23
100 CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC AND STATCOM 5.1 INTRODUCTION The representation of IEEE 14 bus system equipped with TCSC and STATCOM using MiPower simulation software is presented in this chapter. The system is analyzed under severe disturbance to study the transient behavior with and without FACTS controller. The enhancement of the transient stability is carried out with help of TCSC and STATCOM. The enhancement of transient stability is achieved by adjusting line reactance with the help of TCSC and by compensating the reactive power with the help of STATCOM. The performance curves of the system with TCSC, STATCOM and their combination are taken for discussion. The damping of rotor angle oscillation introduced by the individual controller is compared with combined controllers and it is observed that the latter one shows possible improvement. 5.2 LITERATURE REVIEW Many different techniques are available pertaining to investigation of the effect of TCSC on power system stability. Several approaches based on modern control theory have been applied to TCSC controller design. Chen et al (1995) presented a state feedback controller for TCSC by using a pole placement technique. However, the controller requires all system states which reduce its applicability. Chang and Chow (1997) developed a time

CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

  • Upload
    buiminh

  • View
    236

  • Download
    6

Embed Size (px)

Citation preview

Page 1: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

100

CHAPTER 5

IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14

BUS SYSTEM WITH TCSC AND STATCOM

5.1 INTRODUCTION

The representation of IEEE 14 bus system equipped with TCSC

and STATCOM using MiPower simulation software is presented in this

chapter. The system is analyzed under severe disturbance to study the

transient behavior with and without FACTS controller. The enhancement of

the transient stability is carried out with help of TCSC and STATCOM. The

enhancement of transient stability is achieved by adjusting line reactance with

the help of TCSC and by compensating the reactive power with the help of

STATCOM. The performance curves of the system with TCSC, STATCOM

and their combination are taken for discussion. The damping of rotor angle

oscillation introduced by the individual controller is compared with combined

controllers and it is observed that the latter one shows possible improvement.

5.2 LITERATURE REVIEW

Many different techniques are available pertaining to investigation

of the effect of TCSC on power system stability. Several approaches based on

modern control theory have been applied to TCSC controller design.

Chen et al (1995) presented a state feedback controller for TCSC by using a

pole placement technique. However, the controller requires all system states

which reduce its applicability. Chang and Chow (1997) developed a time

Page 2: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

101

optimal control strategy for the TCSC where a performance index of time was

minimized. Lie et al (1995) proposed a fuzzy logic controller for TCSC. The

impedance of the TCSC is adjusted based on the machine rotor angle and the

magnitude of the speed deviation. In addition, different control schemes for

TCSC were proposed such as variable structure controller (Wang et al 1992,

Luor and Hsu 1998), bilinear generalized predictive controller (Rajkumar and

Mohler 1994), and H -based controller (Zhao and Jiang 1998). The neural

networks (Dai et al 1998 and Senjyu et al 2003) have been proposed for

TCSC-based stabilizer design. The damping characteristics of the designed

stabilizers have been demonstrated through simulation results on a multi-

machine power system. Wang et al (2002) presented a robust nonlinear

coordinated control approach to excitation and TCSC for transient stability

enhancement. The excitation controller and TCSC controller have been

designed separately using a direct feedback linearization technique. Lee and

Moon (2003) presented a hybrid linearization method in which the algebraic

and the numerical linearization technique were combined. The TCSC-based

compensation possesses a thyristor-controlled variable capacitor protected by

a metal oxide varistor (MOV) and an air gap. However, the implementation of

this technology changes the apparent line impedance, which is controlled by

the firing angle of the thyristor and is accentuated by other factors including

the MOV. The presence of the TCSC in the fault loop not only affects the

steady-state components but also the transient components. The controllable

reactance, the MOVs protecting the capacitors and the air gaps’ operation

make the protection decision more complex and therefore, the conventional

relaying scheme based on fixed settings has its limitations. Fault classification

and section identification is a very challenging task for a transmission line

with TCSC (Dash et al 2007).

5.3 PROBLEM STATEMENT

One method of analyzing the transient stability is by placing

different types of FACTS controllers in the test system. This may be done

Page 3: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

102

either by placing a single device or combination of devices at a particular

point. The problem is formulated as the insertion of TCSC and STATCOM in

IEEE 14 bus system that is to be analyzed using MiPower simulation software

for enhancing the transient stability.

5.4 GENERAL REPRESENTATION OF TCSC AND STATCOM

The TCSC power circuit shown in Figure 5.1 is similar to that of

the SVC. The key difference between the SVC and TCSC is that the TCSC is

connected in series with the transmission line. In this case, a twelve pulse

configuration is not necessary, since the current harmonics from the TCR are

able to complete their path through the capacitor more easily than through the

rest of the transmission system (Gyugyi 1998).

Figure 5.1 TCSC power circuit

The TCSC has low level controls that generate the firing pulses. In

this case, the firing pulses are synchronized with the line current. The

response of the synchronization circuit has a significant impact on the system

performance. So it is important to match this to the system that is to be

modeled. If the TCSC has multiple modules connected in series, it is necessary

to model the multiple modules for the system study. The global controls generally

produce a commanded Vc or Xc to be inserted in the line. Again, it is necessary to

Page 4: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

103

map these quantities back to produce the firing delay angle through a lookup

table. On the protection side, the converter over-current protection functions

need to be modeled carefully, if the TCSC is to be included in system

protection study. This includes the external overvoltage protection such as

MOVs and bypass breakers. A key concern in the study is the response of the

TCSC controls prior to the action of the external protection, and how they

impact the response of this protection and the relays protecting the line.

Figure 5.2 shows an example of the external protection circuitry.

Figure 5.2 TCSC with over voltage protection

In the TSC scheme, the degree of series compensation is controlled

by increasing or decreasing the number of capacitor banks in series. To

accomplish this, each capacitor bank is inserted or bypassed by a thyristor

valve (switch). To minimize the switching transients and utilize “natural”

commutation, the operation of the thyristor valves is coordinated with voltage

and current zero crossings. In the fixed-capacitor, thyristor-controlled reactor

scheme, the degree of series compensation in the capacitive operating region

(the admittance of the TCR is kept below that of the parallel connected

capacitor) is increased (or decreased) by increasing (or decreasing) the

Page 5: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

104

thyristor conduction period, and thereby the current in the TCR. Minimum

series compensation is reached when the TCR is off. The TCR is designed to

have the capability to limit the voltage across the capacitor during faults and

other system contingencies of similar effect. The two schemes are combined

by connecting a number of TCRs plus a fixed capacitor in series in order to

achieve greater control range and flexibility. The normalized power P versus

transmission angle is plotted as a parametric function of the degree of series

compensation, k=XC/X (where XC is the effective capacitive impedance of

TCSC and X is the line reactance), shown in Figure 5.3. The variable series

capacitive compensation, apart from steady-state control of power flow, is

effective in transient stability improvement, power oscillations damping and

balancing power flow in parallel lines.

Figure 5.3 P versus for series compensation

TCSC is a controller designed to be connected in series with the tie

line to control their impedance. These types of controllers can be used for

damping the rotor angle oscillations. 50% fixed compensation during steady

condition is considered. During the fault, TCSC is bypassed by MOV, in

order to protect the TCSC. After clearing the fault, the compensation is

Page 6: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

105

increased to 70% in order to transfer the high power and to maintain the

stability.

Representation of STATCOM is discussed in section 3.4.

5.5 IEEE 14 BUS SYSTEM

The IEEE 14 bus standard system is considered as the test system.

It consists of five synchronous machines with IEEE type1 AVRs, three of

which are synchronous compensators used only for reactive power support.

There are eleven loads in the system. The 40 MW generator parameter, type1

AVR parameter (type1 AVR diagram is shown in Figure 4.2), the TG data for

the generator (block diagram is shown in Figure 4.3), two winding

transformer data, three winding transformer data, bus data, line data and load

data are given in the Tables 5.1 to 5.8 respectively.

Table 5.1 40 MW generator parameter

VariableDescription

Data

MVA rating 50

MW rating 40

Rated voltage in kV 220

Ra Armature resistance in p.u. 0.004593

X2 Negative sequence reactance in p.u. 0.149

X0 Zero sequence reactance in p.u. 0.066

Xd Direct axis reactance in p.u. 2.036

Xd' Direct axis transient reactance in p.u. 0.237

Xd'' Direct axis sub - transient reactance in p.u. 0.185

Xq Quadrature axis reactance in p.u. 1.8

Xq' Quadrature axis transient reactance in p.u. 0.33

Xq'' Quadrature axis sub – transient reactance in p.u. 0.1678

Tdo' Direct axis open circuit transient time constant in p.u. 4.902

Tdo" Direct axis open circuit sub – transient time constant in p.u. 0.017

Tqo' Quadrature axis open circuit transient time constant in p.u. 0.533

Tqo" Quadrature axis open circuit sub-transient time constant in p.u. 0.1

H Inertia constant (Generator + Exciter) 4

Winding connection Y

Page 7: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

106

Table 5.2 Type1 AVR parameter

Variable Description Data

Trec Input rectifier time constant in s 0.01

Ka Amplifier gain 300

Ta Amplifier time constant in s 0.02

Ke Exciter gain 1

Te Exciter time constant in s 0.3

Kf Regulator stabilizing circuit gain 0.001

Tf Regulator stabilizing circuit time constant 1

Vse1 Saturation function at 0.75 times maximum field voltage 0.4

Vse2 Saturation function at maximum field voltage 0.7

Vrmax Maximum amplifier voltage 6

Vrmin Minimum amplifier voltage -6

Efdmax Maximum field voltage 4

Efdmin Minimum field voltage 0

Table 5.3 TG data for 40 MW generator

Variable Description Data

Droop 0.05

Pmax Maximum power limit 1

Pmin Minimum power limit 0

Cmax Rate of valve opening 0.1

Cmin Rate of valve closing - 0.33

K1 + K2 Power extraction at HP turbine 0.33

K 3 + K 4 Power extraction at IP turbine 0.33

K 5 + K 6 Power extraction at LP turbine 0.34

T1 Phase compensation 1 0.1

T2 Phase compensation 2 0.05

T3 Servo time constant 0.1

Thp HP section time constant in s 0.1

Trh Reheat section time constant in s 10

Tlp LP section time constant in s 999

Tip IP section time constant (including re-heater) in s 0.1

Page 8: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

107

Table 5.4 Two winding transformer data

Rate d MV A Rate d Vol ta ge( kV) % i mpe dan ce

150 220/ 132 10

Table 5.5 Three winding transformer data

Rated MVA Rated Voltage% impedance

(Positive)

% impedance

(Zero)

Primary Secondary Tertiary Primary Secondary Tertiary Primary Secondary Tertiary Primary Secondary Tertiary

150 105 50.25 220 132 3.3 0.31913 0.28616 0.038527 0.01 0.022 0.028

Table 5.6 Bus data

Bus No.Base

Voltage (kV)

Minimum

Voltage (kV)

Maximum

Voltage (kV)

1 220 209 231

2 220 209 231

3 220 209 231

4 220 209 231

5 220 209 231

6 132 125.4 138.6

8 3.3 3.135 3.465

9 132 125.4 138.6

10 132 125.4 138.6

11 132 125.4 138.6

12 132 125.4 138.6

13 132 125.4 138.6

14 132 125.4 138.6

Page 9: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

108

Table 5.7 Line data

Line

No.

From

bus

No.

To

bus

No.

Positive

sequence

resistance

(p.u.)

Positive

sequence

reactance

(p.u.)

Positive

sequence

susceptance

(p.u.)

Zero

sequence

resistance

(p.u.)

Zero

sequence

reactance

(p.u.)

Zero sequence

susceptance

(p.u.)

1 1 5 0.05403 0.22304 0.0246 0.0035 0.0035 0.0035

2 1 2 0.01938 0.05917 0.0264 0.0035 0.3298 0.000001099

3 2 3 0.04699 0.19797 0.0219 0.0035 0.3298 0.000001099

4 2 4 0.05811 0.17632 0.0187 0.0035 0.3298 0.000001099

5 2 5 0.05695 0.17388 0.017 0.0035 0.3298 0.000001099

6 3 4 0.06701 0.17103 0.0173 0.0035 0.3298 0.000001099

7 4 5 0.01335 0.04211 0.0064 0.0035 0.3298 0.000001099

8 6 11 0.09498 0.1989 0 0.0035 0.3298 0.000001099

9 6 12 0.12991 0.25581 0 0.0035 0.3298 0.000001099

10 6 13 0.06615 0.13027 0 0.0035 0.3298 0.000001099

11 9 10 0.03181 0.08450 0 0.0035 0.3298 0.000001099

12 9 14 0.12711 0.27038 0 0.0035 0.3298 0.000001099

13 10 11 0.08205 0.19207 0 0.0035 0.3298 0.000001099

14 12 13 0.22092 0.19988 0 0.0035 0.3298 0.000001099

15 13 14 0.17093 0.34802 0 0.0035 0.3298 0.000001099

Table 5.8 Load data

Load No. Bus No. MW rating MVAr rating

1 2 21.7 12.7

2 3 94.2 19

3 4 47.8 -3.9

4 5 7.6 1.6

5 6 11.2 7.5

6 9 29.5 16.6

7 10 9 5.8

8 11 3.5 1.8

9 12 6.1 1.6

10 13 13.5 5.8

11 14 14.9 5.6

Page 10: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

109

5.5.1 Single Line Diagram of IEEE 14 bus System

The representation of single line diagram of IEEE 14 bus system

using MiPower simulation software is depicted in Figure 5.4.

Figure 5.4 Single line diagram of IEEE 14 bus system

Page 11: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

110

The real power in MW, reactive power in MVAr, the voltage in p.u.

and angle in degree in the system at steady state condition are depicted in

Figure 5.5.

Figure 5.5 Load flow analysis of IEEE 14 bus system

The real power in MW, reactive power in MVAr, the voltage in p.u.

and angle in degree in the system with TCSC between the buses 1 and 5 are

depicted in Figure 5.6.

Page 12: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

111

Figure 5.6 Load flow analysis of IEEE 14 bus system with TCSC

The real power in MW, reactive power in MVAr, the voltage in p.u.

and angle in degree in the system with STATCOM at bus10 are depicted in

Figure 5.7.

Page 13: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

112

Figure 5.7 Load flow analysis of IEEE 14 bus system with STATCOM

The real power in MW, reactive power in MVAr, the voltage in p.u.

and angle in degree in the system with TCSC between the buses 1 and 5 and

STATCOM at bus10 are depicted in Figure 5.8.

Page 14: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

113

Figure 5.8 Load flow analysis of IEEE 14 bus system with TCSC and

STATCOM

Page 15: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

114

5.6 RESULTS WITH DISCUSSIONS

The IEEE 14 bus system is tested for transient stability by creating

three phase to ground fault at bus12 and the effect at bus2 with and without

FACTS controllers is analyzed. The voltage in p.u., frequency in Hertz and

angle in degree with respect to time in second are taken at bus2 for with and

without FACTS controllers individually and their combination, using

MiPower simulation software.

Figure 5.9 Bus2 voltage in p.u. at fault condition

Page 16: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

115

The voltage at bus2 during fault varies from 0.96 p.u. to 1.04 p.u.,

is depicted in Figure 5.9.

Figure 5.10 Bus2 voltage in p.u. at fault condition (with FACTS device)

The voltage at bus2 with FACTS devices (TCSC between the buses

1 and 5 and STATCOM at bus10) varies from 0.965 p.u. to 1.03 p.u. This is

depicted in Figure 5.10.

Page 17: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

116

Figure 5.11 Bus2 frequency in Hertz at fault condition

During steady state condition, the frequency remains constant at 50

Hz and after the fault at bus12, the frequency at bus2 oscillates and comes

below 50 Hz. This is depicted in Figure 5.11. It indicates inadequate power

generation or transmission capability.

Page 18: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

117

Figure 5.12 Bus2 frequency in Hertz at fault condition (with FACTS

device)

With TCSC (between the buses 1 and 5), the fall in frequency is

limited by means of enhancing the transmission capability. With STATCOM

(at bus10), the power transfer capability is increased by means of recovering

the voltage quickly. With both TCSC and STATCOM, the frequency is

recovered gradually towards the normal value because the power transfer

capability and voltage are restored immediately after clearing the fault. This is

depicted in Figure 5.12.

Page 19: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

118

Figure 5.13 Oscillation of rotor angle in degree at fault condition

Power system stability is basically a spring mass problem.

Whenever there is a disturbance in a spring, the mass will oscillate. Similarly,

the generators will oscillate whenever there is a fault in the network. The

oscillation of generators is basically measured with respect to reference bus.

The oscillation level of the generator depends on the disturbance severity.

During fault at bus12, the generator at bus2 oscillates from -18 to 110 degrees

whereas at steady state condition, it is 42 degrees with respect to reference

bus. This is depicted in Figure 5.13. The system is considered stable, for the

disturbance, since the swing is well within the transient limit of 180 degrees.

Page 20: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

119

Figure 5.14 Oscillation of rotor angle in degree at fault condition (with

TCSC)

With TCSC (between the buses 1 and 5), the generator at bus2

oscillates from -18 to 110 degrees whereas at the steady state condition, it is

42 degrees with respect to reference bus. This is depicted in Figure 5.14. The

system is considered stable, for the disturbance, since the swing is well within

the transient limit of 180 degrees.

Page 21: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

120

Figure 5.15 Oscillation of rotor angle in degree at fault condition (with

STATCOM)

With STATCOM (at bus10), the generator at bus2 oscillates from

-18 to 110 degrees whereas at steady state condition, it is 42 degrees with

respect to reference bus. This is depicted in Figure 5.15. The system is

considered stable, for the disturbance, since the swing is well within the

transient limit of 180 degrees.

Page 22: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

121

Figure 5.16 Oscillation of rotor angle in degree at fault condition (with

TCSC and STATCOM)

With FACTS devices (TCSC between the buses 1 and 5 and

STATCOM at bus 10), the generator at bus2 oscillates from 18 to 62 degrees

whereas at steady state condition, it is 42 degrees with respect to reference

bus. This is depicted in Figure 5.16. The system is considered stable, for the

disturbance, since the swing is well within the transient limit of 180 degrees.

When the device is placed separately in the system, the generator

oscillation is not reduced significantly whereas, it is much reduced (from 18

to 62 degrees) when the devices are placed together.

Page 23: CHAPTER 5 IMPROVEMENT OF TRANSIENT STABILITY IN IEEE 14 BUS SYSTEM WITH TCSC …shodhganga.inflibnet.ac.in/bitstream/10603/24335/10/10... ·  · 2014-09-03CHAPTER 5 IMPROVEMENT OF

122

5.7 CONCLUSION

Transient stability study for IEEE 14 bus system is carried out with

TCSC and STATCOM using MiPower simulation software. Oscillation of the

generator is reduced appreciably when connecting both TCSC and

STATCOM together. However, the oscillation of the generator is not reduced

when connecting the TCSC and STATCOM individually. Regarding voltage

and frequency, both are recovered quickly by connecting TCSC and

STATCOM together.