24
Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro [email protected]

Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro

[email protected]

Page 2: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

1. Introduction 2. Maximum HVDC Loading3. Transmission Options4. Planning Studies for FCLs5. Conclusions

Page 3: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

225MW

2175 MW225 MW

LimesoneLong Spruce

Kettle

Jenpeg

Pine FallsGreat FallsMcArthur FallsSeven SistersPointe du BoisSlave FallsSelkirk

Brandon

Grand Rapids

Laurie River

Kelsey

Selkirk -Natural Gas

Brandon – Coal

Brandon – Combustion Turbine

Diesel – Brochet, Lac Brochet, Tadoule Lake, Shamattawa

Route of HVDC

Other transmission

Wuskwatim Services for over 500 000 electricity and 250 000 gas customers

A total generating capacity about 5700 MW produced mainly by 15 hydroelectric stations (95%), and 2 thermal stations.

Manitoba Hydro Generating Stations and Interconnections

1. INTRODUCTION

Page 4: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Provide about 70% generating capacity.

Bipole I and II HVdc lines constructed on the same Right-of-way in 1970

900km overhead lines, difficult terrain and access in the north

Terminated at a common station – Dorsey (inverter)

Parallel operation during emergency (i.e. the loss of one dc tower ) to use the full dc line capacity

The Existing Bipole I and II System

Page 5: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

BPI converter : +/- 463.5kV/1854MW

Commissioned in 1971

Three valve groups per pole

Initially built with Mercury Valves

Refurbished with thyrisors in 1992 and 2004

The Existing Bipole I and II System

BP2 converter: +/- 500kV/2000MW

Two valve groups per pole

Thyristor valves are in service in the range of 30 to 37 years.

Typical thyristor life time around 30-35 year as per industry practice

Page 6: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Future Northern Collector System (NCS) includes five generating stations and three HVDC rectifier stations, of which two new generating stations and Bipole III are new additions to the system.

Dorsey and Riel 230 kV station includes HVDC inverter station and major transmission lines connected to domestic loads and export services

Bipole I/II with over 900 km of DC line at the same corridor

Major Power System Expansion

Bipole III with 1380 km of DC line in west corridor

Page 7: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

System Issues Mitigated

Bipole III transmission corridor added to the existing single corridorBipole III Riel station added to Dorsey

single location for Bipole I and II inverter stationsNew generation support to export sales

and domestic load demands

Page 8: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

MAXIMUM HVDC LOADING RESULTING IN

A large increase in station fault level More coupled network in NCS and southern AC system• A large increase in DC power losses during a single fault at NCS• The operation of Under Frequency Load Shed (UFLS) protection

EVALUATING TRANSMISSION OPTIONS

Fault level study Power flow analysis Stability performance Cost estimate

Page 9: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

2. MAXIMUM HVDC LOADING

Future Northern Collector System

Bipole III

ISD in 2018

(net 1350MW)(net 1224MW)

ISD in 2020ISD TBD

(net 980 MW)

KEEWATINOHK

Page 10: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

1

21,2 %1

%VindropVoltage

VMIIF ∆=

Multi-infeed Interaction Factor (MIIF)The MIIF is a parameter for estimating the degree of voltage interaction between two ac busses to which converters are connected. The multi-infeed interaction factor MIIF could be obtained by applying 1% voltage change at the converter station being studied.

(1)

Page 11: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

NCS system Converter Stations NO MIIF (%)

Existing System Radisson 1 MIIF21 = 0.315

Henday 2 MIIF12 = 0.417

Future SystemBipole III

+Keeyask+Conawapa

Radisson 1 MIIF31 = 0.195MIIF21 = 0.248

Henday 2 MIIF32 = 0.645MIIF21 = 0.342

Keewatinohk 3 MIIF13 = 0.228MIIF23 = 0.548

Table 1: MIIFs of NCS Converter Stations

Henday and Keewatinoow have high electrical coupling with MIIFs above 0.5, which could result in planning concerns.

Page 12: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

TABLE 2: NCS VOLTAGE DURING A STATION FAULT

Fault LocationVoltage (p.u.)

Radisson Henday Keewatinoow

No Fault 1.00 1.00 1.00

Radisson 0 0.74 0.8

Henday 0.63 0 0.35

Long Spruce 0.43 0.43 0.45

Keewatinohk 0.79 0.5 0

Long Spruce and Keewatinohk station fault result in Hendaybus voltage falling below 0.5 pu.

Page 13: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Table 3: NCS POWER DURING A STATION FAULT

Fault LocationPower (MW)(% to its pre-fault level)

BP I BP II BP III

No Fault 1751 1887 1887

Radisson 0 1338 (71%) 1471(78%)

Henday 1034(59%) 0 448 (24%)

Long Spruce 640 (37%) 0 775 (41%)

Keewatinohk 1342 (77%) 0 0

Long Spruce and Keewatinohk station fault result in Hendaybus voltage falling below 0.5 pu and thus trig the Bipole II under voltage protection.

Page 14: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Line Fault Dorsey Riel

KY-R Line Near Radisson 59.4 59.5

LS-HEN Line Near Long Spruce

59.3 59.3

KW-HEN Line Near Henday

59.2 59.2

KW-HEN Line Near Keewatinohk

59.3 59.2

Based on North American Electric Reliability Corporation (NERC) criteria, any single AC fault with normal clearing should not cause the southern system to shed load. The MH load shedding protection is proposed to be set at 59.3 Hz with a duration of less than 65 ms in future system.

Table 4: Dorsey and Riel Frequency Responses

Page 15: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

System Stations SLGF(kA) MSIR(kA) Cap (%)

Existing

LS 33.2 40 83

Radisson 41.1 50 82

Henday 31.6 50 63

BPIIIKY+CW

LS 40.6 40 102

Radisson 50.7 63 81

Henday 42 50 84

Table 5: Fault Level at NCS Stations

In the Northern Collector System, a Single Line to Ground Fault (SLGF) creates the highest station fault level. The practice at Manitoba Hydro is to maintain the station short circuit levels below 95% of their breaker’s Maximum Symmetrical Interrupting Ratings (MSIR). The Radisson station breakers will be replaced by 2020.

Page 16: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

3. TRANSMISSION OPTIONSFollow system criteria and keep maximum generation production

Bipole III

ISD at 2018

(net 1350MW)(net 1024MW)

ISD at 2020ISD at 2020

500 KV

Kettle 2 units(204 MW)

500 kV ac corridor separated from Bipole I, II and III. Keeyask generation and Keetle 2 units connected to 500 kV ac transmission line. Higher costs Best Technical Option

500 kV

Option 1: 500 kV ac development

(net 980 MW)

KEEWATINOHK

Page 17: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Option 2: Splitting NCS – 100 MW Kettle to AC 230 KV system

KETTLE100 MW

TO AC

Connect one Kettle unit to AC Two Kettle units on NCS1 with 204 MW spare One Kettle unit on NCS2 with 473 MW spare Less costsMeet technical requirement

NCS1 NCS2(net 980 MW)

KEEWATINOHK

Page 18: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Option 3: Application of FCLs

Keep NCS intact without splittingFCLs installed near Henday to decouple BPII and BPIII during a faultLowest costsMeet technical requirements of reducing fault level and DC lossesNew technology and new application for transmission level

2xFCL3xFCL

(net 980 MW)

KEEWATINOHK

Page 19: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Table 6: Comparisons of Options

Options Description Generation in DC (MW)

DC Spare over Generation to largest

valve (MW)

Cost ($ M)

1 500 kV AC line 4719 1135MW /500MW Highest

2 Split NCS – 100 MW Kettle to AC2 units on NCS1 and

1 unit on NCS2

NCS1: 1650NCS2: 3827

NCS1: 204 MW/309 MWNCS2: 473 MW/575 MW

Meddle

3 FCLs 5579 575MW/575 Lowest

Page 20: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

4. PLANNING STUDIES FOR OPTION 3 (FCL)

Short Circuit Current Calculation

Fault Locations

Breaker Rating (kA)

kA (no FCLs) kA (with FCLs)

BreakerCapability(%)

Radisson 63.0 50.70 49.50 78.6

Long Spruce 40.0 40.00 34.50 86.3

Henday 50.0 42.01 28.9 57.8

Keewatinohk 50.0 42.7 35.4 70.8

1) Radisson station breakers will be replaced before 2020 and their ratings are 63.0 kA as shown in the table.

2) Option 1 and 2 also meet this technical requirement

Page 21: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Load Flow Studies - NCS Bus Voltage

V <0.5 pu

Page 22: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Table 5: Bipole Power during the Station Faults

Page 23: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

Southern Frequency Responses

Option 1 and 2 also meet this technical requirement.

Page 24: Chenghong Zhou, P.Eng, Pei Wang, P.Eng, Manitoba Hydro · Brandon Grand Rapids Laurie River Kelsey Selkirk -Natural Gas Brandon – Coal Brandon – Combustion Turbine Diesel –

5. CONCLUSIONS

a) Transmission options are recommended and examined on the optimal plans of transmission and generation.

b) The system criteria and cost estimate are considered.c) Planning studies including short circuit analysis, load

flow study and dynamic analysis.d) All options meet the technical requirement. Option 1 is

the best for reducing fault level and DC power losses.e) Option 3 provides the most cost saving.f) The challenge of FCLs is the equipment availability in

transmission level.