COLLEGE TOWNSHIPCOUNCIL MEETING ROOM CONCEPTS
COLLEGE TOWNSHIPCouncil Meeting Room Concepts
OWNER CONCERNS
• Heat from incandescent fixtures.
• Inadequate light levels on work table (10-15 footcandles).
w w w . r e e s e i n c . c o m
COLLEGE TOWNSHIPCouncil Meeting Room Concepts
ADDITIONAL CONCERNS
w w w . r e e s e i n c . c o m
• Glare / heat from track lighting.
• Glare from position of downlights.
• Strain from multiple light levels.
• Light absorbed by curtain.
COLLEGE TOWNSHIPCouncil Meeting Room Concepts
PROPOSED IMPROVEMENTS
• Relocate downlights so they are above worktable only.
• Change from incandescent source to dimmable fluorescent source.
• Replace incandescent (exposed source) track to fluorescent track.
• Provide even illumination on display surfaces.
• Add indirect pendants closer to council table.
• Create lip for additional task light at table.
• Replace dark curtain with lighter color curtain.
w w w . r e e s e i n c . c o m
COLLEGE TOWNSHIPCouncil Meeting Room Concepts
w w w . r e e s e i n c . c o m