57
CII CII 19 TH NATIONAL AWARD FOR EXCELLENCE IN ENERGY MANAGEMENT-2018 PRESENTED BY: - MR NEERAJ TANDON CHIEF ENGINEER FORTIS HEALTHCARE LTD, MOHALI 1

CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

CII

CII

19TH NATIONAL AWARD FOR

EXCELLENCE IN ENERGY

MANAGEMENT-2018

PRESENTED BY: - MR NEERAJ TANDON

CHIEF ENGINEER

FORTIS HEALTHCARE LTD,

MOHALI 1

Page 2: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

FHM- BRIEF INTRODUCTION

Number of Buildings: 3• IPD Block (A block)• OPD Block (B block)• Rehabilitation Centre• Fortis Cancer Institute

Fortis Hospital Mohali Establishes in 2001, and today we are considered to be one of India's most recognized Super specialty hospital.

Hospital set on sprawling 8.22 acres, with built up area of 50336 square meters.

FHM is a 360(435) bedded, JCI and NABH certified multi specialty tertiary care hospital,

Fortis Hospital, Mohali has won several awards, including; Best Design Award from American Institute of Architects,1999

Best Design Award from American Institute of Architects,1999

REHAB

BUILDIN

G

BUILDIN

G B

BUILDING

A

FCI

BLOC

K

Approx 2000 sq.ft/cardiac ICU bed instead of the normal 800-900

sq.ft./in Indian healthcare.

2

Page 3: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

SPECIFIC ENERGY REDUCTION

Parameter 2011-12 2012-13 2013-14 2014-15 2015-16 2016-17 2017-18

KWH 7487915 7138206 7058913 6998773 6805785 6568395 6362423

SEC in kWh/M2 179 149 145 141 137 130 125

Total kWh/Bed 26838 24530 21787 20111 16014 15100 14626

No. Of Beds 279 291 324 348 425 435 435

Average Occupancy

76% 73% 78% 82% 88% 89% 89%

Built Up area 41,760 47,791 48,719 49,720 49,720 50,336 50,336

3

Page 4: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

ENERGY CONSUMPTION TRENDS

4

56.00

58.00

60.00

62.00

64.00

66.00

68.00

70.00

72.00

74.00

76.00 74.88

71.3870.59

69.99

68.06

65.68

63.62

KWH

EPI DOWN

BY 29.39%

National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy

Efficiency, Govt. of India ECO-III project)

150

200

250

300

350

400

363

309 303293 295

285

CO

NSU

MP

TIO

N IN

KLi

tre

s

HSD Consumption

YEAR HSD (kl)

2012-13 363

2017-18 285

SAVINGS 78

Page 5: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

YEARKWH

(LAKH)

2011-12 74.88

2017-18 63.62

SAVINGS 11.25

National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India ECO-III project)

29.3

9%

Reduction0

20

40

60

80

100

120

140

160

180

200

2011-12 2012-13 2013-14 2014-15 2015-16 2016-17 2017-18 BenchMark

179

149 145 141 137130 125

200

SPECIFIC ENERGY CONSUMPTION in kWh/M2

5

Page 6: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

6Reference A report on Energy efficient hospitals survey by CII, Schneider and S.L.Raheja

NATIONAL BENCH MARKING (KWH/SQM)

0

50

100

150

200

250

300

350

400

277296

222 233

355

125

237

293

181

344

204226

Specific Energy Consumption (kWh/Sqm/Year)

Page 7: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

7

EPI Index across Fortis Hospitals

Energy performance Index for Fortis Group Hospitals All Weather

0

50

100

150

200

250

300

350

400

450

202

102

252

125

176

211 221202

268

192

413

240

368

229

323

279

139

166

221

Energy performance Index

Page 8: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

8

International Benchmarking

0

50

100

150

200

250

300 263

225205

143125

205

Specific Energy Consumption - kWh/SqMtrs/year

UK- Typical Practice

Germany -Typical Practice

Serbia-After Refurbishment

UK-General Acute Hospital

Fortis Hospital Mohali

International Bench Mark

Comparison of building energy benchmarks in Serbia, UK and Germany

(CIBSE TM 46), (EnEv)----- KWH/M2

Page 9: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

BENCHMARKING – ENERGY USAGE- OUR CHALLENGES

Current – Consumption patterns ,Perpetual growth in facilities, diagnostic

equipments, additional beds thus increased Energy.

Consumption patterns aren’t fixed, they vary depending on the number of

occupied beds, the footfalls & the local weather conditions. Increasing

energy &Maintenance costs.

EquipmentAvg.

Consumption

HVAC (heating, ventilation,

& air conditioning)45-50%

Lighting 10-15%

Medical Equipment 15-20%

Boilers 8-10%

Water Systems 5-10%

DG Sets (Diesel generator) 1-2%

Laundry 2-3%

Medical Gases 1-2%

STP (sewage treatment

plant)1-2%

Lighting 10- 15%

Medical Equipment

15-20%

Boilers 8-10%

Water Systems 5-10%

DG Sets 1-2 %

Laundry 2-3%

STP 1-2%

Medical Gases 1-2%

HVAC 45-50%

1-1.5 % of

Revenue

now spent

on Energy

9

Page 10: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

60126246

7009 7116 7290

7526 7695179149

145 141

137 130

0

20

40

60

80

100

120

140

160

180

200

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

2011 -12 2012 -13 2013 -14 2014 -15 2015-16 2016-17 2017-18

CO

NN

EC

TE

D L

OA

D I

N K

WH

Additional Load & Specific Energy Consumption YOY

SE

C (

KW

H/S

QM

)

New Machines MRI

3 TESLA Robotic OT Equipments

Elevators/New areas AHU’s

Machines Gamma Scan

and Food outlets

135

How to

further nullify

the effect?

125

10

Page 11: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Power Saving Projects

People Involvement

Engineering Control

New Technology

Productivity Improvement

Renewable Resources of Energy Power

Saving Projects

Ideal V/s Actual

People Involvement

Engineering Control

New Technology

Productivity Improvement

Renewable Resources of Energy

How to

minimize

the impact

of

Additional

Electrical

Load

Conventional

Approach New Approach

Time for a Paradigm

Shift?

Reduce

Recycle

Reuse

Approach followed for Power Consumption Reduction

11

Page 12: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

ROAD MAP TO ACHIVE BENCHMARK /GLOBAL BEST

Review existing power distribution system & identifying patterns of

different loads

Measuring the consumption by providing meters

for all loads.

Monitoring and analysis of high power

consuming equipment patterns & trends

Automation of building services like

HVAC, Lighting, Water and power

management, etc.

Utilize advanced technologies,

innovative & creative ideas.

Measure the savings inline with global

and national bench mark.

Implementing energy saving initiatives.12

Page 13: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Formation of Encon Teams

Measuring the Consumption

by metering the key

locations

Comparing the expected

savings with benchmark

Root cause

analysis

Rectification &

Trending

Further process

improvements by

innovation

Create new

standard/benchmark

Consumption

Monitoring

If No

If

Yes

13

ENERGY CONSERVATION IMPLEMENTING METHODOLOGY

Page 14: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

ENERGY CONSERVATION PROJECTS

New Technology

Renewable

Energy Substitu

tion

Optimum Utilizatio

n

• Solar Photovoltaic Lighting

• CNG/PNG for Boilers

• Geothermal system for water

cooled chillers

• Hot Water generation

through Solar water heater

system

• Water conservation

• HSD consumption reduction

Waste Heat Recovery

(Condensate/Process)

VFD on Identified AHU’s

Sharing one AHU for two

OT’s during night hours

Power factor improvement

Reduction in ripple factor

&PF improvement

• Replacement of Fluorescent

tube/lights with LED Lights

• Replacement of screw chillers

with energy efficient centrifugal

chillers

• Installation of VFD drives with

water pumps

• Replacement of vacuum pumps

with energy efficient VFD

operated vacuum pumps14

Page 15: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

15

Sr. No.

Title of ProjectElectrical Savings (Kwh)

HSD Saving

(KLitres)

Annual Savings

(Rs. Lakhs)

CO2e Reduction

(MT)

12x20kva and 2 x60 kva ups got stopped and connected with central UPS thus optimized its operation (2015-16)

225000 0 16.78 184.5

2On line monitoring of chillers and strict controls on validation velocity meters by entire area (2015-16)

75000 0 5.36 61.5

4AHU ‘s Running Optimized by One AHU feeding two OT’s during nights/non operation hours (2015-16)

48000 0 3.6 39.36

5Water conservation by utilizing STP Water in Toilets as wel as Cooling Towers (2016-17)

10000 0 1.2 8.2

6To convince Cardiac Consultants to stop two Cath Lab machines during night (2016-17)

37000 0 3.55 30.34

7 Switching off 50% Elevators during non peak hours (2016-17) 57000 0 4.29 46.748 Switching off Standby Transformer during winters (2016-17) 21000 0 1.61 17.22

9Condensate recovery from boilers as increase in boiler steam (2017-18)

0 0.25 2.7 0.66

10 Chillers Condenser tubes and Strainer cleaning (2017-18) 80000 0 6.5 65.611 Cooling Tower maintenance and cleaning (2017-18) 20000 0 1.5 16.412 Boilers Tube descaling (2017-18) 0 0.17 1 0.45

13 AHU and FCU Coil cleaning and descaling (2017-18) 56000 0 4.5 45.9214 Gas range burner cleaning and leak testing (2017-18) 18600 0 1.5 15.25

Savings 684600 0.42 56.88 562.48

List of EnCon Project with Zero Investment (2015-18)

Page 16: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

16

Another ENERGY EFFICIENT COOLING TOWER replacement (Balance left)

Replacement of energy efficient primary and secondary pumps and condenser pumps as per tailor made design

Highly energy efficient elevator installed with approx. 55% energy efficient gearless motor for cons

Replacement of Conventional Motors with Energy Efficient Motors.

Energy efficient LED lights Placed at Number of Places (2nd phase)

3.06LkWh

Rs.24.4Lacs

Rs. 24.48Lacs

0.60LkWh

Rs.4.50 Lacs

Rs. 8.02Lacs

PROJECT TITLE SAVINGS/YEAR Investment

0.58LkWh

Rs.3.98 Lacs

Rs. 30Lacs

1.00LkWh

Rs.7.50Lacs

Rs. 4.25Lacs

2.69LkWh

Rs.15.8Lacs

Rs. 17.23Lacs

List of EnCon Project with Investment (2015-16)

CO2 EMISSIONS REDUCTION- 650MT/PA

Page 17: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Replacement of Old Compressor with VFD operated Efficient Motor

VFD on AHU's identified for OT Operations

Replacement of Old inefficient Cooling Tower with new High Efficiency Cooling Tower

LED Lights Replacement for 2500 balance CFL Lights

200Kw Solar Photovoltaic Roof Top Plant

Addition in Capacitors in Capacitor bank as well as machines end

PROJECT TITLE SAVINGS/YEARInvestment

0.28LkWh

1.21LkWh

0.20LkWh

1.16LkWh

3.0LkWh

0.50LkWh

Rs.3.0 Lacs

Rs.13.31 Lacs

Rs.2.46Lacs

Rs.12.93 Lacs

Rs.34.82Lacs

Rs.3.75Lacs

Rs. 4.0Lacs

Rs. 4.50

Lacs

Rs. 7.0Lacs

Rs. 5.0Lacs

Rs. 98.0Lacs

Rs. 1.10Lacs

List of EnCon Project with Investment (2016-

17)

17

Page 18: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Installed PowaTrim to at main EB incomer

To protect against spikes etc. and improves PF.

Water Conservation by utilizing STP water in toilets etc.

HSD savings in Boiler steam

PROJECT TITLE SAVINGS/YEARInvestment

1.68LkWh

0.10LkWh

1.21LkWh

Rs.13.51Lacs

Rs. 10.67Lacs

Rs.3.0 Lacs

Rs. 6.0Lacs

Rs.13.31 Lacs

Rs. 4.50Lacs

List of EnCon Project with Investment (2016-

17)

18

CO2e REDUCTION

770 MT/PA

Page 19: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

PowaTRIM to reduce harmonics and Power Consumption (Second Phase)

VFD on identified AHU's

LED Lights Replacement for Balance CFL Lights phase v

Replacement of old Vacuum Pumps with new VFD operated Vacuum Pumps

Water conservation

174kW Solar Photovoltaic Lighting for parking

PROJECT TITLE SAVINGS/YEARInvestment

1.69LkWh

0.70LkWh

0.50LkWh

0.30LkWh

0.10LkWh

2.50LkWh

Rs.13.27 Lacs

Rs.5.50 Lacs

Rs.3.93Lacs

Rs.2.60 Lacs

Rs.1.30Lacs

Rs.19.65Lacs

Rs. 10.67

Lacs

Rs. 5.0Lacs

Rs. 10.0Lacs

Rs. 14.0Lacs

Rs. 0.70Lacs

Rs. 90.0Lacs

CO2 EMISSIONS REDUCTION- 470 MT/PA

List of EnCon Project with Investment (2017-

18)

19

Page 20: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

CONDENSOR TUBE CLEANING

GOOD ENGINEERING PRACTICES

20

AHU SERVICING AND DESCALING

BOILER TUBE DESCALING

COOLING TOWER

MAINTENANCE

LPG LEAK TESTING AND ARRESTING

Page 21: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Energy saving calculation is determined on the basis of actual kW consumption

of old and new pumps.

Running hrs of chiller-3 & 4 are 6000 hrs/year as per average for last 2.5 years.

On analysis we find that the total electrical energy saving is 306000 kWh/year.

Total monetary saving is 22.03 Rs Lakh/Year.

Payback period for pumping system is 13 months.

Before After

CO2 EMISSIONS REDUCTION- 258.88 MT/PA

Encon Project- New Energy Efficient Tailor

made designed Pumps in HVAC section with VFD

21

Page 22: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

ENCON PROJECT- LED LIGHTS REPLACEMENT

FOR BALANCE CFL LIGHTSCost Benefit Analysis

Energy Savings 50000 kWh/Year

HSD Savings 4000 Ltrs/YearsCost Savings 6.5Lacs/YearInvestment 10.0 LacsPayback 18 Months

Statement

• As a part of Energy conservation

afford balance left out CFL lights

replaced with LED Lights

• 5 years warranty, hence R&M cost

reduced

• 40-45% energy savings

CO2 EMISSIONS REDUCTION- 118.11 MT/PA22

Before After

Page 23: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Cost Benefit Analysis

Energy Savings 10000 kWh/YearHSD Savings 1000 Ltrs/YearsCost Savings 1.30 Lacs/YearInvestment Rs.70000Payback 24 Months

Statement

• To maintain Ground water table, water conservation project selected

• Reduction in bore well usage• 2-3% energy savings• 10-12% bore well water saved

CO2 EMISSIONS REDUCTION- 10.8 MT/PA

ENCON PROJECT- WATER CONSERVATION BY UTILIZING STP WATER IN TOILETS AS WELL AS COOLING TOWERS

23

Page 24: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

ENCON PROJECT- VFD ON AHU’S IDENTIFIED FOR

OT OPERATIONS

CBA

Energy Savings 70000 kWh/Year

Cost Savings 5.5Rs Lacs/Year

Investment 5.0Rs Lacs

Payback 11 Months

Statement

• Wasteful Energy losses were

controlled during night hours by

placing VFD’s for energy saving

purpose

• 15-20% energy savings

CO2 EMISSIONS REDUCTION- 123.27 MT/PA24

Page 25: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

COST BENEFIT ANALYSIS

Energy Savings 20000 kWh/YearHSD Savings 2000 Ltrs/YearsCost Savings 2.46 Lacs/YearInvestment 7.0 LacsPayback 32 Months

Statement

• As a part of Energy Saving initiative

end of life equipment contributing

energy losses, were planned to

replaced

CO2 EMISSIONS REDUCTION- 21.6 MT/PA

ENCON PROJECT- REPLACEMENT OF OLD

INEFFICIENT COOLING TOWER WITH NEW HIGH

EFFICIENCY COOLING TOWER

25

Before After

Page 26: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

• 23.3% reduction achieved in last 3 yearsEnergy Efficiency

• 21.1% reduction in last 3 yearsWater Conservation

• Using 21 % Renewable EnergyRenewable Energy

• 37.6% Reduction in GHG Emission since last 3 yearsGHG Reduction

ENCON EFFORTS: KEY IMPACT

Special Focus on Reduction of “Energy” and “Water” Consumption

• 31% Reduction in thermal energyThermal Energy

• 18% Reduction in Hazardous Waste and 22% Reduction in Process Effluent in last 3 years

Water Management

• Environment friendly HK/Cleaning agents & Chem.

Green Supply Chain

• 10 Project recognized as innovative projects

• Started use of Eco friendly HK chemical and paintsOthers

Key ImpactArea

26

Page 27: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Innovative Project (1)

Optimum and Efficient usage of Vacuum Pump Operation

Obeservations:With increase in bed strength and foot falls there is a

growing need to have sufficient backups. Vacuum pumps are needed to

provide suction in operation theatres.Engineering team came up with the

idea of replacement after observing the energy consumption on pumps.

Challenge: Old Vacuum Pumps were not giving optimum results and

huge energy losses were felt besides increased maintenance costs

Alternate Available: i) Additional new Oil based Pump

ii) VFD operated pump

.

27

Page 28: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Innovative Project (1)

Action Plan:

Phase -1

Planned and stopped the Vacuum Pump during idle time at night after complete

overhauling.

Phase -2

Replaced the Vacuum Pump with VFD operated and high efficiency motor.

Results achieved after Replacement

Annual Energy Consumed (KWh) 216775

Annual Energy Cost (In kWh.) 186773

Energy Saved (In KWh) 30002

Energy Cost Saved Annually (in

Rs.) 240016

Before modification : Running hrs

38 hrs/day

After modification: Running Hrs

24 hrs / day 28

Page 29: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Renewable Energy Optimization

Why Innovative: Parking was shaded with Bougainvillea besides some

tree/poles shades were around giving shadow.

With organizations striving to compete in tight business and complex

Especially when it comes to clean energy. Fortis Engineering took

the initiative to convince the management besides evaluated the

results of roof top plant.

After observing the data on year to year basis Engineering team felt the

need that a lot of energy can still be utilized if we place more Solar

panels. Again Engineering team suggested the idea.

Action Plan

o After deciding the sun pattern convinced the Management for placing

another lot of Solar PV panels on Attendants parking, will serve two

purposes.

o 1 Shade for the parked vehicles

o Automatic clean energy generations

Innovative Project (2)175Kw Car Parking

Solar Plant

29

Page 30: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

INNOVATIVE OPTION -175KW CAR PARKING

SOLAR PLANT

Choosing the best proposal: Convinced the Management for the

PV panels at parking lot as well after first project got successfully

commissioned in 3 months.

Costing Analysis: The parking project was estimated to be a

costly one due to hindrances, shadow and other problems like

dust etc.

Commissioning : Project commissioning was done and phase

wise trial taken for validating the desired vs actual results.

Before After

BEFORE AFTER

CO2 EMISSIONS REDUCTION- 211.50 MT/PA

Cost Benefit

Energy Savings

250000 kWh/Year

Pay back yrs 4 years

30

Page 31: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Innovative Project-3Harmonic reduction in DG sets and Improvement in PF there by reducing

Inductive current in Chiller OperationReducing kVAh based electricity cost &

consumption. Harmonics play an

important role especially in hospital

services where in a lot of electronic as

well as Inductive loads are In use.

Engineering faced a problem when we

sank a new generator of 1250 KVA with

existing old ones of similar ratings. At

times it was getting trips on load as well

as immediately after operation

31

Energy Conversion - Generates current via reactive load produced by site inductive

loads. Current is then injected into the adjacent phases as new, usable power

available towards your Main Incomer.

Power Factor - resonance-free power factor correction to reduce the demand of

reactive non-power currents.

Phase balancing - of voltage and current to reduce waste, demand, friction and

heat in loads.

Harmonic Protection - filtering of non-power currents to reduce the billed

kVAh/kWh consumption

In summary: PowaTRIM returns

out-of-phase power into your

electrical grid. PowaTRIM does

this without consuming energy. It

uses the inductive power you’re

already consuming and re-

introduces this surplus power

onto the adjacent phases.

Page 32: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Action Plan:

Trial with one module on chiller

was chosen as inductive load

of motor was high. PowaTRIM

returns out of phase power into

electrical grid bus bar.

Hence one 150A of load per Powa

TRIM Module was placed which

converted 25kVAr in 18 KVA resulted

not only 8-12% reduction in kVAh

electricity consumption but above all

it corrected the PF, AND REDUCED

THE HARMONICS

Source: Vendor suggested to

implement the Powa Trim.

32

Average kVAh savings per hour 18

hours per day 24

days per annum 275

kVAh savings per annum 118,800

kVAh cost in Rps Rs. 8

Gross Savings per annum Rs. 9.50 lakhs

ROI in Months 11

Cost Benefit

Harmonic reduction in DG sets and Improvement in PF

Page 33: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

SOLAR PHOTOVOLTAIC 200KW ROOF

TOP PLANT & 175 KW CAR PARKING

CBAEnergy Savings 5.75LkWh/YearHSD Savings 0.26KLtrs/YearsCost Savings 56.82 Lacs/YearInvestment 108.0 LacsPayback 36 Months

For clean/renewable energy initiative

rooftop and Car Parking was utilized by

placing 200Kw & 175Kw clean energy

Solar PV panels thus reducing the heat load

on Third floor beside generating renewable

energy

• 3-4% EB units savings

RENEWABLE ENERGY RESORCES

CO2e Reduction 520MT33

Solar water heating 8000Ltr/Hrs

Outcome:

• 57 Tones of CO2

• Equivalent 148 trees planted

• Savings in Million Rs. 1.98

Page 34: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Environment projects & Projects linking with Carbon Emission

Reduction

Developed Green Landscape

The Hospital consists over 45% oflandscapes with over 150 varieties ofgreen plantation of native, less waterconsumption plants. Hence reduction inwater and power consumption whichcaters to reduction in carbon emissionand environmental friendly.

Rain water harvesting pits

Creation of rain water harvestingpit which is having the capacity topercolate over 76% of rain waterconsidering 3 years of averagerainfall. Which is environmentalfriendly as it improves groundwater table.

34

Page 35: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

ENCON ROADMAP – SUSTAINING CONTINUAL

IMPROVEMENT

Condensate

recovery

from Boilers

0.25KLtrs

HSD & 1MT

CO2e

Energy

Efficient LED

Lights Phase

II

0.50LkWh

Energy &

41CO2e

VFD Operated

Vacuum

Pumps

0.30LkWh

Energy &

25MT CO2e

Solar Water

Heating

System

0.50 LkWh

Energy & 42

MT of CO2e

Solar

Photovoltai

c Lighting

5.75LkWh Energy

& 471 MT of

CO2e

Right now % Reduction

in EPI29.39%

PNG for

Boilers

277KLtrs HSD

& 731 MT of

CO2 e

19.2% by 2018

PowaTrim

1.69LkWh

Energy &

139MT

CO2e

ENCON Roadmap – Sustaining continual

improvement

35

Page 36: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Carbon Footprint Reduction

Reference IFHE : International Federation of Hospital

Engineering 2013

0.00

5.00

10.00

15.00

20.00

25.00

22.01

20.11

17.87

16.49

13.1312.38 11.99

20.98

CO

2 in

To

ns

ANNUAL CO2e/BED IN TONS

0

100

200

300

400

500

600

700

800

900

1000

0

286.76

351.78

401.10

559.35

754.01

922.90

Saving in Tons CO2 Emission in Tons

Total CO2e Saving

3538Tons36

Page 37: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

• 240 KLD Sewage Treatment plant with

ultra filtration membrane.

• 100% Recycled water using for

irrigation, cooling tower and

flushing system. Zero discharge

• Segregation of dry and wet waste . Compost being made from Kitchen wet waste. Manure thus produced is used in horticulture and rest being sold to nursery. 3.0 lakhs PA is saved so far and we intend to increase more containers.

DRY AND WET GARBAGE FROM KITCHENSEWAGE TREATMENT PLANT

37

UTILIZATION OF WASTE MATERIALS

Page 38: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

UTILIZATION OF WASTE MATERIALS

STP Water is reused in gardening, Irrigation and in cooling towers, toilets.

Newspaper & waste papers are sent to Rainbow, for recycling.

Plastic, Polythene is send to recycling.

Hospital waste segregation and its disposal as per the PPCB guidelines.

Used Engine oil & lubricant materials are sending to authorized recyclers

Used Batteries are send to authorized agency by Punjab Pollution Board.

38

Page 39: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

WE BELIEVE IN

• Identify, control and

endeavor to reduce

emissions, waste &

inefficient use of resources

& energy.

• Measure and periodically

review our progress and

strive for continuous

improvement.

Protect the safety & health of

our employees and

patients and minimize the

environmental footprint

for our operations.

Commitment to supply

energy on 27x7 basis

OUR ENERGY & ENVIRONMENTAL POLICY

39

Page 40: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

ENVIRONMENTAL MONITORING100% Compliance against the pollution norms:

DG Sets Stack monitoring.

24 hrs Ambient Noise monitoring

DG Sets Noise monitoring.

Monitoring & controlling of

waste water parameter.

Monthly drinking water analysis.

Medical Compressed Air Validation

as per ISO 8573-1: 2010 (E)

40

Page 41: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

ENVIRONMENT FRIENDLY CLEANING

o Minimize exposure of building occupants and

cleaning personnel to potentially hazardous

chemical, biological and particulate

contaminants

o For all chemicals- avoid /minimize the

aerosols

o Minimize atomizing chemicals

o Use toggle top bottles or spray chemicals

onto cloths

o Reduce use of virgin paper in janitorial paper

o Use microfiber based cleaning equipment

which:

o Cut chemical waste up to :80%

o Increase performance up to 6 times

o Reduce labor up to 70%41

Page 42: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

UTILIZATION OF GREEN MATERIALS

Adhering to environmental

norms

Environmental monitoring &

adhering to PPCB norms

Use of environment friendly

green chemicals for cleaning

Use of green seal chemicals helps

in controlling the pollution by

harmful chemicals and protects the

environment.

42

Page 43: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Use of New Technology

Automated Water Taps

Sprinkler System for Irrigation

Automated Urinals

Water Recycling

STP Plant

ETP Plant

UV/SOFTNER in STP

RO Reject Water

Innovation

MGF Backwash

AHU Condensate

Cooling Tower blow down Reuse

Efficiency Improvement

Benchmarking

Auditing

Monitoring & Analysis

Improving

Renewable Substitution

Rain Water Harvesting

Municipal Waste Water Treatment and Reprocessing

MOHALI

WATER – CONSERVATION METHODOLOGY

43

Water Flow Restrictors

Water Less Urinals - Bio Tabs

Page 44: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

0

50

100

150

200

250

300

350

400

2011 -12 2012 -13 2013 -14 2014 -15 2015-16 2016-17 2016-18

300315

330

375

345

280

245

Wa

ter

Co

ns

um

pti

on

in

KL

Water Consumption KL/Day

2011 -12

2012 -13

2013 -14

2014 -15

2015-16

2016-17

2016-18

44

Average Water Consumption Trend

Page 45: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

•Natural lighting in patient areas

•Green house keeping

•Better Indoor Air Quality

•Sound Reduction

•Mercury free hospital

•20-40% Energy savings

•35-40% water savings

•Good day lighting

•No sick building syndrome

•Faster patient recovery

BEST PRACTICES FOLLOWED

THE NEW WAY

FORWARD

45

Page 46: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

46

SNo Description of schemeAmount

INRYear Remarks

1

Installation of 4 nos Rain Water

Harvesting pits for improvement of

ground water table.

4750000 2014-16 Annual saving of 1708 Units

2 STP water reused 750000 2014-16 Annual saving of 10000 Units

3 Installation of LED lights 1723000 2015-16 Units Saved 275000 annually

4 HSD Saved in boiler efficiency 75000 2015-16 27500 liters of HSD saved

5 Solar Lighting 200 KW 9800000 2016-17 Annual Saving of 300000 Units

6Energy efficient LED lights Placed at

Number of Places4900000 2016-17 Annual saving of 472000 Units

7

Water Conservation by utilizing STP

water in toilets etc. 600000 2016-17Annual saving of 10000 Units

and 1000Ltrs HSD

8LED Replacement for balance CFL

Lights 100000 2017-18 Annual saving of 50000 Units

9 Solar Photovoltaic Panels in Parking

and lift mumty9000000 2017-18 Annual saving of 275000 Units

Summary Co2 Emission Reduction

1218 MT (App)31698000 Savings 13.94LkWh Units46

UTILIZATION OF GREEN AND CLEAN

ENERGY

Page 47: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

• Initiated and implemented ERC (Energy Review Committee)

management system for measuring and benchmarking for

Conservation of energy and water .

• ERC committee consists of facility manager & building

managers to monitor, control and optimize power and water

consumption.

• Added the responsibility as part of KRA’s of annual

performance appraisals.

• Have set targets month wise , quarter wise and annually by

effective implementation of metering system, EMS and BMS.

• Formed sub teams for building supervisors & technicians to

create healthy competition among the teams for enhanced

performance and focus.

• Award and Reward systems implemented for innovative and

creative ideas. 47

Involvement of Employees, Team work in Encon,

Monitoring & Reporting formats and Implementation

Methodologies

Page 48: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

48

ENERGY : MONITORING AND MEASURING

Monitor Analyze Improve

• Online energy data capturing system

• Online HVAC monitoring system (BMS)

• Energy meters for load capturing

Monitoring

• Daily energy report

• Monthly report on the energy indices

• Monthly performance review

• Energy trends analysis

Reporting

Daily Report August 2018

8-Aug-18

Today Budg. MTD Act.MTD Budg.YTD Act.YTD %Var MTD %VarYTD 08.08.2017 MTD Diff. MTD.

Energy consumed for the day units 23088 138320 182625 1711710 2675778 25830 201402 -18777

Total Day unit 13428 99988 1590901

Total Night unit 9660 82637 1084877

D.G. unit 0 390 39350 0 569 -179

Energy Genrated by Solar System (215KW) 698 5748 119503 745 5533 215

Energy Genrated by Solar System Fortis-

in(174KW) 538 4374 94566 0 0 4374

Total unit 24324 193137 2929197 26575 207504 -14367

Power factor 0.99

H.S.D.Consumption in Boilers(Ltrs) 635 5245 91510 700 5760 -515

H.S.D.Consumption in D.G.(Ltrs) 0 113 11423 1211 11713 -11600

Total H.S.D. Consumption (Ltrs) 635 7480 5358 92565 102933 0 3 5355

Medical Gas Oxygen Consumption 1282 10060 166923

Medical Gas Nitrous oxide Cons. 0 1 35

Energy consumed for Chiller TR 1 2640 39360 413760 5241 15726 23634

Energy consumed for Chiller TR 2 720 6960 113520 8601 65166 -58206

Energy consumed for Chiller M/C 4 4580 17693 310034 1755 15415 2278

Total unit 7940 64013 837314 8695 56565 7448

Oncology block Consumption 2015 15860 237545 2000 13660 2200

Energy consumed New MRI Unit 476 3768 60180

Energy consumed for Laundry 244 1896 30326

Energy consumed for CSSD 424 2696 40564

Energy consumed for Rehab 544 4672 95456

Energy Genrated by Solar System (ONCO) 47 416 9220

OP Pharmacy 19.8 157.50 2583.62

Energy consumed for PET CT 110 806 13561

Energy consumed for LINAC 120 820 12316

Energy consumed for Gam camra GF 44 335.20 5227.5

Raw Water total production(KL) 490 3991 59648

Raw Water Consumption (KL) 446 3622 53804

Municipal Corporation water (KL) 7 69 1088

Solar water system Cons.(KL) 10 209 3681

Today Budg Today Act.MTD Budg.YTD Act.YTD

Power 1.732 9.440 13.696 116.820 199.033

HSD ( DG + BOILER) 0.365 3.296 3.082 40.788 59.076

Medical gases 0.121 1.128 0.975 13.959 1055.733

Salt 0.008 0.040 0.064 0.495 1.032

0.00 0.00 0.00

Irrigation water consumption- (HR) 0.00 0.00 0.00

CCT(KL) 0.00 0.00 0.00

Clothes washed in Laundry ( Kg) 2870 22100 347920

In- Patient numbers 261 276

No.of Surgeries in Cardiac OT 4 24

No. of Surgeries & Producer. in MSOT& Ortho

OT 31 225

DG- 1 DG- 2 DG- 3

UNIT generated by D.G / Liter #DIV/0! #DIV/0! #DIV/0!

Cost of unit generated by DG@Rs 47.57 litre #DIV/0! #DIV/0! #DIV/0!

Total unit generated by D.G 0 0 0

HSD Consumed 0 0 0

Running time of Equip. (hrs)

Running

time of

Equip.

(hrs.)

Running time of Equip. (hrs.)Running time

of Equip. (hrs.)YTD Budget

Running time

of Equip. (hrs.)

Running time

for Eqpt.

(hrs)

Act.MTD

2016Diff. MTD.

PSEB power fail 0.00 NA 0.25 NA 49.05 0.00 0.35 -0.10

Chiller no-1 0.00 NA 0.00 NA 0.15 0.00 0.00 0.00

Chiller no-2 0.00 NA 0.00 NA 9.00 0.00 0.00 0.00

Chiller no-3 2.15 NA 108.15 NA 1180.50 3.05 122.30 -14.15

Chiller no-4 18.50 NA 72.30 NA 1224.45 20.15 60.20 12.10

HW Generators-2 0.00 NA 0.00 NA 0.00

Boiler no-1 9.62 NA 68.04 NA 904.38

Boiler no-2 2.58 NA 40.38 NA 945.69

Boiler no-3 10.68 NA 71.34 NA 741.91

Boiler no-4 0.00 NA 19.11 NA 761.82

DG-1 0.00 NA 0.00 NA 37.10

DG-2 0.00 NA 0.00 NA 6.35

DG-3 0.00 NA 0.40 NA 26.40

BOREWELL-1 8.83 NA 71.91 NA 1058.26

BOREWELL-3 3.30 NA 31.00 NA 455.45

RO- WTP 11.30 NA 90.00 NA 1510.00

AIR COMPRESSOR-3 0.00 NA 0.00 NA 42.00

AIR COMPRESSOR-4 0.00 NA 24.00 NA 487.00

AIR COMPRESSOR-5 0.00 NA 20.70 NA 385.90

AIR COMPRESSOR-6 24.00 NA 120.00 NA 1687.00

VACUUM PUMP-1 4.35 NA 25.28 NA 856.82

VACUUM PUMP-2 0.00 NA 0.00 NA 34.33

VACUUM PUMP-3 0.00 NA 0.00 NA 596.10

VACUUM PUMP-4 0.00 NA 0.00 NA 63.21

VACUUM PUMP-5 0.00 NA 0.00 NA 51.62

VACUUM PUMP-6 20.00 NA 172.00 NA 1527.00

AGSS 15.00 NA 92.00 NA 1467.60

Page 49: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Energy monitoring format adopted including

methodology used for quantification of saving• Study of power distribution system & identifying power consuming of

different loads

• Measuring the consumption by providing meters for all the loads

• Monitoring of DG sets ,transformers, HT and LT panels, electrical loads, etc.

• Monitoring of power factor, electricity consumption through EMS system

• Monitoring and analysis of power consumption, identifying the high power

consuming equipment (HVAC) & implementing energy saving initiatives

• Preparing of various energy reports like daily, weekly, monthly, etc.

• Data analysis & review of the data collected from the BMS & EMS by our

ERC.

• Quantifying & evaluating the savings by ERC, internal & external energy

audits

• Conducting walkthrough energy audits and recommendations to ourclients for implementation of energy conservation best practices

• Monthly energy performance review & evaluation building wise for effective

control49

Page 50: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Practice FORTIS,

MOHALI

Adaption of Energy Management System Yes

Adaption of Environmental Management System Yes

Use of automated building Management System Yes

Use of Energy performance Indicator (KWH/Pax, KWH/TR ) Yes

Metering of Tenant energy Yes

Reporting of carbon emission to CDP No

Conduct energy audits Yes

Internal & External Stakeholder engagement Yes

Sharing of best practices with others hospitals Yes

Use of renewal energy for day to day operations In Progress

Mapping & reduction of carbon emission as per ACA Yes

WORLD CLASS O&M PRACTICES FOLLOWED

50

Page 51: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

RESULTS OF BEST PRACTICES

IMPLEMENTED 2015-2018

CO2e Reduction 3835.08MT

kWh Reduction 30.28Lakhs

HSD Reduction

171.42KLtrs

Cost Reduction

INR 268.90Lakhs

51

Page 52: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

179 149 145 141 137 130 125

2683824530 21787 20111 16014 15100 14626

279 291 324 348 425 435 435

1

10

100

1000

10000

100000

2011-12 2012-13 2013-14 2014-15 2015-16 2016-17 2017-18

SEC in kWh/M2

Total kWh/Bed

No. Of Beds

Benchmarks 17762 KWh/Bed & 200kWh/m2 (By Bureau of Energy Efficiency, Govt. of India ECO-III

project)

WHERE WE ARE TODAYReduction of CO2e

by 3538MT

(2015-18)

52

Page 53: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

FUTURE PLANCO2

Reduction

1697MT

Energy Conservation Measure Year

Savings

(LkWh)

HSD

(KLitrs)

Saving

(INR

Lacs)

Investment

(In Lacs)

ROI

(Months)

PNG to replace LPG (used in

Kitchen) 2018-19 0.00 17336

8.50 3

PNG for Boilers 2018-19 0.44 274 58 10.00 2

Modification STP/ETP 2018-19 0.49 0 4 20.00 60

VFD Operated Air compressor 2018-19 0.18 0 2 10.50 64

160Kw Solar PV panel

installation 2018-19 2.25 019

125.00 72

LED Replacement (Phase 3) 2018-19 0.99 0 8 10.00 15

Energy efficient High end

Motors 2018-19 0.25 02

5.50 28

Online Chiller Condenser tube

cleaning System 2019-20 0.18 01

5.00 60

Hot water generation through

solar water heating system 2019-20 0.50 3020

42.00 26

Biomass Gassifier 2019-20 0.00 2 11 22.00 24

Summary 1697 MT of CO2

REDUCTION 5.27 479.12 161.67 258.50 354.0053

Page 54: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

Going Forward

141 137 130 125 121 117 113

20111 16014 15100 14626 14000 13500 13000

1

10

100

1000

10000

100000

ROAD MAP FOR 2018-2020

SEC in kWh/M2

Total kWh/Bed

Benchmarks 17762 KWh/Bed (By Bureau of Energy Efficiency, Govt. of India ECO-III project)

54

Reduction of CO2e

by 1953MT

Page 55: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

GOING FORWARDReduction of CO2 emissions by 1953MT

141

By 2015

137 By 2016

130

Yesterday

125 Today

121

By 2019

55

Page 56: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

FHM Awards & Recognition

BEE NATIONAL

ENERGY

CONSERVATION

AWARD 2015

Doc n Doc Gammex

Saviour - Best

Multispecialty Hospital -

2014

Indian Health & Wellness

for Best Green Hospital

Award 2016

Pan Fortis Innovation

Award - 2014

Intel Embedded Challenge

Award for Innovation in

Industry (Catheter

reprocessing) 2014

Best Sustainable Hospital

Project Award by HBII-

MEDGATE - 2014

AHPI Award for Quality

Beyond Accreditation -

2018

CII 16th National award

for Excellence in Energy

Management- 2016

No. 1 Private

Multispecialty Hospital in

Chandigarh – The Week –

Neilsen Best Hospitals

Survey -2015

Asia Pacific Hand

Hygiene Excellence

Award- 2015

AHPI Award for Green

Hospital- 2016-17

NABH Nursing

Excellence- 2016

NABH Nursing Excellence- 2016

Multispecialty Hospital in Chandigarh – The Week –Nielsen Best Hospitals Survey – 2015, 2014

CII National award for Excellence in Energy Management- 2017

AHPI Award for Quality Beyond Accreditation -2017

56

Page 57: CII 19th National Award for Excellence in Energy Management … · 2018. 9. 13. · National Bench mark 200 KWh/ sq. mtr./ year (reference Bureau of Energy Efficiency, Govt. of India

57