Upload
rahulsoniin
View
226
Download
0
Embed Size (px)
Citation preview
7/30/2019 Chilled Beam- Engineering_Guide
1/48
Please refer to the Price Engineers HVAC Handbook
for more information on Active & Passive Beams
S E C T I O N L
Engineering GuideActive & Passive Beams
7/30/2019 Chilled Beam- Engineering_Guide
2/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-2
Return to product page
Introduction
Active & Passive Beams
Engineering Guide
Like radiant heating and cooling systems,active and passive beam systems use wateras well as air to transport energy throughoutthe building. Like radiant and coolingsystems, they oer savings in energy, spaceand maintenance costs. Unlike radiantheating and cooling systems, however,these technologies deliver the majorityo their cooling and heating throughconvection, oten leading to a ully mixedenvironment. This section introduces activeand passive beam systems and their designconsiderations, and addresses the uniquerequirements o some o the most commonapplications.
Management o heat loads can generally
be classied into two dierent types: all-
air systems or hybrid systems. All-airsystems have been the most prominentin North America during the 20th centuryand have been in use since the advent oair conditioning. These systems use air toservice both the ventilation requirementas well as the building cooling loads. Ingeneral, these systems have a central airhandling unit that delivers enough coolor warm air to satisy the building load.Diusers mounted in the zone deliver thisair in such a way as to promote comortand evenly distribute the air. In many cases,the amount o air required to cool or warmthe space or the fuctuations o loads makedesigning in accordance to these principles
dicult.
Hybrid systems combine an air-sideventilation system and a hydronic (or water-side) system.The air-side system is designedto meet all o the ventilation requirementsor the building as well as satisy the latentloads. It is typically a 100% outside airsystem and because the primary unctiono the supply air system is ventilation anddehumidication as opposed to sensiblecooling it can be supplied at higher supplyair temperatures than is typical o traditionalmixing air distribution systems. The water-side system is designed to meet the balanceo the sensible cooling and heating loads.These loads are handled by water-basedproducts, such as active and passive beams,
which transer heat to the zone by induction.
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
3/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-3
Return to product page
Active & Passive BeamsEngineering Guide
Concepts and Benefts
Active and passive beam systems providean eective method or providing heatingor cooling to a space while promoting ahigh level o occupant comort and energyeciency. There are two distinct systemdesign philosophies that are consideredwhen applying hydronic heating and/orcooling:
Hydronic heating or cooling where thehydronic systems are integrated with theprimary ventilation system. These are activebeam systems (Figure 1).
Hybrid heating or cooling systems wherewater-based devices are used in conjunctionwith a scaled-down ventilation system, andmanage the bulk o the sensible coolingload. These systems generally use passivebeams (Figure 2).
Hydronic systems have been successullyused in several applications havingdramatically dierent characteristics. Someexamples o areas where active and passivebeam systems have been applied include:
GreenBuildings
PostSecondaryEducationalFacilities
LoadDrivenLaboratories
K-12Schools
OfceBuildings
Cafeterias
TelevisionStudios
Benefts o Air-Water SystemsThere are many benets to heating andcooling using active or passive beams.Advantages o water-based heating andcooling systems over other mechanicalsystems include:
Energyandsystemefciency
Reducedsystemhorsepower
Improvedindoorenvironmentalquality
Improvedindoorairquality
Increasedthermalcomfort
Reducedmechanicalfootprint
Lowermaintenancecosts
Improvedsystemhygiene
Active or passive beam systems are a good
choice where: Thermal comfort is a major design
consideration
Areaswithhighsensibleloadsexist/arepresent
Areasrequiring a high indoorair quality(100% outdoor air system) exist/are present
Energyconservationisdesired
Energy Efciency
The heat transer capacity o water allows ora reduction in the energy used to transport anequivalent amount o heat as an all-air system(Stetiu, 1998). These reductions can be oundprimarily through reduced an energy.
Figure 1: Air fow diagram o a typical linearactive beam in cooling
Figure 2:Air fow diagram o a passivechilled in cooling
Figure 3: Active beams installedin an oce
Figure 4: Passive beams behinda perorated ceiling
Nozzles
Plenum
Primary Air
Room Air
Coil
Room Air
Primary Air
The higher chilled water supply (CHWS)temperatures used with active and passivebeam systems, typically around 58 F[14.5 C], provide many opportunities or areduction in energy use, including increasedwater-side economizer use. This increasedCHWS temperature also allows or morewet-side economizer hours than would bepossible with other systems where CHWStemperaturesaretypically~45F[7C].
Indoor Air Quality
Depending on the application, undermaximum load, only ~15 to 40% o thecooling air fow in a typical space is outdoorair required by code to satisy the ventilation
requirements. The balance o the supplyair fow is recirculated air which, when nottreated, can transport pollutants through thebuilding. Active and passive beam systemstranser heat directly to/rom the zone andare oten used with a 100% outdoor airsystem that exhausts polluted air directlyto the outside, reducing the opportunityforVOCsandillnesstotravelbetweenairdistribution zones.
Noise
Active and passive beam systems do notusually have an powered devices near thezone. This typically results in lower zone
noise levels than what is achieved with allair systems. In situations where passivebeams are used in conjunction with aquiet air system, such as displacemenventilation, the opportunities or noisereduction increase urther.
Reduced Mechanical Footprint
The increased cooling capacity o wateallows the transport system to be reducedin size. Generally, it is not unusual to beable to replace ~60 t [6 m] o air shat witha 6 in. [150 mm] water riser, increasing theamount o foor space available or use olease. Due to the simplicity o the systems(i.e. reduction in the number o moving parts
and the elimination o zone lters, drainpans, condensate pumps and mechanicacomponents), there tends to be less spacerequired in the interstitial space to supporthe HVAC system.
Lower Maintenance Costs
With no terminal unit or an coil lters omotors to replace, a simple periodic coicleaning is all that is required in order tomaintain the product.
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
4/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-4
Return to product page
Active & Passive BeamsEngineering Guide
When to use Beam Systems
ApplicationTotal Air
Volume (Typ.)Ventilation Requirement
(Typ.)Air-Side
Load Fraction
Ofce 1 cm/t2 [5 L/s m2] 0.15 cm/t2 [0.75L/sm2] 0.15
School 1.5 cm/t2 [7.5L/sm2] 0.5 cm/t2 [2.5 L/s m2] 0.33
Lobby 2 cm/t2 [10 L/s m2] 1 cm/t2 [5 L/s m2] 0.5
Patient Room 6 ach 2 ach 0.33
Load-driven Lab 20 ach 6 ach 0.3
Hygienic System
With the elimination o the majority olters and drain pans, there is a reducedrisk o mold or bacteria growth in the entiremechanical system.
Active and passive beam systems are well-suited to some applications and less so toothers. As a result, each application mustbe reviewed or potential benets as wellas the suitability o these types o systems.Oneconsiderationwhichcanassistinthedecision to employ hydronic systems asopposed to an all-air system is the air-sideload raction, or the percentage o the totalair supply which must be delivered to the
zone to satisy code and dehumidicationrequirements. Table 1 shows the loadraction or several spaces. In the table thebest applications or hydronic systems arethose with the lowest air-side load ractionas they are the ones that will benet the mostrom the eciencies o hydronic systems.Another actor which should be examinedis the sensible heat ratio or the percentageo the cooling load which is sensible asopposed to latent. The latent loads must besatised with an air system and oer somesensible cooling at the same time due tothe temperature o dehumidied air. I thetotal sensible cooling load is signicantlyhigher than the capacity o the air suppliedto satisy the latent loads, a beam system
might be a good choice.Commercial Ofce Buildings
In an oce building, active and passivebeam systems provide several benets. Thelower supply air volume o the air handlingsystem provides signicant energy savings.In addition, the smaller inrastructurerequired to move this lower air fow allowsor small plenum spaces, translating intoshorter foor-to-foor construction or higherceilings. The lower supply air volume andelimination o ans at or near the spaceoers a signicant reduction in generatednoise. The lower air fow oten translatesto reheat requirements being reduced. Inthe case o 100% outside air systems, the
lighting load captured in the return plenumis exhausted rom the building, lowering theoverall cooling load.
Schools
Schools are another application that canbenet greatly rom active and passive beamsystems. Similar to oce buildings, thebenets o a lower supply air volume to thespace are lower an power, shorter plenumheight, reduced reheat requirements andlower noise levels (oten a critical designparameter o schools).
Hospital Patient Rooms
Hospitals are unique applications in thatthe supply air volume required by localcodes or each space is oten greater thanthe requirement o the cooling and heatingload. In some jurisdictions, local code
requires these higher air-change rates orall-air systems only. In these cases, thetotal air-change rate required is reduced isupplemental heating or cooling is used.This allows or a signiicant reductionin system air volume and yields energysavings and other benets.
Furthermore, because thesesystemsaregenerally constant air volume with thepotential to reduce the primary air-changerates, reheat and the cooling energydiscarded as part o the reheat process isa signicant energy savings opportunity.Depending on the application, a 100%outside air system may be used. Thesesystems utilize no return air and thereoreno mixing o return air between patientrooms occurs, potentially lowering the risko hospital associated inections.
Laboratories
In load driven laboratories where the supplyair rate is driven by the internal gains (suchas rerigerators, testing equipment, etc.)as opposed to the exhaust requirements,active and passive beam systems canoer signicant energy savings. In theseenvironments it is not unusual to requirea large air-change rate in order to satisythe load, although signicantly less maybe required by code (ASHRAE, 2008; CSA,2010).
Table 1: Typical load ractions or several spaces in the United States
In these applications, the dierence betweenthe supply air volume required to managethe sensible loads and that required tomeet the ume hood air fow requirementsprovides opportunity or energy savingsthrough the application o active and passivebeams. These savings are typically due tothe reduction in an power as well as theenergy associated with treating the outsideair, which, in the case o a load driven lab,may be signicant.
Hotels / Dorms
Hotels, motels, dormitories and similar typebuildings can also benet rom active andpassivebeamsystems.Fanpowersavingsoten come rom the elimination o ancoil units located in the occupied space.The energy savings associated with theselocal ans is similar in magnitude to thato larger air handling systems. It also allowsor the elimination o the electrical servicerequired or the installation o an coil units,as well as a reduction in the maintenanceo the drain and lter systems. The removalo these ans rom the occupied space alsoprovides lower noise levels, which can be asignicant benet in sleep areas.
Limitations
There are several areas in a building wherehumidity can be dicult to control, suchas lobby areas and locations o egress.These areas may see a signicant short
term humidity load i the entrances are notisolated in some way (revolving doors orvestibules). In these areas, a choice o acomplimentary technology such as an coilunits or displacement ventilation is ideal.
Other applications may have high airfow/ventilation requirements, such as anexhaust driven lab. The majority o thebenet provided by the hydronic system islinked to the reduction in supply air fow.As such, these applications may not seesucient benet to justiy the addition othe hydronic circulation systems, makingthem not likely to be a good candidate orthis technology.
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
5/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-5
Return to product page
Active & Passive BeamsEngineering Guide
Passive Beams
Passive Beams
Passive beams use a heat exchangerusually a coilto change the temperature othe adjacent transerring heat and create adierence in density with the ambient air.The density dierence creates air movementacross the heat exchanger, transerring heatrom the heat exchanger to the air.
Passive beams condition a space usingnatural convection and are primarily usedor handling the sensible cooling load o aspace. They are water-only products, andrequire a separate air system or ventilationair and to remove the latent load. Aswarm air in the room rises, it comes intocontact with the heat exchanger and fowsdownward through the cool coils back intothe space, as seen in Figure 5. In heatingmode, passive beams are generally notused, though in some special instancesthey would condition the space primarilyby thermal radiation.
Product Description
Passive beams are available in models thateither integrate into standard suspendedceiling systems or are suspended reelyrom the ceiling. They are also commonlyinstalled behind perorated metal ceilingsor a uniorm architectural appearance. Aperorated metal ceiling helps reduce dratunder the beam, however, a minimum reearea o 50% is oten required to ensure the
capacity o the beam is not reduced. Passivebeams installed behind a metal peroratedceiling can be seen in Figure 7.
Components
The basic components o passive beamsinclude a heat exchanger, comprising oextruded aluminum ns and copper tubing,commonly termed the coil, and a rame orshroud. These components are illustratedin Figure 8.
Location
Passive beams are ideally suited to aisleways or perimeters o large spaces suchas oices, lobbies, conerence centers,libraries, or any other space that requiresperimeter or additional cooling. Air fowrom a passive beam is straight down sothey are not typically placed above where anoccupant will be stationed or an extendedperiod o time. While the velocity rom apassive beam is low, there is the opportunityor some people in this condition to beuncomortable.
Figure 6: Air fow diagram o a passivebeam in cooling
Figure 5: Room air fow pattern o a passive beam in cooling
Coil
Room Air
Primary Air
Figure 7: Passive beams installed behinda metal perorated ceiling
Face
Figure 8: Components o a typical passive chilled beam
Frame/Shroud
Coil
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
6/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-6
Return to product page
Active & Passive BeamsEngineering Guide
Figure 10: Air fow diagram o a typicallinear active beam in cooling
Figure 11: Air fow diagram o a typicallinear active beam in heating
Active Beams
Plenum
Mounting
Bracket
Primary Air Inlet
Hinged Face to allow
access to the coil
Coil
Figure 12: Components o a typical linear active beam
Figure 9: Room air fow pattern o a typical linear active beam in cooling
Active Beams
Active beams use the ventilation systemto increase the output o the coil, and tohandle both latent and sensible loads o aspace. Unlike radiant panels and chilledsails, which rely primarily on thermalradiation to condition a space, active beamsheat or cool a space through inductionand orced convection. An active beamaccepts dry air rom the system through apressurized plenum. This primary supplyair is then orced through nozzles in orderto create a high velocity air pattern in thearea adjacent to the coil. This high velocitycauses a reduction in the local staticpressure, inducing room air through the
heating/cooling coil. The induced air thenmixes with the primary supply air and isdischarged back into the space via slotsalong the beam (Figure 9). A typical air fowdiagram o a linear active beam in coolingand heating modes can be seen inFigure 10,and Figure 11 respectively.
Components
The basic components o active beamsinclude a heat exchanger with aluminumns and copper tubing, commonly termedthe coil, a plenum box with at least onesupply inlet, internal nozzles, a visible ace,and a rame. Although the congurations oactive beams dier, all general componentsremain the same. These components are
illustrated in Figures 12.Applications
Active beams can be used in oices,meeting rooms, schools, laboratories,hospitals, data centers, airports, any greenbuilding application, and large areas such aslobbies, conerence acilities, lecture hallsor caeterias.
Two basic types o active beams are:
LinearActiveBeams
ModularActiveBeams
Linear Active Beams
2 Way Discharge
Linear active beams with two-sideddischarge are designed to either integrateinto standard suspended ceiling systemsor be suspended reely in an exposedapplication. These beams have two linearair slots that run the length o the beam,one on either side.
NozzlesPrimary Air
Room Air
Nozzles
Plenum
Primary Air
Room Air
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
7/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-7
Return to product page
Active & Passive BeamsEngineering Guide
Primary Air
Room Air
Primary Air
Room Air
Active Beams
Figure 13: Air fow diagram o a linearactive beam in cooling with 1 way discharge Figure 14: Air fow diagram o a lineaactive beam in heating with 1 way discharge
Figure 15: Room air fow pattern o a typical linear active beam in cooling
Figure 16: Air fow diagram o amodular beam in cooling
Figure 17: Air fow diagram o amodular beam in heating
1 Way Discharge
Linear active beams with single-sided airdischarge are designed to either integrateinto standard suspended ceiling systemsor be suspended reely in an exposedapplication. These beams have only onedischarge air slot that runs along one sideo the beam.
The general air fow o linear active beamswith 1 way air distribution in cooling andheating are seen inFigures 13andFigure 14.Figure 15 illustrates the room air fow o atypical 1 way active beam.
PRODUCT TIPLinear active beams with 1 wayair distribution are best suited orplacement along a aade or wall.In applications where 1 way beamsare used with 2 way beams, asymmetric ace may be selected orthe 1 way unit to ensure a consistentappearance rom the room.
PRODUCT TIP
Active beams are typically availablein a 2 pipe or 4 pipe conguration.Beams with 2 pipe congurationshave one supply and one returnpipe or each unit, which servesor either/both heating and coolingpurposes. Beams with 4 pipecongurations have two supplyand two return pipes or each unit,comprising separate loops orcooling and heating.
Modular Active Beams
Modular active beams combine resh airventilation, hydronic heating and cooling,and our-sided air fow. They are typicallyavailable in modular sizes, 2 t x 2 t [600 mm
x 600 mm], and 2 t x 4 t [600 mm x 1200mm], and are available in models eitherdesigned to integrate into standard ceilingtiles or suspend reely rom the ceiling.
The typical air fow pattern o a modularbeam in cooling and heating is illustratedin Figure 16 and Figure 17.Often,thesemodular beams can be customized toindividually modulate the air fow rom eachsideoftheunit.Forexample,onesideoftheunit can be blanked o to create a modularbeam with three-sided air fow.
Beam Return
Room Air
Nozzles
Primary Air
Room Air
Nozzles
Plenum
Primary Air
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
8/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-8
Return to product page
Active & Passive BeamsEngineering Guide
Passive beam systems will vary inperormance, coniguration and layoutdepending on the application. There are,however, some characteristics that arecommonformostsystems.Furthermore,the perormance o passive beams is largelydependent on a common set o actors.This section will discuss how actorssuch as chilled water temperature aectthe perormance and layout o passivebeams. Table 2 shows common designcharacteristics or passive beam systems.
Product Selection and Location Passive Beams
Perormance
The perormance o a passive beam isdependent on several actors:
Waterowrate
Meanwatertemperatureandsurrounding air temperature
Shroudheight
Freeareaoftheairpaths(internalandexternal to the beam)
Location and application
The water fow rate in the coil aects twoperormance actors: the heat transerbetween the water and the coil, whichis dependent on whether the low islaminar (poor) or turbulent (good); and themean water temperature, or the averagetemperature, in the coil. The higher the fow
rate, the closer the discharge temperaturewill be to the inlet, thereby changing theaverage water temperature in the coil.Figure 18 shows the eect o the fowrate, indicated by Reynolds number, onthe capacity o a typical passive beam. Asindicated on the chart, increasing the fowrate into the transitional and turbulentranges (Re > 2300, shaded in the graph)causes an increase in the output o thebeam.
The water fow rate is largely dependenton the pressure drop and return watertemperatures that are acceptable to thedesigner. In most cases, the water fowrate should be selected to be ully turbulentunder design conditions.
The dierence between the mean watertemperature,tw, dened as:
and the surrounding (coil inlet) airtemperature is one o the primary driverso the beam perormance. The larger thisdierence is, the higher the convective heattranser potential. Conversely, a lowertemperature dierence will reduce theamount o potential energy exchange, andthereby capacity. As a result, it is desirablerom a capacity standpoint to select entrywater temperatures as low as possible,
Passive Beam Selection and Design Procedure
Table 2: Design Values or passive beam systems
IP
Room Temperature 74Fto78Finsummer,68Fto72Finwinter
Water Temperatures, Cooling 55Fto58FEWT,5Fto8F T
Design Sound Levels < 40 NC
Cooling Capacity Up to 500 Btu/ht
Ventilation Requirement 0.1 to 0.5 cm/t2 foor area
SI
Room Temperature 23 C to 25 C in summer, 20 C to 22 C in winter
Water Temperatures, Cooling 13Cto15CEWT,3Kto5K T
Design Sound Levels < 40 NC
Cooling Capacity Up to 500 W/mVentilation Requirement 0.5 to 2.5 L/s m2 foor area
Figure 18: Passive beam capacity vs. water fow
40
0 2000 4000 6000 8000 10000 12000
50
60
70
80
90
100
Capacity,
%
Re
Figure 19: Passive beam capacity vs. dierence between mean water and room airtemperature
0
0 5 10 15 20
0 2 4 6 8 10
20
40
60
80
100
120
Capacity,%
tw - troom ,F
tw - troom ,K
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
9/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-9
Return to product page
Active & Passive BeamsEngineering Guide
while maintaining it above the dew pointin the room to ensure sensible cooling only.
In some instances, it might be advantageousto the designer to use higher watertemperatures, where it makes sense roman equipment standpoint. This may alsooer some control simplication where theoutput o the beam is determined by theload in the room:
Astheloadincreases,theairtemperaturerises and increases the dierencebetween it and tw, thereby increasingbeam perormance.
Astheloaddecreases,theairtemperaturealls and reduces the cooling capacity o
the beam.A passive beam uses buoyancy orces andthe stack eect to drive air through thecoil. The stack eect is a phenomenonthat can be used to increase the rate ocirculation through the coil by increasingthe momentum o the alling air. As theair surrounding the coil ns decreases intemperature, it becomes more dense thanthe surrounding air, causing it to all downinto the zone below. Figure 20 shows across section o a passive beam and how theshroud, or skirt, o the beam separates thecool air rom the surrounding air, allowing itto gain momentum and draw an increasingvolume o air into the coil rom above.
The taller this stack is, the more air is drawnthrough the coil, increasing the coolingpotential o the beam. As the volume oair is increased, the velocity o the air allingbelow the beam is also increased. It is notuncommon to adjust the height o the stackin order to adjust the capacity and velocitiesin order to suit application requirements.
Figure 21 shows the increase in capacitywhen the stack height is changed rom 6 in.[150 mm] to 12 in. [300 mm] vs. the dierencebetween troom and tw. The graph indicatesthat the increase in capacity rom the largershroud reduces as the overall capacity othe beam increases. A practical lowerlimit where the mean water temperature is18F[10K]belowtheroomtemperature
translates to a capacity increase o 25% withthe taller stack.
Because the air fow through the beam isdriven by buoyancy orces, any restrictionto the air paths will impact the perormanceo the beam. Figure 22 shows the variousactors that aect perormance, including:
Facedesignofthebeamwhenexposed
Perforatedceilingbelowthebeamwhennot exposed
Gapbetweenthebeamandtheslab
Restrictionsofthe returnairpathwhenthe ceiling is closed (either return grillesor perorated ceiling tiles)
Figure 20: Passive beam air fow pattern
Figure 21: Passive beam capacity vs. temperature dierence
Passive Beam Selection and Design Procedure
1
0 5 10 15 20
0.0 2.0 4.0 6.0 8.0 10.0
1.1
1.2
1.3
1.4
1.5
1.6
Capac
ity12in.
[300mm]Shroud
Capac
ity6in.
[150mm]Shroud
tw - troom,F
tw - troom, K
Figure 22:Factorsthataffectperformanceo passive beams
Figure 23: A passive beam installed abovea perorated ceiling
Slab Clearance
Face TypeReturn Air Path
Slab Clearance
Coil
Shroud/
Stack
Room Air
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
10/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-10
Return to product page
Active & Passive BeamsEngineering Guide
The design o the ace material may restrictair alling through the ace. I the beam isinstalled behind a perorated ceiling, asshown in Figure 23, the air alling belowthe beam will hit the ceiling, spread out,and all into the zone below over a largerarea. As long as there is enough ree areain the ceiling to allow the air to all through(as well as rise through in order to eedthe beam with warm air), there should notbe a reduction in the capacity o the unit.Use o a perorated ceiling is also a goodway to reduce velocities below the beam,i required.
The distance between the top o the beamand the structure can reduce the air fow
and capacity o the passive beam i it is toonarrow. Figure 24 shows the impact o thegap between the beam and the slab in termso the beam width (gap/width).
In most cases, a clearance o 20 to 25% othe beam width is recommended. Theseproducts are generally selected to be 18in. [450 mm] or less in width, which wouldrequire a gap up to 4.5 in. [115 mm].
There are other actors that aectperormance, including the application,choice o ventilation system, and location.It is possible to increase the capacity o thepassive beam through induction. I a highvelocity is located near a passive beam, itmay pull air through the coil at a higher rate
than the natural convection would alone, asindicated in Figure 25. It is also possibleto trap thermal plumes at the buildingenvelope and orce this air though a passivebeam, as shown in Figure 26.
The perormance o the beam undernon-standard conditions, such as thosedescribed above, can be dicult to estimate.Forexample,theplumecomingupfromthe aade may be so strong, and the inletto the plenum so narrow, that the plumecomes across the ace o the beam. Thiswould disturb the air movement throughthe coil, dramatically reducing the capacityo the beam. In these instances, it is bestto conduct a building mockup or usesimulation sotware to understand how the
various parameters aect each other.
40
0.07 0.09 0.11 0.13 0.15 0.17 0.19 0.21 0.23 0 .25
50
60
70
80
90
100
Capacity,
%
Gap / Beam Width
Figure 24:The impact on the capacity o the gap between a passive beam and buildingstructure
Figure 26: Capturing the plume at the perimeter may increase passive beam perormance
Window
Room Air
Primary Air
Ceiling
Figure 25: Inducing air through the passive beam with increased velocity across the ace
Passive Beam
Slot Diffuser
Induced Air
Primary Air
Passive Beam Selection and Design Procedure
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
11/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-11
Return to product page
Active & Passive BeamsEngineering Guide
Figure 27: Expected velocities below an 18 in. wide passive beam
0.0
100 150 200 250 300 350
96 146 196 246 296
10.0
20.0
30.0
40.0
50.0
0.3
0.25
0.2
0.15
0.1
0.05
0
60.0
Velocity,
fpm
Velocity,
m/s
Passive Beam Capacity, W/m
Passive Beam Capacity, Btu/hft
Avg. + 2
Average
Avg. 2
Selection and Location
Due to the air cascade below the passivebeam, it is common to locate the beamabove aisles or along walls. Dependingon the capacity and the expected velocitybelow the beam, the air may pose a risko drat to occupants who are regularlylocated beneath them. Figure 27 showsthe velocity below an 18 in. [450 mm] widepassive beam vs. beam capacity.
In most cases, it is desirable to maintain thevelocity in the occupied zone below 50 pm[0.25 m/s], though this value will depend onthetemperatureoftheair.FromFigure 27,the average velocity (the solid line) rangesfrom35fpm[0.175m/s]to50fpm[0.25m/s],operating between 150 Btu/ht [145 W/m]and 300 Btu/ht [290 W/m].
The installation height is not a critical actorbecause the plumes will make their waydown into the occupied zone. Even witha displacement ventilation system wherethere may be thermal plumes rising romthe occupants and heat sources, thesetend to slide past each other as opposedto mixing.
Selection o passive beams is airlystraightorward. Manuacturers generallyprovide data or standard product that hascapacity vs. fow rate or standard valuestw - troom. In most cases, it is preerable to usesotware because it allows greater control o
the design parameters and more selectionoptions. It is important to consider both thecapacity as well as the velocity beneath thebeam. This usually means selecting longer,narrower beams which typically causelower velocities below them or applicationswhere they are located above stationaryoccupants.
Passive Beam Selection and Design Procedure
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
12/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-12
Return to product page
Active & Passive BeamsEngineering Guide
Design Procedure Passive Beams
1. Determine the ventilation requirement
Theventilationrequirementshouldbecalculatedtomeetventilationcodes.Forexample,usingASHRAEStandard62-2004todetermine the minimum resh air fow rate:
H1
2. Determine the required supply dew-point temperature to remove the latent load
H2
I the required humidity ratio is not practical, recalculate the supply air volume required with the desired humidity ratio.
3. Determine the supply air volume
The supply air volume is the maximum volume required by code or ventilation and the volume required or controlling the latent load:
H3
4. Determine the sensible cooling capacity o the supply air
IP H4
SI H4
5. Determine the sensible cooling required rom the water side
H5
6. Select a beam or series o beams
Select a beam or series o beams that will provide the appropriate amount o cooling using an appropriate entry water temperature.
7. Locate the beams to minimize drat as well as piping length
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
13/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-13
Return to product page
Active & Passive BeamsEngineering Guide
Example 1 - Small Ofce Passive Beams Selection (IP)
Consider a small oce with a southern exposure. The space is designed or two occupants, a computer with LCD monitor, T8 forescenlighting,andhasatemperatureset-pointof75F.Theroomis10ftwide,12ftlong,and9ftfromoortoceiling.
12 ft
9 ft10 ft
SMALL OFFICE
Window
Space Considerations
Oneoftheprimaryconsiderationswhenusinganactiveorpassivebeamsystemishumiditycontrol.Aspreviouslydiscussed,itisimportant to consider both the ventilation requirements and the latent load when designing the air-side o the system. ASHRAE Standard62.1-2010 stipulates the ventilation requirements, but these are oten not sucient to control humidity without specialized equipment.
The assumptions made or this example are as ollows:
Load/personis250Btu/hsensibleand155Btu/hlatent
Lightingloadinthespaceis6.875Btu/hft
Computerloadis300Btu/h(CPUandLCDMonitor)
Totalskinloadis1450Btu/h
Specicheatanddensityoftheairare0.24Btu/lbFand0.075lb/ftrespectively
Designconditionsare75F,with50%relativehumidity
Designdewpoint=55F
Determine:
a) The ventilation requirement.
b) The suitable air and water supply temperatures.
c) A suitable passive beam to meet the cooling requirement.
d) A practical layout or the space.
Design Considerations
Occupants 2
Set-Point 75F
FloorArea 120 t
Exterior Wall 108 t
Volume 1080ft
qoz 800 Btu/h
ql 825 Btu/h
qex 1450 Btu/h
qT 3075Btu/h
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
14/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-14
Return to product page
Active & Passive BeamsEngineering Guide
Example 1 - Small Ofce Passive Beams Selection (IP)
Solution:
a) Determine the ventilation requirement
Theventilationrequirementshouldbecalculatedtomeetventilationcodes.Forexample,usingASHRAEStandard62-2004todeterminethe minimum resh air fow rate or a typical oce space:
b) Determine the required supply dew-point temperature to remove the latent load
FromequationH2:
Using the ventilation rate:
Atthedesignconditions(75F,50%RH),thehumidityratiois65gr/lb,requiringadifferenceinhumidityratiobetweenthesupplyandroom air o:
Fromthegurebelow,thedewpointcorrespondingtothehumidityratiois40F,whichistoocoolforstandardequipment.
Evaluating the humidity ratio at several temperatures:
Humidity Ratio
Dew Point lb/lb gr/lb
40 0.00543 38
45 0.0065 46
50 0.0075 53
55 0.0095 67
0.0095
0.0065
0.0075
0.0054
0.000
0.002
0.004
0.010
0.012
0.014
0.016
0.018
0.020
0.022
0.024
0.026
0.028
0.030
35 40
12.5
13.0
13.5 10%
20%
30%
40%50%
60%
70%8
0%90%
14.0
14.5
15.0
45 50 55 7560 65 70 80 85 90 95 100 105 110 115 120
65
Dry Bulb Temperature, F
Enth
alpy
-Btu/
lbofD
ryAir
HumidityRatio,lbw/lbDA
70
75
80
85
15
20
25
30
35
40
45
50
60 65
Volume - ft3/lb of Dry Air
Saturation Temperature,F
Relative Humidity
40
45
50
55
60
35
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
15/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-15
Return to product page
Active & Passive BeamsEngineering Guide
Example 1 - Small Ofce Passive Beams Selection (IP)
Evaluatingthehumidityratioatseveraltemperaturesshowninthetableledtotheselectionofadewpointof50Finordertouselessexpensive equipment while also minimizing the supply air volume required to control humidity. The required air volume to satisy thelatent load is:
The supply air volume to the oce is the maximum volume required by code or ventilation and the volume required or controllingthe latent load:
Determine the sensible cooling capacity o the supply air
Using equation H4:
Determine the sensible cooling required rom the water side
Assumingachilledwatersupplytemperature2F abovethedesigndewpointinordertoavoidcondensationprovidesamaximumtemperaturedifferencebetweentheMWTandTroomof75F-57F=18F.Usingselectionsoftwaretogenerateasuitableselectionprovides the ollowing perormance:
Perormance
Capacity 2049 Btu/h
Length 72in.
Width 24 in.
Water fow rate 1.01 gpm
Water pressure drop 4.9 thd
It is practical to locate passive beams along a wall where occupants are not regularly located. In this case, the area beside the desk isa good choice.
Person
SMALL OFFICE
Passive Beam
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
16/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-16
Return to product page
Active & Passive BeamsEngineering Guide
Example 1 - Small Ofce Passive Beams Selection (SI)
Consider a small oce with a southern exposure. The space is designed or two occupants, a computer with LCD monitor, T8 forescentlighting, and has a design temperature set-point o 24 C. The room is 3 m wide, 4 m long, and 3 m rom foor to ceiling.
3 m
4 m
3 m
SMALL OFFICE
Window
Space Considerations
Oneoftheprimaryconsiderationswhenusinganactiveorpassivebeamsystemishumiditycontrol.Aspreviouslydiscussed,itisimportant to consider both the ventilation requirements and the latent load when designing the air side o the system. ASHRAE Standard62.1-2010 stipulates the ventilation requirements, but these are oten not sucient to control humidity without specialized equipment.
The assumptions made or the example are as ollows:
Load/personis75Wsensibleand55Wlatent
Lightingloadinthespaceis25W/m
Computerloadis90W(CPUandLCDMonitor)
Totalskinloadis405W
Specicheatanddensityoftheairare1.007kJ/kgkand1.3kg/m3respectively
Designconditionsare24C,with50%relativehumidity
Designdewpoint=13C
Determine:
a) The ventilation requirement.
b) The suitable air and water supply temperatures.
c) A suitable passive beam to meet the cooling requirement.
d) A practical layout or the space.
Design Considerations
Occupants 2
Set-Point 24 C
FloorArea 12 m
Exterior Wall 12 m
Volume 36m
qoz 240 W
ql 300 W
qex 405 W
qT 945 W
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
17/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-17
Return to product page
Active & Passive BeamsEngineering Guide
Solution:
a) Determine the ventilation requirement
Theventilationrequirementshouldbecalculatedtomeetventilationcodes.Forexample,usingASHRAEStandard62-2004todeterminethe minimum resh air fow rate or a typical oce space:
b) Determine the required supply dew-point temperature to remove the latent load
FromequationH2:
Using the ventilation rate:
At the design conditions (24 C, 50% RH), the humidity ratio is 9.5 g/kg, requiring a dierence in humidity ratio between the supply androom air o:
Fromthegurebelow,thedewpointcorrespondingtothehumidityratiois5C,whichistoocoolforstandardequipment.
Evaluating the humidity ratio at several temperatures:
Humidity Ratio
Dew Point g/kg
5 5.57.5 6.75
10 8
12.5 9.25
Example 1 - Small Ofce Passive Beams Selection (SI)
Dry-Bulb Temperature, C
Enthalpy
-kJ/k
gof
Dry
Air
30
25
20
15
10
0
50454035302520150
0
45
40
35
30
25
20
15
50
55
60
65
70
75
85
90
95
100
105
105
110 115 120 125
Volume - m3/kg of Dry Air
Saturation Temperature,C
Relative Humidity
H
umidityRatio,gw/kgDA
30
10
5
15
20
0.78
0.80
0.82
0.84
0.86
0.90
0.92
0.94
0.96
10%
20%
30%
40%
50%
60%
70%8
0%90%
25
9.25
8
6.75
5.5
10 12.5 245 7.5
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
18/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-18
Return to product page
Active & Passive BeamsEngineering Guide
Evaluating the humidity ratio at several temperatures shown in the table led to the selection o a dew point o 10 C in order to use lessexpensive equipment while also minimizing the supply air volume required to control humidity. The required air volume to satisy thelatent load is:
The supply air volume to the oce is the maximum volume required by code or ventilation and the volume required or controllingthe latent load:
Determine the sensible cooling capacity o the supply airUsing equation H4:
Determine the sensible cooling required rom the water side
Assumingachilledwatersupplytemperature1Kabovethedesigndewpointinordertoavoidcondensationprovidesamaximumtemperature dierence between the tw and troomof24C14C=10K.Usingselectionsoftwaretogenerateasuitableselectionprovidesthe ollowing perormance:
PerormanceCapacity 567W
Length 1800 mm
Width 600 mm
Water fow rate 230 L/h
Water pressure drop 14.6 kPa
It is practical to locate passive beams along a wall where occupants are not regularly located. In this case, the area beside the desk isa good choice.
Example 1 - Small Ofce Passive Beams Selection (SI)
Person
SMALL OFFICE
Passive Beam
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
19/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-19
Return to product page
Active & Passive BeamsEngineering Guide
Active beam systems will vary inperormance, coniguration and layoutdepending on the application. There are,however, some characteristics that arecommonformostsystems.Furthermore,the perormance o active beams is largelydependent on a common set o actors.This section will discuss how actors suchas supply air volume and chilled watertemperature aect the perormance andlayout o active beams. Table 3 showscommon design characteristics or activebeam systems.
Product Selection and Location Active Beams
Perormance
The perormance o an active beam isdependent on several actors:
Activebeamconguration
Coilcircuitry
Primaryairow(plenumpressure)
Waterow
As discussed previously, there are severalcongurations o active beams. The mostcommon is the linear type, which is availablein both 1 way and 2 way air patterns. A thirdtype is modular and typically has a 4 waydischarge.
Active beams are appropriate or heatingand cooling. The coil circuitry has a largeeect on the beam perormance. I the beam
is to be used or cooling and heating, it wouldusually have a 4 pipe coil. A 4 pipe coil sharesns between two separate circuits. I thebeam is used or either cooling or heatingonly, the beam may make use o the entirecoil with a single circuit, thereby allowingadditional heat transer rom the water tothe air. The primary driver o active beamcapacity is the plenum pressure. Figure 30and Figure 31 show the air path o linearand modular beams in cooling.
As discussed, it is the primary air that inducesthe room air through the coil, the rate owhich is determined by the nozzle size andthe plenum pressure. A good measure orthe overall perormance o an active beamis known as the transer eciency. This isthe ratio o total heat transerred by the coilper unit volume o primary air:
Typical values or transer eciency vary byapplication type but in general, the higherthe eciency, the more energy savings areavailable or a given system. The transereciency is largely dependent on the air-side load raction and the sensible heat ratio.
Active Beam Selection and Design Procedure
IP
Room Temperature 74Fto78Finsummer,68Fto72Finwinter
Water Temperature, Cooling 55Fto58FEWT,5Fto8F T
Design Sound Levels < 40 NC
Cooling Capacity Up to 1000 Btu/ht
Water Temperature, Heating 110Fto130FEWT,10Fto20F T
Heating Capacity Up to 1500 Btu/ht
Ventilation Requirement 0.1 to 0.5 cm/t2 foor area
Ventilation Capability 5 to 30 cm/t
Primary Air Supply Temperature 50Fto65F
Inlet Static Pressure 0.2 in. w.g. to 1.0 in. w.g. external
SI
Room Temperature 23 C to 25 C in summer, 20 C to 22 C in winter
Water Temperature, Cooling 13Cto15CEWT,3Kto5K TDesign Sound Levels < 40 NC
Cooling Capacity Up to 1000 W/m
Water Temperature, Heating 60Cto70CEWT,5Kto12K
Heating Capacity Up to 1500 W/m
Ventilation Requirement 0.5 to 2.5 L/s m2 foor area
Ventilation Capability 7to40L/sm2
Primary Air Supply Temperature 10 C to 18 C
Inlet Static Pressure 50 Pa to 250 Pa external
Table 3: Design values or active beam systems
Figure 28: Linear type active beam Figure 29: Modular type active beam
Figure 30: Air fow diagram o a typicallinear active beam in cooling
Nozzles
Plenum
Primary Air
Room Air
Figure 31: Air fow diagram o a modulabeam in cooling
Room Air
Nozzles
Plenum
Primary Air
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
20/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-20
Return to product page
Active & Passive BeamsEngineering Guide
Active Beam Selection and Design Procedure
The higher the sensible load raction is, thesmaller the beam nozzle can be, resultingin a higher induction ratio, dened as theratio o the induced mass air fow to that othe primary air:
The selection o smaller nozzles also resultsin higher plenum pressures or a xedprimary air fow rate. Larger nozzles willhave a lower induction ratio but allow moreprimary air to be supplied, though at a lowertranser eciency, as shown in Figure 32.
Figure 33shows the water-side perormanceo a typical beam vs. air fow. The curvescorrespond with various nozzle sizesincreasing in diameter rom let to right. Thelength o the curves is dened by standardoperating pressures. It is noted romthe graphs that the capacity o the beamincreases as more air is supplied, thoughnot in a linear ashion.
Figure 34 shows how the increase incapacity is dependent on the air volume.As shown in the gure, as the nozzle sizeincreases to provide a ve-old increaseinairvolume,onlya175%increaseinthewater-side capacity is realized, while thetranser eciency has reduced by 65%.
The water fow rate in the coil aects twoperormance actors:
The heat transer between the water andthe coil which is dependent on whether thefow is laminar (poor) or turbulent (good).
The mean water temperature, or the averagetemperature in the coil. The higher the fowrate, the closer the discharge temperaturewill be to that o the inlet, assuming nochange in heat transer, thereby changingthe average water temperature in the coil.
Figure 32: Transer eciency is reduced by increasing nozzle size
TransferEfficiency
Smaller Nozzle Larger Nozzle
Figure 33: Capacity o a typical active beam vs. primary air fow
Figure 34: Capacity vs. air volume
0
0
0 10 20 30 40 50 60 70
10 20 30 40 50
400
200
600
800
1000
1200
1400
0
200
400
600
800
1000
1200
Ca
pacity,Btu/hft
C
apacity,W/m
Air Flow, cfm/ft
Air Flow, L /sm
0
100 200 300 400 500 600
100
120
140
160
180
20
40
60
80
200 Capacity Increase
Transfer Efficiency
IncreaseinWater-SideCapacity
,%
Increase in Air Volume, %
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
21/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-21
Return to product page
Active & Passive BeamsEngineering Guide
Figure 35 shows the eect o the waterfow rate, indicated by Reynolds number,on the capacity o a typical active beam.As indicated on the chart, increasing thefow rate into the transitional and turbulentranges (Re > 2300, shown in blue on thegraph) causes an increase in the output othe beam.
The water fow rate is largely dependenton the pressure drop and return watertemperature that are acceptable to thedesigner. In most cases, the water fowrate should be selected to be ully turbulentunder design conditions.
The dierence between the mean watertemperature and the room air temperatureis one o the primary drivers o the beamperormance. The larger this dierenceis, the higher the convective heat transerpotential, as shown inFigure 36.Conversely,a lower temperature dierence will reducethe amount o exchange, and therebycapacity. As a result, it is desirable roma capacity standpoint to select an entrywater temperature as low as possible, whilemaintaining it above the dew point in theroom to ensure sensible-only cooling.
In some instances, it might be advantageousto have higher supply and return watertemperatures, where it makes sense roman equipment standpoint. This may alsooer some control simplication where the
output o the beam is determined by theload in the room:
As the load increases, the air temperaturerises and increases the dierence betweenit and t w, thereby increasing beamperormance.
As the load decreases, the air temperaturealls and reduces the cooling capacity o thebeam.
Active Beam Selection and Design Procedure
Figure 35: Active beam capacity vs. water fow
40
0 2000 4000 6000 8000 10000 12000
50
60
70
80
90
100
Capacity,
%
Re
Figure 36: Active beam capacity vs. dierence between the mean water and room airtemperatures
0
0 5 10 15 20
0 2 4 6 8 10
20
40
60
80
100
120
Capacity,
%
tw - troom ,F
tw - troom , K
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
22/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-22
Return to product page
Active & Passive BeamsEngineering Guide
Design Procedure Active Beams
1. Determine the ventilation requirement
Theventilationrequirementshouldbecalculatedtomeetventilationcodes.Forexample,usingASHRAEStandard62-2004todeterminethe minimum resh air fow rate:
H1
2. Determine the required supply dew-point temperature to remove the latent load
H2
I the required humidity ratio is not practical, recalculate the supply air volume required with the desired humidity ratio.
3. Determine the supply air volume
The supply air volume is the maximum volume required by code or ventilation and the volume required or controlling the latent load:
H3
4. Determine the sensible cooling capacity o the supply air
IP H4
SI H4
5. Determine the sensible cooling required rom the water side
H5
6. Select a beam or series o beams
Select a beam or series o beams that will provide the appropriate amount o cooling and heating using appropriate entry watertemperatures and throw distances.
7. Review that the primary air calculation in (3) is still appropriate
H6
8. Lay out the beams in such a way that the comort in the space is maximized
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
23/48L-23
Return to product page
Active & Passive BeamsEngineering Guide
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are sot conversion.Imperial dimensions are converted to metric and rounded to the nearest millimeter.
Example 2 - Small Ofce Active Beam Selection (IP)
12 ft
9 ft10 ft
SMALL OFFICE
Window
ConsiderthesmallofcepresentedinExample1-SmallOfcePassiveBeamSelection.
Design Considerations
Occupants 2
Set-Point 75F
FloorArea 120 t
Exterior Wall 108 t
Volume 1080ft
qoz 800 Btu/h
ql 825 Btu/h
qex 1450 Btu/h
qT 3075Btu/h
Qs 38 cm
ts 50F
tCHWS 57F
Determine
a) A suitable active beam to meet the cooling requirement.
b) A practical layout or the space.
Solution
Fromexample1-SmallOfcePassiveBeamSelection.
Perormance
Total Capacity 3075Btu/h
Air fow Required or Dehumidication 38 cm
Supply Air Temperature 50F
CHWS Temperature 57F
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
24/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-24
Return to product page
Active & Passive BeamsEngineering Guide
Using selection sotware to select beams with these parameters provides several possible solutions:
Example 2 - Small Ofce Active Beam Selection (IP)
Parameter Option 1 (ACBL) Option 2 (ACBL) Option 3 (ACBM)
Total Capacity 3074Btu/h 3076Btu/h 3077Btu/h
Length 72in. 48 in. 48 in.
Width 24 in. 24 in. 24 in.
Air fow 35 cm 40 cm 40 cm
Throw @ 50 pm 10 t 13 t 10 t
Air Pressure Drop 0.75in. 0.42 in. 0.56 in.
Transer Eciency 88 Btu/h cm 77Btu/hcfm 77Btu/hcfm
WaterFlowRate 0.41 gpm 1.2 gpm 0.61 gpm
Water Pressure Drop 0.63 t hd 3.1 t hd 1.26 t hd
NC 15 18 17
The rst option meets the capacity requirements though has slightly lower air fow than that required to handle the latent loads; it isalso the most ecient option. The second and third options both meet the capacity and air fow requirements.
Revisiting the air volume required:
Fortheprivateofce,eitherselection(2)or(3)isappropriate.Themodularunithastheadvantageoflowerthrowandwouldresultinlower occupied zone velocities. The linear unit can be selected with an integrated return grille, increasing the overall length o the beamwhile allowing the return to appear to be a part o the beam. Both o these layouts are shown below:
Section ViewPlan View
Person
Person
2 wayBeam
IntegratedReturn
Return
SMALL OFFICE
Person
SMALL OFFICE
Person
ModularBeam
Window
Window
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
25/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-25
Return to product page
Active & Passive BeamsEngineering Guide
Example 2 - Small Ofce Active Beam Selection (SI)
12 ft
9 ft10 ft
SMALL OFFICE
Window
ConsiderthesmallofcepresentedinExample1-SmallOfcePassiveBeamSelection.
Design Considerations
Occupants 2
Set-Point 24 C
FloorArea 12 m
Exterior Wall 12 m
Volume 36m
qoz 240 W
ql 300 W
qex 405 W
qT 945 W
Qs 22.5 L/s
ts 10 C
tCHWS 14 C
Determine
a) A suitable active beam to meet the cooling requirement.
b) A practical layout or the space.
Solution
Fromexample1-SmallOfcePassiveBeamSelection.
Perormance
Total Capacity 945 WAir fow Required or Dehumidication 22.5 L/s
Supply Air Temperature 10 C
CHWS Temperature 14 C
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
26/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-26
Return to product page
Active & Passive BeamsEngineering Guide
Using selection sotware to select beams with these parameters provides several possible solutions:
Example 2 - Small Ofce Active Beam Selection (SI)
Parameter Option 1 (ACBL) Option 2 (ACBL) Option 3 (ACBM)
Total Capacity 945 W 946 W 952 W
Length 1.8 m 1.2 m 1.2 m
Width 0.6 m 0.6 m 0.6 m
Air fow 16.5 L/s 22.5 L/s 22.5 L/s
Throw @ 50 pm 3.9 m 3.7m 3 m
Air Pressure Drop 187Pa 107Pa 100 Pa
Transer Eciency 48 Ws/L 25 Ws/L 25 Ws/L
WaterFlowRate 93 L/h 216 L/h 148 L/h
Water Pressure Drop 1.88 kPa 8.07kPa 4.18 kPaNC 15 21 17
The rst option meets the capacity requirements though has slightly lower air fow than that required to handle the latent loads; it isalso the most ecient option. The second and third options both meet the capacity and air fow requirements.
Revisiting the air volume required:
Fortheprivateofce,eitherselection(2)or(3)isappropriate.Themodularunithastheadvantageoflowerthrowandwouldresultinlower occupied zone velocities. The linear unit can be selected with an integrated return grille, increasing the overall length o the beamwhile allowing the return to appear to be a part o the beam. Both o these layouts are shown below:
Section ViewPlan View
Person
Person
2 wayBeam
IntegratedReturn
Return
SMALL OFFICE
Person
SMALL OFFICE
Person
ModularBeam
Window
Window
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
27/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-27
Return to product page
Active & Passive BeamsEngineering Guide
In active beam selection, there is oten atrade-o required between the primary airvolume and the beam length. When thetotal capacity o the beam is consideredthere is an increase in the capacity with anincrease in the primary air volume; though,as indicated in Figure 37, this is largely dueto the increased capacity o the primary airand only slightly due to an increase in theperormance o the cooling coil. The overalleect o an increase in primary air volumeis invariably a reduction in the transereciency o the beam; thereore, care mustbe taken when increasing the air volume pastwhat is required to satisy the ventilationrequirements and latent loads.
In order to determine i it is necessary toincrease the air volume beyond that which isrequired, several actors should be weighed:
1. Beam Size
With higher capacity per unit length o beamit is possible to reduce the size o the beam,which may reduce the visual impact o theHVAC system. It may also help to t beamsinto spaces with high specic loads, such asa corner oce in a hot climate like Phoenixor Dubai.
2. First Cost
The reduction in overall size o the beamdoes oer some rst cost savings, thoughthese should be compared to the rst costadditions required o the air handling system,
including equipment and ductwork. In mostapplications, these costs are similar and maynot oer the benet sought.
3. Energy
By decreasing the transer eciency (orincreasing the percentage o the loadmanaged by air rather than water), there isusually a reduction in the overall eciency othe system. In most cases, it is more ecientto pump energy through the building withwater than air, and so an increase in the loadmanaged by air may cause an increase in thesystem horsepower.
4. Noise
Active beam noise is largely dependent onprimary air fow, thereore an increase in the
primary air volume to the beam will increasethe noise levels in the space.
5. Control
With additional air supplied to the beam,there is an increased risk o overcoolingthe zone under part-load conditions. Thesesystems are typically constant volume, whichreduces the systems ability to control thezone temperature i the minimum capacityo the beam is increased due to an increasein primary air volume.
Managing Primary Air Volume and Capacity
6. Lie-Cycle Cost
This type o design decision is oten best madewith a lie-cycle cost analysis to determine thecost impact over the lie o the building.
There are applications where an increase inair volume is a reasonable design decision,either due to very large specic loads or highventilation rates, such as in a health careapplication. In situations where the specicload is high, there are some options thatwill allow the system to meet the required
capacity but will also maximize the energyeciency:
1. Select an active beam and a passivebeam together.
This allows the designer to minimize theair and add sensible cooling capacity whererequired. This also signicantly increasesthe transer eiciency o the room bykeeping the air volume as low as possiblewhile increasing the sensible capacity.
2. Employ a variable air volume (VAV)strategy.
Whether or an individual oice or ora larger zone, VAV allows the system tosupply the capacity required under designconditions while allowing the air volume
to be turned down to minimum during o-peak hours. The most ecient congurationwould have the air turn up/down only as thesecond stage o cooling, as shown in thediagram below.
Max. Water Flow
Min. Water Flow
Dead Band
Tset-point
CHW
SFl
owHWSFlow
Max. Air Flow
Air
flow
Airfl
ow
Min. Air Flow
Cool WarmRoom Condition
Figure 37: VAV control sequence
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
28/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-28
Return to product page
Active & Passive BeamsEngineering Guide
Example 3 - Small Ofce with High Internal Gains (IP)
Consider the small oce presented in Example 1, though now in a hot climate with an increased solar gain:
12 ft
9 ft10 ft
SMALL OFFICE
Window
Design Considerations
Occupants 2
Set-Point 75F
FloorArea 120 t
Exterior Wall 108 t
Volume 1080ft
qoz 800 Btu/h
ql 825 Btu/h
qex 6575Btu/h
qT 8200 Btu/h
Qs 38 cm
ts 50F
tCHWS 57F
Compare
a)AsuitableactivebeamwithconstantairsupplytoonewithVAV,assuming2175Btu/hofenvelopeloadinoff-peakhours.
b) A suitable active beam to a combination o active and passive beams.
Solution
a) Using sotware, select a beam with the ollowing requirements.
Perormance
Total Capacity 8200 Btu/h
AirFlowrequiredforDehumidication 35 cm
Supply Air Temperature 50F
CHWS Temperature 57F
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
29/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-29
Return to product page
Active & Passive BeamsEngineering Guide
Example 3 - Small Ofce with High Internal Gains (IP)
In this case, increasing the supply air volume was required in order to meet the capacity required:
Parameter Peak Load O-Peak Load
Total Capacity 8202 Btu/h 3817Btu/h
Length 96 in. 96 in.
Width 24 in. 24 in.
AirFlow 140 cm 55 cm
Throw 18 t 10 t
Air Pressure Drop 0.88 in. w.g. 0.15 in. w.g.
Transer Eciency 59 Btu/h cm 69 Btu/h cm
WaterFlowRate 1.23 gpm 1.23 gpm
Water Pressure Drop 5.8 t hd 5.8 t hd
NC 32
7/30/2019 Chilled Beam- Engineering_Guide
30/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-30
Return to product page
Active & Passive BeamsEngineering Guide
Inthisexample,anactivebeamandapassivebeamwereselectedtobethesamesizetosimplifythelayout.Furthermore,thewater-sidepressure drop has been selected to be equivalent to make the piping more straightorward. These beams could be laid out and piped as shown:
Person
SMALL OFFICECHWS
CHWR
Window
P
assiveBeam
A
ctiveBeam
Example 3 - Small Ofce with High Internal Gains (IP)
Person
Person
Beam
SMALL OFFICE
Window Max Load
The layout is the same as in example 1. Reviewing the throw pattern at peak load:
b) Using software again, an active beam and passive beam are selected together
Parameter Passive Beam Active Beam Total
Total Capacity 2718Btu/h 5481 Btu/h 8200 Btu/h
Length 96 in. 96 in. -
Width 24 in. 24 in. -
AirFlow 0 55 cm 55 cm
Throw - 15 t -
Air Pressure Drop n/a 1 in. 1 in.
Transer Eciency n/a 100 Btu/h cm 149 Btu/h cmWaterFlowRate 1.29 gpm 1.65 gpm 2.94 gpm
Water Pressure Drop 9.8 t hd 9.9 t hd 9.9 t hd
NC - 20 20
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
31/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-31
Return to product page
Active & Passive BeamsEngineering Guide
Example 3 - Small Ofce with High Internal Gains (IP)
In this case the air pattern rom the active beam passes over the ace o the passive beam, thereore the concern o velocity below thepassivebeamislargelyeliminated.Furthermore,thistypeofarrangementtendstoincreasetheairvolumethroughthepassivebeam,which would typically result in an increase in perormance.
Comparing the two options:
Parameter Active Beam Active &Passive Beam
Total Capacity 8202 Btu/h 8200 Btu/h
AirFlow 140 cm 55 cm
Throw 18 t 15 t
Air Pressure Drop 0.88 in. 1 in.
Transer Eciency 59 Btu/h cm 149 Btu/h cm
WaterFlowRate 1.23 gpm 2.94 gpm
Water Pressure Drop 5.8 t hd 9.9 t hd
NC 32 20
The dierence between the two is largely in the supply air volume and noise. Selection (1) requires an additional 85 cm, or 250% theamount o air required in the second selection and also has a signicantly higher NC level. This will translate into larger air handlingequipment and ductwork (even or the VAV case), adding cost as well as additional energy to move the air through the building. In someareas, the selection o the system with lower supply air volume translates into signicant energy savings:
This energy savings is or the sensible cooling o the outdoor air only; additional savings would exist in the latent cooling and transporenergy o the additional air volume. There is additional cost in the passive beam, though it may be oset by the increase in equipmenand distribution cost as well as the energy required or the higher air volume case. This will however, depend largely on the applicationand building design.
Annualdegree -hours
Annual ton - hours savedper ofce
Total annual kWh saved perofce
Phoenix 76121 582.33 3654
Atlanta 46253.4 353.84 2220
Minneapolis 25494.8 195.04 1224
Seattle 19345.8 148.00 929
Washington DC 36635.9 280.26 1759
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
32/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-32
Return to product page
Hydronic Heating & Cooling SystemsEngineering Guide
Example 3 - Small Ofce with High Internal Gains (SI)
Consider the small oce presented in Example 1, though now in a hot climate with an increased solar gain:
Design Considerations
Occupants 2
Set-Point 24 C
FloorArea 12 m
Exterior Wall 12 m
Volume 36m
qoz 240 W
ql 300 W
qex 1860 W
qT 2400 W
Qs 22.5 L/s
ts 10 C
tCHWS 14 C
Compare
a) A suitable active beam with constant air supply to one with VAV, assuming 580 W o envelope load in o-peak hours.
b) A suitable active beam to a combination o active and passive beams.
Solution
a) Using sotware, select a beam with the ollowing requirements.
Perormance
Total Capacity 2400 W
AirFlowrequiredforDehumidication 22.5 L/s
Supply Air Temperature 10 C
CHWS Temperature 14 C
3 m
4 m
3 m
SMALL OFFICE
Window
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
33/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-33
Return to product page
Hydronic Heating & Cooling SystemsEngineering Guide
Example 3 - Small Ofce with High Internal Gains (SI)
In this case, increasing the supply air volume was required in order to meet the capacity required:
Parameter Peak Load O-Peak Load
Total Capacity 2400 W 1140 W
Length 2.4 m 2.4 m
Width 600 mm 600 mm
AirFlow 66 L/s 26 L/s
Throw 4.9 m 2.4 m
Air Pressure Drop 221 Pa 35 Pa
Transer Eciency 19 W s/L 27Ws/L
WaterFlowRate 218 L/h 218 L/h
Water Pressure Drop 14.6 kPa 14.6 kPa
NC 33
7/30/2019 Chilled Beam- Engineering_Guide
34/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-34
Return to product page
Active & Passive BeamsEngineering Guide
Example 3 - Small Ofce with High Internal Gains (SI)
Inthisexample,anactivebeamandapassivebeamwereselectedtobethesamesizetosimplifythelayout.Furthermore,thewater-side pressure drop has been selected to be equivalent to make the piping more straightorward. These beams could be laid out andpiped as shown:
Person
SMALL OFFICECHWS
CHWR
Window
PassiveBeam
ActiveBeam
The layout is the same as in example 1. Reviewing the throw pattern at peak load:
b) Using software again, an active beam and passive beam are selected together
Parameter Passive Beam Active Beam Total
Total Capacity 811 W 1606 W 2417W
Length 2.4 m 2.4 m -
Width 600 mm 600 mm -
AirFlow 0 26 L/s 26 L/s
Throw - 3.7m 3.7m
Air Pressure Drop n/a 296 Pa 296 PaTranser Eciency n/a 45 Ws/L 76Ws/L
WaterFlowRate 193 L/h 220 L/h 413 L/h
Water Pressure Drop 8.1 kPa 14.9 kPa 14.9 kPa
NC - 21 21
Person
Person
Beam
SMALL OFFICE
Window Max Load
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
35/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-35
Return to product page
Active & Passive BeamsEngineering Guide
Example 3 - Small Ofce with High Internal Gains (SI)
In this case the air pattern rom the active beam passes over the ace o the passive beam, thereore the concern o velocity below the
passivebeamislargelyeliminated.Furthermore,thistypeofarrangementtendstoincreasetheairvolumethroughthepassivebeam,which would typically result in an increase in perormance.
Comparing the two options:
The dierence between the two is largely in the supply air volume and noise. Selection (1) requires an additional 40 L/s, or 250% theamount o air required in the second selection, and also has a signicantly higher NC level. This will translate into larger air handlingequipment and ductwork (even or the VAV case), adding cost as well as additional energy to move the air through the building. In someareas, the selection o the system with lower supply air volume translates into signicant energy savings:
Parameter Active Beam Active &Passive Beam
Total Capacity 2400 W 2417W
AirFlow 66 L/s 26 L/s
Throw 4.9 m 3.7m
Air Pressure Drop 221 Pa 296 Pa
Transer Eciency 19 Ws/L 76Ws/L
WaterFlowRate 218 L/h 413 L/h
Water Pressure Drop 14.6 kPa 14.9 kPa
NC 33 21
Annualdegree - hours
Total annual kWhsaved per ofce
Phoenix 76121 3654
Atlanta 46253 2220
Minneapolis 25495 1224
Seattle 19346 929
Washington DC 36636 1759
This energy savings is or the sensible cooling o the outdoor air only; additional savings would exist in the latent cooling and transporenergy o the additional air volume. There is additional cost in the passive beam, though it may be oset by the increase in equipmenand distribution cost as well as the energy required or the higher air volume case. This will however, depend largely on the applicationand building design.
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
36/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-36
Return to product page
Active & Passive BeamsEngineering Guide
Example 4 - Active Beams in a Computer Lab (IP)
This space is a school computer lab designed or 26 occupants, 26 computers with one LCD monitor each, a projector,threeprinters,T8orescentlighting,andhas atemperatureset-pointof75 Fat 50%RHin thesummer.Theroomis50 ftlong,50 t wide, and has a foor-to-ceiling height o 9 t. The ceiling is exposed, with possible duct connections in the interior o the space.
Space Considerations
Someoftheassumptionsmadeforthisspaceareasfollows:
Inltrationisminimal,andisneglectedforthepurposesofthisexample.
Thespecicheatanddensityoftheairforthisexamplewillbe0.24Btu/lbFand0.075lb/ft2respectively. Theairhandlingsystemutilizesenergyrecoverytoprovide65Fat50Fdewpoint.Determinetheventilationrequirement
Design Considerations Total
OccupantLoad 250 Btu/h person 6500 Btu/h
Lighting Load 3 Btu/ht2foor 7500Btu/h
Computer Loads 450 Btu/h person 11700Btu/h
Projector Load 188 Btu/h 188 Btu/h
Printer Loads 444 Btu/h 444 Btu/h
Envelope Load 14.6 Btu/ht2aade 6570Btu/h
Total Load 32902 Btu/h
LatentLoad-OccupantLoad 200 Btu/h person 5200 Btu/h
Theventilationrequirementshouldbecalculatedtomeetventilationcodes.Forexample,usingASHRAEStandard62-2004todeterminethe minimum resh air fow rate or a typical oce space:
Determine the required supply dew-point temperature to remove the latent load
Usingahumidityratioofthesupplyairat50Fdewpointandthedesignconditions(75F,50%RH):
Printers Projector
COMPUTER LAB
50ft
50 ft
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
37/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-37
Return to product page
Active & Passive BeamsEngineering Guide
The supply air volume to the oce is the maximum o the volume required by code or ventilation and the volume required or controllingthe latent load:
Using sotware to select a beam with the ollowing requirements:
Example 4 - Active Beams in a Computer Lab (IP)
Perormance
Total Capacity 32902 Btu/h
AirFlowRequiredforDehumidication 632 cm
Supply Air Temperature 65F
Arrives at the ollowing options:
Parameter Option 1 (ACBL) Option 2 (ACBL) Option 3 (ACBM)
Total Capacity 32197Btu/h 33044 Btu/h 32933 Btu/h
Quantity 4 6 6
Length 120 in. 96 in. 48 in.
Width 24 in. 24 in. 24 in.
AirFlow 640 cm 780cfm 870cfm
Throw 11 t 17ft -
Air Pressure Drop 0.99 in. 0.76in. 0.83 in.
Transer Eciency 50.3 Btu/h cm 42.4 Btu/h cm 37.9Btu/hcfm
WaterFlowRate 5.96 gpm 6.48 gpm 9.42 gpm
Water Pressure Drop 9.9 t hd 4.6 t hd 0.71fthd
NC 27 30 -
Oftheseoptions,thesecondcombinationofsix8ftlongbeamsisthebestcombinationofcapacity,efciencyandthrow.Withsixbeams, these could be laid out as shown below:
COMPUTER LAB
Printers Projector
CHWS
CHWR
BeamBeam Beam
BeamBeam Beam
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
38/48
All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2011.Imperial dimensions are converted to metric and rounded to the nearest millimeter.L-38
Return to product page
Active & Passive BeamsEngineering Guide
Example 4 - Active Beams in a Computer Lab (SI)
This space is a school computer lab designed or 26 occupants, 26 computers with one LCD monitor each, a projector, 3 printers, T8forescent lighting, and has a temperature set-point o 24 C at 50% RH in the summer. The room is 15 m long, 15 m wide, and has afoor-to-ceiling height o 3 m. The ceiling is exposed, with duct connections possible in the interior o the space.
15m
15 m
Printers Projector
COMPUTER LAB
Space Considerations
Some o the assumptions made or this space are as ollows:
Inltrationisminimal,andisneglectedforthepurposesofthisexample.
Thespecicheatanddensityoftheairwillbe1.007kgKand1.3kg/m3respectively. Theairhandlingsystemutilizesenergyrecoverytoprovide18Cat10Cdewpoint.
Design Considerations Total
OccupantLoad 75W/person 1950 W
Lighting Load 25 W/m2foor 5625 W
Computer Loads 130 W/person 3380 W
Projector Load 55 W 55 W
Printer Loads 130 W 130 W
Envelope Load 46 W/m2aade 2070W
Total Load 13210 W
LatentLoads-OccupantLoad 60 W/person 1560 W
Determine the ventilation requirementTheventilationrequirementshouldbecalculatedtomeetventilationcodes.Forexample,usingASHRAEStandard62-2004todeterminethe minimum resh air fow rate or a typical oce space:
Determine the required supply dew-point temperature to remove the latent load.
Using a humidity ratio o the supply air at 10 C dew point and the design conditions (24 C, 50% RH):
http://www.price-hvac.com/Catalog/Section_L/CatalogData.aspxhttp://www.price-hvac.com/Catalog/Section_L/CatalogData.aspx7/30/2019 Chilled Beam- Engineering_Guide
39/48
Copyright Price Industries Limited 2011. All Metric dimensions ( ) are soft conversion .Imperial dimensions are converted to metric and rounded to the nearest millimeter. L-39
Return to product page
Active & Passive BeamsEngineering Guide
The supply air volume to the oce is the maximum volume required by code or ventilation and the volume required or controllingthe latent load:
Using sotware, select a beam with the ollowing requirements:
Example 4 - Active Beams in a Computer Lab (SI)
Perormance
Total Capacity 13210 W
AirFlowRequiredforDehumidication 320 L/s
Supply Air Temperature 18 C
Arrives at the ollowing options:
Parameter Option 1 (ACBL) Option 2 (ACBL) Option 3 (ACBM)
Total Capacity 13221 W 13216 W 13220 W
Quantity 6 7 8
Length 3000 mm 2400 mm 1200 mm
Width 600 mm 600 mm 600 mm
AirFlow 426 L/s 497L/s 696 L/s
Throw 3.3 m 6 m -
Air Pressure Drop 220 Pa 250 Pa 193 Pa
Transer Eciency 31 W s/L 17Ws/L 19 W s/L
WaterFlowRate 302 L/s 345 L/s 368 L/s
Water Pressure Drop 9.92 kPa 10.32 kPa 9.12 kPa
NC 27 33 -
Oftheseoptions,thesecondcombinationofsix2.4mbeamsisthebestcombinationofcapacity,efciencyandthrow.Withsi