reversing time) (contract reversing
time)
14 Insulating and way of
extinction of the arch
SF6 SF6
15 Sequence of operation O-0.3 s-CO-3 min. CO/CO-
15 s-CO
O-0.3 s-CO-3
min. Or CO/CO-15
s-CO
16 Height of operation of the
plant
300 m.s.n.m. 300 m.s.n.m.
17 Distance of escape 25 mm/Kv, between phases 25 mm/Kv, between
phases
18 Type of switch Three-phase Three-phase
19 Type of control of the
switch
Single-pole Single-pole
20 Type of mechanisms tensioning spring motor and
manual
tensioning spring
motor and manual
21 Control voltage 110v DC 110v DC
22 voltage auxiliary circuits 208v AC 208v AC
23 Level of seismic
classification
0.3g 0.3g
24 Auxiliary connections 6889 mm (25*245=6125
31*245=7595)
25 Auxiliary contacts 10 NO y 10 NC (Minimum) 10 NO y 10 NC
(Minimum)
26 Capacity of auxiliary
contacts
10 amperes minimum 10 amperes
minimum
27 Voltage of heating office 208v AC 208v AC
28 Bobbins of shot Double Double
29 Bobbin of closing One One
30 Monitoring pressure of the
SF6
With contact of alarm and
block
With contact of
alarm and block
31 Measurement of pressure local local
8/12/2019 CHIXOY
3/8
of the gas
32 anti-pumping relay included included
33 Quality of the gas
according to norm
IEC 376 IEC 376
2. Environmental local conditions.
No Description Local conditions. Offered
1 Speed of the wind 100 km/h 100 km/h
2 Seismic force Acceleration, 0.5 g
horizontal, 0,5 gvertical
Acceleration, 0.5 g
horizontal, 0,5 gvertical
3 Maximum long
temperature of the
day
50 C 50 C
4 Maximum relative
humidity
100% 100%
5 installation height 300 msnm 300 msnm
3. Other requirements of the supply.
8/12/2019 CHIXOY
4/8
No Requirements Offered
1 The technical rating plates must be
in Spanish language, made of steel
Stainless with inscriptions of low
relief for outdoor and of easy
reading.
Yes
2 The switches must bring own
structure of material resistant to
the environment galvanized in
warmly, according to procedure
EN-ISO 1461, CASH 50976 or
ASTM A153 and with capacity of
static load and suitable dynamics
Yes
3 The stature of every switch will
have to be adapted to the current
base of the concrete one
Yes
4 The structure of every switch must
have his point of connection of
earthing
Yes
5 Every switch must bring the
connectors of high tension,
necessary and adapted for the
installation of the equipment
Yes
6 The height of every switch must
be similar to nowadays installed in
such a way that there are not
modified in risky form the
distances and current heights of
the installation
Yes
7 Every switch must rely on
sufficient auxiliary contacts that
they allow to connect all the
circuits of control that allow the
Yes
8/12/2019 CHIXOY
5/8
current operation of the switches
in sure form and that are fulfilled
by the scheme of current
protection
8 In his offer it must guarantee in
form written by a company
qualified and independent from the
quality of the materials used in the
switches and the quality of the
smelting of the fixed parts and
mobiles of the switch
Yes
9 Must be submitted to international
standards both mechanical and
electrical applied in the
manufacture of equipment and
components, if they use their own
rules of the country of origin must
be comparable or better than most
current international standards
Yes
10 In the assembly of the equipment
the use of adjustments is not
allowed in the structure that alters
the quality of the equipment
Yes
11 It is necessary to deliver the full
equipment of SF6 with all the
accessories
Yes
12 It is necessary to deliver a lot of
minimal supplies, attend to any
damage that is generated in the
first operations, this lot must
include:
- 3 relays monitoring SF6 gas
pressure.
Yes
8/12/2019 CHIXOY
6/8
- 3 engines of tightened of spring,
- 6 bobbins of closing.
- 6 bobbins of opening.
- Relays of control.
- Switchboards.
- Switches you die of career.
Bobbins signaling to attend a
switch
Motor
Yes
Yes
Yes
NA
NA
NA
13 Densimeter of SF6 per pole to
floor height for easy viewing,
indicating scale shall have
temperature compensated pressure.
so it must be Equipped with low-
stage press indication, the first one
as alarm and the second for
blockade.
Yes
14 The protections of the elements of
the switch must effect by means of
thermomagnetic switch. They
were not accepted protections by
means of fuses
Yes
15 It must possess a counter of
operations of the type that does not
adjust
Yes
4. Testing.
8/12/2019 CHIXOY
7/8
All switches must bring manufactures testing protocol prior to delivery and receipt
of the same.
5. Manuals and documentation.
No Required Offered
A) Manuals of technical
information it completes.
Dimensions. Torque of
screws and packing
protocol of tests with his
typical values and
measurements realized
during the tests. Important
information for his storage
and managing during the
assembly.
Yes
B) Manuals of operation and
maintenance, where it
includes measurements and
calibrations and parameters
of functioning, in Spanish
language
Yes
C) Fault identification manual,
indicating the most likely
failures and maintenance
program to prevent
Yes
6. Warranty.
8/12/2019 CHIXOY
8/8
The contractor must deliver the original certificate of guarantee of the manufacturer,
whose term must be equal or bigger than 18 months, from the definitive receipt of the
supply and service.
Reply:confirm.
7. Delivery time.
With a maximum of 24 months, counted from the day of the notification to the
beneficiary of the letter of credit. In the same term the contractor has 20 days calendar
for every field of switches, from the notification in writing of the from date of the works
for the supervisor of the contract or the chief of plant.
Reply:confirm.