Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
21
CHAPTER-2:
System Identification & Qualitative Fault Isolation of Hydrostatic Transmission
System.
2.1. Introduction
Hydrostatic transmission (HST) system [Watton,1989] consists of hydrostatic
pump, hydraulic motor and control mechanism; all combined in single housing, and are
operated together in a circuit made of solid pipes or flexible hoses. The output of the
transmission pump can be reversed, and both the direction and speed of motor rotation
can be controlled by direction control valve. Because of the fact that the hydraulic
power is easily started, stopped and controlled, hydrostatic drive can substitute clutch,
gear and shaft in power train, and also can produce infinite speed and torque changes
from full forward to full reverse.
This chapter is focussed on an open circuit hydrostatic transmission (HST)
system, for which a bond graph model is developed for system identification and also
for qualititave fault detection and isolation [Blanke et al. 2003, Simani et al. 2003]. For
the fault analysis, single fault is hypothesised; i.e. a single independent parameter of the
system may be faulty at a time.
Although there have been extensive research on modeling and simulation
[Manring & Luecke, 1998] and failure monitoring [Chinniah et al. 2006] of hydrostatic
transmission systems, to the knowledge of the authors there are little works on the
model-based qualitative fault diagnosis of hydrostatic systems using fault tree and
temporal causal graph (TCG) [Hogan et al. 1996, Hogan et al. 1992]. An analogous
type of system was modelled [Dasgupta et al. 2006] in which dynamic behaviour was
studied through simulation and then it was experimentally validated. But in that
literature neither system identification problem nor FDI analysis was described, which
is addressed in this work.
2.2. Hydrostatic Transmission System:
2.2.1. System Description:
The setup is a typical hydrostatic transmission system with pump loading. It
comprises of a hydraulic power pack, a hydraulic motor with a control valve, a pump
22
with loading circuit and a PLC operated Control Panel. The pictographic view of the
hydraulic transmission system is shown in Fig. 2.1. The circuit diagram of this system
is shown in Fig. 2.2 and bill of materials is given in Table 2.1.
(a) (b)
Fig.2.1: Pictographic view of the set-up installed in ISM,as viewed from different angle.
Fig.2.2: Circuit diagram for the system
23
Table 2.1
Bill of Material
31 Electrical control panel STD SHPL 01
30 Hose 3/8” BSP MARKWELL 06
29 Ball valve 3/8” BSP HYDAC 01
28 Pressure relief valve DPRH 06 T 100 POLYHYDRON 01
27 Pressure relief valve DPRH 06 S 315 POLYHYDRON 01
26 Direction control valve 4DE 06D DSA 220-01-3 POLYHYDRON 01
25 Check valve C 06 S1 03 POLYHYDRON 04
24 Pressure transmitter S10-250, 4-20 ma, 0~200 BAR WIKA 01
23 Hydraulic pump 1 RC 7C (8.6 LPM) POLYHYDRON 01
22 Coupling HYDAX 19 HYDAX 01
21 Hydraulic motor 8 CC M+S 01
20 Pressure transmitter S10-250, 4-20 ma, 0~200 BAR WIKA 01
19 Pressure transmitter S10-250, 4-20 ma, 0~200 BAR WIKA 01
18 Throttle cum check
valve
TCT-10 HYLOC 01
17 Throttle cum check
valve
TCT-10 HYLOC 01
16 D.C. valve 4WE 6E/6X G24V DC REXROTH 01
15 Pressure gauge 0~280 BAR ‘G’ Filled, 1/4”
BSP, 4” Dial
WIKA 03
14 Needle valve ¼”BSP STD 01
13 Pressure reducing
valve
DPMS-06 S A 200 POLYHYDRON 01
12 Pressure relief valve DPRH 06 S 315 POLYHYDRON 01
11B Coupling HYDRAX 19 HYDRAX 01
11A Bell housing SH4284-01-52-3 HYDAXA SHPL 01
10 Electrical motor 0.75KW (1 HP),1450
RPM,420V
LHP 01
09 Hydraulic pump (Gear) 7 LPM (5 cc/rev) DOWTY 01
08B Coupling HYDAX 38 HYDAX 01
08A Bell housing SH4284-01-53-3 SHPL 01
07 Electrical motor 5KW (7.5 HP),1450 RPM, 420
V
LHP 01
06 Hydraulic pump 15 LPM (12 cc/rev) HAWE 01
05 Suction strainer SC3-007 HRDROLINE 01
04 Suction strainer SC3-010 HRDROLINE 01
03 Filler breather FSB 25 HRDROLINE 01
02 Oil level indicator LG2-10 HRDROLINE 01
01 Oil reservoir 100 Lts SHPL 01
Tag Description Specifications/Model code Make Qty
24
A solenoid operated Direction Control valve (DCV) is used to control the flow
direction, while flow control valves (FCV) are used to control the flow quantity. The
load on the system can be varied with a Pressure Relief Valve (PRV). The fluid
pressures at the inlet and outlet side of the motor (motor is item No. 21 in Fig. 2.2) and
outlet side of the pump (item No. 23 in Fig. 2.2) are measured by pressure transducers
(Pmi, Pmo and Ppp represent those measured signals respectively) and speed of the motor
(ωm) is also measured by speed sensor and finally the data are transmitted to PC for
further analysis and signal processing through DAS mounted inside the control panel.
2.2.2. Modeling of the system:
The bond graph model of the system is shown in Fig. 2.3. In the formulation of the
model the following assumption were made:
Fluid inertia is neglected
The fluid has Newtonian characteristics.
Lumped Resistive and capacitive effects are used wherever appropriate.
In Fig. 2.3, the source of effort, Se1 is the pressure source Psupl (N/m2) from the
hydraulic power pack. Likewise, Se14 represents the outlet pressure Ps (which is the
atmospheric pressure in this case). In this study, square-root type nonlinearity is
imposed to model all the Direction Control valves (DCV) and Pressure Relief Valves
(PRV) as given in equation 2.1 in its general form.
. 2( )
( ) (2.1)
d
PQ C A sign P
k P sign P
Where, .
Q is the volume flow rate of oil in m3/sec. Cd is the coefficient of
discharge assumed to be unchanged. A is the port area (in m2) which is perturbed for
fault introduction. ρ is the density of oil, in Kg/m3.ΔP is the pressure differential
between upstream and downstream in N/m2. Sign ΔP is the sign function returns +1
when ΔP is positive and -1 when ΔP is negative.
25
Fig. 2.3: Bond Graph Model of System
The flows through DCV inlet and outlet are modeled as given in Equation 2.2
and 2.3 respectively.
milmilfi PPsignPPkSf supsup2 (2.2)
smosmofo PPsignPPkSf 15 (2.3)
Where kfi and kfo are the parameters related to coefficient of discharge at the inlet and
outlet of the DC valve, respectively.
The next zero junctions linked with 3,4,5,6,7,11 and 12,16,17,18,19,20 represent
the hydraulic motor inlet and outlet ports respectively. R13 shows the resistance cross-
port leakage while R6 and R17 stand for the resistances due to absolute leakage at the
inlet and outlet ports. The C elements, i.e C4, C18, are related to the compressibility of
the fluid with their values representing the bulk stiffness of the fluid. The transformer
accounts for the conversion of the fluid flow into mechanical rotation of the motor with
its transference value equal to the displacement of the motor Dm. The resistances R9 and
R22 show the friction due to the flow control valves that are installed in the fluid
26
pipeline. The elements R25 and I24 represent the frictional resistance to the shaft and the
total moment of inertia of all the rotating devices respectively.
Proceeding further to the secondary (loading) circuit, the two transformers
represent the displacement of the pump while C31 accounts for the bulk modulus of the
fluid just like C4 and C18. The flow through the PRV (item No. 27 in Fig. 2.2) is written
as:
bpppbpppp PPsignPPkSf 33 , (2.4)
Where, Pbp is the pressure maintained by the booster pump in the secondary (loading)
circuit.
The state equations obtained from the bond graph model (Fig. 2.3) are given in
equations 2.5-2.8:
01
supsup
pm
mi
ipl
momi
lkg
mi
mmmilmilfiK
P
R
PP
R
PDPPsignPPk
(2.5)
02
pm
mo
ipl
momi
smosmofo
lkg
mo
mmK
P
R
PPPPsignPPk
R
PD
(2.6)
0pp
pp
bpppbppppmpK
PPPsignPPkD
(2.7)
0121 mbppppfblblmmomim JPPDRRRPPD (2.8)
For estimation of unknown parameters nonlinear regression analysis was done
with steady state consideration and following assumptions.
The bulk modulus of the fluid remains same at all the pressures due to
Newtonian behaviour, i.e. pmpppmopmi KKCKCKC 31184
27
The effect ofR9 and R22 is cumulative and hence their sum i.e. R9+R22 is
important mathematically. Therefore it is chosen
that blblbl RRRRR 22219
The fluid comes out of the motor with the same flow rate as it has entered.
Hence mD 21 . Similarly, pD 43
The parameter related to coefficient of discharge of orifice in the DC valve
inlet and outlets are same, i.e. ffofi kkk .
Leakage resistances at suction and delivery side of the hydraulic motor are
same, i.e. lkglkglkg RRR 21 .
2.3. System Identification:
2.3.1. Nonlinear Regression Analysis:
The following activities were done during experimental study and data acquisition:
The values of mppmomi PPP ,,, (refer Fig. 2.3) were recorded for different loads
on the system.
The load on the system was altered by changing the set point of the pressure
relief valve.
The supply pressure from the power pack was maintained at constant value of 35
bar by adjusting the Pressure Reducing Valve.
Data were recorded only after allowing the system to reach a steady state for
every value of load.
The unknown parameters were found by nonlinear regression analysis [Huang et
al. 2010, Argyrous, 2010]. The estimated parameters were used to identify the kp value
corresponding to each position of the pressure relief valve. The assumption underlying
nonlinear regression is that the model can be approximated by a linear function, given in
Eq. (2.9).
28
j
jiji Jfxf 0, , (2.9)
Where, the function f (..) is defined by each of the Eq. (2.5)-(2.8), 0f the initial
guess, xi the measured states,
j
iij
d
xdfJ
, , and is the unknown set of parameters.
It follows from this that the least squares estimators are given by
yJJJ TT 1 . (2.10)
SPSS non-linear regression package [Argyrous, 2010] was used for this
estimation. All the estimated unknown parameters, and known parameters (provided by
manual) are listed in Table 2.2.
TABLE 2.2
LIST OF PARAMETERS
Parameter Value
Displacement rate of motor, Dm 7.96×10-6
m3/rad
Displacement rate of pump, Dp 1.00745×10-6
m3/rad
Supply pressure, Psupl 3.5×106 Pa
Booster pump pressure, bpP 1.00×106 Pa
Resistance to leakage, Rlkg 6.4779×1016
N.s.m-5
Resistance to cross port leakage, Ripl 16.97088×1018
N.s.m-5
Frictional Resistance to rotation of shaft Rf 1.59154×10-3
N.s.m/rad
Frictional Resistance to the fluid, Rbl 4.758732×10-2
N.s.m/rad
Parameter related to coefficient of discharge
of orifice in the DC valve, kf
0.3226×10-5
kg-0.5
.m3.5
Aggregate moment of inertia of motor pump
combination, J1
1×10-3
kg.m2
Bulk modulus of fluid, Kpm 1×1014
Pa
Parameter related to coefficient of discharge
of orifice in the PRV, kp
4.41x10-8
kg-0.5
.m3.5
29
The values of the parameters, Dm, Dp, and Kpm were obtained from the manual,
and Psupl, Pbp were set at the value given in the Table 2.2. The value of J1 was chosen
suitably as the actual value could not be estimated by steady state analysis of the
system. This assumption would have an effect to the transient characteristics of the
model. However, the behaviour of the system would remain the same at steady state.
Rest of the parameter values were obtained through regression analysis [Draper &
Smith, 1998, Seber & Wild, 1989] using SPSS software [Argyrous 2010].
2.3.2. Validation of System Identification:
The readings from the three pressure sensors Pmi, Pmo, and Ppp and one speed
sensor (ωm or RPM) were recorded at steady state from numerous run of the physical
system at different pump loading, by modulating the set point of PRV in loading circuit.
To compare the system’s response with that from the model, the bond graph model
(Fig.2.3) was transformed to block diagram, as given in Fig. 2.4, and simulated in
MATLAB-Simulink. In the block model (Fig. 2.4), a step function was added inside the
shaded oval (Fig. 2.4) to vary kp (similar to PRV set point modulation in real system),
and then the mean fluid pressures at three tapping points were observed from simulation
at different RPM, when steady state condition reached. Both the data from the real
system experimentation and model simulation are plotted in common scale and shown
in Fig. 2.5-2.7. The figures show that the simulation results are closely matching with
the experimental results. But the experimental data are discreet; because those were
recorded for finite number of run of the system.
The average error and Root Mean Square (RMS) error were calculated as given
in tabular form in Table 2.3. A negative error shows that the simulated value is less than
the experimental value while a positive error indicates that the experimental value is
less than the simulated value. The error percentage is less than 5% for all the four states,
which measures the accuracy of the system identification.
The identified model thus obtained is now the replica for the original system. So
this model has been used for FDI analysis. In this chapter, special importance is given
on qualitative FDI analysis for different hypothesized faults imposed in the real system.
Bond graph model is used for some prediction viz-a-viz fault detection, which has been
validated through model simulation and experimentation.
30
Fig.2.4: The Plant Model
Fig.2.5: Comparison of Experimental
& simulation values of Ppp
Fig. 2.6: Comparison of Experimental
&Simulation values of Pmo
Fig. 2.7: Comparison of Experimental
& Simulation values of Pmi
31
TABLE: 2.3
COMPARISON OF EXPERIMENTAL AND SIMULATION DATA
Variable Average Error RMS Error
Pmi -0.123 % 0.172%
Pmo 2.99% 3.71%
Ppp -2.21% 2.83%
RPM 1.52% 1.82%
2.4. Qualitative FDI Using Fault Tree:
A Fault tree is a logic tree that propagates events, like a qualitative change in
value. For creating a fault tree one starts off with an effect level event. One then
logically proceeds through the fault tree connecting the events. The tree is extended in a
manner till one reaches a cause event which need not be further explored. In order to
construct a fault tree firstly a list is prepared with the effecting (antecedents) and the
affected (consequences) parameters or the power variables at each junction of bond
graph. The variables corresponding to a strong bond becomes the affected one while the
variables and parameters corresponding to all the other weak bonds become effecting
ones or the antecedents. This list is then used to construct a fault tree by searching for
all the antecedents corresponding to a given consequence. The antecedents and
consequences for the concerned hydrostatic system are obtained from the system bond
graph model (refer Fig. 2.3), and are given in Table 2.4.
The tree diagram is now constructed by searching for all the probable antecedents
for an observed consequence. Since, the antecedents obtained from Table 2.4 are the
consequence of some other antecedents from the same table; the diagram continues to
expand like a branch of a tree. A negative sign in the antecedent indicates that it bears
an inverse relationship with the consequence. In each of the fault trees the sign in the
superscript denotes the direction of change in the parameter value. The tree then
proceeds logically to other elements. Fault Tree diagrams for the causes for change in
Pmi, Pmo, Ppp and ωm are shown in Fig. 2.8, Fig. 2.9, Fig. 2.10 and Fig. 2.11 respectively.
The fault tree of Pmi has shown in complete, whereas the fault trees of Pmo, Ppp and ωm
are expanded up to the parameter kp (highlighted in shade), the discharge coefficient of
PRV (item No. 27 in Fig. 2.2), for the sake of brevity.
32
TABLE 2.4: THE ANTECEDENT-CONSEQUENCE CHART FOR THE HST SYSTEM
No Antecedents
Consequences Parameter Power variables
1 Psupl e1
2
e2 f2
3 f2 f1,f3
4 e1,-e3 e2
5 e4 e3,Pmi,e6,e7,e11
6 Kpm f4 e4
7 f3,-f7,-f6, -f11 f4
8 Rlkg-1
e6 f6
9 e11,-e12 e13
10 Ripl-1
e13 f13
11 Kpm f18 e18
12 Rbl2 f22 e22
13
e8,-e9 e10
14 e21,-e22 e23
15
e10,-e23,-e25,-e26, e27 e24
16 J1-1
e24 f24
17 f24 f10, f23, f25, f26, f27
18 Rf f25 e25
19 Dp e29,f26 e26,f29
20 e35,f27 e27,f35
21 f12,-f16,- f17,f20 f18
22 e18 Pmo,e16,e17,e20,e12
23 Ps -e14
24 e14, e16 e15
25
e15 f15
26 f15 f14, f16
27 Dm f21,e20 f20, e21
28 Dm f8,e7 f7,e8
29 Rbl1 f9 e9
30 f10 f8,f9
31 f23 f21,f22
32
f29 ,-f32 f31
33
Fig. 2.8: Fault tree for Pmi
34
Fig. 2.9: Fault tree for Pmo
Fig. 2.10: Fault tree
for Ppp
Fig.2.11: Fault tree
for ωn
From the tree diagrams (Fig. 2.8-2.11), it can be inferred that any decrease (-ve)
in kp with all the other parameters kept unaltered, increases Pmi (+ve), decreases Pmo
(–ve), increases Ppp(+ve) and decreases ωm(–ve). Actually when Pmo is +ve, kp is +ve
(refer Fig. 2.9); conversely when kp goes –ve, Pmo decreases (-ve).
This has been validated though experimentation by switching off the bypass line
DCV (item No. 26 in Fig. 2.2) at a time of 80 s, thereby forcing the flow to pass through
the pressure relief valve (item no.27 in Fig. 2.2) with higher restriction or lower the
parameter related to coefficient of discharge (kp : –ve). The data archived through the
DAS to PC are plotted in Fig. 2.12, which shows the variation of the measured states as
per the prediction made by using Fault Tree.
The time responses of the measured states i.e. Pmi, Pmo, and Ppp and m , obtained from
simulation of block model (Fig.2.4) are given in Fig.2.13. In that simulation, the value
of kp is modulated by halving the step output from initial value to final value at step
time 80 s so that 50 % blockage in PRV is introduced at that time. The simulation result
35
is found in good agreement with the experimental observation both during healthy
condition and after blockage in PRV (item No. 27 in Fig. 2.2) in loading circuit was
introduced.
Fig.2.12: Variation of measured states Pmi, Pmo, Pppandωn both in
normal and faulty condition (Experimental).
Fig.2.13: Variation of measured states Pmi, Pmo, Ppp and ωn both in
normal and faulty condition (Simulation).
36
2.5. Qualitative FDI Using Temporal Causal Graphs:
Fig. 2.14: Linearized bond graph model of the system
Causal graphs are a type of linear graphs, which represent the model structure by
linking various nodes representing variables in the model. The directed edges in the
graph are used to represent constraints corresponding to various passive elements in a
bond graph model (I, C, R and also TF and GY); whereas additive constraints are
represented at the nodes. Temporal causal graph (TCG) [Mostermann and Biswas,
1999] is a special class of causal graphs, in which temporal evolution of variables are
represented qualitatively by accounting for the storage elements encountered in the
causal path. Since TCG is not applicable to nonlinear system model so the BG model
given in Fig.2.3 is linearised by replacing square root type nonlinear representation of
all the valves with linear resistances. The linearized BG model is shown in Fig.2.14.The
linear resistances can be found out by the following way.
37
For same flow rate in DCV
in
mil
milfR
PPPPk
i
sup
sup )(
(2.11)
In Eq. (2.11), estimated value ofif
k is used to find out inR which is equal to
1.386 x 108m
4s
-1N
-1/2.In the same manner the value of outR and plR are found out as
1.386 x 108m
4s
-1N
-1/2 and 5.99 x 10
10 m
4s
-1N
-1/2 respectively.
Temporal causal graphs have a strong similarity to signal flow graphs and thus
they are easily constructed from bond graph models using the method for creating signal
flow graphs. The '1/s' terms in frequency domain representing Laplace transform of
integration with respect to independent variable t (time) are represented as integrals in
temporal causal graphs. The integration with respect to time corresponding to integrally
causalled storage elements introduces delay[Ghiaus 1999; Mosterman and Biswas 1999]
in the system’s response. This delay is depicted as 'dt' in temporal causal graph.
Similarly, 1/dt term is used to represent differentiation in edges corresponding to
storage elements in derivative causality.
The temporal causal graph can be traversed in both forward and backward
direction from an observed or hypothesized fault (in a signal or a parameter). The
backward propagation is used to construct the list of fault candidates, whereas the
forward propagation derives predictions for posteriori behaviour (time evolution)
corresponding to each of the hypothesized faults.
The temporal causal graph for the hydrostatic transmission system is shown in
Fig. 2.15. Let us now consider a fault scenario, whereby the measured pressure in
loading pump (i.e. Ppp) is found to be above its nominal value, i.e. in qualitative terms
e31+.
38
Fig. 2.15: Temporal Causal Graph for the Hydrostatic Transmission System
2.5.1. Hypothesis Generation:
Backward propagation, i.e. chasing the path opposite to the signal flow
direction, is used to produce the fault hypothesis, i.e. a list of fault candidates.
Backward propagation starts from the measurement node whose qualitative state is
available and terminates at parameters or conflicting nodes.
39
Fig. 2.16: Backward Propagation
When traverse back from, e31+ there is a single edge with gain kpp dt to the node
f31. Since e31 is qualitatively higher, it results that bulk modulus of fluid at outlet side of
pump is higher (kpp+) and/or f31 is higher (f31
+). When a parameter is encountered, the
propagation is completed for that branch. Then the back propagation continues for
remaining nodes, i.e. from f31+. The tree representing the back propagation is given in
Fig. 2.16. During back propagation, instantaneous edges are given precedence. This
means that if there are two backward edges from a node with two different orders of
delays and then those two branches meet somewhere else, i.e. they are parallel, and then
the branch with least order of delays is propagated first.
The generated fault hypothesis contains the list of fault candidates and their
likely qualitative state. Under single fault hypothesis, it is assumed that only one
parameter from the set (Kpp+, Rpl
+, Dp
+, J1
-, Rf
-, Dm
+, Rbl1
-, Rbl2
-, Kpmi
+, Kpmo
-, Rin
-, Rlkg1
+,
Rlkg2-, Ripl
+, Rout
-) has deviated from its nominal value. Then the objective is to find
which one parameter?
The very first step in isolating the fault candidate is reduction of dimension of
the set of initial fault candidates. This requires qualitative input from other sensors and
follows the principle similar to the fault tree analysis. In the next step, there are some
parameters that can be considered robust or at least robust to drift in a specific direction.
Considering that the observed deviation in measured signal is abrupt fault, and
not progressive fault and making pragmatic assumptions like the leakage or blockage
40
resistances and the pump displacement do not change, so the initial fault set can be
reduced to (Kpp+, Rpl
+, J1
-, Dm
+, Kpmi
+, Kpmo
-, Rlkg1
+, Ripl
+), which corresponds to the set
of parameters belonging to faulty components in the pump and motor.
2.5.2. Hypothesis Validation:
After the hypothesis generation next is its validation. In this analysis, single fault
hypothesis is considered, among the fault candidates, only one is faulty. Next it is
generated the qualitative trend (QT), i.e. magnitude, slope, and so on, of the output after
inception of the fault, considering each fault candidate one by one. The forward
propagation of the temporal causal graph yields predictions for future behaviour for the
set of measurements for a postulated fault. This prediction takes account of temporal
delays encountered during forward propagation.
Let us consider the fault hypothesis that the resistance in pump plenum has
increased (Rpl+). This can be achieved by switching off the bypass line DCV (item No.
26 in Fig. 2.2), thereby forcing the flow to pass through the pressure relief valve (item
no. 27 in Fig. 2.2) with higher restriction. Starting forward propagation (along the
direction of signal only) from the edge containing parameter Rpl leads to 3132 ff . At
this node, temporal edge (dt in forward path) is encountered and therefore effect on
consequent nodes is time delayed (due to integration). This implies derivative of e31 is
affected instead of its magnitude. This is represented as e31↑, where the number of
arrows represents the number of time delays encountered during forward propagation to
that node and the arrow direction represents the qualitative magnitude, i.e. ‘↓’ for ‘–’
and ‘↑’ for ‘+’.
Fig. 2.17: Forward Propagation
41
Normally, forward propagation is completed when predictions are presented for
a sufficiently higher order. The predicted temporal qualitative trend, also called
temporal signatures, corresponding to hypothesized fault Rpl+ is given in Fig. 2.17.
(a) (b)
(c) (d)
Fig. 2.18: Time response of outputs from sensors (Pmi, Pmo, Ppp, ωn) corresponding to 0.1s of
normal fault-free operation and 50% blockage in the PRV (item No. 27 in Fig. 2.2) thereafter
From TCG (Fig. 2.17), it can be predicted that for the blockage fault in PRV
(Rpl+) the steady state value of Ppp should increase (as e31+ ), that of Pmi (e4+ ) should
increase, Pmo (e18-) should decrease and ωm (f24-) should also decrease. Again, first
derivative (i.e. slope) increases for Ppp (e31). In case of Pmi (e4), first derivative
decreases, second derivative increases and then third derivatives decreases.Similarly the
qualitative states attributed to slope changes can also be observed for Pmo and ωm. The
variation of the states e4 (Pmi), e18 (Pmo), e31 (Ppp) and f24 (ωm) are obtained through
simulation as shown in Fig. 2.18, which is closely matching with the prediction made
through TCG in Fig. 2.17.
42
Note that the sampling period of the DAS (Data Acquisition System) for the
experimental setup is 4 secs. So the transient dynamics could not be validated through
experimentation.
2.6. Conclusions:
Experimental and simulation study in the context of system identification and
model based qualitative FDI were carried out on a hydrostatic transmission system. The
unknown system parameters are estimated offline though nonlinear regression analysis
and then assigned in the system model for simulation study and compared with the state
response of the real system. It is found that the response of the model with the estimated
parameters tracks that from the physical system with sufficient accuracy. Also, the time
response trend of states due to a blockage fault introduced in a PRV (item 27 in Fig.
2.2) in the physical system was observed matching with the responses from the model
simulation. Then this model was used for qualitative FDI through fault tree and TCG.
The prediction from fault tree analysis was validated through model simulation and
experimentation, while that of TCG could be validated through model simulation only.
In TCG, back propagation is used for hypothesis generation, which examines the
qualitative changes of different component parameters (+ or -) for qualitative change (+
or -) of measured state. Next, hypothesis validation is done using forward propagation,
whereby qualitative trend, i.e. magnitude (+ or -), slope ( or ) and temporal delays
due to integration of the states are predicted and matched with the measurement. Now,
assigned nominal parameter value is based on some measurement which contains some
inherent uncertainty. But, the qualitative changes of the states (+ or -) are not measured
quantitatively, thus the uncertainty component is ignored. So, it is difficult to fix a
threshold for the measurements within which the deviation is due to uncertainty and
beyond which the deviation is due to fault. Hence, the fixation of threshold is done
using quantitative FDI and LFT method, addressed in chapter 4 onwards.