Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region

www.EmersonNetworkPower.eu/400VDC

September 2015

Mirna Smrekar; Product Line Manager EMEA

Page 2: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

2

Case Study Overview

Data center with Solar integration

• Small scale data center in 2N concept powered by 400VDC

• 400VDC used with integration of Solar power

• Feeding IT equipment, cooling and lighting

Traditional Data center with AC&DC

• 2N data center concept

• AC&400VDC architectures built in parallel

• Future proof data center design

Traditional Telecom site

• 400VDC used as „transport voltage”

• 400/48VDC conversion close to -48VDC load

• Maximize copper savings and floor space

High Performance Computing

• Minimum heat load

• Efficient DC power distribution within a cabinet

• Scalability with 15kW modules

Different Market Drivers Behind Every Implementation

Page 3: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

3

Drivers for Implementation

Data Centers Telecom

Simplicity of Power Chain

Redundancy & Scalability

Integration of Renewables

Copper Savings

Installation Cost Saving

Centralized Battery

Future

Proof

High Performance Computing

Maximize Efficiency

Minimize Copper Content

Page 4: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

4

Case Study 1 - Bachmann Demostration site for DCC+G Project Data center with 2N concept and integrated solar panels in

same system All components in the system are fed from 400VDC (IT

equipment, lighting, cooling)

Page 5: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

5

Case Study 1 - Bachmann 400VDC rectifiers, Solar MPPT converters and batteries are

integrated in same cabinet

NetSure 4015

Page 6: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

6

Case Study 1 - Bachmann

Emerson Central Rectifier, DC Solar MPPT

controller and batteries

IT cross connection

cabinet

380VDC server cabinet (HP servers)

AC server cabinets

380VDC inverters

Philips DC Lighting

3rd place prize for energy efficiency at the Future-Thinking Data Center Conference in Darmstadt in April 2015

Page 7: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

7

Case Study 2 - Coromatic Coromatic as integrator provided energy efficient data center

inspired by Green.ch project to Scandinavian company Separate AC and 400VDC power paths are designed with 2N

redundancy with 250kVA per side in AC UPS and 120kW per side in 400VDC of installed power

Page 8: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

8

Case Study 2 - Coromatic IT racks were installed with AC power strip on one side and

400VDC power strip on the other side to ensure flexibility Initial load include 80kW of AC power load (cooling, lighting, IT

equipment, auxiliary loads) and 30kW of 400VDC powered loads (HP and Cisco servers)

Future expansion plans 240kW in 400VDC and 300kW of AC power to be installed

Page 9: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

9

Case Study 3 – African Telecom Provider 2 x 120kW 400VDC Power systems are installed in A+B

configuration and 30 minutes of centralized battery backup to ensure support of up to 2000A of -48VDC end loads

Distribution lengths between batteries and 400VDC power system to 400/48V DC/DC distribution can vary up to 77 meters

Page 10: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

10

Installation is done on multiple floors with batteries and 400VDC power system being positioned on ground floor

Compared to traditional -48VDC topology for this site customer achieved 25% savings in Capex using 400VDC as „transportation voltage”

Majority of Capex savings is based on copper and installation simplicity using 400VDC distributed over long power lines

Case Study 3 – African Telecom Provider

400VDC w/ 400/48V Conversion

Comparable -48V Installation

Product

Installation 25% savings

Page 11: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

11

Case Study 4 - RSC

Emerson with partnership with RSC installed 2 sites:

Saint Petersburg Polytechnic University (SPbPU)

o Polytechnic RSC PetaStream - 1st in Russia by energy efficiency level with 2,401.4 Mflops/Watt

o #8 in local Top50 supercomputers list for Russia/CIS

o Feed from NetSure 9500 120kW Power system and using Vicor 400/12V DC/DC converters

Joint Supercomputing Center of Russian Academy of Sciences (JSCC RAS)

RSC PetaStream - The first project on Intel® Xeon Phi™ 7120D in Russia and CIS

Feed from NetSure 4015 30kW Power system and using Vicor 400/12V DC/DC converters

Page 12: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

12

Case Study Summary End User Application Typical

Power Type Primary 400VDC

Driver Power Distribution

Bachmann Data center AC Power

Elimination of conversion stages; integration of solar

power

400V DC distribution to 400V DC loads; AC loads

powered via inverters

Scandinavian Company Data Center AC Power Elimination of

conversion stages

Parallel power paths distributing both 400V DC

and AC power

African Telecom Telecom -48V DC

Cable reduction: cost and cable management

400V DC distribution to -48VDC conversion and

loads

SPbPU supercomputer center & JSCC RAS upgrade

HPC AC Power Reduce losses in

copper and connectors

400V DC distribution to 12V DC conversion and

loads

Page 13: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

13

Conclusion NetSure™ 4015

NetSure™ 9500

NetSure™ 701 w/ 400V DC Input

NetSure™ 5100 w/ 400V DC Input

IP 55 Rectifier/Converter

400V DC Power Systems

400/48V DC/DC Converter Systems

Commercial deployments in Europe and Africa demonstrate increasing maturity and acceptance of 400V DC power as availability of 400VDC

equipment increases daily

Page 14: Commercial Deployments of 400VDC Data/Telecom …dcforum.ru/sites/default/files/12.10-12.30_emerson...Commercial Deployments of 400VDC Data/Telecom Centers in the EMEA Region September

14

Questions?

Thank you!