30
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the de- sign, installation and operation of fire protection systems. 901.2 Fire protection systems. Fire protection systems shall be installed, repaired, operated and maintained in accordance with this code and the Phoenix Fire Code. Any fire protection system for which an exception or reduction to the provisions of this code has been granted shall be consid- ered to be a required system. Exception: Any fire protection system or portion thereof not required by this code shall be permitted to be installed for partial or complete protection provided that such system meets the requirements of this code. 901.3 Modifications. No person shall remove or modify any fire protection system installed or maintained under the provi- sions of this code or the Phoenix Fire Code without approval by both the building official and the fire marshal. 901.4 Threads. Threads provided for fire department connec- tions to sprinkler systems, standpipes, yard hydrants or any other fire hose connection shall be compatible with the connec- tions used by the local fire department. 901.5 Acceptance tests. Fire protection systems shall be tested in accordance with the requirements of this code and the Phoenix Fire Code. When required, the tests shall be con- ducted in the presence of the building official. Tests required by this code, the Phoenix Fire Code and the standards listed in this code shall be conducted at the expense of the owner or the owner’s representative. It shall be unlawful to occupy por- tions of a structure until the required fire protection systems within that portion of the structure have been tested and ap- proved. 901.6 Supervisory service. Where required, fire protection systems shall be monitored by an approved supervising station in accordance with NFPA 72. 901.6.1 Automatic sprinkler systems. Automatic sprin- kler systems shall be monitored by an approved supervising station. Exceptions: 1. A supervising station is not required for automatic sprinkler systems protecting one- and two-family dwellings. 2. Limited area systems serving fewer than 20 sprin- klers. 901.6.2 Fire alarm systems. Fire alarm systems required by the provisions of Section 907.2 of this code and Section 907.2 of the Phoenix Fire Code shall be monitored by an ap- proved supervising station in accordance with Section 907.14. Exceptions: 1. Single- and multiple-station smoke alarms re- quired by Section 907.2.10. 2. Smoke detectors in Group I-3 occupancies. 3. Supervisory service is not required for automatic sprinkler systems in one- and two-family dwellings. 901.6.3 Group H. Manual fire alarm, automatic fire-extin- guishing and emergency alarm systems in Group H occu- pancies shall be monitored by an approved supervising station. Exception: When approved by the building official, on-site monitoring at a constantly attended location shall be permitted provided that notifications to the fire de- partment will be equal to those provided by an approved supervising station. 901.7 Fire areas. Where buildings, or portions thereof, are di- vided into fire areas so as not to exceed the limits established for requiring a fire protection system in accordance with this chapter, such fire areas shall be separated by fire barriers hav- ing a fire-resistance rating of not less than that determined in accordance with Section 706.3.7. SECTION 902 DEFINITIONS 902.1 Definitions. The following words and terms shall, for the purposes of this chapter, and as used elsewhere in this code, have the meanings shown herein. [F] ALARM NOTIFICATION APPLIANCE. A fire alarm system component such as a bell, horn, speaker, light or text display that provides audible, tactile or visible outputs, or any combination thereof. [F] ALARM SIGNAL. A signal indicating an emergency re- quiring immediate action, such as a signal indicative of fire. [F] ALARM VERIFICATION FEATURE. A feature of au- tomatic fire detection and alarm systems to reduce unwanted alarms wherein smoke detectors report alarm conditions for a minimum period of time, or confirm alarm conditions within a given time period, after being automatically reset, in order to be accepted as a valid alarm-initiation signal. [F] ANNUNCIATOR. A unit containing one or more indica- tor lamps, alphanumeric displays or other equivalent means in which each indication provides status information about a cir- cuit, condition or location. [F] AUDIBLE ALARM NOTIFICATION APPLIANCE. A notification appliance that alerts by the sense of hearing. [F] AUTOMATIC. As applied to fire protection devices, is a device or system providing an emergency function without the necessity for human intervention and activated as a result of a predetermined temperature rise, rate of temperature rise or combustion products. 2003 INTERNATIONAL BUILDING CODE® 163R

CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

Embed Size (px)

Citation preview

Page 1: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

CHAPTER 9

FIRE PROTECTION SYSTEMS

SECTION 901GENERAL

9011 Scope The provisions of this chapter shall specify wherefire protection systems are required and shall apply to the de-sign installation and operation of fire protection systems

9012 Fire protection systems Fire protection systems shallbe installed repaired operated and maintained in accordancewith this code and the Phoenix Fire Code

Any fire protection system for which an exception or reductionto the provisions of this code has been granted shall be consid-ered to be a required system

Exception Any fire protection system or portion thereofnot required by this code shall be permitted to be installedfor partial or complete protection provided that such systemmeets the requirements of this code

9013 Modifications No person shall remove or modify anyfire protection system installed or maintained under the provi-sions of this code or the Phoenix Fire Code without approval byboth the building official and the fire marshal

9014 Threads Threads provided for fire department connec-tions to sprinkler systems standpipes yard hydrants or anyother fire hose connection shall be compatible with the connec-tions used by the local fire department

9015 Acceptance tests Fire protection systems shall betested in accordance with the requirements of this code andthe Phoenix Fire Code When required the tests shall be con-ducted in the presence of the building official Tests requiredby this code the Phoenix Fire Code and the standards listed inthis code shall be conducted at the expense of the owner or theownerrsquos representative It shall be unlawful to occupy por-tions of a structure until the required fire protection systemswithin that portion of the structure have been tested and ap-proved

9016 Supervisory service Where required fire protectionsystems shall be monitored by an approved supervising stationin accordance with NFPA 72

90161 Automatic sprinkler systems Automatic sprin-kler systems shall be monitored by an approved supervisingstation

Exceptions

1 A supervising station is not required for automaticsprinkler systems protecting one- and two-familydwellings

2 Limited area systems serving fewer than 20 sprin-klers

90162 Fire alarm systems Fire alarm systems requiredby the provisions of Section 9072 of this code and Section9072 of the Phoenix Fire Code shall be monitored by an ap-proved supervising station in accordance with Section90714

Exceptions

1 Single- and multiple-station smoke alarms re-quired by Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Supervisory service is not required for automaticsprinkler systems in one- and two-family dwellings

90163 Group H Manual fire alarm automatic fire-extin-guishing and emergency alarm systems in Group H occu-pancies shall be monitored by an approved supervisingstation

Exception When approved by the building officialon-site monitoring at a constantly attended location shallbe permitted provided that notifications to the fire de-partment will be equal to those provided by an approvedsupervising station

9017 Fire areas Where buildings or portions thereof are di-vided into fire areas so as not to exceed the limits establishedfor requiring a fire protection system in accordance with thischapter such fire areas shall be separated by fire barriers hav-ing a fire-resistance rating of not less than that determined inaccordance with Section 70637

SECTION 902DEFINITIONS

9021 Definitions The following words and terms shall forthe purposes of this chapter and as used elsewhere in this codehave the meanings shown herein

[F] ALARM NOTIFICATION APPLIANCE A fire alarmsystem component such as a bell horn speaker light or textdisplay that provides audible tactile or visible outputs or anycombination thereof

[F] ALARM SIGNAL A signal indicating an emergency re-quiring immediate action such as a signal indicative of fire

[F] ALARM VERIFICATION FEATURE A feature of au-tomatic fire detection and alarm systems to reduce unwantedalarms wherein smoke detectors report alarm conditions for aminimum period of time or confirm alarm conditions within agiven time period after being automatically reset in order to beaccepted as a valid alarm-initiation signal

[F] ANNUNCIATOR A unit containing one or more indica-tor lamps alphanumeric displays or other equivalent means inwhich each indication provides status information about a cir-cuit condition or location

[F] AUDIBLE ALARM NOTIFICATION APPLIANCE Anotification appliance that alerts by the sense of hearing

[F] AUTOMATIC As applied to fire protection devices is adevice or system providing an emergency function without thenecessity for human intervention and activated as a result of apredetermined temperature rise rate of temperature rise orcombustion products

2003 INTERNATIONAL BUILDING CODEreg 163R

09_Phoenix_IBC_2005_PG163pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20737 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] AUTOMATIC FIRE-EXTINGUISHING SYSTEMAn approved system of devices and equipment which automat-ically detects a fire and discharges an approved fire-extinguish-ing agent onto or in the area of a fire

[F] AUTOMATIC SPRINKLER SYSTEM A sprinkler sys-tem for fire protection purposes is an integrated system of un-derground and overhead piping designed in accordance withfire protection engineering standards The system includes asuitable water supply The portion of the system above theground is a network of specially sized or hydraulically de-signed piping installed in a structure or area generally over-head and to which automatic sprinklers are connected in asystematic pattern The system is usually activated by heatfrom a fire and discharges water over the fire area

[F] AVERAGE AMBIENT SOUND LEVEL The root meansquare A-weighted sound pressure level measured over a24-hour period

[F] CARBON DIOXIDE EXTINGUISHING SYSTEMSA system supplying carbon dioxide (CO2) from a pressurizedvessel through fixed pipes and nozzles The system includes amanual- or automatic-actuating mechanism

[F] CEILING LIMIT The maximum concentration of anair-borne contaminant to which one may be exposed as pub-lished in DOL 29 CFR Part 19101000

[F] CLEAN AGENT Electrically nonconducting volatile orgaseous fire extinguishant that does not leave a residue uponevaporation

[F] CONSTANTLY ATTENDED LOCATION A desig-nated location at a facility staffed by trained personnel on acontinuous basis where alarm or supervisory signals are moni-tored and facilities are provided for notification of the fire de-partment or other emergency services

[F] DELUGE SYSTEM A sprinkler system employing opensprinklers attached to a piping system connected to a water sup-ply through a valve that is opened by the operation of a detec-tion system installed in the same areas as the sprinklers Whenthis valve opens water flows into the piping system and dis-charges from all sprinklers attached thereto

[F] DETECTOR HEAT A fire detector that senses heat pro-duced by burning substances Heat is the energy produced bycombustion that causes substances to rise in temperature

[F] DRY-CHEMICAL EXTINGUISHING AGENT Apowder composed of small particles usually of sodium bicar-bonate potassium bicarbonate urea-potassium-based bicar-bonate potassium chloride or monoammonium phosphatewith added particulate material supplemented by special treat-ment to provide resistance to packing resistance to moistureabsorption (caking) and the proper flow capabilities

[F] EMERGENCY ALARM SYSTEM A system to provideindication and warning of emergency situations involving haz-ardous materials

[F] EMERGENCY VOICEALARM COMMUNICA-TIONS Dedicated manual or automatic facilities for originat-ing and distributing voice instructions as well as alert andevacuation signals pertaining to a fire emergency to the occu-pants of a building

[F] EXPLOSION An effect produced by the sudden violentexpansion of gases that is accompanied by a shock wave or dis-ruption of enclosing materials or structures or both

[F] FIRE ALARM BOX MANUAL See ldquoManual FireAlarm Boxrdquo

[F] FIRE ALARM CONTROL UNIT A system componentthat receives inputs from automatic and manual fire alarm de-vices and is capable of supplying power to detection devicesand transponder(s) or off-premises transmitter(s) The controlunit is capable of providing a transfer of power to the notifica-tion appliances and transfer of condition to relays or devices

[F] FIRE ALARM SIGNAL A signal initiated by a firealarm-initiating device such as a manual fire alarm box auto-matic fire detector water flow switch or other device whoseactivation is indicative of the presence of a fire or fire signature

[F] FIRE ALARM SYSTEM A system or portion of a com-bination system consisting of components and circuits ar-ranged to monitor and annunciate the status of fire alarm orsupervisory signal-initiating devices and to initiate the appro-priate response to those signals

[F] FIRE COMMAND CENTER The principal attended orunattended location where the status of detection alarm com-munications and control systems is displayed and from whichthe system(s) can be manually controlled

[F] FIRE DETECTOR AUTOMATIC A device designedto detect the presence of a fire signature and to initiate action

[F] FIRE PROTECTION SYSTEM Approved devicesequipment and systems or combinations of systems used to de-tect a fire activate an alarm extinguish or control a fire controlor manage smoke and products of a fire or any combinationthereof

[F] FIRE SAFETY FUNCTIONS Building and fire controlfunctions that are intended to increase the level of life safety foroccupants or to control the spread of harmful effects of fire

[F] FOAM-EXTINGUISHING SYSTEM A special systemdischarging a foam made from concentrates either mechani-cally or chemically over the area to be protected

[F] HALOGENATED EXTINGUISHING SYSTEM Afire-extinguishing system using one or more atoms of an ele-ment from the halogen chemical series fluorine chlorine bro-mine and iodine

[F] INITIATING DEVICE A system component that origi-nates transmission of a change-of-state condition such as in asmoke detector manual fire alarm box or supervisory switch

LISTED Equipment materials or services included in a listpublished by an organization acceptable to the building officialand concerned with evaluation of products or services thatmaintains periodic inspection of production of listed equip-ment or materials or periodic evaluation of services and whoselisting states either that the equipment material or servicemeets identified standards or has been tested and found suitablefor a specified purpose

[F] MANUAL FIRE ALARM BOX A manually operateddevice used to initiate an alarm signal

164 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG164pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20749 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] MULTIPLE-STATION ALARM DEVICE Two ormore single-station alarm devices that are capable of intercon-nection such that actuation of one causes all integral or separateaudible alarms to operate It also can consist of one single-sta-tion alarm device having connections to other detectors or to amanual fire alarm box

[F] MULTIPLE-STATION SMOKE ALARM Two or moresingle-station alarm devices that are capable of interconnectionsuch that actuation of one causes all integral or separate audiblealarms to operate

[F] NUISANCE ALARM An alarm caused by mechanicalfailure malfunction improper installation or lack of propermaintenance or an alarm activated by a cause that cannot bedetermined

[F] RECORD DRAWINGS Drawings (ldquoas builtsrdquo) that doc-ument the location of all devices appliances wiring sequenceswiring methods and connections of the components of a firealarm system as installed

[F] SINGLE-STATION SMOKE ALARM An assembly in-corporating the detector the control equipment and thealarm-sounding device in one unit operated from a power sup-ply either in the unit or obtained at the point of installation

[F] SMOKE ALARM A single- or multiple-station alarm re-sponsive to smoke and not connected to a system

[F] SMOKE DETECTOR A listed device that senses visibleor invisible particles of combustion

SMOKEPROOF ENCLOSURE An exit stairway designedand constructed so that the movement of the products of com-bustion produced by a fire occurring in any part of the buildinginto the enclosure is limited

[F] STANDPIPE SYSTEM CLASSES OF Standpipeclasses are as follows

Class I system A system providing 25-inch (64 mm) hoseconnections to supply water for use by fire departments andthose trained in handling heavy fire streams

Class II system A system providing 15-inch (38 mm) hosestations to supply water for use primarily by the building oc-cupants or by the fire department during initial response

Class III system A system providing 15-inch (38 mm)hose stations to supply water for use by building occupantsand 25-inch (64 mm) hose connections to supply a largervolume of water for use by fire departments and thosetrained in handling heavy fire streams

[F] STANDPIPE TYPES OF Standpipe types are as follows

Automatic dry A dry standpipe system normally filledwith pressurized air that is arranged through the use of a de-vice such as dry pipe valve to admit water into the systempiping automatically upon the opening of a hose valve Thewater supply for an automatic dry standpipe system shall becapable of supplying the system demand

Automatic wet A wet standpipe system that has a watersupply that is capable of supplying the system demand auto-matically

Manual dry A dry standpipe system that does not have apermanent water supply attached to the system Manual dry

standpipe systems require water from a fire departmentpumper to be pumped into the system through the fire de-partment connection in order to meet the system demand

Manual wet A wet standpipe system connected to a watersupply for the purpose of maintaining water within the sys-tem but does not have a water supply capable of deliveringthe system demand attached to the system Manual-wetstandpipe systems require water from a fire departmentpumper (or the like) to be pumped into the system in order tomeet the system demand

Semiautomatic dry A dry standpipe system that is ar-ranged through the use of a device such as a deluge valve toadmit water into the system piping upon activation of a re-mote control device located at a hose connection A remotecontrol activation device shall be provided at each hose con-nection The water supply for a semiautomatic drystandpipe system shall be capable of supplying the systemdemand

[F] SUPERVISING STATION A facility that receives sig-nals and at which personnel are in attendance at all times to re-spond to these signals

[F] SUPERVISORY SERVICE The service required tomonitor performance of guard tours and the operative condi-tion of fixed suppression systems or other systems for the pro-tection of life and property

[F] SUPERVISORY SIGNAL A signal indicating the needof action in connection with the supervision of guard tours thefire suppression systems or equipment or the maintenance fea-tures of related systems

[F] SUPERVISORY SIGNAL-INITIATING DEVICE Aninitiation device such as a valve supervisory switch wa-ter-level indicator or low-air pressure switch on a dry-pipesprinkler system whose change of state signals an off-normalcondition and its restoration to normal of a fire protection orlife safety system or a need for action in connection with guardtours fire suppression systems or equipment or maintenancefeatures of related systems

[F] TIRES BULK STORAGE OF Storage of tires where thearea available for storage exceeds 20000 cubic feet (566 m3)

[F] TROUBLE SIGNAL A signal initiated by the fire alarmsystem or device indicative of a fault in a monitored circuit orcomponent

[F] VISIBLE ALARM NOTIFICATION APPLIANCE Anotification appliance that alerts by the sense of sight

[F] WET-CHEMICAL EXTINGUISHING SYSTEM Asolution of water and potassium-carbonate-based chemicalpotassium-acetate-based chemical or a combination thereofforming an extinguishing agent

[F] WIRELESS PROTECTION SYSTEM A system or apart of a system that can transmit and receive signals withoutthe aid of wire

[F] ZONE A defined area within the protected premises Azone can define an area from which a signal can be received anarea to which a signal can be sent or an area in which a form ofcontrol can be executed

2003 INTERNATIONAL BUILDING CODEreg 165

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG165pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20802 PM

Color profile Generic CMYK printer profileComposite Default screen

SECTION 903AUTOMATIC SPRINKLER SYSTEMS

[F] 9031 General Automatic sprinkler systems shall complywith this section

[F] 90311 Alternative protection Alternative automaticfire-extinguishing systems complying with Section 904shall be permitted in lieu of automatic sprinkler protectionwhere recognized by the applicable standard and approvedby the building official

[F] 9032 Where required Approved automatic sprinkler sys-tems in new buildings and structures shall be provided in the lo-cations described in this section and in accordance with theBret Tarver Sprinkler Ordinance (Effective June 17 2002 Re-vised January 12 2005)

An automatic sprinkler system shall be installed throughoutall levels of all new Group A B E F H I M R-1 R-2 R-4 andS occupancies of more than zero square feet and throughout allR-3 occupancies of more than 5000 square feet (465 m2) Thecalculated area shall include all livable space and the area ofany attached garage

Such systems shall be in accordance with NFPA 13 forGroup A B E F H I M and S occupancies NFPA 13R forresidential occupancies up to and including four stories inheight and NFPA 13D for single-family dwellings

Exceptions

1 Detached gazebos and ramadas for residential andpublic use

2 Independent buildings such as restrooms or snackshops 400 square feet (37 m2) or less that are associ-ated with golf courses parks and similar uses

3 Detached noncombustible carports or shade cano-pies

4 Guardhouses that are less than 300 square feet (28 m2)in size used to control access to or within residentialandor commercial developments

5 Detached equipment or storage buildings for com-mercial use not exceeding 300 square feet (28 m2)

6 Detached noncombustible canopies used exclusivelyfor automotive motor fuel-dispensing stations forprivate passenger vehicles not exceeding 5000square feet (465 m2)

7 Manufactured (mobile) home built on a permanentchassis designed and built as a dwelling unit and rec-reational vehicles that were not site built and are por-table in nature

[F] 90321 Existing buildings Existing buildings are re-quired to comply with the provisions of this section whenany of the following apply

1 Building additions that equal 50 percent or more ofthe existing building floor area or exceed 10000square feet (929 m2) whichever is less

2 A building that is less than 2500 square feet (232 m2)and undergoes a change of occupancy to a lower haz-ard level or stays within the current hazard level as de-fined by the Phoenix Fire Code shall not be requiredto provide a fire sprinkler system on a retrofit basis

3 Two or more building permits related to increasedsquare footage that are issued over any three consecu-tive years

4 One or more additions within any three-year periodthat are made to a Group R-3 occupancy and complywith all of the following

41 The aggregate of the additions exceeds 50percent of the original (as of the effective dateof the Bret Tarver Sprinkler Ordinance onJune 17 2002 or at original constructionwhichever is later) square footage of thehouse

42 The new total area of the building is greaterthan 5000 square feet (465 m2)

5 Building remodels are made that require structuralchanges affecting the primary structural system of theexisting building

6 A building that undergoes a change of occupancy to ahigher hazard level or changes occupancy withinHazard Level 1 as defined by the Phoenix Fire Code

[F] 90322 Group H-5 An automatic sprinkler systemshall be installed throughout buildings containing GroupH-5 occupancies The design of the sprinkler system shallnot be less than that required by this code for the occu-pancy hazard classifications in accordance with Table90322

Where the design area of the sprinkler system consists ofa corridor protected by one row of sprinklers the maximumnumber of sprinklers required to be calculated is 13

[F] TABLE 90322GROUP H-5 SPRINKLER DESIGN CRITERIA

LOCATIONOCCUPANCY HAZARD

CLASSIFICATION

Fabrication areas Ordinary Hazard Group 2

Service corridors Ordinary Hazard Group 2

Storage rooms without dispensing Ordinary Hazard Group 2

Storage rooms with dispensing Extra Hazard Group 2

Corridors Ordinary Hazard Group 2

166R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

gt

09_Phoenix_IBC_2005_PG166pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20814 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90323 Rubbish and linen chutes An automatic sprin-kler system shall be installed at the top of rubbish and linenchutes and in their terminal rooms Chutes extendingthrough three or more floors shall have additional sprinklerheads installed within such chutes at alternate floors Chutesprinklers shall be accessible for servicing

[F] 90324 During construction Automatic sprinkler sys-tems required during construction alteration and demoli-tion operations shall be provided in accordance with thePhoenix Fire Code

[F] 90325 Ducts conveying hazardous exhausts Whererequired by the International Mechanical Code automaticsprinklers shall be provided in ducts conveying hazardousexhaust or flammable or combustible materials

Exception Ducts in which the largest cross-sectionaldiameter of the duct is less than 10 inches (254 mm)

[F] 90326 Commercial cooking operations An auto-matic sprinkler system shall be installed in commercialkitchen exhaust hood and duct system where an automaticsprinkler system is used to comply with Section 904

[F] 90327 Other required suppression systems In addi-tion to the requirements of Section 9032 the provisions in-dicated in Table 90327 also require the installation of asuppression system for certain buildings and areas

[F] TABLE 90327ADDITIONAL REQUIRED SUPPRESSION SYSTEMS

SECTION SUBJECT

4028 Covered malls

4032 4033 High-rise buildings

4043 Atriums

4053 Underground structures

4075 Group I-2

4106 Stages

4114 Special amusement buildings

41225 41226 Aircraft hangars

415724 Group H-2

4164 Flammable finishes

4174 Drying rooms

507 Unlimited area buildings

Sprinkler requirements as set forth in thePhoenix Fire Code

[F] 9033 Installation requirements Automatic sprinklersystems shall be designed and installed in accordance withSections 90331 through 90337

[F] 90331 Standards Sprinkler systems shall be designedand installed in accordance with Section 903311903312 or 903313

[F] 903311 NFPA 13 sprinkler systems Where theprovisions of this code require that a building or portionthereof be equipped throughout with an automatic sprin-kler system in accordance with Section 903311 sprin-klers shall be installed throughout in accordance withNFPA 13 except as provided in Section 9033111

[F] 9033111 Exempt locations Automatic sprin-klers shall not be required in the following rooms orareas where such rooms or areas are protected with anapproved automatic fire detection system in accor-dance with Section 9072 that will respond to visibleor invisible particles of combustion Sprinklers shallnot be omitted from any room merely because it isdamp of fire-resistance-rated construction or con-tains electrical equipment

1 Any room where the application of water orflame and water constitutes a serious life or firehazard

2 Any room or space where sprinklers are consid-ered undesirable because of the nature of thecontents when approved by the building offi-cial

3 Generator and transformer rooms separatedfrom the remainder of the building by wallsand floorceiling or roofceiling assemblieshaving a fire-resistance rating of not less than2 hours

4 In rooms or areas that are of noncombustibleconstruction with wholly noncombustible con-tents

[F] 903312 NFPA 13R sprinkler systems Where al-lowed in buildings of Group R up to and including fourstories in height automatic sprinkler systems shall be in-stalled throughout in accordance with NFPA 13R

2003 INTERNATIONAL BUILDING CODEreg 167R

FIRE PROTECTION SYSTEMS

gt

gt

gt

09_Phoenix_IBC_2005_PG167pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20824 PM

Color profile Generic CMYK printer profileComposite Default screen

This page left intentionally blank

168R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG168pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20836 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 9033121 Balconies Sprinkler protection shallbe provided for exterior balconies and ground-floorpatios of dwelling units where the building is of TypeV construction Sidewall sprinklers that are used toprotect such areas shall be permitted to be locatedsuch that their deflectors are within 1 inch (25 mm) to6 inches (152 mm) below the structural members anda maximum distance of 14 inches (356 mm) below thedeck of the exterior balconies that are constructed ofopen wood joist construction

[F] 903313 NFPA 13D sprinkler systems Where al-lowed automatic sprinkler systems in one- and two-fam-ily dwellings shall be installed throughout in accordancewith NFPA 13D

[F] 90332 Quick-response and residential sprinklersWhere automatic sprinkler systems are required by thiscode quick-response or residential automatic sprinklersshall be installed in the following areas in accordance withSection 90331 and their listings

1 Throughout all spaces within a smoke compartmentcontaining patient sleeping units in Group I-2 in ac-cordance with this code

2 Dwelling units and sleeping units in Group R and I-1occupancies

3 Light-hazard occupancies as defined in NFPA 13

[F] 90333 Obstructed locations Automatic sprinklersshall be installed with due regard to obstructions that willdelay activation or obstruct the water distribution patternAutomatic sprinklers shall be installed in or under coveredkiosks displays booths concession stands or equipmentthat exceeds 4 feet (1219 mm) in width Not less than a3-foot (914 mm) clearance shall be maintained between au-tomatic sprinklers and the top of piles of combustible fibers

Exception Kitchen equipment under exhaust hoodsprotected with a fire-extinguishing system in accordancewith Section 904

[F] 90334 Actuation Automatic sprinkler systems shallbe automatically actuated unless specifically provided for inthis code

[F] 90335 Water supplies Water supplies for automaticsprinkler systems shall comply with this section and thestandards referenced in Section 90331 The potable watersupply shall be protected against backflow in accordancewith the requirements of this section and the Arizona StatePlumbing Code

[F] 903351 Domestic services Where the domesticservice provides the water supply for the automaticsprinkler system the supply shall be in accordance withthis section

[F] 9033511 Limited area sprinkler systemsLimited area sprinkler systems serving fewer than 20sprinklers on any single connection are permitted tobe connected to the domestic service where a wet au-tomatic standpipe is not available Limited area sprin-kler systems connected to domestic water suppliesshall comply with each of the following requirements

1 Valves shall not be installed between the do-mestic water riser control valve and the sprin-klers

Exception An approved indicating controlvalve supervised in the open position in ac-cordance with Section 9034

2 The domestic service shall be capable of sup-plying the simultaneous domestic demand andthe sprinkler demand required to be hydrauli-cally calculated by NFPA 13 NFPA 13R orNFPA 13D

[F] 9033512 Residential combination services Asingle combination water supply shall be permittedprovided that the domestic demand is added to thesprinkler demand as required by NFPA 13R

[F] 903352 Secondary water supply A secondaryon-site water supply equal to the hydraulically calculatedsprinkler demand including the hose stream require-ment shall be provided for high-rise buildings in Seis-mic Design Category C D E or F as determined by thiscode The secondary water supply shall have a durationnot less than 30 minutes as determined by the occupancyhazard classification in accordance with NFPA 13

Exception Existing buildings

[F] 90336 Hose threads Fire hose threads used in connec-tion with automatic sprinkler systems shall be approved andcompatible with fire department hose threads

[F] 90337 Fire department connections The location offire department connections shall be approved by the build-ing official

[F] 903371 Locking fire department connection(FDC) caps The fire code official is authorized to re-quire locking FDC caps on fire department connectionsfor water-based fire protection systems where the re-sponding fire department carries appropriate keywrenches for removal

[F] 9034 Sprinkler system monitoring and alarms Allvalves controlling the water supply for automatic sprinkler sys-tems pumps tanks water levels and temperatures critical airpressures and water-flow switches on all sprinkler systemsshall be electrically supervised

Exceptions

1 Automatic sprinkler systems protecting one- andtwo-family dwellings

2 Limited area systems serving fewer than 20 sprin-klers

3 Automatic sprinkler systems installed in accordancewith NFPA 13R where a common supply main is usedto supply both domestic water and the automaticsprinkler systems and a separate shutoff valve for theautomatic sprinkler system is not provided

4 Jockey pump control valves that are sealed or lockedin the open position

2003 INTERNATIONAL BUILDING CODEreg 169R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG169pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20847 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Control valves to commercial kitchen hoods paintspray booths or dip tanks that are sealed or locked inthe open position

6 Valves controlling the fuel supply to fire pump en-gines that are sealed or locked in the open position

7 Trim valves to pressure switches in dry preaction anddeluge sprinkler systems that are sealed or locked inthe open position

[F] 90341 Signals Alarm supervisory and trouble signalsshall be distinctly different and automatically transmitted toan approved central station remote supervising station orproprietary supervising station as defined in NFPA 72 orwhen approved by the building official shall sound an audi-ble signal at a constantly attended location

Exceptions

1 Underground key or hub valves in roadway boxesprovided by the municipality or public utility arenot required to be monitored

2 Backflow prevention device test valves located inlimited area sprinkler system supply piping shallbe locked in the open position In occupancies re-quired to be equipped with a fire alarm system thebackflow preventer valves shall be electrically su-pervised by a tamper switch installed in accor-dance with NFPA 72 and separately annunciated

[F] 90342 Alarms Approved audible devices shall beconnected to every automatic sprinkler system Such sprin-kler water-flow alarm devices shall be activated by waterflow equivalent to the flow of a single sprinkler of the small-est orifice size installed in the system Alarm devices shallbe provided on the exterior of the building in an approvedlocation Where a fire alarm system is installed actuation ofthe automatic sprinkler system shall actuate the building firealarm system

[F] 90343 Floor control valves Approved supervised in-dicating control valves shall be provided at the point of con-nection to the riser on each floor in high-rise buildings

[F] 9035 Testing and maintenance Sprinkler systems shallbe tested and maintained in accordance with the Phoenix FireCode

SECTION 904ALTERNATIVE AUTOMATIC

FIRE-EXTINGUISHING SYSTEMS

[F] 9041 General Automatic fire-extinguishing systemsother than automatic sprinkler systems shall be designed in-stalled inspected tested and maintained in accordance withthe provisions of this section and the applicable referencedstandards

[F] 9042 Where required Automatic fire-extinguishing sys-tems installed as an alternative to the required automatic sprin-kler systems of Section 903 shall be approved by the buildingofficial Automatic fire-extinguishing systems shall not beconsidered alternatives for the purposes of exceptions or reduc-tions permitted by other requirements of this code

[F] 90421 Hood system suppression Each required com-mercial kitchen exhaust hood and duct system required bythe Phoenix Fire Code or the International MechanicalCode to have a Type I hood shall be protected with an ap-proved automatic fire-extinguishing system installed in ac-cordance with this code

[F] 9043 Installation Automatic fire-extinguishing systemsshall be installed in accordance with this section

[F] 90431 Electrical wiring Electrical wiring shall be inaccordance with the National Electrical Code

[F] 90432 Actuation Automatic fire-extinguishing sys-tems shall be automatically actuated and provided with amanual means of actuation in accordance with Section904111

[F] 90433 System interlocking Automatic equipment in-terlocks with fuel shutoffs ventilation controls doorclosers window shutters conveyor openings smoke andheat vents and other features necessary for proper operationof the fire-extinguishing system shall be provided as re-quired by the design and installation standard utilized forthe hazard

[F] 90434 Alarms and warning signs Where alarms arerequired to indicate the operation of automatic fire-extin-guishing systems distinctive audible and visible alarms andwarning signs shall be provided to warn of pending agentdischarge Where exposure to automatic-extinguishingagents poses a hazard to persons and a delay is required toensure the evacuation of occupants before agent dischargea separate warning signal shall be provided to alert occu-pants once agent discharge has begun Audible signals shallbe in accordance with Section 90792

[F] 90435 Monitoring Where a building fire alarm sys-tem is installed automatic fire-extinguishing systems shallbe monitored by the building fire alarm system in accor-dance with NFPA 72

[F] 9044 Inspection and testing Automatic fire-extinguish-ing systems shall be inspected and tested in accordance withthe provisions of this section prior to acceptance

[F] 90441 Inspection Prior to conducting final accep-tance tests the following items shall be inspected

1 Hazard specification for consistency with design haz-ard

2 Type location and spacing of automatic- and man-ual-initiating devices

3 Size placement and position of nozzles or dischargeorifices

4 Location and identification of audible and visiblealarm devices

5 Identification of devices with proper designations

6 Operating instructions

[F] 90442 Alarm testing Notification appliances con-nections to fire alarm systems and connections to approvedsupervising stations shall be tested in accordance with thissection and Section 907 to verify proper operation

170R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG170pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20901 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 904421 Audible and visible signals The audibil-ity and visibility of notification appliances signalingagent discharge or system operation where requiredshall be verified

[F] 90443 Monitor testing Connections to protected pre-mises and supervising station fire alarm systems shall betested to verify proper identification and retransmission ofalarms from automatic fire-extinguishing systems

[F] 9045 Wet-chemical systems Wet-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17A and their listing

[F] 9046 Dry-chemical systems Dry-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17 and their listing

[F] 9047 Foam systems Foam-extinguishing systems shall beinstalled maintained periodically inspected and tested in ac-cordance with NFPA 11 and NFPA 16 and their listing

[F] 9048 Carbon dioxide systems Carbon dioxide extin-guishing systems shall be installed maintained periodicallyinspected and tested in accordance with NFPA 12 and their list-ing

[F] 9049 Halon systems Halogenated extinguishing systemsshall be installed maintained periodically inspected and testedin accordance with NFPA 12A and their listing

[F] 90410 Clean-agent systems Clean-agent fire-extinguish-ing systems shall be installed maintained periodically in-spected and tested in accordance with NFPA 2001 and theirlisting

[F] 90411 Commercial cooking systems The automaticfire-extinguishing system for commercial cooking systemsshall be of a type recognized for protection of commercialcooking equipment and exhaust systems of the type and ar-rangement protected Preengineered automatic dry- andwet-chemical extinguishing systems shall be tested in accor-dance with UL 300 and listed and labeled for the intended ap-plication Other types of automatic fire-extinguishing systemsshall be listed and labeled for specific use as protection forcommercial cooking operations The system shall be installedin accordance with this code its listing and the manufacturerrsquosinstallation instructions Automatic fire-extinguishing systemsof the following types shall be installed in accordance with thereferenced standard indicated as shown

1 Carbon dioxide extinguishing systems NFPA 12

2 Automatic sprinkler systems NFPA 13

3 Foam-water sprinkler system or foam-water spray sys-tems NFPA 16

4 Dry-chemical extinguishing systems NFPA 17

5 Wet-chemical extinguishing systems NFPA 17A

Exception Factory-built commercial cooking recirculatingsystems that are tested in accordance with UL 197 andlisted labeled and installed in accordance with Section3041 of the International Mechanical Code

[F] 904111 Manual system operation A manual actua-tion device shall be located at or near a means of egress fromthe cooking area a minimum of 10 feet (3048 mm) and a

maximum of 20 feet (6096 mm) from the kitchen exhaustsystem The manual actuation device shall be located a min-imum of 4 feet (1219 mm) and a maximum of 5 feet (1524mm) above the floor The manual actuation shall require amaximum force of 40 pounds (178 N) and a maximummovement of 14 inches (356 mm) to actuate the fire sup-pression system

Exception Automatic sprinkler systems shall not be re-quired to be equipped with manual actuation means

[F] 904112 System interconnection The actuation of thefire suppression system shall automatically shut down thefuel or electrical power supply to the cooking equipmentThe fuel and electrical supply reset shall be manual

[F] 904113 Carbon dioxide systems When carbon diox-ide systems are used there shall be a nozzle at the top of theventilating duct Additional nozzles that are symmetricallyarranged to give uniform distribution shall be installedwithin vertical ducts exceeding 20 feet (6096 mm) and hori-zontal ducts exceeding 50 feet (15 240 mm) Dampers shallbe installed at either the top or the bottom of the duct andshall be arranged to operate automatically upon activationof the fire-extinguishing system Where the damper is in-stalled at the top of the duct the top nozzle shall be immedi-ately below the damper Automatic carbon dioxidefire-extinguishing systems shall be sufficiently sized to pro-tect against all hazards venting through a common duct si-multaneously

[F] 9041131 Ventilation system Commercial-typecooking equipment protected by an automatic carbon di-oxide-extinguishing system shall be arranged to shut offthe ventilation system upon activation

[F] 904114 Special provisions for automatic sprinklersystems Automatic sprinkler systems protecting commer-cial-type cooking equipment shall be supplied from a sepa-rate readily accessible indicating-type control valve that isidentified

[F] 9041141 Listed sprinklers Sprinklers used forthe protection of fryers shall be listed for that applicationand installed in accordance with their listing

SECTION 905STANDPIPE SYSTEMS

[F] 9051 General Standpipe systems shall be provided in newbuildings and structures in accordance with this section Firehose threads used in connection with standpipe systems shallbe approved and shall be compatible with fire department hosethreads The location of fire department hose connections shallbe approved In buildings used for high-piled combustible stor-age fire protection shall be in accordance with the PhoenixFire Code

[F] 9052 Installation standards Standpipe systems shall beinstalled in accordance with this section and NFPA 14

[F] 9053 Required installations Standpipe systems shall beinstalled where required by Sections 90531 through 90536and in the locations indicated in Sections 9054 9055 and

2003 INTERNATIONAL BUILDING CODEreg 171R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG171pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20954 PM

Color profile Generic CMYK printer profileComposite Default screen

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 2: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

[F] AUTOMATIC FIRE-EXTINGUISHING SYSTEMAn approved system of devices and equipment which automat-ically detects a fire and discharges an approved fire-extinguish-ing agent onto or in the area of a fire

[F] AUTOMATIC SPRINKLER SYSTEM A sprinkler sys-tem for fire protection purposes is an integrated system of un-derground and overhead piping designed in accordance withfire protection engineering standards The system includes asuitable water supply The portion of the system above theground is a network of specially sized or hydraulically de-signed piping installed in a structure or area generally over-head and to which automatic sprinklers are connected in asystematic pattern The system is usually activated by heatfrom a fire and discharges water over the fire area

[F] AVERAGE AMBIENT SOUND LEVEL The root meansquare A-weighted sound pressure level measured over a24-hour period

[F] CARBON DIOXIDE EXTINGUISHING SYSTEMSA system supplying carbon dioxide (CO2) from a pressurizedvessel through fixed pipes and nozzles The system includes amanual- or automatic-actuating mechanism

[F] CEILING LIMIT The maximum concentration of anair-borne contaminant to which one may be exposed as pub-lished in DOL 29 CFR Part 19101000

[F] CLEAN AGENT Electrically nonconducting volatile orgaseous fire extinguishant that does not leave a residue uponevaporation

[F] CONSTANTLY ATTENDED LOCATION A desig-nated location at a facility staffed by trained personnel on acontinuous basis where alarm or supervisory signals are moni-tored and facilities are provided for notification of the fire de-partment or other emergency services

[F] DELUGE SYSTEM A sprinkler system employing opensprinklers attached to a piping system connected to a water sup-ply through a valve that is opened by the operation of a detec-tion system installed in the same areas as the sprinklers Whenthis valve opens water flows into the piping system and dis-charges from all sprinklers attached thereto

[F] DETECTOR HEAT A fire detector that senses heat pro-duced by burning substances Heat is the energy produced bycombustion that causes substances to rise in temperature

[F] DRY-CHEMICAL EXTINGUISHING AGENT Apowder composed of small particles usually of sodium bicar-bonate potassium bicarbonate urea-potassium-based bicar-bonate potassium chloride or monoammonium phosphatewith added particulate material supplemented by special treat-ment to provide resistance to packing resistance to moistureabsorption (caking) and the proper flow capabilities

[F] EMERGENCY ALARM SYSTEM A system to provideindication and warning of emergency situations involving haz-ardous materials

[F] EMERGENCY VOICEALARM COMMUNICA-TIONS Dedicated manual or automatic facilities for originat-ing and distributing voice instructions as well as alert andevacuation signals pertaining to a fire emergency to the occu-pants of a building

[F] EXPLOSION An effect produced by the sudden violentexpansion of gases that is accompanied by a shock wave or dis-ruption of enclosing materials or structures or both

[F] FIRE ALARM BOX MANUAL See ldquoManual FireAlarm Boxrdquo

[F] FIRE ALARM CONTROL UNIT A system componentthat receives inputs from automatic and manual fire alarm de-vices and is capable of supplying power to detection devicesand transponder(s) or off-premises transmitter(s) The controlunit is capable of providing a transfer of power to the notifica-tion appliances and transfer of condition to relays or devices

[F] FIRE ALARM SIGNAL A signal initiated by a firealarm-initiating device such as a manual fire alarm box auto-matic fire detector water flow switch or other device whoseactivation is indicative of the presence of a fire or fire signature

[F] FIRE ALARM SYSTEM A system or portion of a com-bination system consisting of components and circuits ar-ranged to monitor and annunciate the status of fire alarm orsupervisory signal-initiating devices and to initiate the appro-priate response to those signals

[F] FIRE COMMAND CENTER The principal attended orunattended location where the status of detection alarm com-munications and control systems is displayed and from whichthe system(s) can be manually controlled

[F] FIRE DETECTOR AUTOMATIC A device designedto detect the presence of a fire signature and to initiate action

[F] FIRE PROTECTION SYSTEM Approved devicesequipment and systems or combinations of systems used to de-tect a fire activate an alarm extinguish or control a fire controlor manage smoke and products of a fire or any combinationthereof

[F] FIRE SAFETY FUNCTIONS Building and fire controlfunctions that are intended to increase the level of life safety foroccupants or to control the spread of harmful effects of fire

[F] FOAM-EXTINGUISHING SYSTEM A special systemdischarging a foam made from concentrates either mechani-cally or chemically over the area to be protected

[F] HALOGENATED EXTINGUISHING SYSTEM Afire-extinguishing system using one or more atoms of an ele-ment from the halogen chemical series fluorine chlorine bro-mine and iodine

[F] INITIATING DEVICE A system component that origi-nates transmission of a change-of-state condition such as in asmoke detector manual fire alarm box or supervisory switch

LISTED Equipment materials or services included in a listpublished by an organization acceptable to the building officialand concerned with evaluation of products or services thatmaintains periodic inspection of production of listed equip-ment or materials or periodic evaluation of services and whoselisting states either that the equipment material or servicemeets identified standards or has been tested and found suitablefor a specified purpose

[F] MANUAL FIRE ALARM BOX A manually operateddevice used to initiate an alarm signal

164 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG164pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20749 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] MULTIPLE-STATION ALARM DEVICE Two ormore single-station alarm devices that are capable of intercon-nection such that actuation of one causes all integral or separateaudible alarms to operate It also can consist of one single-sta-tion alarm device having connections to other detectors or to amanual fire alarm box

[F] MULTIPLE-STATION SMOKE ALARM Two or moresingle-station alarm devices that are capable of interconnectionsuch that actuation of one causes all integral or separate audiblealarms to operate

[F] NUISANCE ALARM An alarm caused by mechanicalfailure malfunction improper installation or lack of propermaintenance or an alarm activated by a cause that cannot bedetermined

[F] RECORD DRAWINGS Drawings (ldquoas builtsrdquo) that doc-ument the location of all devices appliances wiring sequenceswiring methods and connections of the components of a firealarm system as installed

[F] SINGLE-STATION SMOKE ALARM An assembly in-corporating the detector the control equipment and thealarm-sounding device in one unit operated from a power sup-ply either in the unit or obtained at the point of installation

[F] SMOKE ALARM A single- or multiple-station alarm re-sponsive to smoke and not connected to a system

[F] SMOKE DETECTOR A listed device that senses visibleor invisible particles of combustion

SMOKEPROOF ENCLOSURE An exit stairway designedand constructed so that the movement of the products of com-bustion produced by a fire occurring in any part of the buildinginto the enclosure is limited

[F] STANDPIPE SYSTEM CLASSES OF Standpipeclasses are as follows

Class I system A system providing 25-inch (64 mm) hoseconnections to supply water for use by fire departments andthose trained in handling heavy fire streams

Class II system A system providing 15-inch (38 mm) hosestations to supply water for use primarily by the building oc-cupants or by the fire department during initial response

Class III system A system providing 15-inch (38 mm)hose stations to supply water for use by building occupantsand 25-inch (64 mm) hose connections to supply a largervolume of water for use by fire departments and thosetrained in handling heavy fire streams

[F] STANDPIPE TYPES OF Standpipe types are as follows

Automatic dry A dry standpipe system normally filledwith pressurized air that is arranged through the use of a de-vice such as dry pipe valve to admit water into the systempiping automatically upon the opening of a hose valve Thewater supply for an automatic dry standpipe system shall becapable of supplying the system demand

Automatic wet A wet standpipe system that has a watersupply that is capable of supplying the system demand auto-matically

Manual dry A dry standpipe system that does not have apermanent water supply attached to the system Manual dry

standpipe systems require water from a fire departmentpumper to be pumped into the system through the fire de-partment connection in order to meet the system demand

Manual wet A wet standpipe system connected to a watersupply for the purpose of maintaining water within the sys-tem but does not have a water supply capable of deliveringthe system demand attached to the system Manual-wetstandpipe systems require water from a fire departmentpumper (or the like) to be pumped into the system in order tomeet the system demand

Semiautomatic dry A dry standpipe system that is ar-ranged through the use of a device such as a deluge valve toadmit water into the system piping upon activation of a re-mote control device located at a hose connection A remotecontrol activation device shall be provided at each hose con-nection The water supply for a semiautomatic drystandpipe system shall be capable of supplying the systemdemand

[F] SUPERVISING STATION A facility that receives sig-nals and at which personnel are in attendance at all times to re-spond to these signals

[F] SUPERVISORY SERVICE The service required tomonitor performance of guard tours and the operative condi-tion of fixed suppression systems or other systems for the pro-tection of life and property

[F] SUPERVISORY SIGNAL A signal indicating the needof action in connection with the supervision of guard tours thefire suppression systems or equipment or the maintenance fea-tures of related systems

[F] SUPERVISORY SIGNAL-INITIATING DEVICE Aninitiation device such as a valve supervisory switch wa-ter-level indicator or low-air pressure switch on a dry-pipesprinkler system whose change of state signals an off-normalcondition and its restoration to normal of a fire protection orlife safety system or a need for action in connection with guardtours fire suppression systems or equipment or maintenancefeatures of related systems

[F] TIRES BULK STORAGE OF Storage of tires where thearea available for storage exceeds 20000 cubic feet (566 m3)

[F] TROUBLE SIGNAL A signal initiated by the fire alarmsystem or device indicative of a fault in a monitored circuit orcomponent

[F] VISIBLE ALARM NOTIFICATION APPLIANCE Anotification appliance that alerts by the sense of sight

[F] WET-CHEMICAL EXTINGUISHING SYSTEM Asolution of water and potassium-carbonate-based chemicalpotassium-acetate-based chemical or a combination thereofforming an extinguishing agent

[F] WIRELESS PROTECTION SYSTEM A system or apart of a system that can transmit and receive signals withoutthe aid of wire

[F] ZONE A defined area within the protected premises Azone can define an area from which a signal can be received anarea to which a signal can be sent or an area in which a form ofcontrol can be executed

2003 INTERNATIONAL BUILDING CODEreg 165

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG165pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20802 PM

Color profile Generic CMYK printer profileComposite Default screen

SECTION 903AUTOMATIC SPRINKLER SYSTEMS

[F] 9031 General Automatic sprinkler systems shall complywith this section

[F] 90311 Alternative protection Alternative automaticfire-extinguishing systems complying with Section 904shall be permitted in lieu of automatic sprinkler protectionwhere recognized by the applicable standard and approvedby the building official

[F] 9032 Where required Approved automatic sprinkler sys-tems in new buildings and structures shall be provided in the lo-cations described in this section and in accordance with theBret Tarver Sprinkler Ordinance (Effective June 17 2002 Re-vised January 12 2005)

An automatic sprinkler system shall be installed throughoutall levels of all new Group A B E F H I M R-1 R-2 R-4 andS occupancies of more than zero square feet and throughout allR-3 occupancies of more than 5000 square feet (465 m2) Thecalculated area shall include all livable space and the area ofany attached garage

Such systems shall be in accordance with NFPA 13 forGroup A B E F H I M and S occupancies NFPA 13R forresidential occupancies up to and including four stories inheight and NFPA 13D for single-family dwellings

Exceptions

1 Detached gazebos and ramadas for residential andpublic use

2 Independent buildings such as restrooms or snackshops 400 square feet (37 m2) or less that are associ-ated with golf courses parks and similar uses

3 Detached noncombustible carports or shade cano-pies

4 Guardhouses that are less than 300 square feet (28 m2)in size used to control access to or within residentialandor commercial developments

5 Detached equipment or storage buildings for com-mercial use not exceeding 300 square feet (28 m2)

6 Detached noncombustible canopies used exclusivelyfor automotive motor fuel-dispensing stations forprivate passenger vehicles not exceeding 5000square feet (465 m2)

7 Manufactured (mobile) home built on a permanentchassis designed and built as a dwelling unit and rec-reational vehicles that were not site built and are por-table in nature

[F] 90321 Existing buildings Existing buildings are re-quired to comply with the provisions of this section whenany of the following apply

1 Building additions that equal 50 percent or more ofthe existing building floor area or exceed 10000square feet (929 m2) whichever is less

2 A building that is less than 2500 square feet (232 m2)and undergoes a change of occupancy to a lower haz-ard level or stays within the current hazard level as de-fined by the Phoenix Fire Code shall not be requiredto provide a fire sprinkler system on a retrofit basis

3 Two or more building permits related to increasedsquare footage that are issued over any three consecu-tive years

4 One or more additions within any three-year periodthat are made to a Group R-3 occupancy and complywith all of the following

41 The aggregate of the additions exceeds 50percent of the original (as of the effective dateof the Bret Tarver Sprinkler Ordinance onJune 17 2002 or at original constructionwhichever is later) square footage of thehouse

42 The new total area of the building is greaterthan 5000 square feet (465 m2)

5 Building remodels are made that require structuralchanges affecting the primary structural system of theexisting building

6 A building that undergoes a change of occupancy to ahigher hazard level or changes occupancy withinHazard Level 1 as defined by the Phoenix Fire Code

[F] 90322 Group H-5 An automatic sprinkler systemshall be installed throughout buildings containing GroupH-5 occupancies The design of the sprinkler system shallnot be less than that required by this code for the occu-pancy hazard classifications in accordance with Table90322

Where the design area of the sprinkler system consists ofa corridor protected by one row of sprinklers the maximumnumber of sprinklers required to be calculated is 13

[F] TABLE 90322GROUP H-5 SPRINKLER DESIGN CRITERIA

LOCATIONOCCUPANCY HAZARD

CLASSIFICATION

Fabrication areas Ordinary Hazard Group 2

Service corridors Ordinary Hazard Group 2

Storage rooms without dispensing Ordinary Hazard Group 2

Storage rooms with dispensing Extra Hazard Group 2

Corridors Ordinary Hazard Group 2

166R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

gt

09_Phoenix_IBC_2005_PG166pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20814 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90323 Rubbish and linen chutes An automatic sprin-kler system shall be installed at the top of rubbish and linenchutes and in their terminal rooms Chutes extendingthrough three or more floors shall have additional sprinklerheads installed within such chutes at alternate floors Chutesprinklers shall be accessible for servicing

[F] 90324 During construction Automatic sprinkler sys-tems required during construction alteration and demoli-tion operations shall be provided in accordance with thePhoenix Fire Code

[F] 90325 Ducts conveying hazardous exhausts Whererequired by the International Mechanical Code automaticsprinklers shall be provided in ducts conveying hazardousexhaust or flammable or combustible materials

Exception Ducts in which the largest cross-sectionaldiameter of the duct is less than 10 inches (254 mm)

[F] 90326 Commercial cooking operations An auto-matic sprinkler system shall be installed in commercialkitchen exhaust hood and duct system where an automaticsprinkler system is used to comply with Section 904

[F] 90327 Other required suppression systems In addi-tion to the requirements of Section 9032 the provisions in-dicated in Table 90327 also require the installation of asuppression system for certain buildings and areas

[F] TABLE 90327ADDITIONAL REQUIRED SUPPRESSION SYSTEMS

SECTION SUBJECT

4028 Covered malls

4032 4033 High-rise buildings

4043 Atriums

4053 Underground structures

4075 Group I-2

4106 Stages

4114 Special amusement buildings

41225 41226 Aircraft hangars

415724 Group H-2

4164 Flammable finishes

4174 Drying rooms

507 Unlimited area buildings

Sprinkler requirements as set forth in thePhoenix Fire Code

[F] 9033 Installation requirements Automatic sprinklersystems shall be designed and installed in accordance withSections 90331 through 90337

[F] 90331 Standards Sprinkler systems shall be designedand installed in accordance with Section 903311903312 or 903313

[F] 903311 NFPA 13 sprinkler systems Where theprovisions of this code require that a building or portionthereof be equipped throughout with an automatic sprin-kler system in accordance with Section 903311 sprin-klers shall be installed throughout in accordance withNFPA 13 except as provided in Section 9033111

[F] 9033111 Exempt locations Automatic sprin-klers shall not be required in the following rooms orareas where such rooms or areas are protected with anapproved automatic fire detection system in accor-dance with Section 9072 that will respond to visibleor invisible particles of combustion Sprinklers shallnot be omitted from any room merely because it isdamp of fire-resistance-rated construction or con-tains electrical equipment

1 Any room where the application of water orflame and water constitutes a serious life or firehazard

2 Any room or space where sprinklers are consid-ered undesirable because of the nature of thecontents when approved by the building offi-cial

3 Generator and transformer rooms separatedfrom the remainder of the building by wallsand floorceiling or roofceiling assemblieshaving a fire-resistance rating of not less than2 hours

4 In rooms or areas that are of noncombustibleconstruction with wholly noncombustible con-tents

[F] 903312 NFPA 13R sprinkler systems Where al-lowed in buildings of Group R up to and including fourstories in height automatic sprinkler systems shall be in-stalled throughout in accordance with NFPA 13R

2003 INTERNATIONAL BUILDING CODEreg 167R

FIRE PROTECTION SYSTEMS

gt

gt

gt

09_Phoenix_IBC_2005_PG167pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20824 PM

Color profile Generic CMYK printer profileComposite Default screen

This page left intentionally blank

168R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG168pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20836 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 9033121 Balconies Sprinkler protection shallbe provided for exterior balconies and ground-floorpatios of dwelling units where the building is of TypeV construction Sidewall sprinklers that are used toprotect such areas shall be permitted to be locatedsuch that their deflectors are within 1 inch (25 mm) to6 inches (152 mm) below the structural members anda maximum distance of 14 inches (356 mm) below thedeck of the exterior balconies that are constructed ofopen wood joist construction

[F] 903313 NFPA 13D sprinkler systems Where al-lowed automatic sprinkler systems in one- and two-fam-ily dwellings shall be installed throughout in accordancewith NFPA 13D

[F] 90332 Quick-response and residential sprinklersWhere automatic sprinkler systems are required by thiscode quick-response or residential automatic sprinklersshall be installed in the following areas in accordance withSection 90331 and their listings

1 Throughout all spaces within a smoke compartmentcontaining patient sleeping units in Group I-2 in ac-cordance with this code

2 Dwelling units and sleeping units in Group R and I-1occupancies

3 Light-hazard occupancies as defined in NFPA 13

[F] 90333 Obstructed locations Automatic sprinklersshall be installed with due regard to obstructions that willdelay activation or obstruct the water distribution patternAutomatic sprinklers shall be installed in or under coveredkiosks displays booths concession stands or equipmentthat exceeds 4 feet (1219 mm) in width Not less than a3-foot (914 mm) clearance shall be maintained between au-tomatic sprinklers and the top of piles of combustible fibers

Exception Kitchen equipment under exhaust hoodsprotected with a fire-extinguishing system in accordancewith Section 904

[F] 90334 Actuation Automatic sprinkler systems shallbe automatically actuated unless specifically provided for inthis code

[F] 90335 Water supplies Water supplies for automaticsprinkler systems shall comply with this section and thestandards referenced in Section 90331 The potable watersupply shall be protected against backflow in accordancewith the requirements of this section and the Arizona StatePlumbing Code

[F] 903351 Domestic services Where the domesticservice provides the water supply for the automaticsprinkler system the supply shall be in accordance withthis section

[F] 9033511 Limited area sprinkler systemsLimited area sprinkler systems serving fewer than 20sprinklers on any single connection are permitted tobe connected to the domestic service where a wet au-tomatic standpipe is not available Limited area sprin-kler systems connected to domestic water suppliesshall comply with each of the following requirements

1 Valves shall not be installed between the do-mestic water riser control valve and the sprin-klers

Exception An approved indicating controlvalve supervised in the open position in ac-cordance with Section 9034

2 The domestic service shall be capable of sup-plying the simultaneous domestic demand andthe sprinkler demand required to be hydrauli-cally calculated by NFPA 13 NFPA 13R orNFPA 13D

[F] 9033512 Residential combination services Asingle combination water supply shall be permittedprovided that the domestic demand is added to thesprinkler demand as required by NFPA 13R

[F] 903352 Secondary water supply A secondaryon-site water supply equal to the hydraulically calculatedsprinkler demand including the hose stream require-ment shall be provided for high-rise buildings in Seis-mic Design Category C D E or F as determined by thiscode The secondary water supply shall have a durationnot less than 30 minutes as determined by the occupancyhazard classification in accordance with NFPA 13

Exception Existing buildings

[F] 90336 Hose threads Fire hose threads used in connec-tion with automatic sprinkler systems shall be approved andcompatible with fire department hose threads

[F] 90337 Fire department connections The location offire department connections shall be approved by the build-ing official

[F] 903371 Locking fire department connection(FDC) caps The fire code official is authorized to re-quire locking FDC caps on fire department connectionsfor water-based fire protection systems where the re-sponding fire department carries appropriate keywrenches for removal

[F] 9034 Sprinkler system monitoring and alarms Allvalves controlling the water supply for automatic sprinkler sys-tems pumps tanks water levels and temperatures critical airpressures and water-flow switches on all sprinkler systemsshall be electrically supervised

Exceptions

1 Automatic sprinkler systems protecting one- andtwo-family dwellings

2 Limited area systems serving fewer than 20 sprin-klers

3 Automatic sprinkler systems installed in accordancewith NFPA 13R where a common supply main is usedto supply both domestic water and the automaticsprinkler systems and a separate shutoff valve for theautomatic sprinkler system is not provided

4 Jockey pump control valves that are sealed or lockedin the open position

2003 INTERNATIONAL BUILDING CODEreg 169R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG169pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20847 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Control valves to commercial kitchen hoods paintspray booths or dip tanks that are sealed or locked inthe open position

6 Valves controlling the fuel supply to fire pump en-gines that are sealed or locked in the open position

7 Trim valves to pressure switches in dry preaction anddeluge sprinkler systems that are sealed or locked inthe open position

[F] 90341 Signals Alarm supervisory and trouble signalsshall be distinctly different and automatically transmitted toan approved central station remote supervising station orproprietary supervising station as defined in NFPA 72 orwhen approved by the building official shall sound an audi-ble signal at a constantly attended location

Exceptions

1 Underground key or hub valves in roadway boxesprovided by the municipality or public utility arenot required to be monitored

2 Backflow prevention device test valves located inlimited area sprinkler system supply piping shallbe locked in the open position In occupancies re-quired to be equipped with a fire alarm system thebackflow preventer valves shall be electrically su-pervised by a tamper switch installed in accor-dance with NFPA 72 and separately annunciated

[F] 90342 Alarms Approved audible devices shall beconnected to every automatic sprinkler system Such sprin-kler water-flow alarm devices shall be activated by waterflow equivalent to the flow of a single sprinkler of the small-est orifice size installed in the system Alarm devices shallbe provided on the exterior of the building in an approvedlocation Where a fire alarm system is installed actuation ofthe automatic sprinkler system shall actuate the building firealarm system

[F] 90343 Floor control valves Approved supervised in-dicating control valves shall be provided at the point of con-nection to the riser on each floor in high-rise buildings

[F] 9035 Testing and maintenance Sprinkler systems shallbe tested and maintained in accordance with the Phoenix FireCode

SECTION 904ALTERNATIVE AUTOMATIC

FIRE-EXTINGUISHING SYSTEMS

[F] 9041 General Automatic fire-extinguishing systemsother than automatic sprinkler systems shall be designed in-stalled inspected tested and maintained in accordance withthe provisions of this section and the applicable referencedstandards

[F] 9042 Where required Automatic fire-extinguishing sys-tems installed as an alternative to the required automatic sprin-kler systems of Section 903 shall be approved by the buildingofficial Automatic fire-extinguishing systems shall not beconsidered alternatives for the purposes of exceptions or reduc-tions permitted by other requirements of this code

[F] 90421 Hood system suppression Each required com-mercial kitchen exhaust hood and duct system required bythe Phoenix Fire Code or the International MechanicalCode to have a Type I hood shall be protected with an ap-proved automatic fire-extinguishing system installed in ac-cordance with this code

[F] 9043 Installation Automatic fire-extinguishing systemsshall be installed in accordance with this section

[F] 90431 Electrical wiring Electrical wiring shall be inaccordance with the National Electrical Code

[F] 90432 Actuation Automatic fire-extinguishing sys-tems shall be automatically actuated and provided with amanual means of actuation in accordance with Section904111

[F] 90433 System interlocking Automatic equipment in-terlocks with fuel shutoffs ventilation controls doorclosers window shutters conveyor openings smoke andheat vents and other features necessary for proper operationof the fire-extinguishing system shall be provided as re-quired by the design and installation standard utilized forthe hazard

[F] 90434 Alarms and warning signs Where alarms arerequired to indicate the operation of automatic fire-extin-guishing systems distinctive audible and visible alarms andwarning signs shall be provided to warn of pending agentdischarge Where exposure to automatic-extinguishingagents poses a hazard to persons and a delay is required toensure the evacuation of occupants before agent dischargea separate warning signal shall be provided to alert occu-pants once agent discharge has begun Audible signals shallbe in accordance with Section 90792

[F] 90435 Monitoring Where a building fire alarm sys-tem is installed automatic fire-extinguishing systems shallbe monitored by the building fire alarm system in accor-dance with NFPA 72

[F] 9044 Inspection and testing Automatic fire-extinguish-ing systems shall be inspected and tested in accordance withthe provisions of this section prior to acceptance

[F] 90441 Inspection Prior to conducting final accep-tance tests the following items shall be inspected

1 Hazard specification for consistency with design haz-ard

2 Type location and spacing of automatic- and man-ual-initiating devices

3 Size placement and position of nozzles or dischargeorifices

4 Location and identification of audible and visiblealarm devices

5 Identification of devices with proper designations

6 Operating instructions

[F] 90442 Alarm testing Notification appliances con-nections to fire alarm systems and connections to approvedsupervising stations shall be tested in accordance with thissection and Section 907 to verify proper operation

170R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG170pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20901 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 904421 Audible and visible signals The audibil-ity and visibility of notification appliances signalingagent discharge or system operation where requiredshall be verified

[F] 90443 Monitor testing Connections to protected pre-mises and supervising station fire alarm systems shall betested to verify proper identification and retransmission ofalarms from automatic fire-extinguishing systems

[F] 9045 Wet-chemical systems Wet-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17A and their listing

[F] 9046 Dry-chemical systems Dry-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17 and their listing

[F] 9047 Foam systems Foam-extinguishing systems shall beinstalled maintained periodically inspected and tested in ac-cordance with NFPA 11 and NFPA 16 and their listing

[F] 9048 Carbon dioxide systems Carbon dioxide extin-guishing systems shall be installed maintained periodicallyinspected and tested in accordance with NFPA 12 and their list-ing

[F] 9049 Halon systems Halogenated extinguishing systemsshall be installed maintained periodically inspected and testedin accordance with NFPA 12A and their listing

[F] 90410 Clean-agent systems Clean-agent fire-extinguish-ing systems shall be installed maintained periodically in-spected and tested in accordance with NFPA 2001 and theirlisting

[F] 90411 Commercial cooking systems The automaticfire-extinguishing system for commercial cooking systemsshall be of a type recognized for protection of commercialcooking equipment and exhaust systems of the type and ar-rangement protected Preengineered automatic dry- andwet-chemical extinguishing systems shall be tested in accor-dance with UL 300 and listed and labeled for the intended ap-plication Other types of automatic fire-extinguishing systemsshall be listed and labeled for specific use as protection forcommercial cooking operations The system shall be installedin accordance with this code its listing and the manufacturerrsquosinstallation instructions Automatic fire-extinguishing systemsof the following types shall be installed in accordance with thereferenced standard indicated as shown

1 Carbon dioxide extinguishing systems NFPA 12

2 Automatic sprinkler systems NFPA 13

3 Foam-water sprinkler system or foam-water spray sys-tems NFPA 16

4 Dry-chemical extinguishing systems NFPA 17

5 Wet-chemical extinguishing systems NFPA 17A

Exception Factory-built commercial cooking recirculatingsystems that are tested in accordance with UL 197 andlisted labeled and installed in accordance with Section3041 of the International Mechanical Code

[F] 904111 Manual system operation A manual actua-tion device shall be located at or near a means of egress fromthe cooking area a minimum of 10 feet (3048 mm) and a

maximum of 20 feet (6096 mm) from the kitchen exhaustsystem The manual actuation device shall be located a min-imum of 4 feet (1219 mm) and a maximum of 5 feet (1524mm) above the floor The manual actuation shall require amaximum force of 40 pounds (178 N) and a maximummovement of 14 inches (356 mm) to actuate the fire sup-pression system

Exception Automatic sprinkler systems shall not be re-quired to be equipped with manual actuation means

[F] 904112 System interconnection The actuation of thefire suppression system shall automatically shut down thefuel or electrical power supply to the cooking equipmentThe fuel and electrical supply reset shall be manual

[F] 904113 Carbon dioxide systems When carbon diox-ide systems are used there shall be a nozzle at the top of theventilating duct Additional nozzles that are symmetricallyarranged to give uniform distribution shall be installedwithin vertical ducts exceeding 20 feet (6096 mm) and hori-zontal ducts exceeding 50 feet (15 240 mm) Dampers shallbe installed at either the top or the bottom of the duct andshall be arranged to operate automatically upon activationof the fire-extinguishing system Where the damper is in-stalled at the top of the duct the top nozzle shall be immedi-ately below the damper Automatic carbon dioxidefire-extinguishing systems shall be sufficiently sized to pro-tect against all hazards venting through a common duct si-multaneously

[F] 9041131 Ventilation system Commercial-typecooking equipment protected by an automatic carbon di-oxide-extinguishing system shall be arranged to shut offthe ventilation system upon activation

[F] 904114 Special provisions for automatic sprinklersystems Automatic sprinkler systems protecting commer-cial-type cooking equipment shall be supplied from a sepa-rate readily accessible indicating-type control valve that isidentified

[F] 9041141 Listed sprinklers Sprinklers used forthe protection of fryers shall be listed for that applicationand installed in accordance with their listing

SECTION 905STANDPIPE SYSTEMS

[F] 9051 General Standpipe systems shall be provided in newbuildings and structures in accordance with this section Firehose threads used in connection with standpipe systems shallbe approved and shall be compatible with fire department hosethreads The location of fire department hose connections shallbe approved In buildings used for high-piled combustible stor-age fire protection shall be in accordance with the PhoenixFire Code

[F] 9052 Installation standards Standpipe systems shall beinstalled in accordance with this section and NFPA 14

[F] 9053 Required installations Standpipe systems shall beinstalled where required by Sections 90531 through 90536and in the locations indicated in Sections 9054 9055 and

2003 INTERNATIONAL BUILDING CODEreg 171R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG171pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20954 PM

Color profile Generic CMYK printer profileComposite Default screen

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 3: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

[F] MULTIPLE-STATION ALARM DEVICE Two ormore single-station alarm devices that are capable of intercon-nection such that actuation of one causes all integral or separateaudible alarms to operate It also can consist of one single-sta-tion alarm device having connections to other detectors or to amanual fire alarm box

[F] MULTIPLE-STATION SMOKE ALARM Two or moresingle-station alarm devices that are capable of interconnectionsuch that actuation of one causes all integral or separate audiblealarms to operate

[F] NUISANCE ALARM An alarm caused by mechanicalfailure malfunction improper installation or lack of propermaintenance or an alarm activated by a cause that cannot bedetermined

[F] RECORD DRAWINGS Drawings (ldquoas builtsrdquo) that doc-ument the location of all devices appliances wiring sequenceswiring methods and connections of the components of a firealarm system as installed

[F] SINGLE-STATION SMOKE ALARM An assembly in-corporating the detector the control equipment and thealarm-sounding device in one unit operated from a power sup-ply either in the unit or obtained at the point of installation

[F] SMOKE ALARM A single- or multiple-station alarm re-sponsive to smoke and not connected to a system

[F] SMOKE DETECTOR A listed device that senses visibleor invisible particles of combustion

SMOKEPROOF ENCLOSURE An exit stairway designedand constructed so that the movement of the products of com-bustion produced by a fire occurring in any part of the buildinginto the enclosure is limited

[F] STANDPIPE SYSTEM CLASSES OF Standpipeclasses are as follows

Class I system A system providing 25-inch (64 mm) hoseconnections to supply water for use by fire departments andthose trained in handling heavy fire streams

Class II system A system providing 15-inch (38 mm) hosestations to supply water for use primarily by the building oc-cupants or by the fire department during initial response

Class III system A system providing 15-inch (38 mm)hose stations to supply water for use by building occupantsand 25-inch (64 mm) hose connections to supply a largervolume of water for use by fire departments and thosetrained in handling heavy fire streams

[F] STANDPIPE TYPES OF Standpipe types are as follows

Automatic dry A dry standpipe system normally filledwith pressurized air that is arranged through the use of a de-vice such as dry pipe valve to admit water into the systempiping automatically upon the opening of a hose valve Thewater supply for an automatic dry standpipe system shall becapable of supplying the system demand

Automatic wet A wet standpipe system that has a watersupply that is capable of supplying the system demand auto-matically

Manual dry A dry standpipe system that does not have apermanent water supply attached to the system Manual dry

standpipe systems require water from a fire departmentpumper to be pumped into the system through the fire de-partment connection in order to meet the system demand

Manual wet A wet standpipe system connected to a watersupply for the purpose of maintaining water within the sys-tem but does not have a water supply capable of deliveringthe system demand attached to the system Manual-wetstandpipe systems require water from a fire departmentpumper (or the like) to be pumped into the system in order tomeet the system demand

Semiautomatic dry A dry standpipe system that is ar-ranged through the use of a device such as a deluge valve toadmit water into the system piping upon activation of a re-mote control device located at a hose connection A remotecontrol activation device shall be provided at each hose con-nection The water supply for a semiautomatic drystandpipe system shall be capable of supplying the systemdemand

[F] SUPERVISING STATION A facility that receives sig-nals and at which personnel are in attendance at all times to re-spond to these signals

[F] SUPERVISORY SERVICE The service required tomonitor performance of guard tours and the operative condi-tion of fixed suppression systems or other systems for the pro-tection of life and property

[F] SUPERVISORY SIGNAL A signal indicating the needof action in connection with the supervision of guard tours thefire suppression systems or equipment or the maintenance fea-tures of related systems

[F] SUPERVISORY SIGNAL-INITIATING DEVICE Aninitiation device such as a valve supervisory switch wa-ter-level indicator or low-air pressure switch on a dry-pipesprinkler system whose change of state signals an off-normalcondition and its restoration to normal of a fire protection orlife safety system or a need for action in connection with guardtours fire suppression systems or equipment or maintenancefeatures of related systems

[F] TIRES BULK STORAGE OF Storage of tires where thearea available for storage exceeds 20000 cubic feet (566 m3)

[F] TROUBLE SIGNAL A signal initiated by the fire alarmsystem or device indicative of a fault in a monitored circuit orcomponent

[F] VISIBLE ALARM NOTIFICATION APPLIANCE Anotification appliance that alerts by the sense of sight

[F] WET-CHEMICAL EXTINGUISHING SYSTEM Asolution of water and potassium-carbonate-based chemicalpotassium-acetate-based chemical or a combination thereofforming an extinguishing agent

[F] WIRELESS PROTECTION SYSTEM A system or apart of a system that can transmit and receive signals withoutthe aid of wire

[F] ZONE A defined area within the protected premises Azone can define an area from which a signal can be received anarea to which a signal can be sent or an area in which a form ofcontrol can be executed

2003 INTERNATIONAL BUILDING CODEreg 165

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG165pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20802 PM

Color profile Generic CMYK printer profileComposite Default screen

SECTION 903AUTOMATIC SPRINKLER SYSTEMS

[F] 9031 General Automatic sprinkler systems shall complywith this section

[F] 90311 Alternative protection Alternative automaticfire-extinguishing systems complying with Section 904shall be permitted in lieu of automatic sprinkler protectionwhere recognized by the applicable standard and approvedby the building official

[F] 9032 Where required Approved automatic sprinkler sys-tems in new buildings and structures shall be provided in the lo-cations described in this section and in accordance with theBret Tarver Sprinkler Ordinance (Effective June 17 2002 Re-vised January 12 2005)

An automatic sprinkler system shall be installed throughoutall levels of all new Group A B E F H I M R-1 R-2 R-4 andS occupancies of more than zero square feet and throughout allR-3 occupancies of more than 5000 square feet (465 m2) Thecalculated area shall include all livable space and the area ofany attached garage

Such systems shall be in accordance with NFPA 13 forGroup A B E F H I M and S occupancies NFPA 13R forresidential occupancies up to and including four stories inheight and NFPA 13D for single-family dwellings

Exceptions

1 Detached gazebos and ramadas for residential andpublic use

2 Independent buildings such as restrooms or snackshops 400 square feet (37 m2) or less that are associ-ated with golf courses parks and similar uses

3 Detached noncombustible carports or shade cano-pies

4 Guardhouses that are less than 300 square feet (28 m2)in size used to control access to or within residentialandor commercial developments

5 Detached equipment or storage buildings for com-mercial use not exceeding 300 square feet (28 m2)

6 Detached noncombustible canopies used exclusivelyfor automotive motor fuel-dispensing stations forprivate passenger vehicles not exceeding 5000square feet (465 m2)

7 Manufactured (mobile) home built on a permanentchassis designed and built as a dwelling unit and rec-reational vehicles that were not site built and are por-table in nature

[F] 90321 Existing buildings Existing buildings are re-quired to comply with the provisions of this section whenany of the following apply

1 Building additions that equal 50 percent or more ofthe existing building floor area or exceed 10000square feet (929 m2) whichever is less

2 A building that is less than 2500 square feet (232 m2)and undergoes a change of occupancy to a lower haz-ard level or stays within the current hazard level as de-fined by the Phoenix Fire Code shall not be requiredto provide a fire sprinkler system on a retrofit basis

3 Two or more building permits related to increasedsquare footage that are issued over any three consecu-tive years

4 One or more additions within any three-year periodthat are made to a Group R-3 occupancy and complywith all of the following

41 The aggregate of the additions exceeds 50percent of the original (as of the effective dateof the Bret Tarver Sprinkler Ordinance onJune 17 2002 or at original constructionwhichever is later) square footage of thehouse

42 The new total area of the building is greaterthan 5000 square feet (465 m2)

5 Building remodels are made that require structuralchanges affecting the primary structural system of theexisting building

6 A building that undergoes a change of occupancy to ahigher hazard level or changes occupancy withinHazard Level 1 as defined by the Phoenix Fire Code

[F] 90322 Group H-5 An automatic sprinkler systemshall be installed throughout buildings containing GroupH-5 occupancies The design of the sprinkler system shallnot be less than that required by this code for the occu-pancy hazard classifications in accordance with Table90322

Where the design area of the sprinkler system consists ofa corridor protected by one row of sprinklers the maximumnumber of sprinklers required to be calculated is 13

[F] TABLE 90322GROUP H-5 SPRINKLER DESIGN CRITERIA

LOCATIONOCCUPANCY HAZARD

CLASSIFICATION

Fabrication areas Ordinary Hazard Group 2

Service corridors Ordinary Hazard Group 2

Storage rooms without dispensing Ordinary Hazard Group 2

Storage rooms with dispensing Extra Hazard Group 2

Corridors Ordinary Hazard Group 2

166R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

gt

09_Phoenix_IBC_2005_PG166pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20814 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90323 Rubbish and linen chutes An automatic sprin-kler system shall be installed at the top of rubbish and linenchutes and in their terminal rooms Chutes extendingthrough three or more floors shall have additional sprinklerheads installed within such chutes at alternate floors Chutesprinklers shall be accessible for servicing

[F] 90324 During construction Automatic sprinkler sys-tems required during construction alteration and demoli-tion operations shall be provided in accordance with thePhoenix Fire Code

[F] 90325 Ducts conveying hazardous exhausts Whererequired by the International Mechanical Code automaticsprinklers shall be provided in ducts conveying hazardousexhaust or flammable or combustible materials

Exception Ducts in which the largest cross-sectionaldiameter of the duct is less than 10 inches (254 mm)

[F] 90326 Commercial cooking operations An auto-matic sprinkler system shall be installed in commercialkitchen exhaust hood and duct system where an automaticsprinkler system is used to comply with Section 904

[F] 90327 Other required suppression systems In addi-tion to the requirements of Section 9032 the provisions in-dicated in Table 90327 also require the installation of asuppression system for certain buildings and areas

[F] TABLE 90327ADDITIONAL REQUIRED SUPPRESSION SYSTEMS

SECTION SUBJECT

4028 Covered malls

4032 4033 High-rise buildings

4043 Atriums

4053 Underground structures

4075 Group I-2

4106 Stages

4114 Special amusement buildings

41225 41226 Aircraft hangars

415724 Group H-2

4164 Flammable finishes

4174 Drying rooms

507 Unlimited area buildings

Sprinkler requirements as set forth in thePhoenix Fire Code

[F] 9033 Installation requirements Automatic sprinklersystems shall be designed and installed in accordance withSections 90331 through 90337

[F] 90331 Standards Sprinkler systems shall be designedand installed in accordance with Section 903311903312 or 903313

[F] 903311 NFPA 13 sprinkler systems Where theprovisions of this code require that a building or portionthereof be equipped throughout with an automatic sprin-kler system in accordance with Section 903311 sprin-klers shall be installed throughout in accordance withNFPA 13 except as provided in Section 9033111

[F] 9033111 Exempt locations Automatic sprin-klers shall not be required in the following rooms orareas where such rooms or areas are protected with anapproved automatic fire detection system in accor-dance with Section 9072 that will respond to visibleor invisible particles of combustion Sprinklers shallnot be omitted from any room merely because it isdamp of fire-resistance-rated construction or con-tains electrical equipment

1 Any room where the application of water orflame and water constitutes a serious life or firehazard

2 Any room or space where sprinklers are consid-ered undesirable because of the nature of thecontents when approved by the building offi-cial

3 Generator and transformer rooms separatedfrom the remainder of the building by wallsand floorceiling or roofceiling assemblieshaving a fire-resistance rating of not less than2 hours

4 In rooms or areas that are of noncombustibleconstruction with wholly noncombustible con-tents

[F] 903312 NFPA 13R sprinkler systems Where al-lowed in buildings of Group R up to and including fourstories in height automatic sprinkler systems shall be in-stalled throughout in accordance with NFPA 13R

2003 INTERNATIONAL BUILDING CODEreg 167R

FIRE PROTECTION SYSTEMS

gt

gt

gt

09_Phoenix_IBC_2005_PG167pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20824 PM

Color profile Generic CMYK printer profileComposite Default screen

This page left intentionally blank

168R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG168pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20836 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 9033121 Balconies Sprinkler protection shallbe provided for exterior balconies and ground-floorpatios of dwelling units where the building is of TypeV construction Sidewall sprinklers that are used toprotect such areas shall be permitted to be locatedsuch that their deflectors are within 1 inch (25 mm) to6 inches (152 mm) below the structural members anda maximum distance of 14 inches (356 mm) below thedeck of the exterior balconies that are constructed ofopen wood joist construction

[F] 903313 NFPA 13D sprinkler systems Where al-lowed automatic sprinkler systems in one- and two-fam-ily dwellings shall be installed throughout in accordancewith NFPA 13D

[F] 90332 Quick-response and residential sprinklersWhere automatic sprinkler systems are required by thiscode quick-response or residential automatic sprinklersshall be installed in the following areas in accordance withSection 90331 and their listings

1 Throughout all spaces within a smoke compartmentcontaining patient sleeping units in Group I-2 in ac-cordance with this code

2 Dwelling units and sleeping units in Group R and I-1occupancies

3 Light-hazard occupancies as defined in NFPA 13

[F] 90333 Obstructed locations Automatic sprinklersshall be installed with due regard to obstructions that willdelay activation or obstruct the water distribution patternAutomatic sprinklers shall be installed in or under coveredkiosks displays booths concession stands or equipmentthat exceeds 4 feet (1219 mm) in width Not less than a3-foot (914 mm) clearance shall be maintained between au-tomatic sprinklers and the top of piles of combustible fibers

Exception Kitchen equipment under exhaust hoodsprotected with a fire-extinguishing system in accordancewith Section 904

[F] 90334 Actuation Automatic sprinkler systems shallbe automatically actuated unless specifically provided for inthis code

[F] 90335 Water supplies Water supplies for automaticsprinkler systems shall comply with this section and thestandards referenced in Section 90331 The potable watersupply shall be protected against backflow in accordancewith the requirements of this section and the Arizona StatePlumbing Code

[F] 903351 Domestic services Where the domesticservice provides the water supply for the automaticsprinkler system the supply shall be in accordance withthis section

[F] 9033511 Limited area sprinkler systemsLimited area sprinkler systems serving fewer than 20sprinklers on any single connection are permitted tobe connected to the domestic service where a wet au-tomatic standpipe is not available Limited area sprin-kler systems connected to domestic water suppliesshall comply with each of the following requirements

1 Valves shall not be installed between the do-mestic water riser control valve and the sprin-klers

Exception An approved indicating controlvalve supervised in the open position in ac-cordance with Section 9034

2 The domestic service shall be capable of sup-plying the simultaneous domestic demand andthe sprinkler demand required to be hydrauli-cally calculated by NFPA 13 NFPA 13R orNFPA 13D

[F] 9033512 Residential combination services Asingle combination water supply shall be permittedprovided that the domestic demand is added to thesprinkler demand as required by NFPA 13R

[F] 903352 Secondary water supply A secondaryon-site water supply equal to the hydraulically calculatedsprinkler demand including the hose stream require-ment shall be provided for high-rise buildings in Seis-mic Design Category C D E or F as determined by thiscode The secondary water supply shall have a durationnot less than 30 minutes as determined by the occupancyhazard classification in accordance with NFPA 13

Exception Existing buildings

[F] 90336 Hose threads Fire hose threads used in connec-tion with automatic sprinkler systems shall be approved andcompatible with fire department hose threads

[F] 90337 Fire department connections The location offire department connections shall be approved by the build-ing official

[F] 903371 Locking fire department connection(FDC) caps The fire code official is authorized to re-quire locking FDC caps on fire department connectionsfor water-based fire protection systems where the re-sponding fire department carries appropriate keywrenches for removal

[F] 9034 Sprinkler system monitoring and alarms Allvalves controlling the water supply for automatic sprinkler sys-tems pumps tanks water levels and temperatures critical airpressures and water-flow switches on all sprinkler systemsshall be electrically supervised

Exceptions

1 Automatic sprinkler systems protecting one- andtwo-family dwellings

2 Limited area systems serving fewer than 20 sprin-klers

3 Automatic sprinkler systems installed in accordancewith NFPA 13R where a common supply main is usedto supply both domestic water and the automaticsprinkler systems and a separate shutoff valve for theautomatic sprinkler system is not provided

4 Jockey pump control valves that are sealed or lockedin the open position

2003 INTERNATIONAL BUILDING CODEreg 169R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG169pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20847 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Control valves to commercial kitchen hoods paintspray booths or dip tanks that are sealed or locked inthe open position

6 Valves controlling the fuel supply to fire pump en-gines that are sealed or locked in the open position

7 Trim valves to pressure switches in dry preaction anddeluge sprinkler systems that are sealed or locked inthe open position

[F] 90341 Signals Alarm supervisory and trouble signalsshall be distinctly different and automatically transmitted toan approved central station remote supervising station orproprietary supervising station as defined in NFPA 72 orwhen approved by the building official shall sound an audi-ble signal at a constantly attended location

Exceptions

1 Underground key or hub valves in roadway boxesprovided by the municipality or public utility arenot required to be monitored

2 Backflow prevention device test valves located inlimited area sprinkler system supply piping shallbe locked in the open position In occupancies re-quired to be equipped with a fire alarm system thebackflow preventer valves shall be electrically su-pervised by a tamper switch installed in accor-dance with NFPA 72 and separately annunciated

[F] 90342 Alarms Approved audible devices shall beconnected to every automatic sprinkler system Such sprin-kler water-flow alarm devices shall be activated by waterflow equivalent to the flow of a single sprinkler of the small-est orifice size installed in the system Alarm devices shallbe provided on the exterior of the building in an approvedlocation Where a fire alarm system is installed actuation ofthe automatic sprinkler system shall actuate the building firealarm system

[F] 90343 Floor control valves Approved supervised in-dicating control valves shall be provided at the point of con-nection to the riser on each floor in high-rise buildings

[F] 9035 Testing and maintenance Sprinkler systems shallbe tested and maintained in accordance with the Phoenix FireCode

SECTION 904ALTERNATIVE AUTOMATIC

FIRE-EXTINGUISHING SYSTEMS

[F] 9041 General Automatic fire-extinguishing systemsother than automatic sprinkler systems shall be designed in-stalled inspected tested and maintained in accordance withthe provisions of this section and the applicable referencedstandards

[F] 9042 Where required Automatic fire-extinguishing sys-tems installed as an alternative to the required automatic sprin-kler systems of Section 903 shall be approved by the buildingofficial Automatic fire-extinguishing systems shall not beconsidered alternatives for the purposes of exceptions or reduc-tions permitted by other requirements of this code

[F] 90421 Hood system suppression Each required com-mercial kitchen exhaust hood and duct system required bythe Phoenix Fire Code or the International MechanicalCode to have a Type I hood shall be protected with an ap-proved automatic fire-extinguishing system installed in ac-cordance with this code

[F] 9043 Installation Automatic fire-extinguishing systemsshall be installed in accordance with this section

[F] 90431 Electrical wiring Electrical wiring shall be inaccordance with the National Electrical Code

[F] 90432 Actuation Automatic fire-extinguishing sys-tems shall be automatically actuated and provided with amanual means of actuation in accordance with Section904111

[F] 90433 System interlocking Automatic equipment in-terlocks with fuel shutoffs ventilation controls doorclosers window shutters conveyor openings smoke andheat vents and other features necessary for proper operationof the fire-extinguishing system shall be provided as re-quired by the design and installation standard utilized forthe hazard

[F] 90434 Alarms and warning signs Where alarms arerequired to indicate the operation of automatic fire-extin-guishing systems distinctive audible and visible alarms andwarning signs shall be provided to warn of pending agentdischarge Where exposure to automatic-extinguishingagents poses a hazard to persons and a delay is required toensure the evacuation of occupants before agent dischargea separate warning signal shall be provided to alert occu-pants once agent discharge has begun Audible signals shallbe in accordance with Section 90792

[F] 90435 Monitoring Where a building fire alarm sys-tem is installed automatic fire-extinguishing systems shallbe monitored by the building fire alarm system in accor-dance with NFPA 72

[F] 9044 Inspection and testing Automatic fire-extinguish-ing systems shall be inspected and tested in accordance withthe provisions of this section prior to acceptance

[F] 90441 Inspection Prior to conducting final accep-tance tests the following items shall be inspected

1 Hazard specification for consistency with design haz-ard

2 Type location and spacing of automatic- and man-ual-initiating devices

3 Size placement and position of nozzles or dischargeorifices

4 Location and identification of audible and visiblealarm devices

5 Identification of devices with proper designations

6 Operating instructions

[F] 90442 Alarm testing Notification appliances con-nections to fire alarm systems and connections to approvedsupervising stations shall be tested in accordance with thissection and Section 907 to verify proper operation

170R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG170pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20901 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 904421 Audible and visible signals The audibil-ity and visibility of notification appliances signalingagent discharge or system operation where requiredshall be verified

[F] 90443 Monitor testing Connections to protected pre-mises and supervising station fire alarm systems shall betested to verify proper identification and retransmission ofalarms from automatic fire-extinguishing systems

[F] 9045 Wet-chemical systems Wet-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17A and their listing

[F] 9046 Dry-chemical systems Dry-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17 and their listing

[F] 9047 Foam systems Foam-extinguishing systems shall beinstalled maintained periodically inspected and tested in ac-cordance with NFPA 11 and NFPA 16 and their listing

[F] 9048 Carbon dioxide systems Carbon dioxide extin-guishing systems shall be installed maintained periodicallyinspected and tested in accordance with NFPA 12 and their list-ing

[F] 9049 Halon systems Halogenated extinguishing systemsshall be installed maintained periodically inspected and testedin accordance with NFPA 12A and their listing

[F] 90410 Clean-agent systems Clean-agent fire-extinguish-ing systems shall be installed maintained periodically in-spected and tested in accordance with NFPA 2001 and theirlisting

[F] 90411 Commercial cooking systems The automaticfire-extinguishing system for commercial cooking systemsshall be of a type recognized for protection of commercialcooking equipment and exhaust systems of the type and ar-rangement protected Preengineered automatic dry- andwet-chemical extinguishing systems shall be tested in accor-dance with UL 300 and listed and labeled for the intended ap-plication Other types of automatic fire-extinguishing systemsshall be listed and labeled for specific use as protection forcommercial cooking operations The system shall be installedin accordance with this code its listing and the manufacturerrsquosinstallation instructions Automatic fire-extinguishing systemsof the following types shall be installed in accordance with thereferenced standard indicated as shown

1 Carbon dioxide extinguishing systems NFPA 12

2 Automatic sprinkler systems NFPA 13

3 Foam-water sprinkler system or foam-water spray sys-tems NFPA 16

4 Dry-chemical extinguishing systems NFPA 17

5 Wet-chemical extinguishing systems NFPA 17A

Exception Factory-built commercial cooking recirculatingsystems that are tested in accordance with UL 197 andlisted labeled and installed in accordance with Section3041 of the International Mechanical Code

[F] 904111 Manual system operation A manual actua-tion device shall be located at or near a means of egress fromthe cooking area a minimum of 10 feet (3048 mm) and a

maximum of 20 feet (6096 mm) from the kitchen exhaustsystem The manual actuation device shall be located a min-imum of 4 feet (1219 mm) and a maximum of 5 feet (1524mm) above the floor The manual actuation shall require amaximum force of 40 pounds (178 N) and a maximummovement of 14 inches (356 mm) to actuate the fire sup-pression system

Exception Automatic sprinkler systems shall not be re-quired to be equipped with manual actuation means

[F] 904112 System interconnection The actuation of thefire suppression system shall automatically shut down thefuel or electrical power supply to the cooking equipmentThe fuel and electrical supply reset shall be manual

[F] 904113 Carbon dioxide systems When carbon diox-ide systems are used there shall be a nozzle at the top of theventilating duct Additional nozzles that are symmetricallyarranged to give uniform distribution shall be installedwithin vertical ducts exceeding 20 feet (6096 mm) and hori-zontal ducts exceeding 50 feet (15 240 mm) Dampers shallbe installed at either the top or the bottom of the duct andshall be arranged to operate automatically upon activationof the fire-extinguishing system Where the damper is in-stalled at the top of the duct the top nozzle shall be immedi-ately below the damper Automatic carbon dioxidefire-extinguishing systems shall be sufficiently sized to pro-tect against all hazards venting through a common duct si-multaneously

[F] 9041131 Ventilation system Commercial-typecooking equipment protected by an automatic carbon di-oxide-extinguishing system shall be arranged to shut offthe ventilation system upon activation

[F] 904114 Special provisions for automatic sprinklersystems Automatic sprinkler systems protecting commer-cial-type cooking equipment shall be supplied from a sepa-rate readily accessible indicating-type control valve that isidentified

[F] 9041141 Listed sprinklers Sprinklers used forthe protection of fryers shall be listed for that applicationand installed in accordance with their listing

SECTION 905STANDPIPE SYSTEMS

[F] 9051 General Standpipe systems shall be provided in newbuildings and structures in accordance with this section Firehose threads used in connection with standpipe systems shallbe approved and shall be compatible with fire department hosethreads The location of fire department hose connections shallbe approved In buildings used for high-piled combustible stor-age fire protection shall be in accordance with the PhoenixFire Code

[F] 9052 Installation standards Standpipe systems shall beinstalled in accordance with this section and NFPA 14

[F] 9053 Required installations Standpipe systems shall beinstalled where required by Sections 90531 through 90536and in the locations indicated in Sections 9054 9055 and

2003 INTERNATIONAL BUILDING CODEreg 171R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG171pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20954 PM

Color profile Generic CMYK printer profileComposite Default screen

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 4: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

SECTION 903AUTOMATIC SPRINKLER SYSTEMS

[F] 9031 General Automatic sprinkler systems shall complywith this section

[F] 90311 Alternative protection Alternative automaticfire-extinguishing systems complying with Section 904shall be permitted in lieu of automatic sprinkler protectionwhere recognized by the applicable standard and approvedby the building official

[F] 9032 Where required Approved automatic sprinkler sys-tems in new buildings and structures shall be provided in the lo-cations described in this section and in accordance with theBret Tarver Sprinkler Ordinance (Effective June 17 2002 Re-vised January 12 2005)

An automatic sprinkler system shall be installed throughoutall levels of all new Group A B E F H I M R-1 R-2 R-4 andS occupancies of more than zero square feet and throughout allR-3 occupancies of more than 5000 square feet (465 m2) Thecalculated area shall include all livable space and the area ofany attached garage

Such systems shall be in accordance with NFPA 13 forGroup A B E F H I M and S occupancies NFPA 13R forresidential occupancies up to and including four stories inheight and NFPA 13D for single-family dwellings

Exceptions

1 Detached gazebos and ramadas for residential andpublic use

2 Independent buildings such as restrooms or snackshops 400 square feet (37 m2) or less that are associ-ated with golf courses parks and similar uses

3 Detached noncombustible carports or shade cano-pies

4 Guardhouses that are less than 300 square feet (28 m2)in size used to control access to or within residentialandor commercial developments

5 Detached equipment or storage buildings for com-mercial use not exceeding 300 square feet (28 m2)

6 Detached noncombustible canopies used exclusivelyfor automotive motor fuel-dispensing stations forprivate passenger vehicles not exceeding 5000square feet (465 m2)

7 Manufactured (mobile) home built on a permanentchassis designed and built as a dwelling unit and rec-reational vehicles that were not site built and are por-table in nature

[F] 90321 Existing buildings Existing buildings are re-quired to comply with the provisions of this section whenany of the following apply

1 Building additions that equal 50 percent or more ofthe existing building floor area or exceed 10000square feet (929 m2) whichever is less

2 A building that is less than 2500 square feet (232 m2)and undergoes a change of occupancy to a lower haz-ard level or stays within the current hazard level as de-fined by the Phoenix Fire Code shall not be requiredto provide a fire sprinkler system on a retrofit basis

3 Two or more building permits related to increasedsquare footage that are issued over any three consecu-tive years

4 One or more additions within any three-year periodthat are made to a Group R-3 occupancy and complywith all of the following

41 The aggregate of the additions exceeds 50percent of the original (as of the effective dateof the Bret Tarver Sprinkler Ordinance onJune 17 2002 or at original constructionwhichever is later) square footage of thehouse

42 The new total area of the building is greaterthan 5000 square feet (465 m2)

5 Building remodels are made that require structuralchanges affecting the primary structural system of theexisting building

6 A building that undergoes a change of occupancy to ahigher hazard level or changes occupancy withinHazard Level 1 as defined by the Phoenix Fire Code

[F] 90322 Group H-5 An automatic sprinkler systemshall be installed throughout buildings containing GroupH-5 occupancies The design of the sprinkler system shallnot be less than that required by this code for the occu-pancy hazard classifications in accordance with Table90322

Where the design area of the sprinkler system consists ofa corridor protected by one row of sprinklers the maximumnumber of sprinklers required to be calculated is 13

[F] TABLE 90322GROUP H-5 SPRINKLER DESIGN CRITERIA

LOCATIONOCCUPANCY HAZARD

CLASSIFICATION

Fabrication areas Ordinary Hazard Group 2

Service corridors Ordinary Hazard Group 2

Storage rooms without dispensing Ordinary Hazard Group 2

Storage rooms with dispensing Extra Hazard Group 2

Corridors Ordinary Hazard Group 2

166R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

gt

09_Phoenix_IBC_2005_PG166pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20814 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90323 Rubbish and linen chutes An automatic sprin-kler system shall be installed at the top of rubbish and linenchutes and in their terminal rooms Chutes extendingthrough three or more floors shall have additional sprinklerheads installed within such chutes at alternate floors Chutesprinklers shall be accessible for servicing

[F] 90324 During construction Automatic sprinkler sys-tems required during construction alteration and demoli-tion operations shall be provided in accordance with thePhoenix Fire Code

[F] 90325 Ducts conveying hazardous exhausts Whererequired by the International Mechanical Code automaticsprinklers shall be provided in ducts conveying hazardousexhaust or flammable or combustible materials

Exception Ducts in which the largest cross-sectionaldiameter of the duct is less than 10 inches (254 mm)

[F] 90326 Commercial cooking operations An auto-matic sprinkler system shall be installed in commercialkitchen exhaust hood and duct system where an automaticsprinkler system is used to comply with Section 904

[F] 90327 Other required suppression systems In addi-tion to the requirements of Section 9032 the provisions in-dicated in Table 90327 also require the installation of asuppression system for certain buildings and areas

[F] TABLE 90327ADDITIONAL REQUIRED SUPPRESSION SYSTEMS

SECTION SUBJECT

4028 Covered malls

4032 4033 High-rise buildings

4043 Atriums

4053 Underground structures

4075 Group I-2

4106 Stages

4114 Special amusement buildings

41225 41226 Aircraft hangars

415724 Group H-2

4164 Flammable finishes

4174 Drying rooms

507 Unlimited area buildings

Sprinkler requirements as set forth in thePhoenix Fire Code

[F] 9033 Installation requirements Automatic sprinklersystems shall be designed and installed in accordance withSections 90331 through 90337

[F] 90331 Standards Sprinkler systems shall be designedand installed in accordance with Section 903311903312 or 903313

[F] 903311 NFPA 13 sprinkler systems Where theprovisions of this code require that a building or portionthereof be equipped throughout with an automatic sprin-kler system in accordance with Section 903311 sprin-klers shall be installed throughout in accordance withNFPA 13 except as provided in Section 9033111

[F] 9033111 Exempt locations Automatic sprin-klers shall not be required in the following rooms orareas where such rooms or areas are protected with anapproved automatic fire detection system in accor-dance with Section 9072 that will respond to visibleor invisible particles of combustion Sprinklers shallnot be omitted from any room merely because it isdamp of fire-resistance-rated construction or con-tains electrical equipment

1 Any room where the application of water orflame and water constitutes a serious life or firehazard

2 Any room or space where sprinklers are consid-ered undesirable because of the nature of thecontents when approved by the building offi-cial

3 Generator and transformer rooms separatedfrom the remainder of the building by wallsand floorceiling or roofceiling assemblieshaving a fire-resistance rating of not less than2 hours

4 In rooms or areas that are of noncombustibleconstruction with wholly noncombustible con-tents

[F] 903312 NFPA 13R sprinkler systems Where al-lowed in buildings of Group R up to and including fourstories in height automatic sprinkler systems shall be in-stalled throughout in accordance with NFPA 13R

2003 INTERNATIONAL BUILDING CODEreg 167R

FIRE PROTECTION SYSTEMS

gt

gt

gt

09_Phoenix_IBC_2005_PG167pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20824 PM

Color profile Generic CMYK printer profileComposite Default screen

This page left intentionally blank

168R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG168pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20836 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 9033121 Balconies Sprinkler protection shallbe provided for exterior balconies and ground-floorpatios of dwelling units where the building is of TypeV construction Sidewall sprinklers that are used toprotect such areas shall be permitted to be locatedsuch that their deflectors are within 1 inch (25 mm) to6 inches (152 mm) below the structural members anda maximum distance of 14 inches (356 mm) below thedeck of the exterior balconies that are constructed ofopen wood joist construction

[F] 903313 NFPA 13D sprinkler systems Where al-lowed automatic sprinkler systems in one- and two-fam-ily dwellings shall be installed throughout in accordancewith NFPA 13D

[F] 90332 Quick-response and residential sprinklersWhere automatic sprinkler systems are required by thiscode quick-response or residential automatic sprinklersshall be installed in the following areas in accordance withSection 90331 and their listings

1 Throughout all spaces within a smoke compartmentcontaining patient sleeping units in Group I-2 in ac-cordance with this code

2 Dwelling units and sleeping units in Group R and I-1occupancies

3 Light-hazard occupancies as defined in NFPA 13

[F] 90333 Obstructed locations Automatic sprinklersshall be installed with due regard to obstructions that willdelay activation or obstruct the water distribution patternAutomatic sprinklers shall be installed in or under coveredkiosks displays booths concession stands or equipmentthat exceeds 4 feet (1219 mm) in width Not less than a3-foot (914 mm) clearance shall be maintained between au-tomatic sprinklers and the top of piles of combustible fibers

Exception Kitchen equipment under exhaust hoodsprotected with a fire-extinguishing system in accordancewith Section 904

[F] 90334 Actuation Automatic sprinkler systems shallbe automatically actuated unless specifically provided for inthis code

[F] 90335 Water supplies Water supplies for automaticsprinkler systems shall comply with this section and thestandards referenced in Section 90331 The potable watersupply shall be protected against backflow in accordancewith the requirements of this section and the Arizona StatePlumbing Code

[F] 903351 Domestic services Where the domesticservice provides the water supply for the automaticsprinkler system the supply shall be in accordance withthis section

[F] 9033511 Limited area sprinkler systemsLimited area sprinkler systems serving fewer than 20sprinklers on any single connection are permitted tobe connected to the domestic service where a wet au-tomatic standpipe is not available Limited area sprin-kler systems connected to domestic water suppliesshall comply with each of the following requirements

1 Valves shall not be installed between the do-mestic water riser control valve and the sprin-klers

Exception An approved indicating controlvalve supervised in the open position in ac-cordance with Section 9034

2 The domestic service shall be capable of sup-plying the simultaneous domestic demand andthe sprinkler demand required to be hydrauli-cally calculated by NFPA 13 NFPA 13R orNFPA 13D

[F] 9033512 Residential combination services Asingle combination water supply shall be permittedprovided that the domestic demand is added to thesprinkler demand as required by NFPA 13R

[F] 903352 Secondary water supply A secondaryon-site water supply equal to the hydraulically calculatedsprinkler demand including the hose stream require-ment shall be provided for high-rise buildings in Seis-mic Design Category C D E or F as determined by thiscode The secondary water supply shall have a durationnot less than 30 minutes as determined by the occupancyhazard classification in accordance with NFPA 13

Exception Existing buildings

[F] 90336 Hose threads Fire hose threads used in connec-tion with automatic sprinkler systems shall be approved andcompatible with fire department hose threads

[F] 90337 Fire department connections The location offire department connections shall be approved by the build-ing official

[F] 903371 Locking fire department connection(FDC) caps The fire code official is authorized to re-quire locking FDC caps on fire department connectionsfor water-based fire protection systems where the re-sponding fire department carries appropriate keywrenches for removal

[F] 9034 Sprinkler system monitoring and alarms Allvalves controlling the water supply for automatic sprinkler sys-tems pumps tanks water levels and temperatures critical airpressures and water-flow switches on all sprinkler systemsshall be electrically supervised

Exceptions

1 Automatic sprinkler systems protecting one- andtwo-family dwellings

2 Limited area systems serving fewer than 20 sprin-klers

3 Automatic sprinkler systems installed in accordancewith NFPA 13R where a common supply main is usedto supply both domestic water and the automaticsprinkler systems and a separate shutoff valve for theautomatic sprinkler system is not provided

4 Jockey pump control valves that are sealed or lockedin the open position

2003 INTERNATIONAL BUILDING CODEreg 169R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG169pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20847 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Control valves to commercial kitchen hoods paintspray booths or dip tanks that are sealed or locked inthe open position

6 Valves controlling the fuel supply to fire pump en-gines that are sealed or locked in the open position

7 Trim valves to pressure switches in dry preaction anddeluge sprinkler systems that are sealed or locked inthe open position

[F] 90341 Signals Alarm supervisory and trouble signalsshall be distinctly different and automatically transmitted toan approved central station remote supervising station orproprietary supervising station as defined in NFPA 72 orwhen approved by the building official shall sound an audi-ble signal at a constantly attended location

Exceptions

1 Underground key or hub valves in roadway boxesprovided by the municipality or public utility arenot required to be monitored

2 Backflow prevention device test valves located inlimited area sprinkler system supply piping shallbe locked in the open position In occupancies re-quired to be equipped with a fire alarm system thebackflow preventer valves shall be electrically su-pervised by a tamper switch installed in accor-dance with NFPA 72 and separately annunciated

[F] 90342 Alarms Approved audible devices shall beconnected to every automatic sprinkler system Such sprin-kler water-flow alarm devices shall be activated by waterflow equivalent to the flow of a single sprinkler of the small-est orifice size installed in the system Alarm devices shallbe provided on the exterior of the building in an approvedlocation Where a fire alarm system is installed actuation ofthe automatic sprinkler system shall actuate the building firealarm system

[F] 90343 Floor control valves Approved supervised in-dicating control valves shall be provided at the point of con-nection to the riser on each floor in high-rise buildings

[F] 9035 Testing and maintenance Sprinkler systems shallbe tested and maintained in accordance with the Phoenix FireCode

SECTION 904ALTERNATIVE AUTOMATIC

FIRE-EXTINGUISHING SYSTEMS

[F] 9041 General Automatic fire-extinguishing systemsother than automatic sprinkler systems shall be designed in-stalled inspected tested and maintained in accordance withthe provisions of this section and the applicable referencedstandards

[F] 9042 Where required Automatic fire-extinguishing sys-tems installed as an alternative to the required automatic sprin-kler systems of Section 903 shall be approved by the buildingofficial Automatic fire-extinguishing systems shall not beconsidered alternatives for the purposes of exceptions or reduc-tions permitted by other requirements of this code

[F] 90421 Hood system suppression Each required com-mercial kitchen exhaust hood and duct system required bythe Phoenix Fire Code or the International MechanicalCode to have a Type I hood shall be protected with an ap-proved automatic fire-extinguishing system installed in ac-cordance with this code

[F] 9043 Installation Automatic fire-extinguishing systemsshall be installed in accordance with this section

[F] 90431 Electrical wiring Electrical wiring shall be inaccordance with the National Electrical Code

[F] 90432 Actuation Automatic fire-extinguishing sys-tems shall be automatically actuated and provided with amanual means of actuation in accordance with Section904111

[F] 90433 System interlocking Automatic equipment in-terlocks with fuel shutoffs ventilation controls doorclosers window shutters conveyor openings smoke andheat vents and other features necessary for proper operationof the fire-extinguishing system shall be provided as re-quired by the design and installation standard utilized forthe hazard

[F] 90434 Alarms and warning signs Where alarms arerequired to indicate the operation of automatic fire-extin-guishing systems distinctive audible and visible alarms andwarning signs shall be provided to warn of pending agentdischarge Where exposure to automatic-extinguishingagents poses a hazard to persons and a delay is required toensure the evacuation of occupants before agent dischargea separate warning signal shall be provided to alert occu-pants once agent discharge has begun Audible signals shallbe in accordance with Section 90792

[F] 90435 Monitoring Where a building fire alarm sys-tem is installed automatic fire-extinguishing systems shallbe monitored by the building fire alarm system in accor-dance with NFPA 72

[F] 9044 Inspection and testing Automatic fire-extinguish-ing systems shall be inspected and tested in accordance withthe provisions of this section prior to acceptance

[F] 90441 Inspection Prior to conducting final accep-tance tests the following items shall be inspected

1 Hazard specification for consistency with design haz-ard

2 Type location and spacing of automatic- and man-ual-initiating devices

3 Size placement and position of nozzles or dischargeorifices

4 Location and identification of audible and visiblealarm devices

5 Identification of devices with proper designations

6 Operating instructions

[F] 90442 Alarm testing Notification appliances con-nections to fire alarm systems and connections to approvedsupervising stations shall be tested in accordance with thissection and Section 907 to verify proper operation

170R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG170pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20901 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 904421 Audible and visible signals The audibil-ity and visibility of notification appliances signalingagent discharge or system operation where requiredshall be verified

[F] 90443 Monitor testing Connections to protected pre-mises and supervising station fire alarm systems shall betested to verify proper identification and retransmission ofalarms from automatic fire-extinguishing systems

[F] 9045 Wet-chemical systems Wet-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17A and their listing

[F] 9046 Dry-chemical systems Dry-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17 and their listing

[F] 9047 Foam systems Foam-extinguishing systems shall beinstalled maintained periodically inspected and tested in ac-cordance with NFPA 11 and NFPA 16 and their listing

[F] 9048 Carbon dioxide systems Carbon dioxide extin-guishing systems shall be installed maintained periodicallyinspected and tested in accordance with NFPA 12 and their list-ing

[F] 9049 Halon systems Halogenated extinguishing systemsshall be installed maintained periodically inspected and testedin accordance with NFPA 12A and their listing

[F] 90410 Clean-agent systems Clean-agent fire-extinguish-ing systems shall be installed maintained periodically in-spected and tested in accordance with NFPA 2001 and theirlisting

[F] 90411 Commercial cooking systems The automaticfire-extinguishing system for commercial cooking systemsshall be of a type recognized for protection of commercialcooking equipment and exhaust systems of the type and ar-rangement protected Preengineered automatic dry- andwet-chemical extinguishing systems shall be tested in accor-dance with UL 300 and listed and labeled for the intended ap-plication Other types of automatic fire-extinguishing systemsshall be listed and labeled for specific use as protection forcommercial cooking operations The system shall be installedin accordance with this code its listing and the manufacturerrsquosinstallation instructions Automatic fire-extinguishing systemsof the following types shall be installed in accordance with thereferenced standard indicated as shown

1 Carbon dioxide extinguishing systems NFPA 12

2 Automatic sprinkler systems NFPA 13

3 Foam-water sprinkler system or foam-water spray sys-tems NFPA 16

4 Dry-chemical extinguishing systems NFPA 17

5 Wet-chemical extinguishing systems NFPA 17A

Exception Factory-built commercial cooking recirculatingsystems that are tested in accordance with UL 197 andlisted labeled and installed in accordance with Section3041 of the International Mechanical Code

[F] 904111 Manual system operation A manual actua-tion device shall be located at or near a means of egress fromthe cooking area a minimum of 10 feet (3048 mm) and a

maximum of 20 feet (6096 mm) from the kitchen exhaustsystem The manual actuation device shall be located a min-imum of 4 feet (1219 mm) and a maximum of 5 feet (1524mm) above the floor The manual actuation shall require amaximum force of 40 pounds (178 N) and a maximummovement of 14 inches (356 mm) to actuate the fire sup-pression system

Exception Automatic sprinkler systems shall not be re-quired to be equipped with manual actuation means

[F] 904112 System interconnection The actuation of thefire suppression system shall automatically shut down thefuel or electrical power supply to the cooking equipmentThe fuel and electrical supply reset shall be manual

[F] 904113 Carbon dioxide systems When carbon diox-ide systems are used there shall be a nozzle at the top of theventilating duct Additional nozzles that are symmetricallyarranged to give uniform distribution shall be installedwithin vertical ducts exceeding 20 feet (6096 mm) and hori-zontal ducts exceeding 50 feet (15 240 mm) Dampers shallbe installed at either the top or the bottom of the duct andshall be arranged to operate automatically upon activationof the fire-extinguishing system Where the damper is in-stalled at the top of the duct the top nozzle shall be immedi-ately below the damper Automatic carbon dioxidefire-extinguishing systems shall be sufficiently sized to pro-tect against all hazards venting through a common duct si-multaneously

[F] 9041131 Ventilation system Commercial-typecooking equipment protected by an automatic carbon di-oxide-extinguishing system shall be arranged to shut offthe ventilation system upon activation

[F] 904114 Special provisions for automatic sprinklersystems Automatic sprinkler systems protecting commer-cial-type cooking equipment shall be supplied from a sepa-rate readily accessible indicating-type control valve that isidentified

[F] 9041141 Listed sprinklers Sprinklers used forthe protection of fryers shall be listed for that applicationand installed in accordance with their listing

SECTION 905STANDPIPE SYSTEMS

[F] 9051 General Standpipe systems shall be provided in newbuildings and structures in accordance with this section Firehose threads used in connection with standpipe systems shallbe approved and shall be compatible with fire department hosethreads The location of fire department hose connections shallbe approved In buildings used for high-piled combustible stor-age fire protection shall be in accordance with the PhoenixFire Code

[F] 9052 Installation standards Standpipe systems shall beinstalled in accordance with this section and NFPA 14

[F] 9053 Required installations Standpipe systems shall beinstalled where required by Sections 90531 through 90536and in the locations indicated in Sections 9054 9055 and

2003 INTERNATIONAL BUILDING CODEreg 171R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG171pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20954 PM

Color profile Generic CMYK printer profileComposite Default screen

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 5: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

[F] 90323 Rubbish and linen chutes An automatic sprin-kler system shall be installed at the top of rubbish and linenchutes and in their terminal rooms Chutes extendingthrough three or more floors shall have additional sprinklerheads installed within such chutes at alternate floors Chutesprinklers shall be accessible for servicing

[F] 90324 During construction Automatic sprinkler sys-tems required during construction alteration and demoli-tion operations shall be provided in accordance with thePhoenix Fire Code

[F] 90325 Ducts conveying hazardous exhausts Whererequired by the International Mechanical Code automaticsprinklers shall be provided in ducts conveying hazardousexhaust or flammable or combustible materials

Exception Ducts in which the largest cross-sectionaldiameter of the duct is less than 10 inches (254 mm)

[F] 90326 Commercial cooking operations An auto-matic sprinkler system shall be installed in commercialkitchen exhaust hood and duct system where an automaticsprinkler system is used to comply with Section 904

[F] 90327 Other required suppression systems In addi-tion to the requirements of Section 9032 the provisions in-dicated in Table 90327 also require the installation of asuppression system for certain buildings and areas

[F] TABLE 90327ADDITIONAL REQUIRED SUPPRESSION SYSTEMS

SECTION SUBJECT

4028 Covered malls

4032 4033 High-rise buildings

4043 Atriums

4053 Underground structures

4075 Group I-2

4106 Stages

4114 Special amusement buildings

41225 41226 Aircraft hangars

415724 Group H-2

4164 Flammable finishes

4174 Drying rooms

507 Unlimited area buildings

Sprinkler requirements as set forth in thePhoenix Fire Code

[F] 9033 Installation requirements Automatic sprinklersystems shall be designed and installed in accordance withSections 90331 through 90337

[F] 90331 Standards Sprinkler systems shall be designedand installed in accordance with Section 903311903312 or 903313

[F] 903311 NFPA 13 sprinkler systems Where theprovisions of this code require that a building or portionthereof be equipped throughout with an automatic sprin-kler system in accordance with Section 903311 sprin-klers shall be installed throughout in accordance withNFPA 13 except as provided in Section 9033111

[F] 9033111 Exempt locations Automatic sprin-klers shall not be required in the following rooms orareas where such rooms or areas are protected with anapproved automatic fire detection system in accor-dance with Section 9072 that will respond to visibleor invisible particles of combustion Sprinklers shallnot be omitted from any room merely because it isdamp of fire-resistance-rated construction or con-tains electrical equipment

1 Any room where the application of water orflame and water constitutes a serious life or firehazard

2 Any room or space where sprinklers are consid-ered undesirable because of the nature of thecontents when approved by the building offi-cial

3 Generator and transformer rooms separatedfrom the remainder of the building by wallsand floorceiling or roofceiling assemblieshaving a fire-resistance rating of not less than2 hours

4 In rooms or areas that are of noncombustibleconstruction with wholly noncombustible con-tents

[F] 903312 NFPA 13R sprinkler systems Where al-lowed in buildings of Group R up to and including fourstories in height automatic sprinkler systems shall be in-stalled throughout in accordance with NFPA 13R

2003 INTERNATIONAL BUILDING CODEreg 167R

FIRE PROTECTION SYSTEMS

gt

gt

gt

09_Phoenix_IBC_2005_PG167pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20824 PM

Color profile Generic CMYK printer profileComposite Default screen

This page left intentionally blank

168R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG168pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20836 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 9033121 Balconies Sprinkler protection shallbe provided for exterior balconies and ground-floorpatios of dwelling units where the building is of TypeV construction Sidewall sprinklers that are used toprotect such areas shall be permitted to be locatedsuch that their deflectors are within 1 inch (25 mm) to6 inches (152 mm) below the structural members anda maximum distance of 14 inches (356 mm) below thedeck of the exterior balconies that are constructed ofopen wood joist construction

[F] 903313 NFPA 13D sprinkler systems Where al-lowed automatic sprinkler systems in one- and two-fam-ily dwellings shall be installed throughout in accordancewith NFPA 13D

[F] 90332 Quick-response and residential sprinklersWhere automatic sprinkler systems are required by thiscode quick-response or residential automatic sprinklersshall be installed in the following areas in accordance withSection 90331 and their listings

1 Throughout all spaces within a smoke compartmentcontaining patient sleeping units in Group I-2 in ac-cordance with this code

2 Dwelling units and sleeping units in Group R and I-1occupancies

3 Light-hazard occupancies as defined in NFPA 13

[F] 90333 Obstructed locations Automatic sprinklersshall be installed with due regard to obstructions that willdelay activation or obstruct the water distribution patternAutomatic sprinklers shall be installed in or under coveredkiosks displays booths concession stands or equipmentthat exceeds 4 feet (1219 mm) in width Not less than a3-foot (914 mm) clearance shall be maintained between au-tomatic sprinklers and the top of piles of combustible fibers

Exception Kitchen equipment under exhaust hoodsprotected with a fire-extinguishing system in accordancewith Section 904

[F] 90334 Actuation Automatic sprinkler systems shallbe automatically actuated unless specifically provided for inthis code

[F] 90335 Water supplies Water supplies for automaticsprinkler systems shall comply with this section and thestandards referenced in Section 90331 The potable watersupply shall be protected against backflow in accordancewith the requirements of this section and the Arizona StatePlumbing Code

[F] 903351 Domestic services Where the domesticservice provides the water supply for the automaticsprinkler system the supply shall be in accordance withthis section

[F] 9033511 Limited area sprinkler systemsLimited area sprinkler systems serving fewer than 20sprinklers on any single connection are permitted tobe connected to the domestic service where a wet au-tomatic standpipe is not available Limited area sprin-kler systems connected to domestic water suppliesshall comply with each of the following requirements

1 Valves shall not be installed between the do-mestic water riser control valve and the sprin-klers

Exception An approved indicating controlvalve supervised in the open position in ac-cordance with Section 9034

2 The domestic service shall be capable of sup-plying the simultaneous domestic demand andthe sprinkler demand required to be hydrauli-cally calculated by NFPA 13 NFPA 13R orNFPA 13D

[F] 9033512 Residential combination services Asingle combination water supply shall be permittedprovided that the domestic demand is added to thesprinkler demand as required by NFPA 13R

[F] 903352 Secondary water supply A secondaryon-site water supply equal to the hydraulically calculatedsprinkler demand including the hose stream require-ment shall be provided for high-rise buildings in Seis-mic Design Category C D E or F as determined by thiscode The secondary water supply shall have a durationnot less than 30 minutes as determined by the occupancyhazard classification in accordance with NFPA 13

Exception Existing buildings

[F] 90336 Hose threads Fire hose threads used in connec-tion with automatic sprinkler systems shall be approved andcompatible with fire department hose threads

[F] 90337 Fire department connections The location offire department connections shall be approved by the build-ing official

[F] 903371 Locking fire department connection(FDC) caps The fire code official is authorized to re-quire locking FDC caps on fire department connectionsfor water-based fire protection systems where the re-sponding fire department carries appropriate keywrenches for removal

[F] 9034 Sprinkler system monitoring and alarms Allvalves controlling the water supply for automatic sprinkler sys-tems pumps tanks water levels and temperatures critical airpressures and water-flow switches on all sprinkler systemsshall be electrically supervised

Exceptions

1 Automatic sprinkler systems protecting one- andtwo-family dwellings

2 Limited area systems serving fewer than 20 sprin-klers

3 Automatic sprinkler systems installed in accordancewith NFPA 13R where a common supply main is usedto supply both domestic water and the automaticsprinkler systems and a separate shutoff valve for theautomatic sprinkler system is not provided

4 Jockey pump control valves that are sealed or lockedin the open position

2003 INTERNATIONAL BUILDING CODEreg 169R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG169pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20847 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Control valves to commercial kitchen hoods paintspray booths or dip tanks that are sealed or locked inthe open position

6 Valves controlling the fuel supply to fire pump en-gines that are sealed or locked in the open position

7 Trim valves to pressure switches in dry preaction anddeluge sprinkler systems that are sealed or locked inthe open position

[F] 90341 Signals Alarm supervisory and trouble signalsshall be distinctly different and automatically transmitted toan approved central station remote supervising station orproprietary supervising station as defined in NFPA 72 orwhen approved by the building official shall sound an audi-ble signal at a constantly attended location

Exceptions

1 Underground key or hub valves in roadway boxesprovided by the municipality or public utility arenot required to be monitored

2 Backflow prevention device test valves located inlimited area sprinkler system supply piping shallbe locked in the open position In occupancies re-quired to be equipped with a fire alarm system thebackflow preventer valves shall be electrically su-pervised by a tamper switch installed in accor-dance with NFPA 72 and separately annunciated

[F] 90342 Alarms Approved audible devices shall beconnected to every automatic sprinkler system Such sprin-kler water-flow alarm devices shall be activated by waterflow equivalent to the flow of a single sprinkler of the small-est orifice size installed in the system Alarm devices shallbe provided on the exterior of the building in an approvedlocation Where a fire alarm system is installed actuation ofthe automatic sprinkler system shall actuate the building firealarm system

[F] 90343 Floor control valves Approved supervised in-dicating control valves shall be provided at the point of con-nection to the riser on each floor in high-rise buildings

[F] 9035 Testing and maintenance Sprinkler systems shallbe tested and maintained in accordance with the Phoenix FireCode

SECTION 904ALTERNATIVE AUTOMATIC

FIRE-EXTINGUISHING SYSTEMS

[F] 9041 General Automatic fire-extinguishing systemsother than automatic sprinkler systems shall be designed in-stalled inspected tested and maintained in accordance withthe provisions of this section and the applicable referencedstandards

[F] 9042 Where required Automatic fire-extinguishing sys-tems installed as an alternative to the required automatic sprin-kler systems of Section 903 shall be approved by the buildingofficial Automatic fire-extinguishing systems shall not beconsidered alternatives for the purposes of exceptions or reduc-tions permitted by other requirements of this code

[F] 90421 Hood system suppression Each required com-mercial kitchen exhaust hood and duct system required bythe Phoenix Fire Code or the International MechanicalCode to have a Type I hood shall be protected with an ap-proved automatic fire-extinguishing system installed in ac-cordance with this code

[F] 9043 Installation Automatic fire-extinguishing systemsshall be installed in accordance with this section

[F] 90431 Electrical wiring Electrical wiring shall be inaccordance with the National Electrical Code

[F] 90432 Actuation Automatic fire-extinguishing sys-tems shall be automatically actuated and provided with amanual means of actuation in accordance with Section904111

[F] 90433 System interlocking Automatic equipment in-terlocks with fuel shutoffs ventilation controls doorclosers window shutters conveyor openings smoke andheat vents and other features necessary for proper operationof the fire-extinguishing system shall be provided as re-quired by the design and installation standard utilized forthe hazard

[F] 90434 Alarms and warning signs Where alarms arerequired to indicate the operation of automatic fire-extin-guishing systems distinctive audible and visible alarms andwarning signs shall be provided to warn of pending agentdischarge Where exposure to automatic-extinguishingagents poses a hazard to persons and a delay is required toensure the evacuation of occupants before agent dischargea separate warning signal shall be provided to alert occu-pants once agent discharge has begun Audible signals shallbe in accordance with Section 90792

[F] 90435 Monitoring Where a building fire alarm sys-tem is installed automatic fire-extinguishing systems shallbe monitored by the building fire alarm system in accor-dance with NFPA 72

[F] 9044 Inspection and testing Automatic fire-extinguish-ing systems shall be inspected and tested in accordance withthe provisions of this section prior to acceptance

[F] 90441 Inspection Prior to conducting final accep-tance tests the following items shall be inspected

1 Hazard specification for consistency with design haz-ard

2 Type location and spacing of automatic- and man-ual-initiating devices

3 Size placement and position of nozzles or dischargeorifices

4 Location and identification of audible and visiblealarm devices

5 Identification of devices with proper designations

6 Operating instructions

[F] 90442 Alarm testing Notification appliances con-nections to fire alarm systems and connections to approvedsupervising stations shall be tested in accordance with thissection and Section 907 to verify proper operation

170R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG170pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20901 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 904421 Audible and visible signals The audibil-ity and visibility of notification appliances signalingagent discharge or system operation where requiredshall be verified

[F] 90443 Monitor testing Connections to protected pre-mises and supervising station fire alarm systems shall betested to verify proper identification and retransmission ofalarms from automatic fire-extinguishing systems

[F] 9045 Wet-chemical systems Wet-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17A and their listing

[F] 9046 Dry-chemical systems Dry-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17 and their listing

[F] 9047 Foam systems Foam-extinguishing systems shall beinstalled maintained periodically inspected and tested in ac-cordance with NFPA 11 and NFPA 16 and their listing

[F] 9048 Carbon dioxide systems Carbon dioxide extin-guishing systems shall be installed maintained periodicallyinspected and tested in accordance with NFPA 12 and their list-ing

[F] 9049 Halon systems Halogenated extinguishing systemsshall be installed maintained periodically inspected and testedin accordance with NFPA 12A and their listing

[F] 90410 Clean-agent systems Clean-agent fire-extinguish-ing systems shall be installed maintained periodically in-spected and tested in accordance with NFPA 2001 and theirlisting

[F] 90411 Commercial cooking systems The automaticfire-extinguishing system for commercial cooking systemsshall be of a type recognized for protection of commercialcooking equipment and exhaust systems of the type and ar-rangement protected Preengineered automatic dry- andwet-chemical extinguishing systems shall be tested in accor-dance with UL 300 and listed and labeled for the intended ap-plication Other types of automatic fire-extinguishing systemsshall be listed and labeled for specific use as protection forcommercial cooking operations The system shall be installedin accordance with this code its listing and the manufacturerrsquosinstallation instructions Automatic fire-extinguishing systemsof the following types shall be installed in accordance with thereferenced standard indicated as shown

1 Carbon dioxide extinguishing systems NFPA 12

2 Automatic sprinkler systems NFPA 13

3 Foam-water sprinkler system or foam-water spray sys-tems NFPA 16

4 Dry-chemical extinguishing systems NFPA 17

5 Wet-chemical extinguishing systems NFPA 17A

Exception Factory-built commercial cooking recirculatingsystems that are tested in accordance with UL 197 andlisted labeled and installed in accordance with Section3041 of the International Mechanical Code

[F] 904111 Manual system operation A manual actua-tion device shall be located at or near a means of egress fromthe cooking area a minimum of 10 feet (3048 mm) and a

maximum of 20 feet (6096 mm) from the kitchen exhaustsystem The manual actuation device shall be located a min-imum of 4 feet (1219 mm) and a maximum of 5 feet (1524mm) above the floor The manual actuation shall require amaximum force of 40 pounds (178 N) and a maximummovement of 14 inches (356 mm) to actuate the fire sup-pression system

Exception Automatic sprinkler systems shall not be re-quired to be equipped with manual actuation means

[F] 904112 System interconnection The actuation of thefire suppression system shall automatically shut down thefuel or electrical power supply to the cooking equipmentThe fuel and electrical supply reset shall be manual

[F] 904113 Carbon dioxide systems When carbon diox-ide systems are used there shall be a nozzle at the top of theventilating duct Additional nozzles that are symmetricallyarranged to give uniform distribution shall be installedwithin vertical ducts exceeding 20 feet (6096 mm) and hori-zontal ducts exceeding 50 feet (15 240 mm) Dampers shallbe installed at either the top or the bottom of the duct andshall be arranged to operate automatically upon activationof the fire-extinguishing system Where the damper is in-stalled at the top of the duct the top nozzle shall be immedi-ately below the damper Automatic carbon dioxidefire-extinguishing systems shall be sufficiently sized to pro-tect against all hazards venting through a common duct si-multaneously

[F] 9041131 Ventilation system Commercial-typecooking equipment protected by an automatic carbon di-oxide-extinguishing system shall be arranged to shut offthe ventilation system upon activation

[F] 904114 Special provisions for automatic sprinklersystems Automatic sprinkler systems protecting commer-cial-type cooking equipment shall be supplied from a sepa-rate readily accessible indicating-type control valve that isidentified

[F] 9041141 Listed sprinklers Sprinklers used forthe protection of fryers shall be listed for that applicationand installed in accordance with their listing

SECTION 905STANDPIPE SYSTEMS

[F] 9051 General Standpipe systems shall be provided in newbuildings and structures in accordance with this section Firehose threads used in connection with standpipe systems shallbe approved and shall be compatible with fire department hosethreads The location of fire department hose connections shallbe approved In buildings used for high-piled combustible stor-age fire protection shall be in accordance with the PhoenixFire Code

[F] 9052 Installation standards Standpipe systems shall beinstalled in accordance with this section and NFPA 14

[F] 9053 Required installations Standpipe systems shall beinstalled where required by Sections 90531 through 90536and in the locations indicated in Sections 9054 9055 and

2003 INTERNATIONAL BUILDING CODEreg 171R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG171pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20954 PM

Color profile Generic CMYK printer profileComposite Default screen

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 6: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

This page left intentionally blank

168R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG168pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20836 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 9033121 Balconies Sprinkler protection shallbe provided for exterior balconies and ground-floorpatios of dwelling units where the building is of TypeV construction Sidewall sprinklers that are used toprotect such areas shall be permitted to be locatedsuch that their deflectors are within 1 inch (25 mm) to6 inches (152 mm) below the structural members anda maximum distance of 14 inches (356 mm) below thedeck of the exterior balconies that are constructed ofopen wood joist construction

[F] 903313 NFPA 13D sprinkler systems Where al-lowed automatic sprinkler systems in one- and two-fam-ily dwellings shall be installed throughout in accordancewith NFPA 13D

[F] 90332 Quick-response and residential sprinklersWhere automatic sprinkler systems are required by thiscode quick-response or residential automatic sprinklersshall be installed in the following areas in accordance withSection 90331 and their listings

1 Throughout all spaces within a smoke compartmentcontaining patient sleeping units in Group I-2 in ac-cordance with this code

2 Dwelling units and sleeping units in Group R and I-1occupancies

3 Light-hazard occupancies as defined in NFPA 13

[F] 90333 Obstructed locations Automatic sprinklersshall be installed with due regard to obstructions that willdelay activation or obstruct the water distribution patternAutomatic sprinklers shall be installed in or under coveredkiosks displays booths concession stands or equipmentthat exceeds 4 feet (1219 mm) in width Not less than a3-foot (914 mm) clearance shall be maintained between au-tomatic sprinklers and the top of piles of combustible fibers

Exception Kitchen equipment under exhaust hoodsprotected with a fire-extinguishing system in accordancewith Section 904

[F] 90334 Actuation Automatic sprinkler systems shallbe automatically actuated unless specifically provided for inthis code

[F] 90335 Water supplies Water supplies for automaticsprinkler systems shall comply with this section and thestandards referenced in Section 90331 The potable watersupply shall be protected against backflow in accordancewith the requirements of this section and the Arizona StatePlumbing Code

[F] 903351 Domestic services Where the domesticservice provides the water supply for the automaticsprinkler system the supply shall be in accordance withthis section

[F] 9033511 Limited area sprinkler systemsLimited area sprinkler systems serving fewer than 20sprinklers on any single connection are permitted tobe connected to the domestic service where a wet au-tomatic standpipe is not available Limited area sprin-kler systems connected to domestic water suppliesshall comply with each of the following requirements

1 Valves shall not be installed between the do-mestic water riser control valve and the sprin-klers

Exception An approved indicating controlvalve supervised in the open position in ac-cordance with Section 9034

2 The domestic service shall be capable of sup-plying the simultaneous domestic demand andthe sprinkler demand required to be hydrauli-cally calculated by NFPA 13 NFPA 13R orNFPA 13D

[F] 9033512 Residential combination services Asingle combination water supply shall be permittedprovided that the domestic demand is added to thesprinkler demand as required by NFPA 13R

[F] 903352 Secondary water supply A secondaryon-site water supply equal to the hydraulically calculatedsprinkler demand including the hose stream require-ment shall be provided for high-rise buildings in Seis-mic Design Category C D E or F as determined by thiscode The secondary water supply shall have a durationnot less than 30 minutes as determined by the occupancyhazard classification in accordance with NFPA 13

Exception Existing buildings

[F] 90336 Hose threads Fire hose threads used in connec-tion with automatic sprinkler systems shall be approved andcompatible with fire department hose threads

[F] 90337 Fire department connections The location offire department connections shall be approved by the build-ing official

[F] 903371 Locking fire department connection(FDC) caps The fire code official is authorized to re-quire locking FDC caps on fire department connectionsfor water-based fire protection systems where the re-sponding fire department carries appropriate keywrenches for removal

[F] 9034 Sprinkler system monitoring and alarms Allvalves controlling the water supply for automatic sprinkler sys-tems pumps tanks water levels and temperatures critical airpressures and water-flow switches on all sprinkler systemsshall be electrically supervised

Exceptions

1 Automatic sprinkler systems protecting one- andtwo-family dwellings

2 Limited area systems serving fewer than 20 sprin-klers

3 Automatic sprinkler systems installed in accordancewith NFPA 13R where a common supply main is usedto supply both domestic water and the automaticsprinkler systems and a separate shutoff valve for theautomatic sprinkler system is not provided

4 Jockey pump control valves that are sealed or lockedin the open position

2003 INTERNATIONAL BUILDING CODEreg 169R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG169pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20847 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Control valves to commercial kitchen hoods paintspray booths or dip tanks that are sealed or locked inthe open position

6 Valves controlling the fuel supply to fire pump en-gines that are sealed or locked in the open position

7 Trim valves to pressure switches in dry preaction anddeluge sprinkler systems that are sealed or locked inthe open position

[F] 90341 Signals Alarm supervisory and trouble signalsshall be distinctly different and automatically transmitted toan approved central station remote supervising station orproprietary supervising station as defined in NFPA 72 orwhen approved by the building official shall sound an audi-ble signal at a constantly attended location

Exceptions

1 Underground key or hub valves in roadway boxesprovided by the municipality or public utility arenot required to be monitored

2 Backflow prevention device test valves located inlimited area sprinkler system supply piping shallbe locked in the open position In occupancies re-quired to be equipped with a fire alarm system thebackflow preventer valves shall be electrically su-pervised by a tamper switch installed in accor-dance with NFPA 72 and separately annunciated

[F] 90342 Alarms Approved audible devices shall beconnected to every automatic sprinkler system Such sprin-kler water-flow alarm devices shall be activated by waterflow equivalent to the flow of a single sprinkler of the small-est orifice size installed in the system Alarm devices shallbe provided on the exterior of the building in an approvedlocation Where a fire alarm system is installed actuation ofthe automatic sprinkler system shall actuate the building firealarm system

[F] 90343 Floor control valves Approved supervised in-dicating control valves shall be provided at the point of con-nection to the riser on each floor in high-rise buildings

[F] 9035 Testing and maintenance Sprinkler systems shallbe tested and maintained in accordance with the Phoenix FireCode

SECTION 904ALTERNATIVE AUTOMATIC

FIRE-EXTINGUISHING SYSTEMS

[F] 9041 General Automatic fire-extinguishing systemsother than automatic sprinkler systems shall be designed in-stalled inspected tested and maintained in accordance withthe provisions of this section and the applicable referencedstandards

[F] 9042 Where required Automatic fire-extinguishing sys-tems installed as an alternative to the required automatic sprin-kler systems of Section 903 shall be approved by the buildingofficial Automatic fire-extinguishing systems shall not beconsidered alternatives for the purposes of exceptions or reduc-tions permitted by other requirements of this code

[F] 90421 Hood system suppression Each required com-mercial kitchen exhaust hood and duct system required bythe Phoenix Fire Code or the International MechanicalCode to have a Type I hood shall be protected with an ap-proved automatic fire-extinguishing system installed in ac-cordance with this code

[F] 9043 Installation Automatic fire-extinguishing systemsshall be installed in accordance with this section

[F] 90431 Electrical wiring Electrical wiring shall be inaccordance with the National Electrical Code

[F] 90432 Actuation Automatic fire-extinguishing sys-tems shall be automatically actuated and provided with amanual means of actuation in accordance with Section904111

[F] 90433 System interlocking Automatic equipment in-terlocks with fuel shutoffs ventilation controls doorclosers window shutters conveyor openings smoke andheat vents and other features necessary for proper operationof the fire-extinguishing system shall be provided as re-quired by the design and installation standard utilized forthe hazard

[F] 90434 Alarms and warning signs Where alarms arerequired to indicate the operation of automatic fire-extin-guishing systems distinctive audible and visible alarms andwarning signs shall be provided to warn of pending agentdischarge Where exposure to automatic-extinguishingagents poses a hazard to persons and a delay is required toensure the evacuation of occupants before agent dischargea separate warning signal shall be provided to alert occu-pants once agent discharge has begun Audible signals shallbe in accordance with Section 90792

[F] 90435 Monitoring Where a building fire alarm sys-tem is installed automatic fire-extinguishing systems shallbe monitored by the building fire alarm system in accor-dance with NFPA 72

[F] 9044 Inspection and testing Automatic fire-extinguish-ing systems shall be inspected and tested in accordance withthe provisions of this section prior to acceptance

[F] 90441 Inspection Prior to conducting final accep-tance tests the following items shall be inspected

1 Hazard specification for consistency with design haz-ard

2 Type location and spacing of automatic- and man-ual-initiating devices

3 Size placement and position of nozzles or dischargeorifices

4 Location and identification of audible and visiblealarm devices

5 Identification of devices with proper designations

6 Operating instructions

[F] 90442 Alarm testing Notification appliances con-nections to fire alarm systems and connections to approvedsupervising stations shall be tested in accordance with thissection and Section 907 to verify proper operation

170R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG170pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20901 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 904421 Audible and visible signals The audibil-ity and visibility of notification appliances signalingagent discharge or system operation where requiredshall be verified

[F] 90443 Monitor testing Connections to protected pre-mises and supervising station fire alarm systems shall betested to verify proper identification and retransmission ofalarms from automatic fire-extinguishing systems

[F] 9045 Wet-chemical systems Wet-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17A and their listing

[F] 9046 Dry-chemical systems Dry-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17 and their listing

[F] 9047 Foam systems Foam-extinguishing systems shall beinstalled maintained periodically inspected and tested in ac-cordance with NFPA 11 and NFPA 16 and their listing

[F] 9048 Carbon dioxide systems Carbon dioxide extin-guishing systems shall be installed maintained periodicallyinspected and tested in accordance with NFPA 12 and their list-ing

[F] 9049 Halon systems Halogenated extinguishing systemsshall be installed maintained periodically inspected and testedin accordance with NFPA 12A and their listing

[F] 90410 Clean-agent systems Clean-agent fire-extinguish-ing systems shall be installed maintained periodically in-spected and tested in accordance with NFPA 2001 and theirlisting

[F] 90411 Commercial cooking systems The automaticfire-extinguishing system for commercial cooking systemsshall be of a type recognized for protection of commercialcooking equipment and exhaust systems of the type and ar-rangement protected Preengineered automatic dry- andwet-chemical extinguishing systems shall be tested in accor-dance with UL 300 and listed and labeled for the intended ap-plication Other types of automatic fire-extinguishing systemsshall be listed and labeled for specific use as protection forcommercial cooking operations The system shall be installedin accordance with this code its listing and the manufacturerrsquosinstallation instructions Automatic fire-extinguishing systemsof the following types shall be installed in accordance with thereferenced standard indicated as shown

1 Carbon dioxide extinguishing systems NFPA 12

2 Automatic sprinkler systems NFPA 13

3 Foam-water sprinkler system or foam-water spray sys-tems NFPA 16

4 Dry-chemical extinguishing systems NFPA 17

5 Wet-chemical extinguishing systems NFPA 17A

Exception Factory-built commercial cooking recirculatingsystems that are tested in accordance with UL 197 andlisted labeled and installed in accordance with Section3041 of the International Mechanical Code

[F] 904111 Manual system operation A manual actua-tion device shall be located at or near a means of egress fromthe cooking area a minimum of 10 feet (3048 mm) and a

maximum of 20 feet (6096 mm) from the kitchen exhaustsystem The manual actuation device shall be located a min-imum of 4 feet (1219 mm) and a maximum of 5 feet (1524mm) above the floor The manual actuation shall require amaximum force of 40 pounds (178 N) and a maximummovement of 14 inches (356 mm) to actuate the fire sup-pression system

Exception Automatic sprinkler systems shall not be re-quired to be equipped with manual actuation means

[F] 904112 System interconnection The actuation of thefire suppression system shall automatically shut down thefuel or electrical power supply to the cooking equipmentThe fuel and electrical supply reset shall be manual

[F] 904113 Carbon dioxide systems When carbon diox-ide systems are used there shall be a nozzle at the top of theventilating duct Additional nozzles that are symmetricallyarranged to give uniform distribution shall be installedwithin vertical ducts exceeding 20 feet (6096 mm) and hori-zontal ducts exceeding 50 feet (15 240 mm) Dampers shallbe installed at either the top or the bottom of the duct andshall be arranged to operate automatically upon activationof the fire-extinguishing system Where the damper is in-stalled at the top of the duct the top nozzle shall be immedi-ately below the damper Automatic carbon dioxidefire-extinguishing systems shall be sufficiently sized to pro-tect against all hazards venting through a common duct si-multaneously

[F] 9041131 Ventilation system Commercial-typecooking equipment protected by an automatic carbon di-oxide-extinguishing system shall be arranged to shut offthe ventilation system upon activation

[F] 904114 Special provisions for automatic sprinklersystems Automatic sprinkler systems protecting commer-cial-type cooking equipment shall be supplied from a sepa-rate readily accessible indicating-type control valve that isidentified

[F] 9041141 Listed sprinklers Sprinklers used forthe protection of fryers shall be listed for that applicationand installed in accordance with their listing

SECTION 905STANDPIPE SYSTEMS

[F] 9051 General Standpipe systems shall be provided in newbuildings and structures in accordance with this section Firehose threads used in connection with standpipe systems shallbe approved and shall be compatible with fire department hosethreads The location of fire department hose connections shallbe approved In buildings used for high-piled combustible stor-age fire protection shall be in accordance with the PhoenixFire Code

[F] 9052 Installation standards Standpipe systems shall beinstalled in accordance with this section and NFPA 14

[F] 9053 Required installations Standpipe systems shall beinstalled where required by Sections 90531 through 90536and in the locations indicated in Sections 9054 9055 and

2003 INTERNATIONAL BUILDING CODEreg 171R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG171pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20954 PM

Color profile Generic CMYK printer profileComposite Default screen

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 7: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

[F] 9033121 Balconies Sprinkler protection shallbe provided for exterior balconies and ground-floorpatios of dwelling units where the building is of TypeV construction Sidewall sprinklers that are used toprotect such areas shall be permitted to be locatedsuch that their deflectors are within 1 inch (25 mm) to6 inches (152 mm) below the structural members anda maximum distance of 14 inches (356 mm) below thedeck of the exterior balconies that are constructed ofopen wood joist construction

[F] 903313 NFPA 13D sprinkler systems Where al-lowed automatic sprinkler systems in one- and two-fam-ily dwellings shall be installed throughout in accordancewith NFPA 13D

[F] 90332 Quick-response and residential sprinklersWhere automatic sprinkler systems are required by thiscode quick-response or residential automatic sprinklersshall be installed in the following areas in accordance withSection 90331 and their listings

1 Throughout all spaces within a smoke compartmentcontaining patient sleeping units in Group I-2 in ac-cordance with this code

2 Dwelling units and sleeping units in Group R and I-1occupancies

3 Light-hazard occupancies as defined in NFPA 13

[F] 90333 Obstructed locations Automatic sprinklersshall be installed with due regard to obstructions that willdelay activation or obstruct the water distribution patternAutomatic sprinklers shall be installed in or under coveredkiosks displays booths concession stands or equipmentthat exceeds 4 feet (1219 mm) in width Not less than a3-foot (914 mm) clearance shall be maintained between au-tomatic sprinklers and the top of piles of combustible fibers

Exception Kitchen equipment under exhaust hoodsprotected with a fire-extinguishing system in accordancewith Section 904

[F] 90334 Actuation Automatic sprinkler systems shallbe automatically actuated unless specifically provided for inthis code

[F] 90335 Water supplies Water supplies for automaticsprinkler systems shall comply with this section and thestandards referenced in Section 90331 The potable watersupply shall be protected against backflow in accordancewith the requirements of this section and the Arizona StatePlumbing Code

[F] 903351 Domestic services Where the domesticservice provides the water supply for the automaticsprinkler system the supply shall be in accordance withthis section

[F] 9033511 Limited area sprinkler systemsLimited area sprinkler systems serving fewer than 20sprinklers on any single connection are permitted tobe connected to the domestic service where a wet au-tomatic standpipe is not available Limited area sprin-kler systems connected to domestic water suppliesshall comply with each of the following requirements

1 Valves shall not be installed between the do-mestic water riser control valve and the sprin-klers

Exception An approved indicating controlvalve supervised in the open position in ac-cordance with Section 9034

2 The domestic service shall be capable of sup-plying the simultaneous domestic demand andthe sprinkler demand required to be hydrauli-cally calculated by NFPA 13 NFPA 13R orNFPA 13D

[F] 9033512 Residential combination services Asingle combination water supply shall be permittedprovided that the domestic demand is added to thesprinkler demand as required by NFPA 13R

[F] 903352 Secondary water supply A secondaryon-site water supply equal to the hydraulically calculatedsprinkler demand including the hose stream require-ment shall be provided for high-rise buildings in Seis-mic Design Category C D E or F as determined by thiscode The secondary water supply shall have a durationnot less than 30 minutes as determined by the occupancyhazard classification in accordance with NFPA 13

Exception Existing buildings

[F] 90336 Hose threads Fire hose threads used in connec-tion with automatic sprinkler systems shall be approved andcompatible with fire department hose threads

[F] 90337 Fire department connections The location offire department connections shall be approved by the build-ing official

[F] 903371 Locking fire department connection(FDC) caps The fire code official is authorized to re-quire locking FDC caps on fire department connectionsfor water-based fire protection systems where the re-sponding fire department carries appropriate keywrenches for removal

[F] 9034 Sprinkler system monitoring and alarms Allvalves controlling the water supply for automatic sprinkler sys-tems pumps tanks water levels and temperatures critical airpressures and water-flow switches on all sprinkler systemsshall be electrically supervised

Exceptions

1 Automatic sprinkler systems protecting one- andtwo-family dwellings

2 Limited area systems serving fewer than 20 sprin-klers

3 Automatic sprinkler systems installed in accordancewith NFPA 13R where a common supply main is usedto supply both domestic water and the automaticsprinkler systems and a separate shutoff valve for theautomatic sprinkler system is not provided

4 Jockey pump control valves that are sealed or lockedin the open position

2003 INTERNATIONAL BUILDING CODEreg 169R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG169pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20847 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Control valves to commercial kitchen hoods paintspray booths or dip tanks that are sealed or locked inthe open position

6 Valves controlling the fuel supply to fire pump en-gines that are sealed or locked in the open position

7 Trim valves to pressure switches in dry preaction anddeluge sprinkler systems that are sealed or locked inthe open position

[F] 90341 Signals Alarm supervisory and trouble signalsshall be distinctly different and automatically transmitted toan approved central station remote supervising station orproprietary supervising station as defined in NFPA 72 orwhen approved by the building official shall sound an audi-ble signal at a constantly attended location

Exceptions

1 Underground key or hub valves in roadway boxesprovided by the municipality or public utility arenot required to be monitored

2 Backflow prevention device test valves located inlimited area sprinkler system supply piping shallbe locked in the open position In occupancies re-quired to be equipped with a fire alarm system thebackflow preventer valves shall be electrically su-pervised by a tamper switch installed in accor-dance with NFPA 72 and separately annunciated

[F] 90342 Alarms Approved audible devices shall beconnected to every automatic sprinkler system Such sprin-kler water-flow alarm devices shall be activated by waterflow equivalent to the flow of a single sprinkler of the small-est orifice size installed in the system Alarm devices shallbe provided on the exterior of the building in an approvedlocation Where a fire alarm system is installed actuation ofthe automatic sprinkler system shall actuate the building firealarm system

[F] 90343 Floor control valves Approved supervised in-dicating control valves shall be provided at the point of con-nection to the riser on each floor in high-rise buildings

[F] 9035 Testing and maintenance Sprinkler systems shallbe tested and maintained in accordance with the Phoenix FireCode

SECTION 904ALTERNATIVE AUTOMATIC

FIRE-EXTINGUISHING SYSTEMS

[F] 9041 General Automatic fire-extinguishing systemsother than automatic sprinkler systems shall be designed in-stalled inspected tested and maintained in accordance withthe provisions of this section and the applicable referencedstandards

[F] 9042 Where required Automatic fire-extinguishing sys-tems installed as an alternative to the required automatic sprin-kler systems of Section 903 shall be approved by the buildingofficial Automatic fire-extinguishing systems shall not beconsidered alternatives for the purposes of exceptions or reduc-tions permitted by other requirements of this code

[F] 90421 Hood system suppression Each required com-mercial kitchen exhaust hood and duct system required bythe Phoenix Fire Code or the International MechanicalCode to have a Type I hood shall be protected with an ap-proved automatic fire-extinguishing system installed in ac-cordance with this code

[F] 9043 Installation Automatic fire-extinguishing systemsshall be installed in accordance with this section

[F] 90431 Electrical wiring Electrical wiring shall be inaccordance with the National Electrical Code

[F] 90432 Actuation Automatic fire-extinguishing sys-tems shall be automatically actuated and provided with amanual means of actuation in accordance with Section904111

[F] 90433 System interlocking Automatic equipment in-terlocks with fuel shutoffs ventilation controls doorclosers window shutters conveyor openings smoke andheat vents and other features necessary for proper operationof the fire-extinguishing system shall be provided as re-quired by the design and installation standard utilized forthe hazard

[F] 90434 Alarms and warning signs Where alarms arerequired to indicate the operation of automatic fire-extin-guishing systems distinctive audible and visible alarms andwarning signs shall be provided to warn of pending agentdischarge Where exposure to automatic-extinguishingagents poses a hazard to persons and a delay is required toensure the evacuation of occupants before agent dischargea separate warning signal shall be provided to alert occu-pants once agent discharge has begun Audible signals shallbe in accordance with Section 90792

[F] 90435 Monitoring Where a building fire alarm sys-tem is installed automatic fire-extinguishing systems shallbe monitored by the building fire alarm system in accor-dance with NFPA 72

[F] 9044 Inspection and testing Automatic fire-extinguish-ing systems shall be inspected and tested in accordance withthe provisions of this section prior to acceptance

[F] 90441 Inspection Prior to conducting final accep-tance tests the following items shall be inspected

1 Hazard specification for consistency with design haz-ard

2 Type location and spacing of automatic- and man-ual-initiating devices

3 Size placement and position of nozzles or dischargeorifices

4 Location and identification of audible and visiblealarm devices

5 Identification of devices with proper designations

6 Operating instructions

[F] 90442 Alarm testing Notification appliances con-nections to fire alarm systems and connections to approvedsupervising stations shall be tested in accordance with thissection and Section 907 to verify proper operation

170R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG170pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20901 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 904421 Audible and visible signals The audibil-ity and visibility of notification appliances signalingagent discharge or system operation where requiredshall be verified

[F] 90443 Monitor testing Connections to protected pre-mises and supervising station fire alarm systems shall betested to verify proper identification and retransmission ofalarms from automatic fire-extinguishing systems

[F] 9045 Wet-chemical systems Wet-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17A and their listing

[F] 9046 Dry-chemical systems Dry-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17 and their listing

[F] 9047 Foam systems Foam-extinguishing systems shall beinstalled maintained periodically inspected and tested in ac-cordance with NFPA 11 and NFPA 16 and their listing

[F] 9048 Carbon dioxide systems Carbon dioxide extin-guishing systems shall be installed maintained periodicallyinspected and tested in accordance with NFPA 12 and their list-ing

[F] 9049 Halon systems Halogenated extinguishing systemsshall be installed maintained periodically inspected and testedin accordance with NFPA 12A and their listing

[F] 90410 Clean-agent systems Clean-agent fire-extinguish-ing systems shall be installed maintained periodically in-spected and tested in accordance with NFPA 2001 and theirlisting

[F] 90411 Commercial cooking systems The automaticfire-extinguishing system for commercial cooking systemsshall be of a type recognized for protection of commercialcooking equipment and exhaust systems of the type and ar-rangement protected Preengineered automatic dry- andwet-chemical extinguishing systems shall be tested in accor-dance with UL 300 and listed and labeled for the intended ap-plication Other types of automatic fire-extinguishing systemsshall be listed and labeled for specific use as protection forcommercial cooking operations The system shall be installedin accordance with this code its listing and the manufacturerrsquosinstallation instructions Automatic fire-extinguishing systemsof the following types shall be installed in accordance with thereferenced standard indicated as shown

1 Carbon dioxide extinguishing systems NFPA 12

2 Automatic sprinkler systems NFPA 13

3 Foam-water sprinkler system or foam-water spray sys-tems NFPA 16

4 Dry-chemical extinguishing systems NFPA 17

5 Wet-chemical extinguishing systems NFPA 17A

Exception Factory-built commercial cooking recirculatingsystems that are tested in accordance with UL 197 andlisted labeled and installed in accordance with Section3041 of the International Mechanical Code

[F] 904111 Manual system operation A manual actua-tion device shall be located at or near a means of egress fromthe cooking area a minimum of 10 feet (3048 mm) and a

maximum of 20 feet (6096 mm) from the kitchen exhaustsystem The manual actuation device shall be located a min-imum of 4 feet (1219 mm) and a maximum of 5 feet (1524mm) above the floor The manual actuation shall require amaximum force of 40 pounds (178 N) and a maximummovement of 14 inches (356 mm) to actuate the fire sup-pression system

Exception Automatic sprinkler systems shall not be re-quired to be equipped with manual actuation means

[F] 904112 System interconnection The actuation of thefire suppression system shall automatically shut down thefuel or electrical power supply to the cooking equipmentThe fuel and electrical supply reset shall be manual

[F] 904113 Carbon dioxide systems When carbon diox-ide systems are used there shall be a nozzle at the top of theventilating duct Additional nozzles that are symmetricallyarranged to give uniform distribution shall be installedwithin vertical ducts exceeding 20 feet (6096 mm) and hori-zontal ducts exceeding 50 feet (15 240 mm) Dampers shallbe installed at either the top or the bottom of the duct andshall be arranged to operate automatically upon activationof the fire-extinguishing system Where the damper is in-stalled at the top of the duct the top nozzle shall be immedi-ately below the damper Automatic carbon dioxidefire-extinguishing systems shall be sufficiently sized to pro-tect against all hazards venting through a common duct si-multaneously

[F] 9041131 Ventilation system Commercial-typecooking equipment protected by an automatic carbon di-oxide-extinguishing system shall be arranged to shut offthe ventilation system upon activation

[F] 904114 Special provisions for automatic sprinklersystems Automatic sprinkler systems protecting commer-cial-type cooking equipment shall be supplied from a sepa-rate readily accessible indicating-type control valve that isidentified

[F] 9041141 Listed sprinklers Sprinklers used forthe protection of fryers shall be listed for that applicationand installed in accordance with their listing

SECTION 905STANDPIPE SYSTEMS

[F] 9051 General Standpipe systems shall be provided in newbuildings and structures in accordance with this section Firehose threads used in connection with standpipe systems shallbe approved and shall be compatible with fire department hosethreads The location of fire department hose connections shallbe approved In buildings used for high-piled combustible stor-age fire protection shall be in accordance with the PhoenixFire Code

[F] 9052 Installation standards Standpipe systems shall beinstalled in accordance with this section and NFPA 14

[F] 9053 Required installations Standpipe systems shall beinstalled where required by Sections 90531 through 90536and in the locations indicated in Sections 9054 9055 and

2003 INTERNATIONAL BUILDING CODEreg 171R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG171pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20954 PM

Color profile Generic CMYK printer profileComposite Default screen

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 8: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

5 Control valves to commercial kitchen hoods paintspray booths or dip tanks that are sealed or locked inthe open position

6 Valves controlling the fuel supply to fire pump en-gines that are sealed or locked in the open position

7 Trim valves to pressure switches in dry preaction anddeluge sprinkler systems that are sealed or locked inthe open position

[F] 90341 Signals Alarm supervisory and trouble signalsshall be distinctly different and automatically transmitted toan approved central station remote supervising station orproprietary supervising station as defined in NFPA 72 orwhen approved by the building official shall sound an audi-ble signal at a constantly attended location

Exceptions

1 Underground key or hub valves in roadway boxesprovided by the municipality or public utility arenot required to be monitored

2 Backflow prevention device test valves located inlimited area sprinkler system supply piping shallbe locked in the open position In occupancies re-quired to be equipped with a fire alarm system thebackflow preventer valves shall be electrically su-pervised by a tamper switch installed in accor-dance with NFPA 72 and separately annunciated

[F] 90342 Alarms Approved audible devices shall beconnected to every automatic sprinkler system Such sprin-kler water-flow alarm devices shall be activated by waterflow equivalent to the flow of a single sprinkler of the small-est orifice size installed in the system Alarm devices shallbe provided on the exterior of the building in an approvedlocation Where a fire alarm system is installed actuation ofthe automatic sprinkler system shall actuate the building firealarm system

[F] 90343 Floor control valves Approved supervised in-dicating control valves shall be provided at the point of con-nection to the riser on each floor in high-rise buildings

[F] 9035 Testing and maintenance Sprinkler systems shallbe tested and maintained in accordance with the Phoenix FireCode

SECTION 904ALTERNATIVE AUTOMATIC

FIRE-EXTINGUISHING SYSTEMS

[F] 9041 General Automatic fire-extinguishing systemsother than automatic sprinkler systems shall be designed in-stalled inspected tested and maintained in accordance withthe provisions of this section and the applicable referencedstandards

[F] 9042 Where required Automatic fire-extinguishing sys-tems installed as an alternative to the required automatic sprin-kler systems of Section 903 shall be approved by the buildingofficial Automatic fire-extinguishing systems shall not beconsidered alternatives for the purposes of exceptions or reduc-tions permitted by other requirements of this code

[F] 90421 Hood system suppression Each required com-mercial kitchen exhaust hood and duct system required bythe Phoenix Fire Code or the International MechanicalCode to have a Type I hood shall be protected with an ap-proved automatic fire-extinguishing system installed in ac-cordance with this code

[F] 9043 Installation Automatic fire-extinguishing systemsshall be installed in accordance with this section

[F] 90431 Electrical wiring Electrical wiring shall be inaccordance with the National Electrical Code

[F] 90432 Actuation Automatic fire-extinguishing sys-tems shall be automatically actuated and provided with amanual means of actuation in accordance with Section904111

[F] 90433 System interlocking Automatic equipment in-terlocks with fuel shutoffs ventilation controls doorclosers window shutters conveyor openings smoke andheat vents and other features necessary for proper operationof the fire-extinguishing system shall be provided as re-quired by the design and installation standard utilized forthe hazard

[F] 90434 Alarms and warning signs Where alarms arerequired to indicate the operation of automatic fire-extin-guishing systems distinctive audible and visible alarms andwarning signs shall be provided to warn of pending agentdischarge Where exposure to automatic-extinguishingagents poses a hazard to persons and a delay is required toensure the evacuation of occupants before agent dischargea separate warning signal shall be provided to alert occu-pants once agent discharge has begun Audible signals shallbe in accordance with Section 90792

[F] 90435 Monitoring Where a building fire alarm sys-tem is installed automatic fire-extinguishing systems shallbe monitored by the building fire alarm system in accor-dance with NFPA 72

[F] 9044 Inspection and testing Automatic fire-extinguish-ing systems shall be inspected and tested in accordance withthe provisions of this section prior to acceptance

[F] 90441 Inspection Prior to conducting final accep-tance tests the following items shall be inspected

1 Hazard specification for consistency with design haz-ard

2 Type location and spacing of automatic- and man-ual-initiating devices

3 Size placement and position of nozzles or dischargeorifices

4 Location and identification of audible and visiblealarm devices

5 Identification of devices with proper designations

6 Operating instructions

[F] 90442 Alarm testing Notification appliances con-nections to fire alarm systems and connections to approvedsupervising stations shall be tested in accordance with thissection and Section 907 to verify proper operation

170R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG170pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20901 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 904421 Audible and visible signals The audibil-ity and visibility of notification appliances signalingagent discharge or system operation where requiredshall be verified

[F] 90443 Monitor testing Connections to protected pre-mises and supervising station fire alarm systems shall betested to verify proper identification and retransmission ofalarms from automatic fire-extinguishing systems

[F] 9045 Wet-chemical systems Wet-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17A and their listing

[F] 9046 Dry-chemical systems Dry-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17 and their listing

[F] 9047 Foam systems Foam-extinguishing systems shall beinstalled maintained periodically inspected and tested in ac-cordance with NFPA 11 and NFPA 16 and their listing

[F] 9048 Carbon dioxide systems Carbon dioxide extin-guishing systems shall be installed maintained periodicallyinspected and tested in accordance with NFPA 12 and their list-ing

[F] 9049 Halon systems Halogenated extinguishing systemsshall be installed maintained periodically inspected and testedin accordance with NFPA 12A and their listing

[F] 90410 Clean-agent systems Clean-agent fire-extinguish-ing systems shall be installed maintained periodically in-spected and tested in accordance with NFPA 2001 and theirlisting

[F] 90411 Commercial cooking systems The automaticfire-extinguishing system for commercial cooking systemsshall be of a type recognized for protection of commercialcooking equipment and exhaust systems of the type and ar-rangement protected Preengineered automatic dry- andwet-chemical extinguishing systems shall be tested in accor-dance with UL 300 and listed and labeled for the intended ap-plication Other types of automatic fire-extinguishing systemsshall be listed and labeled for specific use as protection forcommercial cooking operations The system shall be installedin accordance with this code its listing and the manufacturerrsquosinstallation instructions Automatic fire-extinguishing systemsof the following types shall be installed in accordance with thereferenced standard indicated as shown

1 Carbon dioxide extinguishing systems NFPA 12

2 Automatic sprinkler systems NFPA 13

3 Foam-water sprinkler system or foam-water spray sys-tems NFPA 16

4 Dry-chemical extinguishing systems NFPA 17

5 Wet-chemical extinguishing systems NFPA 17A

Exception Factory-built commercial cooking recirculatingsystems that are tested in accordance with UL 197 andlisted labeled and installed in accordance with Section3041 of the International Mechanical Code

[F] 904111 Manual system operation A manual actua-tion device shall be located at or near a means of egress fromthe cooking area a minimum of 10 feet (3048 mm) and a

maximum of 20 feet (6096 mm) from the kitchen exhaustsystem The manual actuation device shall be located a min-imum of 4 feet (1219 mm) and a maximum of 5 feet (1524mm) above the floor The manual actuation shall require amaximum force of 40 pounds (178 N) and a maximummovement of 14 inches (356 mm) to actuate the fire sup-pression system

Exception Automatic sprinkler systems shall not be re-quired to be equipped with manual actuation means

[F] 904112 System interconnection The actuation of thefire suppression system shall automatically shut down thefuel or electrical power supply to the cooking equipmentThe fuel and electrical supply reset shall be manual

[F] 904113 Carbon dioxide systems When carbon diox-ide systems are used there shall be a nozzle at the top of theventilating duct Additional nozzles that are symmetricallyarranged to give uniform distribution shall be installedwithin vertical ducts exceeding 20 feet (6096 mm) and hori-zontal ducts exceeding 50 feet (15 240 mm) Dampers shallbe installed at either the top or the bottom of the duct andshall be arranged to operate automatically upon activationof the fire-extinguishing system Where the damper is in-stalled at the top of the duct the top nozzle shall be immedi-ately below the damper Automatic carbon dioxidefire-extinguishing systems shall be sufficiently sized to pro-tect against all hazards venting through a common duct si-multaneously

[F] 9041131 Ventilation system Commercial-typecooking equipment protected by an automatic carbon di-oxide-extinguishing system shall be arranged to shut offthe ventilation system upon activation

[F] 904114 Special provisions for automatic sprinklersystems Automatic sprinkler systems protecting commer-cial-type cooking equipment shall be supplied from a sepa-rate readily accessible indicating-type control valve that isidentified

[F] 9041141 Listed sprinklers Sprinklers used forthe protection of fryers shall be listed for that applicationand installed in accordance with their listing

SECTION 905STANDPIPE SYSTEMS

[F] 9051 General Standpipe systems shall be provided in newbuildings and structures in accordance with this section Firehose threads used in connection with standpipe systems shallbe approved and shall be compatible with fire department hosethreads The location of fire department hose connections shallbe approved In buildings used for high-piled combustible stor-age fire protection shall be in accordance with the PhoenixFire Code

[F] 9052 Installation standards Standpipe systems shall beinstalled in accordance with this section and NFPA 14

[F] 9053 Required installations Standpipe systems shall beinstalled where required by Sections 90531 through 90536and in the locations indicated in Sections 9054 9055 and

2003 INTERNATIONAL BUILDING CODEreg 171R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG171pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20954 PM

Color profile Generic CMYK printer profileComposite Default screen

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 9: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

[F] 904421 Audible and visible signals The audibil-ity and visibility of notification appliances signalingagent discharge or system operation where requiredshall be verified

[F] 90443 Monitor testing Connections to protected pre-mises and supervising station fire alarm systems shall betested to verify proper identification and retransmission ofalarms from automatic fire-extinguishing systems

[F] 9045 Wet-chemical systems Wet-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17A and their listing

[F] 9046 Dry-chemical systems Dry-chemical extinguishingsystems shall be installed maintained periodically inspectedand tested in accordance with NFPA 17 and their listing

[F] 9047 Foam systems Foam-extinguishing systems shall beinstalled maintained periodically inspected and tested in ac-cordance with NFPA 11 and NFPA 16 and their listing

[F] 9048 Carbon dioxide systems Carbon dioxide extin-guishing systems shall be installed maintained periodicallyinspected and tested in accordance with NFPA 12 and their list-ing

[F] 9049 Halon systems Halogenated extinguishing systemsshall be installed maintained periodically inspected and testedin accordance with NFPA 12A and their listing

[F] 90410 Clean-agent systems Clean-agent fire-extinguish-ing systems shall be installed maintained periodically in-spected and tested in accordance with NFPA 2001 and theirlisting

[F] 90411 Commercial cooking systems The automaticfire-extinguishing system for commercial cooking systemsshall be of a type recognized for protection of commercialcooking equipment and exhaust systems of the type and ar-rangement protected Preengineered automatic dry- andwet-chemical extinguishing systems shall be tested in accor-dance with UL 300 and listed and labeled for the intended ap-plication Other types of automatic fire-extinguishing systemsshall be listed and labeled for specific use as protection forcommercial cooking operations The system shall be installedin accordance with this code its listing and the manufacturerrsquosinstallation instructions Automatic fire-extinguishing systemsof the following types shall be installed in accordance with thereferenced standard indicated as shown

1 Carbon dioxide extinguishing systems NFPA 12

2 Automatic sprinkler systems NFPA 13

3 Foam-water sprinkler system or foam-water spray sys-tems NFPA 16

4 Dry-chemical extinguishing systems NFPA 17

5 Wet-chemical extinguishing systems NFPA 17A

Exception Factory-built commercial cooking recirculatingsystems that are tested in accordance with UL 197 andlisted labeled and installed in accordance with Section3041 of the International Mechanical Code

[F] 904111 Manual system operation A manual actua-tion device shall be located at or near a means of egress fromthe cooking area a minimum of 10 feet (3048 mm) and a

maximum of 20 feet (6096 mm) from the kitchen exhaustsystem The manual actuation device shall be located a min-imum of 4 feet (1219 mm) and a maximum of 5 feet (1524mm) above the floor The manual actuation shall require amaximum force of 40 pounds (178 N) and a maximummovement of 14 inches (356 mm) to actuate the fire sup-pression system

Exception Automatic sprinkler systems shall not be re-quired to be equipped with manual actuation means

[F] 904112 System interconnection The actuation of thefire suppression system shall automatically shut down thefuel or electrical power supply to the cooking equipmentThe fuel and electrical supply reset shall be manual

[F] 904113 Carbon dioxide systems When carbon diox-ide systems are used there shall be a nozzle at the top of theventilating duct Additional nozzles that are symmetricallyarranged to give uniform distribution shall be installedwithin vertical ducts exceeding 20 feet (6096 mm) and hori-zontal ducts exceeding 50 feet (15 240 mm) Dampers shallbe installed at either the top or the bottom of the duct andshall be arranged to operate automatically upon activationof the fire-extinguishing system Where the damper is in-stalled at the top of the duct the top nozzle shall be immedi-ately below the damper Automatic carbon dioxidefire-extinguishing systems shall be sufficiently sized to pro-tect against all hazards venting through a common duct si-multaneously

[F] 9041131 Ventilation system Commercial-typecooking equipment protected by an automatic carbon di-oxide-extinguishing system shall be arranged to shut offthe ventilation system upon activation

[F] 904114 Special provisions for automatic sprinklersystems Automatic sprinkler systems protecting commer-cial-type cooking equipment shall be supplied from a sepa-rate readily accessible indicating-type control valve that isidentified

[F] 9041141 Listed sprinklers Sprinklers used forthe protection of fryers shall be listed for that applicationand installed in accordance with their listing

SECTION 905STANDPIPE SYSTEMS

[F] 9051 General Standpipe systems shall be provided in newbuildings and structures in accordance with this section Firehose threads used in connection with standpipe systems shallbe approved and shall be compatible with fire department hosethreads The location of fire department hose connections shallbe approved In buildings used for high-piled combustible stor-age fire protection shall be in accordance with the PhoenixFire Code

[F] 9052 Installation standards Standpipe systems shall beinstalled in accordance with this section and NFPA 14

[F] 9053 Required installations Standpipe systems shall beinstalled where required by Sections 90531 through 90536and in the locations indicated in Sections 9054 9055 and

2003 INTERNATIONAL BUILDING CODEreg 171R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG171pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 20954 PM

Color profile Generic CMYK printer profileComposite Default screen

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 10: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

9056 Standpipe systems are permitted to be combined withautomatic sprinkler systems

Exception Standpipe systems are not required in GroupR-3 occupancies as applicable in Section 1012

[F] 90531 Building height Class III standpipe systemsshall be installed throughout buildings where the floor levelof the highest story is located more than 30 feet (9144 mm)above the lowest level of fire department vehicle access orwhere the floor level of the lowest story is located more than30 feet (9144 mm) below the highest level of fire depart-ment vehicle access

Exceptions

1 Class I standpipes are allowed in buildingsequipped throughout with an automatic sprinklersystem in accordance with Section 903311 or903312

2 Class I manual standpipes are allowed in openparking garages where the highest floor is locatednot more than 150 feet (45 720 mm) above the low-est level of fire department vehicle access

3 Class I manual dry standpipes are allowed in openparking garages that are subject to freezing tem-peratures provided that the hose connections arelocated as required for Class II standpipes in ac-cordance with Section 9055

4 Class I standpipes are allowed in basementsequipped throughout with an automatic sprinklersystem

[F] 90532 Group A Class I automatic wet standpipesshall be provided in nonsprinklered Group A buildings hav-ing an occupant load exceeding 1000 persons

Exceptions

1 Open-air-seating spaces without enclosed spaces

2 Class I automatic dry and semiautomatic drystandpipes or manual wet standpipes are allowedin buildings where the highest floor surface usedfor human occupancy is 75 feet (22 860 mm) orless above the lowest level of fire department vehi-cle access

[F] 90533 Covered mall buildings A covered mall build-ing shall be equipped throughout with a standpipe systemwhere required by Section 9053 Covered mall buildingsnot required to be equipped with a standpipe system by Sec-tion 9053 shall be equipped with Class I hose connectionsconnected to a system sized to deliver 250 gallons per min-ute (9464 Lmin) at the most hydraulically remote outletHose connections shall be provided at each of the followinglocations

1 Within the mall at the entrance to each exit passage-way or corridor

2 At each floor-level landing within enclosed stairwaysopening directly on the mall

3 At exterior public entrances to the mall

[F] 90534 Stages Stages greater than 1000 square feet inarea (93 m2) shall be equipped with a Class III wet standpipe

system with 15-inch and 25-inch (38 mm and 64 mm) hoseconnections on each side of the stage

Exception Where the building or area is equippedthroughout with an automatic sprinkler system the hoseconnections are allowed to be supplied from the auto-matic sprinkler system and shall have a flow rate of notless than that required by NFPA 14 for Class IIIstandpipes

[F] 905341 Hose and cabinet The 15-inch (38 mm)hose connections shall be equipped with sufficientlengths of 15-inch (38 mm) hose to provide fire protec-tion for the stage area Hose connections shall beequipped with an approved adjustable fog nozzle and bemounted in a cabinet or on a rack

[F] 90535 Underground buildings Underground build-ings shall be equipped throughout with a Class I automaticwet or manual wet standpipe system

[F] 90536 Helistops and heliports Buildings with ahelistop or heliport that are equipped with a standpipe shallextend the standpipe to the roof level on which the helistopor heliport is located in accordance with Section 11075 ofthe Phoenix Fire Code

[F] 9054 Location of Class I standpipe hose connectionsClass I standpipe hose connections shall be provided in all ofthe following locations

1 In every required stairway a hose connection shall beprovided for each floor level above or below gradeHose connections shall be located at an intermediatefloor level landing between floors unless otherwiseapproved by the building official

2 On each side of the wall adjacent to the exit opening ofa horizontal exit

3 In every exit passageway at the entrance from the exitpassageway to other areas of a building

4 In covered mall buildings adjacent to each exteriorpublic entrance to the mall and adjacent to each en-trance from an exit passageway or exit corridor to themall

5 Where the roof has a slope less than four units verticalin 12 units horizontal (333-percent slope) eachstandpipe shall be provided with a hose connection lo-cated either on the roof or at the highest landing ofstairways with stair access to the roof An additionalhose connection shall be provided at the top of themost hydraulically remote standpipe for testing pur-poses

6 Where the most remote portion of a nonsprinkleredfloor or story is more than 150 feet (45 720 mm) froma hose connection or the most remote portion of asprinklered floor or story is more than 200 feet (60960 mm) from a hose connection the building officialis authorized to require that additional hose connec-tions be provided in approved locations

[F] 90541 Protection Risers and laterals of Class Istandpipe systems not located within an enclosed stairwayor pressurized enclosure shall be protected by a degree of

172R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG172pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21006 PM

Color profile Generic CMYK printer profileComposite Default screen

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 11: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

fire resistance equal to that required for vertical enclosuresin the building in which they are located

Exception In buildings equipped throughout with anapproved automatic sprinkler system laterals that are notlocated within an enclosed stairway or pressurized en-closure are not required to be enclosed within fire-resis-tance-rated construction

[F] 90542 Interconnection In buildings where more thanone standpipe is provided the standpipes shall be intercon-nected in accordance with NFPA 14

[F] 9055 Location of Class II standpipe hose connectionsClass II standpipe hose connections shall be accessible and lo-cated so that all portions of the building are within 30 feet (9144mm) of a nozzle attached to 100 feet (30 480 mm) of hose

[F] 90551 Groups A-1 and A-2 In Group A-1 and A-2occupancies with occupant loads of more than 1000 hoseconnections shall be located on each side of any stage oneach side of the rear of the auditorium on each side of thebalcony and on each tier of dressing rooms

[F] 90552 Protection Fire-resistance-rated protection ofrisers and laterals of Class II standpipe systems is not re-quired

[F] 90553 Class II system 1-inch hose A minimum1-inch (25 mm) hose shall be permitted to be used for hosestations in light-hazard occupancies where investigated andlisted for this service and where approved by the building of-ficial

[F] 9056 Location of Class III standpipe hose connectionsClass III standpipe systems shall have hose connections lo-cated as required for Class I standpipes in Section 9054 andshall have Class II hose connections as required in Section9055

[F] 90561 Protection Risers and laterals of Class IIIstandpipe systems shall be protected as required for Class Isystems in accordance with Section 90541

[F] 90562 Interconnection In buildings where more thanone Class III standpipe is provided the standpipes shall beinterconnected at the bottom

[F] 9057 Cabinets Cabinets containing fire-fighting equip-ment such as standpipes fire hoses fire extinguishers or firedepartment valves shall not be blocked from use or obscuredfrom view

[F] 90571 Cabinet equipment identification Cabinetsshall be identified in an approved manner by a permanentlyattached sign with letters not less than 2 inches (51 mm)high in a color that contrasts with the background color in-dicating the equipment contained therein

Exceptions

1 Doors not large enough to accommodate a writtensign shall be marked with a permanently attachedpictogram of the equipment contained therein

2 Doors that have either an approved visual identifi-cation clear glass panel or a complete glass doorpanel are not required to be marked

[F] 90572 Locking cabinet doors Cabinets shall be un-locked

Exceptions

1 Visual identification panels of glass or other ap-proved transparent frangible material that is easilybroken and allows access

2 Approved locking arrangements

3 Group I-3

[F] 9058 Dry standpipes Dry standpipes shall not be in-stalled

Exception Where subject to freezing and in accordancewith NFPA 14

[F] 9059 Valve supervision Valves controlling water sup-plies shall be supervised in the open position so that a change inthe normal position of the valve will generate a supervisory sig-nal at the supervising station required by Section 9034 Wherea fire alarm system is provided a signal shall also be transmit-ted to the control unit

Exceptions

1 Valves to underground key or hub valves in roadwayboxes provided by the municipality or public utilitydo not require supervision

2 Valves locked in the normal position and inspected asprovided in this code in buildings not equipped with afire alarm system

[F] 90510 During construction Standpipe systems requiredduring construction and demolition operations shall be pro-vided in accordance with Section 3311

SECTION 906PORTABLE FIRE EXTINGUISHERS

[F] 9061 General Portable fire extinguishers shall be pro-vided in occupancies and locations as required by the PhoenixFire Code

SECTION 907FIRE ALARM AND DETECTION SYSTEMS

[F] 9071 General This section covers the application instal-lation performance and maintenance of fire alarm systems andtheir components

[F] 90711 Construction documents Construction docu-ments for fire alarm systems shall be submitted for reviewand approval prior to system installation Construction doc-uments shall include but not be limited to all of the follow-ing

1 A floor plan which indicates the use of all rooms

2 Locations of alarm-initiating and notification appli-ances

3 Alarm control and trouble signaling equipment

4 Annunciation

2003 INTERNATIONAL BUILDING CODEreg 173R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG173pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21018 PM

Color profile Generic CMYK printer profileComposite Default screen

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 12: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

5 Power connection

6 Battery calculations

7 Conductor type and sizes

8 Voltage drop calculations

9 Manufacturers model numbers and listing informa-tion for equipment devices and materials

10 Details of ceiling height and construction

11 The interface of fire safety control functions

[F] 90712 Equipment Systems and their componentsshall be listed and approved for the purpose for which theyare installed

[F] 9072 Where required An approved manual automatic ormanual and automatic fire alarm system shall be provided inaccordance with Sections 90721 through 907223 Whereautomatic sprinkler protection installed in accordance withSection 903311 or 903312 is provided and connected tothe building fire alarm system automatic heat detection re-quired by this section shall not be required An approved auto-matic fire detection system shall be installed in accordancewith the provisions of this code and NFPA 72 Devices combi-nations of devices appliances and equipment shall complywith Section 90712 The automatic fire detectors shall besmoke detectors except that an approved alternative type of de-tector shall be installed in spaces such as boiler rooms whereduring normal operation products of combustion are present insufficient quantity to actuate a smoke detector

[F] 90721 Group A A manual fire alarm system shall beinstalled in accordance with NFPA 72 in Group A occupan-cies having an occupant load of 300 or more Portions ofGroup E occupancies occupied for assembly purposes shallbe provided with a fire alarm system as required for theGroup E occupancy

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the notification applianceswill activate upon sprinkler water flow

[F] 907211 System initiation in Group A occupan-cies with an occupant load of 1000 or more Activa-tion of the fire alarm in Group A occupancies with anoccupant load of 1000 or more shall initiate a signal us-ing an emergency voicealarm communications systemin accordance with NFPA 72

Exception Where approved the prerecorded an-nouncement is allowed to be manually deactivated fora period of time not to exceed 3 minutes for the solepurpose of allowing a live voice announcement froman approved constantly attended location

[F] 907212 Emergency power Emergencyvoicealarm communications systems shall be providedwith an approved emergency power source

[F] 90722 Group B A manual fire alarm system shall beinstalled in Group B occupancies having an occupant loadof 500 or more persons or more than 100 persons above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not requiredwhere the building is equipped throughout with an auto-matic sprinkler system and the alarm notification appli-ances will activate upon sprinkler water flow

[F] 90723 Group E A manual fire alarm system shall beinstalled in Group E occupancies When automatic sprin-kler systems or smoke detectors are installed such systemsor detectors shall be connected to the building fire alarmsystem

Exceptions

1 Group E occupancies with an occupant load of lessthan 50

2 Manual fire alarm boxes are not required in GroupE occupancies where all the following apply

21 Interior corridors are protected by smokedetectors with alarm verification

22 Auditoriums cafeterias gymnasiums andthe like are protected by heat detectors orother approved detection devices

23 Shops and laboratories involving dusts orvapors are protected by heat detectors orother approved detection devices

24 Off-premises monitoring is provided

25 The capability to activate the evacuationsignal from a central point is provided

26 In buildings where normally occupiedspaces are provided with a two-way com-munication system between such spacesand a constantly attended receiving stationfrom where a general evacuation alarm canbe sounded except in locations specifi-cally designated by the building official

[F] 90724 Group F A manual fire alarm system shall beinstalled in Group F occupancies that are two or more storiesin height and have an occupant load of 500 or more above orbelow the lowest level of exit discharge

Exception Manual fire alarm boxes are not required ifthe building is equipped throughout with an automaticsprinkler system and the notification appliances will acti-vate upon sprinkler water flow

[F] 90725 Group H A manual fire alarm system shall beinstalled in Group H-5 occupancies and in occupancies usedfor the manufacture of organic coatings An automaticsmoke detection system shall be installed for highly toxicgases organic peroxides and oxidizers in accordance withChapters 37 39 and 40 respectively of the Phoenix FireCode

[F] 90726 Group I A manual fire alarm system and an au-tomatic fire detection system shall be installed in Group Ioccupancies An electrically supervised automatic smokedetection system shall be provided in waiting areas that areopen to corridors

Exception Manual fire alarm boxes in patient sleepingareas of Group I-1 and I-2 occupancies shall not be re-quired at exits if located at all nursesrsquo control stations or

174R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG174pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21031 PM

Color profile Generic CMYK printer profileComposite Default screen

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 13: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

other con stantly at tended staff lo ca tions pro vided such sta tions are vis i ble and con tin u ously ac ces si ble and that travel dis tances re quired in Sec tion 90731 are not exshyceeded

[F] 907261 Group I-2 Cor ri dors in nurs ing homes (both in ter me di ate-care and skilled nurs ing fa cil i ties) de tox i fi ca tion fa cil i ties and spaces open to the cor ri dors shall be equipped with an au to matic fire de tec tion sysshytem

Ex cep tions

1 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing units are pro shyvided with smoke de tec tors that com ply with UL 268 Such de tec tors shall pro vide a vi sual dis play on the cor ri dor side of each pa tient sleep ing unit and an au di ble and vi sual alarm at the nurs ing sta tion at tend ing each unit

2 Cor ri dor smoke de tec tion is not re quired in smoke com part ments that con tain pa tient sleepshying rooms where pa tient sleep ing unit doors are equipped with au to matic door-clos ing de vices with in te gral smoke de tec tors on the unit sides in stalled in ac cor dance with their list ing proshyvided that the in te gral de tec tors per form the re shyquired alert ing func tion

[F] 907262 Group I-3 Group I-3 oc cu pan cies shall be equipped with a man ual and au to matic fire alarm sys tem in stalled for alert ing staff

[F] 9072621 Sys tem ini ti a tion Ac tu a tion of an au to matic fire-ex tin guish ing sys tem a man ual fire alarm box or a fire de tec tor shall ini ti ate an ap proved fire alarm sig nal which au to mat i cally no ti fies staff Presignal sys tems shall not be used

[F] 9072622 Man ual fire alarm boxes Man ual fire alarm boxes are not re quired to be lo cated in ac shycor dance with Sec tion 9073 where the fire alarm boxes are pro vided at staff-at tended lo ca tions hav ing di rect su per vi sion over ar eas where man ual fire alarm boxes have been omit ted Man ual fire alarm boxes shall be per mit ted to be locked in ar eas oc cu pied by de tain ees pro vided that staff mem bers are pres ent within the sub ject area and have keys readily avail able to op er ate the man ual fire alarm boxes

[F] 9072623 Smoke de tec tors An ap proved au toshymatic smoke de tec tion sys tem shall be in stalled through out res i dent hous ing ar eas in clud ing sleep ing ar eas and con tig u ous day rooms group ac tiv ity spaces and other com mon spaces nor mally ac ces si ble to res i dents

Ex cep tions

1 Other ap proved smoke de tec tion ar rangeshyments pro vid ing equiv a lent pro tec tion inshyclud ing but not lim ited to plac ing de tec tors in ex haust ducts from cells or be hind pro tecshytive guards listed for the pur pose are al lowed

FIRE PROTECTION SYSTEMS

when nec es sary to pre vent dam age or tam shyper ing

2 Sleeping units in Use Con di tions 2 and 3 3 Smoke de tec tors are not re quired in sleep ing

units with four or fewer oc cu pants in smoke com part ments that are equipped through out with an ap proved au to matic sprin kler sysshytem

[F] 90727 Group M A man ual fire alarm sys tem shall be in stalled in Group M oc cu pan cies other than cov ered mall build ings com ply ing with Sec tion 402 hav ing an oc cu pant load of 500 or more per sons or more than 100 per sons above or be low the low est level of exit dis charge

Ex cep tion Man ual fire alarm boxes are not re quired if the build ing is equipped through out with an au to matic sprin kler sys tem and the alarm no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow

[F] 907271 Oc cu pant no ti fi ca tion Dur ing times that the build ing is oc cu pied in lieu of the au to matic ac ti vashytion of alarm no ti fi ca tion ap pli ances the man ual fire alarm sys tem shall be al lowed to ac ti vate an alarm sig nal at a con stantly at tended lo ca tion from which evac u a tion in struc tions shall be ini ti ated over an emer gency voicealarm com mu ni ca tion sys tem in stalled in ac cor-dance with Sec tion 9072122 The emer gency voicealarm com mu ni ca tion sys tem shall be al lowed to be used for other an nounce ments pro vided the man ual fire alarm use takes pre ce dence over any other use

[F] 90728 Group R-1 Fire alarm sys tems shall be inshystalled in Group R-1 oc cu pan cies as re quired in Sec tions 907281 through 907283

[F] 907281 Man ual fire alarm sys tem A man ual fire alarm sys tem shall be in stalled in Group R-1 oc cu panshycies

Ex cep tions

1 A man ual fire alarm sys tem is not re quired in build ings not over two sto ries in height where all in di vid ual guestrooms and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each in di vid ual guestroom has an exit di rectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through out the build ing when the fol low ing con di tions are met 21 The build ing is equipped through out with

an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler wa ter flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

2003 INTERNATIONAL BUILDING CODEreg 175

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 14: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

FIRE PROTECTION SYSTEMS

[F] 907282 Au to matic fire alarm sys tem An au toshymatic fire alarm sys tem shall be in stalled through out all in te rior cor ri dors serv ing guestrooms

Ex cep tion An au to matic fire de tec tion sys tem is not re quired in build ings that do not have in te rior cor rishydors serv ing guestrooms and each guestroom has a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to an exit

[F] 907283 Smoke alarms Smoke alarms shall be inshystalled as re quired by Sec tion 907210 In build ings that are not equipped through out with an au to matic sprin kler sys tem in stalled in ac cor dance with Sec tion 903311 or 903312 the smoke alarms in guestrooms shall be conshynected to an emer gency elec tri cal sys tem and shall be an-nun ci ated by guestroom at a con stantly at tended lo ca tion from which the fire alarm sys tem is ca pa ble of be ing man u ally ac ti vated

[F] 90729 Group R-2 A man ual fire alarm sys tem shall be in stalled in Group R-2 oc cu pan cies where

1 Any dwell ing unit or sleep ing unit is lo cated three or more sto ries above the low est level of exit dis charge

2 Any dwell ing unit or sleep ing unit is lo cated more than one story be low the high est level of exit disshycharge of ex its serv ing the dwell ing unit or sleep ing unit or

3 The build ing con tains more than 16 dwell ing units or sleep ing units

Ex cep tions

1 A fire alarm sys tem is not re quired in build ings not over two sto ries in height where all dwell ing units or sleep ing units and con tig u ous at tic and crawl spaces are sep a rated from each other and pub lic or com mon ar eas by at least 1-hour fire par ti tions and each dwell ing unit or sleep ing unit has an exit di shyrectly to a pub lic way exit court or yard

2 Man ual fire alarm boxes are not re quired through shyout the build ing when the fol low ing con di tions are met

21 The build ing is equipped through out with an au to matic sprin kler sys tem in ac cor-dance with Sec tion 903311 or 903312

22 The no ti fi ca tion ap pli ances will ac ti vate upon sprin kler flow and

23 At least one man ual fire alarm box is inshystalled at an ap proved lo ca tion

3 A fire alarm sys tem is not re quired in build ings that do not have in te rior cor ri dors serv ing dwell ing units and are pro tected by an ap proved au to matic sprin kler sys tem in stalled in ac cor dance with Sec shytion 903311 or 903312 pro vided that dwell ing units ei ther have a means of egress door open ing di rectly to an ex te rior exit ac cess that leads di rectly to the ex its or are served by open-ended cor ri dors

de signed in ac cor dance with Sec tion 10226 Exshycep tion 4

[F] 907210 Sin gle- and mul ti ple-sta tion smoke alarms Listed sin gle- and mul ti ple-sta tion smoke alarms shall be inshystalled in ac cor dance with the pro vi sions of this code and the house hold fire-warn ing equip ment pro vi sions of NFPA 72

[F] 9072101 Where re quired Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in the lo ca tions de shyscribed in Sec tions 90721011 through 90721013

[F] 90721011 Group R-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled in all of the fol shylow ing lo ca tions in Group R-1

1 In sleep ing ar eas 2 In ev ery room in the path of the means of egress

from the sleep ing area to the door lead ing from the sleep ing unit

3 In each story within the sleep ing unit in clud ing base ments For sleep ing units with split lev els and with out an in ter ven ing door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721012 Groups R-2 R-3 R-4 and I-1 Sinshygle- or mul ti ple-sta tion smoke alarms shall be inshystalled and main tained in Groups R-2 R-3 R-4 and I-1 re gard less of oc cu pant load at all of the fol low ing lo ca tions

1 On the ceil ing or wall out side of each sep a rate sleep ing area in the im me di ate vi cin ity of bed shyrooms

2 In each room used for sleep ing pur poses 3 In each story within a dwell ing unit in clud ing

base ments but not in clud ing crawl spaces and un in hab it able at tics In dwell ings or dwell ing units with split lev els and with out an in ter venshying door be tween the ad ja cent lev els a smoke alarm in stalled on the up per level shall suf fice for the ad ja cent lower level pro vided that the lower level is less than one full story be low the up per level

[F] 90721013 Group I-1 Sin gle- or mul ti ple-stashytion smoke alarms shall be in stalled and main tained in sleep ing ar eas in oc cu pan cies in Group I-1 Sin gle- or mul ti ple-sta tion smoke alarms shall not be re quired where the build ing is equipped through out with an aushyto matic fire de tec tion sys tem in ac cor dance with Secshytion 90726

[F] 9072102 Power source In new con struc tion reshyquired smoke alarms shall re ceive their pri mary power from the build ing wir ing where such wir ing is served from a com mer cial source and shall be equipped with a bat tery backup Smoke alarms shall emit a sig nal when the bat ter ies are low Wiring shall be per ma nent and

2003 INTERNATIONAL BUILDING CODEreg 176

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 15: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

without a disconnecting switch other than as required forovercurrent protection

Exception Smoke alarms are not required to beequipped with battery backup in Group R-1 wherethey are connected to an emergency electrical system

[F] 9072103 Interconnection Where more than onesmoke alarm is required to be installed within an individ-ual dwelling unit in Group R-2 R-3 or R-4 or within anindividual dwelling unit or sleeping unit in Group R-1the smoke alarms shall be interconnected in such a man-ner that the activation of one alarm will activate all of thealarms in the individual unit The alarm shall be clearlyaudible in all bedrooms over background noise levelswith all intervening doors closed

[F] 9072104 Acceptance testing When the installa-tion of the alarm devices is complete each detector andinterconnecting wiring for multiple-station alarm de-vices shall be tested in accordance with the householdfire warning equipment provisions of NFPA 72

[F] 907211 Special amusement buildings An approvedautomatic smoke detection system shall be provided in spe-cial amusement buildings in accordance with this section

Exception In areas where ambient conditions will causea smoke detection system to alarm an approved alterna-tive type of automatic detector shall be installed

[F] 9072111 Alarm Activation of any single smokedetector the automatic sprinkler system or any other au-tomatic fire detection device shall immediately sound analarm at the building at a constantly attended locationfrom which emergency action can be initiated includingthe capability of manual initiation of requirements inSection 9072112

[F] 9072112 System response The activation of twoor more smoke detectors a single smoke detector withalarm verification the automatic sprinkler system orother approved fire detection device shall automatically

1 Cause illumination of the means of egress withlight of not less than 1 foot-candle (11 lux) at thewalking surface level

2 Stop any conflicting or confusing sounds and vi-sual distractions and

3 Activate an approved directional exit marking thatwill become apparent in an emergency Such sys-tem response shall also include activation of a pre-recorded message clearly audible throughout thespecial amusement building instructing patrons toproceed to the nearest exit Alarm signals used inconjunction with the prerecorded message shallproduce a sound which is distinctive from othersounds used during normal operation The wiringto the auxiliary devices and equipment used to ac-complish the above fire safety functions shall bemonitored for integrity in accordance with NFPA72

[F] 9072113 Emergency voicealarm communica-tion system An emergency voicealarm communication

system which is also allowed to serve as a public addresssystem shall be installed in accordance with NFPA 72and shall be audible throughout the entire special amuse-ment building

[F] 907212 High-rise buildings Buildings with a floorused for human occupancy located more than 75 feet (22860 mm) above the lowest level of fire department vehicleaccess shall be provided with an automatic fire alarm sys-tem and an emergency voicealarm communication systemin accordance with Section 9072122

Exceptions

1 Airport traffic control towers in accordance withSections 412 and 907222

2 Open parking garages in accordance with Section4063

3 Buildings with an occupancy in Group A-5

4 Low-hazard special occupancies in accordancewith Section 50312

5 Buildings with an occupancy in Group H-1 H-2 orH-3 in accordance with Section 415

[F] 9072121 Automatic fire detection Smoke detec-tors shall be provided in accordance with this sectionSmoke detectors shall be connected to an automatic firealarm system The activation of any detector required bythis section shall operate the emergency voicealarmcommunication system Smoke detectors shall be lo-cated as follows

1 In each mechanical equipment electrical trans-former telephone equipment or similar roomwhich is not provided with sprinkler protection el-evator machine rooms and in elevator lobbies

2 In the main return air and exhaust air plenum ofeach air-conditioning system having a capacitygreater than 2000 cubic feet per minute (cfm)(094 m3s) Such detectors shall be located in aserviceable area downstream of the last duct inlet

3 At each connection to a vertical duct or riser serv-ing two or more stories from a return air duct orplenum of an air-conditioning system In GroupR-1 and R-2 occupancies a listed smoke detector isallowed to be used in each return air riser carryingnot more than 5000 cfm (24 m3s) and serving notmore than 10 air inlet openings

[F] 9072122 Emergency voicealarm communica-tion system The operation of any automatic fire detec-tor sprinkler water-flow device or manual fire alarm boxshall automatically sound an alert tone followed by voiceinstructions giving approved information and directionson a general or selective basis to the following terminalareas on a minimum of the alarming floor the floorabove and the floor below in accordance with the Phoe-nix Fire Code

1 Elevator lobbies

2 Corridors

3 Rooms and tenant spaces exceeding 1000 squarefeet (93 m2) in area

2003 INTERNATIONAL BUILDING CODEreg 177R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG177pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21052 PM

Color profile Generic CMYK printer profileComposite Default screen

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 16: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

4 Dwelling units or sleeping units in Group R-2 oc-cupancies

5 Sleeping units in Group R-1 occupancies

6 Areas of refuge as defined in Section 1002

Exception In Group I-1 and I-2 occupancies thealarm shall sound in a constantly attended area and ageneral occupant notification shall be broadcast overthe overhead page

[F] 90721221 Manual override A manual over-ride for emergency voice communication shall beprovided for all paging zones

[F] 90721222 Live voice messages The emer-gency voicealarm communication system shall alsohave the capability to broadcast live voice messagesthrough speakers located in elevators exit stairwaysand throughout a selected floor or floors

[F] 90721223 Standard The emergencyvoicealarm communication system shall be designedand installed in accordance with NFPA 72

[F] 9072123 Fire department communication sys-tem An approved two-way fire department communi-cation system designed and installed in accordance withNFPA 72 shall be provided for fire department use Itshall operate between a fire command center complyingwith Section 911 and elevators elevator lobbies emer-gency and standby power rooms fire pump rooms areasof refuge and inside enclosed exit stairways The fire de-partment communication device shall be provided ateach floor level within the enclosed stairway

Exception Fire department radio systems where ap-proved by the fire department

[F] 907213 Atriums connecting more than two storiesA fire alarm system shall be installed in occupancies with anatrium that connects more than two stories The system shallbe activated in accordance with Section 9076 Such occu-pancies in Group A E or M shall be provided with an emer-gency voicealarm communication system complying withthe requirements of Section 9072122

[F] 907214 High-piled combustible storage areas Anautomatic fire detection system shall be installed through-out high-piled combustible storage areas where required bythe Phoenix Fire Code

[F] 907215 Delayed egress locks Where delayed egresslocks are installed on means of egress doors in accordancewith Section 1008186 an automatic smoke or heat detec-tion system shall be installed as required by that section

[F] 907216 Aerosol storage uses Aerosol storage roomsand general-purpose warehouses containing aerosols shallbe provided with an approved manual fire alarm systemwhere required by the Phoenix Fire Code

[F] 907217 Lumber plywood and veneer mills Lumberplywood and veneer mills shall be provided with a manualfire alarm system

[F] 907218 Underground buildings with smoke exhaustsystem Where a smoke exhaust system is installed in an un-

derground building in accordance with this code automaticfire detectors shall be provided in accordance with this sec-tion

[F] 9072181 Smoke detectors A minimum of onesmoke detector listed for the intended purpose shall beinstalled in the following areas

1 Mechanical equipment electrical transformertelephone equipment elevator machine or similarrooms

2 Elevator lobbies

3 The main return and exhaust air plenum of eachair-conditioning system serving more than onestory and located in a serviceable area downstreamof the last duct inlet

4 Each connection to a vertical duct or riser servingtwo or more floors from return air ducts or ple-nums of heating ventilating and air-conditioningsystems except that in Group R occupancies alisted smoke detector is allowed to be used in eachreturn air riser carrying not more than 5000 cfm(24 m3s) and serving not more than 10 air inletopenings

[F] 9072182 Alarm required Activation of the smokeexhaust system shall activate an audible alarm at a con-stantly attended location

[F] 907219 Underground buildings Where the lowestlevel of a structure is more than 60 feet (18 288 mm) belowthe lowest level of exit discharge the structure shall beequipped throughout with a manual fire alarm system in-cluding an emergency voicealarm communication systeminstalled in accordance with Section 9072122

[F] 9072191 Public address system Where a firealarm system is not required by Section 9072 a publicaddress system shall be provided that shall be capable oftransmitting voice communications to the highest levelof exit discharge serving the underground portions of thestructure and all levels below

[F] 907220 Covered mall buildings Covered mall build-ings exceeding 50000 square feet (4645 m2) in total floorarea shall be provided with an emergency voicealarm com-munication system An emergency voicealarm communi-cation system serving a mall required or otherwise shall beaccessible to the fire department The system shall be pro-vided in accordance with Section 9072122

[F] 907221 Residential aircraft hangars A minimum ofone listed smoke alarm shall be installed within a residentialaircraft hangar as defined in Section 41231 and shall be in-terconnected into the residential smoke alarm or othersounding device to provide an alarm that will be audible inall sleeping areas of the dwelling

[F] 907222 Airport traffic control towers An automaticfire detection system shall be provided in airport traffic con-trol towers

[F] 907223 Battery rooms An approved automaticsmoke detection system shall be installed in areas contain-ing stationary lead-acid battery systems having a liquid ca-

178R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG178pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21104 PM

Color profile Generic CMYK printer profileComposite Default screen

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 17: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

pacity of more than 50 gallons (1893 L) The detectionsystem shall be supervised by an approved central propri-etary or remote station service or a local alarm that willsound an audible signal at a constantly attended location

[F] 9073 Manual fire alarm boxes Manual fire alarm boxesshall be installed in accordance with Sections 90731 through90735

[F] 90731 Location Manual fire alarm boxes shall be lo-cated not more than 5 feet (1524 mm) from the entrance toeach exit Additional manual fire alarm boxes shall be lo-cated so that travel distance to the nearest box does not ex-ceed 200 feet (60 960 mm)

Exception Manual fire alarm boxes shall not be re-quired in Group E occupancies where the building isequipped throughout with an approved automatic sprin-kler system the notification appliances will activate onsprinkler water flow and manual activation is providedfrom a normally occupied location

[F] 90732 Height The height of the manual fire alarmboxes shall be a minimum of 42 inches (1067 mm) and amaximum of 48 inches (1219 mm) measured verticallyfrom the floor level to the activating handle or lever of thebox

[F] 90733 Color Manual fire alarm boxes shall be red incolor

[F] 90734 Signs Where fire alarm systems are not moni-tored by a supervising station an approved permanent signshall be installed adjacent to each manual fire alarm box thatreads WHEN ALARM SOUNDSmdashCALL FIRE DE-PARTMENT

Exception Where the manufacturer has permanentlyprovided this information on the manual fire alarm box

[F] 90735 Protective covers The building official is au-thorized to require the installation of listed manual firealarm box protective covers to prevent malicious falsealarms or provide the manual fire alarm box with protectionfrom physical damage The protective cover shall be trans-parent or red in color with a transparent face to permit visi-bility of the manual fire alarm box Each cover shall includeproper operating instructions A protective cover that emitsa local alarm signal shall not be installed unless approved

[F] 9074 Power supply The primary and secondary powersupplies for the fire alarm system shall be provided in accor-dance with NFPA 72

[F] 9075 Wiring Wiring shall comply with the requirementsof the National Electrical Code and NFPA 72 Wireless protec-tion systems utilizing radio-frequency transmitting devicesshall comply with the special requirements for supervision oflow-power wireless systems in NFPA 72

[F] 9076 Activation Where an alarm notification system isrequired by another section of this code it shall be activated by

1 A required automatic fire alarm system

2 Sprinkler water-flow devices

3 Required manual fire alarm boxes

[F] 9077 Presignal system Presignal systems shall not be in-stalled unless approved by the building official and the fire de-partment Where a presignal system is installed 24-hourpersonnel supervision shall be provided at a location approvedby the fire department in order that the alarm signal can be ac-tuated in the event of fire or other emergency

[F] 9078 Zones Each floor shall be zoned separately and azone shall not exceed 22500 square feet (2090 m2) The lengthof any zone shall not exceed 300 feet (91 440 mm) in any direc-tion

Exception Automatic sprinkler system zones shall not ex-ceed the area permitted by NFPA 13

[F] 90781 Zoning indicator panel A zoning indicatorpanel and the associated controls shall be provided in an ap-proved location The visual zone indication shall lock in un-til the system is reset and shall not be canceled by theoperation of an audible alarm-silencing switch

[F] 90782 High-rise buildings In buildings used for hu-man occupancy that have floors located more than 75 feet(22 860 mm) above the lowest level of fire department vehi-cle access a separate zone by floor shall be provided for allof the following types of alarm-initiating devices whereprovided

1 Smoke detectors

2 Sprinkler water-flow devices

3 Manual fire alarm boxes

4 Other approved types of automatic fire detection de-vices or suppression systems

[F] 9079 Alarm notification appliances Alarm notificationappliances shall be provided and shall be listed for their pur-pose

[F] 90791 Visible alarms Visible alarm notification ap-pliances shall be provided in accordance with Sections907911 through 907913

Exceptions

1 Visible alarm notification appliances are not re-quired in alterations except where an existing firealarm system is upgraded or replaced or a new firealarm system is installed

2 Visible alarm notification appliances shall not berequired in exits as defined in Section 10021

[F] 907911 Public and common areas Visible alarmnotification appliances shall be provided in public areasand common areas

[F] 907912 Employee work areas Where employeework areas have audible alarm coverage the wiring sys-tems shall be designed so that visible alarm notificationappliances can be integrated into the alarm system

[F] 907913 Groups I-1 and R-1 Group I-1 and R-1sleeping units in accordance with Table 907913 shallbe provided with a visible alarm notification applianceactivated by both the in-room smoke alarm and the build-ing fire alarm system

[F] 907914 Group R-2 In Group R-2 occupancies re-quired by Section 907 to have a fire alarm system all

2003 INTERNATIONAL BUILDING CODEreg 179R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG179pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21119 PM

Color profile Generic CMYK printer profileComposite Default screen

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 18: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

dwelling units and sleeping units shall be provided withthe capability to support visible alarm notification appli-ances in accordance with ICC A1171

[F] 90792 Audible alarms Audible alarm notification ap-pliances shall be provided and shall sound a distinctivesound that is not to be used for any purpose other than that ofa fire alarm The audible alarm notification appliances shallprovide a sound pressure level of 15 decibels (dBA) abovethe average ambient sound level or 5 dBA above the maxi-mum sound level having a duration of at least 60 secondswhichever is greater in every occupied space within thebuilding The minimum sound pressure levels shall be 70dBA in occupancies in Groups R and I-1 90 dBA in me-chanical equipment rooms and 60 dBA in other occupan-cies The maximum sound pressure level for audible alarmnotification appliances shall be 120 dBA at the minimumhearing distance from the audible appliance Where the av-erage ambient noise is greater than 105 dBA visible alarmnotification appliances shall be provided in accordance withNFPA 72 and audible alarm notification appliances shall notbe required

Exception Visible alarm notification appliances shallbe allowed in lieu of audible alarm notification appli-ances in critical-care areas of Group I-2 occupancies

[F] TABLE 907913VISIBLE AND AUDIBLE ALARMS

NUMBER OFSLEEPING UNITS

SLEEPING UNITS WITHVISIBLE AND AUDIBLE ALARMS

6 to 25 2

26 to 50 4

51 to 75 7

76 to 100 9

101 to 150 12

151 to 200 14

201 to 300 17

301 to 400 20

401 to 500 22

501 to 1000 5 of total

1001 and over 50 plus 3 for each 100 over 1000

[F] 90710 Fire safety functions Automatic fire detectors uti-lized for the purpose of performing fire safety functions shallbe connected to the buildingrsquos fire alarm control panel where afire alarm system is required by Section 9072 Detectors shallupon actuation perform the intended function and activate thealarm notification appliances or a visible and audible supervi-sory signal at a constantly attended location In buildings notrequired to be equipped with a fire alarm system the automaticfire detector shall be powered by normal electrical service andupon actuation perform the intended function The detectorsshall be located in accordance with NFPA 72

[F] 90711 Duct smoke detectors Duct smoke detectors shallbe connected to the buildingrsquos fire alarm control panel when afire alarm system is provided Activation of a duct smoke de-tector shall initiate a visible and audible supervisory signal at a

constantly attended location Duct smoke detectors shall not beused as a substitute for required open-area detection

Exceptions

1 The supervisory signal at a constantly attended loca-tion is not required where duct smoke detectors acti-vate the buildingrsquos alarm notification appliances

2 In occupancies not required to be equipped with a firealarm system actuation of a smoke detector shall acti-vate a visible and audible signal in an approved loca-tion Smoke detector trouble conditions shall activatea visible or audible signal in an approved location andshall be identified as air duct detector trouble

[F] 90712 Access Access shall be provided to each detectorfor periodic inspection maintenance and testing

[F] 90713 Fire-extinguishing systems Automatic fire-extin-guishing systems shall be connected to the building fire alarmsystem where a fire alarm system is required by another sectionof this code or is otherwise installed

[F] 90714 Monitoring Where required by this chapter or thePhoenix Fire Code an approved supervising station in accor-dance with NFPA 72 shall monitor fire alarm systems

Exception Supervisory service is not required for

1 Single- and multiple-station smoke alarms requiredby Section 907210

2 Smoke detectors in Group I-3 occupancies

3 Automatic sprinkler systems in one- and two-familydwellings

[F] 90715 Automatic telephone-dialing devices Automatictelephone-dialing devices used to transmit an emergency alarmshall not be connected to any fire department telephone numberunless approved by the fire chief

[F] 90716 Acceptance tests Upon completion of the installa-tion of the fire alarm system alarm notification appliances andcircuits alarm-initiating devices and circuits supervisory-sig-nal initiating devices and circuits signaling line circuits andprimary and secondary power supplies shall be tested in accor-dance with NFPA 72

[F] 90717 Record of completion A record of completion inaccordance with NFPA 72 verifying that the system has beeninstalled in accordance with the approved plans and specifica-tions shall be provided

[F] 90718 Instructions Operating testing and maintenanceinstructions and record drawings (ldquoas builtsrdquo) and equipmentspecifications shall be provided at an approved location

[F] 90719 Inspection testing and maintenance The mainte-nance and testing schedules and procedures for fire alarm andfire detection systems shall be in accordance with the PhoenixFire Code

SECTION 908EMERGENCY ALARM SYSTEMS

[F] 9081 Group H occupancies Emergency alarms for thedetection and notification of an emergency condition in Group

180R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG180pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21241 PM

Color profile Generic CMYK printer profileComposite Default screen

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 19: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

19MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

H occupancies shall be provided in accordance with Section 4147

[F] 9082 Group H-5 occupancy Emergency alarms for notishyfication of an emergency condition in an HPM facility shall be provided as required in Section 415946 A continuous gas-detection system shall be provided for HPM gases in acshycordance with Section 41597

[F] 9083 Highly toxic and toxic materials A gas detection system shall be provided for indoor storage and use of highly toxic and toxic gases to detect the presence of gas at or below the permissible exposure limit (PEL) or ceiling limit of the gas for which detection is provided The system shall be capable of monitoring the discharge from the treatment system at or below one-half the IDLH limit

Exception A gas detection system is not required for toxic gases when the physiological warning properties are at a level below the accepted PEL for the gas

[F] 90831 Alarms The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is deshytected The alarm shall be both visible and audible and shall provide warning both inside and outside the area where gas is detected The audible alarm shall be distinct from all other alarms

Exception Signal transmission to a constantly attended control station is not required when not more than one cylinder of highly toxic or toxic gas is stored

[F] 90832 Shutoff of gas supply The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for whichever gas is detected

Exception Automatic shutdown is not required for reacshytors utilized for the production of highly toxic or toxic compressed gases where such reactors are

1 Operated at pressures less than 15 pounds per square inch gauge (psig) (1034 kPa)

2 Constantly attended

3 Provided with readily accessible emergency shutshyoff valves

[F] 90833 Valve closure The automatic closure of shutoff valves shall be in accordance with the following

1 When the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure the shutoff valve in the gas cabishynet or exhausted enclosure for the specific gas deshytected shall automatically close

2 Where the gas-detection sampling point initiating the gas detection system alarm is within a gas room and compressed gas containers are not in gas cabinets or exhausted enclosures the shutoff valves on all gas lines for the specific gas detected shall automatically close

3 Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribushy

FIRE PROTECTION SYSTEMS

tion manifold enclosure the shutoff valve for the compressed container of specific gas detected supplyshying the manifold shall automatically close

Exception When the gas-detection sampling point initishyating the gas-detection system alarm is at a use location or within a gas valve enclosure of a branch line downshystream of a piping distribution manifold the shutoff valve in the gas valve enclosure for the branch line loshycated in the piping distribution manifold enclosure shall automatically close

[F] 9084 Ozone gas-generator rooms Ozone gas-generator rooms shall be equipped with a continuous gas-detection sysshytem that will shut off the generator and sound a local alarm when concentrations above the PEL occur

[F] 9085 Repair garages A flammable-gas detection system shall be provided in repair garages for vehicles fueled by nonodorized gases in accordance with Section 40666

[F] 9086 Refrigerant detector Machinery rooms shall conshytain a refrigerant detector with an audible and visual alarm The detector or a sampling tube that draws air to the detector shall be located in an area where refrigerant from a leak will concenshytrate The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values for the refrigerant classificashytion indicated in the International Mechanical Code Detectors and alarms shall be placed in approved locations

Exception Detectors are not required in ammonia system machinery rooms equipped with a vapor detector in accorshydance with the International Mechanical Code

SECTION 909SMOKE CONTROL SYSTEMS

[F] 9091 Scope and purpose This section applies to mechanshyical or passive smoke control systems when they are required by other provisions of this code The purpose of this section is to establish minimum requirements for the design installation and acceptance testing of smoke control systems that are inshytended to provide a tenable environment for the evacuation or relocation of occupants These provisions are not intended for the preservation of contents the timely restoration of operashytions or for assistance in fire suppression or overhaul activities Smoke control systems regulated by this section serve a differshyent purpose than the smoke- and heat-venting provisions found in Section 910 Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the Internashytional Mechanical Code

[F] 9092 General design requirements Buildings structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accorshydance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engishyneering relevant to the design The construction documents shall include sufficient information and detail to adequately deshyscribe the elements of the design necessary for the proper imshyplementation of the smoke control systems These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions

2003 INTERNATIONAL BUILDING CODEreg 181

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 20: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

20MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

[F] 9093 Special inspection and test requirements In addishytion to the ordinary inspection and test requirements which buildings structures and parts thereof are required to undergo smoke control systems subject to the provisions of Section 909 shall undergo special inspections and tests sufficient to verify the proper commissioning of the smoke control design in its fishynal installed condition The design submission accompanying the construction documents shall clearly detail procedures and methods to be used and the items subject to such inspections and tests Such commissioning shall be in accordance with generally accepted engineering practice and where possible based on published standards for the particular testing inshyvolved The special inspections and tests required by this secshytion shall be conducted under the same terms in Section 1704

[F] 9094 Analysis A rational analysis supporting the types of smoke control systems to be employed their methods of operashytion the systems supporting them and the methods of construcshytion to be utilized shall accompany the submitted construction documents and shall include but not be limited to the items inshydicated in Sections 90941 through 90946

[F] 90941 Stack effect The system shall be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the systemrsquos capabilities In determining the maximum probable stack effect altitude elevation weather history and interior temperatures shall be used

[F] 90942 Temperature effect of fire Buoyancy and exshypansion caused by the design fire in accordance with Secshytion 9099 shall be analyzed The system shall be designed such that these effects do not adversely interfere with the systemrsquos capabilities

[F] 90943 Wind effect The design shall consider the adshyverse effects of wind Such consideration shall be consistent with the wind-loading provisions of Chapter 16

[F] 90944 HVAC systems The design shall consider the effects of the heating ventilating and air-conditioning (HVAC) systems on both smoke and fire transport The analysis shall include all permutations of systems status The design shall consider the effects of the fire on the HVAC systems

[F] 90945 Climate The design shall consider the effects of low temperatures on systems property and occupants Air inlets and exhausts shall be located so as to prevent snow or ice blockage

[F] 90946 Duration of operation All portions of active or passive smoke control systems shall be capable of continshyued operation after detection of the fire event for not less than 20 minutes

[F] 9095 Smoke barrier construction Smoke barriers shall comply with Section 709 and shall be constructed and sealed to limit leakage areas exclusive of protected openings The maximum allowable leakage area shall be the aggregate area calculated using the following leakage area ratios

1 Walls AAw = 000100

2 Exit enclosures AAw = 000035

3 All other shafts AAw = 000150

4 Floors and roofs AAF = 000050

where

A = Total leakage area square feet (m2)

AF = Unit floor or roof area of barrier square feet (m2)

Aw = Unit wall area of barrier square feet (m2)

The leakage area ratios shown do not include openings due to doors operable windows or similar gaps These shall be inshycluded in calculating the total leakage area

[F] 90951 Leakage area The total leakage area of the barshyrier is the product of the smoke barrier gross area multiplied by the allowable leakage area ratio plus the area of other openings such as gaps and operable windows Compliance shall be determined by achieving the minimum air pressure difference across the barrier with the system in the smoke control mode for mechanical smoke control systems Passhysive smoke control systems tested using other approved means such as door fan testing shall be as approved by the building official

[F] 90952 Opening protection Openings in smoke barrishyers shall be protected by automatic-closing devices actuated by the required controls for the mechanical smoke control system Door openings shall be protected by fire door asshysemblies complying with Section 71533

Exceptions

1 Passive smoke control systems with autoshymatic-closing devices actuated by spot-type smoke detectors listed for releasing service inshystalled in accordance with Section 90710

2 Fixed openings between smoke zones which are protected utilizing the airflow method

3 In Group I-2 where such doors are installed across corridors a pair of opposite-swinging doors withshyout a center mullion shall be installed having vishysion panels with approved fire-rated glazing materials in approved fire-rated frames the area of which shall not exceed that tested The doors shall be close fitting within operational tolerances and shall not have undercuts louvers or grilles The doors shall have head and jamb stops astragals or rabbets at meeting edges and automatic-closing devices Positive-latching devices are not reshyquired

4 Group I-3

5 Openings between smoke zones with clear ceiling heights of 14 feet (4267 mm) or greater and bank-down capacity of greater than 20 minutes as determined by the design fire size

[F] 909521 Ducts and air transfer openings Ducts and air transfer openings are required to be protected with a minimum Class II 250degF (121degC) smoke damper complying with Section 716

[F] 9096 Pressurization method The primary mechanical means of controlling smoke shall be by pressure differences across smoke barriers Maintenance of a tenable environment is not required in the smoke control zone of fire origin

2003 INTERNATIONAL BUILDING CODEreg 182

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 21: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

21MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

[F] 90961 Minimum pressure difference The minimum pressure difference across a smoke barrier shall be 005-inch water gage (00124 kPa) in fully sprinklered buildings In buildings permitted to be other than fully sprinklered the smoke control system shall be designed to achieve pressure differences at least two times the maxishymum calculated pressure difference produced by the design fire

[F] 90962 Maximum pressure difference The maximum air pressure difference across a smoke barrier shall be detershymined by required door-opening or closing forces The actual force required to open exit doors when the system is in the smoke control mode shall be in accordance with Section 100812 Opening and closing forces for other doors shall be determined by standard engineering methods for the resolushytion of forces and reactions The calculated force to set a side-hinged swinging door in motion shall be determined by

F = Fdc + K(WA P)2(W- d) (Equation 9-1)

where

A = Door area square feet (m2)

d = Distance from door handle to latch edge of door feet (m)

F = Total door opening force pounds (N)

Fdc = Force required to overcome closing device pounds (N)

K = Coefficient 52 (10)

W = Door width feet (m)

∆P = Design pressure difference inches of water (Pa)

[F] 9097 Airflow design method When approved by the building official smoke migration through openings fixed in a permanently open position which are located between smoke control zones by the use of the airflow method shall be permitshyted The design airflow shall be in accordance with this section Airflow shall be directed to limit smoke migration from the fire zone The geometry of openings shall be considered to prevent flow reversal from turbulent effects

[F] 90971 Velocity The minimum average velocity through a fixed opening shall not be less than

v = 2172 [h (Tf - To)(Tf + 460)]12 (Equation 9-2)

For SI v = 1199 [h (Tf - To)Tf]12

where

h = Height of opening feet (m)

Tf = Temperature of smoke degF (degK)

To = Temperature of ambient air degF (degK)

v = Air velocity feet per minute (mminute)

[F] 90972 Prohibited conditions This method shall not be employed where either the quantity of air or the velocity of the airflow will adversely affect other portions of the smoke control system unduly intensify the fire disrupt

2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

plume dynamics or interfere with exiting In no case shall airflow toward the fire exceed 200 feet per minute (102 ms) Where the formula in Section 90971 requires airflow to exceed this limit the airflow method shall not be used

[F] 9098 Exhaust method When approved by the building official mechanical smoke control for large enclosed volumes such as in atriums or malls shall be permitted to utilize the exshyhaust method The design exhaust volumes shall be in accorshydance with this section

[F] 90981 Exhaust rate The height of the lowest horizonshytal surface of the accumulating smoke layer shall be mainshytained at least 10 feet (3048 mm) above any walking surface which forms a portion of a required egress system within the smoke zone The required exhaust rate for the zone shall be the largest of the calculated plume mass flow rates for the possible plume configurations Provisions shall be made for natural or mechanical supply of air from outside or adjacent smoke zones to make up for the air exhausted Makeup airshyflow rates when measured at the potential fire location shall not exceed 200 feet per minute (60 960 mm per minshyute) toward the fire The temperature of the makeup air shall be such that it does not expose temperature-sensitive fire protection systems beyond their limits

[F] 90982 Axisymmetric plumes The plume mass flow rate (mp) in pounds per second (kgs) shall be determined by placing the design fire center on the axis of the space being analyzed The limiting flame height shall be determined by

zl = 0533Qc 25 (Equation 9-3)

For SI zl = 0166Qc 25

where

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

Qc = Convective heat output British thermal units persecond (kW) (The value of Qc shall not be taken as less than 070Q)

z = Height from top of fuel surface to bottom of smoke layer feet (m)

zl = Limiting flame height feet (m) The zl value must be greater than the fuel equivalent diameter (see Secshytion 9099)

for z gt zl

mp = 0022Qc 13z53 + 00042Qc

For SI mp = 0071 Qc 13z53 + 00018Qc

for z = zl

mp = 0011 Qc

For SI mp = 0035Qc

for z lt zl

mp = 00208Qc 35z

For SI mp = 0032Qc 35z

To convert mp from pounds per second of mass flow to a volumetric rate the following equation shall be used

V = 60 mpρ (Equation 9-4)

183

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 22: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

22MdataCODESibc_2003Final VP_Boca09_ibc_2003vpTuesday December 07 2004 21755 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

where

V = Volumetric flow rate cubic feet per minute (m3s)

ρ = Density of air at the temperature of the smoke layer pounds per cubic feet (T in degF) [kgm3 (T in degC)]

[F] 90983 Balcony spill plumes The plume mass flow rate (mp) for spill plumes shall be determined using the geoshymetrically probable width based on architectural elements and projections in the following equation

mp = 0124(QW2)13(zb + 025H) (Equation 9-5)

For SI mp = 036(QW2)13(zb + 025H)

where

H = Height above fire to underside of balcony feet (m)

mp = Plume mass flow rate pounds per second (kgs)

Q = Total heat output

W = Plume width at point of spill feet (m)

zb = Height from balcony feet (m)

[F] 90984 Window plumes The plume mass flow rate (mp) shall be determined from

mp = 0077(AwHw 12)13(zw+a)53 + 018AwHw

12

(Equation 9-6)

For SI mp = 068(AwHw 12)13(zw + a)53 + 15AwHw

12

where

Aw = Area of the opening square feet (m2)

Hw = Height of the opening feet (m)

mp = plume mass flow rate pounds per second (kgs)

zw = Height from the top of the window or opening to thebottom of the smoke layer feet (m)

a = 24Aw 25Hw

15 - 21Hw

[F] 90985 Plume contact with walls When a plume conshytacts one or more of the surrounding walls the mass flow rate shall be adjusted for the reduced entrainment resulting from the contact provided that the contact remains constant Use of this provision requires calculation of the plume dishyameter that shall be calculated by

d = 048 [(Tc + 460)(Ta + 460)]12z (Equation 9-7)

For SI d = 048 (TcTa)12z

where

d = Plume diameter feet (m)

Ta = Ambient air temperature degF (degK)

Tc = Plume centerline temperature degF (degK)

= 060 (Ta + 460) Qc 23 z -53 + Ta

z = Height at which Tc is determined feet (m)

For SI Tc = 008 Ta Qc 23 z -53 + Ta

[F] 9099 Design fire The design fire shall be based on a Q of not less than 5000 Btus (5275 kW) unless a rational analysis is performed by the registered design professional and approved by the building official The design fire shall be based on the analysis in accordance with Section 9094 and this section

[F] 90991 Factors considered The engineering analysis shall include the characteristics of the fuel fuel load effects included by the fire and whether the fire is likely to be steady or unsteady

[F] 90992 Separation distance Determination of the deshysign fire shall include consideration of the type of fuel fuel spacing and configuration The ratio of the separation disshytance to the fuel equivalent radius shall not be less than 4 The fuel equivalent radius shall be the radius of a circle of equal area to floor area of the fuel package The design fire shall be increased if other combustibles are within the sepashyration distance as determined by

R = [Q(12πq)]12 (Equation 9-8)

where

q = Incident radiant heat flux required for nonpiloted ignition Btuft2 sdot s (Wm2)

Q = Heat release from fire Btus (kW)

R = Separation distance from target to center of fuel package feet (m)

[F] 90993 Heat-release assumptions The analysis shall make use of best available data from approved sources and shall not be based on excessively stringent limitations of combustible material

[F] 90994 Sprinkler effectiveness assumptions A docushymented engineering analysis shall be provided for condishytions that assume fire growth is halted at the time of sprinkler activation

[F] 90910 Equipment Equipment such as but not limited to fans ducts automatic dampers and balance dampers shall be suitable for its intended use suitable for the probable exposure temperatures that the rational analysis indicates and as apshyproved by the building official

[F] 909101 Exhaust fans Components of exhaust fans shall be rated and certified by the manufacturer for the probshyable temperature rise to which the components will be exshyposed This temperature rise shall be computed by

Ts = (Qcmc) + (Ta) (Equation 9-9)

where

c = Specific heat of smoke at smoke layer temperature BtulbdegF (kJkg sdot K)

m = Exhaust rate pounds per second (kgs)

Qc = Convective heat output of fire Btus (kW)

Ta = Ambient temperature degF (degK)

Ts = Smoke temperature degF (degK)

Exception Reduced Ts as calculated based on the assurshyance of adequate dilution air

2003 INTERNATIONAL BUILDING CODEreg 184

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 23: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

[F] 909102 Ducts Duct materials and joints shall be capa-ble of withstanding the probable temperatures and pressuresto which they are exposed as determined in accordance withSection 909101 Ducts shall be constructed and supportedin accordance with the International Mechanical CodeDucts shall be leak tested to 15 times the maximum designpressure in accordance with nationally accepted practicesMeasured leakage shall not exceed 5 percent of design flowResults of such testing shall be a part of the documentationprocedure Ducts shall be supported directly from fire-resis-tance-rated structural elements of the building by substan-tial noncombustible supports

Exception Flexible connections (for the purpose of vi-bration isolation) complying with the International Me-chanical Code that are constructed of approvedfire-resistance-rated materials

[F] 909103 Equipment inlets and outlets Equipmentshall be located so as to not expose uninvolved portions ofthe building to an additional fire hazard Outside air inletsshall be located so as to minimize the potential for introduc-ing smoke or flame into the building Exhaust outlets shallbe so located as to minimize reintroduction of smoke intothe building and to limit exposure of the building or adjacentbuildings to an additional fire hazard

[F] 909104 Automatic dampers Automatic dampers re-gardless of the purpose for which they are installed withinthe smoke control system shall be listed and conform to therequirements of approved recognized standards

[F] 909105 Fans In addition to other requirementsbelt-driven fans shall have 15 times the number of belts re-quired for the design duty with the minimum number ofbelts being two Fans shall be selected for stable perfor-mance based on normal temperature and where applicableelevated temperature Calculations and manufacturerrsquos fancurves shall be part of the documentation procedures Fansshall be supported and restrained by noncombustible de-vices in accordance with the requirements of Chapter 16Motors driving fans shall not be operated beyond theirnameplate horsepower (kilowatts) as determined frommeasurement of actual current draw and shall have a mini-mum service factor of 115

[F] 90911 Power systems The smoke control system shall besupplied with two sources of power Primary power shall be thenormal building power systems Secondary power shall befrom an approved standby source complying with the NationalElectrical Code The standby power source and its transferswitches shall be in a separate room from the normal powertransformers and switch gear and shall be enclosed in a roomconstructed of not less than 1-hour fire-resistance-rated firebarriers ventilated directly to and from the exterior Power dis-tribution from the two sources shall be by independent routesTransfer to full standby power shall be automatic and within 60seconds of failure of the primary power The systems shallcomply with the National Electrical Code

[F] 909111 Power sources and power surges Elementsof the smoke management system relying on volatile mem-ories or the like shall be supplied with uninterruptablepower sources of sufficient duration to span a 15-minute pri-

mary power interruption Elements of the smoke manage-ment system susceptible to power surges shall be suitablyprotected by conditioners suppressors or other approvedmeans

[F] 90912 Detection and control systems Fire detection sys-tems providing control input or output signals to mechanicalsmoke control systems or elements thereof shall comply withthe requirements of Section 907 Such systems shall beequipped with a control unit complying with UL 864 and listedas smoke control equipment

Control systems for mechanical smoke control systems shallinclude provisions for verification Verification shall includepositive confirmation of actuation testing manual overridethe presence of power downstream of all disconnects andthrough a preprogrammed weekly test sequence report abnor-mal conditions audibly visually and by printed report

[F] 909121 Wiring In addition to meeting requirementsof the National Electrical Code all wiring regardless ofvoltage shall be fully enclosed within continuous raceways

[F] 909122 Activation Smoke control systems shall beactivated in accordance with this section

[F] 9091221 Pressurization airflow or exhaustmethod Mechanical smoke control systems using thepressurization airflow or exhaust method shall havecompletely automatic control

[F] 9091222 Passive method Passive smoke controlsystems actuated by approved spot-type detectors listedfor releasing service shall be permitted

[F] 909123 Automatic control Where completely auto-matic control is required or used the automatic-control se-quences shall be initiated from an appropriately zonedautomatic sprinkler system complying with Section903311 manual controls that are readily accessible to thefire department and any smoke detectors required by engi-neering analysis

[F] 90913 Control air tubing Control air tubing shall be ofsufficient size to meet the required response times Tubingshall be flushed clean and dry prior to final connections andshall be adequately supported and protected from damageTubing passing through concrete or masonry shall be sleevedand protected from abrasion and electrolytic action

[F] 909131 Materials Control air tubing shall be harddrawn copper Type L ACR in accordance with ASTM B42 ASTM B 43 ASTM B 68 ASTM B 88 ASTM B 251and ASTM B 280 Fittings shall be wrought copper or brasssolder type in accordance with ASME B 1618 or ASME B1622 Changes in direction shall be made with appropriatetool bends Brass compression-type fittings shall be used atfinal connection to devices other joints shall be brazed us-ing a BCuP5 brazing alloy with solidus above 1100degF(593degC) and liquids below 1500degF (816degC) Brazing fluxshall be used on copper-to-brass joints only

Exception Nonmetallic tubing used within control pan-els and at the final connection to devices provided thatall of the following conditions are met

1 Tubing shall be listed by an approved agency forflame and smoke characteristics

2003 INTERNATIONAL BUILDING CODEreg 185R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG185pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21312 PM

Color profile Generic CMYK printer profileComposite Default screen

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 24: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

2 Tubing and connected devices shall be completelyenclosed within galvanized or paint-grade steel en-closure of not less than 0030 inch (076 mm) (No22 galvanized sheet gage) thickness Entry to theenclosure shall be by copper tubing with a protec-tive grommet of neoprene or teflon or by suitablebrass compression to male-barbed adapter

3 Tubing shall be identified by appropriately docu-mented coding

4 Tubing shall be neatly tied and supported withinenclosure Tubing bridging cabinet and door ormoveable device shall be of sufficient length toavoid tension and excessive stress Tubing shall beprotected against abrasion Tubing serving deviceson doors shall be fastened along hinges

[F] 909132 Isolation from other functions Control tub-ing serving other than smoke control functions shall be iso-lated by automatic isolation valves or shall be anindependent system

[F] 909133 Testing Control air tubing shall be tested atthree times the operating pressure for not less than 30 min-utes without any noticeable loss in gauge pressure prior tofinal connection to devices

[F] 90914 Marking and identification The detection andcontrol systems shall be clearly marked at all junctions ac-cesses and terminations

[F] 90915 Control diagrams Identical control diagramsshowing all devices in the system and identifying their locationand function shall be maintained current and kept on file withthe building official the fire department and in the fire com-mand center in format and manner approved by the fire chief

[F] 90916 Fire-fighterrsquos smoke control panel Afire-fighterrsquos smoke control panel for fire department emer-gency response purposes only shall be provided and shall in-clude manual control or override of automatic control formechanical smoke control systems The panel shall be locatedin a fire command center complying with Section 911 andshall comply with Sections 909161 through 909163

[F] 909161 Smoke control systems Fans within thebuilding shall be shown on the fire-fighterrsquos control panel Aclear indication of the direction of airflow and the relation-ship of components shall be displayed Status indicatorsshall be provided for all smoke control equipment annunci-ated by fan and zone and by pilot-lamp-type indicators asfollows

1 Fans dampers and other operating equipment in theirnormal statusmdashWHITE

2 Fans dampers and other operating equipment in theiroff or closed statusmdashRED

3 Fans dampers and other operating equipment in theiron or open statusmdashGREEN

4 Fans dampers and other operating equipment in afault statusmdashYELLOWAMBER

[F] 909162 Smoke control panel The fire-fighterrsquos con-trol panel shall provide control capability over the complete

smoke-control system equipment within the building as fol-lows

1 ON-AUTO-OFF control over each individual piece ofoperating smoke control equipment that can also becontrolled from other sources within the buildingThis includes stairway pressurization fans smoke ex-haust fans supply return and exhaust fans elevatorshaft fans and other operating equipment used or in-tended for smoke control purposes

2 OPEN-AUTO-CLOSE control over individual damp-ers relating to smoke control and that are also con-trolled from other sources within the building

3 ON-OFF or OPEN-CLOSE control over smoke con-trol and other critical equipment associated with a fireor smoke emergency and that can only be controlledfrom the fire-fighterrsquos control panel

Exceptions

1 Complex systems where approved where the con-trols and indicators are combined to control and in-dicate all elements of a single smoke zone as a unit

2 Complex systems where approved where thecontrol is accomplished by computer interface us-ing approved plain English commands

[F] 909163 Control action and priorities The fire-fighterrsquos control panel actions shall be as follows

1 ON-OFF OPEN-CLOSE control actions shall havethe highest priority of any control point within thebuilding Once issued from the fire-fighterrsquos controlpanel no automatic or manual control from any othercontrol point within the building shall contradict thecontrol action Where automatic means are providedto interrupt normal nonemergency equipment opera-tion or produce a specific result to safeguard the build-ing or equipment (ie duct freezestats duct smokedetectors high-temperature cutouts temperature-ac-tuated linkage and similar devices) such means shallbe capable of being overridden by the fire-fighterrsquoscontrol panel The last control action as indicated byeach fire-fighterrsquos control panel switch position shallprevail In no case shall control actions require thesmoke control system to assume more than one con-figuration at any one time

Exception Power disconnects required by the Na-tional Electrical Code

2 Only the AUTO position of each three-positionfire-fighterrsquos control panel switch shall allow auto-matic or manual control action from other controlpoints within the building The AUTO position shallbe the NORMAL nonemergency building controlposition Where a fire-fighterrsquos control panel is in theAUTO position the actual status of the device (onoff open closed) shall continue to be indicated by thestatus indicator described above When directed by anautomatic signal to assume an emergency conditionthe NORMAL position shall become the emergencycondition for that device or group of devices withinthe zone In no case shall control actions require the

186R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG186pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21620 PM

Color profile Generic CMYK printer profileComposite Default screen

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 25: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

smoke control system to assume more than one con-figuration at any one time

[F] 90917 System response time Smoke-control system acti-vation shall be initiated immediately after receipt of an appro-priate automatic or manual activation command Smokecontrol systems shall activate individual components (such asdampers and fans) in the sequence necessary to prevent physi-cal damage to the fans dampers ducts and other equipmentFor purposes of smoke control the fire-fighterrsquos control panelresponse time shall be the same for automatic or manual smokecontrol action initiated from any other building control pointThe total response time including that necessary for detectionshutdown of operating equipment and smoke control systemstartup shall allow for full operational mode to be achieved be-fore the conditions in the space exceed the design smoke condi-tion The system response time for each component and theirsequential relationships shall be detailed in the required ratio-nal analysis and verification of their installed condition re-ported in the required final report

[F] 90918 Acceptance testing Devices equipment compo-nents and sequences shall be individually tested These tests inaddition to those required by other provisions of this code shallconsist of determination of function sequence and where ap-plicable capacity of their installed condition

[F] 909181 Detection devices Smoke or fire detectorsthat are a part of a smoke control system shall be tested in ac-cordance with Chapter 9 in their installed condition Whenapplicable this testing shall include verification of airflowin both minimum and maximum conditions

[F] 909182 Ducts Ducts that are part of a smoke controlsystem shall be traversed using generally accepted practicesto determine actual air quantities

[F] 909183 Dampers Dampers shall be tested for func-tion in their installed condition

[F] 909184 Inlets and outlets Inlets and outlets shall beread using generally accepted practices to determine airquantities

[F] 909185 Fans Fans shall be examined for correct rota-tion Measurements of voltage amperage revolutions perminute (rpm) and belt tension shall be made

[F] 909186 Smoke barriers Measurements using in-clined manometers or other approved calibrated measuringdevices shall be made of the pressure differences acrosssmoke barriers Such measurements shall be conducted foreach possible smoke control condition

[F] 909187 Controls Each smoke zone equipped with anautomatic-initiation device shall be put into operation bythe actuation of one such device Each additional devicewithin the zone shall be verified to cause the same sequencewithout requiring the operation of fan motors in order to pre-vent damage Control sequences shall be verified through-out the system including verification of override from thefire-fighterrsquos control panel and simulation of standby powerconditions

[F] 909188 Special inspections for smoke controlSmoke control systems shall be tested by a special inspector

[F] 9091881 Scope of testing Special inspectionsshall be conducted in accordance with the following

1 During erection of ductwork and prior to conceal-ment for the purposes of leakage testing and re-cording of device location

2 Prior to occupancy and after sufficient completionfor the purposes of pressure-difference testingflow measurements and detection and control ver-ification

[F] 9091882 Qualifications Special inspection agen-cies for smoke control shall have expertise in fire protec-tion engineering mechanical engineering andcertification as air balancers

[F] 9091883 Reports A complete report of testingshall be prepared by the special inspector or special in-spection agency The report shall include identificationof all devices by manufacturer nameplate data designvalues measured values and identification tag or markThe report shall be reviewed by the responsible regis-tered design professional and when satisfied that the de-sign intent has been achieved the responsible registereddesign professional shall seal sign and date the report

[F] 90918831 Report filing A copy of the final re-port shall be filed with the building official and anidentical copy shall be maintained in an approved lo-cation at the building

[F] 909189 Identification and documentation Chartsdrawings and other documents identifying and locatingeach component of the smoke control system and describ-ing its proper function and maintenance requirements shallbe maintained on file at the building as an attachment to thereport required by Section 9091883 Devices shall have anapproved identifying tag or mark on them consistent withthe other required documentation and shall be dated indicat-ing the last time they were successfully tested and by whom

[F] 90919 System acceptance Buildings or portions thereofrequired by this code to comply with this section shall not be is-sued a certificate of occupancy until such time that the buildingofficial determines that the provisions of this section have beenfully complied with and that the fire department has receivedsatisfactory instruction on the operation both automatic andmanual of the system

Exception In buildings of phased construction a tempo-rary certificate of occupancy as approved by the buildingofficial shall be permitted provided that those portions ofthe building to be occupied meet the requirements of thissection and that the remainder does not pose a significanthazard to the safety of the proposed occupants or adjacentbuildings

90920 Smokeproof enclosures Where required by Section101918 a smokeproof enclosure shall be constructed in ac-cordance with this section A smokeproof enclosure shall con-sist of an enclosed interior exit stairway that conforms toSection 10191 and an outside balcony or ventilated vestibulemeeting the requirements of this section Where access to theroof is required by the Phoenix Fire Code such access

2003 INTERNATIONAL BUILDING CODEreg 187R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG187pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21634 PM

Color profile Generic CMYK printer profileComposite Default screen

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 26: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

shall be from the smokeproof enclosure where a smokeproofenclosure is required

909201 Access Access to the stair shall be by way of avestibule or an open exterior balcony The minimum dimen-sion of the vestibule shall not be less than the required widthof the corridor leading to the vestibule but shall not have awidth of less than 44 inches (1118 mm) and shall not have alength of less than 72 inches (1829 mm) in the direction ofegress travel

909202 Construction The smokeproof enclosure shall beseparated from the remainder of the building by not lessthan a 2-hour fire-resistance-rated fire barrier without open-ings other than the required means of egress doors The ves-tibule shall be separated from the stairway by not less than a2-hour fire-resistance-rated fire barrier The open exteriorbalcony shall be constructed in accordance with the fire-re-sistance-rating requirements for floor construction

9092021 Door closers Doors in a smokeproof enclo-sure shall be self-closing or automatic-closing by actua-tion of a smoke detector installed at the floor-sideentrance to the smokeproof enclosure in accordance withSection 71537 The actuation of the smoke detector onany door shall activate the closing devices on all doors inthe smokeproof enclosure at all levels Smoke detectorsshall be installed in accordance with Section 90710

909203 Natural ventilation alternative The provisionsof Sections 9092031 through 9092033 shall apply toventilation of smokeproof enclosures by natural means

9092031 Balcony doors Where access to the stairwayis by way of an open exterior balcony the door assemblyinto the enclosure shall be a fire door in accordance withSection 7153

9092032 Vestibule doors Where access to the stair-way is by way of a vestibule the door assembly into thevestibule shall be a fire door complying with Section7153 The door assembly from the vestibule to the stair-way shall have not less than a 20-minute fire protectionrating complying with Section 7153

9092033 Vestibule ventilation Each vestibule shallhave a minimum net area of 16 square feet (15 m2) ofopening in a wall facing an outer court yard or publicway that is at least 20 feet (6096 mm) in width

909204 Mechanical ventilation alternative The provi-sions of Sections 9092041 through 9092044 shall applyto ventilation of smokeproof enclosures by mechanicalmeans

9092041 Vestibule doors The door assembly from thebuilding into the vestibule shall be a fire door complyingwith Section 7153 The door assembly from the vesti-bule to the stairway shall have not less than a 20-minutefire protection rating in accordance with Section 7153The door from the building into the vestibule shall beprovided with gaskets or other provisions to minimize airleakage

9092042 Vestibule ventilation The vestibule shall besupplied with not less than one air change per minute andthe exhaust shall not be less than 150 percent of supply

Supply air shall enter and exhaust air shall dischargefrom the vestibule through separate tightly constructedducts used only for that purpose Supply air shall enterthe vestibule within 6 inches (152 mm) of the floor levelThe top of the exhaust register shall be located at the topof the smoke trap but not more than 6 inches (152 mm)down from the top of the trap and shall be entirely withinthe smoke trap area Doors in the open position shall notobstruct duct openings Duct openings with controllingdampers are permitted where necessary to meet the de-sign requirements but dampers are not otherwise re-quired

90920421 Engineered ventilation system Wherea specially engineered system is used the system shallexhaust a quantity of air equal to not less than 90 airchanges per hour from any vestibule in the emergencyoperation mode and shall be sized to handle three ves-tibules simultaneously Smoke detectors shall be lo-cated at the floor-side entrance to each vestibule andshall activate the system for the affected vestibuleSmoke detectors shall be installed in accordance withSection 90710

9092043 Smoke trap The vestibule ceiling shall be atleast 20 inches (508 mm) higher than the door openinginto the vestibule to serve as a smoke and heat trap and toprovide an upward-moving air column The height shallnot be decreased unless approved and justified by designand test

9092044 Stair shaft air movement system The stairshaft shall be provided with a dampered relief openingand supplied with sufficient air to maintain a minimumpositive pressure of 010 inch of water (25 Pa) in the shaftrelative to the vestibule with all doors closed

909205 Stair pressurization alternative Where thebuilding is equipped throughout with an automatic sprinklersystem in accordance with Section 903311 the vestibuleis not required provided that interior exit stairways are pres-surized to a minimum of 015 inch of water (37 Pa) and amaximum of 035 inch of water (87 Pa) in the shaft relativeto the building measured with all stairway doors closed un-der maximum anticipated stack pressures

909206 Ventilating equipment The activation of venti-lating equipment required by the alternatives in Sections909204 and 909205 shall be by smoke detectors installedat each floor level at an approved location at the entrance tothe smokeproof enclosure When the closing device for thestair shaft and vestibule doors is activated by smoke detec-tion or power failure the mechanical equipment shall acti-vate and operate at the required performance levels Smokedetectors shall be installed in accordance with Section90710

9092061 Ventilation systems Smokeproof enclosureventilation systems shall be independent of other build-ing ventilation systems The equipment and ductworkshall comply with one of the following

1 Equipment and ductwork shall be located exteriorto the building and directly connected to thesmokeproof enclosure or connected to the

188 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG188pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21653 PM

Color profile Generic CMYK printer profileComposite Default screen

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 27: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

smokeproof enclosure by ductwork enclosed by2-hour fire-resistance-rated fire barriers

2 Equipment and ductwork shall be located withinthe smokeproof enclosure with intake or exhaustdirectly from and to the outside or throughductwork enclosed by 2-hour fire-resistance-ratedfire barriers

3 Equipment and ductwork shall be located withinthe building if separated from the remainder of thebuilding including other mechanical equipmentby 2-hour fire-resistance-rated fire barriers

9092062 Standby power Mechanical vestibule andstair shaft ventilation systems and automatic fire detec-tion systems shall be powered by an approved standbypower system conforming to Section 403101 and Chap-ter 27

9092063 Acceptance and testing Before the mechan-ical equipment is approved the system shall be tested inthe presence of the building official to confirm that thesystem is operating in compliance with these require-ments

[F] 90921 Underground building smoke exhaust systemWhere required in accordance with Section 4055 for under-ground buildings a smoke exhaust system shall be provided inaccordance with this section

[F] 909211 Exhaust capability Wherecompartmentation is required each compartment shall havean independent automatically activated smoke exhaust sys-tem capable of manual operation The system shall have anair supply and smoke exhaust capability that will provide aminimum of six air changes per hour

[F] 909212 Operation The smoke exhaust system shallbe operated in the compartment of origin by the followingindependently of each other

1 Two cross-zoned smoke detectors within a single pro-tected area of a single smoke detector monitored by analarm verification zone or an approved equivalentmethod

2 The automatic sprinkler system

3 Manual controls that are readily accessible to the firedepartment

[F] 909213 Alarm required Activation of the smoke ex-haust system shall activate an audible alarm at a constantlyattended location

SECTION 910SMOKE AND HEAT VENTS

[F] 9101 General Where required by this code or otherwiseinstalled smoke and heat vents or mechanical smoke exhaustsystems and draft curtains shall conform to the requirements ofthis section

Exception Frozen-food warehouses used solely for stor-age of Class I and II commodities where protected by an ap-proved automatic sprinkler system

[F] 9102 Where required Approved smoke and heat ventsshall be installed in the roofs of one-story buildings or portionsthereof occupied for the uses set forth in Sections 91021through 91024

[F] 91021 Groups F-1 and S-1 Buildings and portionsthereof used as a Group F-1 or S-1 occupancy having morethan 50000 square feet (4645 m2) in undivided area

Exception Group S-1 aircraft repair hangars

[F] 91022 Group H Buildings and portions thereof usedas a Group H occupancy as shown

1 In occupancies classified as Group H-2 or H-3 any ofwhich are over 15000 square feet (1394 m2) in singlefloor area

Exception Buildings of noncombustible con-struction containing only noncombustible materi-als

2 In areas of buildings in Group H used for storingClass 2 3 and 4 liquid and solid oxidizers Class 1and unclassified detonable organic peroxides Class 3and 4 unstable (reactive) materials or Class 2 or 3 wa-ter-reactive materials as required for a high-hazardcommodity classification

Exception Buildings of noncombustible construc-tion containing only noncombustible materials

[F] 91023 High-piled combustible storage Buildingsand portions thereof containing high-piled combustiblestock or rack storage in any occupancy group in accordancewith Section 413 and the Phoenix Fire Code

[F] 91024 Exit access travel distance increase Buildingsand portions thereof used as a Group F-1 or S-1 occupancywhere the maximum exit access travel distance is increasedin accordance with Section 10152

[F] 9103 Design and installation The design and installationof smoke and heat vents and draft curtains shall be as specifiedin this section and Table 9103

[F] 91031 Vent operation Smoke and heat vents shall beapproved and labeled and shall be capable of being operatedby approved automatic and manual means Automatic oper-ation of smoke and heat vents shall conform to the provi-sions of this section

[F] 910311 Gravity-operated drop-out vents Auto-matic smoke and heat vents containing heat-sensitiveglazing designed to shrink and drop out of the vent open-ing when exposed to fire shall fully open within 5 min-utes after the vent cavity is exposed to a simulated firerepresented by a time-temperature gradient that reachesan air temperature of 500degF (260degC) within 5 minutes

[F] 910312 Sprinklered buildings Where installed inbuildings provided with an approved automatic sprinklersystem smoke and heat vents shall be designed to oper-ate automatically

[F] 910313 Nonsprinklered buildings Where in-stalled in buildings not provided with an approved auto-matic sprinkler system smoke and heat vents shalloperate automatically by actuation of a heat-responsive

2003 INTERNATIONAL BUILDING CODEreg 189R

FIRE PROTECTION SYSTEMS

09_Phoenix_IBC_2005_PG189pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21704 PM

Color profile Generic CMYK printer profileComposite Default screen

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 28: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

device rated at between 100degF (38degC) and 220degF(104degC) above ambient

Exception Gravity-operated drop-out vents comply-ing with Section 910311

[F] 91032 Vent dimensions The effective venting areashall not be less than 16 square feet (15 m2) with no dimen-sion less than 4 feet (1219 mm) excluding ribs or guttershaving a total width not exceeding 6 inches (152 mm)

[F] 91033 Vent locations Smoke and heat vents shall belocated 20 feet (6096 mm) or more from adjacent lot linesand fire walls and 10 feet (3048 mm) or more from fire bar-rier walls Vents shall be uniformly located within the roofarea above high-piled storage areas with considerationgiven to roof pitch draft curtain location sprinkler locationand structural members

[F] 91034 Draft curtains Where required draft curtainsshall be provided in accordance with this section

Exception Where areas of buildings are equipped withearly suppression fast-response (ESFR) sprinklers draftcurtains shall not be provided within these areas Draftcurtains shall only be provided at the separation betweenthe ESFR sprinklers and the conventional sprinklers

[F] 910341 Construction Draft curtains shall be con-structed of sheet metal lath and plaster gypsum board orother approved materials which provide equivalent per-formance to resist the passage of smoke Joints and con-nections shall be smoke tight

[F] 910342 Location and depth The location andminimum depth of draft curtains shall be in accordancewith Table 9103

[F] 9104 Mechanical smoke exhaust Where approved by thebuilding official engineered mechanical smoke exhaust shallbe an acceptable alternate to smoke and heat vents

[F] 91041 Location Exhaust fans shall be uniformlyspaced within each draft-curtained area and the maximumdistance between fans shall not be greater than 100 feet (30480 mm)

[F] 91042 Size Fans shall have a maximum individual ca-pacity of 30000 cfm (142 m3s) The aggregate capacity ofsmoke exhaust fans shall be determined by the equation

C = A times 300 (Equation 9-10)

where

C = Capacity of mechanical ventilation required in cu-bic feet per minute (m3s)

A = Area of roof vents provided in square feet (m2) in ac-cordance with Table 9103

[F] 91043 Operation Mechanical smoke exhaust fansshall be automatically activated by the automatic sprinklersystem or by heat detectors having operating characteristicsequivalent to those described in Section 91031 Individualmanual controls of each fan unit shall also be provided

[F] 91044 Wiring and control Wiring for operation andcontrol of smoke exhaust fans shall be connected ahead of

190R 2003 INTERNATIONAL BUILDING CODEreg

FIRE PROTECTION SYSTEMS

TABLE 9103REQUIREMENTS FOR DRAFT CURTAINS AND SMOKE AND HEAT VENTSa

OCCUPANCYGROUP ANDCOMMODITY

CLASSIFICATION

DESIGNATEDSTORAGE HEIGHT

(feet)

MINIMUM DRAFTCURTAIN DEPTH

(feet)

MAXIMUM AREAFORMED BY DRAFT

CURTAINS(square feet)

VENT AREATO FLOOR AREA

RATIO

MAXIMUMSPACING OF

VENT CENTERS(feet)

MAXIMUMDISTANCE TO

VENTS FROM WALLOR DRAFT

CURTAINSb

(feet)

Group F-1 mdash 02 times Hc

but ge 4 50000 1100 120 60

Group S-1I-IV

(Option 1)

le 20 6 10000 1100 100 60

gt 20 le 40 6 8000 175 100 55

Group S-1I-IV

(Option 2)

le 20 4 3000 175 100 55

gt 20 le 40 4 3000 150 100 50

Group S-1High hazard(Option 1)

le 20 6 6000 150 100 50

gt 20 le 30 6 6000 140 90 45

Group S-1High hazard(Option 2)

le 20 4 4000 150 100 50

gt 20 le 30 4 2000 130 75 40

For SI 1 foot = 3048 mm 1 square foot = 00929 m2a Requirements for rack storage heights in excess of those indicated shall be in accordance with Chapter 23 of the Phoenix Fire Code For solid-piled storage heights

in excess of those indicated an approved engineered design shall be usedb The distance specified is the maximum distance from any vent in a particular draft curtained area to walls or draft curtains which form the perimeter of the draft cur-

tained areac H is the height of the vent in feet above the floor

09_Phoenix_IBC_2005_PG190pSMdataCODESSTATE CODESPhoenix2005Replacement pagesBuilding CodeFinal VP09_Phoenix_IBC_2005vpFinalWednesday July 13 2005 21717 PM

Color profile Generic CMYK printer profileComposite Default screen

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 29: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

FIRE PROTECTION SYSTEMS

the main dis con nect and pro tected against ex po sure to tem shyper a tures in ex cess of 1000degF (538degC) for a pe riod of not less than 15 min utes Con trols shall be lo cated so as to be im me di ately ac ces si ble to the fire ser vice from the ex te rior of the build ing and pro tected against in te rior fire ex po sure by fire bar ri ers hav ing a fire-re sis tance rat ing not less than 1 hour

[F] 91045 Sup ply air Sup ply air for ex haust fans shall be pro vided at or near the floor level and shall be sized to pro shyvide a min i mum of 50 per cent of re quired ex haust Openshyings for sup ply air shall be uni formly dis trib uted around the pe riph ery of the area served

[F] 91046 In ter locks In com bi na tion com fort air-hanshydlingsmoke re moval sys tems or in de pend ent com fort air-han dling sys tems fans shall be con trolled to shut down in ac cor dance with the ap proved smoke con trol se quence

SECTION 911FIRE COMMAND CENTER

[F] 9111 Fea tures Where re quired by other sec tions of this code a fire com mand cen ter for fire de part ment op er a tions shall be pro vided The lo ca tion and ac ces si bil ity of the fire com mand cen ter shall be sep a rated from the re main der of the build ing by not less than a 1-hour fire-re sis tance-rated fire barshyrier The room shall be a min i mum of 96 square feet (9 m2) with a min i mum di men sion of 8 feet (2438 mm) A lay out of the fire com mand cen ter and all fea tures re quired by the sec tion to be con tained therein shall be sub mit ted for ap proval prior to inshystal la tion The fire com mand cen ter shall com ply with NFPA 72 and shall con tain the fol low ing fea tures

1 The emer gency voicealarm com mu ni ca tion sys tem unit

2 The fire de part ment com mu ni ca tions unit

3 Fire de tec tion and alarm sys tem an nun ci a tor unit

4 An nun ci a tor unit vi su ally in di cat ing the lo ca tion of the el e va tors and whether they are op er a tional

5 Sta tus in di ca tors and con trols for air-han dling sys tems 6 The fire-fighterrsquos con trol panel re quired by Sec tion

90916 for smoke con trol sys tems in stalled in the buildshying

7 Con trols for un lock ing stair way doors si mul ta neously

8 Sprin kler valve and wa ter-flow de tec tor dis play pan els

9 Emer gency and standby power sta tus in di ca tors 10 A tele phone for fire de part ment use with con trolled ac shy

cess to the pub lic tele phone sys tem 11 Fire pump sta tus in di ca tors

12 Sche matic build ing plans in di cat ing the typ i cal floor plan and de tail ing the build ing core means of egress fire pro tec tion sys tems fire-fight ing equip ment and fire de part ment ac cess

13 Work ta ble 14 Gen er a tor su per vi sion de vices man ual start and trans shy

fer fea tures 15 Pub lic ad dress sys tem where spe cif i cally re quired by

other sec tions of this code

2003 INTERNATIONAL BUILDING CODEreg 191

2003 INTERNATIONAL BUILDING CODEreg 192

Page 30: CHAPTER 9 FIRE PROTECTION SYSTEMS - … 9.pdfCHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 ... fire protection systems are required and shall apply to the de ... partment will be equal

2003 INTERNATIONAL BUILDING CODEreg 192