19
57 CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC ELIMINATION 4.1. INTRODUCTION TO p-q THEORY In 1983, a new theory for the control of active filters in three-phase power systems was proposed (Hirofumi Akagi et al. 2007). It is called Generalized Theory of the Instantaneous Reactive Power in Three-Phase Circuits or p-q Theory. It is initially developed for three-phase three wire systems and three-phase four-wire systems for compensation of harmonic pollution in the utility side. The neutral current compensation is also done by this theory. The compensation in the utility systems is done by the generation of reference compensation current using the three phase p-q theory (Peterson and Singh 2009). But in some cases of voltage imbalance in three phase systems due to harmonic voltages, the sinusoidal reference current for compensation is not generated for all the phases. This limitation in the three phase systems is overcomed by the introduction of single phase p-q theory. It uses simple calculations for deriving the reference current in all conditions of imbalances due to the power defects. The designing by using this theory is also efficient and flexible (Leszek and Czarnecki 2004). It can be used for compensation of both single phase and three systems.

CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

57

CHAPTER 4

INSTANTANEOUS p-q THEORY BASED

HARMONIC ELIMINATION

4.1. INTRODUCTION TO p-q THEORY

In 1983, a new theory for the control of active filters in three-phase

power systems was proposed (Hirofumi Akagi et al. 2007). It is called

Generalized Theory of the Instantaneous Reactive Power in Three-Phase

Circuits or p-q Theory. It is initially developed for three-phase three wire

systems and three-phase four-wire systems for compensation of harmonic

pollution in the utility side. The neutral current compensation is also done by

this theory.

The compensation in the utility systems is done by the generation

of reference compensation current using the three phase p-q theory

(Peterson and Singh 2009). But in some cases of voltage imbalance in three

phase systems due to harmonic voltages, the sinusoidal reference current for

compensation is not generated for all the phases. This limitation in the three

phase systems is overcomed by the introduction of single phase p-q theory. It

uses simple calculations for deriving the reference current in all conditions of

imbalances due to the power defects. The designing by using this theory is

also efficient and flexible (Leszek and Czarnecki 2004). It can be used for

compensation of both single phase and three systems.

Page 2: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

58

4.2 INSTANTANEOUS p-q THEORY BASED ACTIVE

REGENERATIVE FILTER

The single phase p-q theory is used for compensation of harmonic

pollution in the utility. This is based on a set of instantaneous powers defined

in time domain and it is used for getting real time control in both transient and

steady state conditions. This single phase p-q theory has an ability to generate

the sinusoidal current in the utility side under voltage imbalance conditions

due to power quality issues. Thus reference compensation current is derived

by this theory which will compensate the distorted voltages and currents. This

reference current can be used for tracking the switching of converters and thus

harmonics are reduced in the power supply.

The instantaneous phase voltage and current are v(t) and i(t)

respectively. Using the instantaneous space vector concept, the v(t) can be

represented as follows,

))t(sin(j))t(cos(VVe)t(v ))t((j

)t(jV)t(V ir (4.1)

)t(Vr and )t(Vi are the amplitudes of real and imaginary part of )t(v

Similarly current can be given as

)t(jI)t(I)t(i ir (4.2)

)t(Ir and )t(Ii are the amplitudes of real and imaginary part of

)t(i

Page 3: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

59

)t(p1

, )t(q1

are the single phase instantaneous active and reactive

powers. They are given by the equation as,

)]t(I)t(V)t(I)t(V[)t(piirr1

(4.3)

)]t(I)t(V)t(I)t(V[)t(qriir1

(4.4)

The matrix formation from the above equation is indicated as

)t(I

)t(I

)t(V)t(V

)t(V)t(V

)t(q

)t(p

i

r

ri

ir

1

1 (4.5)

The single phase p-q theory uses Clarke transform -

-

-

coordinate plane system is given by the equation

i

i

vv

vv

q

p (4.6)

The power components can be expressed as

p~pivivp (4.7)

p - Mean value of the instantaneous real power. It corresponds to

the energy per unit time that is transferred from the power source to the load.

It is the only desired power component that is to be supplied by the power

source.

p~ -Alternating value of the instantaneous real power. It is the

energy per unit time that is exchanged between the power source and the load.

q~qivivq (4.8)

Page 4: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

60

q - Mean value of instantaneous imaginary power

q~ - Alternating value of instantaneous imaginary power

The instantaneous imaginary power (q) corresponds to the power

exchanged between the system phases and there is no transference or

exchange of energy between the power source and the load. It is the

undesirable power component and should be compensated.

For eliminating the harmonics components of active ( p~ ) and

reactive power ( q~ ), the reference compensation current is calculated by

)q~q(

p~

vv

vv

i

i1

c

c (4.9)

-

coordinate plane system is given by the equation as

)q(v)p~(vvv

1i

22

*C,ref (4.10)

The instantaneous p-q theory based controller is implemented for

compensating the nonlinear loads (Vasco Soares et al. 2000). It continuously

tracks the changes of harmonics content in the utility and compensation is

provided. The implementation of this controller with ARHF is depicted in

Figure 4.1.

Page 5: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

61

Figure 4.1 Proposed ARHF with p-q theory based current controller

This controller determines the compensating current reference as in

equation and force the power converter (Leszek and Czarnecki 2007) to

synthesize accurately for having sinusoidal current at the source side. This

control strategy (Juraj Altus et al. 2005) makes the compensated current

proportional to the phase voltage, which resembles the waveform of pure

resistive load. It also eliminates the power oscillations (Joao Afonso et al.

2000). Thus p-q theory forms a very efficient basis for designing the

controllers of harmonic damping (Murat Kale and Engin Ozdemir 2005).

4.2.1 p-q theory based current wave shaper with High Pass Filter

For the same p-q theory based current controller implementation, a

High Pass Filter (HPF) is added as shown in the Figure 4.2.

Page 6: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

62

Figure 4.2 Proposed ARHF with p-q theory based current controller

and High Pass Filter

The main usage of this passive high pass filter is to improve the

damping performance of high order harmonics. So p-q theory based reactive

component of passive HPF is also derived in addition to the above reference

current derivation This derivation includes active, reactive and harmonics

component of nonlinear loads (Khadkikar et al. 2009).

For a single phase system with nonlinear load the load current can

be given as

)tnsin(2)t( nn,L1n

L ii (4.11)

Under normal circumstances the voltage at the PCC can be given as the

)tnsin(v2)t(v nPCCPCC (4.12)

Page 7: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

63

The HPF current can be represented as

)90tsin(i2)t(i n,hphp

(4.13)

From the above the instantaneous active power for nonlinear load

can be calculated as

)t(i).t(v)t(pLPCCL

LL

p~p (4.14)

And in the same way the instantaneous reactive power is given as

)t(i).t(v~)t(qLPCCL

LL

q~q (4.15)

Also the instantaneous reactive power of HPF is given as follows,

)t(i).t(v~(t)qhpPCChp

hphp

q~qLL

q~q (4.16)

where L

p , L

q and hp

p represent the constants and L

p~ , L

q~ and hp

p~

denote the variable component and )t(v~PCC

denotes the PCC voltage shifted

by 90º.

By obtaining the constant part in (4.13),(4.14),(4.15) the active

(iL,p),reactive (iL,q) and harmonics current (iL,h), components of nonlinear load

current and the reactive (ihp,q) components of passive HPF current can be

readily calculated as follows,

)t(uv

p2)t(i

PCC

L

P,L (4.17)

)90t(uv

q2)t(i

PCC

L

P,L (4.18)

)t(i)t(i)t(i)t(iP,LP,LLh,L (4.19)

Page 8: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

64

and

)90t(uv

q2)t(i

PCC

hp

q,hp (4.20)

where u(t) is the unit vector in phase with PCC voltage.

The generalized transfer function approach to harmonic filter

design is given below. The HPF impedance transfer function Hhp(s) can be

given in normalized form as

1S

Q

1)

S(

)1S

(S

A)S(Z)S(H

P

2

P

P

hphp (4.21)

hP

CA

1,

hPhP

0CL

1,

hP

hP

PL

R,

hP

hP

hPL

CRQ

w 0 p is the

pole resonant frequency and Q is the quality factor.

The passive HPF is tuned to 1.28 kHz of resonant frequency. The

inductor bypass resistor Rhp, is chosen to have desired high pass response and

The Q factor value is selected as 0.69 considering the required high pass

response over a wide frequency band.

The injected current transfer function Hcds(S) can be derived as

)S(Z)S(Z

)S(Z

)S(i

)S(i)S(H

Shp

hp

h

h,s

cds (4.22)

Thus the ARHF with this passive high pass filter combined to

mitigate the lower and higher order harmonics

Page 9: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

65

4.3 SIMULATION BY USING MATLAB

In the Indian context the following factors from load end can be

considered for the generations of higher-level harmonics. More use of solid

state power converters for industrial drives, use of arc and induction furnaces

for mini steel and non-ferrous metal plants, use of thyristors for locomotives,

especially for railways due to the massive electrification program and

extensive use of single phase electronics loads in domestic sectors are causes

for generation. Not only that the rapid use of energy conservation devices in

both domestic sector and industrial sector such as electronics chokes for tube

lights, electronics energy controllers for motors and electronics fan regulators

etc., also injects harmonics substantially.

This is due to the semiconductors used in those solid state

electronics. This type of loads draws current in a short pulse only during the

peak of the sine wave. Thus resulting in the high frequency harmonics which

are superimposed onto the fundamental 50Hz frequency. Thus the uneven

switching of the converters increase the harmonic pollution in the supply

systems and these types of loads are called as nonlinear loads.

The uneven switching of the nonlinear converter loads injects the

harmonics and thus causes distortions in the electric power supply. The

current and voltage waveform distortion mainly depends upon the size of the

nonlinear loads and its source impedance. The amount of distortion increases

as the percentage of nonlinearity increases. So the uneven switching of

converters with their distortions is modelled using MATLAB. The converters

like single phase full bridge rectifier and single phase half bridge rectifier are

used as loads. The harmonics produced by these loads are controlled by single

phase H bridge regenerative rectifier which gives four quadrant

characteristics.

Page 10: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

66

In this modelling, the single phase full bridge and half bridge

rectifier is considered as nonlinear load 1(NL1) and nonlinear load 2(NL2).

The simulation circuits for nonlinear load 1 and 2 (Joorabian et al. 2011) are

given in Figure 4.3 to 4.6. The p-q theory based current controller is

implemented for both loads. Figure 4.3 gives the simulated circuit of NL1

without high pass filter and Figure 4.4 gives the circuit of NL1 with high pass

filter. In the same way simulation is also done for NL2 without and with HPF

(Figure 4.5 and 4.6). Figures 4.7 and 4.8 give the affected source current due

to NL1& NL2.The distorted source due to the uneven switching of NL2 is

given in Figure 4.8. Figure 4.9 and 4.10 show the source current waveforms

without any compensation controllers. The total current harmonic distortion

(THDi) for both loads are given as,

NL1 is 89.54% and

NL2 is 190.55%.

Figure 4.3 Simulated Nonlinear Load 1 with p-q theory based

controller & without HPF

Page 11: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

67

Figure 4.4 Simulated Nonlinear Load 1 with p-q theory based

controller & with HPF

Figure 4.5 Simulated Nonlinear Load 2 with p-q theory based

controller & without HPF

Page 12: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

68

Figure 4.6 Simulated Nonlinear Load 2 with p-q theory based

controller & with HPF

The two cycles of the source current are taken for analysis. The FFT

harmonic profiles are also shown for that selected signal. Figure 4.11 and 4.12

gives the two cycle FFT window and its profile due to the addition of NL1 with

source. The FFT window of the utility current due to NL2 is given in Figures

4.13 and 4.14. The results after the use of the active regenerative harmonic

filter with p-q theory based current compensator without HPF is given in

Figures 4.15 and 4.17 for both loads. After the usage of HPF further harmonic

mitigation is done for both loads and it is shown in Figures 4.16 and 4.18.

Page 13: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

69

Figure 4.7 Source current due to Nonlinear Load 1

Figure 4.8 Source current due to Nonlinear Load 2

Page 14: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

70

Figure 4.9 FFT analysis of uncompensated Nonlinear Load 1

Figure 4.10 FFT analysis of uncompensated Nonlinear Load 2

Page 15: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

71

Figure 4.11 Two cycle FFT window (NL1 source current)

Figure 4.12 FFT profile (NL1 source current) THDi=89.54%

Page 16: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

72

Figure 4.13 Two cycle FFT window (NL2 source current)

Figure 4.14 FFT profile (NL2 source current) THDi=190.55%

Page 17: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

73

Figure 4.15 Harmonics spectrum for NL1 with p-q theory based ARHF

& without HPF

Figure 4.16 Harmonics spectrum for NL1 with p-q theory based ARHF

& HPF

Page 18: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

74

Figure 4.17 Harmonic profile of NL2 with ARHF and without HPF

Figure 4.18 Harmonic profile of NL2with ARHF and with HPF

Page 19: CHAPTER 4 INSTANTANEOUS p-q THEORY BASED HARMONIC …shodhganga.inflibnet.ac.in/bitstream/10603/22887/9/09_chapter 4.pdf · the energy per unit time that is transferred from the power

75

The overall performance of regenerative filter incorporating p-q

theory based current controllers and HPF is given as

THDi (NL1) = 5.81%

THDi(NL2) =19.84%

4.4 SUMMARY

The single phase p-q theory for harmonic filtering is dealt in this

chapter. The power compensation leading to harmonic limitation derived from

p-q theory is analysed. In order to eliminate the higher order harmonics an

additional filter is also implemented. The usage of ARHF with the

application of p-q theory is explained with the simulation results. Thus the

harmonic cancellation by using the single phase p-q theory has different

functionalities as

Elimination of power oscillations

Improvement of power factor

Elimination of current harmonics

Harmonic damping.