Upload
trandang
View
222
Download
0
Embed Size (px)
Citation preview
1
CHAPTER 1
INTRODUCTION TO MEDIUM VOLTAGE DRIVES
Table of Contents
Chapter -1. Introduction to Medium Voltage Drives
S.No. Name of the Sub-Title Page No. 1.1 Introduction 2
1.2 Overview of Medium Voltage drive 2
1.2.1 Industrial Applications of MV drive 4
1.3 General Block diagram of MV drive 5
1.4 Requirements and Technical Challenges in
control of MV drive 8
1.4.1 High Power converter efficiency 9
1.4.2 Harmonic minimization to satisfy
IEEE 519-1992 harmonic guidelines 10
1.5 Survey of inverter topologies used by manufacturers
in Present Market 12
1.6 Conclusions 16
2
INTRODUCTION TO MEDIUM VOLTAGE DRIVES
1.1 INTRODUCTION
This chapter emphasizes the technical challenges and
requirements of modern high-power medium voltage drives, which are
foundation for the proposed research work. The general block diagram
of MV drive and functions of each block and numerous industrial
applications are presented. The main technical challenges and
requirements of MV drives such as high converter efficiency, less
switching frequency losses of the semiconductor switching devices
and less total harmonic distortion to comply with IEEE 519-1992
harmonic guidelines are discussed. Finally, a summary of inverter
topologies such as Neutral Point Clamped (NPC), Flying Capacitor (FC)
and Cascade H-Bridge (CHB) topologies along with ratings in MV Drive
products by major drive manufacturers are presented.
1.2 OVERVIEW OF MEDIUM VOLTAGE DRIVES
With the recent technical requirements of modern industry such
as higher power ratings with high converter efficiency, improved
reliability, energy saving and reduced cost leads to the extensive usage
of modern high-power medium voltage (MV) drives in many industrial
applications [1]-[5]. Though, MV drives cover power ratings from
0.4MW to 100MW at the medium voltage level of 2.3kV to 13.8kV,
majority of the installed MV drives are in 1 to 4 MW power range and
the voltage ratings of 3.3kV to 6.6kV as represented in Fig.1.1.
3
Nowadays, around 85% of the total installed drives are pumps,
compressors, conveyers and fans, only 15% of the installed drives are
nonstandard as represented in Fig.1.2 (a). According to the present
market research, 97% of the installed MV motors operate at fixed
speed and 3% are variable-speed drives as shown in Fig. 1.2 (b) [6].
In majority of industrial applications, fans and pumps usually
driven by fixed speed motors, controlling of air or liquid flow is usually
achieved by conventional mechanical methods such as throttling, flow
Fig: 1.1 Voltage and power ranges of the MV drive. Source: Rockwell Automation [7]
(a) Load types for the MV drive (b) MV drive versus MV motors
Fig: 1.2 (a) & (b) MV drive market survey. Source: ABB [7]
4
control valves and inlet dampers, resulting in a substantial amount of
energy loss. On other hand by using electrically driven, compressors
wellhead pumps are the current alternatives to traditional water and
gas injection for pressure augmenting requirements. Hence, usage of
electrically driven motors can significantly minimize the energy loss
and productivity can be increased by installing the MV drive [3].
1.2.1 Industrial Applications of MV drive
With the recent advancements in semiconductor technology,
switching devices like GTOs, IGBTs and IGCTs led the pace of MV
drives since 1980s. MV drives are extensively used in various
industrial applications because of the advantages such as high
efficiency, high dynamic performance, considerable savings on energy
cost, regenerative braking, four quadrant operation and increase in
productivity [7]. Some of the applications are in Table 1.1.
Table: 1.1 A summary of MV Drive industrial applications [7]
S.No Industry Applications
1 Power Feed water pumps, induced draft fans,
compressors, forced draft fans and blowers.
2 Oil & Gas
Turbo compressors, pipeline pumps,
mixers/extruders, reciprocating compressors
and centrifugal pumps.
3 Metals Hot rolling mill drives, sectional steel mills
and blast furnace converter.
4 Mining Ore mills, bucket wheel excavators, conveyor
belts and blowers
5
5 Transportation Propulsion for naval vessels, shuttle tankers
and traction drives for locomotives.
6 Cement Kiln induced draft fans, forced draft fans and
preheat tower fans.
1.3 GENERAL BLOCK DIAGRAM OF MV DRIVE
The general block diagram of MV drive is represented in Fig. 1.3,
the main parts of MV drive are rectifier, line-side filter, transformer, dc
filter, inverter and motor-side filter. Depending upon the application
and system requirements, the selection of rectifier topology, inverter
topology, transformer connections, line and motor side filters will be
varied. Specifications of supply system for MV drive are at the medium
voltage level of 2.3kV to 13.8kV.
The main function of the rectifier in MV drive is to convert ac
supply voltage to a fixed or adjustable magnitude of dc voltage.
Commonly used rectifier topologies are multi pulse diode-rectifier and
multi pulse SCR-rectifier. Among these two topologies multi pulse
Fig: 1.3 General block diagram of the MV drive [7].
6
diode-rectifiers are used as front end convertors, by major high power
drive manufacturers around the world [8]-[9]. In addition to above
mentioned function, the purpose of multi pulse diode-rectifier is to
reduce harmonic content in output voltage waveform.
In general, by using six pulse rectifiers, the lower order harmonics
such as 5th and 7th are cancelled out. The %THD of the line current,
further decreases by increasing the pulse number of diode rectifier.
Compared to six-pulse diode rectifiers, 12-pulse diode-rectifiers have
better harmonic profile but does not satisfy IEEE 519-1992 harmonic
guidelines.
At present in MV drive, 18-pulse and 24-pulse diode-rectifiers are
used as front end rectifiers which have better harmonic profile and
satisfy IEEE 519-1992 harmonic guidelines. The main functions of the
phase shifting transformers are to produce required phase
displacement for harmonic cancellation, proper secondary voltage and
an electrical isolation between rectifier and utility supply. The
commonly used configurations are Y/Z and ∆/Z (zigzag) configuration
[10].
The line and motor side filters are optional and are decided by
depending on system requirements and type of converter employed. In
the case of voltage source converters the dc filter can be a capacitor,
which provides constant dc voltage to the inverter but in the case of
current source converters the dc filter can be an inductor which
reduces the ripples in dc current waveform [7].
7
The main function of the inverter is to convert fixed dc supply into
adjustable magnitude of ac with adjustable frequency. The inverters
which are used in MV drive can be classified into current source
inverter (CSI) and voltage source inverter (VSI). The function of VSI is
to convert dc voltage into a three-phase ac voltage with adjustable
magnitude and frequency where as current source inverter converts
dc current to an adjustable ac current [11].
The advantages of voltage source inverter are:
1. Operates easily at no load
2. Asymmetric blocking devices can be used
3. Less interactive with load
4. Requires regenerative converter on line side
5. Highly reliable
6. Good dynamic response as compared to CSI
Inspite of above mentioned advantages, control of voltage source
inverter is complex when compared to current source inverter [12].
The advantages of current source inverter are [13]-[14]:
1. Because of inherent four-quadrant operation extra power circuit
is not required
2. More rugged
3. Control is easy when compared to VSI
4. Operating at higher power levels
5. Multimachine operating capability
8
Disadvantages of CSI are:
1. Sluggish dynamic response compared to VSI
2. It cannot be used in open loop.
3. Inferior efficiency, overall cost and transient response than VSI.
4. Unable to operate at no load
5. Multimachine operation is very difficult
In general, voltage source inverter or current source inverter can be
chosen based on system requirements and applications.
Commercially, the various topologies for voltage source inverter which
are used by MV drive manufacturers are neutral point clamped (NPC),
flying capacitor (FC) and cascaded H-bridge (CHB) topologies [15].
1.4 REQUIREMENTS AND TECHNICAL CHALLENGES IN CONTROL OF MV DRIVES
The standard requirements for the MV drives are high efficiency,
minimum space requirement, less energy loss, low noise, easy to use,
easy to integrate, minimum downtime for repairs, high dynamic
performance, low maintenance, significant savings on energy cost,
four quadrant operation and high reliability. In addition to these
requirements, the main technical challenges in control of MV drives
are: high converter efficiency, high input power factor and maintaining
the value of %THD to comply with IEEE 519-1992 harmonic
guidelines [16].
9
1.4.1 High Converter Efficiency
High converter efficiency is one of the important requirements in
high-power MV drive applications. Particularly in high-power
converters, the high switching of semi conductor switches leads to
high switching losses and further leads to poor converter efficiency.
In particular, switching losses are directly related with the modulation
strategies which have been selected in control of multilevel inverters
[17]. Hence, selection of suitable modulation strategy with less
switching losses and also with less %THD has been an important
requirement to be addressed in MV Drives.
If the device switching losses are not minimized, the cooling
requirements can be increased, which leads to increase in physical
size, manufacturing cost of the switching devices [7]. Fast switching
speed of the switching devices may cause high 푑푣 푑푡⁄ at the falling and
rising edges of the inverter output voltage waveform. The high 푑푣 푑푡⁄
may results in failure of motor winding insulation and also causes
electromagnetic emission in cables, which are connected in between
motor and inverter, which further effects the operation of sensitive
equipments [18].
On other hand, the reduction in the switching frequency leads to
increase in %THD of line and motor side waveforms. Therefore efforts
should be made to minimize %THD in output voltage waveform with
optimum switching frequency.
10
1.4.2 Harmonic minimization to satisfy IEEE 519-1992 harmonic guidelines
Harmonics deteriorates the performance of an electric drive.
Particularly, switching devices used in the power electronic converters
in MV drive generate harmonics in line and motor side voltage and
current waveforms. The distorted voltage and current waveforms may
cause several problems such as motor derating, over heating of the
electrical machines, interference with communication malfunction of
utility relays and control signals which results in unwanted tripping of
computer controlled industrial process which leads to expensive
downtime and ruined product.
In addition to above effects, line side capacitors are used in MV
industrial drives to reduce %THD and for power factor compensation.
These capacitors may form LC resonant circuit with the line
inductance of the system and resonates with harmonic voltages and
currents which results in severe oscillations (or) over voltages that
may destroy switching devices in converter circuits. Hence, harmonic
minimization in multilevel inverter has been an interesting challenging
research topic since several decades [19].
For the reasons mentioned above, the Institute of Electrical and
Electronics Engineers (IEEE) and The American National Standards
Institute (ANSI) have established certain harmonic guidelines for
unbalanced and distorted voltages in the power systems for specific
applications [16] & [20]-[21]. Due to the increasing huge increment in
11
the usage of power semiconductor devices in high-power converters
have prompted growing concern over the harmonic distortion in
modern power distribution systems. All the manufacturers and
industries should comply with specified limits of harmonic distortion
guidelines.
In this connection, the Institute of Electrical and Electronics
(IEEE) has established certain guidelines for harmonic regulation,
such as IEEE standard 519-1992 harmonic guidelines [16] as listed in
Table 1.2.
The converters used in high-power medium voltage drives should
satisfy these specified limits of percentage total harmonic distortion
(%THD).The percentage total harmonic distortion (%THD) can be
calculated according to equation 1.1
%푇퐻퐷 = ∑∞ 푋100 (1.1)
Where Vh is the amplitude of the hth harmonic voltage and V1 is
the amplitude of the fundamental voltage.
Table: 1.2 Voltage Distortion Guidelines for Power Systems[22]
S.No. Voltage Level *Dedicated Power System
Generated Power
System
1 Medium voltage (2.4kV to 69kV)
8% 5%
2 High voltage (115kV and above)
1.5% 1.5%
* A dedicated power system is one supplying only converters or loads
that are not affected by voltage distortion
12
1.5 SURVEY OF INVERTER TOPOLOGIES USED BY MANUFACTURERS IN PRESENT MARKET
In order to meet the technical requirements & challenges in MV
drives, various inverter topologies with different ratings and
modulation control schemes are available in the present market.
However, each inverter topology has its own unique features but also
have drawbacks as mentioned in chapter 2.
As mentioned earlier, in commercial market, there exists three
main topologies for multilevel inverters such as neutral point clamped
(NPC) topology, flying capacitor (FC) topology, and the cascaded H-
Bridge topology and effectively implemented by the major drive
manufacturing companies in the world.
Table 1.3 provides, summary of various topologies and power
ranges by major drive manufacturers in the world [23].
In neutral point clamped topology, three-level NPC has been widely
accepted by several manufacturers such as ABB which uses this
topology in both their ACS 1000 and ACS 6000 series [6]. Flying
capacitor topology, four-level flying Capacitor is most preferred
topology, if the switching frequency is high and one of the
manufacturers of drives such as Alstom, has adapted this topology for
VDM 6000 series [24].
13
Table: 1.3 Summary of the inverter configurations used in MV Drive in present market [23]
S.No. Inverter Configuration Power Range (MVA)
Manufacturer
1 Two-level voltage source
inverter 1.4-7.2 Alstom(VDM5000)
2 Three-level neutral point
clamped inverter
0.3-5 ABB(ACS1000)
3-27 (ACS6000)
3-20 General
Electric(Innovation Series MV-SP)
0.6-7.2 Siemens
(SIMOVERT-MV)
0.3-2.4 General Electric-
Toshiba (Dura-Bilt5 MV)
3 Multilevel cascaded H-
bridge inverter
0.3-22 ASI Robicon
(Perfect Harmony)
0.5-6 Toshiba
(TOSVERT-MV)
0.45-7.5 General Electric
(Innovation MV-GP Type H)
4 NPC/ H-bridge inverter 0.4-4.8 Toshiba
(TOSVERT 300MV)
5 Flying-capacitor inverter 0.3-8 Alstom
(VDM6000 symphony)
6 PWM current source
inverter 0.2-20
Rockwell Automation
(Power Flex 7000)
7 Load commutated inverter
>10 Siemens
(SIMOVERT S) >10 ABB(LCI)
>10 Alstom
(ALSPA SD7000)
14
The cascaded H-bridge topology is one of the emerging topology
which uses low-voltage blocking devices (e.g. 1700V IGBTs) to achieve
higher operating voltage and power levels. In this topology, present
manufacturers uses three to six equal H-bridge cells per phase, which
results in a seven to thirteen levels in the output phase voltage
waveform. This type of topology has been used by leading
manufacturer Siemens to develop the product named as Perfect
harmony.
ACS 6000 model MV drive developed by ABB with the
specifications of 3.3kV, 36MW along with various parts such as line
supply unit, control unit, inverter unit, dc link and water cooling unit
are represented in Fig. 1.4.
16
1.6 CONCLUSIONS
This chapter provides the foundation for the problem formation
to address the technical challenges and requirements of MV drive. A
brief overview of MV drive and functioning of each block and various
industrial applications are discussed. In addition to that main
technical challenges and the requirements of MV drives such as high
converter efficiency and less %THD to comply with IEEE 519-1992
harmonic guidelines are discussed. Finally, the various inverter
topologies and power ratings used by leading MV Drive manufacturers
in the world are listed in detail.
In subsequent chapters, above mentioned technical challenges are
clearly addressed by selecting a suitable multilevel inverter
configuration, modulation strategy to control multilevel inverter.
Further the challenges in solving non linear transcendental SHE
equations set formulated in control of chosen multilevel inverter
configuration are addressed. The simulation results are
experimentally validated.