Code of Practice for Fire Safety in Buildings 2011

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011

Page 2: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Code of Practice for Fire Safety in Buildings 2011

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 2

The New Code of Practice for Fire Safety in Buildings 2011 (FS Code) was issued by Buildings Department on 30 September 2011

Several briefing sessions were organized by Buildings Department and HKIA in October 2011

Queries and questions were collected from HKIA members after the briefing sessions which were sent to BD on 18 November 2011 for a written response.

Page 3: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Salient Points of Amendments affecting Building Design

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 3

Code of Practice for Fire Safety in Buildings 2011

Page 4: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Contents of the FS Code

Part A - Introduction

Part B - Means of Escape (MOE)

Part C - Fire Resisting Construction (FRC) Deemed to comply provisions

Part D - Means of Access (MOA)

Part E - Fire Properties of BuildingElements and Components

Part F - Fire Safety Management

Part G - Guidelines on Fire Engineering Alternative Solutions

4HKIA Intensive CPD Seminar 2011 on 17 Dec 2011

Page 5: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

8 Use Classifications are introduced in the FS Code :1. - Residential2. - Hotel and similar Transient Accommodation3. - Institutional4. - Commercial5. - Assembly6. - Industrial7. - Carparks8. - Plant Rooms & the like

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 5

New OF are provided for accommodation types not previously defined in the old MOE Code

e.g. Carparks - 30 m2 per personPlant rooms - 30 m2 per person (for net floor area exceeding 100 m2)

Clause B4.1 Occupant Capacity and Occupancy FactorClause B4.1 Occupant Capacity and Occupancy Factor

Use Classifications

Page 6: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part B : Means of Escape

Clause B8.2 Access to Required Staircases

Access should be provided from one staircase to another staircase (without going through private premises)

at each floor; at one of every 5 floors of a domestic

building not exceeding 15 storeys; in case refuge floor(s) is/are provided,

at the refuge floor(s) AND the roof.

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 6

Page 7: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part B : MEANS OF ESCAPEClause B9.1 Exits at Ground Storey

Any opening from ground storey to the required staircase shall be through a protected lobby

Clause B11.2 & B11.3 Travel Distance

Travel distance for most of the Use Classifications (except UC-3 for institutional use) have been relaxed, especially for residential (UC-1) and Hotel (UC-2).

Travel distance for Use Classification 3 (Institutional) has been tightened.

Clause B11.4 Multi-level Flats (e.g. Triplex, etc.)

Flats with 3 or more levels should be provided with access to a protected exit at 2 or more levels.

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 7

Page 8: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part B : MEANS OF ESCAPE

Clause B17.5 Protected Lobby for required staircases from Basement

Protected lobby is no longer required for required staircases from basement : which is provided with a pressurization system; which is an independent staircase (serving one basement only)

Clause B20.9 PPE Premises with an Occupant Capacity not more than 500 (other than Cinema / theatre)

Relaxation of thoroughfare requirement for small scale PPT not being a Cinema or Theatre

Such Places of Public Entertainment with an OC of not more than 500 may be permitted to abut on one thoroughfare only.

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 8

Page 9: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part C : FIRE RESISTING CONSTRUCTION

Most of the Fire Compartment limit have been changed from “Volume” to “Area”.

Clauses C3.2 and C4.2 Fire Rated Doors

Fire Rated Doors through a fire barrier should have the same Fire Resisting Rating (FRR) as that of the fire barrier.

(only half of the FRP of the compartment / wall is required in old FRC Code)

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 9

Page 10: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part C : FIRE RESISTING CONSTRUCTION

Clause C5.2 Separation between Buildings on the Same Site

Separation distance between buildings on the same site depends on the angle between external walls of the buildings,

In general, - minimum of 900mm for external walls with an angle of more than 135 degrees;

Minimum of 1800mm for external walls with an angle of less than 135 degrees.

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 10

Page 11: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part C : FIRE RESISTING CONSTRUCTION

Clause C8.1 Insulation Criteria for Fire Rated Doors and Fire Shutters for Fire Compartment Openings

Fire Shutters and Fire Rated Doorsforming more than 25% of the fire barrier forming part of a fire compartment wall are required to have Insulation Criteria in addition to the integrity requirement.

(Note : The new requirement for insulation criteria is effective immediately subsequent to BD’s issue of the revised PNAP No. APP-83 in August 2011.)

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 11

Page 12: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part C : FIRE RESISTING CONSTRUCTION

Clause C10.3 Atrium in a Building

New restrictions to design of atrium in a building :

max. volume of 28,000 m3. Max. 15m from the lowest connected floor to the underside of the

structural member at atrium ceiling Sprinkler system to be provided to the atrium Max. 3 interconnected floors within an atrium.

Any atrium design not complying with the above is subject to special approval upon submission of a Fire Engineering proposal.

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 12

Page 13: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part C : FIRE RESISTING CONSTRUCTION

Clause C10.1 Protection of Openings between Floors

450mm fire rated downstand around openings between floors is required in sprinkler protected buildings only.

Clause C11.1 Protection against External Fire Spread

Protection at external wall between floors can be achieved by means of : 900mm vertical spandrel element with the required FRR; 500mm horizontal projection with the required FRR.

The above can be waived for sprinkler protected buildings.

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 13

Page 14: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part C : FIRE RESISTING CONSTRUCTIONClause C13.4 Open Kitchen in Residential Use (UC-1) Open kitchen in residential use can be approved without

submission of any fire engineering proposal, subject to the following provisions : Smoke Detectors Sprinklers Fire rated full height wall adjacent to the exit door.

Clause C16.4 Fire Rated Doors

bottom gap between doors and floor is now relaxed from 4mm to 10mm

smoke seal should be provided to all fire rated doors of the following: a flat or guestroom; a protected lobby; a projector room of a cinema for film projection.

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 14

Page 15: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

Part D : MEANS OF ACCESS

Most of the requirements for Means of Access remain unchanged except :

Clause D8.4 Fireman’s Lift

Direct line measurement for floors that the internal layout is not shown on plan is relaxed from 40m to 45m.

Clause D17.2 Firefighting & Rescue Stairway

FRR of firefighting and rescue stairway is reduced from twice of the overall building FRR to the same as the overall building FRR.

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 15

Page 16: Code of Practice for Fire Safety in Buildings 2011 - HKIA PDF/Session2_Part1_FSCode.pdf · Code of Practice for Fire Safety in Buildings 2011 HKIA Intensive CPD Seminar 2011 on 17

APPLICATION OF NEW FIRE SAFETY CODE

Projects for which consent to the commencement offoundation works has been given after 1 April, 2012, the new Fire Safety Code should be complied with.

The new FS Code may be adopted for plans submitted before 1 April, 2012 provided that it is used in its entirety.

For existing building (based on old codes), only the areas affected by the proposed A&A works (together with the affected exit routes) will need to comply with the new FS Code.

For licensed premises in existing buildings, only the areas subject to a new license application (including the affected exit routes) will need to comply with the new FS Code.

HKIA Intensive CPD Seminar 2011 on 17 Dec 2011 16