Combustible Dust Explosion Hazard Awareness
Instructor Guide
Texas Engineering Extension Service (TEEX)Professional and Regulatory Training (PRT)
A Member of The Texas A&M University System
OS PRT281 TR 07/09
The Texas A&M University System
Texas Engineering Extension Service (TEEX)
Professional and Regulatory Training (PRT)
COMBUSTIBLE DUST EXPLOSION HAZARD AWARENESS
INSTRUCTOR GUIDE
COMBUSTIBLE DUST EXPLOSION HAZARD AWARENESS
INSTRUCTOR GUIDE
Copyright InformationCOMBUSTIBLE DUST EXPLOSION HAZARD AWARENESS
© 2009 Texas Engineering Extension ServiceAll Rights Reserved. First Edition July 2009.Printed in the United States of America
Reproduction of this document, in whole or in part, requires written authorization from the Director, Texas Engineering Extension Service (TEEX), The Texas A&M University System, unless such reproduction is authorized or executed by the United States Government.
The safety statements, procedures, and guidelines contained in this manual are current as of the publication date. Prior to using the safety statements, procedures, and guidelines contained in this manual, it is advised that you confirm the currency of these statements, procedures, and guidelines with the appropriate controlling authorities.
This training is provided under Susan B. Harwood grant number 17798-08-60-F-48 awarded to the Texas Engineering Extension Service, OSHA Training Institute Southwest Education Center from the Occupational Safety and Health Administration, U.S. Department of Labor. It does not necessarily reflect the views or policies of the U.S. Department of Labor, nor does mention of trade names, commercial products, or organizations imply endorsement by the U.S. Government.
© 2009, Texas Engineering Extension Service. All rights reserved.
Table of ContentsClass Schedule.................................................vii
Distribution Shipping List ................................. viii
Instructor Preparation Checklist ........................ix
Module 0: Introduction and Orientation .....................................0-1
Instructional Guidance ............................. 0-1
Materials/Equipment ................................ 0-1
Instructor Preparation............................... 0-1
Introduction..................................................... 0-3
About this Course ........................................... 0-4
Course Goal ............................................. 0-4
Target Audience ....................................... 0-4
Delivery Methods ..................................... 0-4
Course Prerequisites................................ 0-4
Recommended Training........................... 0-4
Course Length.......................................... 0-4
Certification Information ........................... 0-4
Registration/Attendance Rosters ............. 0-5
Class Schedule ........................................ 0-5
Participant Evaluation Strategy ................ 0-6
Administrative Instructions.............................. 0-6
Resource List ........................................... 0-6
Icon Key ................................................... 0-8
Summary.................................................. 0-8
Module 0 PowerPoint Slides........................... 0-9
Module 1: Combustible Dust Introduction ...................................1-1
Instructional Guidance ............................. 1-1
Materials/Equipment ................................ 1-1
Instructor Preparation............................... 1-1
Introduction..................................................... 1-3
Key Terms ...................................................... 1-4
Combustible Dust Characteristics .................. 1-7
Dispersion ................................................ 1-7
Surface Area to Mass Ratio ..................... 1-8
Explosion Dynamics ................................ 1-8
Classification of Dust Flammability ................ 1-8
Health Hazards .............................................. 1-9
The History of Dust Explosions ...................... 1-9
Farmer's Export Company–December 28, 1977.............................. 1-9
Amoco Chemical Company–October 21, 1980.................................. 1-9
CTA Acoustics–February 20, 2003 ........ 1-10
Imperial Sugar Company–February 7, 2008 ................................ 1-10
Chemical Safety Board (CSB) Study–2003 ....................................................1-11
OSHA Combustible Dust SEP–March 2008 ........................................ 1-12
Application of Participants’ Knowledge/Skills....................................... 1-13
Evaluation of Participants............................. 1-13
Summary...................................................... 1-13
Module 1 Review Questions ........................ 1-15
Module 1 PowerPoint Slides ........................ 1-17
Module 2: Dust Control ...................2-1Instructional Guidance............................. 2-1
Materials/Equipment................................ 2-1
Instructor Preparation .............................. 2-1
Introduction .................................................... 2-3
Pressure Relief Valve..................................... 2-4
Dust Escape................................................... 2-4
Dust Escape ............................................ 2-4
Facility Design ......................................... 2-4
Equipment Integrity.................................. 2-4
Dust Collection ............................................... 2-5
Cleanup Methods .................................... 2-6
Vacuum Cleaner Filter ............................. 2-6
Dust Accumulation Prevention ....................... 2-6
Application of Participants’ Knowledge/Skills......................................... 2-8
© 2009, Texas Engineering Extension Service. All rights reserved.
IGiv
Evaluation of Participants ............................... 2-8
Summary ........................................................ 2-8
Module 2 Review Questions........................... 2-9
Module 2 PowerPoint Slides......................... 2-11
Module 3: Ignition Control ..............3-1Instructional Guidance ............................. 3-1
Materials/Equipment ................................ 3-1
Instructor Preparation............................... 3-1
Introduction..................................................... 3-3
Five Elements for Dust Explosions................. 3-4
Ignition Sources.............................................. 3-5
Definition of an Ignition Source ................ 3-5
Static Electricity ........................................ 3-5
Hot Surfaces ............................................3-6
Open Flame or Glowing Ember................ 3-6
Electric Arcs and Sparks .......................... 3-6
Industrial Trucks....................................... 3-6
Powder Actuated Tools ............................ 3-7
Smoldering Nests..................................... 3-7
Accidental Mechanical Impact.................. 3-7
Hot Work Permits and Lockout/Tagout........... 3-7
Separator Devices .......................................... 3-8
Intrinsically Safe Devices ......................... 3-8
Explosion Proof Devices .......................... 3-9
National Electric Code .................................... 3-9
NEC Classification–Article 500 ................ 3-9
NEC Classification–Groups E, F, and G ............................. 3-10
Application of Participants’ Knowledge/Skills ....................................... 3-11
Evaluation of Participants ............................. 3-11
Summary ...................................................... 3-11
Module 3 Review Questions......................... 3-13
Module 3 PowerPoint Slides......................... 3-15
Module 4: Support Systems............4-1Instructional Guidance ............................. 4-1
Materials/Equipment ................................ 4-1
Instructor Preparation............................... 4-1
Introduction .................................................... 4-3
Organizational Support .................................. 4-4
Plant Personnel Support.......................... 4-4
Management Support System ................. 4-4
Engineering Support System................... 4-4
Operations Support System .................... 4-5
Maintenance Support Systems................ 4-5
Documentation Systems ................................ 4-5
Application of Participants’ Knowledge/Skills......................................... 4-7
Evaluation of Participants............................... 4-7
Summary........................................................ 4-7
Module 4 Review Questions .......................... 4-9
Module 4 PowerPoint Slides ........................ 4-11
Module 5: Damage Control .............5-1Instructional Guidance............................. 5-1
Materials/Equipment................................ 5-1
Instructor Preparation .............................. 5-1
Introduction .................................................... 5-3
Damage Control Systems .............................. 5-4
Spark Ember Detection............................ 5-4
Extinguishing System .............................. 5-5
Hazard Separation................................... 5-5
Hazard Segregation................................. 5-5
Deflagration Venting ................................ 5-5
Pressure Relief Venting ........................... 5-5
Specialized Fire Suppression Systems ... 5-6
Emergency Response Planning..................... 5-7
Pre-explosion........................................... 5-7
Dust Explosion......................................... 5-7
Post Explosion......................................... 5-7
Application of Participants’ Knowledge/Skills......................................... 5-9
Evaluation of Participants............................... 5-9
Summary........................................................ 5-9
Module 5 Review Questions ........................ 5-11
Module 5 PowerPoint Slides ........................ 5-13
© 2009, Texas Engineering Extension Service. All rights reserved.
IG v
Module 6: Facility Dust Assessment ...................................6-1
Instructional Guidance ............................. 6-1
Materials/Equipment ................................ 6-1
Instructor Preparation............................... 6-1
Introduction..................................................... 6-3
Facility Dust Assessment ............................... 6-4
Dust Assessment Characteristics................... 6-4
Dust Combustibility .................................. 6-4
Dust Characteristics ................................. 6-6
Area Volume............................................. 6-7
Hidden Area Inspection............................ 6-7
Dispersion Method ................................... 6-7
Ignition Sources ....................................... 6-8
Electrical Classification ............................ 6-8
Ventilation Systems.................................. 6-8
Physical Barriers ...................................... 6-9
Checklist "Self-Audit" ...................................... 6-9
Application of Participants’ Knowledge/Skills ....................................... 6-11
Evaluation of Participants ............................. 6-11
Summary ...................................................... 6-11
Module 6 Review Questions......................... 6-13
Module 6 PowerPoint Slides......................... 6-15
Appendix A: Resources ................. A-1Appendix B: List of
Products/Materials in Powdered Form ............................ B-1
Appendix C: Relevant Acronyms...................................... C-1
Appendix D: Course Exam ............ D-1
© 2009, Texas Engineering Extension Service. All rights reserved.
IGvi
Class Schedule
© 2009, Texas Engineering Extension Service. All rights reserved.
IG vii
Class Schedule
Day1
Session ModuleInstructional Hours
Classroom Lab/FieldActivity Total
AM Session 1
Module 0: Course Introduction 30 min 0 30 min Module 1: Combustible Dust Introduction 60 min 0 60 min
Module 2: Dust Control 60 min 0 60 min Break 0 0 15 min
AMSession 2
Module 3: Ignition Control 60 min 0 60 min Module 4: Support Systems 60 min 0 60 min
Lunch 0 0 60 min PM
Session 1 Module 5: Damage Control 60 min 0 60 min Break 0 0 15 min
PMSession 2 Module 6: Facility Dust Assessment 90 min 0 90 min
PMSession 3 Course Exam 60 min 0 60 min
Daily Totals 8 hours 0 min 9 hours
Course Totals 8 hours 9 hours
Distribution Shipping List
© 2009, Texas Engineering Extension Service. All rights reserved.
IGviii
Distribution Shipping ListP
(OS PRT281 TR) Combustible Dust Explosion Hazard Awareness
Distribution Center Shipping List
Training Materials
1 per Student:
Combustible Dust Explosion Hazard Awareness (PRT281)
Miscellaneous Materials – 1 per class unless otherwise noted
Return Labels – (if shipped)
White copy of this Pack-Out list
Notes
Number of manuals for students determined by pre-registration in TIGRS 1 week prior to class with 10 additional manuals.
APPROVALS:
Curriculum Services Program Manager
Instructor Preparation Checklist
© 2009, Texas Engineering Extension Service. All rights reserved.
IG ix
Instructor Preparation Checklist
1. Equipment Computer
Video/Data Projector
Screen
Stands for projectors and computers if required (2 each)
Extension cords with multiple plugs
2. Supplies Pencils
3. Instructional Aids/Media Combustible Dust Explosion Hazard Awareness Instructor Guide
Computer disk with instructional media (back-up)
Dry Erase/Chalk Board (Depends on classroom provided equipment)
4. Participant Materials Combustible Dust Explosion Hazard Awareness Participant Manual
Student rosters and course evaluations from Customer Care Center Representative
Participant registration forms
5. Special Requirements/Instructions Ensure class location is booked and if not reserve it.
Take along promotional material for participants desiring information on other TEEX courses.
It is not unusual to have participants who arrive late.
Keep rosters updated for correct attendance record.
Replacements are sometimes sent due to conflicts in contract performance. Be sure you check rosters and add or subtract appropriately.
Participants not listed on roster must have their paid registration verified (by instructor) with Customer Care Center (979) 845-6563.
Instructor Preparation Checklist
© 2009, Texas Engineering Extension Service. All rights reserved.
IGx
© 2009, Texas Engineering Extension Service. All rights reserved.
Module
Introduction and OrientationInstructional GuidanceTime: 30 minutes
Materials/Equipment1. Participant Manual
2. PowerPoint visuals for module 0
3. Whiteboard/markers/eraser
4. Video/data projector
5. Screen or monitor
Instructor PreparationPrepare projector and position first powerpoint slide.
Introduction and Orientation
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 2
Introduction and OrientationIntroduction
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 3
Introduction
In this module, the participants will complete registration procedures and receive course information, including prerequisites and attendance requirements, as well as evaluation and certification information. The instructor will conduct a brief overview of the course which includes the goals and objectives, required participant equipment, and class schedule.
Terminal ObjectiveUpon successful completion of this module, the participant will be able to participate in the course.
Enabling Objectives1. Complete TEEX course registration forms.2. Ask questions related to the course.
Slides 1-2
Slide 3
Slide 4
Introduction and OrientationAbout this Course
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 4
About this Course
This course provides participants with information about combustible dust that could identify process problems that could cause catastrophic fire or explosion.
Course GoalUpon successful completion of this course, the participant will be able to assess combustible dust explosion potential and the safety systems in place to minimize dust explosion hazards.
Target AudienceThis course is designed for anyone evaluating and managing operations that can generate combustible dust and CSHO leaders.
Delivery MethodsCourse delivery consists of lectures and group discussions.
Course PrerequisitesNone
Recommended TrainingNone
Course Length8 hours
Certification InformationTEEX has been approved as an Authorized Provider by the International Association for Continuing Education and Training (IACET), 8405 Greensboro Drive, Suite 800, McLean, VA 22102. In obtaining this approval, TEEX has demonstrated that it complies with the ANSI/IACET Standards which are widely recognized as standards of good practice internationally. As a result of their Authorized Provider membership status, TEEX is authorized to offer IACET CEU’s for its programs that qualify under ANSI/IACET Standards. TEEX is authorized by IACET to offer 0.4 CEUs for this program.
Slide 5
Introduction and OrientationAbout this Course
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 5
Registration/Attendance RostersTEEX-PRT attendance policy requires all students to fully attend enrolled classes. You must attend the entire class to receive a certificate of completion. We realize that extenuating circumstances may arise that would take you out of class and use the following policy to handle those situations.
If an extenuating circumstance requires you to attend less than 100% of class, you must complete a Student Absentee Request form and submit it to the instructor for approval before leaving. If the extenuating circumstance arises during non-class hours, you must complete the Student Absentee Request form immediately upon return to the classroom and submit it to the instructor for approval. With an approved absence for extenuating circumstances you may have options for make-up work. See your instructor.
Unexcused absences will require you to make up time missed by attending the same course offered at another time. You must enroll through TEEX-PRT Registrars to attend the makeup course. In order to receive a certificate of completion, each participant must:
• Complete a registration form at the beginning of the course;
• Sign the attendance roster for each morning and afternoon of the course; and
• Complete the evaluation at the end of the course.
Class Schedule
Day 1
Morning
Module 0: Introduction and Orientation
Module 1: Combustible Dust Introduction
Module 2: Combustible Dust Control
Module 3: Ignition Control
Slide 6
Introduction and OrientationAdministrative Instructions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 6
Afternoon
Module 4: Support Systems
Module 5: Damage Control
Module 6: Facility Dust Assessment
Appendix A: Resources
Course Exam
Participant Evaluation Strategy
The evaluation plan incorporates strategies for evaluating participants’ progress in the classroom. The instructor will use oral questioning during the presentation and discussions to assess the participants’ mastery of the material. The group activities will also allow the instructor to determine how well participants can apply classroom information to real-life situations. Problem areas identified in the classroom will be reviewed in further detail. Successful completion of the course depends on classroom responses, participation in group discussions, completion of review questions, and successful completion of a course examination with a grade of 70% or higher.
Administrative Instructions
Instructors will use this portion of the course for introductions and to familiarize the participants with the facility’s safety and convenience features, the location of the facility’s designated smoking area(s), and any additional resources or equipment available.
Resource ListWhile Appendix A contains a number of resources concerning combustible dust, several online resources worth noting include the following:
• 29 Code of Federal Regulations §1910.119 can be found at www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=STANDARDS&p_id=9760
• A Guide to Combustible Dusts by North Carolina Department of Labor can be found at www.nclabor.com/osha/etta/indguide/ig43.pdf
Slide 6
Introduction and OrientationAdministrative Instructions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 7
• Combustible Dusts presented by Bruce L. Rottner, CSP at the 2006 American Industrial Hygiene Association (AIHce) can be found at www.aiha.org/aihce06/handouts/cr314rottner.pdf
• Ethylene Safety Incidents presented by Kolmetz.com can be found at kolmetz.com/pdf/Ethylene-safety-incidents.pdf
• Hazardous or Combustible Dusts, Fumes and Fibres by Government of Western Australia, Department of Commerce’s can be found at www.commerce.wa.gov.au/worksafe/PDF/Guides/dust_fume_fibre.pdf
• North Carolina Department of Labor (NCDOL) Industry Alert- Combustible Dust: A Major Hot Work Hazard can be found at www.nclabor.com/osha/etta/hazard_alerts/combdust_hotwork.pdf
• OSHA Fact Sheet: Combustible Dust Explosions produced by OSHA can be found at www.osha.gov/OshDoc/data_General_Facts/OSHAcombustibledust.pdf
• Understanding NFPA 654: Protecting Your Plant from Dust Explosions produced by BS&B Pressure Safety Management, L.L.C can be found at www.bsbipd.com/PDF/understandingNFPA654%202006%20Edition.pdf
• U.S. Chemical Safety and Hazard Investigation Board Hearing on Hazard Communication in the 21st Century Workplace (March 2004) can be found at www.osha.gov/dsg/hazcom/finalmsdsreport.html
Introduction and OrientationAdministrative Instructions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 8
Icon KeyThe following icons are used in this manual:
SummaryNow that the administrative section of the course has been completed, continue to Module 1: Combustible Dust Introduction.
DVD
Review Question
Slide(s)
Slide
Slide 7
Introduction and OrientationModule 0 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 9
Module 0 PowerPoint Slides
Module 0
OS PRT281 TR 1
Introduction and Orientation
This training is provided under Susan B. Harwood grant number 16633-07-60-F-48 awarded to the Texas Engineering Extension Service, OSHA Training Institute Southwest Education Center from the Occupational Safety and Health Administration U S Department of Labor It does
OS PRT281 TR 2
Administration, U.S. Department of Labor. It doesnot necessarily reflect the views or policies of the U.S. Department of Labor, nor does mention of trade names, commercial products, or organizations imply endorsement by the U.S. Government.
Terminal Objectives
Upon successful completion of this module, the participant will be able to participate in the course.
OS PRT281 TR 3
Introduction and OrientationModule 0 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 10
Enabling Objectives
• Complete TEEX course registration forms.• Ask questions related to the course.
OS PRT281 TR 4
Course Goal
Upon the successful completion of this course, the participant will be able to assess combustible dust explosion potential and the safety systems in place to minimize dust
OS PRT281 TR 5
safety systems in place to minimize dustexplosion hazards.
Course Schedule
• Module 1: Combustible Dust Introduction• Module 2: Combustible Dust Control• Module 3: Ignition Control
OS PRT281 TR 6
• Module 4: Support Systems• Module 5: Damage Control• Module 6: Facility Dust Assessment
Introduction and OrientationModule 0 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 11
Next Module
OS PRT281 TR 7
Module 1: Combustible Dust Introduction
Introduction and OrientationModule 0 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG0 - 12
© 2009, Texas Engineering Extension Service. All rights reserved.
Module
Combustible Dust Introduction
Instructional GuidanceTime: 60 minutes
Materials/Equipment1. Participant manual
2. PowerPoint visuals for module 1
3. Whiteboard/markers/eraser
4. Video/data projector
5. Screen or monitor
Instructor Preparation1. Prepare projector and position first PowerPoint slide.
2. Review this module’s objectives with participants so they are aware of what they will be learning during this module.
Combustible Dust Introduction
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 2
Combustible Dust IntroductionIntroduction
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 3
Introduction
To gain a solid foundation in understanding combustible dust, it is important to understand the characteristics and activities that create combustible dust.
Terminal ObjectiveUpon successful completion of this module, participants will be able to describe the characteristics of combustible dust.
Enabling ObjectivesUpon successful completion of this module, the participant will be able to:1. Define the key terms relevant to combustible dust.2. Describe the characteristics of combustible dust.3. Identify the six classifications of combustible dust flammability.4. Explain the health hazards associated with combustible dust work
environments.5. Review the event history of combustible dust incidents.
Slide 1
Slide 2
Slides 3-4
Combustible Dust IntroductionKey Terms
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 4
Key Terms
There are several terms that are specific to combustible dust. Combustible Dust is any finely divided solid material that is 420 microns or smaller in diameter (material passing a U.S. No. 40 Standard Sieve) and presents a fire or explosion when dispersed or ignited in air.
OSHA identifies 130 products or materials that pose a threat for combustible dust explosions which include the following:
• Agricultural products and dusts
• Biosolids
• Carbonaceous dusts
• Chemical dusts
• Metal dusts
• Organic dusts
• Plastic dusts and additives
• Wood dusts
• Industries handling combustible dusts
• Agriculture
• Chemical
• Coal
• Food products
• Forest and furniture
Instructor NoteUse the following question to facilitate a discussion.
When thinking about combustible dust, what industries/manufacturing process/products pose a threat for combustible dust explosions?
Slide 5
Combustible Dust IntroductionKey Terms
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 5
• Metal processing
• Paper
• Pharmaceutical
• Recycling
• Textile
• Tire and rubber
• Wastewater treatment
Figure 1.1 situates a breakdown of dust explosions, according to industries, occurring in 2008. In 2008, the food industry had 27% of all dust explosions.
Instructor NoteUse the following question to facilitate a discussion.
What factors would cause the food industry to be plagued with the largest number of dust explosions?
Figure 1.1: Dust Explosions According to Industry
Slide 6
Combustible Dust IntroductionKey Terms
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 6
The following are key terms that will be used throughout the remainder of the course:
• Ignition—When the temperature of powder or dust exceeds the temperature of the surrounding air.
• Dispersion—The scattering of dust into the atmosphere.
• Optimum cloud density—Allows sufficient distance between the particles to allow access of oxygen around the particles; but close enough so that the heat of one ignited particle can initiate reactions in nearby particles.
• Fire—A rapid oxidation process with the evolution of light and heat in varying intensities (2C+O2 2CO).
• Deflagration—Occurs when there is a combustion reaction where the velocity of the reaction front through the unreacted fuel medium is less than the speed of sound. This type of explosion is associated with vapor or dust clouds and can occur when enough dust particles are suspended in an enclosure. Deflagration requires fuel to be in a confined enclosure and easily dispersed within the enclosure.
• Detonation—Combustion where a supersonic shock wave is produced. When related to dust, detonation is often called layered detonation and is highly destructive.
• Primary explosion—The initial explosion in processing equipment or in an area where dust has accumulated. This explosion triggers a larger, more destructive explosion.
• Secondary explosion—Triggered by a primary explosion and occurs when accumulated dust is shaken loose or damage occurs to dust containment systems from a primary explosion.
Instructor NoteWhen viewing powerpoint slide 11, take a moment to discuss the Primary/Secondary Explosion animation. To view the animation, click on any part of the graphic on slide 11.
During this time explain to participants the cause of the primary explosion and then the secondary explosion.
Slide 7
Slide 8
Slide 9
Slides 10-11
Combustible Dust IntroductionCombustible Dust Characteristics
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 7
Combustible Dust Characteristics
Characteristics of combustible dust include the following:
• Particle size
• Chemical properties of dust
• Moisture content
• Cloud dispersion
The following are general parameters of combustible dust:
• Average minimum concentration is approximately 0.05 oz/ft3 or 50g/m3
• Materials that ignited above 0.50 joules are not considered sensitive to ignition by electrostatic discharge
• Minimum ignition temperature of the cloud is <400°C
• Minimum ignition temperature of a 5mm layer is <300°C
• Minimum ignition energy of the cloud is <15mJ
Dispersion Ease of dispersion into the air has several factors including the following:
• Individual density of dust particles
• Diameters
• Shapes
• Cohesive properties with respect to each other
• Adhesive properties with respect to supporting surfaces
Slide 12
Slide 13
Slide 14
Combustible Dust IntroductionClassification of Dust Flammability
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 8
There are also external factors that affect dust dispersion. These include the following:
• Structure and intensity of aerodynamic disturbances
• Location of dust loading (roof, floor, walls, shelves) and
• Geometry of those surfaces
Surface Area to Mass RatioDust explosions occur when there is a rapid oxidation of the particle surface. An increasing surface to mass ratio allows less heat to dissipate into the mass. The less heat absorbed by the mass of the particle, the more that heat accelerates the reaction.
Explosion DynamicsThe effect of an explosion depends on the amount of power the dust can generate when it explodes. This is often referred to as explosion dynamics and two of it's most important attributes are Thermodynamics and Kinetics.
• Thermodynamics is the amount of heat liberated during combustion. Keep in mind that different types of dust will generate various levels of heat.
• Kinetics is the rate at which heat is liberated during combustion.
When significant heat is released at a rapid rate during the combustion of dust, the explosion is more powerful than when the amount of heat is less or the explosion rate is less rapid.
Classification of Dust Flammability
There are six classifications of dust flammability:
• Class 1: there is no self sustained combustion
• Class 2: there is local combustion of a short duration
• Class 3: a local self-sustained combustion has not propagation
• Class 4: there is propagating, smoldering combustion
Slide 15
Slide 16
Slide 17
Combustible Dust IntroductionHealth Hazards
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 9
• Class 5: when there is propagation of an open flame
• Class 6: there is explosive combustion
Health Hazards
Dusts cause various hazards. The worst health hazard can be death, either by explosion or severe burns or as an airborne contaminant.
Dusts pose other hazards besides explosivity, such as:
• Reduced visibility
• Slippery surface conditions
• Asbestos and silica (While not explosive, present a serious respiratory hazards and can cause long-term health effects, such as silicosis or asbestosis.)
The History of Dust Explosions
Farmer's Export Company–December 28, 1977A spark near the grain elevators in Galveston, Texas, caused a massive explosion near the Galveston docks. The blast occurred in a tunnel that connected the elevator to a loading dock. Two ships were unloading grain at the time of the blast. Eighteen people died and at least 35 were injured. This was the second explosion at an American grain elevator in five days. The first was in New Orleans where 35 people were killed.
The force of the Galveston blast was tremendous. There were large holes blown out of the side of concrete silos and automobile-sized chunks of concrete were thrown more than 200 feet away. Windows were shattered a mile away and the blast was heard 70 miles away. A nearby railroad switch engine was completely twisted into a tangle of steel.
Amoco Chemical Company–October 21, 1980A polypropylene unit located near New Castle, Delaware exploded during the night. The initial explosion was triggered by the ignition of a propylene vapor cloud. This explosion shook loose combustible dust that caused a substantial secondary explosion. Six workers died and more than 100 were injured.
Slide 18
Slides 19-20
Slide 21
Combustible Dust IntroductionThe History of Dust Explosions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 10
The total loss and damage estimate was in excess of $45 million. There was so much damage to the site that Amoco chose not to rebuild at this site. This decision led to the loss of 300 jobs.
CTA Acoustics–February 20, 2003The Corbin, Kentucky facility produced fiberglass mats and insulation for the automotive industry. During production, phenolic resin powder (fuel source) dust accumulated in the production area.The dust likely ignited when a fire in a malfunctioning oven ignited a cloud of resin dust generated during the cleaning of a production line.
The Chemical Safety Board (CSB) investigation found use of compressed air, electric fans, and brooms to remove dust formed a cloud near the production line oven. The oven was running hot, due to a malfunctioning temperature controller. Therefore, the oven door was left open to try to control the temperature.The explosion and fire destroyed the manufacturing plant, killed seven workers and injured many others.
Three years before the CTA explosion, there was a similar explosion at the Jahn Foundry plant in Springfield, Massachusetts. This explosion involved the same type of phenolic resin powder and was supplied by the same supplier that CTA used. Three people were killed, nine were injured, and the plant was destroyed in the Jahn Foundry explosion.
The phenolic resin materials sold to CTA by the supplier were not labeled EXPLOSIVE. CTA denied any awareness of the explosive nature of the powder, even though the Jahn Foundry explosion report sited phenolic resin dust as the fuel source. CTA also stated that they relied upon the supplier and their MSDS for information regarding the material.
CTA had a history of small fires caused by accumulation of combustible materials. It was reported that CTA employees routinely put out these fires using extinguishers and hoses.
Imperial Sugar Company–February 7, 2008Perhaps the most televised and reported dust explosion occurred at the Imperial Sugar refinery near Savannah, Georgia. Fourteen people died and 38 were injured, including 14 with serious, life-threatening burns.
The explosion damage included tops of silos that were missing completely and brick walls that were totally blown out. The explosion occurred in the section of the refinery where sugar was pulverized into powdered sugar and packaged. The initial explosion was likely caused by a bucket elevator which sent more combustible dust into the atmosphere, providing a fuel source for the larger secondary explosion.
Slide 22
Slide 23
Combustible Dust IntroductionThe History of Dust Explosions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 11
The OSHA investigators found that the Imperial Sugar Senior Management was fully aware of combustible dust hazards and that steps had been taken to find out what the hazards were of combustible dust in the refinery. However, these steps were not followed up with any action to eliminate the hazards.
OSHA indicated 51 serious violations, which included the following:
• Improper installation of a dust collection system
• Lack of sensors on conveyer belts
• Failure to construct a blast-proof exterior wall in the powder room
On March 7, 2008, the head of OSHA sent a letter directly to the CEO of Imperial Sugar because of the blast at the Savannah refinery. This letter urged him to eliminate any potential combustible dust hazards at the plant in Gramercy, Louisiana. On March 14th, OSHA inspected the Gramercy plant. The inspectors found combustible dust ranging from an inch to four feet deep. Due to the inspection findings, OSHA posted an imminent danger notice because of the high likelihood of fire and explosion.
The explosion of the Imperial Sugar Company plan in Savannah, has brought significance to the importance of combustible dust regulation in all industries.
Chemical Safety Board (CSB) Study–2003The CSB conducted a combustible dust explosion study in 2003. They found that over a 25-year period, there were 119 fatalities and 718 injuries contributed to combustible dust explosions and fires.
This study prompted a recommendation to OSHA (Occupational Safety and Health Administration) to get involved with combustible dust incidents and prevention. In addition the CSB recommended to ANSI (American National Standards Institute) to modify the Z400.1. This modification focuses on MSDSs including information on combustible dust hazards.
Slide 24
Slide 25
Combustible Dust IntroductionThe History of Dust Explosions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 12
OSHA Combustible Dust SEP–March 2008As a result of the CSB study and multiple combustible dust incidents, particularly the Imperial Sugar explosion, OSHA sent out a letter and bulletin entitled, Combustible Dust in Industry: Preventing and Mitigating the Effects of Fire Explosion, to 30,000 workplaces in March 2008. This OSHA-wide directive was issued with instruction, policies and procedures for inspecting workplaces that create or handle combustible dusts. In addition, OSHA reissued the Combustible Dust National Emphasis Program (CPL 03-00-008), which included inspections for combustible dust hazards.
Many unfortunate incidents involving combustible dust occurred before industry and regulators took notice. Just recently regulations and policies are bringing the needed focus on combustible dust safety.
Slide 26
Combustible Dust IntroductionApplication of Participants’ Knowledge/Skills
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 13
Application of Participants’ Knowledge/Skills
Participants will apply their knowledge by answering review questions at the end of the module.
Evaluation of Participants
Evaluation is based on participants’ active participation in class discussions and responses to review questions at the end of the module.
Summary
Until recently, not much was done to regulate safety for combustible dust. Now, regulations and policies are being developed and implemented in many industries to prevent catastrophic occurrences involving combustible dust. In addition to specific history of accidents involving combustible dust, this module provided an overview of properties of combustible dust, health hazards associated with dust, and standards that are specific to the electric industry.
Slide 27
Combustible Dust IntroductionSummary
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 14
Combustible Dust IntroductionModule 1 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 15
Module 1 Review Questions
Directions: Circle the letter of the best answer.
1. Combustible dust is any finely divided solid material that is ________ microns or smaller in diameter. (1-3)
a. 420
b. 380
c. 240
d. 520
2. A primary explosion is often the largest one. (1-5)
a. True
b. False
3. Which explosion garnered the most attention with respect to the importance of combustible dust regulations? (1-5)
a. CTA Acoustics - Corbin, KY
b. Imperial Sugar - Savannah, GA
c. Amoco Chemical - New Castle, DE
d. Farmer's Export Company - Galveston, TX
4. Properties of combustible dust include all of the following EXCEPT: (1-6)
a. Particle size
b. Chemical Properties of dust
c. Cloud dispersion
d. Time in atmosphere
5. The less heat absorbed by the mass of the particle, the ________ that heat accelerates the reaction. (1-8)
a. more
b. less
6. Reduced visibility is a health hazard associated with combustible dust. (1-9)
a. True
b. False
Combustible Dust IntroductionModule 1 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 16
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 17
Module 1 PowerPoint Slides
Module 1
OS PRT281 TR 1
Combustible Dust Introduction
Terminal Objectives
Upon successful completion of this module, participants will be able to describe the characteristics of combustible dust.
OS PRT281 TR 2
Enabling Objectives
• Define the key terms relevant to combustible dust.
• Describe the characteristics of combustible dust
OS PRT281 TR 3
dust.• Identify the six classifications of
combustible dust flammability.
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 18
Enabling Objectives
• Explain the health hazards associated with combustible dust work environments.
• Review the event history of combustible dust incidents
OS PRT281 TR 4
dust incidents.
Key Terms
• Combustible dust– Finely divided solid material– 420 microns or smaller in diameter
Flammable/explosive when ignited
OS PRT281 TR 5
– Flammable/explosive when ignited
• Agriculture products and dusts• Industries handling combustible dusts
Dust Explosions According to Industry
OS PRT281 TR 6
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 19
Key Terms
• Ignition– Temperature of powder/dust exceeds
temperature of air
• Dispersion
OS PRT281 TR 7
• Dispersion– Scattering of dust into atmosphere
Key Terms
• Optimum cloud density– Sufficient distance between particles– Access to oxygen around particles
Fi
OS PRT281 TR 8
• Fire– Rapid oxidation process– 2C + O2 2CO
Key Terms
• Deflagration– Combustion reaction– Associated with vapor/dust clouds
D t ti
OS PRT281 TR 9
• Detonation– Combustion producing supersonic shockwave– Layered detonation, highly destructive
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 20
Key Terms
• Primary explosion– Initial explosion– Triggers larger explosion
S d l i
OS PRT281 TR 10
• Secondary explosion– Triggered by primary explosion
Primary/Secondary Explosion
OS PRT281 TR 11
Combustible Dust Characteristics
• Particle size• Chemical properties of dust• Moisture content
OS PRT281 TR 12
• Cloud dispersion
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 21
Combustible Dust Characteristics
General Parameters– Average minimum concentration 0.05 oz/ft3 or
50 g/m3
– Materials that ignite above 0 50 joules
OS PRT281 TR 13
Materials that ignite above 0.50 joules– Minimum ignition temp of cloud <400°C– Minimum ignition temp of 5mm layer <300°C– Minimum ignition energy of cloud <15 mJ
Ease of Dispersion
• Individual density of dust particles • Diameters• Shapes
OS PRT281 TR 14
• Cohesive properties with respect to each other
• Adhesive properties with respect to supporting surfaces
External Factors of Dispersion
• Structure/intensity of aerodynamic disturbances
• Location of dust loadingG t f f
OS PRT281 TR 15
• Geometry of surfaces
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 22
Explosion Dynamics
• Thermodynamics– Amount of heat liberated during combustion– Different types of dust generate various levels
of heat
OS PRT281 TR 16
of heat
• Kinetics– Rate at which heat is liberated during
combustion
Classification of Dust Flammability
• Class 1: no self sustained combustion• Class 2: local combustion of short duration• Class 3: local, self-sustained combustion
OS PRT281 TR 17
• Class 4: propagating, smoldering combustion
• Class 5: propagation of open flame• Class 6: explosive combustion
Health Hazards
• Death• Severe burns• Reduced visibility
OS PRT281 TR 18
• Slippery surface conditions• Respiratory hazards
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 23
History of Dust Explosions
• Farmers Export Company• Amoco Chemical Company• CTA Acoustics
OS PRT281 TR 19
• Imperial Sugar Company • CSB study• OSHA Combustible Dust SEP
Farmer’s Export Company
• December 28, 1977-Galveston, TX• Spark near grain elevator caused
explosion18 di d 35 i j d
OS PRT281 TR 20
• 18 died, 35 injured
Amoco Chemical Company
• October 21, 1980-New Castle, DE• Polypropylene unit exploded• 6 died, 100 or more injured
OS PRT281 TR 21
• Damage estimated at $45million
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 24
CTA Acoustics
• February 20, 2003-Corbin, KY• Phenolic resin powder dust accumulated• Dust ignited due to malfunctioning oven
OS PRT281 TR 22
• 7 died
Imperial Sugar Company
• February 7, 2008-Savannah, GA• Dust explosion caused by bucket elevator• Explosion occurred where sugar was
l i d
OS PRT281 TR 23
pulverized• 14 died, 38 injured• CSB Video
– http://www.chemsafety.gov/videoroom/detail.aspx?vid=30
Imperial Sugar Company
• March 7, 2008– OSHA sends letter to Imperial Sugar CEO
• Urged to eliminate combustible dust at Gramercy, LA plant
OS PRT281 TR 24
p
• March 14,2008– OSHA inspects Gramercy, LA plant
• Inspectors found combustible dust• Dust ranging from an inch to 4 ft deep
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 25
CSB Study
• Conducted in 2003• Recommended
– OSHA involvementP ti
OS PRT281 TR 25
• Prevention• Reduction in incidents
– ANSI modification• MSDS to include info on combustible dust hazards
OSHA Combustible Dust SEP
• March 2008-OSHA letter/bulletin distributed
• OSHA directives issuedOSHA’ C b tibl D t N ti l
OS PRT281 TR 26
• OSHA’s Combustible Dust NationalEmphasis Program
Next Module
OS PRT281 TR 27
Module 2: Dust Control
Combustible Dust IntroductionModule 1 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG1 - 26
© 2009, Texas Engineering Extension Service. All rights reserved.
Module
Dust Control
Instructional GuidanceTime: 60 minutes
Materials/Equipment1. Participant Manual
2. PowerPoint visuals for module 2
3. Whiteboard/markers/eraser
4. Video/data projector
5. Screen or monitor
Instructor Preparation1. Prepare projector and position first PowerPoint slide.
2. Review the module’s objectives with participants so they are aware of what they will be learning during this module.
Dust Control
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 2
Dust ControlIntroduction
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 3
Introduction
Now that combustible dust has been defined and characterized, this module will discuss ways that dust can escape and become a hazard. In addition, proper cleanup methods will be discussed.
Terminal ObjectiveUpon the successful completion of this module, the participant will be able to explain combustible dust control techniques.
Enabling ObjectivesUpon successful completion of this module, participants will be able to:1. Explain the purpose of the pressure relief valve.2. Discuss methods used to minimize dust escape.3. Discuss dust collection methods.4. Identify procedures necessary to prevent dust accumulation.
Slide 1
Slide 2
Slide 3
Dust ControlPressure Relief Valve
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 4
Pressure Relief Valve
Pressure Relief Valve (PRV)—A safety device that relieves in case of overpressure. When the set pressure is exceeded, the relief valve becomes the path of least resistance as the valve is forced open and a portion of the product is diverted through the auxiliary route.
Dust Escape
Dust EscapeDust escape can occur when raw material escapes through leaks in storage units, conveyors, and processing equipment. The escape of dust can occur during material loading or unloading and during transfer operations.
Facility DesignOne way to prevent dust escape is to design the facility for the least amount of dust escape and accumulation. One design measure is to utilize surfaces that minimize dust accumulation and facilitate cleaning. In addition, storage units, containers, elevators and chutes should be sealed. Access should be provided to all hidden areas to permit recurring inspections, especially to elevated surfaces. A very important design measure is to locate relief valves away from dust hazard areas, which could result in dust dispersion.
Equipment Integrity
Many types of equipment can generate dust while in operation. Some of the most common dust-causing equipment include the following:
• Bagging operations
• Conveyer belts
• Driers
Slide 4
Slide 5
Instructor NoteUse the following question to facilitate a discussion.
When discussing combustible dust, what are several types of equipment that are known to generate dust?
Slide 6
Dust ControlDust Collection
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 5
• Filters
• Grinders
• Mixers
• Mills
• Ovens
Maintenance of this equipment is critical to minimize the escape of dust. The equipment should be cleaned regularly and maintained to ensure proper working order. Part of equipment maintenance includes regularly checking and maintaining seals on storage units, container, elevators, and chutes.
Dust Collection
In the event of dust escape, cleaning up dust residues needs to occur at regular intervals. It only takes 1/32" of an inch accumulated dust (approximate thickness of a dime) to cause an explosion.
ONLY USE vacuum cleaners approved for dust collection to ensure that dust is not dispersed.
There are several types of dust collectors available including:
• Bag house
• Cartridge
• Cyclone
• Portable
• Wet
Bag House Dust Collector. Provides the effective collection of fine to medium-sized abrasive, sticky or curly particles, or of heavy dust loads.
Cartridge Dust Collector. Provides continuous collection and removal of airborne dust. This type of collector allows for collection of dust without shutting down the area. In addition, this type of collector can be used for a broad spectrum of industrial processes.
Slide 7
Slide 8
Dust ControlDust Accumulation Prevention
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 6
Cyclone Dust Collector. Separates and removes medium to large particles of various kinds of dust, such as wood shavings and metal grinding chips.
Portable Dust Collector. Uses an extractor arm to facilitate the extraction of dust, fume, smoke, and mist.
Wet Dust Collector. Provides for the safe collection of potentially hazardous or explosive dusts, such as aluminum, titanium, or mixed metals.
Cleanup MethodsWhen needed to cleanup dust, USE ONLY cleaning methods that do not generate dust clouds. Types of safe dust removal methods include the wet method or water removal and the use of explosion-proof, industrial vacuums.
If needing to clean a small area, cleaners like Simple Green®, Windex®, or other similar cleaner are acceptable.
Vacuum Cleaner FilterFilters should be cleaned or replaced according to the manufacturer's instructions. There are also explosion-proof vacuums designed with maintenance-free filters.
Dust Accumulation Prevention
There are several critical steps to prevent dust accumulation. The first is to develop and implement a hazardous dust inspection. Hidden areas and equipment need to be thoroughly checked for dust. Once dust is collected, the dust should be tested to identify if it is considered combustible.
The next step is to develop and implement a housekeeping plan to prevent dust accumulation.
Instructor NoteWhen viewing powerpoint slide 10, take a moment to discuss the Cyclone Dust Collector Control animation.
Slides 9-10
Slide 11
Slide 12
Slide 13
Dust ControlDust Accumulation Prevention
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 7
The last step is to maintain the control program on a continuous basis. This program needs to be in writing and should establish frequency and methods of dust accumulation prevention.
ALWAYS be vigilant! Inspections are critical when the weather is cold and humidity is low. Low humidity levels make dust particularly easy to disperse and ignite. For examples, of eight catastrophic dust explosions since 1995, all but one occurred during cold weather months, with four occurring in February alone.
When needed to cleanup dust, only use cleaning methods that do NOT generate dust clouds. Types of safe dust removal methods include the wet method or water removal and the use of explosion-proof, industrial vacuums.
Instructor NoteUse the following question to facilitate a discussion.
When discussing the development of housekeeping plans, what are several items/areas that should be routinely cleaned or inspected?
Slide 13
Dust ControlApplication of Participants’ Knowledge/Skills
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 8
Application of Participants’ Knowledge/Skills
Participants will apply their knowledge by answering review questions at the end of the module.
Evaluation of Participants
Evaluation is based on participants’ active participation in class discussions and responses to review questions at the end of the module.
Summary
In order to be able to control dust in a facility, it is important to understand how dust accumulates and how to plan and implement a dust control program. This module discussed how dust escapes from equipment and accumulates on surfaces. It also described the steps to take to prepare a dust control program. The next module will discuss how to keep ignition of dust under control.
Slide 14
Dust ControlModule 2 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 9
Module 2 Review Questions
Directions: Circle the letter of the best answer.
1. A ________ is a safety device that relieves in case of overpressure.(2-3)
a. pressure relief valve
b. bag house dust collector
c. cartridge dust collector
d. portable dust collector
e. wet dust collector
2. Dust escape can occur when ________. (2-3)
a. raw material leaks through leaks or cracks
b. loading, unloading, or transferring of material is taking place
c. storage units are not properly sealed
d. All of the above
3. Which of the following is crucial in the design of a facility to prevent combustible dust incidents? (2-3)
a. Utilizing surfaces that maximize dust accumulation
b. Storage units, containers, elevators, and chutes need to remain open
c. Providing access to all hidden areas
d. Locate relief valves near dust hazard areas
4. ONLY USE vacuum cleaners approved for dust collection to ensure that dust is not dispersed. (2-4)
a. True
b. False
5. If dust escapes, use cleanup methods that do not generate dust clouds, such as ________. (2-6)
a. Airing out the facility
b. Water removal/Wet method
c. Blower fans
d. None of the above
Dust ControlModule 2 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 10
Dust ControlModule 2 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 11
Module 2 PowerPoint Slides
Module 2
OS PRT281 TR 1
Dust Control
Terminal Objectives
Upon the successful completion of this module, participants will be able to explain combustible dust control techniques.
OS PRT281 TR 2
Enabling Objectives
• Explain the purpose of the pressure relief valve.
• Discuss methods used to minimize dust escape
OS PRT281 TR 3
escape.• Discuss dust collection methods.• Identify procedures necessary to prevent
dust accumulation.
Dust ControlModule 2 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 12
Pressure Release Valve
• PRV• Safety device• Releases in case of overpressure
OS PRT281 TR 4
Dust Escape and Accumulation-Design
• Utilize surfaces that minimize dust accumulation
• Utilize surfaces that facilitate cleaningP id t hidd
OS PRT281 TR 5
• Provide access to hidden areas• Locate PRVs away from dust hazard areas
Dust Escape and Accumulation-Equipment Integrity
• Dust generating equipment• Maintenance of equipment is critical • Clean equipment regularly
OS PRT281 TR 6
Dust ControlModule 2 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 13
Dust Collection
• Cleanup dust at regular intervals• ONLY USE approved vacuum cleaners
– Bag house C t id
OS PRT281 TR 7
– Cartridge– Cyclone– Portable– Wet
Dust Collection
• Bag House– Effective on abrasive, sticky or curly particles– Effective with heavy dust loads
C t id
OS PRT281 TR 8
• Cartridge– Continuous collection/removal of airborne
dust– Allows collection without shutting down– Used on broad spectrum of industrial
processes
Dust Collection
• Cyclone– Separates/removes medium to large particles
• PortableU t t t f ilit t l
OS PRT281 TR 9
– Uses extractor arm to facilitate removal
• Wet – Safe collection of hazardous/explosive dusts
Dust ControlModule 2 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 14
Cyclone Dust Control
OS PRT281 TR 10
Cleanup Methods
• Use methods that do not generate dust clouds
• Safe removal methodsW t th d/ t l
OS PRT281 TR 11
– Wet method/water removal– Explosion-proof industrial vacuum
• Small areas may be wiped clean
Vacuum Cleaner Filter
• Clean/replace according to manufacturer’s instructions
• Maintenance-free filters
OS PRT281 TR 12
Dust ControlModule 2 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 15
Dust Accumulation Prevention
1. Implement hazardous dust inspection2. Implement housekeeping plan3. Implement control program
OS PRT281 TR 13
– Written plan– Establish frequency and methods
Next Module
OS PRT281 TR 14
Module 3: Ignition Control
Dust ControlModule 2 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG2 - 16
© 2009, Texas Engineering Extension Service. All rights reserved.
Module
Ignition Control
Instructional GuidanceTime: 60 minutes
Materials/Equipment1. Participant Manual
2. PowerPoint visuals for module 3
3. Whiteboard/markers/eraser
4. Video/data projector
5. Screen or monitor
Instructor Preparation1. Prepare projector and position first PowerPoint slide.
2. Review this module’s objectives with participants so they are aware of what they will be learning during this module.
Ignition Control
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 2
Ignition ControlIntroduction
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 3
Introduction
Similar to any fire, there are certain elements that must exist for a dust explosion to occur. These elements, with a focus on ignition sources, will be discussed in this module.
Terminal ObjectiveUpon successful completion of this module, the participant will be able to explain the work procedures for controlling ignition.
Enabling ObjectivesUpon successful completion of this module, participants will be able to:1. Identify the five elements present in a dust explosion.2. Identify ignition sources.3. Discuss hot work permits and Lockout/Tagout (LOTO).4. Discuss use of separator devices.5. Identify classifications applicable to combustible dust contained in
the National Electric Code (NEC).
Slide 1
Slide 2
Slide 3
Ignition ControlFive Elements for Dust Explosions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 4
Five Elements for Dust Explosions
In addition to the three basic elements of the Fire Triangle (oxygen, fuel and ignition) that must be present for a fire or explosion to occur, dust explosions require a total of five elements, turning the fire triangle into a fire pentagon. These five elements include the following:
• Combustible dust in fine particles
• Oxygen
• Dust dispersed into air
• Energy source to ignite mixture
• Confinement (walls, ceilings, floors, roofs, process equipment, ducting)
The standard fire triangle contains three components: fuel, ignition, and oxygen. The combustible dust components also include fuel, ignition, and oxygen but add confinement and dispersion. So instead of a triangle, combustible dust explosions are best represented by a pentagon, Figure 3.1.
Figure 3.1: Fire Triangle vs. Fire Pentagon
Instructor NoteWhen viewing powerpoint slide 6, take a moment to discuss the Traingle and Pentagon animation. To start the animation please click the PLAY button.
Please remind participants about the necessary addition of 2 components for a combustible dust explosion.
Slide 4
Slides 5-6
Ignition ControlIgnition Sources
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 5
Ignition Sources
Definition of an Ignition SourceAn ignition source is anything that can deliver enough energy in the form of heat to ignite a substance. Examples include the following:
• Static electricity
• Hot surfaces
• Open flame or embers
• Electric arcs and sparks
• Industrial trucks
• Powder actuated tools
• Smoldering nests
• Heat from accidental mechanical impact
Static ElectricityStatic electricity is defined as an electrical charging of materials through physical contact and separation, and the positive and negative electrical charges formed by this process.
When dealing with static electricity, if the process is not or cannot be properly grounded then the charge may build up to the point where it will discharge with a static arc. This discharge may provide an ignition source to any nearby mixture of dust and air.
Slide 7
Slide 8
Instructor NoteWhen viewing powerpoint slide 10, take a moment to discuss the Static Electricity animation.
During this time please review the definition of static electricity.
Slides 9-10
Ignition ControlIgnition Sources
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 6
Hot SurfacesAny surface that exceeds the minimum auto-ignition temperature is considered a hot surface. When a hot surface has a layer of combustible dust, then the combination of the two may cause ignition. Combustible liquids can often mix with dust layers that are on a hot surface, providing another source of ignition. Combustible liquids include lubricants and oils often necessary for equipment to operate.
Open Flame or Glowing EmberIt is critical to eliminate ALL open flames or embers. These sources may not be evident and include the following:
• Candles
• Smoking
• Sterno Heaters
• Flares
• Strike anywhere matches
• Single-action lighter
• Furnaces
Electric Arcs and SparksAn electric arc is a continuous discharge of a current formed when a strong current jumps a gap in a circuit or between two electrodes. In comparison, a spark is a random, momentary discharge.
Industrial TrucksA motor vehicle, such as an industrial truck, can create a spark when the engine is engaged. There are several ways for this spark to occur:
• Starter
• Combustion
• Backfire
There is an additional hazard with diesel engines. Gases can be sucked into a diesel engine, which makes shutting off the engine impossible.
Slide 11
Slide 12
Slide 13
Slide 14
Ignition ControlHot Work Permits and Lockout/Tagout
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 7
Powder Actuated ToolsThese types of tools provide a spark when a bullet is fired. In addition, the concussion caused from the firing of the tool can shake dust loose.
Smoldering NestsA smoldering nest is a collection of material that is in a dust environment and can smolder from a chemical or biological reaction. An example is sewage sludge that has a reaction that produces heat and smolders. This smoldering material is located near combustible dust. The dust is disturbed and the area and ignites.
Accidental Mechanical ImpactAccident mechanical impact can occur in rotating equipment when repeated impact gives rise to a hot spot. If this equipment contains materials that can produce a spark, like titanium and some aluminums, then a spark can occur.
Hot Work Permits and Lockout/Tagout
A permit MUST BE obtained prior to any hot work such as:
• Welding
• Brazing
• Cutting
• Grinding
• Soldering
When combustible material within a 35-foot radius of hot work cannot be removed, flame retardant tarps are used to cover materials.
Floors and surfaces within the 35-foot radius of a hot work area must be completely free of any combustibles including dust. And all openings or cracks in walls, floors, or ducts must be covered.
Lockout and Tagout (LOTO) is used on equipment to prevent sparks from activating switches or breakers. Using these procedures eliminates any change of an accidental ignition source from occurring.
Slide 15
Slide 16
Slide 17
Slide 18
Slide 19
Ignition ControlSeparator Devices
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 8
LOTO procedures are designed to prevent unintentional or accidental operation of equipment or electrical circuits that may provide an ignition source. Locking out requires a lock that physically prevents the switch, breaker or other device from being activated. The tagout of the system is important and includes the person locking the equipment and other important conditions of the LOTO.
Separator Devices
These devices remove foreign materials capable of igniting combustible dusts. When using an air separation device, an explosion isolation device must be installed on return air lines to prevent an explosion.
Intrinsically Safe DevicesAn Intrinsically Safe (IS) device contains equipment and wiring that is incapable of releasing sufficient electrical or thermal energy under normal or abnormal conditions to cause the ignition of a specific hazardous atmospheric mixture in its most easily ignited concentrated.
For example, mining operations use intrinsically safe air-conditioning devices to supply air, but do not create enough energy to be considered an ignition source.
Other examples include the following:
• Infrared temperature sensors
• LED indicating lights
• Magnetic pickup flowmeters
• Pressure, flow, and level switches
• Potentiometers
• Proximity switches
• Solenoid valves
Instructor NoteUse the following question to facilitate a discussion.
What are some common separator devices used within various industries?
Slide 20
Slide 21
Ignition ControlNational Electric Code
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 9
• Strain gauges
• Telephones and radios
• Thermocouples
Explosion Proof DevicesThese devices should be used on the following:
• Light fixtures
• Engine switches
• Pumps
• Motors
• Other equipment that may be placed in hazardous areas
This explosion-proof technology should be the sole option only when an IS-rated device is unavailable. An IS device may not be an option on a pump with a large motor that is of a size that it cannot be made intrinsically safe.
National Electric Code
The National Electric Code (NEC) is a U.S. standard for safe installation of electrical wiring and equipment. These standards are part of the National Fire Codes series published by the National Fire Protection Association (NFPA) and are commonly mandated by state or local law. These standards were first published in 1897 and are updated every three years. The most recent issue was published in 2008.
NEC Classification–Article 500Article 500 of the National Electric Code (NEC) defines area classification based on Classes, Groups, and Divisions.
The Class designates the type of flammable substance that may be present in an area, such as gas vs. dust.
The Group further defines the Class by designating the specific substance that may be present such as, acetylene vs. hydrocarbon.
The Division designates the likelihood of the flammable substance being present.
Slide 22
Slide 23
Slide 24
Ignition ControlNational Electric Code
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 10
NEC Classification–Groups E, F, and GWithin Class II Dusts, there are three groups: E, F, and G.
Group E. Atmospheres containing combustible metal dusts such as: Aluminum, Chromium Ferromanganese, Iron, Manganese, and Magnesium.
Group F. Atmospheres containing combustible carbonaceous dusts. These dusts have more than 8% total entrapped volatiles or have been sensitized by other materials so that they present an explosion hazard. These include Coal, Carbon Black, Charcoal, Pitch, and Coke Dust.
Group G . Atmospheres containing other combustible dusts such as Flour, Grain, Wood Flour, Plastic, and Chemicals.
Slide 25
Ignition ControlApplication of Participants’ Knowledge/Skills
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 11
Application of Participants’ Knowledge/Skills
Participants will apply their knowledge by answering review questions at the end of the module.
Evaluation of Participants
Evaluation is based on participants’ active participation in class discussions and responses to review questions at the end of the module.
Summary
Eliminating ignition sources from a combustible dust area is key to preventing an explosion. An often-overlooked source is an ignition source outside of the immediate area that still has access to the area through a venting system, ductwork, or other route. All ignition sources, where in the immediate area or connected to the combustible dust area, must be eliminated.
Slide 26
Ignition ControlSummary
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 12
Ignition ControlModule 3 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 13
Module 3 Review Questions
Directions: Circle the letter of the best answer.
1. The shape that best represents the elements of combustible dust explosions is a ________. (3-4)
a. square
b. triangle
c. pentagon
d. hexagon
2. Possible ignition sources include all of the following EXCEPT: (3-5)
a. Static electricity
b. Dented surface
c. Open flame or embers
d. Electric arcs and sparks
3. Which of the following is an example of open flame or flowing ember ignition source? (3-6)
a. Smoking
b. Flares
c. Furnaces
d. All of the above
4. Combustible materials must be moved far away from hot work zone. How far away from the hot zone should materials be moved? (3-7)
a. 15-foot
b. 35-foot
c. 55-foot
d. 75-foot
Ignition ControlModule 3 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 14
5. Lockout/Tagout is used to perform what function? (3-8)
a. Inform workers what circuits to operate
b. Prevent activation of equipment or electrical circuits that can cause injury or provide an ignition source.
c. Keep personal items secure
d. Protect high security areas
6. In the case where a pump with a large motor is of a size that cannot be made intrinsically safe, explosion-proof equipment and practices would be mandatory. (3-9)
a. True
b. False
7. The ________ is a U.S. standard for safe installation of electrical wiring and equipment. (3-9)
a. CSB
b. SEP
c. NEC
d. CTA
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 15
Module 3 PowerPoint Slides
Module 3
OS PRT281 TR 1
Ignition Control
Terminal Objectives
Upon the successful completion of this module, participants will be able to explain the work procedures for controlling ignition.
OS PRT281 TR 2
Enabling Objectives
• Identify the five elements present in a dust explosion.
• Identify ignition sources.• Discuss hot work permits and Lockout/Tagout
OS PRT281 TR 3
Discuss hot work permits and Lockout/Tagout(LOTO).
• Discuss use of separator devices.• Identify classifications applicable to combustible
dust contained in the National Electric Code (NEC).
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 16
5 Elements for Dust Explosion
• Combustible dust in fine particles• Oxygen• Dust dispersed into air
OS PRT281 TR 4
• Energy source to ignite mixture• Confinement
Triangle and Pentagon
OS PRT281 TR 5
Triangle and Pentagon
OS PRT281 TR 6
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 17
Ignition Sources
• Anything that delivers enough energy for ignition
• ExamplesSt ti l t i it
OS PRT281 TR 7
– Static electricity– Hot surface– Open flame or ember– Electric arcs and sparks
Ignition Sources
• Examples– Industrial trucks– Powder actuated tools
Smoldering nests
OS PRT281 TR 8
– Smoldering nests– Heat from accidental mechanical impact
Static Electricity
• Electrical charging of materials• Charging through physical contact• Properly ground to prevent discharge
OS PRT281 TR 9
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 18
Static Electricity
OS PRT281 TR 10
Hot Surfaces
• Any surface that exceeds min. auto-ignition temperature
• Combustible dust/liquids on hot surfaceC b tibl li id
OS PRT281 TR 11
• Combustible liquids– Lubricants– Oils
Open Flame/Glowing Ember
• Eliminate all open flames or embers• Potential sources
– CandlesS ki
OS PRT281 TR 12
– Smoking– Flares– Matches/lighters– Furnances
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 19
Electric Arcs and Sparks
• Electric Arc– Continuous discharge of a current– formed when strong current jumps gap
S k
OS PRT281 TR 13
• Spark– Random, momentary discharge
Industrial Trucks
• Creates spark when engine engaged• Spark can occur in
– StarterC b ti
OS PRT281 TR 14
– Combustion– Backfire
• Diesel engine– Gases sucked in/shutoff not possible
Powder Actuated Tools
• Provides spark when bullet is fired• Concussion from firing can shake dust
loose
OS PRT281 TR 15
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 20
Smoldering Nests
• Collection of material in dust environment• Material can smolder• Chemical/biological reaction
OS PRT281 TR 16
Accidental Mechanical Impact
• Can occur in rotating equipment• Repeated impact creates hot spots• Spark can occur if material is capable
OS PRT281 TR 17
– Titanium– Some aluminums
Hot Work
• Obtain permit PRIOR to hot work• Combustible material
– If possible remove all materialR t id 35 f t di
OS PRT281 TR 18
– Remove outside 35-foot radius– Cover with flame retardant tarps if unmovable
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 21
Electrical Lockout/Tagout
• Used to prevent sparks• Eliminates accidental ignition
OS PRT281 TR 19
Separator Devices
• Removes foreign materials capable of igniting dust
• Isolation device must be installedWh i i ti i d i
OS PRT281 TR 20
– When using air separation air device– Install on return air lines
Intrinsically Safe Devices
• Equipment/wiring incapable of releasing sufficient energy to cause ignition
• ExamplesP fl d l l it h
OS PRT281 TR 21
– Pressure, flow, and level switches– Solenoid valves– thermocouples
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 22
Explosion Proof Devices
• Use explosion proof devices– Light fixtures– Engine switches
Pumps/motors
OS PRT281 TR 22
– Pumps/motors
• Sole option when IS-rated device is unavailable
National Electric Code
• Standard for safe installation of electrical wiring/equipment
• Part of National Fire Codes1 t bli h d i 1897
OS PRT281 TR 23
• 1st published in 1897• Updated every 3 years
National Electric Code
• NEC Classification-Article 500– Class: designates type of flammable
substance– Group: designates specific substances
OS PRT281 TR 24
Group: designates specific substances– Division: designates likelihood of flammable
substances
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 23
National Electric Code-Class II Dusts
• Group E: combustible metal dusts• Group F: combustible carbonaceous dusts• Group G: other combustible dusts
OS PRT281 TR 25
Next Module
OS PRT281 TR 26
Module 4: Support Systems
Ignition ControlModule 3 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG3 - 24
© 2009, Texas Engineering Extension Service. All rights reserved.
Module
Support Systems
Instructional GuidanceTime: 60 minutes
Materials/Equipment1. Participant Manual
2. PowerPoint visuals for module 4
3. Whiteboard/markers/eraser
4. Video/data projector
5. Screen or monitor
Instructor Preparation1. Prepare projector and position first PowerPoint slide.
2. Review the module’s objectives with participants so they are aware of what they will be learning during this module.
Support Systems
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 2
Support SystemsIntroduction
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 3
Introduction
Just as important as a combustible dust program is having the support for one. Support comes in different forms, and these forms will be discussed in this module.
Terminal ObjectiveUpon the successful completion of this module, participants will be able to explain methods organizations may use to reinforce combustible dust safety.
Enabling ObjectivesUpon successful completion of this module, the participant will be able to:1. Discuss four organizational support systems.2. Explain how a documentation system may be used to support safety
efforts.
Slide 1
Slide 2
Slides 3
Support SystemsOrganizational Support
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 4
Organizational Support
Plant Personnel SupportA critical aspect of any program is to ensure that everyone is trained properly prior to working in a hazardous environment. Initial training needs to include specific topics directly related to combustible dust hazards. Training should also include how to use Material Safety Data Sheets (MSDS) once it is verified that the MSDS are current and thorough.
In addition, training needs to include how to respond to combustible dust incidents. This training not only needs to be specific to combustible dust, but this training should be refreshed and redelivered on a periodic basis and should be up-to-date on any new regulations and policies.
Management Support SystemManagement plays a key role in any successful combustible dust program. Any substantial efforts of training and safety begin at this level. Management can begin by ensuring that the proper and approved cleaning equipment is available for use. Management should also initiate and monitor a regular cleaning program and openly support combustible dust training initiatives.
Engineering Support SystemEngineering has a huge impact on the prevention and mitigation of combustible dust explosions.
In the design phase, engineering should allow access to hidden areas around equipment, design combustible dust-producing areas that are separated, blast-proof, and resistant. In addition, the use of intrinsically safe and explosion-proof devices needs to be incorporated into the design.
Instructor NoteUse the following question to facilitate a discussion.
In today’s current industries, are employees being effectively trained on the hazards of combustible dust?
Slide 4
Slide 5
Slide 6
Support SystemsDocumentation Systems
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 5
During damage control construction efforts, engineering should evaluate the level of pressure resistance, relieving, and venting in the combustible dust areas. A thorough review of relief valve placement, detection systems, and extinguishing systems may reveal that improvements are needed.
Operations Support SystemOperations also plays an important part in any combustible dust program. Good housekeeping is very important wherever any combustible materials are used. These areas should be clear of burnable materials, and liquid spills need to be cleaned up immediately.
Another way that operations plays an important role is to report any malfunctioning equipment to maintenance immediately.
In the day-to-day operations, the elimination of ignition sources reduces the probability of a combustible dust incident.
Maintenance Support SystemsRegular equipment inspection and maintenance are important for controlling hazards of flammable and combustible materials.
Maintenance personnel must carry out repairs to equipment promptly and properly, making note of special equipment, like explosion-proof fittings.
Past incidents show that fires and explosions have resulted from the addition of non-approved parts or equipment to approved systems when maintenance was being performed.
Documentation Systems
A documentation system is critical to the success of a combustible dust program. All of the support systems of a facility contribute data to the documentation system. Any time data is being collected and recorded, it is necessary, and may be required to maintain all documentation related to that data.
Slide 7
Slide 8
Slide 9
Instructor NoteUse the following question to facilitate a discussion.
What are some common documentation systems used within various industries?
Slide 10
Support SystemsDocumentation Systems
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 6
A documentation systems allows for the following:
• Program review (for internal or OSHA audits): by entering checklists and items into a documentation system, audits for internal review can be performed, and results documented.
• Employee participation efforts: One of the fourteen PSM elements is employee participation. Using a documentation system is one way of keeping employees involved in the combustible dust program, as well as fulfilling the PSM requirement.
• Data backup (back up electronic information)
• Easy retrieval of information
Slide 10
Support SystemsApplication of Participants’ Knowledge/Skills
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 7
Application of Participants’ Knowledge/Skills
Participants will apply their knowledge by answering review questions at the end of the module.
Evaluation of Participants
Evaluation is based on participants’ active participation in class discussions and responses to review questions at the end of the module.
Summary
Everyone in the organization plays a role in preventing combustible dust explosions. This commitment to safety needs to be unified and visible throughout the organization. A zero-tolerance approach should always be the standard when dealing with safety issues, especially those related to combustible dust.
Slide 11
Support SystemsSummary
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 8
Support SystemsModule 4 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 9
Module 4 Review Questions
Directions: Circle the letter of the best answer.
1. All plant personnel must ________. (4-4)
a. be aware of combustible materials used in plant
b. be aware of necessary response to combustible dust incidents
c. attend combustible dust training
d. all of the above
2. Engineering has a huge impact on combustible dust prevention by all of the following EXCEPT: (4-4)
a. Allowing hidden areas
b. Designing combustible dust producing areas to be blast-proof and resistant
c. Using intrinsically safe and explosion-proof devices in design
d. Placing relief valves away from combustible dust areas
3. A documentation system is critical to the success of a combustible dust program. (4-5)
a. True
b. False
Support SystemsModule 4 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 10
Support SystemsModule 4 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 11
Module 4 PowerPoint Slides
Module 4
OS PRT281 TR 1
Support Systems
Terminal Objectives
Upon the successful completion of this module, participants will be able to explain methods organizations may use to reinforce combustible dust safety
OS PRT281 TR 2
combustible dust safety.
Enabling Objectives
• Discuss four organizational support systems.
• Explain how a documentation system may be used to support safety efforts
OS PRT281 TR 3
be used to support safety efforts.
Support SystemsModule 4 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 12
Plant Personnel Support
• Properly train personnel for any hazardous environment
• TrainingS ifi t i l t d t b tibl d t
OS PRT281 TR 4
– Specific topics related to combustible dust– Use of MSDS– Incident response– Review/refresh on periodic basis
Management Support System
• Key in successful combustible dust program
• Training effortsS f t ff t
OS PRT281 TR 5
• Safety efforts• Ensures proper/regular cleaning
Engineering Support System
• Prevention/mitigation of combustible dust explosions
• Design phaseA t hidd
OS PRT281 TR 6
– Access to hidden areas– Dust producing areas separated/blast proof– Use of intrinsically safe/explosion proof
devices
Support SystemsModule 4 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 13
Engineering Support System
• Damage control– Evaluate level of pressure resistance– Relief/venting in dust areas
Pressure relief valve placement
OS PRT281 TR 7
– Pressure relief valve placement– Detection systems– Extinguishing systems
Operations Support System
• Good housekeeping• Report/maintenance of malfunctioning
equipmentEli i ti f i iti
OS PRT281 TR 8
• Elimination of ignition sources
Maintenance Support System
• Regular inspection/maintenance• Prompt/proper maintenance• Documentation of equipment
OS PRT281 TR 9
• Ensure use of approved parts/equipment
Support SystemsModule 4 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG4 - 14
Documentation System
• Maintain documentation• Allows for program review• Allows for employee participation
OS PRT281 TR 10
• Provides data backup• Easy retrieval
Next Module
OS PRT281 TR 11
Module 5: Damage Control
© 2009, Texas Engineering Extension Service. All rights reserved.
Module
Damage Control
Instructional GuidanceTime: 60 minutes
Materials/Equipment1. Participant manual
2. PowerPoint visuals for module 5
3. Whiteboard/markers/eraser
4. Video/data projector
5. Screen or monitor
Instructor Preparation1. Prepare projector and position first PowerPoint slide.
2. Review this module’s objectives with participants so they are aware of what they will be learning during this module.
Damage Control
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 2
Damage ControlIntroduction
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 3
Introduction
The saying "plan for the worst, but hope for the best" definitely should be applied when it comes to preparing for a safety incident such as a dust explosion. This module will discuss systems that need to be in place to guard against a catastrophic event due to combustible dust.
Terminal ObjectiveUpon successful completion of this module, participants will be able to describe methods used to prevent or control damage from a combustible dust explosion.
Enabling ObjectivesUpon successful completion of this module, the participant will be able to:1. Discuss types of damage control systems.2. Discuss emergency response planning.
Slide 1
Slide 2
Slide 3
Damage ControlDamage Control Systems
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 4
Damage Control Systems
A damage control system is any system used for monitoring, suppressing, and eliminating dust.
There are various types of systems that can be used in a combustible dust area. These include:
• Spark ember detection
• Extinguishing
• Hazards separation
• Hazard segregation
• Deflagration venting
• Pressure relief venting
• Specialized fire suppression
Spark Ember DetectionThis type of system can eliminate early causes of fires or dust explosions by detecting spark or ember IR radiation.
Spark ember detection systems are primarily used as a fire prevention method in dust collectors and where pneumatic conveying systems are used. When a spark or ember is detected, the system automatically activates programmable countermeasures such as the following:
• Deluge valves
• Abort gates
• Alarm systems
Instructor NoteUse the following question to facilitate a discussion.
What are several common damage control systems used within today’s industries?
Slide 4
Slides 5-6
Damage ControlDamage Control Systems
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 5
• Automatic machinery shutdown
• Extinguishing devices
Extinguishing SystemWhen an extinguishing system is triggered, it immediately releases a fine mist of water downstream. Sparks and embers are extinguished without interrupting production. This type of system greatly reduces the risk of personnel injury, equipment damage, and downtime.
Hazard SeparationThis system is one that is best considered during the design of the facility or during a remodel. The hazard separation system isolates the combustible dust hazard by putting distance between combustible dust areas. By separating volatile areas, the risk of turning a bad situation into a catastrophic one is minimized.
Hazard SegregationIf putting distance between areas is not an option, a hazard segregation system may be an option. This system isolates the hazard by placing a barrier between combustible dust areas. By doing this, special protection measures can be implemented without burdening the entire plant or building.
Deflagration VentingThe deflagration venting system controls damage caused by explosions. When an explosion occurs, the vents release expanding gases through openings thereby reducing pressure below the level that would cause damage.
Pressure Relief VentingPressure relief venting follows the same premise as deflagration venting. It provides pressure relief for equipment, such as storage tanks and low pressure vessels, to prevent an explosion from occurring.
Slide 7
Slide 8
Slide 9
Instructor NoteWhen viewing powerpoint slide 11 and 12, take a moment to discuss the Explosion without Venting and Explosion with Venting animation. At this time review the differences between the two explosions, noting the benefits of deflagration venting.
Slides 10-12
Slides 13-14
Damage ControlDamage Control Systems
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 6
Specialized Fire Suppression Systems
Sprinklers
One of the most standard forms of fire suppression systems is the sprinkler system. A series of water pipes are supplied by a reliable water supply. Each sprinkler head is independent, heat-activated, and responsible for water distribution during a fire.
Carbon Dioxide
Water can be damaging to electronic equipment. The Carbon Dioxide CO2 system should be used in areas where there is sensitive electronic equipment since the CO2 will not normally cause damage to this type of equipment.
This system extinguishes fire by reducing the oxygen content below the point where it can support combustion. The system is supplied by CO2 stored in high pressure cylinders or low pressure CO2 tanks.
Dry Powder Extinguishers
Standard or multi-purpose dry powder fire extinguishers are safe to use on most kinds of fires (Class A, B, and C). Some examples of these types of fires are those caused by oil, fat, paint, solvents, grease, propane, butane, natural gas, or electrical equipment.The effect of the powder is to knock down the flames. These extinguishers are best for fires involving flammable liquids or gases. Standard powders work well only on burning liquids, however the multi-purpose type is more effective on other types of fire, especially on burning solids.
Deluge Foam
The deluge foam system is connected to a water supply through a deluge valve. This valve is opened by the operation of a smoke or heat detection system.
This type of system should be used in high hazard areas, such as chemical storage or processing facilities needing high velocity suppression.
Slide 15
Slide 16
Slide 17
Damage ControlEmergency Response Planning
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 7
Emergency Response Planning
Detailed planning must be done for the following dust explosion events:
• Pre-explosion
• Dust explosion
• Post-explosion
A fire, in its beginning or incipient stage, can be controlled with portable fire extinguishers, Class II standpipe systems, and small hose systems.
Pre-explosionPrior to an explosion ever occurring, develop an Emergency Action Plan (EAP) with special consideration for combustible dust.
Dust ExplosionIf a dust explosion occurs, evacuate the area immediately and initiate the Emergency Action Plan.
An incipient fire can initiate dust explosion even if the fire is of some distance from the combustible dust area. Ignited materials can travel through process equipment far from the ignition source until it reaches the combustible cloud.
Even though an incipient fire can initiate dust explosions, these types of explosion are not incipient. Incipient fire brigades are not trained to fight dust explosion fires and cannot use hose streams to fight these types of fires. In addition, these brigades typically have little or no personal protective equipment (PPE).
Dust explosions are categorized as a fully involved fire that prompts a fire department response. These departments have the necessary specialized training required to fight involved fires.
Post ExplosionAfter the explosion hazard has passed and the fires are extinguished, initiate an investigation as soon as the area is safe.
Unfortunately, combustible dust fires and explosion destroy much of the evidence necessary for the investigation.
Slide 18
Slide 19
Slides 20-21
Slides 22-24
Damage ControlEmergency Response Planning
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 8
It is difficult to determine what causes a combustible dust explosion. It is estimated that a cause for the explosion is determined in only 50% of the dust explosion cases. However, any dust samples that can be collected should be gathered for analysis.
After an incident, the working environment at the plant will change. The community and regulatory industries will have a renewed interest in the facility.
Having the proper person or people chosen to speak to the public is a necessity. Internally, facility personnel will have a perceived risk of elevated hazard. There may even be displayed fear from personnel who are apprehensive about returning to their work areas.
Communications from the organization is strongly recommended. There may also be a strong push to rebuild and resume operations. Getting personnel back to work and manufacturing back online is important not only monetarily, but also psychologically. However, EHS personnel, along with the facility management, are the ones to decide when to resume normal operations.
A different focus needs to be placed on rebuilding equipment and facilities once thought to be safe but still led to a dust explosion. Theories and solution may be numerous and varied, so strong leadership and direction will be needed to recover.
Damage ControlApplication of Participants’ Knowledge/Skills
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 9
Application of Participants’ Knowledge/Skills
Participants will apply their knowledge by answering review questions at the end of the module.
Evaluation of Participants
Evaluation is based on participants’ active participation in class discussions and responses to review questions at the end of the module.
Summary
Planning for the worst beforehand could save lives and reduce injuries to employees, neighbors to the facility, and the facility itself. No one wants to think about the worst actually occurring, but doing so allows the organization to be ready in the event of a combustible dust explosion.
Slide 25
Damage ControlSummary
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 10
Damage ControlModule 5 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 11
Module 5 Review Questions
Directions: Circle the letter of the best answer.
1. The following is an example of a damage control system: (5-4)
a. Spark ember detection
b. Hazard segregation
c. Deflagration venting
d. All of the above
2. A deluge fire suppression system is used in places considered to be a high hazard area, such as chemical storage. (5-6)
a. True
b. False
3. Which is a key emergency response activity that must be performed prior to an explosion occurring? (5-7)
a. Being familiar with response measures and where response tools are located
b. Developing an EAP
c. Being familiar with emergency rescue procedures
d. All of the above
4. Determining the cause of a combustible dust explosion is only achieved in about ________ of cases. (5-8)
a. 10%
b. 25%
c. 50%
d. 75%
Damage ControlModule 5 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 12
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 13
Module 5 PowerPoint Slides
Module 5
OS PRT281 TR 1
Damage Control
Terminal Objectives
Upon the successful completion of this module, participants will be able to describe methods used to prevent or control damage from a combustible dust explosion
OS PRT281 TR 2
from a combustible dust explosion.
Enabling Objectives
• Discuss types of damage control systems.• Discuss emergency response planning.
OS PRT281 TR 3
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 14
Damage Control Systems
• Monitoring/suppressing/eliminating dust• Various types of systems
– Spark ember detectionE ti i hi
OS PRT281 TR 4
– Extinguishing– Hazards separation/segregation– Deflagration venting– Pressure relief venting– Specialized fire suppression
Spark Ember Detection
• Eliminate early causes of fires/explosions• Detects spark/ember IR radiation• Fire prevention method
OS PRT281 TR 5
– Dust collectors– Pneumatic conveying systems
Spark Ember Detection
• System activates countermeasures– Deluge valves– Abort gates
Alarm systems
OS PRT281 TR 6
– Alarm systems– Automatic machinery shutdown– Extinguishing devices
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 15
Extinguishing System
• Releases fine mist of water• Sparks/embers extinguished without
interrupting productionG tl d
OS PRT281 TR 7
• Greatly reduces– Personnel injury– Equipment damage– Downtime
Hazard Separation
• Isolates combustible dust hazard• Puts distance between dust and hazard• Implement system during
d i / d li
OS PRT281 TR 8
design/remodeling
Hazard Segregation
• Used when separation is not possible• Isolates hazard by using a barrier• Implementation without burdening entire
l t/b ildi
OS PRT281 TR 9
plant/building
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 16
Deflagration Venting
• Controls damage caused by explosions• Vents release expanding gases• Gases reduce pressure below danger
l l
OS PRT281 TR 10
levels
Explosion Without Venting
OS PRT281 TR 11
Explosion Venting
OS PRT281 TR 12
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 17
Pressure Relief Venting
• Same premise as deflagration venting• Provides pressure relief to prevent
explosions
OS PRT281 TR 13
Pressure Relief Venting
OS PRT281 TR 14
Specialized Fire Suppression Systems
• Sprinklers– Most standard form of fire suppression– Heat activated
C b Di id
OS PRT281 TR 15
• Carbon Dioxide– Will not damage electronic equipment– Reduces oxygen levels
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 18
Dry Powder Extinguishers
• Standard/Multi-purpose– Safe for most kinds of fires
• “Knocks down” the flamesf f h fl bl l d /
OS PRT281 TR 16
• Best for fires with flammable liquids/gases
Deluge Foam
• System is connected to a water supply– Valve opened by smoke/heat detection
system
• Used in high hazard areas
OS PRT281 TR 17
• Used in high hazard areas– Chemical storage– Processing facilities
Emergency Response Planning
• Requires detailed planning• 3 phases of planning
1. Pre-explosion2 D t l i
OS PRT281 TR 18
2. Dust explosion3. Post explosion
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 19
Pre-Explosion
• Develop Emergency Action Plan (EAP)• Take special consideration for combustible
dust
OS PRT281 TR 19
Dust Explosion
• Implement EAP• Evacuate area• NOT incipient fire
OS PRT281 TR 20
– Explosions can be initiated by incipient fire– Ignited materials can travel
Dust Explosion
• Incipient fire brigades– Limited training– Typically hose streams
PPE
OS PRT281 TR 21
– PPE
• Categorized as fully involved fire– Fire department response– Specialized training
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 20
Post-Explosion
• Initiate investigation when safe– Most evidence is destroyed– Only 50% of cases determine cause
Collect any dust samples
OS PRT281 TR 22
– Collect any dust samples
• Change in working environment– Paranoia, fear, and stress– Perceived risk– apprehension
Post-Explosion
• Increased interest– Community– Regulatory industries
C i ti f i ti
OS PRT281 TR 23
• Communication from organization– Public relations– Choosing a speaker
Post-Explosion
• Resuming normal operations• Recovery
– Rebuilding with safety in mindSt l d hi /di ti d d
OS PRT281 TR 24
– Strong leadership/direction needed
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 21
Next Module
OS PRT281 TR 25
Module 6: Facility Dust Assessment
Damage ControlModule 5 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG5 - 22
© 2009, Texas Engineering Extension Service. All rights reserved.
Module
Facility Dust Assessment
Instructional GuidanceTime: 90 minutes
Materials/Equipment1. Participant Manual
2. PowerPoint visuals for module 6
3. Whiteboard/markers/eraser
4. Video/data projector
5. Screen or monitor
Instructor Preparation1. Prepare projector and position first PowerPoint slide.
2. Review the module’s objectives with participants so they are aware of what they will be learning during this module.
Facility Dust Assessment
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 2
Facility Dust AssessmentIntroduction
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 3
Introduction
In the previous module, types of prevention and response systems were discussed, as well as emergency response actions. This module covers the importance of also conducting a detailed assessment that identifies the type of dust hazard at your facility, and how to create a checklist that can be used for auditing.
Terminal ObjectiveUpon the successful completion of this module, participants will be able to describe the benefits of a facility dust assessment.
Enabling ObjectivesUpon successful completion of this module, the participant will be able to:1. Explain the importance of a facility dust assessment.2. Identify the components of a facility dust assessment.3. Discuss the value of self-audit checklists.
Slide 1
Slide 2
Slide 3
Facility Dust AssessmentFacility Dust Assessment
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 4
Facility Dust Assessment
Conducting an assessment is an important step toward implementing a combustible dust program. A facility analysis needs to be conducted by a qualified team and each facility needs to have a specific hazard analysis.
The dust assessment should consider the following:
• All locations where combustible dust is concentrated during normal equipment operations as well as in the event of equipment failure
• Areas where dust can settle, both in normally occupied areas and in hidden concealed areas
When conducting a facility dust assessment, carefully identify the following:
• Materials that can be combustible, including particle size of materials
• Processes that use, consume, or produce combustible dusts
• Open areas where combustible dusts may build up
• Hidden areas where combustible dusts may accumulate
• Ways that dust may be dispersed in the air
• Potential ignition sources
• Electrical equipment classification
• Ventilation systems
• Physical barriers present or needed to hinder explosion effects
Dust Assessment Characteristics
Dust CombustibilityDust combustibility in the primary factor in an assessment. Identify all materials that can be combustible when finely divided. In addition, identify the processes which use, consume, or produce combustible dusts.
Slide 4
Slide 5
Slide 6
Slide 7
Facility Dust AssessmentDust Assessment Characteristics
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 5
It is a requirement to declare all hazards of a product on the Material Safety Data Sheet (MSDS). Unfortunately, the dust explosion hazard is under-recognized and often not declared on the MSDS. Do no rely solely on the MSDS for all dust explosion hazards. Laboratory testing of your specific dust will determine if there is a hazard.
Laboratory Testing
Testing is necessary to determine if a facility's specific dust is a hazard. The facility needs to be checked for the concentration levels for combustion.
There are several tests that are typically conducted and are:
Minimum Ignition Temperature (MIT) Cloud
Using a Godbert-Greenwald furnace to conduct this test the following should be performed:
1. Disperse air into the furnace.
2. Watch for positive results if flame is at bottom of furnace.
3. Test continues in increments of 5°C.
4. The standard quality of dust should remain at 0.1g (limits of 0.05 and 1.0).
5. Combustibility is verified if positive results occur in one or more trails in a group of four.
Minimum Ignition Temperature Layer
Using the US Bureau of Mines test perform the following:
1. This test involves a metal-mesh basket filled with dust to be tested.
2. Air of a known temperature is flowed across the dust powder.
3. When the temperature of dust powder exceeds the surrounding air, then the ignition temperature of the dust layer is determined.
Hot Plate Test
Using the Hot Plate Test perform the following:
1. A metal ring is placed on a the hot plate.
2. The ring is filled with the dust to be tested.
Slide 7
Slide 8
Slide 9
Slide 10
Facility Dust AssessmentDust Assessment Characteristics
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 6
3. Thermocouples record the temperature of the hot plate and dust.
4. If the dust temperature exceeds the hot plate by 20°C, the ignition is recorded.
Conduct Maximum Explosion Pressure (Pmax)/Rate of Pressure Rise (Rmax)
Using a Hartmann apparatus and a 20-liter sphere.
Dust CharacteristicsDifferent dusts of the same materials will have various ignitability and explosibility characteristics, depending on the following:
• Particle size
• Particle shape
• Moisture content
Note: Characteristics of a material can change while passing through process equipment, so testing of the material under like conditions is critical.
Area VolumeWhen determining the area volume, include all open areas where dusts may accumulate.
Hidden Area InspectionIdentify any hidden areas where dusts may accumulate, such as the following:
• Behind equipment
• On top of beams
Slide 11
Instructor NoteWhen viewing powerpoint slide 13, take a moment to discuss the Air Flowing Through Pipe animation.
During this time please review the basic characteristics of dust and how how characteristics can change while passing through processing equipment.
Slides 12-13
Slides 14-15
Facility Dust AssessmentDust Assessment Characteristics
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 7
• Above suspended ceilings
• On top of light fixtures
• On platforms
Dispersion MethodIdentify means by which dust may be dispersed in the air. Make note of the quantity and concentration that is likely dispersed.
Ignition SourcesIdentify potential ignition sources and be sure to consider ignition sources that are connected to the area by process equipment.
Electrical ClassificationIdentify areas requiring special electrical equipment classification due to the presence (or potential presence) of combustible dust.
29 CFR §1910.307 covers the requirements for electric equipment and wiring in locations that are considered classified. Classifications depend on the following:
• Properties of flammable vapors, liquids or gases, or combustible dusts or fibers that may be present
• The likelihood that a flammable or combustible concentration or quantity is present
Class II locations are areas where there is a hazard of combustible dust.
Instructor NoteWhen viewing powerpoint slide 10, take a moment to discuss the Hidden Area Inspection animation.
Please note that to locate the hidden areas, the instructor must scroll over various locations on the animation. When the instructor has located a hidden area the item will pop up with an explanation.
During this animation please answer participant’s questions regarding hidden area inspections.
Slide 16
Slide 17
Slide 18
Facility Dust AssessmentChecklist "Self-Audit"
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 8
Ventilation SystemsVentilation systems are a key issue when these systems connect to a possible stray ignition source.
When assessing a ventilation system and the connected areas, consider the following:
• Fans and blowers
• Air separation devices
• Ducts
• Exhaust air
Physical BarriersThere are three types of physical barriers that can be used to contain the effects of a combustible dust explosion, as follows:
• Physical: Walls, partitions
• Mechanical: Fast-acting shutoff valves and rotary valves
• Chemical: Suppressant injected to extinguish flame when pressure wave or flame detected
These physical barriers should be created in the path of a possible explosion.
Checklist "Self-Audit"
Creating a checklist is recommended to ensure all topics of a dust assessment are covered. This checklist may also be used to conduct regular self-audits. The following sample questions may be included on the checklist:
• "No Smoking" signs posted in the area?
• Fire extinguishers selected and provided for the types of materials in areas where they are to be used?
• Equipment is free of dust?
Slide 19
Slide 20
Slides 21-22
Facility Dust AssessmentChecklist "Self-Audit"
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 9
• Storage tanks are equipped with emergency venting?
• Rooms where combustible dust is present have explosion-proof lights? Switches?
Online system can be used create electronic checklists, audits, and record findings and recommendations. Figure 6.1 from MESHsystems™ is an example of an online Audit system.
Figure 6.1: MESHsystems™ Online Audit System
Facility Dust AssessmentApplication of Participants’ Knowledge/Skills
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 10
Application of Participants’ Knowledge/Skills
Participants will apply their knowledge by answering review questions at the end of the module.
Evaluation of Participants
Evaluation is based on participants’ active participation in class discussions and responses to review questions at the end of the module.
Summary
Conducting a dust assessment is the first step in launching a combustible dust program at your facility. If you already have a dust program in place, an assessment is a valuable tool to evaluate what you have in place and make improvements to ensure the safety of your employees. Formulating assessment questions and creating a dust assessment audit is a way to continuously improve safety and avoid organizational complacency. An online system, like MESHsystems™ allows for up-to-date, real-time access to checklists and audit information that can be tracked and monitored.
Slide 23
Facility Dust AssessmentModule 6 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 11
Module 6 Review Questions
Directions: Circle the letter of the best answer.
1. When conducting a facility dust assessment, one should carefully identify which of the following? (6-4)
a. Combustible materials
b. Open areas
c. Hidden areas
d. All of the above
1. Different dusts of the same materials will have various ignitability and explosibility characteristics, depending on all EXCEPT: (6-6)
a. Particle size
b. Density
c. Particle shape
d. Moisture content
2. The following is an area where dust may accumulate: (6-6)
a. Behind equipment
b. On top of beams
c. On top of light fixtures
d. All of the above
3. A fast-acting shutoff valve is an example of what type of barrier? (6-8)
a. Mechanical
b. Physical
c. Chemical
d. Particle
4. Creating a checklist is recommended to ensure all topics of a dust assessment are covered.
a. True
b. False
Facility Dust AssessmentModule 6 Review Questions
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 12
Facility Dust AssessmentModule 6 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 13
Module 6 PowerPoint Slides
Module 6
OS PRT281 TR 1
Facility Dust Assessment
Terminal Objectives
Upon the successful completion of this module, the participants will be able to describe the benefits of a facility dust assessment
OS PRT281 TR 2
assessment.
Enabling Objectives
• Explain the importance of a facility dust assessment.
• Identify the components of a facility dust assessment
OS PRT281 TR 3
assessment.• Discuss the value of self-audit checklists.
Facility Dust AssessmentModule 6 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 14
Facility Dust Assessment
• Conducted by a qualified team– Facility Analysis– Hazard Analysis
C id
OS PRT281 TR 4
• Consider– Locations where combustible dust is
concentrated– Locations where dust can settle
• Hidden areas• Occupied areas
Facility Dust Assessment
• Identify– Combustible materials– Processes that use/consume/produce
combustible dust
OS PRT281 TR 5
combustible dust– Open/hidden areas– Dust dispersion– Potential ignition sources
Facility Dust Assessment
• Identify (cont.)– Electrical equipment classification– Ventilation systems
Physical barriers that are present/needed
OS PRT281 TR 6
– Physical barriers that are present/needed
Facility Dust AssessmentModule 6 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 15
Dust Combustibility
• Primary factor in assessment• MSDS
– Do not rely on existing MSDS
b
OS PRT281 TR 7
• Laboratory testing– Determine if specific dust is a hazard– Check concentration levels– Determine MIT cloud
Dust Combustibility-Testing
• Godbert-Greenwald Furnace1. Air dispersion into furnace2. Positive results if flame at bottom of furnace3 Increments of 5°C
OS PRT281 TR 8
3. Increments of 5°C4. Standard quality of dust 0.1g 5. Positive results
Dust Combustibility-Testing
• MIT Layer-US Bureau of Mines Test1. Metal mesh basket filled with dust2. Air of known temperature flowed across
powder
OS PRT281 TR 9
powder3. Ignition when temperature of powder
exceeds air
Facility Dust AssessmentModule 6 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 16
Dust Combustibility-Testing
• Hot Plate Test1. Metal ring placed on hot plate2. Ring filled with dust3 Thermocouples record temperature of hot
OS PRT281 TR 10
3. Thermocouples record temperature of hotplate/dust
4. If dust temperature exceeds hot plate temperature by 20°C then Step 5
5. Ignition recorded
Dust Combustibility-Testing
• Maximum explosion pressure (Pmax)/Rate of pressure rise (Rmax)– Hartmann apparatus
20 liter sphere
OS PRT281 TR 11
– 20-liter sphere
Dust Characteristics
• Dust ignitability/explosibility depends on:– Particle size– Particle shape
Moisture content
OS PRT281 TR 12
– Moisture content
• Characteristics of dust can change
Facility Dust AssessmentModule 6 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 17
Dust Characteristics
OS PRT281 TR 13
Hidden Area Inspection
• Identify areas where dust accumulates:– Behind equipment– On top of beams
Above suspended ceilings
OS PRT281 TR 14
– Above suspended ceilings– On top of light fixtures– On platforms
Hidden Area Inspection
OS PRT281 TR 15
Facility Dust AssessmentModule 6 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 18
Dispersion Method
• Means by which dust may be dispersed• Note
– Quantity C t ti
OS PRT281 TR 16
– Concentration
Ignition Sources
• Identify potential ignition sources• Consider process equipment
OS PRT281 TR 17
Electrical Classification
• Identify areas requiring classification• CFR 40 §1910.307• Classification depends on
OS PRT281 TR 18
– Flammable properties– Likelihood that flammable/combustible
quantity is present
Facility Dust AssessmentModule 6 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 19
Ventilation System
• Key issue when connected to possible stray ignition source
• ConsiderF d bl
OS PRT281 TR 19
– Fans and blowers– Air separation devices– Ducts– Exhaust air
Physical Barriers
• 3 types of barriers– Physical– Mechanical
Chemical
OS PRT281 TR 20
– Chemical
• Placed in locations/paths of possible explosion
Checklist “Self-Audit”
• Checklists ensures all topics covered• Can use checklists for self audits• Questions to ask
OS PRT281 TR 21
– No smoking signs posted?– Equipment free of dust?– Storage tanks equipped with emergency
venting?
Facility Dust AssessmentModule 6 PowerPoint Slides
© 2009, Texas Engineering Extension Service. All rights reserved.
IG6 - 20
MESHsystems Online Audit System
OS PRT281 TR 22
Course Review
OS PRT281 TR 23
© 2009, Texas Engineering Extension Service. All rights reserved.
Appendix
Resources
Resources
© 2009, Texas Engineering Extension Service. All rights reserved.
IGA - 2
ResourcesResources
© 2009, Texas Engineering Extension Service. All rights reserved.
IGA - 3
Resources
As combustible dust incidents have drawn more attention, more and more resources are available to assist in research and prevention of explosions due to combustible dust.
OrganizationsThere are three leading organizations in the forefront of combustible dust policies. The following three organizations offer incident histories, regulations, and policies on combustible dust:
• Occupational Safety and Health Administration (OSHA) (www.osha.gov)
• U.S. Chemical Safety and Hazard Investigation Board (CSB): (www.chemsafety.org)
• Combustible Dust Policy Institute (www.combustibledust.com)
Web Sites
Regulatory Compliance Portal
A valuable resource is the Regulatory Compliance Portal (www.compliancehome.com). This site has the latest white papers, training information, conferences, webcast information, news, regulations, jobs, and information about vendors' products and services. Although there are many other topics besides combustible dust, there is also a good amount of information on combustible dust.
EHS Today
The Web site ehstoday.com contains article from the EHS Today magazine.
OHS Online
At www.ohsonline.com you will find a vast amount of information on various topics in Health and Safety.
The Pump Handle
This site, http://thepumphandle.wordpress.com, calls itself as the "Water cooler for the public health crowd." There are a lot of non-industry topics, but the industry-related topics are very informative.
ResourcesResources
© 2009, Texas Engineering Extension Service. All rights reserved.
IGA - 4
BooksMore and more books are becoming available regarding combustible dust. The books that serve as good resources include the following:
• Development and Control of Dust Explosions by John Nagy
• Industrial Dust Explosion by Cashdollar/Hertzberg
• Dust Explosions in Process Industries by Rolf K. Eckhoff
• Classifying Explosion-Prone Areas for Petroleum, Chemical, and Related Industries by W.O.F. Korver
• Dust Explosion Prevention and Protection by John Barton
Regulations and StandardsThe National Fire Protection Association (NFPA) has created codes dealing with combustible dust hazards and prevention. The NFPA codes include the following:
• NFPA 61: Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food Product Facilities
• NFPA 70: National Electric Code (2008)
• NFPA 484: Standards for Combustible Metals
• NFPA 499: Recommended Practice for the Classification of Combustible Dusts and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas (2004)
• NFPA 654: Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids (2006)
• NFPA 664: Standard for the Prevention of Fires and Explosions in Wood Processing and Woodworking Facilities
DirectivesOccupational Safety and Health Administration (OSHA) released a program entitled CPL 03-00-008 OSHA Combustible Dust National Emphasis Program. This program contains policies and procedures for inspecting workplaces that create or handle combustible dusts.
ResourcesResources
© 2009, Texas Engineering Extension Service. All rights reserved.
IGA - 5
A poster was created by OSHA and can be downloaded and posted on your job site. The poster can be found at www.osha.gov/Publications/combustibledustposter.pdf.
ResourcesResources
© 2009, Texas Engineering Extension Service. All rights reserved.
IGA - 6
© 2009, Texas Engineering Extension Service. All rights reserved.
Appendix
List of Products/Materials inPowdered Form
List of Products/Materials in Powdered Form
© 2009, Texas Engineering Extension Service. All rights reserved.
IGB - 2
List of Products/Materials in Powdered FormProducts/Materials in Powdered Form
© 2009, Texas Engineering Extension Service. All rights reserved.
IGB - 3
Products/Materials in Powdered Form
The following list provides a number of product/materials in powdered form that have the potential to cause a catastrophic event:
• Agricultural Products
• Egg white
• Milk, powdered
• Milk, nonfat, dry
• Soy flour
• Starch, corn
• Starch, rice
• Starch, wheat
• Sugar
• Sugar, milk
• Sugar, beet
• Tapioca
• Whey
• Wood flour
• Agricultural dusts
• Alfalfa
• Apple
• Beet root
• Carrageen
• Carrot
List of Products/Materials in Powdered FormProducts/Materials in Powdered Form
© 2009, Texas Engineering Extension Service. All rights reserved.
IGB - 4
• Cocoa bean dust
• Cocoa powder
• Coconut shell dust
• Coffee dust
• Corn meal
• Cornstarch
• Cotton
• Cottonseed
• Garlic powder
• Gluten
• Grass dust
• Green coffee
• Hops (malted)
• Lemon peel dust
• Lemon pulp
• Linseed
• Locust
• Bean gum
• Malt
• Oat flour
• Oat grain dust
• Olive pellets
• Onion powder
List of Products/Materials in Powdered FormProducts/Materials in Powdered Form
© 2009, Texas Engineering Extension Service. All rights reserved.
IGB - 5
• Parsley (dehydrated)
• Peach
• Peanut meal and skins
• Peat
• Potato
• Potato flour
• Potato starch
• Raw yucca seed dust
• Rice dust
• Rice flour
• Rice starch
• Rye flour
• Semolina
• Soybean dust
• Spice dust
• Spice powder
• Sugar (10x)
• Sunflower
• Sunflower seed dust
• Tea
• Tobacco blend
• Tomato
• Walnut dust
List of Products/Materials in Powdered FormProducts/Materials in Powdered Form
© 2009, Texas Engineering Extension Service. All rights reserved.
IGB - 6
• Wheat flour
• Wheat grain dust
• Wheat starch
• Xanthan gum
• Carbonaceous Dust
• Charcoal, activated
• Charcoal, wood
• Coal, bituminous
• Coke, petroleum
• Lampblack
• Lignite
• Peat, 22% H2O
• Soot, pine
• Cellulose
• Cellulose pulp
• Cork
• Corn
• Chemical Dusts
• Adipic acid
• Anthraquinone
• Ascorbic acid
• Calcium acetate
• Calcium stearate
List of Products/Materials in Powdered FormProducts/Materials in Powdered Form
© 2009, Texas Engineering Extension Service. All rights reserved.
IGB - 7
• Carboxy-methylcellulose
• Dextrin
• Lactose
• Lead stearate
• Methyl-cellulose
• Paraformaldehyde
• Sodium ascorbate
• Sodium stearate
• Sulfur
• Metal Dusts
• Aluminum
• Bronze
• Iron carbonyl
• Magnesium
• Zinc
• Plastic dusts
• (poly) Acrylamide
• (poly) Acrylonitrile
• (poly) Ethylene (low-pressure process)
• Epoxy resin
• Melamine resin
• Melamine, molded (phenol-cellulose)
• Melamine, molded (wood flour and mineral filled phenol-formaldehyde)
List of Products/Materials in Powdered FormProducts/Materials in Powdered Form
© 2009, Texas Engineering Extension Service. All rights reserved.
IGB - 8
• (poly) Methyl acrylate
• (poly) Methyl acrylate, emulsion polymer
• Phenolic resin
• (poly) Propylene
• Terpene-phonel resin
• Urea-formaldehyde/cellulose, molded
• (poly) Vinyl acetate/ethylene copolymer
• (poly) Vinyl alcohol
• (poly) Vinyl butyral
• (poly) Vinyl chloride/ethylene/vinyl acetylene suspension copolymer
• (poly) Vinyl chloride/vinyl acetylene emulsion copolymer
© 2009, Texas Engineering Extension Service. All rights reserved.
Appendix
Relevant Acronyms
Relevant Acronyms
© 2009, Texas Engineering Extension Service. All rights reserved.
IGC - 2
Relevant AcronymsAcronyms
© 2009, Texas Engineering Extension Service. All rights reserved.
IGC - 3
Acronyms
ANSI American National Standards Institute
API American Petroleum Institute
ASME American Society of Mechanical Engineers
ASTM American Society for Testing and Materials
CCPS Center for Chemical Process Safety
CERCLA Comprehensive Environmental Response, Compensation and Liability Act
CFR Code of Federal Regulations
DOE U.S. Department of Energy
DOT U.S. Department of Transportation
DCS Distributed Control System
EMR Experience Modification Rate
EPA Environmental Protection Agency
ERPG Emergency Response Planning Guideline
EHS Environment, Health, and Safety
EVC Equilibrium Vapor Concentration
FMEA Failure Mode and Effects Analysis
FTA Fault Tree Analysis
GOCO Government Owned Contractor Operated
HAZCOM Hazard Communication (Standard)
HAZOP Hazard and Operability Analysis
Relevant AcronymsAcronyms
© 2009, Texas Engineering Extension Service. All rights reserved.
IGC - 4
HDBK Handbook
HHC Highly Hazardous Chemical
IDLH Immediately Dangerous to Life or Health
IEEE Institute of Electrical and Electronic Engineers
ISA Instrument Society of America
JHA Job Hazard Analysis
JSA Job Safety Analysis
LPG Liquid Petroleum Gas
M&O Management and Operations
MOC Management of Change
MSDS Materials Safety Data Sheet
NDT Nondestructive Testing
NFPA National Fire Protection Association
ORC Organization Resources Counselors
OSHA Occupational Safety and Health Administration
P&ID Piping and Instrumentation Diagram
PEL Permissible Exposure Limit
PHA Process Hazard Analysis
PrHA Process Hazard Analysis
PSI Process Safety Information
PSM Process Safety Management
PSR Pre-startup Review
Relevant AcronymsAcronyms
© 2009, Texas Engineering Extension Service. All rights reserved.
IGC - 5
PSI Process Safety Information
QA Quality Assurance
RCRA Resource Conservation and Recovery Act
RMP Risk Management Program
SAR Safety Analysis Report
SASS Safety Assurance System Summary
SCBA Self-Contained Breathing Apparatus
SHI Substance Hazard Index
SOP Standard Operating Procedure
TLV Threshold Limit Value
TQ Threshold Quantity
TSD Treatment, Storage, and Disposal
Relevant AcronymsAcronyms
© 2009, Texas Engineering Extension Service. All rights reserved.
IGC - 6
© 2009, Texas Engineering Extension Service. All rights reserved.
Appendix
Course Exam
Course Exam
© 2009, Texas Engineering Extension Service. All rights reserved.
IGD - 2
Course ExamCourse Exam
© 2009, Texas Engineering Extension Service. All rights reserved.
IGD - 3
Course Exam
1. A primary explosion is often the largest one.
a. True
b. False
2. The less heat absorbed by the mass of the particle, the ________ that heat accelerates the reaction.
a. more
b. less
3. Characteristics of combustible dust include all of the following EXCEPT:
a. Particle size
b. Chemical properties of dust
c. Cloud dispersion
d. Time in atmosphere
4. Which explosion brought about the most amount of attention to the importance of regulations for combustible dust?
a. CTA Acoustics-Corbin, KY
b. Imperial Sugar-Savannah, GA
c. Amoco Chemical-New Castle, DE
d. Farmer's Export Company-Galveston, TX
5. Dust escape can occur when ________.
a. raw material leaks through leaks or cracks
b. loading, unloading or transferring of material is taking place
c. storage units are not properly sealed
d. All of the above
Course ExamCourse Exam
© 2009, Texas Engineering Extension Service. All rights reserved.
IGD - 4
6. The design of a facility is crucial to prevent combustible dust incidents and include ________.
a. utilizing surfaces that maximize dust accumulation
b. storage units, containers, elevators, and chutes need to remain open
c. providing access to all hidden areas
d. locate relief valves near dust hazard areas
7. If dust escapes, use cleanup methods that do not generate dust clouds, such as ________.
a. airing out the facility
b. water removal/Wet method
c. blower fans
d. none of the above
8. When it comes to the fire triangle for combustible dusts, the shape that best represents the elements of combustible dust explosions is a ________.
a. square
b. triangle
c. pentagon
d. hexagon
9. Possible ignition sources include all of the following EXCEPT
a. Static electricity
b. Dented surface
c. Open flame or ember
d. Electric arcs and sparks
10. Which of the following is an example of open flame or glowing ember ignition source?
a. Smoking
b. Flares
c. Furnaces
d. All of the above
Course ExamCourse Exam
© 2009, Texas Engineering Extension Service. All rights reserved.
IGD - 5
11. Combustible materials must be moved far away from hot work zone. What radius away from the hot work zone should the materials be moved to?
a. 15-foot
b. 35 foot
c. 55-foot
d. 75-foot
12. A pump with a large motor is of a size that cannot be made intrinsically safe, so explosion proof equipment and practices would be mandatory.
a. True
b. False
13. All plant personnel must ________.
a. be aware of combustible materials used in plant
b. be aware of necessary response to combustible dust incidents
c. attend combustible dust training
d. All of the above
14. Engineering has a huge impact on combustible dust prevention by all EXCEPT:
a. Allowing hidden areas
b. Designing combustible dust producing areas to be blast proof and resistant
c. Using intrinsically safe and explosion-proof devices in design
d. Placing relief valve away from combustible dust areas
15. An example of a damage control system is a ________.
a. spark ember detection
b. hazard segregation
c. deflagration venting
d. All of the above
16. A deluge fire suppression system is used in places considered to be a high hazard area, such as chemical storage.
a. True
b. False
Course ExamCourse Exam
© 2009, Texas Engineering Extension Service. All rights reserved.
IGD - 6
17. Which is a key emergency response activity that must be performed prior to an explosion occurring?
a. Being familiar with response measures and where response tools are located
b. Developing EAP
c. Being familiar with emergency rescue procedures
d. All of the above
18. Determining the cause of a combustible dust explosion is only achieved in about ________ of cases.
a. 10%
b. 25%
c. 50%
d. 75%
19. Different dusts of the same materials will have various ignitability and explosibility characteristics, depending on the following, EXCEPT:
a. Particle Size
b. Density
c. Particle Shape
d. Moisture Content
20. ________ is an area where dust may accumulate.
a. Behind equipment
b. On top of beams
c. On top of light fixtures
d. All of the above
21. A fast acting shutoff valve is an example of a ________.
a. mechanical
b. physical
c. chemical
d. particle
A Member of The Texas A&M University System877-833-9638 www.teex.org
TEXAS ENGINEERING EXTENSION SERVICE
LAW ENFORCEMENT
SAFETY & HEALTH
HOMELAND SECURITY
FIRE SERVICES
PUBLIC WORKS
SEARCH & RESCUE
TECHNOLOGY TRANSFER