FERROLI LIMITEDFerroli began producing heating appliances and equipment in Italy

during the 1950s. Today, the company is still family-owned but now

operates ten ultra-modern factories in Europe, employing over 2,500

people and producing a wide range of wall hung, cast iron and welded

steel boilers, making Ferroli one of the largest and most successful

heating appliance manufacturers in the world.

FERROLI COMMERCIAL AND INDUSTRIAL BOILERSThe commercial and industrial boiler range covers wall hung and floor

standing steel and cast iron designs, condensing, atmospheric, pressure

jet units, gas and oil models. Outputs range from 50kW to 14,000kW.

Other products include heat pumps, cylinders, solar heating and

plate heat exchangers. Ferroli’s UK warehouse, backed by its huge

manufacturing facility in Italy, offers delivery ex-stock for most smaller

boiler models and for all frequently used parts. It also assembles and

commissions sectional boilers in the UK to suit particular requirements.

Commercial Boilers

Pressure Jet Boilers

Atmospheric Boilers

Condensing Boilers

Index

Wall Mounted Econcept 51A Page 4

Energy Top Page 6

Floor Standing Econcept 101 Page 8

Energy Top Page 10

Pegasus N Page 12

Atlas A Page 14

Atlas D Page 16

GN2 Range Page 18

GN4 Range Page 20

Prextherm RSW Quadra Page 22

Prextherm RSW Tonda Page 24

Prextherm RSH Quadra Page 26

Prextherm RSH Tonda Page 28

Industrial Heating Vapoprex LVP Page 30

Vapoprex HVP Page 30

Vapoprex 3GF Page 30

Vapoprex 3GN Page 30

Prextherm RSW/RSH Page 31

Prextherm T3G Page 31

Prextherm T3G ASL Page 31

Prextherm ASH/ASL Page 31

Prextherm 3GN AS Page 31

Prextherm 3GF Page 31

Cylinders Aquacyl Twin Coil Page 32

Heat Pumps HXA Page 34

HXP Page 36

Solar Aquasol XS Page 38

Aquacyl Page 40

Ecotop Page 42

Page 3: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

PRODUCTIONThe division, ISO 9001 certified by TÜV SUD, operates in production facilities

covering twenty thousand square metres, including the factory, technical and

design offices and management-sales departments. Ferroli Industrial Heating

adopts a “project” approach: a team of professionals that can satisfy all

customer needs, the best technology applied in the production department

and the use of materials and processes compliant with EN standards mean

that all products are CE marked and approved in various foreign countries.

The manufacturing flexibility of the Ferroli facilities allows the company to

respond to a vast variety of market demands, from simple heating systems to

sophisticated installations for district heating and serving production plants.

Specialist engineers and technicians conduct level two non-destructive testing

(ultrasound, X rays, liquid penetrants) and various welding procedures qualified

by the Italian Welding Institute, according to the standard EN ISO 3834,

involving all the welding featured in our projects, including submerged

arc and TIG welding, welding with basic electrodes and flux-cored welding.

The investments made have allowed a high level of automation to be

reached in the cutting and welding process.

ENERGY SAVINGS, QUALITY AND EFFICIENCYThe current national and international energy market situation requires

constant attention in order to achieve and maintain high efficiency in the use

of thermal energy. Our generators are designed with large heat exchange

surfaces and are fitted with heat recovery units and economisers. These

features considerably increase efficiency and at the same time significantly

reduce both heat loss and running costs. The Ferroli systems also have a low

environmental impact, complying with even the strictest standards in terms

of atmospheric emissions and efficiency parameters.

TECHNOLOGY AND RESEARCHTechnology, research and special care paid to quality are the elements that

define the entire manufacturing procedure of the Industrial Heating Division.

Ferroli Industrial Heating implements an advanced design system, with a

3D drawing program, selects very high quality raw materials and accessories,

and pays meticulous care to every phase in construction, using specialist

personnel with proven experience and the most modern cutting and welding

equipment. Intelligent and effective management of the entire heating plant

is one of the crucial aspects of all modern companies that want to rationally

exploit the heat generated by their boilers.

SERVICEFerroli Industrial Heating guarantees its customers a high level of service.

The quality of our service is a decisive factor in every sale and every stage in

after-sales support. The company implements ongoing training to ensure the

maximum professionalism of our service centres, our technicians and our

installers. The company can provide service on systems and products

in all situations. This ability to serve the customer in relation to any type of

need that may arise has made Ferroli Industrial and Commercial Heating the

benchmark in terms of Customer Satisfaction.

3

Page 4: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

Modulating high efficiency premix condensing boiler for heating installations

Modular installation without the need of additional controllers

Microprocessor controls

Independent external switching of controls to maximise efficiency

Hot surface ignition with independent flame detection probe

Low water pressure protection switch

Independent internal 6 bar safety valve

Can be used on pressurised systems or open vented systems where min. 1 bar is available

Modular boiler control –The Econcept 51A is ready for modular application. The heat output

of the various modules can be optimised according to the heating load of the system

Modular, premix, condensingheat generators, with veryhigh efficiency and very lowpolluting emission, operatingon natural gas or LPG. These generators have beendesigned to be installed inmodular configurations, (upto five) to extend the benefitsof high-efficiency heating tolarger applications.

4

2 year*

parts & labourGuarantee

Econcept 51A – Wall mountedWall mounted modulating condensing boiler for heating

with premix burner with very low emissions

Page 5: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

5

PUMP ACCESSORY KIT (Code 042034X0)For the advanced management of an external hot water cylinder the boiler can be fitted with a special kit which allows the pump for the hotwater cylinder and the return connection to behoused directly in the boiler. The electronic board manages priority of the hot water cylinder,switched by the cylinder’s control stat. When thecylinder is satisfied the boiler automaticallyreturns to heating mode.

TREVERSE FLAME CERAMIC BURNERSThe ECONCEPT 51A modules feature premixceramic burners with reverse micro-flame, eachmade up of six plates fastened via a specialgasket to a metal frame capable of absorbingthermal expansion. These burners have very lowpolluting emissions, both NOx and CO2.

HEAT EXCHANGERSThe heat exchangers design, build and materials ensure high efficiency, constantperformances reliability.

CASCADING OPERATIONThe ECONCEPT 51A series modules have beendeveloped for connection in series to make up asingle heat generator that, in steps of 50kW, canhave a total output up to 250kW. Each withelectronic programming to ensure the optimumoperation from 11kW to 250kW.

Control boardEach ECONCEPT 51A is fitted with a user friendlymulti-function display panel, which controls allbasic operations. It will control up to fivecombustion units and handles the central heatingpump plus a second pump or diverting selectorvalve for the hot water storage cylinder.

Technical specificationsEconcept 51A

Heat input in central heating operation max. kW 49.8

min. kW 11.2

Heat output in central heating max. kW 48.8

operation (80-60°C) min. kW 11.0

Heat output in central heating max. kW 53.0

operation (50-30°C) min. kW 12.0

Operating pressure max. bar 6.0

min. bar 0.8

Height mm 720

Width mm 630

Depth mm 380

All connections Ø 3/4"

Water circuit content l 10

Max outlet temperature °C 95.0

Index of protection IP X5D

Power supply voltage V/Hz 230/50

Power input W 190

Empty weight kg 124.0

Type of appliance B23

Efficiency

Efficiency (80-60°C) Pmax % 98.0

Pmin % 98.5

Efficiency (50-30°C) Pmax % 106.4

Pmin % 107.5

Efficiency 30% (30°C) % 109.0

NOx class 5

Page 6: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

Modulating high efficiency premix condensing boiler for heating installations

Modular installation without the need of additional controllers

Microprocessor controls

Independent external switching of controls to maximise efficiency

Hot surface ignition with independent flame detection probe

Low water pressure protection switch

Independent internal 6 bar safety valve

Can be used on pressurised systems or open vented systems where min. 1 bar is available

Modular boiler control –The Energy Top W is ready for modular application. The heat output

of the various modules can be optimised according to the heating load of the system

Unique spiral corrugated heat exchanger

Suitable for heating only systems,featuring high energy savings and are environmentally-friendly (4 star energy rating). Cascadingconnection of multiple generators can be performed using special fluegas and water circuit accessories.The models are configured foroperation on natural gas but can be converted to LPG using a specialconversion kit.

Energy Top – Wall mounted Wall mounted heat generators featuring a premix burner, condensing

operation, very high efficiency and very low polluting emissions.

6

2 year*

parts & labourGuarantee

Page 7: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

FURNACEThe new total premixed air-gascombustion unit with variable speedfan, pneumatic gas valve and cylindricalmetal fibre burner allows a range ofmodulation that, depending on themodel, can extend from 11 to 100% ofrated output, with efficiency exceeding107%. The very low emissions – NOxand CO2 – as well as minimising theenvironmental impact, also ensures theheat exchanger remains clean overtime, reducing maintenance.

ELECTRONIC CONTROLThe evolved electronics on ENERGYTOP can manage situations in whichmultiple heat generators are used incascade, minimising the configurationand commissioning operations.

CASCADING OPERATIONMultiple generators can be linked.The models are factory configured for operation on natural gas and can be converted to LPG using a special conversion kit.

7

Technical specificationsW80 W125

Output and Efficiency

Heat input, central heating max. kW 75.0 116.0

min. kW 17.0 25.0

Heat output, central heating max. (80 - 60°C) kW 73.5 113.7

min. (80 - 60°C) kW 16.7 24.6

max. (50 - 30°C) kW 79.5 123.0

min. (50 - 30°C) kW 18.3 26.9

Efficiency Pmax (80 - 60°C) % 98.0 98.0

Pmin (80 - 60°C) % 98.5 98.5

Pmax (50 - 30°C) % 106.0 106.0

Pmin (50 - 30°C) % 107.5 107.5

30% (30°C) % 109.0 109.0

Efficiency class Directive 92/42 EEC ★★★★ ★★★★NOx class 5 5

Central heating operating pressure max-min. bar 6-0.8 6-0.8

Central heating temperature max. °C 95 95

Max exchanger Δt °C 40 40

Water content litres 5 7

Electrical specifications

Index of protection IP X5D X5D

Power supply voltage V/Hz 230/50 230/50

Power input (not including the pump) max. W 95 200

Structural characteristics

Weight kg 46 51

Height mm 900 900

Width mm 445 445

Depth mm 430 430

Water circuit

Outlet/return fittings inches 11/2" 11/2"

Gas fitting inches 1" 1"

Combustion data

Losses through the stack with burner ON at Pmax-Pmin % 2.2-1.3 1.8-1.3

Losses through the casing with burner ON at Pmax-Pmin % 0.2-0.2 0.2-0.2

Losses through the stack with burner OFF % 0.03 0.02

Losses through the casing with burner OFF % 0.4 0.4

Flue gas temperature at Pmax-Pmin (80/60) °C 65-60 67-60

(50/30) °C 43-33 45-34

Flue gas flow-rate at Pmax-Pmin kg/h 126.2-30.1 195.2-44.3

Condensate flow-rate at Pmax-Pmin kg/h 8.7-2.0 13.5-3.2

CO2 at Pmax-Pmin (G20) % 9.0-8.5 9.0-8.5

CO2 at Pmax-Pmin (G31) % 10-9.2 10-9.2

CO weighted mg/kWh 35.0 35.0

NOx weighted mg/kWh 29.0 29.0

Page 8: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

Modulating high efficiency premix condensing boiler for heating installations

Vertical modular structure with built-in manifold pipework

Dual heat exchangers with independent microprocessor controls

Independent external switching of controls to maximise efficiency

Hot surface ignition with independent flame detection probe

Low water pressure protection switch

Independent internal 6 bar safety valves

Boiler manifold can be bolted directly together; minimises use of space and installation time

Can be used on pressurised systems or open vented systems where min. 1 bar is available

Modular boiler control –The Econcept 101 is ready for modular application. The heat output

of the various modules can be optimised according to the heating load of the system

Modular, premix, condensingheat generators, with veryhigh efficiency and very lowpolluting emission, operatingon natural gas or LPG. These generators have beendesigned to be installed inmodular configurations, (upto five) to extend the benefitsof high-efficiency heating tolarger applications.

Econcept 101– Floor standingFloor standing, modulating condensing boiler for heating with dual

heat exchanger and double premix burner with very low emissions

8

2 year*

parts & labourGuarantee

Page 9: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

9

Technical specifications

Econcept 101

Output max/min.

Heat input kW 99.6/11.2

Useful heat output 80°C - 60°C kW 97.6/11.0

Useful heat output 50°C - 30°C kW 106.0/12.0

Efficiency (net)

80°C - 60°C Full load % 98.0

50°C - 30°C % 106.4

Part load (30%) % 109.0

NOx emissions

Class 5

Gas supply (natural gas G20)

Supply pressure mbar 20.0

Flow rate max/min m3/h 10.54/1.19

Gas supply (LPG G31)

Supply pressure mbar 37.0

Flow rate max/min kg/h 7.8/0.88

Central heating

Maximum operating pressure bar 6

Hot water content litres 12.8

Dimensions, weights, fittings

Height mm 1650

Width mm 704

Depth mm 410

Weight (empty) kg 150

Gas fitting DN50

Central heating fittings DN80

Power supply

Max power input W 380

Power supply voltage/frequency V/Hz 230V/50Hz

Index of protection IP X5D

TREVERSE FLAME CERAMIC BURNERSThe ECONCEPT 101 modules featurepremix ceramic burners with reverse micro-flame, each made up of six platesfastened via a special gasket to a metalframe capable of absorbing thermalexpansion. These burners have very lowpolluting emissions, both NOx and CO2.

HEAT EXCHANGERSThe heat exchangers design, build andmaterials ensure high efficiency, constantperformances reliability.

CASCADING OPERATIONThe ECONCEPT101 series modules havebeen developed for connection in series tomake up a single heat generator that, insteps of 50kW, can have a total output ofaround 500kW. Each with electronicprogramming to ensure the optimumoperation from 11kW to 500kW.

Page 10: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Energy Top – Floor standingFloor standing cabinet heat generators featuring a premix burner,

condensing operation, very high efficiency and very low polluting emissions

10

2 year*

parts & labourGuarantee

Features and Benefits

Low emissions – NOX and CO2

Individual and multiple configurations

4 star energy rating

Painted steel insulated cabinet, with reversible door (left-right) for B80 and B125 units only

Natural gas and can be converted to LPG using a special conversion kit

The range features four sizes, two with single burner and two with double burners

Cascade configurations suitable for different types of flue options

Boiler manifold can be bolted directly together; minimises use of space and installation time

Can be used on pressurised or open vented systems where min. 1 bar is available

Suitable for heating systems only,featuring high energy savings and are environmentally-friendly (4 star energy rating). Cascading connection of multiplegenerators can be performedusing special flue gas and water circuit accessories.The models are configured for operation on natural gas but can be converted to LPGusing a special conversion kit.

The water circuit in cabinet modules, compared to the wall-hung versions, is already included asstandard with all the components required for complete and correct installation in the boiler room.Each unit is connected to the central heating outlet and return water manifolds via 3-way on-offvalves with atmospheric discharge and fixed speed pump.

Page 11: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

11

Technical specificationsB80 B125 B160 B250

Output and Efficiency

Heat input, central heating max. kW 75.0 116.0 150.0 232.0

min. kW 17.0 25.0 17.0 25.0

Heat output, central heating max. (80 - 60°C) kW 73.5 113.7 147.0 227.4

min. (80 - 60°C) kW 16.7 24.6 16.7 24.6

max. (50 - 30°C) kW 79.5 123.0 159.0 246.0

min. (50 - 30°C) kW 18.3 26.9 18.3 26.9

Efficiency Pmax (80 - 60°C) % 98.0 98.0 98.0 98.0

Pmin (80 - 60°C) % 98.5 98.5 98.5 98.5

Pmax (50 - 30°C) % 106.0 106.0 106.0 106.0

Pmin (50 - 30°C) % 107.5 107.5 107.5 107.5

30% (30°C) % 109.0 109.0 109.0 109.0

Efficiency class Directive 92/42 EEC ★★★★ ★★★★ ★★★★ ★★★★NOx class 5 5 5 5

Central heating operating pressure max-min. bar 6-0.8 6-0.8 6-0.8 6-0.8

Central heating temperature max. °C 95 95 95 95

Max exchanger Δt °C 40 40 40 40

Water content litres 13 15 26 30

Electrical specifications

Index of protection IP X5D X5D X5D X5D

Power supply voltage V/Hz 230/50 230/50 230/50 230/50

Max power input (not including the pump) W 285 390 570 780

Structural characteristics

Weight kg 110 115 190 210

Height mm 1700 1700 1700 1700

Width mm 500 500 1000 1000

Depth mm 450 450 450 450

Water circuit

Outlet/return fittings inches DN100 DN100 DN100 DN100

Gas fitting inches DN65 DN65 DN65 DN65

Combustion data, single furnace

Type of appliance B23 B23 B23 B23

Losses through the stack with burner ON at Pmax-Pmin % 2.2-1.3 1.8-1.3 2.2-1.3 1.8-1.3

Losses through the casing with burner ON at Pmax-Pmin % 0.2-0.2 0.2-0.2 0.2-0.2 0.2-0.2

Losses through the stack with burner OFF % 0.03 0.02 0.03 0.02

Losses through the casing with burner OFF % 0.4 0.4 0.4 0.4

Flue gas temperature at Pmax-Pmin (80/60) °C 65-60 67-60 65-60 67-60

Flue gas temperature at Pmax-Pmin (50/30) °C 43-33 45-34 43-33 45-34

Flue gas flow-rate at Pmax-Pmin kg/h 126.2-30.1 195.2-44.3 126.2-30.1 195.2-44.3

Condensate flow-rate at Pmax-Pmin kg/h 8.7-2.0 13.5-3.2 8.7-2.0 13.5-3.2

CO2 at Pmax-Pmin (G20) % 9.0-8.5 9.0-8.5 9.0-8.5 9.0-8.5

CO2 at Pmax-Pmin (G31) % 10-9.2 10-9.2 10-9.2 10.-9.2

CO weighted mg/kWh 35.0 35.0 35.0 35.0

NOx weighted mg/kWh 29.0 29.0 29.0 29.0

Page 12: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

A range of outputs from 51 to 289 kW

Stainless steel main burner

Double body gas valve with shut-off devices controlled by the regulating and safety thermostats

Flue gas safety thermostat

Electronic ignition with ionising flame regulation with reset button and intermittent pilot burner

Main switch

Temperature/pressure gauges

Regulating thermostat

Safety thermostat

Automatic air vent valve

Pressure stabiliser and gas pressure gauge

Drain cock

Flue gas test point on flue gas chamber

High efficiency

cast iron floor

standing boiler

with atmospheric

burner for the

production of

hot water for

central heating

installations.

Pegasus NGas-fired cast iron floor boiler with atmospheric burner

12

2 year*

parts & labourGuarantee

Page 13: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

13

Technical specificationsPegasus N F2 51 F2 68 F2 85 F2 102 F3 119 F3 136 F3 153 F3 170 F3 187 F3 221 F3 255 F3 289

Heat output kW 51 68 85 102 119 136 153 170 187 221 255 289

Btu x1000 174 232 290 348 406 464 522 580 638 754 870 986

Rated heat input nett kW 56 74.8 93 112 131 149 168 187 206 243 280 317

Btu x1000 191 255 317 382 447 508 573 638 703 829 955 1082

Design Flow rate at 82ºC/71ºC litre/sec 1.10 1.47 1.84 2.21 2.56 2.90 3.30 3.67 4.03 4.76 5.49 6.23

Minimum flow rate litre/sec 0.44 0.59 0.74 0.88 1.02 1.16 1.32 1.47 1.61 1.90 2.20 2.50

Boiler water content litres 22 25 30 34 38 42 46 50 54 62 70 78

Maximum working pressure bar 4 4 4 4 4 4 4 4 4 4 4 4

Sections 4 5 6 7 8 9 10 11 12 14 16 18

Dimensions A mm 550 640 720 800 930 1020 1100 1190 1270 1440 1610 1780

B mm 103 103 103 103 133 148 148 173 173 173 198 198

C Ø mm 180 180 200 200 220 250 250 300 300 300 350 350

D mm 43 46 44 42 50 53 58 60 58 57 62 66

E mm 35 38 36 34 42 45 43 46 44 45 46 49

F mm 900 900 900 900 1050 1050 1050 1050 1050 1050 1100 1100

Connections a1 11/2" 11/2" 11/2" 11/2" 2" 2" 2" 2" 2" 2" 2" 2"

a2 11/2" 11/2" 11/2" 11/2" 2" 2" 2" 2" 2" 2" 2" 2"

a3 3/4" 3/4" 3/4" 3/4" 1" 1" 11/2" 11/2" 11/2" 11/2" 11/2" 11/2"

Principal gas nozzles no. 3 4 5 6 7 8 9 10 11 13 15 17

Elec. power supply V/Hz 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50

Total power input Watt 20 20 20 20 32 32 60 60 60 60 60 60

Weight (with packaging) kg 250 300 350 400 470 530 575 625 665 760 875 945

KEY

a1 central heating return inlet

a2 central heating flow outlet

a3 gas input

PEGASUS F2 N PEGASUS F3 N

Page 14: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

New compact design

High efficiency cast iron boiler body

Silent operation thanks to low flues turbulence

Widely copes with requirements for 2 stars efficiency according to directive 92/42 EEC

New analogue control panel with smart fume cover

Control board includes thermometer and pressure gauge, ignition switch, safety thermostat with

manual reset and temperature setting knob

Optional range of one and two stage* burners to be easily fitted, both for gas or liquid fuel

* Two stage only available on Atlas A 95

3 pass-flue floor standing

boiler, only heating,

for oil or gas jet burner.

Atlas AFloor Standing Boiler

14

2 year*

parts & labourGuarantee

Equipped with a user-friendly,

control panel.

Page 15: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

15

Technical specifications

Atlas A 32 47 62 78 95

Max thermal output kW 32 47 62 78 95

Max thermal capacity kW 34.9 51.6 67.7 85.6 103

Water content litres 18 23 28 33 38

Efficiency Pmax (80°– 60°C) % 91.7 91.1 91.5 91.1 92

Max. heating operating pressure bar 6 6 6 6 6

Dimensions D mm 400 500 600 732 832

B Ø mm 115 115 115 115 115

F Ø mm 120-130 120-130 120-130 120-130 120-130

Empty weight kg 127 166 205 244 283

Number of sections 3 4 5 6 7

IP protection rate IP X0D X0D X0D X0D X0D

500

B

F

850

105 105145 145

1

2

3

KEY

1 system delivery Ø 11/2"

2 system return Ø 11/2"

3 heating system drain cock 1/2"

Page 16: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

High performing three-pass cast iron section

3 star efficiency according to EN 92/42 CEE

Digital control panel suitable for connection to opentherm remote control and outdoor probe

Evolved digital interface for settings and monitoring of CH-DHW temperatures and advanced features

(economy, outside temperature compensation, troubleshooting)

Self-diagnostic micro processor

Central Heating frost protection system

Easy-to-maintain thanks to hinged combustion chamber door

New compact design

Built-in handling of a DHW tank

Floor standing cast iron boiler, oil or gas fired, for central heating.A smart compact design withadvanced technology. Highefficency, low fuel consumptionand low emissions.

Atlas DThree-pass cast iron floor standing boiler

16

2 year*

parts & labourGuarantee

Page 17: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

17

500 D

850

105 105145 145

1

2

3B

F

KEY

1 system delivery Ø 11/2"

2 system return Ø 11/2"

3 heating system drain cock 1/2"

Technical specifications

Atlas D 30 42 55 70 87

Heat output kW 30 42 55 70 87

Heat input kW 32.2 45 58.8 74.7 93

Heating water content litres 18 23 28 33 38

Efficiency Pmax (80°– 60°C) % 93 93,3 93,5 93,7 94

Working pressure in heating bar 6 6 6 6 6

Dimensions D mm 400 500 600 732 832

B Ø mm 115 115 115 115 115

F Ø mm 120-130 120-130 120-130 120-130 120-130

Empty weight kg 127 166 205 244 283

Number of Sections 3 4 5 6 7

Index of protection IP X0D X0D X0D X0D X0D

Page 18: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

Ferroli boilers are manufactured from high quality cast iron and are designed for a reliable

long life – with a 10-year manufacturer’s material guarantee on the cast iron work

All GN models are suitable for natural gas, LPG or oil-fired pressure jet burners, with a dual fuel option

The GN range is a highly efficient boiler with on/off, high/low or modulating burner operation

We can also supply pre-mix burners which are fully modulating, low NOX and quiet

High efficiency, reduce fuel consumption

Boiler body is insulated with high density mineral fibre to minimise heat loss from the heat exchanger

GN2 models have a double-pass heat exchanger

Designed for use with fully pumped indirect systems operating at working pressures up to 6 bar at

90ºC flow temperature

The pre-wired control panel is housed in a stylish casing and incorporates: on/off illuminated

switches; high/low thermostatic control with limit thermostat (manual re-set); and a

temperature and pressure gauge

Front access for ease of maintenance and minimum side clearance required

Suitable for modular installations

High efficiency heatgenerators for theproduction of hot waterfor central heatinginstallations servingmedium to largeresidential or industrialpremises. The GN rangeof boilers is availablefor pressure jet oil,forced air gas or dualfuel with a range ofburners for ON/OFF orhigh/low operation.

GN2Gas, oil or dual fuel, cast iron, free-standing boilers

18

2 year*

parts & labourGuarantee

Page 19: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

19

Technical specifications

Number of sections 05 06 07 08 09 10 11 12 13 14

Delivered heat output max. kW 90 108 126 144 162 180 198 216 234 252

min. kW 73 87 101 115 129 143 157 171 185 199

Heat input max. kW 98.8 117.4 136.9 156.5 176.0 195.6 215.2 234.7 254.3 273.9

min. kW 80 95 110 125 140 155 170 185 200 215

Water content litres 49 57 65 73 81 89 97 105 113 121

Design flow rate @ Δt 11ºC litres/sec 1.95 2.35 2.74 3.13 3.52 3.91 4.3 4.7 5.01 5.47

Water pressure loss @ Δt 11ºC mb 2.8 3.4 4.8 6.5 8.5 11 13 16 19 23

Design flow rate @ Δt 20ºC litres/sec 1.07 1.29 1.5 1.72 1.93 2.15 2.36 2.58 2.79 3.00

Water pressure loss @ Δt 20ºC mb – – 0.5 0.8 1.8 2.2 2.6 3.2 4.0 4.5

Water pressure max bar 6 6 6 6 6 6 6 6 6 6

Static head min m 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

Flow rate min litres/sec 0.72 0.86 1.0 1.15 1.29 1.43 1.58 1.72 1.86 2.0

Input gas rate max m3 13 15 17 20 22 24 27 29 32 33

Working pressure boiler gas mb 20 20 20 20 20 20 20 20 20 20

Max gas inlet gas pressure mb 25 25 25 25 25 25 25 25 25 25

Draught required @ boiler flue outlet mb 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02

Pascal 2 2 2 2 2 2 2 2 2 2

Burner pressure as Burner manufacturers data

Flue gas volume @ NTP m3 140 159 196 218 247 273 305 326 370 402

Flue gas temperature ºC 220 220 220 220 220 220 220 220 220 220

Boiler flue gas resistance mb 0.3 0.31 0.32 0.33 0.34 0.36 0.37 0.38 0.39 0.40

Electric supply 230v 50Hz Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

Combustion chamber Δp mbar 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4

Combustion chamber volume litres 63 77 91 104 118 132 146 160 174 187

Dimensions Height mm 1196 1196 1196 1196 1196 1196 1196 1196 1196 1196

Width mm 600 600 600 600 600 600 600 600 600 600

Depth mm 647 757 867 977 1087 1197 1307 1417 1527 1637

Blast tube diameter mm 130 130 130 154 154 154 154 154 154 154

Flue diameter mm 180 180 200 200 200 200 200 200 200 200

Fittings Water flow/return ND80 3 3 3 3 3 3 3 3 3 3

Drain cock inches 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"

Gas inlet connection as Burner manufacturers data

Weight kg 310 361 412 463 514 565 616 670 725 780

Clearance Front (min) mm 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Rear (min) mm 800 800 800 800 800 800 800 800 800 800

Side (min) mm 200 200 200 200 200 200 200 200 200 200

Page 20: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

20

2 year*

parts & labourGuarantee

Features and Benefits

Ferroli boilers are manufactured from high quality cast iron and are designed for a reliable long

life – with a 10-year manufacturer’s material guarantee on the cast iron work

All GN models are suitable for natural gas, LPG or oil-fired pressure jet burners, with a dual fuel option

The GN range is a highly efficient boiler with on/off, high/low or modulating burner operation

We can also supply pre-mix burners which are fully modulating, low NOX and quiet

High efficiency, reduce fuel consumption

Boiler body is insulated with high density mineral fibre to minimise heat loss from the heat exchanger

GN4 has a triple-pass heat exchanger for maximum heat transfer and ultra-high operating efficiency

Designed for use with fully pumped indirect systems operating at working pressures up to 6 bar at

90ºC flow temperature

The pre-wired control panel is housed in a stylish casing and incorporates: on/off illuminated

switches; high/low thermostatic control with limit thermostat (manual re-set); and a

temperature and pressure gauge

Front access for ease of maintenance and minimum side clearance required

Suitable for modular installations

High efficiency heatgenerators for theproduction of hot waterfor central heatinginstallations servingmedium to largeresidential or industrialpremises. The GN rangeof boilers is availablefor pressure jet oil,forced air gas or dualfuel with a range ofburners for ON/OFF orhigh/low operation.

GN4Gas, oil or dual fuel, cast iron free-standing boilers

Page 21: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

21

Technical specifications

Number of sections 07 08 09 10 11 12 13 14

Delivered heat output max. kW 200 250 300 360 420 480 560 650

min. kW 120 150 180 215 250 290 330 390

Heat input max. kW 217 270 324 388 452 516 600 695

min. kW 128 160 192 229 266 309 352 416

Water content litres 143 163 183 203 223 243 263 283

Design flow rate @ Δt 11ºC litres/sec 4.32 5.39 6.46 7.75 9.08 10.4 12.1 14.1

Water pressure loss @ Δt 11ºC mb 66 99 139 178 215 254 292 331

Design flow rate @ Δt 20ºC litres/sec 2.58 2.7 3.3 3.87 4.53 5.17 6.03 7.0

Water pressure loss @ Δt 20ºC mb 20 30 42 54 65 77 88 100

Water pressure max bar 6 6 6 6 6 6 6 6

Static head min m 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1

Flow rate min litres/sec 1.73 2.16 2.6 3.6 3.12 1.16 4.85 5.63

Input gas rate max m3 20.28 25.23 30.28 36.26 42.24 48.22 56.07 64.95

Working pressure boiler gas mb 20 20 20 20 20 20 20 20

Max gas inlet gas pressure mb 25 25 25 25 25 25 25 25

Burner pressure as Burner manufacturers data

Flue gas volume @ NTP m3 318 393 468 558 646 734 848 977

Flue gas temperature ºC 200 200 200 200 200 200 200 200

Draught required @ boiler flue outlet mb 0.02 0.02 0.02 0.02 0.02 0.02 0.02 0.02

Pascal 2 2 2 2 2 2 2 2

Electric supply 230v 50Hz Yes Yes Yes Yes Yes Yes Yes Yes

Combustion chamber Length mm 880 1010 1140 1270 1400 1530 1660 1790

Ø mm 500 500 500 500 500 500 500 500

Combustion chamber volume litres 161.3 185.1 208.9 232.8 256.6 280.4 304.3 328.1

Dimensions Height mm 1193 1193 1193 1193 1193 1193 1193 1193

Width mm 850 850 850 850 850 850 850 850

Depth mm 1040 1170 1300 1430 1560 1690 1820 1950

Flue diameter mm 180 180 250 250 250 250 250 250

Fittings Water flow/return ND80 3 3 3 3 3 3 3 3

Drain cock inches 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"

Gas inlet connection as Burner manufacturers data

Weight kg 940 1050 1170 1270 1400 1510 1630 1740

Clearance Front (min) mm 1000 1000 1000 1000 1000 1000 1000 1000

Rear (min) mm 800 800 800 800 800 800 800 800

Side (min) mm 200 200 200 200 200 200 200 200

Page 22: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

The shape design of the heat exchanger ensures an optimum ratio between the combustion volumes and the heat exchange surfaces

The materials used ensure the long life of the boiler

New turbulators improve the heat exchange of the flue gas and at the same time ensures a lowerpressure drop

A baffle plate has been fitted at the central heating system return inlet to improve the circulation ofcold water towards the bottom of the boiler. This solution ensures more uniform distribution of theheat exchange fluid across the boiler’s heat exchange surface, achieving maximum heat exchange with less stress on the walls

The tube bundle has been positioned above the combustion chamber, so that the flue gas is alwaysdischarged into a “hot”environment, preventing condensation forming

The burner is not aligned with the combustion chamber, but rather has been moved downwards. This assists the reversal of the flame, reduces the pressure drop on the flue gas side and as aconsequence extends the operating range of the generator

The combustion chamber is completely cooled (even at the rear), to ensure a greater heat exchangesurface and improve the distribution of the heating load across the walls

The steel body is completely lined with an 80mm thick layer of glass wool, in turn covered by a sturdylayer of tearproof material

The door can be hinged on the right-hand or left-hand side, has a double door stop with a new-concept locking and centring system. The door lining in the “Quadra” is made from ceramic fibre

The PREXTHERM RSWQuadra series heatgenerators arepressurised combustionboilers with flamereversal in thecombustion chamberand three flue gas passes.

18 models available from 92 to 1890kW

22

Prextherm RSW QuadraPressurised steel boilers

Page 23: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

23

Technical specifications

������������������

���������

�����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������

���������������������������������������������������������������������������������������������������������������������������������������������������������������������������

��������������������������������������������������������������������������������������������������������������������������������

������������������������������������������������������������������������������������������������������

�����������������������������������������������������������������������������������������������������������������������������������������������

�����������������������������������������������������������������������������������������������������������������������������������������������

������������������������������������������������������������������������������������������������������������������

���� �� �� �� ��

����

����

�������������������������������

���������������������������

����

����

����

����

����

������������

�������������

�������������������

������������������������������������������������������������������������������������

ktrnhjgbnfybt

�����������������������������������������������������������������

������������������������

����

����

����

��������������������

�������������������������������������������

��

��

�����������������������

���������������������������������������

��

������������������������

�����������������������������

����������������������������

���������������������������������������

����������������������������������������

������������������������������

�������������������������������������������

�������������������������������������������������������������Pfdjlcrjq yjvth�����������������

������������������������������������������������������������������������������������������� Ntgkjghjbpdjlbntkmyjcnm�������������������������

����������������� �������������������������������� ���������������������������� Gjktpyfz Ntgkjdfzvjoyjcnm

����������������������� ��������������������������������������������������� ���������������������������������� Vfrc= hf,jxtt lfdktybt

�������������������������� ����������������������������������������������������� ��������������������������������������������������� Vfrc= hf,jxfz ntvgthfnehf

���

��������������

������������������

���

��������������������������������������������������������������������������������������������������������������������������������������������������������

�������������������������������������������������������������������������������������������������Jghtccjdjxyjt l fdktybt#Lfnf

���������������������������������������������������

Vjltkm

Rjl

J,mtv rjnkjdjq djls

'

W

HT6

T3 - T1 - T2 T2 - T1 - T3

T5

T3 T1 T2

T4

L

T4

T5

KEY

T1 Central heating flow outlet

T2 Central heating return inlet

T3 Expansion vessel attachment

T4 Boiler drain

T5 Flue attachment

T6 Burner attachment fitting

92 107 152 190 240 300 350 399 525 600 720 820 940 1060 1250 1480 1600 1890

Heat output min. kW 60 70 100 137 160 196 228 260 341 390 468 533 611 689 813 962 1040 1229

max. kW 92 107 152 190 240 300 350 399 525 600 720 820 940 1060 1250 1480 1600 1890

Heat input min. kW 64.3 75 107.3 147.4 170.9 209.5 242.5 277.5 364.5 417 502 566 651 731 884 1046 1128 1336

max. kW 99.5 116 165 206 261 326 378 432 567 648 777 881 1011 1140 1359 1608 1736 2054

Water content dm3 120 120 185 185 235 300 360 365 405 465 735 735 850 1250 1250 1500 1500 1630

Energy marking (Directive 92/42 EEC) ��� ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★ ★★Efficiency at Pn max (Tm 70°C) % 92.48 92.00 92.30 91.95 92.25 92.05 92.51 92.30 92.50 92.56 92.71 93.10 92.95 93.05 92.00 92.03 92.15 92.01

Efficiency at Pn min (Tm 70°C) % 93.33 93.20 94.30 92.99 93.60 93.50 95.25 93.70 93.55 93.49 93.30 94.20 93.80 96.20 93.20 93.48 93.55 93.51

Efficiency at 30% Pn max (Tm 50°C) % 93.95 93.65 94.50 93.46 94.24 94.12 95.50 94.19 94.15 94.32 93.60 94.40 94.20 96.75 93.41 93.68 93.80 93.76

Δt smokes-environment � gas 150.9/105.9 161.5/118 161.6/119 167.1/115.7 162.5/109 167/115 159.9/97.9 161.5/113 159.4/115 157.9/108.9 157/120 148.2/100 153.8/105 151.6/96.7 179.6/121 176.3/108 173.6/107 176.7/107

CO2 gas 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

CO2 oil 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13

Specific Thermic load mW/m2h 34.3 36.8 32.3 40.4 41.3 42.2 41.1 44.3 47.7 46.1 42.3 48.2 47.0 39.2 46.2 44.8 48.4 51.0

Volumetric Thermic load mW/m2h 1.10 1.28 1.17 1.47 1.53 1.48 1.45 1.35 1.26 1.20 1.25 1.42 1.44 1.26 1.51 1.34 1.44 1.58

Shell loss* % 1.3 1.3 1.2 1.1 1.0 1.0 1.0 1.0 0.9 0.9 0.8 0.8 0.7 0.7 0.6 0.6 0.6 0.6

Loss at chimney burner on % 6.22 6.7 6.7 6.95 6.75 6.95 6.49 6.7 6.6 6.54 6.49 6.1 6.35 6.25 7.4 7.37 7.25 7.39

Loss at chimney burner off ** % 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Working pressure bar 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

Water side pressure drop Δt 10°C � Δp mbar 8 11 20 12 17 40 48 43 40 51 32 40 51 65 86 110 110 100

Δt 20°C � Δp mbar 2 2 5 3 4 9 13 16 12 16 10 18 16 20 25 32 32 29

Combustion chamber Internal Ø mm 390 390 420 420 420 488 488 538 638 638 686 686 686 776 776 830 830 830

Length mm 700 700 920 920 1170 1135 1385 1395 1385 1660 1670 1670 1854 2104 2250 2500 2500 2500

Volume m3 0.09 0.09 0.14 0.14 0.17 0.22 0.26 0.32 0.45 0.54 0.62 0.62 0.70 0.90 0.90 1.20 1.20 1.30

Surface total m2 2.9 2.9 4.7 4.7 5.8 7.1 8.5 9 11 13 17 17 20 27 27 33 33 37

Flue gas side pressure drop � Δp mbar 0.5 0.7 1.2 1.2 2.3 3.3 3.5 4.4 4.3 4.8 4.5 5.6 5.4 6 6.5 6.5 6.8 7

Flue gas flow-rate gas Kg/h 150 175 249 312 394 492 571 652 856 979 1179 1329 1523 1720 2050 2426 2620 3099

oil Kg/h 159 186 264 331 418 522 606 692 909 1039 1252 1411 1617 1825 2176 2576 2781 3290

Boiler weight (empty) kg 260 260 350 350 440 480 550 590 860 970 1250 1250 1420 1580 2250 2650 2700 2850

Dimensions Height mm 925 925 980 980 980 1100 1100 1100 1250 1250 1400 1400 1400 1580 1580 1730 1730 1730

Width mm 760 760 810 810 810 950 950 950 1060 1060 1260 1260 1450 1450 1530 1530 1530 1530

Length mm 1046 1046 1296 1296 1516 1546 1816 1817 1838 2098 2158 2158 2398 2420 2420 2722 2722 2722

Connections T1 DN 2" 2" 21/2" 21/2" 21/2" 21/2" 21/2" 21/2" 80 80 100 100 100 125 125 150 150 150

T2 DN 2" 2" 21/2" 21/2" 21/2" 21/2" 21/2" 21/2" 80 80 100 100 100 125 125 150 150 150

T3 DN 11/4" 11/4" 11/2" 11/2" 11/2" 11/2" 11/2" 11/2" 2" 2" 21/2" 21/2" 21/2" 3" 3" 100 100 100

T4 DN 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 11/2" 11/2" 11/2"

T5 Ø mm 200 200 220 220 220 220 220 220 250 250 350 350 350 400 400 450 450 450

* Air Blocked, temperature 20ºC** Combustion air closed

Page 24: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

24

Features and Benefits

The shape design of the heat exchanger ensures an optimum ratio between the combustion volumes and the heat exchange surfaces

The materials used ensure the long life of the boiler

New turbulators improve the heat exchange of the flue gas and at the same time ensure a lowerpressure drop

A baffle plate has been fitted at the central heating system return inlet to improve the circulation ofcold water towards the bottom of the boiler. This solution ensures more uniform distribution of theheat exchange fluid across the boiler’s heat exchange surface, achieving maximum heat exchange with less stress on the walls

The tube bundle has been positioned above the combustion chamber, so that the flue gas is alwaysdischarged into a “hot”environment, preventing condensation forming

The burner is not aligned with the combustion chamber, but rather has been moved downwards. This assists the reversal of the flame, reduces the pressure drop on the flue gas side and as aconsequence extends the operating range of the generator

The combustion chamber is completely cooled (even at the rear), to ensure a greater heat exchangesurface and improve the distribution of the heating load across the walls

The steel body is completely lined with an 80mm thick layer of glass wool, in turn covered by a sturdylayer of tearproof material

The door can be hinged on the right-hand or left-hand side, has a double door stop with a new-concept locking and centring system. The door lining in the “Tonda” has a double cement lining plusan extra layer of insulating material

Prextherm RSW TondaPressurised steel boilers

The PREXTHERM RSWTonda series heatgeneratorsare pressurisedcombustion boilers with flame reversalin the combustionchamber and three flue gas passes.

7 models availablefrom 2360 to 6000kW

Page 25: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

25

Technical specifications

������������������

���������

�����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������

���������������������������������������������������������������������������������������������������������������������������������������������������������������������������

��������������������������������������������������������������������������������������������������������������������������������

������������������������������������������������������������������������������������������������������

�����������������������������������������������������������������������������������������������������������������������������������������������

�����������������������������������������������������������������������������������������������������������������������������������������������

������������������������������������������������������������������������������������������������������������������

�� �� �� ���� ��

����

������������

�������������

�������������������

������������������������������������������������������������������������������������

ktrnhjgbnfybt

�����������������������������������������������������������������

������������������������

����

����

����

��������������������

�������������������������������������������

��

��

�����������������������

���������������������������������������

��

������������������������

�����������������������������

����������������������������

���������������������������������������

����������������������������������������

������������������������������

�������������������������������������������

�������������������������������������������������������������Pfdjlcrjq yjvth�����������������

������������������������������������������������������������������������������������������� Ntgkjghjbpdjlbntkmyjcnm�������������������������

����������������� �������������������������������� ���������������������������� Gjktpyfz Ntgkjdfzvjoyjcnm

����������������������� ��������������������������������������������������� ���������������������������������� Vfrc= hf,jxtt lfdktybt

�������������������������� ����������������������������������������������������� ��������������������������������������������������� Vfrc= hf,jxfz ntvgthfnehf

���

��������������

������������������

���

��������������������������������������������������������������������������������������������������������������������������������������������������������

�������������������������������������������������������������������������������������������������Jghtccjd jxyjt lfdktybt#Lfnf

���������������������������������������������������

Vjltkm

Rjl

J,mtv rjnkjdjq djls

'

����

����

�������������������������������

���������������������������

����

����

����

����

W

T1

H

T4

T6

T1 - T3 - T2

L

T3 T2 T2 - T3 - T1

T5T5

T4

KEY

T1 Central heating flow outlet

T2 Central heating return inlet

T3 Expansion vessel attachment

T4 Boiler drain

T5 Flue attachment

T6 Burner attachment fitting

2360 3000 3600 4000 4500 5000 6000

Heat output min. kW 1535 1950 2340 2600 2926 3251 3902

max. kW 2360 3000 3600 4000 4500 5000 6000

Heat input min. kW 1668 2113 2536 2819 3165 3515 4215

max. kW 2565 3250 3900 4334 4868 5407 6483

Water content dm3 2150 2600 2950 4500 4950 6250 7000

Energy marking (Directive 92/42 EEC) ��� ★★ ★★ ★★ ★★ ★★ ★★ ★★Efficiency at Pn max (Tm 70°C) % 92.00 92.30 92.31 92.30 92.45 92.47 92.55

Efficiency at Pn min (Tm 70°C) % 93.20 93.51 93.72 93.51 93.40 93.30 93.50

Efficiency at 30% Pn max (Tm 50°C) % 93.65 93.76 94.21 93.76 94.05 93.90 94.35

Δt smokes-environment � gas 179.1/120 172.5/113 172.3/114 174.7/113 171.4/105 171.4/106 169.2/109

CO2 gas 10 10 10 10 10 10 10

CO2 oil 13 13 13 13 13 13 13

Specific Thermic load mW/m2h 52.4 49.1 52.9 45.4 46.3 45.0 43.7

Volumetric Thermic load mW/m2h 1.22 1.16 1.21 1.14 1.18 1.12 1.20

Shell loss* % 0.5 0.5 0.5 0.4 0.4 0.4 0.4

Loss at chimney burner on % 7.4 7.2 7.19 7.3 7.15 7.13 7.05

Loss at chimney burner off ** % 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Working pressure bar 6 6 6 6 6 6 6

Water side pressure drop Δt 10°C � Δp mbar 150 145 190 250 280 200 215

Δt 20°C � Δp mbar 42 45 61 70 80 55 65

Combustion chamber Internal Ø mm 980 1130 1130 1174 1174 1278 1278

Length mm 2750 3000 3300 3300 3300 3300 3300

Volume m3 2.10 2.80 3.20 3.80 4.10 4.80 5.40

Surface total m2 45 61 68 88 97 111 137

Flue gas side pressure drop � Δp mbar 7.2 7.5 8.2 9.5 10.5 10.8 12.0

Flue gas flow-rate gas Kg/h 3870 4904 5884 6539 7344 8158 9781

oil Kg/h 4108 5205 6246 6941 7795 8660 10383

Boiler weight (empty) kg 3900 5300 5800 7500 8000 9600 11500

Dimensions Height mm 1950 2140 2140 2325 2325 2525 2525

Width mm 1610 1800 1800 1980 1980 2180 2180

Length mm 3232 3446 3816 4086 4436 4458 4958

Connections T1 DN 150 200 200 200 200 250 250

T2 DN 150 200 200 200 200 250 250

T3 DN 100 125 125 125 125 150 150

T4 DN 11/2" 11/2" 11/2" 11/2" 11/2" 11/2" 11/2"

T5 Ø mm 450 500 500 600 600 650 650

* Air Blocked, temperature 20ºC** Combustion air closed

Page 26: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

26

Features and Benefits

The shape design of the heat exchanger ensures an optimum ratio between the combustion volumes and the heat exchange surfaces

The materials used ensure the long life of the boiler

New turbulators improve the heat exchange of the flue gas and at the same time ensure a lowerpressure drop

A baffle plate has been fitted at the central heating system return inlet to improve the circulation ofcold water towards the bottom of the boiler. This solution ensures more uniform distribution of theheat exchange fluid across the boiler’s heat exchange surface, achieving maximum heat exchange with less stress on the walls

The tube bundle has been positioned above the combustion chamber, so that the flue gas is alwaysdischarged into a “hot”environment, preventing condensation forming

The burner is not aligned with the combustion chamber, but rather has been moved downwards. This assists the reversal of the flame, reduces the pressure drop on the flue gas side and as aconsequence extends the operating range of the generator

The combustion chamber is completely cooled (even at the rear), to ensure a greater heat exchangesurface and improve the distribution of the heating load across the walls

The steel body is completely lined with an 80mm thick layer of glass wool, in turn covered by a sturdylayer of tearproof material

The door can be hinged on the right-hand or left-hand side, has a double door stop with a new-concept locking and centring system. The door lining in the “Quadra” is made from ceramic fibre

The PREXTHERM RSHQuadra series heatgeneratorsare pressurisedcombustion boilers with flame reversalin the combustionchamber and three flue gas passes.

12 models available from 92 to 940kW

Prextherm RSH QuadraHigh efficiency pressurised steel boilers

Page 27: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

27

Technical specifications

������������������

���������

�����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������

���������������������������������������������������������������������������������������������������������������������������������������������������������������������������

��������������������������������������������������������������������������������������������������������������������������������

������������������������������������������������������������������������������������������������������

�����������������������������������������������������������������������������������������������������������������������������������������������

�����������������������������������������������������������������������������������������������������������������������������������������������

������������������������������������������������������������������������������������������������������������������

���� �� �� �� ��

����

����

�������������������������������

���������������������������

����

����

����

����

����

������������

�������������

�������������������

������������������������������������������������������������������������������������

ktrnhjgbnfybt

�����������������������������������������������������������������

������������������������

����

����

����

��������������������

�������������������������������������������

��

��

�����������������������

���������������������������������������

��

������������������������

�����������������������������

����������������������������

���������������������������������������

����������������������������������������

������������������������������

�������������������������������������������

�������������������������������������������������������������Pfdjlcrjq yjvth�����������������

������������������������������������������������������������������������������������������� Ntgkjghjbpdjlbntkmyjcnm�������������������������

����������������� �������������������������������� ���������������������������� Gjktpyfz Ntgkjdfzvjoyjcnm

����������������������� ��������������������������������������������������� ���������������������������������� Vfrc= hf,jxtt lfdktybt

�������������������������� ����������������������������������������������������� ��������������������������������������������������� Vfrc= hf,jxfz ntvgthfnehf

���

��������������

������������������

���

��������������������������������������������������������������������������������������������������������������������������������������������������������

�������������������������������������������������������������������������������������������������Jghtccjdjxyjt l fdktybt#Lfnf

���������������������������������������������������

Vjltkm

Rjl

J,mtv rjnkjdjq djls

'

W

HT6

T3 - T1 - T2 T2 - T1 - T3

T5

T3 T1 T2

T4

L

T4

T5

KEY

T1 Central heating flow outlet

T2 Central heating return inlet

T3 Expansion vessel attachment

T4 Boiler drain

T5 Flue attachment

T6 Burner attachment

80 90 130 160 200 250 350 450 500 600 700 800

Heat output min. kW 60 70 100 137 160 196 260 341 390 468 533 611

max. kW 92 107 152 190 240 320 399 500 600 720 820 940

Heat input min. kW 63.7 74.3 105.8 144.4 168.4 206 272.6 357 407.9 489.8 558.4 638.9

max. kW 97.7 113.5 160.8 200.2 252.6 336.4 418.4 523.5 627.6 753.6 859.1 982.9

Water content dm3 120 185 235 304 362 337 405 471 735 850 850 1240

Energy marking (Directive 92/42 EEC) ��� ★★★ ★★★ ★★★ ★★★ ★★★ ★★★ ★★★ ★★★ ★★★ ★★★ ★★★ ★★★Efficiency at Pn max (Tm 70°C) % 94.19 94.27 94.52 94.92 95.02 95.15 95.37 95.52 95.62 95.56 95.47 96.00

Efficiency at Pn min (Tm 70°C) % 95.40 95.50 95.75 95.44 95.71 95.84 96.06 96.21 96.31 96.25 96.16 96.34

Efficiency at 30% Pn max (Tm 50°C) % 95.42 95.52 95.77 95.75 96.02 96.12 96.37 96.52 96.62 96.56 96.47 96.65

Δt smokes-environment � gas 112.9/85.6 111.1/83.4 107.8/80.1 101.1/82.7 101.1/79 98.2/76.8 95.5/73.6 92.2/70.3 92.2/70.3 93.5/78.4 97.8/75.8 93.8/71.9

CO2 gas 10 10 10 10 10 10 10 10 10 10 10 10

CO2 oil 13 13 13 13 13 13 13 13 13 13 13 13

Specific Thermic load mW/m2h 31.7 22.7 26.2 26.3 28.2 35.5 36.2 38.4 35.2 36.0 41.0 34.8

Volumetric Thermic load mW/m2h 1.08 0.81 0.94 0.91 0.97 1.05 0.92 0.96 1.01 1.07 1.22 1.09

Shell loss* % 1.3 1.3 1.2 1.1 1.0 1.0 0.9 0.9 0.8 0.8 0.7 0.7

Loss at chimney burner on % 4.51 4.43 4.28 3.98 3.98 3.85 3.73 3.58 3.58 3.6 3.83 3.65

Loss at chimney burner off ** % 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

Working pressure bar 6 6 6 6 6 6 6 6 6 6 6 6

Water side pressure drop Δt 10°C � Δp mbar 11 20 12 17 40 48 40 51 32 40 51 65

Δt 20°C � Δp mbar 2 5 3 4 9 13 12 16 10 18 16 20

Combustion chamber Internal Ø mm 390 420 420 420 420 488 638 638 686 686 686 776

Length mm 700 920 920 1170 1170 1135 1385 1660 1670 1670 1854 2104

Volume m3 0.09 0.14 0.17 0.22 0.26 0.32 0.45 0.54 0.62 0.70 0.70 0.90

Surface total m2 2.9 4.7 5.8 7.2 8.5 9 11 13 17 20 20 27

Flue gas side pressure drop � Δp mbar 0.7 1.2 1.2 2.3 3.3 3.5 4.3 4.8 4.5 5.6 5.4 6

Flue gas flow-rate gas Kg/h 156 182 258 321 405 539 670 838 1005 1207 1376 1574

oil Kg/h 161 186 264 329 415 553 687 860 1031 1238 1411 1615

Boiler weight (empty) kg 260 350 350 440 480 550 860 970 1250 1250 1420 1580

Dimensions Height mm 925 980 980 1100 1100 1100 1250 1250 1400 1400 1400 1580

Width mm 760 810 810 950 950 950 1060 1060 1260 1450 1450 1450

Length mm 1046 1296 1516 1546 1816 1817 1838 2098 2158 2398 2398 2420

Connections T1 DN 2" 21/2" 21/2" 21/2" 21/2" 21/2" 80 80 100 100 100 125

T2 DN 2" 21/2" 21/2" 21/2" 21/2" 21/2" 80 80 100 100 100 125

T3 DN 11/4" 11/2" 11/2" 11/2" 11/2" 11/2" 2" 2" 21/2" 21/2" 21/2" 3"

T4 DN 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"

T5 Ø mm 200 220 220 220 220 220 250 250 350 350 350 400

* Air Blocked, temperature 20ºC** Combustion air closed

Page 28: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

28

Features and Benefits

The shape design of the heat exchanger ensures an optimum ratio between the combustion volumes and the heat exchange surfaces

The materials used ensure the long life of the boiler

New turbulators improve the heat exchange of the flue gas and at the same time ensure a lowerpressure drop

A baffle plate has been fitted at the central heating system return inlet to improve the circulation ofcold water towards the bottom of the boiler. This solution ensures more uniform distribution of theheat exchange fluid across the boiler’s heat exchange surface, achieving maximum heat exchange withless stress on the walls

The tube bundle has been positioned above the combustion chamber, so that the flue gas is alwaysdischarged into a “hot”environment, preventing condensation forming

The burner is not aligned with the combustion chamber, but rather has been moved downwards. Thisassists the reversal of the flame, reduces the pressure drop on the flue gas side and as a consequenceextends the operating range of the generator

The combustion chamber is completely cooled (even at the rear), to ensure a greater heat exchangesurface and improve the distribution of the heating load across the walls

The steel body is completely lined with an 80mm thick layer of glass wool, in turn covered by a sturdylayer of tearproof material

The door can be hinged on the right-hand or left-hand side, has a double door stop with a new-concept locking and centring system. The door lining in the “Tonda” has a double cement lining plusan extra layer of insulating material

The PREXTHERM RSHTonda series heatgeneratorsare pressurisedcombustion boilers with flame reversalin the combustionchamber and three flue gas passes.

6 models availablefrom 1060 to 3000kW

Prextherm RSH TondaHigh efficiency pressurised steel boilers

Page 29: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

29

Technical specifications

������������������

���������

�����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������

���������������������������������������������������������������������������������������������������������������������������������������������������������������������������

��������������������������������������������������������������������������������������������������������������������������������

������������������������������������������������������������������������������������������������������

�����������������������������������������������������������������������������������������������������������������������������������������������

�����������������������������������������������������������������������������������������������������������������������������������������������

������������������������������������������������������������������������������������������������������������������

�� �� �� ���� ��

����

������������

�������������

�������������������

������������������������������������������������������������������������������������

ktrnhjgbnfybt

�����������������������������������������������������������������

������������������������

����

����

����

��������������������

�������������������������������������������

��

��

�����������������������

���������������������������������������

��

������������������������

�����������������������������

����������������������������

���������������������������������������

����������������������������������������

������������������������������

�������������������������������������������

�������������������������������������������������������������Pfdjlcrjq yjvth�����������������

������������������������������������������������������������������������������������������� Ntgkjghjbpdjlbntkmyjcnm�������������������������

����������������� �������������������������������� ���������������������������� Gjktpyfz Ntgkjdfzvjoyjcnm

����������������������� ��������������������������������������������������� ���������������������������������� Vfrc= hf,jxtt lfdktybt

�������������������������� ����������������������������������������������������� ��������������������������������������������������� Vfrc= hf,jxfz ntvgthfnehf

���

��������������

������������������

���

��������������������������������������������������������������������������������������������������������������������������������������������������������

�������������������������������������������������������������������������������������������������Jghtccjd jxyjt lfdktybt#Lfnf

���������������������������������������������������

Vjltkm

Rjl

J,mtv rjnkjdjq djls

'

����

����

�������������������������������

���������������������������

����

����

����

����

W

T1

H

T4

T6

T1 - T3 - T2

L

T3 T2 T2 - T3 - T1

T5T5

T4

KEY

T1 Central heating flow outlet

T2 Central heating return inlet

T3 Expansion vessel attachment

T4 Boiler drain

T5 Flue attachment

T6 Burner attachment

900 1100 1300 1600 2000 2600

Heat output min. kW 689 813 962 1229 1535 1950

max. kW 1060 1250 1480 1845 2360 3000

Heat input min. kW 719.9 848.2 1004.4 1291.2 1603.1 2033.7

max. kW 1107.6 1304.2 1545.2 1930 2464.7 3128.8

Water content dm3 1490 1490 1620 1925 2600 2920

Energy marking (Directive 92/42 EEC) ��� ★★★ ★★★ ★★★ ★★★ ★★★ ★★★Efficiency at Pn max (Tm 70°C) % 95.72 95.86 95.8 95.60 95.77 95.90

Efficiency at Pn min (Tm 70°C) % 96.41 96.55 96.46 95.80 96.39 96.59

Efficiency at 30% Pn max (Tm 50°C) % 96.72 96.87 96.81 96.50 96.78 96.91

Δt smokes-environment � gas 94.4/72.5 91.3/69.3 92.7/70.6 97.1/77.3 95.5/73.4 92.7/70.6

CO2 gas 10 10 10 10 10 10

CO2 oil 13 13 13 13 13 13

Specific Thermic load mW/m2h 32.1 37.8 40.0 41.0 38.6 44.1

Volumetric Thermic load mW/m2h 0.93 1.08 1.18 0.92 0.88 0.97

Shell loss* % 0.6 0.6 0.6 0.6 0.5 0.5

Loss at chimney burner on % 3.68 3.54 3.60 3.80 3.73 3.60

Loss at chimney burner off ** % 0.1 0.1 0.1 0.1 0.1 0.1

Working pressure bar 6 6 6 6 6 6

Water side pressure drop Δt 10°C � Δp mbar 86 110 100 150 145 190

Δt 20°C � Δp mbar 25 32 29 42 45 61

Combustion chamber Internal Ø mm 776 830 830 980 1130 1130

Length mm 2250 2500 2500 2750 3000 3300

Volume m3 1.20 1.20 1.30 2.10 2.80 3.20

Surface total m2 33 33 37 45 61 68

Flue gas side pressure drop � Δp mbar 6.5 6.5 6.8 7 7.2 7.5

Flue gas flow-rate gas Kg/h 1774 2088 2474 3091 3947 5010

oil Kg/h 1819 2142 2538 3171 4049 5140

Boiler weight (empty) kg 2250 2650 2850 3900 5300 5800

Dimensions Height mm 1730 1730 1730 1950 2140 2140

Width mm 1530 1530 1530 1610 1800 1800

Length mm 2722 2722 2722 3232 3446 3816

Connections T1 DN 150 150 150 150 200 200

T2 DN 150 150 150 150 200 200

T3 DN 100 100 100 100 125 125

T4 DN 11/2" 11/2" 11/2" 11/2" 11/2" 11/2"

T5 Ø mm 450 450 450 450 500 500

* Air Blocked, temperature 20ºC** Combustion air closed

Page 30: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Vapoprex LVPSteam output from 150 to 3000kg/hLow pressure steam boiler with three flue passes, two in furnace.

Vapoprex HVPSteam output from 150 to 5000kg/h Medium pressure steam boiler with three flue passes, two in furnace.

Vapoprex 3GFSteam output from 1700 to 8500kg/hMedium pressure steam boiler with three flue passes.

Vapoprex 3GNSteam output from 2000 to 28000kg/hMedium pressure steam boiler with three flue passes.

30

Steam Generators

Industrial Heating

Ferroli Industrial Heating offers a range ofboilers for markets worldwide, with outputsvarying between 100 and 19500kW:

• generators for the production of hotwater, superheated water and steam(with flame reversal and 3 flue passes)

• solid fuel generators for the production of hot water, superheated water andsaturated steam

Page 31: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

31

Hot water boilers

Superheated water boilers

Prextherm T 3GHeat output from 1200 to 19500kWHot water boiler with three flue passes, two in furnace.

Prextherm T 3G ASLHeat output from 1200 to 6000kWSuperheated water boiler max temperature 140°, with three flue passes.

Prextherm ASH/ASLHeat output from 160 to 3500kWSuperheated water boiler with three flue passes, two in furnace.

Prextherm 3GF1400 to 3000kWSuperheated water boiler with three flue passes.

Prextherm 3GN ASHeat output from 1400 to 19500kWSuperheated water boiler with three flue passes.

Hot Water Prextherm RSW/RSHHeat output from 92 to 3600kWHot water boiler with three flue passes, two in furnace.

Page 32: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Aquacyl twin coil cylinder is idealfor solar water heating. The lower coil can be heated byenergy from the solar collector. If hot water is required at a highertemperature than can be achievedby solar energy alone, then a FerroliHigh Efficiency boiler fires and heatsthe upper coil to boost the watertemperature. Alternatively thecylinder’s electric immersionheater(s) may be used to boostthe hot water temperature.

32

Aquacyl Twin CoilHigh quality stainless steel hot water cylinder

for use on unvented hot water systems

Features and Benefits

Twin coil for fastest heat recovery

No anode

Easy to install

Easy to commission

Simple electrical installation

Stylish appearance

Long life stainless steel body

Low density, low HCFC insulation ensures optimum efficiency

Easy to adjust immersion heaters

No internal expansion bubble to maintain

All pipe and electrical connections are possible from cylinder ‘front’

25 year guarantee plus nationwide cover from our own service engineers

Special features

Two 3kW immersion heaters fitted as standard (optional 6, 9 and 12kW heaters available)

6kW titanium heaters available for hard water areas or for customers with bore holes

Page 33: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

33

Ferroli’s Aquacyl cylinder range iseasy to install and commission.Each model is supplied completewith all necessary temperature andpressure expansion valves and vessels.

The Aquacyl cylinder vessel has a 25 yearmanufacturer’s guarantee as standard.

Technical specifications875170 875200 875250 875300 875510 875000

Storage capacity litres 170 200 250 300 500 1000

Overall diameter mm 510 554 554 554 660 820

Overall height mm 1200 1120 1330 1650 1835 2314

Overall height with expansion vessel on top mm 1480 1400 1330 2110 FM FM

Weight when full kg 220 250 310 360 556 1185

Primary flow/return connections 3/4" 3/4" 3/4" 3/4" 1" 1"

Cold feed/hot draw off connections 3/4" 3/4" 3/4" 3/4" 1" 1"

Maximum water supply pressure bar 12 12 12 12 12 12

System operating pressure bar 3 3 3 3 3 3

Expansion vessel charge pressure bar 3 3 3 3 3 3

Expansion relief valve set pressure bar 6 6 6 6 6 6

Temp and pressure relief valve set pressure bar 7 7 7 7 7 7

Temp and pressure relief valve lift temperature ºC 90 90 90 90 90 90

Maximum primary work pressure bar 3 3 3 3 3 3

Recommended maintenance Annual Annual Annual Annual Annual Annual

Immersion heater 3kW 230/240V L= 355mm 1 1 1 1 1 1

FM = Floor Mounted

Page 34: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

Remote thermostat

Wired or wireless remote control unit

Humidity control sensors for cooling mode

Built-in microprocessor control unit to manage the heating / cooling circuit

Expansion modules for management of multiple zones

Integrated management of multiple units in cascade (max. 16)

Legionella protection function

Digital management of special tariff time bands

Timer/programmer for timed domestic hot water production (with external storage cylinder)

Built-in compressor oil frost protection system

Outdoor probe for climate control supplied as standard

Built-in room humidity control with humidity sensor (optional) for cooling in summer

Control of solar heating system integration

Operating hour counter for the compressor and the pumps

Integrated management (with three heat output levels) of the supplementary electric heater (optional)

The HXA series heatpumps – suitable for familyhouses or small apartmentbuildings. Heat pumps donot require gas connectionsor the installation of flues.Ideal for new build as wellas being a cost effectiveretrofit solution in houseswhich currently rely uponliquid fuel systems (oil,LPG). The units can also beintegrated with a solarheating system.

Air Source Heat Pumps HXARenewable energy

34

The advanced microprocessor control unit can control theheating/cooling system, the domestic hot water storage cylinder and a solar heating system.

Page 35: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

35

Technical specifications

KEY1 Heating circuit return

2 Heating circuit return for use with integral standard orhigh head pump options

3 Heating flow

4 Heating flow with “Supplementary electric heater” option

Unit 1 2 3

Model 7.1 8.1 10.1 12.1 15.1 18.1

Power supply V-ph-Hz 230-1-50 230-1-50 230-1-50 230-1-50 – –

F.L.A. Maximum total input current A 13.4 17.1 22.0 24.8 – –

F.L.I. Maximum total power input kW 2.9 3.7 4.7 5.3 – –

Maximum total peak current A 82 112 141 174 – –

M.I.C. Maximum total peak current

with soft starter (option) A 41 43 49 59 – –

Power supply V-ph-Hz – – 400-3N-50 400-3N-50 400-3N-50 400-3N-50

F.L.A. Maximum total input current A – – 8.1 9.0 11.1 13.9

F.L.I. Maximum total power input kW – – 4.7 5.3 6.2 8.0

Maximum total peak current A – – 54 69 87 106

M.I.C. Maximum total peak current

with soft starter (option) A – – 33 40 48 55

Supplemental electric heaters (option)

Power supply V-ph-Hz 230-1-50 230-1-50 230-1-50 230-1-50 – –

– – 400-3N-50 400-3N-50 400-3N-50 400-3N-50

F.L.A. Maximum total input current (230V-1N-50Hz) A 28.7 28.7 28.7 28.7 – –

F.L.A. Maximum total input current (400V-3N-50Hz) A – – 9.5 9.5 9.5 9.5

F.L.I. Maximum total power input kW 6.6 6.6 6.6 6.6 6.6 6.6

Operational weight

Unit without options kg 89 96 108 126 143 152

Options

Control of the flow-rate of the heating circuit

Standard pump kg 7 7 7 7 14 14

High pressure pump kg 9 9 14 14 15 15

Supplementary electric heaters kg 5 5 5 5 5 5

Noise

Sound pressure level at 1 metre db(A) 55 55 57 57 59 59

D60

E

F

962G

52

L

356

97

56 994

H

102 710394 179

1

3

2

4

1

3

2

4

Unit 1 2 3Connections male 1" 1" 1"

D mm 509 759 1059

E mm 535 646 946

F mm 177 427 727

G mm 569 819 1119

L mm 155 155 97

H mm 903 1153 1453

Page 36: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

Three-speed heating circuit pump on the unit

Multistage high pressure heating circuit pump on the unit

Multistage high efficiency heating circuit pump on the unit

Snow protection cover (for outdoor installation)

Three-stage supplementary electric heaters

Remote thermostat

Wired or wireless remote control unit

Humidity control sensors in cooling mode

Three-way valve for the management of domestic hot water on the unit

Single-phase power supply (in versions up to 13kW)

Built-in microprocessor control unit to manage the heating/cooling system

Expansion modules for management of multiple zones

Integrated management of multiple units in cascade (max.16)

Legionella protection function

Digital input for management of special tariff time bands

Timer/programmer for timed domestic hot water production (with external storage cylinder)

Outdoor probe for climate control supplied as standard

Built-in room humidity control with humidity sensor (optional) for cooling in summer

Control of solar heating system integration

Operating hour counter for the compressor and pumps

Integrated management (with three heat output levels) of the supplementary electric heater (optional)

Ductable for indoor installation

Suitable for family housesor small apartmentbuildings. Heat pumps do not require gasconnections or theinstallation of flues. Idealfor newbuild as well asbeing a cost effectiveretrofit solution in houseswhich currently rely uponliquid fuel systems (oil,LPG). The units can alsobe integrated with a solarheating system.

Air Source Heat Pumps HXPReverse cycle (active reverse cycle) for OUTDOOR or INDOOR installation

36

Page 37: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

37

Technical specifications

KEY1 Heating circuit return

2 Heating circuit flow

3 Domestic hot water outlet

Unit 1 2 3Model 11.1 13.1 16.1 18.1 21.1 24.1 27.1 31.1 35.1Power supply V-ph-Hz 230-1-50 230-1-50 – – – – – – –

F.L.A. Maximum total input current A 22.5 25.3 – – – – – – –

F.L.I. Maximum total power input kW 4.8 5.4 – – – – – – –

Maximum total peak current A 142 175 – – – – – – –

M.I.C. Maximum total peak current

with soft starter (option) A 50 60 – – – – – – –

Power supply V-ph-Hz 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50

F.L.A. Maximum total input current A 8.6 9.5 10.6 11.5 12.8 17.1 22.1 23.1 26.1

F.L.I. Maximum total power input kW 4.8 5.4 6.1 7.4 8.2 11.0 14.3 14.9 16.9

Maximum total peak current A 55 70 87 96 105 125 146 155 162

M.I.C. Maximum total peak current

with soft starter (option) A 34 41 48 51 54 63 68 72 74

Supplemental electric heaters (option)Power supply V-ph-Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50

V-ph-Hz 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50 400-3N-50

F.L.A. Maximum total input current (230V-1N-50Hz) A 39.1 39.1 39.1 39.1 39.1 39.1 78.3 78.3 78.3

F.L.A. Maximum total input current (400V-3N-50Hz) A 13.0 13.0 13.0 13.0 13.0 13.0 26.0 26.0 26.0

F.L.I. Maximum total power input kW 9.0 9.0 9.0 9.0 9.0 9.0 18.0 18.0 18.0

System pump – standard (option)Power supply V-ph-Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50

F.L.A. Maximum total input current A 0.8 0.8 0.8 1.1 1.1 1.1 2.1 2.1 2.1

F.L.I. Maximum total power input kW 0.15 0.15 0.15 0.21 0.21 0.21 0.41 0.41 0.41

System pump – high pressure (option)Power supply V-ph-Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50

F.L.A. Maximum total input current A 1.1 1.1 1.1 2.1 2.1 2.1 2.3 2.3 2.3

F.L.I. Maximum total power input kW 0.21 0.21 0.21 0.41 0.41 0.41 0.45 0.45 0.45

System pump – high efficiency (option)Power supply V-ph-Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50

F.L.A. Maximum total input current A 0.7 0.7 0.7 0.7 0.7 0.7 1.6 1.6 1.6

F.L.I. Maximum total power input kW 0.14 0.14 0.14 0.14 0.14 0.14 0.31 0.31 0.31

Operational WeightUnit without options kg 209 221 223 279 283 301 355 357 360

Options

Heating circuit flow-rate control Standard pump kg 5 5 5 6 6 6 7 7 7

High pressure pump kg 6 6 6 7 7 7 7 7 7

High efficiency pump kg 5 5 5 5 5 5 7 7 7

Domestic hot water production

Three-way valve kg 7 7 7 9 9 9 9 9 9

Supplementary electric heaters kg 7 7 7 7 7 7 14 14 14

Accessories – Protection cover kg 24 24 24 31 31 31 38 38 38

NoiseSound pressure level without protection cover db(A) 56 56 57 59 59 60 60 61 61

at 1 metre with protection cover db(A) 53 53 54 55 55 56 56 57 57

B1

B2

A

H

1

32

1

32

Unit 1 2 3Connections male 1" 11/4" 11/4"

A mm 730 880 1180

B1 mm 730 880 880

B2 mm 1630 1810 1810

H mm 1470 1620 1620

Page 38: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

Quick and easy installation

Available in two sizes, the space saving all-in-one configuration makes the Aquasol XS

convenient to site

Pre-plumbed pipework saves on materials, reduces install time – saves costs for the home-owner

Specifically developed, easy-to-use controls for simple set-up and system monitoring

Additional heating coil and electric immersion element are included for supplementary heating of the

stored hot water for legionella protection

Revolutionary in-roof solar collectors, available in portrait or landscape, for both tile and slate roofs

Built in Solar Fluid ‘Drain-Back’ system prevents the solar collector freezing or overheating

No requirement for glycol based solar fluid. Simply fill with mains water

Connect the heating coil to a Ferroli Optimax HE Plus System or OV condensing boiler for a complete

household energy efficient heating solution

All components are easy to access for commissioning and servicing

Designed and manufactured to the highest specification

10 year warranty on the Aquasol XS Cylinder

By having the pumping

station and solar controller

all factory fitted into one

unit, the Aquasol XS storage

unit takes significantly less

time and cost to install.

Connecting the electric

wiring, solar coil, back up

heating and hot water

circuits is made simple.

Solar – Aquasol XSDrain Back Solar Systems

38

Page 39: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

39

Solar storage – lower part of tank litres 100

Back-up storage – upper part of tank litres 85

Back-up heat exchanger m2/kW 0.75/25

Electrical element kW 3kW

Dimensions (HxWxD) mm 1275 x 598 x 590

Weight empty kg 67

Recommended collector type Thermic 42

12mm flow. 15mm return. Col Loop Max L=m* m 27

15mm flow. 15mm return. Col Loop Max L=m* m 22

Solar storage = lower part of tank litres 150

Back-up storage = upper part of tank litres 130

Back-up heat exchanger m2/kW 0.90/30

Electrical element kW 3

Dimensions (HxWxD) mm 1785 x 598 x 590

Weight empty kg 84

Recommended collector type 2 x Thermic 28

12mm flow. 15mm return. Col Loop Max L=m* m 22

15mm flow. 15mm return. Col Loop Max L=m* m 18

* Maximum pipe (10x8mm/15x13mm) length collector circuit (L=flow + return) without the need to install an additional Drain-Back tank.

Product code 12021 12031 12035

Model name 28S 42L 42P

Height mm 1776 1776 2596

Width mm 1751 2596 1776

Depth mm 105 105 105

Weight kg 60 84 84

Gross panel area m2 3.11 4.61 4.61

Nett panel area m2 2.75 4.12 4.12

Zero loss collector efficiency 0.743 0.743 0.743

Heat loss coefficient A1 W/m2K 3.194 3.194 3.194

Aquasol XS 300T – ZU40030000Includes installation kit: (Monobloc Pressure Reducing Valve (PRV), Expansion Vessel,Tundish, Y Strainer, Brackets and Flex (where applicable))

Aquasol XS 200T – 24022FEIncludes installation kit: (Monobloc Pressure Reducing Valve (PRV), Expansion Vessel,Tundish, Y Strainer, Brackets and Flex (where applicable))

Technical specifications

Solar Panel (in-roof)

Page 40: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

Individual system components for the ultimate flexibility of siting

Three solar collector panel sizes to choose from and suitable for tile or slate roofs

Five different sized twin coil cylinders and 4 sizes drain back vessel options for exact specification to

the property needs

Solar panels can be mounted to either sloping or flat roofs

Extensive warranties on all components (Collectors – 10 years, Cylinder Vessel – 25 years)

Solar – AquacylDrain Back Solar Systems

40

Each system component isspecified and supplied forindividual siting andinstallation. Providingflexibility as the fundamentalbenefit of the Aquacyl system.The range of size options foreach major part means thatany property can be cateredfor. Furthermore, the ability to position them individuallyeradicates potentialrestrictions caused by internallayout or space constraints.

Page 41: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

41

Pumping Station

Product code ZU40021001

The pumping station has a 6m pump head and comes complete with:

• Built in controller for

- system monitoring display

- flow gauge

- up to 3 temperature sensors

- pump speed control

- system function control

• Pressure gauges

• Pressure relief valve

• Connections for filling and emptying

The essential heart of the Aquacyl solar solution.

Product code 12021 12031 12035

Model name 28S 42L 42P

Height mm 1776 1776 2596

Width mm 1751 2596 1776

Depth mm 105 105 105

Weight kg 60 84 84

Gross panel area m2 3.11 4.61 4.61

Nett panel area m2 2.75 4.12 4.12

Zero loss collector efficiency 0.743 0.743 0.743

Heat loss coefficient A1 W/m2K 3.194 3.194 3.194

Product code 20131 20033 20136 20140

Capacity litres 10 20 30 50

External (HxWxD) mm 260 x 310 x 260 400 x 365 x 355 400 x 520 x 355 400 x 830 x 355

Material Mild steel Mild steel Mild steel Mild steel

Pressure tested bar 4.5 4.5 4.5 4.5

Max peak temp °C 200 200 200 200

Max collector array m2 6 12.5 21 33

Technical specifications

Aquacyl Twin Coil Cylinders See page 33 for full range specifications

Solar Panel

Drain-back Units

Page 42: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Features and Benefits

Individual system components for the ultimate flexibility of siting

Two portrait solar collector panel sizes to choose from both are suitable for

tile or slate roofs with ‘on-roof’ fixing

Five different sized twin coil cylinders for exact specification to the property needs

Solar panels can be mounted on either sloping or flat roofs

Easy installation with ‘click clamps’ and double O-ring joints

Absorber of pure copper (12 tubes) with titanium oxide coating

Pre mixed solar fluid

Solar Keymark certification

High SAP ratings

Extensive warranties on all components (Collectors – 10 years, Cylinder Vessel – 25 years)

A bespoke solution for theultimate flexibility – Ferroli’sEcotop pressurised solar heatingsystem can be tailored to meetall your hot water needs. TheEcotop installation is filled with a solar fluid thatremains within the solarpanel and pressurised sealed system. Each systemcomponent is specified and supplied for individualsiting and installation.

Solar – EcotopPressurised solar heating for any home

42

Page 43: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

43

Technical specifications

Twin Line Pumping Station

Product code ZU40022001

The twin line pumping station has a 6m pump head and comes complete with:• Built in controller for- system monitoring display- flow gauge- up to 3 temperature sensors- pump speed control- system function control

• Pressure gauges

• Pressure relief valve

• Connections for filling and emptying

The essential heart of the Aquacyl solar solution.

Product code 0XCK1RXA 0XCK2RXA

Model name Ecotop VF 2.0 Ecotop VF 2.3

Height mm 1700 2000

Width mm 1160 1160

Depth mm 80 80

Weight kg 35 43

Gross panel area m2 1.97 2.32

Nett panel area m2 1.87 2.21

Zero loss collector efficiency 0.755 0.755

Heat loss coefficient A1 W/m2K 3.720 3.720

The Ecotop basic solar kit consists of:Solar Collector(s) – depending on quantity required.

Support Frame Box Kit(s) – used to support the solar panel on either sloping or flat roofs.

Hydraulic Kit – used to make the hydraulic connections to the solar panel.

Pump Station complete with solar controller.

Solar Expansion Vessel – accommodates the expansion of the solar system fluid.

Solar Expansion Vessel connection kit – to connect and support the expansion vessel.

Interconnection kit – hydraulic connection for more than one panel installation.

Aquacyl Twin Coil Cylinders See page 33 for full range specifications

Solar Panel

Page 44: Commercial Heating - Ferroli...Commercial Heating FERROLI LIMITED Ferroli began producing heating appliances and equipment in Italy during the 1950s. Today, the company is still family-owned

Commercial/V1/01.11

Whilst every effort is taken to ensure the accuracy of the information contained within thebrochure, the details are offered in good faith and Ferroli Ltd. accepts no liability for mattersarising as a result of errors and/or omissions.

The information in this brochure was correct at the time of printing, however specificationsand designs may be changed owing to Ferroli’s policy of continuous product research anddevelopment. The technical specifications in the product instruction manual supersedesand should always be referred to during installation and maintenance.

Reproduction of this publication, or any part, is not permitted without the written consent ofFerroli Ltd. Please contact our Marketing Communications via [email protected] forfurther information. The statutory rights of the consumer are not affected.

Ferroli LimitedLichfield Road, Branston Industrial EstateBurton on Trent, Staffordshire, DE14 3HD