Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
CLICK I/O Module Specifications
C0-04AD-24-Channel Analog Voltage Input Module4-channel analog voltage input module, 13-bit resolution, range: 0-10V.External 24VDC power required, removable terminal block included.(replacement ADC p/n C0-8TB).
ZipLink Pre-Wired PLC ConnectionCables and Modules for CLICK PLC
ZL-RTB20 20-pin feed-through connector module
11-pin connector cableZL-C0-CBL11 (0.5 m length)ZL-C0-CBL11-1 (1.0 m length)ZL-C0-CBL11-2 (2.0 m length)
CH1CH2CH3CH40V0V0V0V0V
24V0V
C0-04AD-20-10V
INPUTAll ‘0V’terminals areconnectedinternally.
CH1CH2CH3CH40V0V0V0V0V
24V0V
C0-04AD-20-10V
INPUTAtecoin
+–Voltage
Transmitter
+–Voltage
Transmitter
+–Voltage
Transmitter
+–Voltage
Transmitter
+–
24VDCPowerSupply
CHn
0V
Connect the unusedchannel to 0V terminal.
Wiring Diagram C0-04AD-2 Input SpecificationsInputs per Module 4Input Range 0-10 VResolution 13-bit, 1.22 mV per countInput Type Single ended (one common)Maximum Continuous Overload ±100 VDCInput Impedance >150k�
Filter Charactistics Low pass, -3 dB at 500 HzSample Duration Time 6.25 msAll Channel Update Rate 25 msOpen Circuit Detection Time Zero reading within 100 msAccuracy vs. Temperature ±75 PPM/°C maximum
Maximum Inaccuracy 0.5% of range (including tempera-ture changes)
Linearity Error (End to End) ±3 count maximum,monotonic with no missing codes
Input Stability andRepeatability ±2 count maximum
Full Scale Calibration Error(Including Offset) ±8 count maximum
Offset Calibration Error ±8 count maximumMaximum Crosstalk at DC,50/60 Hz ±2 count maximum
Field to Logic Side Isolation 1800 VAC for 1 sec.External 24 VDC PowerRequired 65 mA
Base Power Required (24 VDC) 23 mATerminal Block Replacement ADC p/n C0-8TBWeight 2.9 oz (82 g)
NOTE: When using this module you must also use CLICKprogramming software and CPU firmware version V1.40 or later.
CPU Module(C0-00DD1-D)
I/O Module(C0-16ND3)
I/O Module(C0-16TD1)
Power Supply(C0-01AC)
C-more Micro-GraphicPanel
Port 1or
Port 2
Only monochrome models can be powered from port 1 or 2.
Power Budgeting
Current Consumption (mA) Example
Part NumberPower Budget
24 VDC(logic side)
External24 VDC
(field side)C0-00DD1-D 120 60C0-16ND3 40 0C0-16TD1 80 100C-more Micro 90 0Total: 333300 116600 **
* Plus calculated load of connected I/O devices.
Other 24 VDC PowerSupply
Example: PSP24-60S
CLICK 24 VDC PowerSupply
C0-00AC or C0-01AC
Power BudgetingThere are two areas to be consideredwhen determining the power required tooperate a CLICK PLC system. The firstarea is the power required by the CLICKCPU, along with the internal logic sidepower that the CPU provides to its ownI/O and any connected I/O modules thatare powered through the CPU’s expansionport; plus any device, such as a C-moreMicro-Graphic panel, that is poweredthrough one of the CPU’s communicationports.
The second area is the power required byall externally connected I/O devices. Thisshould be viewed as the field side powerrequired. The field side power is depen-dent on the voltage used for a particularinput or output device as it relates to thewired I/O point, and the calculated loadrating of the connected device.
It is strongly recommended that the powersource for the logic side be separate fromthe power source for the field side to helpeliminate possible electrical noise.
Power budgeting requires the calculationof the total current that the 24 VDC powersource needs to provide to CLICK’s logicside, and also a separate calculation ofthe total current required for all devicesoperating from the field side of the PLCsystem.
See the Power Budgeting Example shownto the right. The table shows currentrequirements for a CLICK CPU, two I/Omodules, and a C-more Micro. Use thetotal amperage values to select a propersized power supply.
Power Budgeting Using theCLICK Programming SoftwareThe CLICK Programming software canalso be used for power budgeting. Basedon the amperage rating of thepower supply selected in thefirst column, your powerbudget is calculated bysubtracting each consecutivemodule’s power consumptionfrom the total available powerbudget. If you exceed themaximum allowable powerconsumption the powerbudget row is highlighted inred.
CPU Current Consumption (mA)
Part NumberPower Budget
24 VDC(logic side)
External24 VDC
(field side)Basic CPU Modules
C0-00DD1-D 120 60C0-00DD2-D 120 0C0-00DR-D 120 0C0-00AR-D 120 0
Standard CPU ModulesC0-01DD1-D 140 60
C0-01DD2-D 140 0
C0-01DR-D 140 0
C0-01AR-D 140 0
Analog CPU ModulesC0-02DD1-D 140 60C0-02DD2-D 140 0C0-02DR-D 140 0
I/O Module Current Consumption(continued) (mA)
Part NumberPower Budget
24 VDC(logic side)
External24 VDC
(field side)Discrete Combo I/O Modules
C0-16CDD1 80 50
C0-16CDD2 80 0
C0-08CDR 80 0
Analog Input ModulesC0-04AD-1 20 65C0-04AD-2 23 65C0-04RTD 25 0C0-04THM 25 0
Analog Output ModulesC0-04DA-1 20 145C0-04DA-2 20 85
Analog Combo I/O ModulesC0-4AD2DA-1 25 75
C0-4AD2DA-2 20 65
C-more Micro-Graphic PanelMonochrome
only 90 0
I/O Module Current Consumption (mA)
Part NumberPower Budget
24 VDC(logic side)
External24 VDC
(field side)Discrete Input Modules
C0-08ND3 30 0
C0-08ND3-1 30 0
C0-16ND3 40 0
C0-08NE3 30 0
C0-16NE3 40 0
C0-08NA 30 0
Discrete Output ModulesC0-08TD1 50 15C0-08TD2 50 0C0-16TD1 80 100C0-16TD2 80 0C0-08TA 80 0C0-04TRS 100 0C0-08TR 100 0
Power Budgeting Example
I/O ModulesA variety of discrete, combo, and analogI/O modules are available for the CLICKPLC system. Up to eight I/O modules canbe connected to a CLICKCPU module to expand thesystem I/O count and meetthe needs of a specificapplication. Complete I/Omodule specifications andwiring diagrams can befound later in this section.
Choosing the I/O Type
Analog CPU ModulesThe Analog CLICK CPU modules areavailable with different combinations ofDC in, DC sinking, sourcing or relay out,and analog in and out.
They also have an RS-485 port forModbus and ASCII communications, andthe battery backup feature which willretain the data in SRAM for 5 years(battery sold separately; part no.D2-BAT-1).
The table lists the part numbers showingthe various I/O type combinations.
C0-02DD1-D
C1
X1
X2
X3
X4
C2
Y1
Y2
Y3
Y4
+V
AD1V
AD1I
AD2V
AD2I
ACOM
DA1V
DA1I
DA2V
DA2I
RS-485PORT3
PORT2
PORT1
PWR
RUN
ERR
TX2
RX2
TX1
RX1
TX3
RX3
CommunicationPorts
LED StatusIndicators
PLC ModeSwitch 4 Discrete
Inputs
4 DiscreteOutputs
2 AnalogInputs
2 AnalogOutputs
Analog CPU
Analog CLICK CPUs
Part Number DiscreteInput Types
DiscreteOutput Types
Analog InputTypes
Analog OutputTypes
ExternalPower
C0-02DD1-D4 DC(sink/source)
4 DC (sink) 2 channel; voltage (0-5VDC) / current (4-20mA); selectableseparately per channel;12 bit
2 channel; voltage (0-5VDC) / current (4-20mA); selectableseparately per channel;12 bit
24 VDC (requiredfor all CPUs)C0-02DD2-D 4 DC (source)
C0-02DR-D 4 relay
C0-08ND3 C0-08ND3-1 C0-08NE3C0-16ND3 C0-08NAC0-16NE3
Discrete Input Modules
Discrete Input Modules
Part Number I/O Type/Number/Commons
Sink orSource
VoltageRatings
C0-08ND3 DC/8/2 Sink or Source 12-24 VDCC0-08ND3-1 DC/8/2 Sink or Source 3.3-5 VDCC0-16ND3 DC/16/4 Sink or Source 24 VDCC0-08NE3 AC/DC / 8/2 Sink or Source 24 VAC/VDCC0-16NE3 AC/DC / 16/4 Sink or Source 24 VAC/VDCC0-08NA AC/8/2 N/A 100-120 VAC
Choosing the I/O Type
Discrete Output Modules
Discrete I/O Modules(continued)
C0-16TD1C0-08TD1 C0-08TD2 C0-16TD2 C0-08TA C0-04TRS C0-08TR
Discrete Combo I/O Modules
C0-16CDD2PWR24V 4mA
OUTPUTINPUT
C11234
5678+V1234C25678
12-24V 0.1A
C0-16CDD2
C0-16CDD1PWR24V 4mA
OUTPUTINPUT
C11234
5678C21234+V5678
5-27V 0.1A
C11234
C21234
250V~ 1A 50-60Hz
C0-08CDRPWR12-24V 2.5-5mA
30V 1A
INPUTOUTPUT
C0-16CDD1 C0-08CDR
Discrete Combo I/O Modules
PartNumber Input Type Input Voltage Output Type
Output Voltage /Current Ratings
C0-16CDD1 8 DC (source/sink) 24 VDC 8 DC (sink) 5-27 VDC /0.1 A
C0-16CDD2 8 DC (source/sink) 24 VDC 8 DC (source) 12-24 VDC /0.1 A
C0-08CDR 4 DC (source/sink) 12-24 VDC 4 (relay) 6.25-24 VDC, 1 A6-240 VAC, 1 A
Discrete Output Modules
Part Number I/O Type/Number/ Commons
Sink orSource
Voltage/CurrentRatings
C0-08TD1 DC/8/2 Sink 3.3-27 VDC, 0.3 AC0-08TD2 DC/8/1 Source 12-24 VDC, 0.3 AC0-16TD1 DC/16/2 Sink 5-27 VDC, 0.1 AC0-16TD2 DC/16/2 Source 12-24 VDC, 0.1 AC0-08TA AC/8/2 N/A 17-240 VAC, 0.3 A
C0-04TRS Relay/4/4 N/A 6-27 VDC, 7 A6-240 VAC, 7 A
C0-08TR Relay/8/2 N/A 6-27 VDC, 1 A6-240 VAC, 1 A
Choosing the I/O Type
Analog I/O Modules
Analog Input Modules
C0-04RTDPt, Cu, Ni, RES
INPUT
COMR1+R1–R1CCOMCOMR2+R2–R2CCOMCOMR3+R3–R3CCOMCOMR4+R4–R4CCOM
C0-04RTD
CH1CH2CH3CH40V0V0V0V0V
24V0V
C0-04AD-10-20mA
INPUT
CH1CH2CH3CH40V0V0V0V0V
24V0V
C0-04AD-20-10V
INPUT
COMTC1+TC1–TC2+TC2–COMTC3+TC3–TC4+TC4–COM
C0-04THMJ,K,E,R,S,T,B,N,C,mV
INPUT
C0-04AD-1 C0-04AD-2 C0-04THM
Analog Input ModulesPart
Number Analog Input Types External PowerRequired
C0-04AD-1 4 channel, current (0-20 mA), 13 bit 24 VDCC0-04AD-2 4 channel, voltage (0-10 V), 13 bit 24 VDC
C0-04RTD 4 channel RTD input (0.1 degree °C/°Fresolution), or resistive input (0 to 3125 ohms) None
C0-04THM 4 channel thermocouple input (0.1 degree °C/°Fresolution), or voltage input (-156.25 mV to 1.25 V), 16 bit None
CH1CH2CH3CH40V0V0V0V0V24V0V
C0-04DA-14-20mA
OUTPUT
CH1CH2CH3CH40V0V0V0V0V24V0V
C0-04DA-20-10V
OUTPUT
C0-04DA-1 C0-04DA-2
Analog Output Modules
Analog Output Modules
Part Number Analog Output Types External PowerRequired
C0-04DA-1 4 channel, current sourcing (4-20 mA), 12 bit 24 VDCC0-04DA-2 4 channel, voltage (0-10 V), 12 bit 24 VDC
General SpecificationsFor All CLICK PLCProductsThese general specifications apply to allCLICK CPUs, optional I/O modules, andoptional power supply products. Pleaserefer to the appropriate I/O temperaturederating charts under both the CPU andI/O module specifications to determinebest operating conditions based on theambient temperature of your particularapplication.
General SpecificationsPower Input Voltage Range 20-28 VDCMaximum Power Consumption 5 W (No 5 V use from communication port)Maximum Inrush Current 30 A (less than 1ms)Acceptable External Power Drop Max 10 ms
Operating TemperatureAnalog, analog combo I/O modules only: 32°F to 140°F (0°C to 60°C);All other modules: 32°F to 131°F (0°C to 55°C), IEC 60068-2-14 (TestNb, Thermal Shock)
Storage Temperature–4°F to 158°F (–20°C to 70°C)IEC 60068-2-1 (Test Ab, Cold)IEC 60068-2-2 (Test Bb, Dry Heat)IEC 60068-2-14 (Test Na, Thermal Shock)
Ambient Humidity 30% to 95% relative humidity (non–condensing)Environmental Air No corrosive gases. Environmental pollution level is 2 (UL840)
Vibration MIL STD 810C, Method 514.2, EC60068-2-6JIS C60068-2-6 (Sine wave vibration test)
Shock MIL STD 810C, Method 516.2, IEC60068-2-27, JIS C60068-2-27
Noise Immunity
Comply with NEMA ICS3-304, Impulse noise 1µs, 1000VEN61000-4-2 (ESD), EN61000-4-3 (RFI), EN61000-4-4 (FTB)EN61000-4-5 (Surge), EN61000-4-6 (Conducted)EN61000-4-8 (Power frequency magnetic field immunity)RFI: No interference measured at 150 and 450 MHz (5w/15cm)
Emissions EN55011:1998 Class AAgency Approvals UL508 (File No. E157382, E316037); CE (EN61131-2)Other RoHS
Choosing the I/O Type / Specifications
Analog I/O Modules(continued)
Analog Combo I/O Modules
C0-4AD2DA-10-20mA In
4-20mA Out
OUTPUTINPUT
CH10V
CH20V
CH30V
CH40V
CH10V
CH20V
24V0V
C0-4AD2DA-20-10V
OUTPUTINPUT
CH10V
CH20V
CH30V
CH40V
CH10V
CH20V
24V0V
C0-4AD2DA-1 C0-4AD2DA-2
Analog Combo I/O Modules
Part Number Analog Input Type Analog Output Type External PowerRequired
C0-4AD2DA-1 4 channel, current (0-20 mA),13 bit
2 channel, current sourcing(4-20 mA), 12 bit 24 VDC
C0-4AD2DA-2 4 channel, voltage (0-10 V),13 bit
4 channel, voltage(0-10 V), 12 bit 24 VDC
Wiring Solutions using the ZIPLink WiringSystemZZIIPPLinks eliminate the normally tedious process of wiring between devicesby utilizing prewired cables and DIN rail mount connector modules. It's assimple as plugging in a cable connector at either end or terminating wiresat only one end. Prewired cables keep installation clean and efficient,using half the space at a fraction of the cost of standard terminal blocks.
ZZIIPPLinks are available in a variety of styles to suit your needs, includingfeedthrough connector module. ZZIIPPLinks are available for all Basic andStandard CLICK CPU modules and most discrete and analog I/O modules.Pre-printed I/O-specific adhesive label strips for quick marking of ZZIIPPLinkmodules are provided with ZZIIPPLink cables.
Wiring System for CLICK PLCs
Using the PLC CPU and I/O Modules to ZZIIPPLinkConnector Modules selector tables located in this section,
1. Locate your CPU or I/O module. 2. Select a ZIPLink Module. 3. Select a corresponding ZIPLink Cable.
Solution 1: CLICK CPU and I/O Modules to ZIPLinkConnector ModulesWhen looking for quick and easy I/O-to-field termination, a ZZIIPPLinkconnector module used in conjunction with a prewired ZZIIPPLink cable,consisting of an I/O terminal block at one end and a multi-pin connectorat the other end, is the best solution.
Solution 2: CLICK CPU and I/O Modules to 3rd PartyDevicesWhen wanting to connect I/O to another device within close proximity ofthe I/O modules, no extra terminal blocks are necessary when using theZZIIPPLink Pigtail Cables. ZZIIPPLink Pigtail Cables are prewired to an I/Oterminal block with color-coded pigtail with soldered-tip wires on the otherend.
Using the I/O Modules to 3rd Party Devices selector tableslocated in the ZZIIPPLink section,
1. Locate your CPU or I/O module. 2. Select a ZIPLink Pigtail Cable that is compatible
with your 3rd party device.
Solution 3: GS Series and DuraPulse DrivesCommunication CablesNeed to communicate via Modbus RTU to a drive or a network ofdrives?
ZZIIPPLink cables are available in a wide range of configurations for connecting to PLCs and SureServo, SureStep, StellarSoft Starter and AC drives. Add a ZZIIPPLink communications module toquickly and easily set up a multi-device network.
Using the Drives Communication selector tableslocated in the ZZIIPPLink section,
1. Locate your Drive and type of communications. 2. Select a ZIPLink cable and other associated hardware.
Solution 4: Serial Communications CablesZZIIPPLink offers communications cables for use with CLICK CPUs that canalso be used with other communications devices. Connections includea 6-pin RJ12 connector which can be used in conjunction with the RJ12Feedthrough module.
Using the Serial Communications Cables selectortable located in the ZZIIPPLink section,
1. Locate your connector type 2. Select a cable.
CLICK PLC Discrete Input Module ZIPLink SelectorI/O Module ZIPLink
InputModule
# ofTerms Component Module PartNo.
Cable PartNo.
C0-08ND3 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-08ND3-1 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-08NE3 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-08NA 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
C0-16ND3 20Feedthrough ZL-RTB20 ZL-C0-CBL20*Sensor ZL-LTB16-24 ZL-C0-CBL20*
C0-16NE3 20Feedthrough ZL-RTB20 ZL-C0-CBL20*Sensor ZL-LTB16-24 ZL-C0-CBL20*
CLICK PLC CPU Module ZIPLink SelectorPLC ZIPLink
CPUModule # of Terms Component Module Part
No.Cable PartNo.
C0-00DD1-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-00DD2-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-00DR-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-00AR-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-01DD1-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-01DD2-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-01DR-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-01AR-D 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-02DD1-D 20
No ZZIIPPLinks are available for analog CPU modules.C0-02DD2-D 20C0-02DR-D 20
CLICK PLC Combo I/O Module ZIPLink SelectorI/O Module ZIPLink
ComboModule # of Terms Component Module Part
No.Cable PartNo.
C0-16CDD1 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-16CDD2 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-08CDR 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
CLICK PLC Discrete Output Module ZIPLink SelectorI/O Module ZIPLink
OutputModule # of Terms Component Module Part
No.Cable PartNo.
C0-08TD1 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-08TD2 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-08TR 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-08TA 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*
C0-16TD1 20Feedthrough ZL-RTB20 ZL-C0-CBL20*Fuse ZL-RFU202 ZL-C0-CBL20*Relay (sinking) ZL-RRL16-24-1 ZL-C0-CBL20*
C0-16TD2 20Feedthrough ZL-RTB20 ZL-C0-CBL20*Fuse ZL-RFU202 ZL-C0-CBL20*Relay (sourcing) ZL-RRL16-24-2 ZL-C0-CBL20*
C0-04TRS1 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*
1 Note: The C0-04TRS relay output is derated not to exceed 2A per point maximumwhen used with the ZIPLink wiring system.
2 Note: Fuses (5 x 20 mm) are not included. See Edison Electronic Fuse section for(5 x 20 mm) fuse. S500 and GMA electronic circuit protection for fast-acting maxi-mum protection. S506 and GMC electronic circuit protection for time-delay perfor-mance. Ideal for inductive circuits.To ensure proper operation, do not exceed the voltage and current rating ofZIPLink module. ZL-RFU20 = 2A per circuit.
CLICK PLC Analog I/O Module ZIPLink SelectorI/O Module ZIPLink
AnalogModule
# ofTerms Component Module PartNo.
Cable PartNo.
C0-04AD-1 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-04AD-2 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-04RTD 20 No ZIPLinks are available for RTD and thermocouple
modules.C0-04THM 11C0-04DA-1 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-04DA-2 11 Feedthrough ZL-RTB20 ZL-C0-CBL11*C0-4AD2DA-1 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*C0-4AD2DA-2 20 Feedthrough ZL-RTB20 ZL-C0-CBL20*
Wiring System for CLICK PLCs
* Select the cable length by replacing the * with: Blank = 0.5m, -1 = 1.0m, or -2 = 2.0m.