Upload
stacy-ricker
View
215
Download
0
Tags:
Embed Size (px)
Citation preview
COLORADO SPRINGS FIRE DEPARTMENT
2009 International Fire 2009 International Fire Code – Major Changes and Code – Major Changes and
Proposed AmendmentsProposed Amendments
Kris CooperDeputy Fire Marshal
September 22, 2010
"Protecting life and property today - creating a safer tomorrow"
Overview
Introduction to ICC Code Cycle
2009 IFC – Major Changes
2009 IBC – Major Changes of Interest to CSFD
CSFD Proposed Amendments
THIS PRESENTATION IS NOT ALL EMCOMPASING, IT IS ONLY A
SUMMARY OF HIGHLIGHTS OF THE IFC, IBC AND PROPOSED
AMENDMENTS.
ICC Code Cycle – 3 Years
Call For Committees Proposed Changes
Public Proposal Form
Code Development Hearings Reports of Hearings Final Action Hearings Final Action Results
Local Code Cycle
Regulatory Agencies Review Codes PPRBD and CSFD Meet Review Committees Established
CSFD Staff
Proposed Amendments Proposal Forms
Public Process City Council Adoption
IFC Significant Changes
Section 202, 903.2.2, 907.2.2
Defines Ambulatory Health Care Facilities Group B occupancies used for outpatient
surgery and similar activities that render patients incapable of self preservation
Requires Sprinkler and Automatic Fire Detection Throughout
Section 311.5
Dangerous Building Placards
Information placards for fire fighters to identify hazards associated with vacant structures
311.5 continued
Structural or Interior Hazards Exist
Normal Structural Conditions
Major Structural or Interior Hazards Exist, Exterior Operations Only
Additional Markings: R/O Roof Opening, S/M Stairs Missing, F/E Fire Escapes, H/F Holes in Floor
Section 403.3
Requires crowd managers for assemblies or events where more than 1,000 people congregate. 1 crowd manager to every 250
occupants Assist with evacuation procedures Not intended to require dedicated staff
Section 404
Code now includes provisions for occupants who need assistance with evacuation. Previous CSFD amendment for “special
needs occupants” Applies to emergency plans
Section 404.3.3
Lockdown plans for schools Required to be included in Fire and Life
Safety Plans Required to be approved by the fire code
official CSFD is not going to require approval of the
fire and life safety plans (amendment).
Section 508
Fire Command Center Room size increased from 96 square feet
to 200 square feet with a minimum dimension of 10’
Layout must be approved by CSFD See 508.1.5 for required features
Section 510 & Appendix J
Emergency responder radio coverage ALL buildings shall have approved radio
coverage for emergency responders. May require bi-directional amplifiers
This item is still being discussed.
Section 603.4.2
Portable Outdoor Gas-Fire Heating Appliances 5’ clearance to buildings and other
combustibles Also see Section 307 for clearances of
outdoor burning (50’), recreational fires (25’) and portable outdoor fireplaces (15’).
Outdoor Heating Appliances
5’ or manufacturer’s specifications 15’ or manufacturer’s specifications
Section 607.3, 903.3.1.1.1
Fire Service access elevators Buildings greater than 120’ Adjacent to exit enclosure (stairway) Driven by 9/11
Section 608
Stationary battery systems Expended battery types
Lithium – Ion Lithium Metal Polymer Nickel cadmium Nonrecombinant Recombinant
Section 609.3.3.1
Frequency for Inspection of Kitchen Hoods – Table 609.3.3.1 High Volume Cooking – 3 months
24 hour cooking operations Low Volume Cooking – 12 months
Churches, seasonal businesses Solid Fueled Cooking – 1 month
BBQ pits, smokers All Other Cooking Operations – 6 months
Section 903.2.3
E (Educational) Occupancies Reduces sprinkler threshold from 20,000
square feet to 12,000 square feet
Section 903.2.7
Requires sprinklers for the display and sale of upholstered furniture in M Occupancies, regardless of size of fire area No Specified Threshold Huge Implications for Plan Review Driven by Charleston Fire
Section 907 Complete re-write of the section No major changes
Side note: 2010 NFPA 72 now the National Fire Alarm and Signaling Code Recognizes other alarm functions Fire Alarm not necessarily priority signals Mass Notification Systems
Section 909
Smoke Control Systems CSFD had previously amended this
section to be more restrictive. Accepting code as written with this
adoption.
Section 913.2.1
Protection of Fire Pump Enclosures Dedicate rooms High Rise
2 hour separation Non-High Rise
1 hour separation
Section 1005.1
Minimum Egress Width No longer have different design width for
sprinkled vs. non-sprinkled structures 0.3 inches per occupant for stairs 0.2 inches per occupant for all other
means of egress Loss of any one means of egress shall
not reduce the available egress width to less than 50% of required capacity.
Section 1007.3, 1007.4, 1007.6.3 & 1007.8
Areas of Refuge Not required in buildings protected
throughout with sprinklers Elevators now approved for occupant
evacuation as a means of egress Two-way communication required for areas
of refuge and evacuation elevators
Section 1008.1.9.8
Electromagnetically locked egress doors Clarifies the use of magnetic locks on
egress doors
Section 1011.4
Exit Signs Electrically Powered Self-luminous Photo-luminescent
Must comply with UL 924 – Emergency Lighting and Power Equipment.
Section 1024
Luminous Egress Path Markings High Rise Structures Required in exit enclosures of new and
existing buildings CSFD not adopting retroactive application
Required on hand rails, stair treads and landings
Luminous Egress Path Markings
Section 2206.8
Provides requirements for dispensing Alcohol Blended Fuels Specific listing of equipment Signage requirements for facility
identification
Alcohol Blended Fuels: Including those containing 85% ethanol and 15% unleaded gas (E-85). Flammable liquids consisting of ethanol or other alcohols blended greater than 15% by volume
Chapter 24
Now treats tents, canopies and membrane structure the same Reasoning: Canopies can have walls
added to become tents 2,400 square foot permit threshold
(amendment)
Chapter 46
Combines requirements for existing buildings into one chapter Look at this closely as it contains
significant retroactive requirements CSFD has amended this section with lots
of deletions.
International Building Code
The following code sections are from the 2009 IBC These are fire related items or CSFD has
a specific interest in them.
Section 419
Guidance on live work units Classified as R-2 Non-residential use up to 50%
Section 703.6
Marking and identification of fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions
Allows for easy identification of rated assemblies
Marking and Identification
Section 909.20
Stairwells can be pressurized or built with a vestibule Design will impact standpipe valve
locations.
Section 1018.4
Dead End Corridors Increase from 20’ to 50’ in B, E, F,I-1, M,
R-1, R-2, R-4, S and U occupancies Must have NFPA 13 sprinkler system
Section 3002.4
Elevator cars must be sixed to accommodate a 24” x 84” stretcher
Local Amendments
Local changes made to the code during the adoption process as a means to clarify, comply with City Code and/or Charter, or modify code requirements.
Based upon local practices, polices, procedures or interpretations.
Less is more approach
Chapter 1 - Administration
Changes made in order to be consistent with The Code of the City of Colorado Springs. Administrative Powers Penalties Fire Board of Appeals
Permits
Permits as listed in the code maintained as written Modified some hazmat permit threshold
amounts Added permit amounts for electrolytes Added Work at Risk Permits
105.7.15 – Fire Lanes
Added a new permit for the construction of Fire Lanes Applies to alternative methods
Grass Pave Gravel Pave
Alternative Fire Lanes
Fees
Reinspections Fees Cleaned up language where fees may
apply to routine fire inspections
Subsequent review fees Added a provision for the collection of
fees where plans are revised and or updated and require additional reviews beyond the initial approval
Section 407.2
Allows MSDS to be in electronic format
CSFD amendment to specify format and storage on thumb drive in Knox Box Microsoft Word 2000 or newer PDF
Section 901.5
Approved Contractors Going with 3rd party testing Will include fire alarm, fire alarm monitoring
contractors, water based fire suppression, portable fire extinguishers, special hazard systems and fire hydrants
New state law for testing for all fire sprinkler installers Unknown impact from state law
904.11.2
Kitchen Fire Suppression Systems Added requirement to cut off power to
any appliances under the hood or any power source that could be used to supply power to an appliance under the hood.
904.11.6.4
Kitchen Hood Ventilation Added a new code section to require the
exhaust to start and/or stay on upon activation of the fire suppression system.
Prevents heat roll out from the hood that might activate sprinklers.
905.4
Standpipe Connections in Stairways Provides guidance where the standpipe
valve will be located when the stairway is built with a vestibule per the IBC.
1107.1
Helistops and Heliports Added additional language to require
design and construction to NFPA 407 and 418 in addition to the IBC.
3006.1
Medical Gas Systems Must be installed by Credentialed
installers ASSE 6010, 6015, 6020 & 6030
Chapter 47
NFPA Standards All NFPA Standards referenced in
Chapter 47 Automatically adopted on January 1 of the
year following the affective date of the standard.
Residential Sprinklers
International Residential Code Requires sprinklers in all dwelling units,
to include 1 and 2 family dwellings Colorado Springs is not proposing
adoption of this section Each jurisdiction may evaluate this
separately.
Timeframe
Mid September - October Public Process
November Present to City Council
January 1, 2011 Effective Date