Power Circuit
1 Motor Starting Equipment Star Delta / Solid State StarterProtection Fuses / MCBsOver Load Relay for compressorsOver Load Relay for FansPhase volt Monitor
2 SafetiesHP SwitchLP SwitchOil Pressure SwitchAnti FreezeLow Chilled water FlowLoss of Refrigerant charge
3 Capacity Control ( Leaving water temperature to be held withing +/- 0.1 deg C)
Sensor Controller First Stage ofTemp Sensor Controller Solenoid Valves
Cut of Cylinders
4 Display Type LED / LCD / Super VGA
5 Display Parameters Chw Temp entChw Temp LeavingCondensing tempEvaporator TempSuction Super HeatDischarge Super Heat% Load
6 Compressor Controller Lead / Lag control or Run time equalisationPump down at the beginging and end of every cycleLimiting of chilled water temperature pull down rate at start up to 0.56 deg C per minute
7 Keeping a Track of Records
Second Stage ofCut of Compressors
Controls
Capacity Control
Sensor Controller First Stage of Second Stage ofAction Action
Recips Temp Sensor Controller Solenoid Valves Cut of CompressorsCut of Cylinders
Screw Temp Sensor Controller Slide valve unloads Cut of Compressorsthe screw
Centrifugal Temp Sensor Controller Hydraulic assemblycloses the Guide vanes
Absorption Temp Sensor Controller Closes the Steamcontrol valve
Split unit Temp Sensor Relay Switches of compressor
Window uniTemp Sensor Relay Switches of compressor
Fridge Temp Sensor Relay Switches of compressor