Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
4-1
Chap.4
Chapter 4 Specifications of HG3F/4F
1 Product List................................................................................................4-2 1.1 Main Unit..................................................................................................................... 4-2 1.2 Accessories ................................................................................................................... 4-2 1.3 Options ......................................................................................................................... 4-2
2 Part names and Functions.........................................................................4-4 2.1 Front............................................................................................................................. 4-4 2.2 Rear .............................................................................................................................. 4-5 2.3 Layout of Touch Switches ........................................................................................... 4-7
3 Main Unit Specifications ............................................................................4-9 3.1 Applicable Standards .................................................................................................. 4-9 3.2 General Specifications................................................................................................. 4-9 3.3 External Dimensions................................................................................................. 4-11 3.4 Function Specifications ............................................................................................. 4-13 3.5 Display Specifications ............................................................................................... 4-14 3.6 Operation Specifications ........................................................................................... 4-15 3.7 Power supply Input Specifications ........................................................................... 4-15 3.8 Serial Interface1 Specifications ................................................................................ 4-16 3.9 Serial Interface2 Specifications ................................................................................ 4-17 3.10 Expansion Interface Specifications ........................................................................ 4-18 3.11 O/I link Interface Specifications ............................................................................. 4-18 3.12 Ethernet (LAN) Interface Specifications................................................................ 4-18 3.13 Compact Flash(CF) interface specification............................................................ 4-19 3.14 Parallel Interface Specifications............................................................................. 4-19
4 Installation and Wiring .............................................................................4-21 4.1 Installation Location ................................................................................................. 4-21 4.2 Installation................................................................................................................. 4-21 4.3 Wiring......................................................................................................................... 4-22
5 Inspection ................................................................................................4-24
Chapter4 Specifications of HG3F/4F
4-2
1 Product List
1.1 Main Unit
Main Unit
Display Type
Interface Type No.
RS232C/485(422) Ethernet·CF I/F
HG3F-FT22TF-* 10.4inch TFT color LCD RS232C/485(422) HG3F-FT22VF-*
RS232C/485(422) Ethernet·CF I/F
HG4F-JT22TF-* 12.1inch TFT color LCD RS232C/485(422) HG4F-JT22VF-*
*: Main Unit Color B: Dark gray W: Light gray
1.2 Accessories
Type No. Notes HG9Z-4K1 Mounting Clip (4) B-748, 749 Operating Instruction Sheet (1)
(HG3F) B-750, 751 Operating Instruction Sheet (1)
(HG4F)
1.3 Options
Configuration software (WindO/I-NV2)
Type No. Description HG9Y-B1118 Japanese manual HG9Y-B1119 English manual SW1A-W1C CD-ROM
Maintenance Cable
Type No. Description HG9Z-XCM22 2m D-sub 9P socket
(PC side) for Windows PC
Mounting Clip
Type No. Description HG9Z-4K1PN10 Mounting clip (HG9Z-4K1),
10 pieces per package
PLC Connecting Cable
Type No. Description PF3S-KS1 For IDEC FA3S Link Unit, 5mFC4A-KC2C For IDEC MicroSmart, 5m HG9Z-3C115 For IDEC MICRO3, 5m HG9Z-3C125 For IDEC MICRO3C,
OpenNet Controller MicroSmart, 5m
HG9Z-3C135 RS-232C (25pin, D-sub), for Mitsubishi, Omron, etc. link unit, 5m
HG9Z-3C145 RS-232C (9pin, D-sub), Mitsubishi, etc. link unit, 5m
HG9Z-3C155 RS-232C (9pin, D-sub), Omron etc. RS-232C I/F, 5m
HG9Z-3C165 For Mitsubishi A and FX series programming port, 5m
1 Product List
4-3
Chap.4
Protective Sheet
Type No. Description HG9Z-3DAPN02 Protective sheet for touch
switch type (2 sheets per package for HG3F)
HG9Z-4DAPN02 Protective sheet for touch switch type (2 sheets per package for HG4F)
Replacement Backlight
Type No. Description HG9Z-3FB Backlight for HG3F HG9Z-4FB1 or HG9Z-4FB2 (*)
Backlight for HG4F
Expansion Unit
Type No. Description HG9Z-3P102 Digital I/O
(16 inputs and 16 outputs)
O/I Link Unit
Type No. Description HG9Z-2G1 Dedicated communication
unit
CF Card
Type No. Description HG9Z-MF32 CF Card (32MB)
(*) Type No. of Replacement Backlight The HG4F uses two different types of replacement backlights depending on the production date. When ordering a replacement backlight, look for the Replacement Backlight Type No. label on the back of the HG4F. For the label position, see the figure “2 Part names and Functions”. When the label is found, specify HG9Z-4FB1 or HG9Z-4FB2 indicated on the label. If the label is not found, specify HG9Z-4FB1.
Chapter4 Specifications of HG3F/4F
4-4
2 Part names and Functions
2.1 Front
• HG3F-FT22∆F-* (Touch Switch Type)
Touch switches
• HG4F-JT22∆F-* (Touch Switch Type)
Touch switches
2 Part names and Functions
4-5
Chap.4
2.2 Rear
• HG3F-FT22ΔF-*
• HG4F-JT22ΔF-*
(2)
(3)
(4)
(5)
(6)
(7)
(9)
(10)
(11)
(1)
(8)
(1)
(6)
(3)
(4)
(5)
(2)
(7)
(9)
(10)
(11)
(8)
(12)
Chapter4 Specifications of HG3F/4F
4-6
No. Name Description 1 Power Supply and Function Ground Terminal block 3P 2 Serial Interface 2 Mini-DIN 8P connector 3 Expansion Interface 60P connector 4 Serial Interface 1 D-sub25P connector 5 O/I Link Interface Special connector 6 Parallel Interface D-sub25P connector 7 CF Interface Connects the Compact Flash 8 Access Stop Switch CF extraction permission switch 9 Ethernet Interface Connects to Ethernet (10BASE-T)
10 Rubber Packing 11 Nameplate 12 Replacement Backlight Type No. Label Indicates the replacement backlight Type No.
2 Part names and Functions
4-7
Chap.4
2.3 Layout of Touch Switches
Touch switches can be placed on the grids. The physical switch layout is as shown in the illustration below.
・ HG3F-FT22ΔF-*
・ HG4F-JT22ΔF-*
20 2
0
480
640
20
2
0
600
800
Chapter4 Specifications of HG3F/4F
4-8
・ EX4R
• Pressing the touch panel of EX4R will not work while the maintenance cable is inserted into Serial Interface 2.
• For the initial settings of the analog touch panel, refer to Chapter 33 "2.1.2 Initialize" in the "MICRO/I HG2G, HG1F/2F/2S/3F/4F Instruction Manual".
• When more than one button is pressed, the touch screen will not be able to detect such operation. Instead, the center point between buttons pressed in the display area will be triggered. This is due to the detection characteristics of the analog touch panel. When more than one button is pressed simultaneously, the resulting operation may vary.
1
1
600
800
3 Main Unit Specifications
4-9
Chap.4
3 Main Unit Specifications
3.1 Applicable Standards
UL508, UL1604, CSA C22.2 No.213
Safety Standards
IEC/EN61131 EMC Standards IEC/EN61000-6-4,
IEC/EN61131-2
3.2 General Specifications
Electrical Specifications
Rated Operating Voltage
24VDC
Power Voltage Range
80% to 120% of rated voltage (including ripple)
Power Consumption
25W maximum
Allowable Momentary Power Interruption
10ms maximum, Level PS-2 (IEC/EN61131)
Inrush Current 15A maximum.(cold start) Dielectric Strength 1500VAC 10mA, 1 minute
(between power terminals and FG)
Insulation Resistance
10MΩ minimum (500VDC mega) (between power terminals and FG)
Environmental Specifications
Operating Ambient Temperature (operation)
HG3F:0 to 50°C HG4F:0 to 45°C (no freezing)
Operating Relative Humidity (operation)
20 to 85%RH (no dew) (no condensation)
Storage Ambient Temperature
-20 to 60°C (no freezing)
Storage Relative Humidity
20 to 85%RH (no condensation)
Altitude 0 to 2000m (operation), 0 to 3000m (transport) (IEC61131-2)
Vibration Resistance 10 to 55Hz 9.8m/s2 (2 hours each in 3 axes) (IEC60068-2-6)
Shock Resistance
147m/s2 ,11ms (5 shocks each in 3 axes) (IEC60068-2-27)
Pollution Degree
Pollution degree 2 (IEC60664-1)
Corrosion Immunity Free from corrosive gases
Effect of Incorrect Connection
Reversal of DC power supply polarity
No damage but the equipment will not operate
Connection to Power supply that exceeds ratings
Permanent failure likely
Earthing
Function earth Wire to ensure stable equipment operation
Chapter4 Specifications of HG3F/4F
4-10
Construction
Installation Buried panel Protection IP66 (at the front of the
installation panel), NEMA TYPE 4,4x,13
Terminals Power supply input: M4 screw Tightening torque: 1.0 to 1.3Nm
Dimensions HG3F: 324(W) x 240(H) x 56(D)mmHG4F: 348(W) x 270(H) x 58(D)mm
Weight HG3F: 2800g (approx.) HG3F: 3400g (approx.)
Noise Specifications
Electrostatic Discharge
ESD-3 (RH-1) level 3 Contact +/-6KV/ Air +/-8KV
IEC/EN61000-4-2
Electro- magnetic Field
10V/m AM80% 80MHz to 1000 MHz
IEC/EN61000-4-3
Fast Transient Burst Withstand- ability
Common mode: Level 3 Power supply: +/-2KV Communication line: +/-1KV
IEC/EN61000-4-4
Damped Oscillatory Wave
Serial mode: Power supply: +/-1KV
IEC/EN61000-4-12
Power-up Surge Immunity
Between 500V L-FG
IEC/EN61000-4-5
Radiated Emission
IEC/EN61000-6-4
3 Main Unit Specifications
4-11
Chap.4
3.3 External Dimensions
HG3F-FT22ΔF-*
(Pan
el T
hick
ness
)
Chapter4 Specifications of HG3F/4F
4-12
HG4F-JT22ΔF-*
(Pan
el T
hick
ness
)
3 Main Unit Specifications
4-13
Chap.4
3.4 Function Specifications
Number of screens
Base Screens: 3,000 screens Popup Screens: 3,000 screens
Screen memory
Approx. 6Mbyte max.(Flash memory)(including the optional fonts)
Screen types Base Screen, Popup Screen, System Screen
Number of parts
480/screen (Base Screen) 480/screen (Popup screen)
Number of host devices
256 read, 512 write/screen (Base Screen) 64 read, 128 write/screen (Popup Screen)
Parts Bit Button Word Button Goto Screen Button Print Button Key Button Multi Button Keypad Selector Switch Potentiometer Numerical Input Character Input Pilot Lamp Multi-State Lamp Picture Display Message Display Message Switching Display Alarm List Display Alarm Log Display Numerical Display Bar Graph Trend Chart Pie Chart Meter Calendar Bit Write Command Word Write Command
Goto Screen Command Print Command Screen Script Command Multi Command Timer
Operation modes
Run Mode: Normal operation
Data Transfer Mode: Data upload and download
System Mode: Initial setting, clock setting, system information, self diagnosis and debug
Screen creation andoperation settings
WindO/I-NV2 software application
Calendar Year, Month, Day, Hour, Min., Sec. and Day-of-week +/-30 sec. per month (at 25°C)
Power failuremaintenance
Maintenance object: Calendar, Alarm Log Data: 1024 points (max.), Data Log Data: approx. 3000 points (max.), and 1024 keep internal relay/1024 resister Maintenance period: 1 month (at 25°C)
Chapter4 Specifications of HG3F/4F
4-14
3.5 Display Specifications
Display Functions
Display HG3F: 10.4 inch TFT color LCD (transparent type) HG4F: 12.1 inch TFT color LCD (transparent type)
Effective display area
HG3F: 211(W) x 158(H) mm HG4F: 246(W) x 184(H) mm
Display resolution HG3F: 640(W) x 480(H) dots HG4F: 800(W) x 600(H) dots
Pixel pitch HG3F: 0.33(W) x 0.33(H) mm HG4F: 0.3075(W) x 0.3075(H)mm
Display colors 256
Contrast adjustment
Can be adjusted from the front touch panel
Size/ number
1/4 size: 8 x 8 dots/ HG3F: 80 characters x 60 linesHG4F: 100 characters x 75 lines
1/2 size: 8 x 16 dots/ HG3F: 80 characters x 30 linesHG4F: 100 characters x 37 lines
Full size: 16 x 16 dots/ HG3F: 40 characters x 30 linesHG4F: 50 characters x 37 lines
Double size: 32 x 32 dots/ HG3F: 20 characters x 15 linesHG4F: 25 characters x 18 lines
Character Display
Types 8 x 8 dots, 8 x 16 dot: English, Katakana, Symbols (JIS8 bit code), ISO-8859-1(European),
ANSI1250(Central European),
ANSI1257(Baltic), ANSI1251(Cyrillic)
16 x 32 dots, 24 x 48 dots, 32 x 64 dots: ISO-8859-1(European) 16 x 16 dot:
Japanese: 1st and 2nd standard JIS, Chinese, Korean, Taiwanese
32 x 32 dots: Japanese: 1st and 2nd standard JIS
Character attributes
Magnification: 0.5, 1, 2, 3, 4 and 8 (ver. and hor.) Attributes: Blink, reverse, bold, embossed
3 Main Unit Specifications
4-15
Chap.4
Types Line, rectangle, Polyline
polygon, circle, ellipse, pie,arc, polygon (3, 4, 5, 6, and8 sided), bitmap image andpaint
Line types
Solid, dotted, dashed, long dashed, long dashed dot andlong dashed dot dot
Line width
1,2,3 and 5 dots
Graphics Display
Graphic symbol attribute
Blink switch display between specified colors (1or 0.5 second period)
Presumed Life Of Display
HG3F: 100,000hours (min.)HG4F: 80,000 hours (min.)(at 25°C)
Backlight
Light Source Cold-cathode tube Presumed Life Of Back Light
Standard 50,000 hours* *Luminance drop to half after continuous lighting at room temperature
Replacement Possible Control Auto off
3.6 Operation Specifications
Touch Switches
Switch mechanism Touch switches Switch method Matrix resistive
film type Composition HG3F: 32 x 24
HG4F: 40 x 30 Operation force 0.2 to 0.8N Life 1,000,000 cycles min. Confirmation Electronic buzzer
3.7 Power supply Input Specifications
Wiring Wire: 0.75-2.0mm2(AWG18-14) Maintain separation between the inputwiring and the power, output and communications wiring.
Connector Terminal block 3P: M4 screw
Connector Pin Layout
Connector Pin Functions
Symbol Function + Power supply +24V DC - Power supply -24V DC
Function ground
Ground the functional ground terminal to ensure stable operation.
1 2 3
+
―
Chapter4 Specifications of HG3F/4F
4-16
3.8 Serial Interface1 Specifications
RS-232C
Electrical characteristics
EIA RS-232C compliant
Transmission speed
1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200bps
Synchronization Asynchronous Communication method
Half or full duplex
Control system Hardware control/none Protocol (1) PLC-link protocol for a variety
of PLCs and communication units(2) DM Link
Transmission distance
15m (5m when connected to a PLC programming port)
Connection format
1:1
RS-485 (422) Electrical characteristics
EIA RS-485 (422) compliant
Transmission speed
1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200bps
Synchronization Asynchronous Communication method
Half or full duplex
Control system Hardware control/none Protocol (1) PLC-link protocol for a variety
of PLCs and communication units(2) DM Link
Transmission distance
300m (5m when connected to a PLC programming port)
Connection format
1:1 or 1:N
Only one of the RS-232C or RS-485 (422) ports can be used at one time.
Connector
Connector D-sub 25P connector (socket)
Connecting and disconnecting cycles
500 cycles (min.)
Connector Pin Layout
3 Main Unit Specifications
4-17
Chap.4
Connector Pin Functions
No. Name Function 1 FG Frame Ground 2 SD Send Data (RS-232C) 3 RD Receive Data (RS-232C) 4 RS Send Demand (RS-232C) 5 CS Clear to Send (RS-232C) 6 --- --- 7 SG Signal Ground 8 --- --- RS-485 RS-422
9 TERM Terminator*1 TERM Terminator*1
10 RDA Receive Data A RD+ Receive Data (+)
11 SDA Send Data A SD+ Send Data (+)12 --- --- --- --- 13 --- --- --- --- 14 --- --- --- --- 15 SDB Send Data B SD- Send Data (-)
16 RDB Receive Data B RD- Receive Data (-)
17 --- --- --- ---
18 CS- Clear to Send (-)
19 RS- Request to Send(-)
20 ER Data Terminal Ready (RS-232C)
21 CS+ Clear to Send (+)
22 RS+ Request to Send (+)
23 --- --- --- --- 24 --- --- --- --- 25 --- --- --- ---
*1 To enable the 330Ω built-in terminator, connect terminal No.9 [TERM] and terminal No.10 [RDA/RD (+)] together.
3.9 Serial Interface2 Specifications
Electrical characteristics
EIA RS-232C compliant
Transmission speed
9600, 19200, 38400, 57600 and 115200 bps
Synchronization Asynchronous Communication method
Half duplex
Protocol Dedicated protocol Connector Mini DIN8P connector Connection and disconnection cycles
1000 cycles (min.)
Connector Pin Layout
Connector Pin Functions
No. Name Function 1 RS Request to send 2 ER Data terminal ready 3 SD Send data 4 RD Receive data 5 DR Data set ready 6 EN Use as needed 7 SG Signal ground 8 NC No connection
Connect pin 6 (EN) and pin 2 (ER) unless performing maintenance communications for downloading project data.
6
3
4
78
5
2 1
Chapter4 Specifications of HG3F/4F
4-18
3.10 Expansion Interface
Specifications
Method Dedicated Interface to Expansion Unit
Compatible Unit Digital I/O unit Electrical characteristics
HG Series dedicated bus
Connector Dedicated connector
Outline
The HG3F/4F can be used in conjunction with optional units. Refer to the Expansion Unit instruction manual for details.
3.11 O/I link Interface Specifications
Method Dedicated interface to O/I link Unit
Connector Dedicated connector Recommended cable
0.3mm2 Twisted-pair shielded cable Conductor resistance:85Ω/km maximum Shield resistance:20Ω/km maximum
Outline
The HG3F/4F Operator Interface can be connected to an O/I Link Unit for 1:N communication with a PLC. This allows high-speed communication with the PLC host.
3.12 Ethernet (LAN) Interface
Specifications
Internet Specification: IEEE802.3 standard compliance Network Type: 10BASE-T Connector: RJ-45 modular jack
Connector Pin Layout
Connector Pin Functions
Pin # Name Function 1 TDP Transmit data+ 2 TDM Transmit data- 3 RDP Received data+ 4 NC No connection 5 NC No connection 6 RDM Received data- 7 NC No connection 8 NC No connection
1 8
3 Main Unit Specifications
4-19
Chap.4
3.13 Compact Flash(CF) interface
specification
Interface specification:CFA* standard compliance Connector: 50-pin CF card connector
Connector Pin Layout
Pin No. Name Pin No. Name
1 GND 26 CD1# 2 D3 27 D11 3 D4 28 D12 4 D5 29 D13 5 D6 30 D14 6 D7 31 D15 7 CE1# 32 CE2# 8 A10 33 VS1# 9 OE# 34 IORD# 10 A9 35 IOWR# 11 A8 36 WE# 12 A7 37 IREQ# 13 VCC 38 VCC 14 A6 39 CSEL# 15 A5 40 VS2# 16 A4 41 RESET 17 A3 42 WAIT# 18 A2 43 INPACK# 19 A1 44 REG# 20 A0 45 BVD/SPKR# 21 D0 46 BVD1/STSC
HG# 22 D1 47 D8 23 D2 48 D9 24 WP_IOIS16# 49 D10 25 CD2# 50 GND
3.14 Parallel Interface Specifications
Electrical characteristics
Centronics interface compliant
Support ESC/P, PC-PR, PCL
The printer is initialized in the following cases.
• The HG3F/4F is turned off when connected to a printer that is on.
• The printer cable is disconnected and connected again while the HG3F/4F is off and the printer is on.
Connector
Connector D-sub 25P connector (socket) Connecting and disconnecting cycles
500 cycle (min.)
Connector Pin Layout
2550
Eject Bottom
26 1
Chapter4 Specifications of HG3F/4F
4-20
Connector Pin Functions
Pin No. Name Function 1 STRB Strobe 2 PD0 Data Bit 0 3 PD1 Data Bit 1 4 PD2 Data Bit 2 5 PD3 Data Bit 3 6 PD4 Data Bit 4 7 PD5 Data Bit 5 8 PD6 Data Bit 6 9 PD7 Data Bit 7 10 --- --- 11 BUSY Busy 12 --- --- 13 --- --- 14 --- --- 15 --- --- 16 INIT Reset 17 --- --- 18 SG Signal ground 19 SG Signal ground 20 SG Signal ground 21 SG Signal ground 22 SG Signal ground 23 SG Signal ground 24 SG Signal ground 25 SG Signal ground
Please perform the following wiring when HG3F/4F be connected with the printer. Refer to the printer instruction manual for details.
HG3F/4F
D-sub 25P Connector
Printer
Name Pin No.
Shielding Name
Shield Cover Shield
STRB 1 STROBE
PD0 2 DATA0
PD1 3 DATA1
PD2 4 DATA2
PD3 5 DATA3
PD4 6 DATA4
PD5 7 DATA5
PD6 8 DATA6
PD7 9 DATA7
BUSY 11 BUSY
INIT 16 INIT
SG 18-25 SG
4 Installation and Wiring
4-21
Chap.4
4 Installation and Wiring Be aware of the following when mounting the HG Series main unit and wiring it to the host unit.
4.1 Installation Location
Operating Environmental Considerations
To ensure reliable and safe operation of the equipment, avoid the types of installation locations listed below.
・ Places where there is a lot of dust, salt or iron
filings.
・ Places where the equipment will be splashed
with oil or chemicals.
・ Places where the equipment will be exposed to
direct sunlight.
・ Places where corrosive or flammable gasses
are present.
・ Places where vibration will be directly
transmitted to the equipment.
・ Places where condensation may occur due to
sudden temperature changes.
Ambient temperature considerations
・ Allow sufficient space for ventilation, and install
the equipment away from heat sources.
・ Allow at least 100mm between the HG3F/4F
and walls or other equipment.
・ If installing the HG3F/4F in a location where the
ambient temperature will exceed the allowed
rating, install cooling fans or air-conditioning
equipment.
・ The HG3F/4F has been designed to use natural
airflow for cooling when installed vertically. If
you install it using any other orientation, use
forced-air cooling, or lower the ambient
operating temperature.
4.2 Installation
Place the HG3F/4F in a panel cut-out and fasten with the attached mounting clips at four places to a torque of 0.4 through 0.6 N・m uniformly. Do not tighten excessively or unevenly, otherwise the HG3F/4F may be damaged. Take into consideration the viewing angle and switch operation factors when choosing the installation height.
If the installation screws are not installed so that they are at right angles to the panel, the unit may separate from the panel.
HG3F/4F
Panel Mounting Clip
Chapter4 Specifications of HG3F/4F
4-22
Panel Cut-out Dimensions [Dimension: mm]
HG3F-FT22∆F-* HG4F-JT22∆F-*
4.3 Wiring
Wiring Considerations
・ Do not install the HG3F/4F close to high-voltage
or arc-generating equipment (such as circuit
breakers etc.).
・ Install the unit at least 200mm from the high
input voltage of the power supply.
・ In the case of DC power supply models, keep
the distance between the unit and the power
supply as short as possible.
・ Use separate power supplies and wiring for
electromotive equipment and I/O equipment.
・ A host connection cable is provided with the
equipment. Please specify your requirement.
・ If you will use your own cable for connecting to
the host, ensure that the connector and wiring
are of the recommended type. Also, do not
exceed the recommended length for the
cable.
t = 2 to 5228±
0.5
302±0.5
t = 2 to 5258+1
332+1 0
0
4 Installation and Wiring
4-23
Chap.4
Wiring to the Power Supply Terminals
・ Terminal No. allocation is as follows.
Symbol Function + Power supply +24VDC - Power supply -24VDC
Function ground
・ Use applicable cables for wiring and
recommended ferrules, (made by JST ) as
follows:
Applicable cable -------- Twist the AWG14 to
18(0.75 to 2.0mm2)
Use V1.25-4(RAV1.25-4),V2-P4(JST)
considerable.
・ The tightening torque range is 1.0N.m to
1.3N.m.
・ Twist the AWG14 to 18(0.75 to 2.0mm2) power
supply wires as tightly together as possible,
and keep the wiring distance between the
power supply and the unit as short as
possible.
・ Function Ground and Signal Ground are
connected internally of HG3F/HG4F.
・ Use separate power supplies and wiring for
electromotive equipment and I/O equipment.
・ For safety purposes, connect Function Ground
terminal of HG3F/HG4F to earth ground.
・ Use an IEC60127-approved fuse of 1A on the
power line to meet voltage and current
requirements (recommended fuse: Littelfuse 5
x 20mm slow-blow type 218000 series Type
T). This is required when exporting equipment
containing the HG3F/4F to Europe.
Note: Special Conditions
・ If you decide to use a single power supply for
HG3F/4F with more than one external device,
take extra precautions.
Some external devices may produce electrical
noise and short circuit the entire system setup,
therefore, damaging the communication
circuit of HG3F/4F and non-isolated
Communication Device (i.e. PLC).
To prevent such damage, choose a proper
solution depending on your system setup.
・ Use a separate earth ground from the external
noise source device.
・ The wire for grounding should be thick and
short in order to direct the noise from the
noise source device to the earth ground.
・ Use a separate power supply from the external
noise source device.
・ Disconnect the Function Ground terminal of
HG3F/4F from earth ground. (Be sure to
check the EMC performance on your system
because if the Function Ground is
disconnected, it may decrease EMC
performance.)
・ Connect Function Ground terminal of HG3F/4F
and 0V of the Power Supply in order to direct
the noise to 0V. This will avoid the noise from
going through the communication circuit.
+
―
Chapter4 Specifications of HG3F/4F
4-24
・ Insert an isolator on the communication line of
HG3F/HG4F and the non-isolated
communication device (i.e. PLC) to prevent
damage.
Wiring Serial Interface 1
・ Use the recommended connector (connector:
JBZ-25P-90(JST), cover: J-C25-C2(JST)).
・ Perform the wiring in accordance with the
requirements of the communication method
used. This will minimize the influence of
external electrical noise and electrical noise
generated by the wiring itself. EMC evaluation
has not been done for the cables.
・ Use shielding for the cables, and install line
clamp filters near each end of the cable.
Example TDK: ZCAT2035-0930
5 Inspection Periodically inspect the HG3F/4F to keep it in the best operating condition at all times.
・ The HG3F/4F display screen and protective
sheet are easily damaged. Never attempt to
operate the unit with tools or other hard
objects.
・ To clean the display screen, wipe it with a soft
cloth moistened with a mild detergent or
alcohol. Never attempt to clean the display screen
using paint thinner, ammonia, strong acid, strong alkaline, or other powerful solvents.
・ Terminals and connectors
Check for loose screws, loose connectors and
damaged wiring.
・ Installation
Check the installation brackets and screws for
warping and looseness.