Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
Winnipeg Information Bulletin 2007-002-B/E
CLARIFICATION FOR FIRE ALARM AUDIBILITY IN MULTI-RESIDENTIAL BUILDINGS
Refer to the following pages for the slide presentation…
Issued by: Ken Oertel, Chief Electrical Inspector Development & Inspections Division, Planning Property & Development Department 65 Garry Street • Winnipeg • Manitoba R3C 4K4 August 8, 2007 [email protected] Page 1 of 1
MBC 3.2.4.18.(10) & (11)
• Background: – The 2006 Manitoba Building Code requires that audible fire alarm
devices in suites of residential occupancy be supervised. – This is a change from the 1998 MBC where Sentence 3.2.4.19.(11)
directly stated that the audible devices located within suites of residential occupancy “are not required to have individual electrical supervision.”
– That statement was deleted in the 2006 MBC and although Article
3.2.4.18. doesn’t specifically state that supervision is required, Item 3.3.1.1 in CAN/ULC-S524, Installation of Fire Alarm Systems, does.
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies.
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
Suite signaling device(s) (typ.) Typical Floor Plan
Ten Units Per Floor Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
Suite signaling device(s) (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. Class B wiring c/w isolator modules and E.O.L. resistor in corridor
Suite Isolation Module (typ.)
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. Class B wiring c/w isolator modules and E.O.L. resistor in corridor
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. Class B wiring c/w isolator modules and E.O.L. resistor in corridor
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. Class B wiring c/w isolator modules and E.O.L. resistor in corridor AND Class A wiring between isolators & suite devices – 3.2.4.18.(10)(a)
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. Class B wiring c/w isolator modules and E.O.L. resistor in corridor AND Class A wiring between isolators & suite devices – 3.2.4.18.(10)(a)
Each audible signal device must be supervised!
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. Class B wiring c/w isolator modules and E.O.L. resistor in corridor and Class A wiring between isolators & suite devices – 3.2.4.18.(10)(a)
Unit 2
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. UNACCEPTABLE – Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
Unit 2
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. UNACCEPTABLE – Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
Corridor
Unit 2
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. UNACCEPTABLE – Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
Unit 2
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. UNACCEPTABLE – Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
Unit 2
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. UNACCEPTABLE – Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
THIS IS AN UNACCEPTABLE METHOD
Unit 2
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. UNACCEPTABLE – Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
THIS IS AN UNACCEPTABLE METHOD
Audible signal devices are not supervised!
(was allowed in previous MBC; is no longer acceptable)
Corridor
Unit 2
to FACP
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
Suite Isolation Module (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. UNACCEPTABLE – Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
THIS IS AN UNACCEPTABLE METHOD
Audible signal devices are not supervised!
(was allowed in previous MBC; is no longer acceptable)
Corridor
Unit 2
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
Each audible signal device must be supervised.
The corridor audible circuit must be separate from other floors and from the dwelling units as per MBC Clauses 3.2.4.18.(11)(a) & (b). The circuit can be wired as Class A or B.
Unit 2
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
Audible device
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
Each audible signal device must be supervised.
The corridor audible circuit must be separate from other floors and from the dwelling units as per MBC Clauses 3.2.4.18.(11)(a) & (b). The circuit can be wired as Class A or B.
Unit 2
Typical Floor Plan Ten Units Per Floor
Condos, Apartments
Corridor
to FACP
Audible device
Unit 7
Unit 8
Unit 9
Unit 10
Unit 6
Unit 1
Unit 2
Unit 3
Unit 4
Unit 5
Suite signaling device(s) (typ.)
There are three different methods that may be used to wire in-suite audible signal devices in residential occupancies:
1. Class A circuit (return loop circuit) – 3.2.4.18.(10)(a)
2. Each Unit on separate circuit – 3.2.4.18.(10)(b)
3. Class B wiring c/w isolator modules and E.O.L. resistor in both the corridor and between isolators & suite devices
Each audible signal device must be supervised.
The corridor audible circuit must be separate from other floors and from the dwelling units as per MBC Clauses 3.2.4.18.(11)(a) & (b). The circuit can be wired as Class A or B.