43
19 CHAPTER 2 PROPOSED I- DETECTION ALGORITHMS FOR THREE PHASE SHUNT ACTIVE POWER FILTER 2.1 INTRODUCTION Nonlinear loads draw currents that are non-sinusoidal create voltage drop in distribution conductors. Typical nonlinear loads include rectifiers, variable speed drives, any other loads based on solid state conversion. These nonlinear loads will absorb reactive power from the source thereby distorting the source current waveform. The distorted source current will affect the power quality. Harmonic distortion is the production of harmonic frequencies by an electronic system when a signal is applied at the input and it is measured in terms of Total Harmonic Distortion (THD) which is a measure of power quality (Filipski et al 1994). Additional losses in the electrical distribution systems are caused by the harmonic currents. The Shunt Active Power filter (SAPF) is used as one of the remedies for the undesired characteristic of nonlinear loads which cause the problems due to harmonics (Riyadi et al 2007). The I-COS proposed for the SAPF to reduce THD of the source current.

CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

19

CHAPTER 2

PROPOSED I-

DETECTION ALGORITHMS FOR THREE

PHASE SHUNT ACTIVE POWER FILTER

2.1 INTRODUCTION

Nonlinear loads draw currents that are non-sinusoidal create

voltage drop in distribution conductors. Typical nonlinear loads include

rectifiers, variable speed drives, any other loads based on solid state

conversion. These nonlinear loads will absorb reactive power from the source

thereby distorting the source current waveform. The distorted source current

will affect the power quality. Harmonic distortion is the production of

harmonic frequencies by an electronic system when a signal is applied at the

input and it is measured in terms of Total Harmonic Distortion (THD) which

is a measure of power quality (Filipski et al 1994). Additional losses in the

electrical distribution systems are caused by the harmonic currents. The Shunt

Active Power filter (SAPF) is used as one of the remedies for the undesired

characteristic of nonlinear loads which cause the problems due to harmonics

(Riyadi et al 2007). The I-COS

proposed for the SAPF to reduce THD of the source current.

Page 2: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

20

2.2 SCHEMATIC DIAGRAM OF SHUNT ACTIVE POWER

FILTER

The configuration of Shunt Active Power Filter fixed in the

distribution network at the point of common coupling through filter

inductance is shown in Figure 2.1. Dai et al (2001) and Cirrincione et al

(2009) had focused on the analysis of single phase SAPF. The nonlinear load

current will have fundamental component and harmonic current

components, which is represented as given in equation (2.1)

(2.1)

If the shunt active power filter provides the total reactive and

harmonic power, source current is(t) will be in phase with the utility voltage

and would be sinusoidal. At this time, the active power filter must provide the

compensation current, = Therefore, the active power filter

estimates the fundamental component of the load current and compensates the

harmonic current and reactive power.

Figure 2.1 Configuration of shunt active power filter with nonlinear load

Page 3: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

21

The active power filter estimates the fundamental component of the

load current and compensates the harmonic current and reactive power.

2.3 IMPORTANCE OF MULTILEVEL INVERTER

The Multilevel Inverter (Rodriguez et al 2002) is used for high

power energy conversion. It does not need a coupling transformer to interface

it with high power system. The advantages of the Multilevel Inverter will

enable the circuit to operate with less output voltage harmonics and less

electromagnetic interference (Du et al 2004).

Multilevel Inverter with advanced control technique was introduced

by Brendan Peter McGrath & Donald Grahame Holmes (2002) for medium

and high power applications. Compared with the traditional two level voltage

source inverter, the Multilevel Inverter has the advantages of smaller output

voltage step, lower harmonic components, more electromagnetic

compatibility and lower switching losses. Multilevel inverters are the most

modern technology for medium to high voltage range which includes motor

drives, power distribution, power quality and power conditioning applications

(Vassillios et al 2008; Wenxi Yao et al 2008; Buso et al 1998; Wang & Chen

2004).

Ehagwat & Stefanovic (1983) and Tolbert et al (1998) had applied

Multilevel Inverter for the application of reduction of harmonics. The

Multilevel Inverter has a multiple of the usual six switches found in a three

phase inverter to synthesize a sinusoidal voltage from several levels of

voltages, typically obtained from the capacitor voltage sources. The main

motivation for such converters is that, the current is shared among these

multiple switches, allowing a high converter power rating than the individual

switch VA rating. As the number of level increases, the synthesized output

Page 4: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

22

waveform approaches a desired waveform with decreasing harmonic

distortion, approaching zero.

2.3.1 Classification of Multilevel Inverter

The Multilevel Inverters are classified according to the

configuration (Wang Liqiao et al 2004). The various types of Multilevel

Inverters are as follows:

Diode clamped inverter,

Flying capacitor

Cascaded H-bridge inverter.

Among the inverter topologies, the flying capacitor inverter is

difficult to be realized as each capacitor must be charged with different

voltages as the voltage level increases. Moreover, the Clamped inverter, also

known as a neutral clamped converter is difficult to be expanded to

multilevel, due to the natural problem of the DC link voltage unbalancing.

Table 2.1 shows the of power component requirements per phase

leg among three Multilevel Inverters where m is the number of levels over

one cycle. Ahmed et al (2007) and Ebrahim & Babaei (2008) discussed

cascaded multilevel Inverter which requires less number of components, that

makes cascaded multi level inverter more suitable than the others. As the

number of levels increase, the THD in the output voltage of inverter is

reduced accordingly but considering the complexity in control, packaging

problems of much high level inverters, a seven level inverter is chosen for the

present research.

Page 5: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

23

Table 2.1 Components for different configurations of multilevel inverter

Inverter Configuration

Diode-Clamped Multilevel Inverter

Flying Capacitors Multilevel Inverter

Cascaded Inverters Multilevel

Inverter

Switching devices 2(m-1) 2(m-1) 2(m-1)

Diodes 2(m-1) 2(m-1) 2(m-1)

Clamping diodes (m-1)(m-2) 0 0

DC bus capacitors (m-1) (m-1) (m-1)/2

Balancing capacitors 0 (m-1)(m-2)/2 0

The components required by the cascaded multilevel inverter for

particular level is less than other configurations. Hence the small size, low

cost and simple control circuit of cascade MLI are the attractive features.

2.3.1.1 Proposed Power Circuit of Seven Level Cascaded H Bridge

Multilevel Inverter for Shunt Active Power Filter

A Cascaded Multilevel Inverter consists of series of H-bridge

(single-phase full bridge) inverters, each with their own isolated DC bus. This

multilevel inverter generates output voltage almost sinusoidal waveform from

several separate DC sources. The individual source supply may be obtained

from solar cells, fuel cells, batteries and ultra-capacitors. This Multilevel

Inverter does not need any transformer or clamping diodes or flying

capacitors. Each level can generate three different voltage outputs +Vdc, 0 and

-Vdc by connecting the DC sources to the AC output side. The output voltage

of m-level inverter is the sum of all the individual inverter outputs. Each of

the H-

each H-bridge unit generates a quasi-square waveform by phase shifting its

Page 6: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

24

h switching

device always conducts for 180o regardless of the pulse width so that the

switching method results in equalizing the current stress in each active device.

This inverter is suitable for high voltage and high power inversion because of

its ability to synthesize waveforms with better harmonic spectrum and low

switching frequency (Vlviita & Ovaska 1998).

Fang Zheng Peng et al (1996) dealt with separate DC sources for

Multilevel Inverter for Static VAR Generation. The Cascaded H-bridge

inverter (Roozbeh Naderi & Abdolreza Rahmati 2008) has separate DC

sources. The modularized circuit layout and package are possible. The

problem of the DC link voltage unbalancing does not occur, thus easily

expanding to any level. Due to these advantages, the cascaded inverter bridge

has been widely applied to such applications as High Voltage DC

transmission, Static VAR Compensator, stabilizer, high power motor drive.

The following are the advantages of cascaded multilevel inverter:

Known to eliminate the excessively large number of bulky

transformers required by the multi-phase inverters, clamping

diodes required by the diode clamped Multilevel Inverters

and capacitors required by the flying capacitor Multilevel

Inverters.

Simple and modular configuration.

Flexibility in extending to higher number of levels without

undue increase in circuit complexity, simplified fault

finding, repair facilities and packaging.

Allows optimized cyclic use of power devices to ensure

symmetrical utilization, symmetrical thermal problems and

wear.

Page 7: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

25

Overall improvement in inverter performance and high

quality output voltage (Hossein Iman-Eini et al 2008).

Figure 2.2 Power circuit of seven level cascaded H bridge inverter

Three single phase units of seven level inverter has been

constructed and grounded separately for ease of control. Figure 2.2 shows the

power circuit of a seven level cascaded inverter composed of three full bridge

inverters connected in series on each phase. These three units collectively

form a three phase three wire shunt active power filter (Simone Buso et al

1998 and Shuai Lu et al 2007).

2.4 PROPOSED CONFIGURATION OF SHUNT ACTIVE

POWER FILTER WITH MULTILEVEL INVERTER

Shunt Active Power Filter acts as a current source adding equal but

opposite harmonic and quadrature components of load current at the point of

common coupling. In effect, the system views nonlinear load together with

active power filter as an ideal resistor. Three phase SAPF system

Page 8: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

26

(Rahmani et al 2006) is connected in the distribution network at the point of

common coupling through filter inductances and operates in closed loop.

Figure 2.3 illustrates the proposed configuration of shunt active power filter

with multilevel inverter. The nonlinear load is connected to the three phase

source.

Figure 2.3 Proposed configuration of SAPF with multilevel inverter

2.5 ANALYSIS OF UNCOMPENSATED THREE PHASE SYSTEM

The three phase supply system feeding nonlinear load is analysed

through simulation. The analysis is carried out with balanced as well as

unbalanced loads to evaluate the performance of the system without

compensation.

2.5.1 Simulation results of uncompensated three phase system with balanced load condition

The three phase balanced load is connected in the proposed three

phase system. The proposed system is simulated to analyse the performance

and quality of the power. The source voltage and source current before

compensation are shown in Figures 2.4 and 2.5 respectively.

Page 9: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

27

Figure 2.4 Source voltage of three phase system

Figure 2.5 Source current of the three phase system before compensation with balanced load condition

The source voltage waveform is pure sinusoidal waveform, but the

current is distorted due to the switching action of the nonlinear load. The

harmonic profile of the source current before compensation and its power

factor are shown in Figures 2.6 and 2.7. The current drawn from the source is

a quasi-square waveform having total harmonic distortion of 28.97% and

power factor is measured as 0.7257 lagging. The THD measured is

significantly above the allowable limit which affects the performance of the

equipment connected to the supply system.

Page 10: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

28

Figure 2.6 Harmonic profile of source current in uncompensated system with balanced load condition

Figure 2.7 Power factor of the three phase system before compensation with balanced load condition

2.5.2 Simulation results of uncompensated three phase system with

unbalanced load condition

In general the loads connected to three phase supply system are

unbalanced because of fluctuations in the connected load. Hence, it is

necessary to evaluate the performance of the system under unbalanced load

conditions before and after compensation.

Page 11: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

29

The three phase system is simulated in MATLAB/SIMULINK with

unbalanced load conditions. The three phase diode rectifier with RL load

connected in one phase will act as the nonlinear load and resistive load is

connected to the other phases. Unbalances is created in three phase load by

altering the load impedance of any one or two phases. The current drawn by

the three phase nonlinear load is a quasi-square waveform as shown in Figure

2.8 and its harmonic spectrum is also shown in Figure 2.9. From the harmonic

spectrum, the total harmonic distortion is measured as 29.35%

Figure 2.8 Source current before compensation with unbalanced load condition

Figure 2.9 Harmonic profile of source current in uncompensated system with unbalanced load condition

Page 12: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

30

Figure 2.10 Power factor before compensation with unbalanced load condition

The source current and voltage relationship before compensation

and the power factor is measured as 0.6932 lagging is illustrated in

Figure 2.10

2.6 NEW TIME DOMAIN APPROACHES FOR THE DESIGN

OF CASCADED H BRIDGE MULTILEVEL INVERTER

BASED SHUNT ACTIVE POWER FILTER

The performance of active power filter is dependent on two parts,

current control system and harmonic reference generation. The development

of compensation signals in terms of voltages or currents is the important part

of APF's control strategy which affects its ratings and transient as well as

steady state performance. Donghua Chen & Shaojun Xie (2004) introduced

the control strategies applied to SAPF which generates compensation signals

based on time domain or frequency domain. The frequency domain approach

uses the Fourier Transform and its analysis, which leads to a large amount of

calculations, making the control methods much more complicated. In the time

domain approach, traditional concepts of circuit analysis and algebraic

transformations associated with changes of reference frames are used,

simplifying the control task. One of the time domain control strategies is the

Page 13: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

31

instantaneous reactive power theory (PQ theory) which was proposed by

Akagi et al (1984), Chang & Shee (2004) and Herrera & Salmeron (2007).

Gabrio Superti Furga & Grazia Todeschini (2008) have dealt PQ

theory based on the time domain and the theory is for steady state and

transient operation. The control of APF in the real time, the simplicity of its

calculations are the main advantages.

Soares et al (2000), Haque (2002), Tarokh et al (2003), Dai et al

(2004) and Herrera et al (2008),) and explained the Instantaneous reactive

power theory applied to active power filter compensation. Gong et al (2002),

Gray et al (2004), Geng Wang et al (2004), Han et al (2005) Nair &

Bhuvaneswari (2006) and Ghandchi et al (2008) had studied the generation of

novel reference compensating current for analysis of Shunt Active Power

Filter with frequency domain approach, However, the performance of the

SAPF was not satisfactory and the result showed that the process is time

consuming The voltage source converters are used as the active power filter,

which has a DC capacitor voltage control as an energy storage device.

A single pulse for each half cycle is applied to synthesize an AC

voltage, for most of the application which shows dynamic performance. PWM

techniques applied to a voltage source inverter consist of chopping the DC

bus voltage to produce AC voltage of an arbitrary waveform. With PWM

techniques, the AC output of the filter is controlled as a current or voltage

source device.

2.6.1 Proposed I-

Compensating current

In the desired mains current is the product of real component of

load current (IL-

Page 14: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

32

with the mains voltage. The three phase supply is required to supply only the

active portion of the load current. The SAPF is expected to provide

compensation for the harmonic and reactive portion of the three phase load

current so that only balanced currents are drawn from mains, which are purely

sinusoidal and in phase with the supply voltage. The reference compensating

currents (Bhuvaneswari et al 2006a) are then derived as the difference

between the load currents and the desired source current. Assuming a

balanced source, the three-phase instantaneous voltages are specified in

equations (2.2), (2.3) and (2.4)

(2.2)

(2.3)

(2.4)

The balanced three-phase source supplies a nonlinear reactive load

with unbalanced load. The unbalanced, three-phase, reactive, harmonic-rich

load currents are expressed as given in equations (2.5) to (2.10).

(2.5)

(2.6)

(2.7)

(2.8)

(2.9)

(2.10)

Page 15: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

33

where , are Phase angles of fundamental currents in each

phase;

, and are Phase angles of nth harmonic currents in each phase;

, are Three phase fundamental current amplitudes;

, are Three phase nth harmonic currents amplitudes

The magnitude of the real component of the fundamental load

current in each phase is specified as in equations (2.11), (2.12) and (2.13).

(2.11)

(2.12)

(2.13)

To ensure balanced, sinusoidal currents at a unity power factor to

be drawn from the source, the magnitude of the desired source current is

expressed as the average of the magnitudes of the real components of the

fundamental load currents in the three phases are given in equations (2.14)

and (2.15).

(2.14)

(2.15)

Let Ua, Ub, and Uc be the unit amplitude of the phase-to-ground

source voltages in the three phases, as given in equations (2.16), (2.17)

and (2.18).

(2.16)

Page 16: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

34

(2.17)

(2.18)

The desired (reference) source currents in the three phases are

given as (2.19), (2.20) and (2.21).

(2.19)

(2. 20)

(2.21)

The reference compensation currents for the SAPF are thus

deduced as the difference between the actual load current and the desired

source current in each phase which is expressed in equations (2.22), (2.23)

and (2.24).

(2.22)

(2.23)

(2.24)

If the three-phase load currents are balanced, the reference

compensation currents will then essentially be the sum of the reactive

component of load current and the harmonic components in each phase which

are given in equations (2.25),(2.26) and (2.27).

(2.25)

(2.26)

(2.27)

Page 17: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

35

Figure 2.11 shows the simulink model for incorporating the

I-

current in each phase.

Figure 2.11 Simulink model of proposed I-

2.6.2 Role of DC Link Capacitor Voltage Balancing

The DC link capacitor voltage balancing is used to maintain the

capacitor voltage at constant value to effectively operate SAPF. The active

filter topology is essentially identical to that of an active rectifier, similar

control strategies for the active rectifier are applicable. The DC capacitor

voltage is directly affected by the real power transferred across the active

filter. To keep the voltage constant, ideally no real power should be

transferred. However, due to losses in switching devices and other

components, a small amount of real power is looked-for Sato et al (1997) and

Samir Kouro et al (2008). Figure 2.12 illustrates the DC link capacitor voltage

control circuit for the SAPF. Whenever real power flows into the active filter

to compensate for the losses, the DC link voltage tends to fluctuate Chandra

et al (2000) and Chudamani et al (2009). The voltage fluctuations at the DC

link capacitor of the SAPFs are used to calculate the extra power loss in the

Page 18: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

36

inverter and the interface transformer. The corresponding phase current

amplitude is calculated using a Proportional Integral (PI) controller. The loss

component is added to the magnitude of the reference compensation current

in each phase. This ensures that the losses in the SAPF are being taken care of

by the three phase source and the DC link voltage of the SAPF.

Figure 2.12 Block diagram of DC link capacitor voltage control circuit

2.6.3 Block Diagram of Filter Current Tracking Control

The filter current in each phase is continuously monitored to check

if it is tracking the reference compensation current. The filter currents are

continuously compared with the reference compensation currents and an error

signal is produced. This error signal is shaped to bring it within the linear

modulation range of the multilevel inverter. The error signal is fed into the

Page 19: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

37

multicarrier PWM circuit as modulating signal. Figure 2.13 illustrates filter

current tracking control scheme which is also called current control circuit.

The pulse pattern generated from the PWM circuit is suitably distributed to

trigger the switching devices of the inverter. The output currents generated is

resemblance with the reference compensation current commands in all

respect.

Figure 2.13 Block diagram of filter current tracking control

2.6.4 Simulink model of I- the design of Shunt

Active Power Filter

The I- for shunt active power filter is simulated in

MATLAB/SIMULINK. The nonlinear load is a three phase bridge rectifier

feeding R-L load. The simulation is carried out for various load conditions for

providing harmonic compensation, load balancing and reactive power

compensation. It is clearly seen that despite the fact that the load is nonlinear

reactive, the three phase currents drawn from the source are fairly sinusoidal

after compensation. The simulink model of three phase system feeding

nonlinear load is shown in Figure 2.14.

Page 20: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

38

Figure 2.14 Simulink model for seven level inverter for SAPF with balanced load condition

The SAPF generates the filter current using I-COS

simulation circuit consists of following five sections, namely

(i) Three phase balanced supply system

(ii) The nonlinear load, which is a diode rectifier feeding RL

load

Page 21: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

39

(iii) I- m based circuitry for reference

compensation current extraction

(iv) PWM circuit for generating the gate pulses of inverter

(v) A seven level inverter which generates the current required

for compensation. The diode rectifier absorbs reactive power

and non-sinusoidal current from the source while the SAPF

is not in action.

The simulink model for I-

compensating current. The simulation parameters used for the simulation and

their values are tabulated in Table 2.2.

Table 2.2 Simulation parameters with balanced load condition

Parameters Values

Supply phase voltage per phase 220 V(rms)

System frequency 50 Hz

Value of filter inductor 0.5 mH

Load impedance

Carrier frequency for PWM generation 10 KHz

2.7 RESULTS AND DISCUSSION

2.7.1 Simulation Results of SAPF using I- Algorithm with Balanced Load Condition

With the intention of reducing the harmonics, the SAPF is connected at point of common coupling (PCC). The reference compensating current generated using I- is shown in Figure 2.15.

Page 22: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

40

Figure 2.15 Reference compensating current using I-with balanced load condition

The resulting source current after compensation and its harmonic profile are shown in Figures 2.16 and 2.17. The close resemblance of the waveforms indicates proper working of the filter.

Figure 2.16 Compensated source current using I-balanced load condition

Under balanced load condition, the reference and filter currents are

similar in each phase except phase angle.

Page 23: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

41

Figure 2.17 Harmonic profile of source current using I-with balanced load condition

The total harmonic distortion of the source current is measured as 4.18% of the proposed I-improves the power factor.

The simulation is carried out with different load impedance values.

the Table 2.3 shows the variation of THD and the power factor of source

current for various values of load impedances and hence source current.

Table 2.3 THD and power factor for various values of source current with balanced load condition

S.No

Load Values

; L in mH

Source Current (Amps)

THD (%) Power factor

Before Comp.

After Comp.

Before Comp.

After Comp.

1 5 1.5 25.32 4.01 0.7725 0.9627 2 22.5 9.06 27.33 4.05 0.7505 0.9467

3 25 9.853 27.94 4.09 0.7363 0.9527

4 27.5 11 28.97 4.14 0.7257 0.9514

5 30 11.55 29.03 4.18 0.7138 0.9395

6 32.5 13.48 30.02 4.22 0.7047 0.9268

7 35 17.39 30.98 4.31 0.7012 0.9113

8 37.5 20.22 31.54 4.41 0.6982 0.9105

9 40 21.48 32.03 4.45 0.6911 0.9032

Page 24: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

42

From the Table 2.3, it is inferred that the I-

performs well for variable load also and generates reference compensating

current dynamically and maintains the THD and power factor irrespective of

the load impedance values. The Figures 2.18 and 2.19 explain the variation

of THD and power factor with respect to source current.

Figure 2.18 THD Vs Source current using I- balanced load condition

Figure 2.19 Power factor Vs Source current using I-with balanced load condition

0

5

10

15

20

25

30

35

0 5 10 15 20 25

THD

(%)

Source current (Amp)

Before compensation

After compensation

0

0.2

0.4

0.6

0.8

1

1.2

0 5 10 15 20 25

Pow

er fa

ctor

Source current (Amp)

Before compensation

After compensation

Page 25: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

43

2.7.2 Simulation Results of SAPF using I- Algorithm with

Unbalanced Load Condition

In general the three phase supply system is subjected to the unbalanced load

condition. This is because of the unpredicted loading of connected load and

demand. It is required to analyze the performance of SAPF with I-

algorithm for unbalanced load condition. The system with I-

based SAPF is simulated.

Figure 2.20 shows the Reference compensation current for

phase a . The reference compensating currents and filter currents for the

other phases are having different magnitude and phase angles depending upon

the values of load impedances.

Figure 2.20 Reference compensating current using I-with unbalanced load condition

Source current after compensation and its corresponding harmonic

profile are shown in Figures 2.21 and 2.22 with total harmonic distortion of

4.87%.

Page 26: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

44

Figure 2.21 Compensated source current using I-unbalanced load condition

Figure 2.22 Harmonic profile of source current using I-with unbalanced load condition

Figure 2.23 shows the source voltage and current waveforms after

compensation and power factor is measured as 0.8497 lagging.

Page 27: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

45

Figure 2.23 Voltage and current waveforms after compensation using I-

Various values of unbalanced load is connected to the three phase

system and the results are obtained from the simulation. The results are

investigated and produced in Table 2.4.

Table 2.4 THD and Power factor for various values of source current with unbalanced load condition

S.No

Load Values

30mH 30mH

La in mH

Source Current (Amps)

THD (%) Power factor

Before Comp.

After Comp.

Before Comp.

After Comp.

1 5 1.5 24.73 4.09 0.7478 0.7201 2 22.5 9.06 25.33 4.23 0.7425 0.8602 3 25 9.853 26.04 4.37 0.7308 0.8579 4 27.5 11 27.65 4.58 0.7299 0.8502 5 30 11.55 28.97 4.87 0.7257 0.8497 6 32.5 13.48 29.12 4.91 0.7157 0.8487 7 35 17.39 29.35 5.01 0.7038 0.8465 8 37.5 20.22 30.54 5.12 0.6926 0.8375 9 40 21.48 31.03 4.23 0.6911 0.8302

Page 28: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

46

The THD and power factor values are maintained constant with the required generation of compensating current by the control circuit based on I-algorithm. Figures 2.24 and 2.25 show the variation of THD and power factor with I- unbalanced load condition.

Figure 2.24 THD Vs Source current using I-unbalanced load condition

Figure 2.25 Power factor Vs source current using I- with unbalanced load condition 2.8 GENERATION OF REFERENCE COMPENSATING CURRENT USING SYNCHRONOUS DETECTION ALGORITHM In the Synchronous Detection (SD) Algorithm, the average real

power consumed by the load with respect to the three phases gives the desired

0

5

10

15

20

25

30

35

0 10 20 30

TH

D (%

)

Source current (Amp)

Before compensation

After compensation

00.10.20.30.40.50.60.70.80.9

1

0 5 10 15 20 25

Pow

er F

acto

r

Source current (Amp)

Before compensation

After compensation

Page 29: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

47

mains currents, assuming them to be balanced and in-phase with the supply

voltage after compensation. The reference compensation signals are then

derived as the difference between the load currents and the desired mains

currents.

Lin et al (1992) had discussed about the Synchronous Detection

(SD) theory which can work effectively under balanced as well as unbalanced

source and load conditions because the compensating currents are calculated

considering the magnitudes of per phase voltage. The following assumptions

are made in calculating the three phase compensating currents using equal

current distribution method of synchronous detection algorithm.

(i) Voltage is not distorted

(ii) Loss in the neutral line is negligible. The equal current

synchronous detection algorithm shows a better profile of

source current after compensation.

The reference compensation currents are used as modulating wave

for the multi carrier pulse width modulation circuitry (Tolbert et al 1998). SD

algorithm is basically used for the determination of amplitude of the source

currents. In the SD algorithm (Viktor Valouch et al 1999), the three phase

main currents are assumed to be balanced after compensation.

The real power P(t) consumed by the load could be calculated from

the instantaneous voltages and load currents as given in equation (2.28)

( 2. 28)

where are the instantaneous values of supply voltages and

are the instantaneous values of load currents. The average value

Page 30: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

48

is determined by applying to a low pass filter. The real power is then

split into three phases as given in equations (2.29), (2.30) and (2.31).

(2.29)

(2.30)

(2.31)

Thus for purely sinusoidal balanced supply voltages,

(2.32)

With the objective of achieving Unity Power Factor (UPF), the desired mains

currents are obtained as given in equations (2.33), (2.34) and (2.35).

(2.33)

(2.34)

(2. 35)

where, are the amplitudes of the supply voltages. The

compensation currents are calculated as given in equations (2.36), (2.37) and

(2.38).

(2.36)

(2.37)

(2.38)

The Simulink model for control circuit of synchronous detection

algorithm is shown in Figure 2.26. The control circuit generates the required

compensating current depending upon the requirement of the individual

phase. The developed circuit is incorporated in the main simulation circuit of

Page 31: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

49

SD algorithm based SAPF compensating three phase system with the

nonlinear load.

Figure 2.26 Simulink model for control circuit of synchronous detection algorithm

2.8.1 Simulink model of Synchronous Detection Algorithm for the

design of Shunt Active Power Filter

The proposed Synchronous Detection algorithm is designed to

control SAPF with the generation of filter current and hence compensated

current. The simulation parameters used for the simulation of I-

algorithm based SAPF are used. Simulink model of Shunt Active Power Filter

with Synchronous Detection Algorithm is depicted in Figure 2.27.

Page 32: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

50

Figure 2.27 Simulink model of shunt active power filter with synchronous detection algorithm

2.9 RESULTS AND DISCUSSION

2.9.1 Simulation Results of SAPF using Synchronous Detection

Algorithm with Balanced Load Condition

The results of the simulation are obtained by changing the load

impedance. SD algorithm is developed to estimate the required Reference

compensating current which is given in Figure 2.28. It is clearly seen that

despite the fact that load is nonlinear reactive, three phase currents drawn

from the source are fairly sinusoidal and high power factor after

compensation.

Page 33: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

51

Figure 2.28 Reference compensating current using synchronous Detection algorithm with balanced load condition

The source current after compensation and its corresponding

harmonic spectrum are shown in Figures 2.29 and 2.30.

The system is simulated in MATLAB/SIMULINK to validate the

effectiveness of the proposed SD control algorithm for balanced load

conditions.

Figure 2.29 Compensated source current using synchronous detection algorithm with balanced load condition

Page 34: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

52

Figure 2.30 Harmonic profile of source current using synchronous detection algorithm with balanced load condition

The system with SAPF incorporating SD algorithm is simulated

under variable load conditions. The THD values and power factor are

tabulated in Table 2.5.

Table 2.5 THD and Power factor for various values of source current with balanced load condition

S.No

Load Values

L in mH

Source Current (Amps)

THD (%) Power factor

Before Comp.

After Comp.

Before Comp.

After Comp.

1 5 1.5 25.32 3.82 0.7478 0.9583

2 22.5 9.06 27.33 3.91 0.7425 0.9578

3 25 9.853 27.94 3.97 0.7308 0.9534

4 27.5 11 28.97 4.01 0.7299 0.9517

5 30 11.55 29.03 4.08 0.7257 0.9504

6 32.5 13.48 30.02 4.13 0.7157 0.9489

7 35 17.39 30.98 4.25 0.7038 0.9345

8 37.5 20.22 31.54 4.28 0.6926 0.9205

9 40 21.48 32.03 4.31 0.6911 0.9175

Page 35: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

53

The Synchronous Detection algorithm performs well and it

maintains the THD and power factor for inconsistent loads by producing

proper compensating current.

Figure 2.31 THD Vs Source current using synchronous detection algorithm with balanced load condition

The source current is varied intentionally by changing the

connected load to observe the change of THD and Power factor. Figures 2.31

and 2.32 illustrate the variation of THD and power factor.

Figure 2.32 Power factor Vs Source current using synchronous detection algorithm with balanced load condition

0

5

10

15

20

25

30

35

0 5 10 15 20 25

THD

(%)

Source current (Amp

BeforeCompensationAftercompensation

00.20.40.60.8

11.2

0 10 20 30

Pow

er F

acto

r

Source current (Amp)

BeforeCompensationAftercompensation

Page 36: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

54

2.9.2 Simulation Results of SAPF using Synchronous Detection

Algorithm with Unbalanced Load Condition

The system is simulated in MATLAB/SIMULINK to validate the

effectiveness of the proposed SD control algorithm for unbalanced load

conditions. The simulation parameters used for the simulation and their values

are tabulated in Table 2.6.

Table 2.6 Simulation parameters with unbalanced load condition

Parameters Values Supply voltage per phase 220 V (rms)

Filter inductance 2 mH Load impedance Ra=Rb mH Reference value of DC link voltage 400V DC link capacitor(C) 2200 µF

Carrier frequency for PWM generation 10 kHz

Reference compensation current for phase a , is shown in

Figure 2.33. The reference compensation currents and filter currents for phase

b and c are produced with different magnitude and phase angle depending

upon the compensation requirement to maintain THD and power factor.

Figure 2.33 Reference compensating current using synchronous detection algorithm with unbalanced load condition

Page 37: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

55

Figures 2.34 and 2.35 illustrate the source current and its harmonic

profile.

Figure 2.34 Compensated source current using synchronous detection algorithm with unbalanced load condition

The source currents are obtained for different values of loads. The

waveform shown in the Figure 2.34 is for a particular load parameter

Figure 2.35 Harmonic spectum of source current using synchronous detection algorithm with unbalanced load condition

The relationship of source voltage and source current is shown in

Figure 2.36. The power factor is found as 0.8464 lagging.

Page 38: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

56

Figure 2.36 Source voltage and current waveforms using synchronous detection algorithm with unbalanced load condition

The loads connected to the system is changed to vary the current

drawn from the source. Table 2.7 gives details about the variation of THD and

power factor for different load impedance values under unbalanced load

condition.

Table 2.7 THD and power factor for various values of source current with unbalanced load condition

S.No

Load Values

La in mH

Source Current (Amps)

THD (%) Power factor

Before Comp.

After Comp.

Before Comp.

After Comp.

1 5 1.5 24.73 5.01 0.7478 0.7302

2 22.5 9.06 25.33 5.05 0.7425 0.8595

3 25 9.853 26.04 5.18 0.7308 0.8523

4 27.5 11 27.65 5.21 0.7299 0.8514

5 30 11.55 28.97 5.25 0.7257 0.8464

6 32.5 13.48 29.12 5.31 0.7157 0.8321

7 35 17.39 29.35 5.38 0.7038 0.8216

8 37.5 20.22 30.54 5.42 0.6926 0.8202

Page 39: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

57

From the results, it is concluded that SD algorithm based control

circuit generates compensating current to maintain the THD and the power

factor. Figures 2.37 and 2.38 illustrate the variation of THD and power factor

with respect to source current. The variation of source current is achieved by

changing the load impedance values.

Figure 2.37 THD Vs Source current using synchronous detection algorithm with unbalanced load condition

Figure 2.38 Power factor Vs Source current using synchronous detection algorithm with unbalanced load condition

0

5

10

15

20

25

30

35

0 5 10 15 20 25

THD

(%)

Source current

Before compensation

After compensation

00.10.20.30.40.50.60.70.80.9

1

0 5 10 15 20 25

Pow

er F

acto

r

Source current (Amp)

Before compensation

After compensation

Page 40: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

58

2.10 COMPARISON OF RESULTS

The system with balanced and unbalanced load is simulated by

connecting SAPF incorporating I-COS

harmonic profiles are presented and discussed. The power factor of the supply

system is also measured.

Figure 2.39 Performance (THD) comparison of SAPF using I-and SD algorithms with balanced load condition

Figures 2.39 and 2.40 illustrate the comparative analysis of SAPF

performance with I-

observed that Synchronous Detection algorithm based control circuit

compensates effectively and brings the THD and power factor of source

current below that of I- thm based SAPF.

00.5

11.5

22.5

33.5

44.5

5

0 5 10 15 20 25

THD

(%)

Source current (Amp)

I-COS Algorithm

SynchronousDetection Algorithm

Page 41: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

59

Figure 2.40 Performance (Power factor) comparison of SAPF using I- condition

Figures 2.41 and 2.42 show the variation of THD and power factor

of the source current drawn by the nonlinear unbalanced loads. In the

unbalanced load conditions, the I-

generates compensating current and performs better than that of SD

algorithm based SAPF.

Figure 2.41 Performance (THD) comparison of SAPF using I- SD algorithms with unbalanced load condition

0

0.2

0.4

0.6

0.8

1

1.2

0 5 10 15 20 25

Pow

er F

acto

r

Source current (Amp)

I-COS Algorithm

SynchronousDetection Algorithm

0

1

2

3

4

5

6

0 5 10 15 20 25

THD

(%)

Source current (Amp)

I-COS algorithm

Synchronous Detectionalgorithm

Page 42: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

60

Figure 2.42 Performance (Power factor) comparison of SAPF using I- condition

The comparative analysis of THD and power factor of three phase

supply system with SD and I-COS

L=35mH) is furnished in Table 2.8.

Table 2.8 Performance comparison of SAPF with I-algorithms

Parameters Before compensation After Compensation

SD Algorithm I-

Balanced Load

Unbalanced Load

Balanced Load

Unbalanced Load

Balanced Load

Unbalanced Load

THD (%) 28.97 29.35 4.08 5.25 4.18 4.87

Power factor (lagging)

0.7257 0.6932 0.9517 0.8464 0.9514 0.8497

From the analysis, it is inferred that the SAPF with SD algorithm

performs well in balanced load condition and I-COS

works better with unbalanced load condition and it also reduces the THD

00.10.20.30.40.50.60.7

0.80.9

1

0 5 10 15 20 25

Pow

er F

acto

r

Source current (Amp)

I-COS algorithm

SynchronousDetection algorithm

Page 43: CHAPTER 2 PROPOSED I- DETECTION …shodhganga.inflibnet.ac.in/bitstream/10603/33161/7/07...Figure 2.2 Power circuit of seven level cascaded H bridge inverter Three single phase units

61

much below the IEEE standards. The power factor of the system is also very

much improved.

2.11 SUMMARY

The effectiveness of the proposed I-COS are

demonstrated with computer simulation in MATLAB/SIMULINK. The

simulation is performed for various load conditions for providing harmonic

compensation. The results of the simulation are obtained and analyzed for

different values of load impedances. The waveforms of source currents are

obtained and analyzed. The source currents are found to have THD well

below the recommended IEEE-519 standard of 5% after compensation. Thus,

the behavior of the shunt active power filter is analyzed for different load

conditions. It can be clearly seen that despite the fact that the load is nonlinear

reactive, the three phase currents drawn from the source are fairly sinusoidal

after compensation. A detailed performance comparison of SAPF is carried

out with I- It is concluded from

the analysis that the performance of shunt active power filter with I-COS

and SD algorithms has become much better than the conventional SAPF.

Among the two methods, I-

computational burden. Moreover, it gives good responses when the load is

nonlinear and unbalanced. The SD algorithm is identified to be superior when

the load is nonlinear as well as balanced. The proportional Integral and Fuzzy

Logic Controllers are designed and developed for SAPF. The results of the

simulation are investigated in the next chapter.