUCTION MATERIALS: The ventila-tor shall be 18 gauge all-stainless steel con-struction. A number 4 finish shall be provided on all exposed surfaces.
LIGHT FIXTURES: Ventilator shall be equipped with U.L. Listed ___ 100 Watt Dome Incandescent or ___ Recessed 150 Watt In-candescent or ___ Recessed Fluorescent fixtures. Light fixtures shall be prewired to a single point of connection at the factory.
APPROVALS: Ventilator to be U.L. Listed, list-ed by NSF, and in accordance with all recom-mendations of NFPA 96. The ventilator must meet all applicable codes.
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
*For full model number add canopy depth and height in inches as suffix (Example: Model SW(E-DI)-6024 for hood size 60” deep x 24” high)
710 Powerline Road Suite HDeerfield Beach, FL 33442
(954) 570-9860 (800) 322-8730 FAX (954) 570-9865www.hooddepot.net
• Top Enclosure Skirts• S/S Filters• Wall Panels• 3” Left or Right Standoffs• Fluorescent Lights
Page 18
Hood lengths available from 4’0” to 16’0” in 6” increments. For lengths 6’6” to 12’0” the maximum offset from centerline and/or make-up air openings to end of hood shall not exceed 6”0”. Lengths from 12’0” to 16’0” shall incorporate two exhaust ducts, each not to exceed 6’0” on center. Filters and lights are added in proportion to length.
Sizes Available
Lengths Available
Model SW(DI)Island Style Exhaust Canopy
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
Model SW(DI)
Light & Medium duty: Cooking surfaces to 400˚= 250 cfm / lf per side. Heavy duty: Cooking surfaces to 850˚= 280 cfm / lf per side. CFM criteria can vary and a higher cfm/lf is sometimes factory advised; contact us for airflow recommendation for your specific appliance layout. Also see SWLV(DI) for lower cfm light and medium duty hoods.
Airflow Data
EQUIPMENT TYPE:MEDIUM LOAD..........Kettles (under 60 Gals.), hot top ranges, gas fryers, griddlesHEAVY LOAD.............Charbroilers, high grease equipment
Engineering Data
ElectricalAn optional Hood Depot Control Panel can be provided for each exhaust fan. A contactor or motor starter will be provided for each fan. See section “Control Panels” in our catalog or visit our web site for more information.
Static PressureStatic pressure drops across ventilator: Model SW(DI).......................0.625 W.G. at the duct collar
Canopy Hanging WeightsHood Depth 80” 90” 108” 120” (Other depths avail.)Wgt. per lin. ft. (LBS) 100 110 130 140
Perspective View (N.T.S.)
Canopies available in widths of 80”, 96”, 108” and 120”. Height can be 24” or 30” depending on ceiling height. Custom widths and heights available; contact factory.
End View Elevation / Cutaway
Note: Fire cabinet weight needs to be added to canopy hanging weight below
Page 19
Ceiling mounted canopy style ventilator for use over light/medium duty equipment suitable for interior ceiling heights less than 8’6” by recessing into false ceiling.
These SWLV(DI) Series models are for low velocity wall-mounted canopy ventilators which are U.L. Listed under the category of “Exhaust Hood Without Exhaust Damper.” Units are available in custom depths depending on particular cooking battery layout. All models include a full array of U.L. classified grease removing filters and a grease col-lecting gutter sloped to a removeable grease cup at either end.
When properly operated and maintained, the liquefied grease is drained off into a con-tainer for periodic removal and cleaning.
At periodic intervals (such as the end of each cooking day) the filters are to be re-moved and cleaned. They may be washed in a dishwasher, hand washed or soaked and rinsed.
Appropriately conditioned supply air must be mechanically delivered to the space to replace exhausted air. Generally 80% is so delivered through the HVAC system with the remaining 20% flowing naturally from adjoining areas.
Exhaust fan(s) and supply fan(s) are available. See fan section of catalog or web site for design information. Fans must be designed for Hood Depot air volumes and static pres-sure drop for the entire system and must be in compliance with local codes.• Exhaust fan(s) should be properly sized and include UL762 listings• Discharge ducts should be vertical when possible and located away from air intakes• Supply fan(s) should be equipped with throw-away or cleanable type filters• Exhaust and supply fans require a magnetic starter switch with 120 Volt holding coil and should be electrically interlocked for simultaneous operation• Exhaust/supply fans should be operated through a listed kitchen hood control panel
NFPA 96 and most other codes require a fire extinguishing system for protection of both the duct collar and plenum areas of ventilators and for the protection of cooking equip-ment such as fat fryers, griddles, ranges and broilers which may be source of ignition of grease. Check with local fire authorities for exact requirements.
Consult Hood Depot regarding custom services addressing:• Exhaust Fans, Supply Fans and rooftop units• Fire protection systems• Heat Recovery Units• Reduced Throat (low air volume) Ventilators• Utility Distribution Systems (UDS)• Air Purification Systems• Listed Control Panels• Demand Ventilation• ASTM 2519 High Efficiency Filters
Model SWLV(DI) Island Style Low Velocity Exhaust Canopy
ITEM NO.__________
PRODUCT SPECIFICATIONS
APPLICATION
DESCRIPTION
OPERATION
MAINTENANCE
AIR SUPPLY GUIDELINES
EXHAUST/SUPPLY FAN UNITS
FIRE PROTECTION
OPTIONAL EQUIPMENT
Furnish Hood Depot’s ventilator model SWLV(DI) (ventilator without fire damper at the inlet slot) as shown on plans, with a depth of _______ and an overall length of _______ and to meet the following requirements:
GENERAL DESCRIPTION: Ventilator is a conventional filter-type hood with continuous array of baffle U.L. Classified filters along the entire ventilator length. Ventilators up to 12’ to include semi-concealed pitched gutter which slopes to removable grease cup. Ventilators over 12’ include two pitched gutters that slope to removable grease cups located at each extreme end. Ventilator shall include means for hanging.
CONSTRUCTION MATERIALS: The ventila-tor shall be 18 gauge all-stainless steel con-struction. A number 4 finish shall be provided on all exposed surfaces.
LIGHT FIXTURES: Ventilator shall be equipped with U.L. Listed ___ 100 Watt Dome Incandescent or ___ Recessed 150 Watt In-candescent or ___ Recessed Fluorescent fixtures. Light fixtures shall be prewired to a single point of connection at the factory.
APPROVALS: Ventilator to be U.L. Listed, list-ed by NSF, and in accordance with all recom-mendations of NFPA 96. The ventilator must meet all applicable codes.
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
*For full model number add canopy depth and height in inches as suffix (Example: Model SWLV(DI)-12024 for hood size 120” deep x 24” high)
710 Powerline Road Suite HDeerfield Beach, FL 33442
(954) 570-9860 (800) 322-8730 FAX (954) 570-9865www.hooddepot.net
• HEPA Intake Units• Top Enclosure Skirts• S/S Filters• Wall Panels• 3” Left or Right Standoffs• Fluorescent Lights
Page 16
Hood lengths available from 4’0” to 16’0” in 6” increments. For lengths 6’6” to 12’0” the maximum offset from centerline and/or make-up air openings to end of hood shall not exceed 6”0”. Lengths from 12’0” to 16’0” shall incorporate two exhaust ducts, each not to exceed 6’0” on center. Filters and lights are added in proportion to length.
Sizes Available
Lengths Available
Model SWLV(DI)Island Style Low Velocity Exhaust Canopy
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
Model SWLV(DI)
U.L. Listed for 150CFM / L.F. per side. Contact factory for de-sign criteria for specific appliance line layout designed for more CFM / L.F. (if equipment includes ranges fryers or griddles).
Airflow Data
EQUIPMENT TYPE:LIGHT LOAD..............Steamers, ovens, kettles (under 20 Gals.), open burner ranges, griddles, electric fryers, braising pans
Engineering Data
ElectricalAn optional Hood Depot Control Panel can be provided for each exhaust fan. A contactor or motor starter will be provided for each fan. See section “Control Panels” in our catalog or visit our web site for more information.
Static PressureStatic pressure drops across ventilator: Model SWLV(DI).......................0.50 W.G. at the duct collar
Canopy Hanging WeightsHood Depth 80” 96” 108” 120” (Other depths avail.)Wgt. per lin. ft. (LBS) 100 110 130 140
Perspective View (N.T.S.)
Canopies available in widths of 80”, 96”, 108” and 120”. Height can be 24” or 30” depending on ceiling height. Custom widths and heights available; contact factory.
Note: Fire cabinet weight needs to be added to canopy hanging weight below
Page 17
End View Elevation / Cutaway
Ceiling mounted canopy style ventilator for use over medium duty equipment suitable for interior ceiling heights less than 8’6” by recessing into false ceiling.
These AM(DI) Series models are for high velocity ceiling-mounted canopy ventilators which are U.L. Listed under the category of “Exhaust Hood Without Exhaust Damper.” Units are available in custom depths depending on particular cooking battery layout. All models include a full array of U.L. classified grease removing filters and a grease collecting gutter sloped to a removeable grease cup at either end. Supply air is to be introduced through the interior of the hood (short circuit)
When properly operated and maintained, the liquefied grease is drained off into a con-tainer for periodic removal and cleaning.
At periodic intervals (such as the end of each cooking day) the filters are to be re-moved and cleaned. They may be washed in a dishwasher, hand washed or soaked and rinsed.
Appropriately conditioned supply air must be mechanically delivered to the space to re-place exhausted air. Generally 50% is so delivered through the hood with the remaining 50% flowing naturally from adjoining areas and through the HVAC system.
Exhaust fan(s) and supply fan(s) are available. See fan section of catalog or web site for design information. Fans must be designed for Hood Depot air volumes and static pres-sure drop for the entire system and must be in compliance with local codes.• Exhaust fan(s) should be properly sized and include UL762 listings• Discharge ducts should be vertical and located away from air intakes• Supply fan(s) should be equipped with throw-away or cleanable type filters• Exhaust and supply fans require a magnetic starter switch with 120 Volt holding coil and should be electrically interlocked for simultaneous operation• Exhaust and supply fans should be operated through a listed kitchen hood control panel
NFPA 96 and most other codes require a fire extinguishing system for protection of both the duct collar and plenum areas of ventilators and for the protection of cooking equip-ment such as fat fryers, griddles, ranges and broilers which may be source of ignition of grease. Check with local fire authorities for exact requirements.
Consult Hood Depot regarding custom services addressing:• Exhaust Fans, Supply Fans and rooftop units• Fire protection systems• Heat Recovery Units• Reduced Throat (low air volume) Ventilators• Utility Distribution Systems (UDS)• Air Purification Systems• Listed Control Panels• Demand Ventilation• ASTM 2519 High Efficiency Filters
Model AM(DI)Internally Compensated Exhaust Canopy
ITEM NO.__________
PRODUCT SPECIFICATIONS
APPLICATION
DESCRIPTION
OPERATION
MAINTENANCE
AIR SUPPLY GUIDELINES
EXHAUST/SUPPLY FAN UNITS
FIRE PROTECTION
OPTIONAL EQUIPMENT
Furnish Hood Depot’s ventilator model AM(DI) (ventilator without fire damper at the inlet slot) as shown on plans, with a depth of _______ and an overall length of _______ and to meet the following requirements:
GENERAL DESCRIPTION: Ventilator is a conventional filter-type hood with continuous array of baffle U.L. Classified filters along the entire ventilator length. Ventilators up to 12’ to include semi-concealed pitched gutter which slopes to removable grease cup. Ventilators over 12’ include two pitched gutters that slope to removable grease cups located at each extreme end. Ventilator shall include means for hanging.
CONSTRUCTION MATERIALS: The ventila-tor shall be 18 gauge all-stainless steel con-struction. A number 4 finish shall be provided on all exposed surfaces.
LIGHT FIXTURES: Ventilator shall be equipped with U.L. Listed ___ 100 Watt Dome Incandescent or ___ Recessed 150 Watt In-candescent or ___ Recessed Fluorescent fixtures. Light fixtures shall be prewired to a single point of connection at the factory.
APPROVALS: Ventilator to be U.L. Listed, list-ed by NSF, and in accordance with all recom-mendations of NFPA 96. The ventilator must meet all applicable codes.
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
*For full model number add canopy depth and height in inches as suffix (Example: Model AM(DI)-12024 for hood size 120” deep x 24” high)
710 Powerline Road Suite HDeerfield Beach, FL 33442
(954) 570-9860 (800) 322-8730 FAX (954) 570-9865www.hooddepot.net
• HEPA Intake Units• Top Enclosure Skirts• S/S Filters• Wall Panels• 3” Left or Right Standoffs• Fluorescent Lights
Page 22
Hood lengths available from 4’0” to 16’0” in 6” increments. For lengths 6’6” to 12’0” the maximum offset from centerline and/or make-up air openings to end of hood shall not exceed 6”0”. Lengths from 12’0” to 16’0” shall incorporate two exhaust ducts, each not to exceed 6’0” on center. Filters and lights are added in proportion to length.
Sizes Available
Lengths Available
Model AM(DI)Island Style Internally Compensated Exhaust Canopy
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
U.L. Listed for 300CFM / L.F. exhaust air and 150CFM / L.F. supply air per side. Contact factory for design criteria for specific appliance line layout designed for more CFM / L.F. (if equipment includes ranges fryers or griddles).
Airflow Data
EQUIPMENT TYPE:LIGHT LOAD.........Steamers, ovens, kettles (under 20 Gals.), open burner ranges, pasta cookers, electric fryers, braising pans
Engineering Data
ElectricalAn optional Hood Depot Control Panel can be provided for each exhaust fan. A contactor or motor starter will be provided for each fan. See section “Control Panels” in our catalog or visit our web site for more information.
Static PressureStatic pressure drops across ventilator: Model AM(DI).......................0.625 W.G. at the duct collar
Canopy Hanging WeightsHood Depth 108” 120” 132” (Other depths avail.)Wgt. per lin. ft. (LBS) 130 150 170
Perspective View (N.T.S.)
Canopies available in widths of 108”, 120” and 132”. Height can be 24” or 30” depending on ceiling height. Custom widths and heights available; contact factory. End View Elevation / Cutaway
Model AM(DI)
Note: Fire cabinet weight needs to be added to canopy hanging weight below
Page 23
Ceiling mounted canopy style ventilator for use over medium duty equipment suitable for interior ceiling heights less than 8’6” by recessing into false ceiling.
These SW(FP-DI) Series models are low velocity ceiling-mounted canopy ventilators which are U.L. Listed under the category of “Exhaust Hood Without Exhaust Damper.” Units are available in custom depths depending on particular cooking battery layout. All models include a full array of U.L. classified grease removing filters and a grease collecting gutter sloped to a removeable grease cup at either end. Supply plenum to be designed for air to be introduced with a velocity of approximately 150 fpm. Supply plenum depth varies depending on exhaust cfm.
When properly operated and maintained, the liquefied grease is drained off into a con-tainer for periodic removal and cleaning.
At periodic intervals (such as the end of each cooking day) the filters are to be re-moved and cleaned. They may be washed in a dishwasher, hand washed or soaked and rinsed.
Appropriately conditioned supply air must be mechanically delivered to the space to re-place exhausted air. Generally 50-80% is so delivered through the hood with the remain-ing 20-50% flowing naturally from adjoining areas and through the HVAC system.
Exhaust fan(s) and supply fan(s) are available. See fan section of catalog or web site for design information. Fans must be designed for Hood Depot air volumes and static pres-sure drop for the entire system and must be in compliance with local codes.• Exhaust fan(s) should be properly sized and include UL762 listings• Discharge ducts should be vertical and located away from air intakes• Supply fan(s) should be equipped with throw-away or cleanable type filters• Exhaust and supply fans require a magnetic starter switch with 120 Volt holding coil and should be electrically interlocked for simultaneous operation• Exhaust and supply fans should be operated through a listed kitchen hood contral panel
NFPA 96 and most other codes require a fire extinguishing system for protection of both the duct collar and plenum areas of ventilators and for the protection of cooking equip-ment such as fat fryers, griddles, ranges and broilers which may be source of ignition of grease. Check with local fire authorities for exact requirements.
Consult Hood Depot regarding custom services addressing:• Exhaust Fans, Supply Fans and rooftop units• Fire protection systems• Heat Recovery Units• Reduced Throat (low air volume) Ventilators• Utility Distribution Systems (UDS)• Air Purification Systems• Listed Control Panels• ASTM 2519 High Efficiency Filters
Model SW(FP-DI)Compensated Exhaust Canopy with
ITEM NO.__________
PRODUCT SPECIFICATIONS
APPLICATION
DESCRIPTION
OPERATION
MAINTENANCE
AIR SUPPLY GUIDELINES
EXHAUST/SUPPLY FAN UNITS
FIRE PROTECTION
OPTIONAL EQUIPMENT
Furnish Hood Depot’s ventilator model SW(FP-DI) (ventilator without fire damper at the inlet slot) as shown on plans, with a depth of _______ and an overall length of _______ and to meet the following requirements:
GENERAL DESCRIPTION: Ventilator is a conventional filter-type hood with continuous array of baffle U.L. Classified filters along the entire ventilator length. Ventilators up to 12’ to include semi-concealed pitched gutter which slopes to removable grease cup. Ventilators over 12’ include two pitched gutters that slope to removable grease cups located at each extreme end. Ventilator shall include means for hanging.
CONSTRUCTION MATERIALS: The ventila-tor shall be 18 gauge all-stainless steel con-struction. A number 4 finish shall be provided on all exposed surfaces.
LIGHT FIXTURES: Ventilator shall be equipped with U.L. Listed ___ 100 Watt Dome Incandescent or ___ Recessed 150 Watt In-candescent or ___ Recessed Fluorescent fixtures. Light fixtures shall be prewired to a single point of connection at the factory.
APPROVALS: Ventilator to be U.L. Listed, list-ed by NSF, and in accordance with all recom-mendations of NFPA 96. The ventilator must meet all applicable codes.
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
*For full model number add canopy depth and height in inches as suffix (Example: Model SW(FP-DI)-12024 for hood size 120” deep x 24” high)
710 Powerline Road Suite HDeerfield Beach, FL 33442
(954) 570-9860 (800) 322-8730 FAX (954) 570-9865www.hooddepot.net
Front Plenum
• Demand Ventilation• HEPA Intake Units• Top Enclosure Skirts• S/S Filters• Wall Panels• 3” Left or Right Standoffs• Fluorescent Lights
Page 26
Hood lengths available from 4’0” to 16’0” in 6” increments. For lengths 6’6” to 12’0” the maximum offset from centerline and/or make-up air openings to end of hood shall not exceed 6”0”. Lengths from 12’0” to 16’0” shall incorporate two exhaust ducts, each not to exceed 6’0” on center. Filters and lights are added in proportion to length.
Sizes Available
Lengths Available
Model SW(FP-DI)Island Style Compensated Exhaust Canopy
with Front Plenum
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
Model SW(FP-DI)
Light & Medium duty: Cooking surfaces to 400˚= 250 cfm /lf of exhaust air and 200 cfm /lf of supply air per side. Heavy duty: Cooking surfaces to 850˚= 280 cfm / lf of exhaust air and 224 cfm /lf of supply air per side. CFM criteria can vary and a higher cfm/lf is sometimes factory advised; contact us for airflow recommendation for your specific appliances.
Airflow Data
EQUIPMENT TYPE:MEDIUM LOAD..........Kettles (under 60 Gals.), hot top ranges, gas fryers, griddlesHEAVY LOAD.............Charbroilers, high grease equipment
Engineering Data
ElectricalAn optional Hood Depot Control Panel can be provided for each exhaust fan. A contactor or motor starter will be provided for each fan. See section “Control Panels” in our catalog or visit our web site for more information.
Static PressureStatic pressure drops across ventilator: Model SW(FP-DI).......................0.625 W.G. at the duct collar
Canopy Hanging WeightsHood Depth 80” 96” 106” 120” 132” (Others available)LBS per lin. ft. 100 110 130 150 170
Perspective View (N.T.S.)
Canopies available in widths of 80”, 96”, 108”, 120 and 132”. Height can be 24” or 30” depending on ceiling height. Custom widths and heights available; contact factory.
End View Elevation / Cutaway
Note: Fire cabinet weight needs to be added to canopy hanging weight below
Page 27
Ceiling mounted canopy style ventilator for use over medium duty equipment suitable for interior ceiling heights less than 8’6” by recessing into false ceiling.
These SIMA(FP) Series models are low velocity ceiling-mounted canopy ventilators which are U.L. Listed under the category of “Exhaust Hood Without Exhaust Damper.” Units are available in custom depths depending on particular cooking battery layout. All models include a full array of U.L. classified grease removing filters and a grease collecting gutter sloped to a removeable grease cup at either end. Supply plenum to be designed for air to be introduced with a velocity of approximately 150 fpm. Supply plenum depth varies depending on exhaust cfm.
When properly operated and maintained, the liquefied grease is drained off into a con-tainer for periodic removal and cleaning.
At periodic intervals (such as the end of each cooking day) the filters are to be re-moved and cleaned. They may be washed in a dishwasher, hand washed or soaked and rinsed.
Appropriately conditioned supply air must be mechanically delivered to the space to re-place exhausted air. Generally 50-80% is so delivered through the hood with the remain-ing 20-50% flowing naturally from adjoining areas and through the HVAC system.
Exhaust fan(s) and supply fan(s) are available. See fan section of catalog or web site for design information. Fans must be designed for Hood Depot air volumes and static pres-sure drop for the entire system and must be in compliance with local codes.• Exhaust fan(s) should be properly sized and include UL762 listings• Discharge ducts should be vertical and located away from air intakes• Supply fan(s) should be equipped with throw-away or cleanable type filters• Exhaust and supply fans require a magnetic starter switch with 120 Volt holding coil and should be electrically interlocked for simultaneous operation• Exhaust and supply fans should be operated through a listed kitchen hood contral panel
NFPA 96 and most other codes require a fire extinguishing system for protection of both the duct collar and plenum areas of ventilators and for the protection of cooking equip-ment such as fat fryers, griddles, ranges and broilers which may be source of ignition of grease. Check with local fire authorities for exact requirements.
Consult Hood Depot regarding custom services addressing:• Exhaust Fans, Supply Fans and rooftop units• Fire protection systems• Heat Recovery Units• Reduced Throat (low air volume) Ventilators• Utility Distribution Systems (UDS)• Air Purification Systems• Listed Control Panels• ASTM 2519 High Efficiency Filters
Model SIMA(FP) Single Island Compensated Exhaust
ITEM NO.__________
PRODUCT SPECIFICATIONS
APPLICATION
DESCRIPTION
OPERATION
MAINTENANCE
AIR SUPPLY GUIDELINES
EXHAUST/SUPPLY FAN UNITS
FIRE PROTECTION
OPTIONAL EQUIPMENT
Furnish Hood Depot’s ventilator model SIMA(FP) (ventilator without fire damper at the inlet slot) as shown on plans, with a depth of _______ and an overall length of _______ and to meet the following requirements:
GENERAL DESCRIPTION: Ventilator is a conventional filter-type hood with continuous array of baffle U.L. Classified filters along the entire ventilator length. Ventilators up to 12’ to include semi-concealed pitched gutter which slopes to removable grease cup. Ventilators over 12’ include two pitched gutters that slope to removable grease cups located at each extreme end. Ventilator shall include means for hanging.
CONSTRUCTION MATERIALS: The ventila-tor shall be 18 gauge all-stainless steel con-struction. A number 4 finish shall be provided on all exposed surfaces.
LIGHT FIXTURES: Ventilator shall be equipped with U.L. Listed ___ 100 Watt Dome Incandescent or ___ Recessed 150 Watt In-candescent or ___ Recessed Fluorescent fixtures. Light fixtures shall be prewired to a single point of connection at the factory.
APPROVALS: Ventilator to be U.L. Listed, list-ed by NSF, and in accordance with all recom-mendations of NFPA 96. The ventilator must meet all applicable codes.
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
*For full model number add canopy depth and height in inches as suffix (Example: Model SW(FP-DI)-12024 for hood size 120” deep x 24” high)
710 Powerline Road Suite HDeerfield Beach, FL 33442
(954) 570-9860 (800) 322-8730 FAX (954) 570-9865www.hooddepot.net
Canopy with Front Plenum
• Demand Ventilation• HEPA Intake Units• Top Enclosure Skirts• S/S Filters• Wall Panels• 3” Left or Right Standoffs• Fluorescent Lights
Page 22
Single Island Compensated Exhaust
Hood lengths available from 4’0” to 16’0” in 6” increments. For lengths 6’6” to 12’0” the maximum offset from centerline and/or make-up air openings to end of hood shall not exceed 6”0”. Lengths from 12’0” to 16’0” shall incorporate two exhaust ducts, each not to exceed 6’0” on center. Filters and lights are added in proportion to length.
Sizes Available
Lengths Available
Model SIMA(FP)Single Island Compensated Exhaust Canopy
with Front Plenum
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
Light & Medium duty: Cooking surfaces to 400˚= 250 cfm /lf of exhaust air and 200 cfm /lf of supply air per side. Heavy duty: Cooking surfaces to 850˚= 280 cfm / lf of exhaust air and 224 cfm /lf of supply air per side. CFM criteria can vary and a higher cfm/lf is sometimes factory advised; contact us for airflow recommendation for your specific appliances.
Airflow Data
EQUIPMENT TYPE:MEDIUM LOAD..........Kettles (under 60 Gals.), hot top ranges, gas fryers, griddlesHEAVY LOAD.............Charbroilers, high grease equipment
Engineering Data
ElectricalAn optional Hood Depot Control Panel can be provided for each exhaust fan. A contactor or motor starter will be provided for each fan. See section “Control Panels” in our catalog or visit our web site for more information.
Static PressureStatic pressure drops across ventilator: Model SW(FP-DI).......................0.625 W.G. at the duct collar
Canopy Hanging WeightsHood Depth 80” 96” 106” 120” 132” (Others available)LBS per lin. ft. 100 110 130 150 170
Canopies available in widths of 80”, 96”, 108”, 120 and 132”. Height can be 24” or 30” depending on ceiling height. Custom widths and heights available; contact factory.
Page 23
Perspective View (N.T.S.)
Model SIMA(FP)
Note: Fire cabinet weight needs to be added to canopy hanging weight below
End View Elevation / Cutaway
STANDARD FEATURES
are constructed of 18 gauge, stainless steel with No. 4 finish all exposed surfaces.
All seams and joints have liquid tight continuous external welds, ground and polished to match the finished product.
Full length grease trough with removable containers located outside the air flow.
U.L. listed vapor proof incandescent light fixtures mounted, pre-piped and pre-wired to a junction box.
Full length filter frame with UL approved baffle type filters, tight fitting, yet easily removable.
Stainless steel 3” standoff
Model SIMA Single Island Style Exhaust Canopy
OPTIONS
_____Hood pre-piped for U.L. approved automatic fire suppression system.
____Integrated stainless steel cabinet with concealed fire system cylinder.
____Integrated UL listed control panel.
_____U.L. approved baffle type stainless steel filters.
____Recessed U.L. listed fluorescent light fixtures.
____Exhaust collar fire dampers.
____100% stainless steel construction.
____Stainless steel side fillers insulated or non-insulated.
____Stainless steel top enclosure skirt.
EXHAUST/SUPPLY AIR
Medium Duty - fryers, griddles, ranges, grease producing equipment. 225 CFM/Linear foot Heavy Duty - charbroilers, gas flues, high grease producing equipment. 380 CFM/Linear foot
SIZES AVAILABLE
Width Height Model 48” 24” SIMA-4824 48” 30” SIMA-483056” 24” SIMA-5624
56” 30” SIMA-5630 62” 24” SIMA-6224 62” 30” SIMA-6230 68” 24” SIMA-6824 68” 30” SIMA-6830 74” 24” SIMA-7424 74” 30” SIMA-7430
710 S. Powerline Road Suite H - Deerfield Beach, FL 33442—(954) 570-9860—(800) 322-8730-FAX (954) 570-9865 WWW. HOODDEPOT.NET
Ceiling mounted canopy style ventilator for use over medium duty equipment suitable for interior ceiling heights less than 8’6” by recessing into false ceiling.
These SIMA(PF) Series models are low velocity ceiling-mounted canopy ventilators which are U.L. Listed under the category of “Exhaust Hood Without Exhaust Damper.” Units are available in custom depths depending on particular cooking battery layout. All models include a full array of U.L. classified grease removing filters and a grease col-lecting gutter sloped to a removeable grease cup at either end. Supply air introduced through perforated diffusers on the face and rear of the hood.
When properly operated and maintained, the liquefied grease is drained off into a con-tainer for periodic removal and cleaning.
At periodic intervals (such as the end of each cooking day) the filters are to be re-moved and cleaned. They may be washed in a dishwasher, hand washed or soaked and rinsed.
Appropriately conditioned supply air must be mechanically delivered to the space to re-place exhausted air. Generally 70% is so delivered through the hood with the remaining 30-50% flowing naturally from adjoining areas and through the HVAC system.
Exhaust fan(s) and supply fan(s) are available. See fan section of catalog or web site for design information. Fans must be designed for Hood Depot air volumes and static pres-sure drop for the entire system and must be in compliance with local codes.• Exhaust fan(s) should be properly sized and include UL762 listings• Discharge ducts should be vertical and located away from air intakes• Supply fan(s) should be equipped with throw-away or cleanable type filters• Exhaust and supply fans require a magnetic starter switch with 120 Volt holding coil and should be electrically interlocked for simultaneous operation• Exhaust and supply fans should be operated through a listed kitchen hood control panel
NFPA 96 and most other codes require a fire extinguishing system for protection of both the duct collar and plenum areas of ventilators and for the protection of cooking equip-ment such as fat fryers, griddles, ranges and broilers which may be source of ignition of grease. Check with local fire authorities for exact requirements.
Consult Hood Depot regarding custom services addressing:• Exhaust Fans, Supply Fans and rooftop units• Fire protection systems• Heat Recovery Units• Reduced Throat (low air volume) Ventilators• Utility Distribution Systems (UDS)• Air Purification Systems• Listed Control Panels• ASTM 2519 High Efficiency Filters
Model SIMA(PF)Single Island Compensated Exhaust Canopy
ITEM NO.__________
PRODUCT SPECIFICATIONS
APPLICATION
DESCRIPTION
OPERATION
MAINTENANCE
AIR SUPPLY GUIDELINES
EXHAUST/SUPPLY FAN UNITS
FIRE PROTECTION
OPTIONAL EQUIPMENT
Furnish Hood Depot’s ventilator model SIMA(PF) (ventilator without fire damper at the inlet slot) as shown on plans, with a depth of _______ and an overall length of _______ and to meet the following requirements:
GENERAL DESCRIPTION: Ventilator is a conventional filter-type hood with continuous array of baffle U.L. Classified filters along the entire ventilator length. Ventilators up to 12’ to include semi-concealed pitched gutter which slopes to removable grease cup. Ventilators over 12’ include two pitched gutters that slope to removable grease cups located at each extreme end. Ventilator shall include means for hanging.
CONSTRUCTION MATERIALS: The ventila-tor shall be 18 gauge all-stainless steel con-struction. A number 4 finish shall be provided on all exposed surfaces.
LIGHT FIXTURES: Ventilator shall be equipped with U.L. Listed ___ 100 Watt Dome Incandescent or ___ Recessed 150 Watt In-candescent or ___ Recessed Fluorescent fixtures. Light fixtures shall be prewired to a single point of connection at the factory.
APPROVALS: Ventilator to be U.L. Listed, list-ed by NSF, and in accordance with all recom-mendations of NFPA 96. The ventilator must meet all applicable codes.
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
*For full model number add canopy depth and height in inches as suffix (Example: Model SIMA(FRP)-6024 for hood size 60” deep x 24” high)
710 Powerline Road Suite HDeerfield Beach, FL 33442
(954) 570-9860 (800) 322-8730 FAX (954) 570-9865www.hooddepot.net
with Perforated Face
• Demand Ventilation• HEPA Intake Units• Top Enclosure Skirts• S/S Filters• Wall Panels• 3” Left or Right Standoffs• Fluorescent Lights
Page 26
Hood lengths available from 4’0” to 16’0” in 6” increments. For lengths 6’6” to 12’0” the maximum offset from centerline and/or make-up air openings to end of hood shall not exceed 6”0”. Lengths from 12’0” to 16’0” shall incorporate two exhaust ducts, each not to exceed 6’0” on center. Filters and lights are added in proportion to length.
Sizes Available
Lengths Available
Model SIMA(PF)Single Island Compensated Exhaust Canopy
with Perforated Face
710 S. Powerline Road, Suite H • Deerfield Beach, FL 33442 • (954) 570-9860 • (800) 322-8730 • Fax (954) 570-9865www.hooddepot.net
Model SIMA(PF)
Light & Medium duty: Cooking surfaces to 400˚= 250 cfm / lf. CFM criteria can vary and a higher cfm/lf is sometimes factory advised; contact us for airflow recommendation for your specific appliances.
Airflow Data
EQUIPMENT TYPE:MEDIUM LOAD......Kettles (under 60 Gals.), hot top ranges, gas fryers, griddles, braising pansHEAVY LOAD.............Charbroilers, high grease equipment
Engineering Data
ElectricalAn optional Hood Depot Control Panel can be provided for each exhaust fan. A contactor or motor starter will be provided for each fan. See section “Control Panels” in our catalog or visit our web site for more information.
Static PressureStatic pressure drops across ventilator: Model SIMA(FRP).......................0.625 W.G. at the duct collar
Canopy Hanging WeightsHood Depth 54” 60” 66” 72” (Other depths avail.)Wgt. per lin. ft. (LBS) 100 115 130 155
Perspective View (N.T.S.)
Canopies available in widths of 54”, 60”, 66” and 72”. Height can be 24” or 30” depending on ceiling height. Custom widths and heights available; contact factory.
End View Elevation / Cutaway
Note: Fire cabinet weight needs to be added to canopy hanging weight below
Page 27
_____ x _____ SupplyCollar 3” Tall