    Bulk requirement of water is used in thermal plantsfor the purpose of cooling the steam in condensers.

    The requirement of water for this purpose is of theorder of 1.5-to2.0 cusecs/MW of installation.

    Where sufficient water is available once throughsystem is used.

    Where water supply is not consistent, closed loopcooling system with cooling tower is used.

  • 7/30/2019 Circulating Water System

    3/44

    24 December 2012 3

    A circulating water pump house

    Intake channel

    Trash rack

    A chlorination plant

    Traveling water screen

    Connecting pipe line to condenser

    Outlet channel

    A cooling tower

  • 7/30/2019 Circulating Water System

    4/44

    24 December 2012 4

    We shall discuss the open loop system first.

  • 7/30/2019 Circulating Water System

    5/44

    24 December 2012 5

    A circulating water pump house

    It houses the main CW pumps. Vertical

    submergible pump with operating pressure

    around 1 Kg/ cm2.

    The pump house resides on the fore bay.

    The fore bay is flooded through intake system.

  • 7/30/2019 Circulating Water System

    6/44

    24 December 2012 6

    It is RCC open trench from where Raw water is taken

    through canal/reservoir. The intake level is normally 10-15 ft. above from flood

    level of the water source and 12 m in depth.

    Intake

    Trash Rack

    Trash rack to avoid entering wood, tree branches, animal,plastic, floating object.

    provides uniform flow/suction to the CW pump

    Traveling Water Screen

    It catches small pieces of coal, sand, gravel, wood,plastic, herbs, leaves which can go into the impeller andmay choke/damage the pump.

  • 7/30/2019 Circulating Water System

    7/44

    24 December 2012 7

    Chemical dosing done for disabling micro organismdevelopment inside the tube.

    Condenser is fitted with 4 way valve to enablereverse flow through condenser when required.

    Hot water coming out from condenser is allowed topass through long outlet channel to get cool down

    before meeting the main stream of water. Performance of condenser mainly depends on Inlettemp. to the condenser, Condenser tube fouling, Airingress in condenser etc.

  • 7/30/2019 Circulating Water System

    8/44

    24 December 2012 8

    Open Loop system:

    Water is abundant

    Reduction in the APC..

    Condenser

    River Flow

    Steam from Turbine

    Pump

    Hotwater

    Cold Water

  • 7/30/2019 Circulating Water System

    9/44

    24 December 2012 9

    CW scheme

    Reservoir/ River Canal Intake

    Trash rack

    TWS

    CW pumps

    Condenser

    Hot Pond

    CT pumps

    Cooling tower

  • 7/30/2019 Circulating Water System

    10/44

    24 December 2012 10

    HotPond:

    Hot Water from the condenser discharged to hot pondand provide source for the CT pump.

    CT Pump

    It takes suction from the Hot pond and discharged

    the water to the riser tubes of Cooling towers

  • 7/30/2019 Circulating Water System

    11/44

    24 December 2012 11

    Cooling Tower - Introduction

    A cooling tower is an air and water management

    device, which consists of fan stacks, fans, drift

    eliminators, fill and water/air distribution systems. It uses principle of evaporation of water in

    unsaturated air.

  • 7/30/2019 Circulating Water System

    12/44

    24 December 2012 12

    Cooling Tower - Introduction

    Cooling tower is the most important equipment for

    closed cycle water recirculation system.

    The efficiency of cooling tower has direct effect on

    condenser vacuum and in turn, the heat rate of thestation.

    1oC rise in cold water temperature in a 200MW unit

    corresponds to 5mm vacuum loss leading to 7.5Kcal/kwh loss in heat rate and in 500MW, 5.74

    Kcal/kwh loss in heat rate..

  • 7/30/2019 Circulating Water System

    13/44

    24 December 2012 13

    Wet type

    Dry type

    Wet type cooling towers are two type

    1.natural draft 2.mechanical draft

    Mechanical draft may be devided in to two type

    1.forced draft

    2.induced draft Both of these can be counter flow type or cross flow

    type.

  • 7/30/2019 Circulating Water System

    14/44

    24 December 2012 14

    Cooling Towerin NTPC Ltd.There are 75 cooling towers in operation in NTPC.

    Induced Draught Cooling Towers

    Cross flow type 24 Counter flow splash bar fill type 21

    Counter flow film fill type 20

    Natural Draught Cooling Towers

    Natural draught type. 08

  • 7/30/2019 Circulating Water System

    15/44

    24 December 2012 15

    It produces air flow through utilization of stack orchimney effect.pressure diff. causing air flow isgiven by p (pr head developed)=(p outer-p

    inner).H.g The fill is located in the lower portion of shell with

    upper 85 to 90% of shell empty which is used tocreate chimney effect.

    They are more suitable in the area of high relativehumidity and low temp.

    They may be of cross flow or counter flow.

  • 7/30/2019 Circulating Water System

    16/44

    24 December 2012 16

  • 7/30/2019 Circulating Water System

    17/44

    24 December 2012 17

    Forced draft

    Advantage:-fan is subjected to less severecondition

    Disadvantage:-recirculation more Induced draft

    Advantage:-min recirculation

    Disadvantage:-fan is subjected to warm humidcondition.

  • 7/30/2019 Circulating Water System

    18/44

    24 December 2012 18

    Counter flow :-fill is arranged over entire towerplan.fill is typically film type.

    Advantage:-more thermal efficiency, smallesttower,lower capital cost, lower pumping head

    Disad:-increased pressure drop requires morehorse power of fan.

    Cross flow:-fill is arranged at the outer perimeter.

    Advantage:-large air inlet area hence pressure dropis less.

    Disad:-high pumping head due to more height of fill.

    MECHANICAL DRAFT C.T.

  • 7/30/2019 Circulating Water System

    19/44

    24 December 2012 19

  • 7/30/2019 Circulating Water System

    20/44

    24 December 2012 20

    T f C li T

  • 7/30/2019 Circulating Water System

    21/44

    24 December 2012 21

    Types of Cooling Towers

  • 7/30/2019 Circulating Water System

    22/44

    24 December 2012 22A BIRDs EYE VIEW OF NDCTs OF DADRI-Coal (4 X 210 MW)

  • 7/30/2019 Circulating Water System

    23/44

    24 December 2012 23

    1.Rectangular type:-each cell indentical, more long

    area required, low capital cost,for plant upto

    250mw.

    2.Round type:-less recirculation, more capitalcost,for plant more than 250mw.

  • 7/30/2019 Circulating Water System

    24/44

    24 December 2012 24

    Parameters are used to develop the tower design :

    Water flow rate Cooling range

    Design Heat load

    Design Wet-bulb temperature.

    Recirculation and interference

    DBT and relative humidity

  • 7/30/2019 Circulating Water System

    25/44

    24 December 2012 25

    Condenser and c.t. are designed on the basis of

    MCR load point.

  • 7/30/2019 Circulating Water System

    26/44

    24 December 2012 26

    The impact the design wet-bulb temperature has on the

    size and power requirements of a cooling tower is criticalto optimizing the cooling tower economics.

    In the majority of applications, the design duty of anevaporative cooling tower is based upon anacceptable/required cold water return temperature

    If investment and operational costs were not a concern,the ideal design wet-bulb temperature would be equal to,or higher than, the highest local wet-bulb temperaturerecorded.

    In this way, the returned water temperature would neverbe higher than the acceptable/required cold watertemperature.

    Design W.B.T.=DESIGN AMBIENT D.B.T.-RECIRCULATION ALLOWANCE.

  • 7/30/2019 Circulating Water System

    27/44

    24 December 2012 27

    The component most likely to provide improvementin tower performance is the fill packing.

    The earliest and most common designs utilized

    splash type fills Film type counter flow designs using relatively low

    cost PVC materials.

    The new film type designs provide energy savings

    both in fan power and pump head through the highsurface areas per cubic feet of fill.

  • 7/30/2019 Circulating Water System

    28/44

    24 December 2012 28

    Splash type consisting of splashBars used for crossflow and

    Counterflow.

    Film type consisting of thin film of

    Sheets used mostly for counterflow

  • 7/30/2019 Circulating Water System

    29/44

    24 December 2012 29

    In splash fill, the hot water strikes the bar and

    breaks up into many smaller drops.

  • 7/30/2019 Circulating Water System

    30/44

    24 December 2012 30

    Film fill consists of flat or formed sheets to provide

    a surface upon which water and air come in

    contact for heat exchange.

  • 7/30/2019 Circulating Water System

    31/44

    24 December 2012 31

    A cooling tower drift eliminator is a low pressure,

    momentum filter. Components are arranged to force the air leaving the fill

    section to make a series of directional changes.

    Water droplets, which cannot negotiate these turns,impinge on the surface of the eliminator, from which they

    are collected and drained back into the wet side of thetower.

    The designer's goal is to provide the maximum driftelimination at reasonable cost and minimum pressureloss.

    The design of drift eliminators has undergonetremendous improvement in the last decade.

    New eliminator configurations accomplish thisimprovement while actually reducing eliminator pressure

    losses

  • 7/30/2019 Circulating Water System

    32/44

    24 December 2012 32

    Drift Eliminators

    Cellular eliminators are typically constructed of PVC

    sheets vacuum formed into very precise, compound

    shapes, with an integral honeycomb strength. The

    compound shape allows significant improvements indrift eliminations and the use of cellular structure

    appreciably reduces the pressure losses through the

    eliminator when compared to either the wood lath or

    wave form eliminators.

    The net free are of well-designed, modern cellular

    eliminators is in excess of 95%.

  • 7/30/2019 Circulating Water System

    33/44

    24 December 2012 33

  • 7/30/2019 Circulating Water System

    34/44

    24 December 2012 34

    Air-Water Distribution System Design1) Water Distribution:

    Assured performance is a function of nozzle design, nozzle installationpattern, nozzle distance, and the structural cleanliness of the spraychamber.

    To provide the primary function of precise water distribution, thenozzle must be designed with other considerations in mind:

    The location of counter flow nozzles and the potential for poor qualitycirculating water demands that the nozzle system be designed tominimize fouling.

    The nozzle must be capable of providing uniform distribution over awide range of flows, without significant loss in nozzle performance.

    The nozzle must be capable of efficient operation while consuming aminimum of expensive pump energy.

  • 7/30/2019 Circulating Water System

    35/44

    24 December 2012 35

    Air-Water Distribution System Design2)Air Distribution: Three variables control the distribution of air to

    the fill in a counter flow configuration.

    The first is the air inlet geometry.

    Pressure Ratio : The pressure ratio reflects the ratio ofresistance to available entering air energy. The higher the ratio,the better entering air will be spread out before entering the fill.The lower the pressure ratio, the less uniform, and less stablethe distribution of air flow becomes. The degradation of air flowuniformity is readily apparent, particularly at the inlet.

    (Pressure Ratio = Static Pressure / Velocity Pressure at Air Inlet)

    The third is the fan coverage over the eliminators

  • 7/30/2019 Circulating Water System

    36/44

    24 December 2012 36

    Each fan has only one design point which isestablished by a specific air flow, total pressure,air density, and fan speed.

    The factors that must be known when replacing

    a fan on an existing installation are:

    1. Fan diameter.

    2. Installed motor horsepower.

    3. Gear reduction ratio of gear reducer.4. Shaft size or gear reducer model.

    5. Some estimate of elevation above sea level ofinstallation.

  • 7/30/2019 Circulating Water System

    37/44

    24 December 2012 37

    Cooling Tower Performance

  • 7/30/2019 Circulating Water System

    38/44

    24 December 2012 38

    Cooling Tower Performance

    Cooling Tower Effectiveness=ActualCooling/Maximum Cooling Possible =Range/(Range+Approach)

    Cooling Tower Capacity = mass flow rate X specificHeat x Temperature Difference

    Evaporation Loss in cub mtr/Hr =0.00085x1.8xcirculation rate x Temperature Diff.

    Cycle of Concentration = Dissolve solid in circulatingwater/Dissolve solid in make up water

    Blow Down =1-1.5 percent of total water flow

    To replenish the losses make up water 2-2.5% ofwater flow is added

  • 7/30/2019 Circulating Water System

    39/44

    24 December 2012 39

    Intake Channel Level (Normal)---------- 202 mtrs

    C.T.PUMP

    Nos 2 for each 210 MW unit

    Discharge 4160 L/sec or 15000 m cube per hour

    Head 17.855 mwc

    Speed 405 rpm

    Make KIRLOSKAR BROTHERS LTD.(U5)

  • 7/30/2019 Circulating Water System

    40/44

    24 December 2012 40

    Type Induction Motor

    Speed 421 rpm

    KW 930

    Current 108.5 amps

    Volts 6600 volts, 3 Ph. 50 C/S

    Make BHEL

  • 7/30/2019 Circulating Water System

    41/44

    24 December 2012 41

    Make Gammon(U4)/ Paharpur(U5)

    Number 1 for each unit of 210 MW

    No. of cells/tower 16

    Rate of flow/unit 27000 m cube per hour per tower

    Cooling Range 10 degree C

    Max operating inlet water temperature 50 degree C

  • 7/30/2019 Circulating Water System

    42/44

    24 December 2012 42

    Fan Type Induced Draft

    No of fans/Tower 16

    No of blades/fan 9

    No of row of fan 2(8 in each row)

    Dia. 7315 mm

    Reduction gear Ratio 10:1 L.X.

    Fan Speed 151 rpm

  • 7/30/2019 Circulating Water System

    43/44

    24 December 2012 43

    Make N.G.E.F

    Volts 415 V

    Current 130 amps

    K.W. 75

    Speed 1475 rpm