Checklist for Type Approvals of Instrument Transformers

  • Upload
    matreng

  • View
    226

  • Download
    1

Embed Size (px)

Citation preview

  • 8/10/2019 Checklist for Type Approvals of Instrument Transformers

    1/3

    Physikalisch-Technische BundesanstaltBraunschweig and Berlin

    AG 2.34 Type Approval & Conformi ty Assessment

    Checklist for type approvals of instrument transformers

    Applied national requirements and ordinances

    PTB-Anforderungen 20.2Eichordnung Anlage20; Abschnitt 2PTB-Testing Instructions for Instrument Transformers

    International standard:

    EN 60044-1 for current transformersEN 60044-2 for inductive voltage transformers

    (1) Informal application for type approval with:

    (2) Description of:

    design and mode of operation of the instrument transformer safety measures taken locations of main mark and protective mark

    (3) Informative photographs of the transformer

    (4) Drawing of:

    rating plate dimensional drawing sectional drawing core

    (5) Block diagram indicating the terminal markings (EN 60044-1/-2)

    (6) Example of a calculation of the transformer:

    calculations easy to reconstruct Mllinger-Gewecke diagram magnetization curve

    (7) Technical data current and voltage transformers:

    rated insulation level and class of insulation

    rated primary current / voltage rated secondary current / voltage rated output rated fequency number of measurement ranges accuracy class extended measurement ranges (current transformer) number of measuring cores number of cores rated short-time thermal current Ith(current transformer) rated voltage factor; rated time; rated thermal output (voltage

    transformer)

    (8) Test sample(s) in arrangement with working group 2.34

    Physikalisch -Techn ische Bundesanstalt, Bundesallee 100 D-38116 Braunschweig, vers. 2008-08-05. Allrights r eserved, No part may be reproduced without the prior wri tten permission o f PTB

  • 8/10/2019 Checklist for Type Approvals of Instrument Transformers

    2/3

    (9) Current transformer:

    Type tests:

    Short-time current tests EN 60044-1 (7.1)

    Temperature rise test PTB-A 20.2 (4.6)EN 60044-1 (7.2)

    Lightning impulse test EN 60044-1 (7.3.2)

    Switching impulse test EN 60044-1 (7.3.3)

    Wet test for outdoor type transformers EN 60044-1 (7.4)

    Determinations of errors of the testsample

    EO-20.2 (3.1.1)PTB-A 20.2 (4)PTB-Testing Instructions (3.4)

    Routine tests:

    Verifications of terminal markings EN 60044-1 (8.1)

    Power-frequency withstand tests onprimary winding

    EN 60044-1 (8.2.1)

    Partial discharge measurement EN 60044-1 (8.2.2)

    Power-frequency withstand tests onsecondary winding

    EN 60044-1 (8.3/14.4.4)

    Power-frequency withstand testsbetween sections EN 60044-1 (8.3/14.4.4)

    Inter-turn overvoltage test EN 60044-1 (8.4/14.4.5)

    Determinations of errors of the testsample

    EO-20.2 (3.1.1)PTB-A 20.2 (4)PTB-Testing Instructions (3.4)

    Physikalisch -Techn ische Bundesanstalt, Bundesallee 100 D-38116 Braunschweig, vers. 2008-08-05. Allrights r eserved, No part may be reproduced without the prior wri tten permission o f PTB

  • 8/10/2019 Checklist for Type Approvals of Instrument Transformers

    3/3

    (10) Voltage transformer:

    Type tests:

    Short-circuit withstand capability test EN 60044-2 (8.2)

    Temperature rise test EN 60044-2 (8.1)

    Lightning impulse test EN 60044-2 (8.3.2)

    Switching impulse test EN 60044-2 (8.3.3/14.4.4)

    Wet test for outdoor type transformers EN 60044-2 (8.4/14.4.4))

    Determinations of errors of the testsample

    EO-20.2 (3.2.1)PTB-A 20.2 (4)PTB-Testing Instructions (3.5)

    Routine tests:

    Verifications of terminal markings EN 60044-2 (9.1)

    Power-frequency withstand tests onprimary winding

    EN 60044-2 (9.2)

    Partial discharge measurement EN 60044-2 (9.2.4)

    Power-frequency withstand tests onsecondary winding

    EN 60044-2 (9.3)

    Power-frequency withstand testsbetween sections EN 60044-2 (9.3)

    Determinations of errors of the testsample

    EO-20.2 (3.2.1)PTB-A 20.2 (4)PTB-Testing Instructions (3.5)

    Physikalisch -Techn ische Bundesanstalt, Bundesallee 100 D-38116 Braunschweig, vers. 2008-08-05. Allrights r eserved, No part may be reproduced without the prior wri tten permission o f PTB