A. 112 This document is not a contract. SOCOMEC reserves the right to modify features without prior notice in view of continued improvement. 2006-2007 Functions SIRCOVER products are manually operated multipolar changeover switches. They ensure switching, transfer of sources or transfer of two low voltage circuits on load as well as their safety disconnection. SIRCOVER By-Pass are manually operated changeover switches. They are a combination of three interlocked switches enabling the use with 3 + 6 pole or 4 + 8 pole. They insulate by providing simultaneous safety isolation top and bottom and by passing loads or low voltage circuits mainly during maintenance operations. Conformity to standards • IEC 60947-3 • EN 60947-3 • VDE 0660 Part 107 (1992) • NBN EN 60947-3 • BS EN 60947-3 Approvals and certifications (1) • Bureau Véritas • BBJ Poland (attestation of verification) (1) In progress for certain ratings. General characteristics • 3 stable positions (I, 0, II) or overlapping contacts on request (I, I + II, II) , and on load changeover switching (AC-22 and AC-23) • Fully visible breaking • IP20 device and accessories. Available on request • Devices 6 or 8 pole • Devices with overlapping (make before break) contacts (I, I+II, I) • Devices with over-sized neutral e.g.: 3 x 250 A + N 400 A • Devices with advanced neutral. Functions References Accessories Characteristics Dimensions Changeover switches SIRCOVER and SIRCOVER by-pass 125 to 3150 A SOCOMEC general catalogue svr_107_a_1_cat svr_125_a_1_cat SIRCOVER 3 pole SIRCOVER by-pass 4 pole

Change Over

Embed Size (px)

DESCRIPTION

switchgear

Citation preview

Page 1: Change Over

A. 112 This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

FunctionsSIRCOVER products are manuallyoperated multipolar changeover switches.They ensure switching, transfer of sourcesor transfer of two low voltage circuits onload as well as their safety disconnection.

SIRCOVER By-Pass are manuallyoperated changeover switches.They are a combination of threeinterlocked switches enabling the use with3 + 6 pole or 4 + 8 pole.They insulate by providing simultaneoussafety isolation top and bottom and bypassing loads or low voltage circuitsmainly during maintenance operations.

Conformity to standards• IEC 60947-3• EN 60947-3• VDE 0660 Part 107 (1992) • NBN EN 60947-3• BS EN 60947-3

Approvals and certifications(1)

• Bureau Véritas• BBJ Poland (attestation of verification)

(1) In progress for certain ratings.

General characteristics• 3 stable positions (I, 0, II) or overlapping

contacts on request (I, I + II, II) , and onload changeover switching (AC-22 andAC-23)

• Fully visible breaking• IP20 device and accessories.

Available on request• Devices 6 or 8 pole• Devices with overlapping (make before

break) contacts (I, I+II, I) • Devices with over-sized neutral e.g.:

3 x 250 A + N 400 A• Devices with advanced neutral.

FunctionsReferencesAccessoriesCharacteristicsDimensions

Changeover switches

SIRCOVER andSIRCOVER by-pass125 to 3150 A

SOCOMEC general catalogue

svr_

107_

a_1_

cat

svr_

125_

a_1_

cat

SIRCOVER 3 pole

SIRCOVER by-pass 4 pole

Page 2: Change Over

A. 113

Changeover switches

SIRCOVER and SIRCOVER by-pass

SOCOMEC general catalogue This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

svr_

103_

a_1_

x_ca

t

SIRCOVER by-pass (I,0,II)

Break before make application.

• SIRCOVER by-pass 125 to 1 600 A

Typical application

1

2

3

4

5

6

7

Overview (for further details, please see theinstallation instructions supplied with eachdevice).

1. Direct front operation.

2. External front operation.

3 et 4. Auxiliary contacts.

5. Bridging bar.

6. Terminal shrouds.

7. Inter phase barrier.

• SIRCOVER 125 to 3 150 A

SIRCOVER by-pass with overlapping contacts (on request)

Make before break application.

Charge Charge Charge

I

I

I

II

I

O

I

I

II

I

IIIII

I

II

I

I

II

I

I

II

I IIO

I IIO

I IIO

atys

_570

_a_1

_x_c

at

I

I

II

I

I

II

I

I

II

I III+II

I III+II

I III+II

atys

_571

_a_1

_x_c

at

Illustrations

Page 3: Change Over

4109 1002

Switches

A. 114 This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

� FunctionsReferencesAccessoriesCharacteristicsDimensions

Changeover switches

SIRCOVER andSIRCOVER by-pass125 to 3150 A

SOCOMEC general catalogue

References

svr_

112_

a_1_

cat

125 A 160 A 200 A 250 AFront operation changeover switch (switch body only) - SIRCOVERNo. of poles Changeover operation type References References References References

3 pole I - 0 - II 4100 3013 4100 3016 4100 3019 4100 30254 pole I - 0 - II 4100 4013 4100 4016 4100 4019 4100 40253 pole I - I+II - II 4190 3013 4190 3016 4190 3019 4190 30254 pole I - I+II - II 4190 4013 4190 4016 4190 4019 4190 4025

Front operation changeover switch (switch body only) - SIRCOVER by-pass

3 + 6 pole I - 0 - II 4100 7013 4100 7016 4100 7019 4100 70254 + 8 pole I - 0 - II 4100 9013 4100 9016 4100 9019 4100 9025

AccessoriesDirect operation handle

Black SIRCOVER 4199 5012 4199 5012 4199 5012 4199 5012Black SIRCOVER by-pass 4199 5012 4199 5012 4199 5012 2799 7052

External operation handle

I - 0 - II IP55 1421 2113 1421 2113 1421 2113 1421 2113I - 0 - II IP65 1423 2113 1423 2113 1423 2113 1423 2113

SIRCOVERSIRCOVER

I - 0 - II IP55 1421 2113 1421 2113 1421 2113 -I - 0 - II IP65 1423 2113 1423 2113 1423 2113 1433 3113

SIRCOVER by-passSIRCOVER by-pass

Shaft extension for external operation (for dimensions see “Accessories” pages)

200 mm 1400 1020 1400 1020 1400 1020 1400 1020320 mm 1400 1032 1400 1032 1400 1032 1400 1032

SIRCOVERSIRCOVER

200 mm 1400 1020 1400 1020 1400 1020 1401 1520320 mm 1400 1032 1400 1032 1400 1032 1401 1532

SIRCOVER by-passSIRCOVER by-pass

Bridging bars

1 pole 4109 0019 4109 0019 4109 0019 4109 0025

Auxiliary contacts (1 per position)

1st / 2nd AC NO/NC 4109 0021 4109 0021 4109 0021 4109 0021

Terminal shrouds (1 set) (1)(2)

3 pole top / bottom / front(I) / rear (II) 2694 3014 2694 3014 2694 30214 pole top / bottom / front(I) / rear (II) 2694 4014 2694 4014 2694 4021

top / bottomtop / bottom

(1) To shroud front switch top and bottom 2 references required for SIRCOVER and 3 references required for SIRCOVER by-pass.(2) To fully shroud front and rear / top and bottom 4 references required for SIRCOVER and 6 references required for SIRCOVER by-pass.(3) Specific handle included.(4) Lock not included.

Terminal screens (1 per position)

3 pole 1509 3012 1509 3012 1509 3012 1509 30254 pole 1509 4012 1509 4012 1509 4012 1509 4025

Handle key interlocking accessories - For direct front operation

Locking using RONIS EL11AP lock in position O(3)(4) 4109 1006 4109 1006 4109 1006 4109 1006Locking using RONIS EL11AP lock in position I, O, II(3)(4) 4109 1002 4109 1002 4109 1002

Handle key interlocking accessories - For external front operation

Locking using RONIS EL11AP lock in position O(4) 1499 7701 1499 7701 1499 7701 1499 7701Locking using CASTELL type K lock in position O(4) 1499 7702 1499 7702 1499 7702 1499 7702

400 A

References

4100 30394100 40394190 30394190 4039

4100 70394100 9039

4199 50122799 7052

1421 21131423 2113

-1433 3113

I - I+II - II IP65 1423 2114 1423 2114 1423 2114 1423 2114SIRCOVER 1423 2114

1400 10201400 10321401 15201401 1532

4109 0039

4109 0021

2694 30212694 4021

1509 30251509 4025

4109 10064109 1002

1499 77011499 7702

2694 30142694 4014

Page 4: Change Over

4109 1002

A. 115This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

Changeover switches

SIRCOVER and SIRCOVER by-pass

SOCOMEC general catalogue

References

SwitchesFront operation changeover switch (switch body only) - SIRCOVERNo. of poles Changeover operation type

3 pole I - 0 - II4 pole I - 0 - II3 pole I - I+II - II4 pole I - I+II - II

Front operation changeover switch (switch body only) - SIRCOVER by-pass

3 + 6 pole I - 0 - II4 + 8 pole I - 0 - II

AccessoriesDirect operation handle

Black

External operation handle

I - 0 - II IP55

I - I+II - II IP65I - 0 - II IP65

I - 0 - II IP65

Shaft extension for external operation (for dimensions see “Accessories” pages)

200 mm320 mm

SIRCOVER

SIRCOVERSIRCOVER

SIRCOVER by-pass

SIRCOVERSIRCOVER

Bridging bars

1 pole

Auxiliary contacts (1 per position)

1st / 2nd AC NO/NC 3/4 poles

Terminal shrouds (1 set) (1)(2)

3 pole top / bottom / front (I) / rear (II)4 pole top / bottom / front (I) / rear (II)

top / bottomtop / bottom

(1) To shroud front switch top and bottom 2 references required for SIRCOVER and 3 references required for SIRCOVER by-pass.(2) To fully shroud front and rear / top and bottom 4 references required for SIRCOVER and 6 references required for SIRCOVER by-pass.(3) Specific handle included.(4) Lock not included.(5) This locking facility can be configured by the user in the 3 positions.

Terminal screens (1 per position)

3 pole4 pole

Handle key interlocking accessories - For direct front operation

Locking using RONIS EL11AP lock in position O(3)(4)

Locking using RONIS EL11AP lock in position I, O, II(3)(4)

Handle key interlocking accessories - For external front operation

Locking using RONIS EL11AP lock in position O(4)

Locking using CASTELL type K lock in position O(4)

DIRECT OPERATION

New handle=

New shaft

EXTERNAL OPERATION

T O O R D E R

+ O T H E R A C C E S S O R I E S

Directhandle

Switchbody

Switchbody

Externalhandle+ Shaft+ +

NEW

SHAFT

NEW

HANDLE

pict

o_08

0_b_

1_gb

svr_

113_

a_1_

cat

500 A 630 A 800 A

References References References

4100 3050 4100 3063 4100 30804100 4050 4100 4063 4100 40804190 3050 4190 3063 4190 30804190 4050 4190 4063 4190 4080

4100 7050 4100 7063 4100 70804100 9050 4100 9063 4100 9080

4199 5012 4199 5012 2799 7052Black

SIRCOVERSIRCOVER by-pass 2799 7052 2799 7052 2799 7012

1421 2113 1421 2113 -

1423 2114 1423 2114 1433 31141423 2113 1423 2113 1433 3113

1433 3113 1433 3113 4199 7146

1400 1020 1400 1020 1401 15201400 1032 1400 1032 1401 1532

200 mm320 mm

SIRCOVER by-passSIRCOVER by-pass

1401 1520 1401 1520 2799 30151401 1532 1401 1532 -

450 mm SIRCOVER by-pass - - 2799 3019

4109 0050 4109 0063 4109 0080

4109 0021 4109 0021 4109 0021

2694 3051 2694 3051 -2694 4051 2694 4051 -

1509 3063 1509 3063 1509 30801509 4063 1509 4063 1509 4080

4109 1006 4109 1006 4109 1004(5)

4109 1002 4109 1004(5)

1499 7701 1499 7701 1499 77011499 7702 1499 7702 1499 7702

1250 A 1600 A

References References

4100 3120 4100 31604100 4120 4100 41604190 3120 4190 31604190 4120 4190 4160

4100 7120 4100 71604100 9120 4100 9160

2799 7052 2799 70522799 7012 2799 7012

- -

1433 3114 1433 31141433 3113 1433 3113

4199 7146 4199 7146

1401 1520 1401 15201401 1532 1401 15322799 3015 2799 3015

- -2799 3019 2799 3019

4109 0120 4109 0160

4109 0021 4109 0021

- -- -

1509 3080 1509 31601509 4080 1509 4160

4109 1004(5) 4109 1004(5)

4109 1004(5) 4109 1004(5)

consult us consult us consult us consult us consult us

1499 7701 1499 77011499 7702 1499 7702

Locking in the 0 position with a 230 VAC undervoltage coil system

Page 5: Change Over

svr_

113_

a_2_

cat

svr_

053_

a_1_

cat

1800 A 2000 ASwitchesFront operation changeover switch (switch body only) - SIRCOVERNo. of poles Changeover operation type References References

3 pole I - 0 - II 4100 3180 4200 32004 pole I - 0 - II 4100 4180 4200 42003 pole I - I+II - II 4190 3180 -4 pole I - I+II - II 4190 4180 -

AccessoriesDirect operation handle

Black SIRCOVER 2799 7052 2799 7012

External operation handle

I - 0 - II IP65 1433 3113 2799 7146I - I+II - II

SIRCOVERSIRCOVER IP65 1433 3114 -

Shaft extension for external operation (for dimensions see “Accessories” pages)

200 mm 1401 1520 -320 mm 1401 1532 2799 3018

SIRCOVERSIRCOVER

Bridging bars

1 pole 4109 0160 consult us

Auxiliary contacts (1 per position)

1st AC NO/NC 4109 0021 4409 00212nd AC NO/NC 4109 0021 4409 0022

Terminal screens (1 per position)

3 pole 1509 3160 standard4 pole 1509 4160 standard

Handle key interlocking accessories - For direct front operation

Locking using RONIS EL11AP lock in position O (1) 4109 1004(2) 4409 2007Locking using RONIS EL11AP lock in position I, O, II (1) 4109 1004(2) 4409 2003Locking in the 0 position with a 230 VAC undervoltage coil system. consult us 4409 9161

Handle key interlocking accessories - For external front operation

Locking using RONIS EL11AP lock in position O (1) 1499 7701 2799 7002(2)

Locking using CASTELL type K lock in position O (1) 1499 7702 2799 7003

2500 A 3150 A

References References

4200 3250 4200 33104200 4250 4200 4310

- -- -

2799 7012 2799 7012

2799 7146 2799 7146- -

- -2799 3018 2799 3018

consult us consult us

4409 0021 4409 00214409 0022 4409 0022

standard standardstandard standard

4409 2007 4409 20074409 2003 4409 20034409 9161 4409 9161

2799 7002(2) 2799 7002(2)

2799 7003 2799 7003

(1) Lock not included.(2) This locking facility can be configured by the user in the 3 positions.

A. 116 This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

��

FunctionsReferencesAccessoriesCharacteristicsDimensions

References

Changeover switches

SIRCOVER andSIRCOVER by-pass125 to 3150 A

SOCOMEC general catalogue

Page 6: Change Over

A. 117

Changeover switches

SIRCOVER andSIRCOVER by-pass

(1) Double lever handle.

SOCOMEC general catalogue This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

DIRECT OPERATION

New handle=

New shaft

EXTERNAL OPERATION

T O O R D E R

+ O T H E R A C C E S S O R I E S

Directhandle

Switchbody

Switchbody

Externalhandle+ Shaft+ +

NEW

SHAFT

NEW

HANDLE

pict

o_08

0_b_

1_gb

AccessoriesDirect operation handles

acce

s_12

9_a_

1_ca

t

acce

s_15

3_a_

1_ca

t

ReferencesSIRCOVER

Rating (A) Handle colour Handle type References

125 … 630 Black Single lever 4199 5012800 … 1800 Black Single lever 2799 70522000 … 3150 Black Double lever 2799 7012

SIRCOVER by-pass

Rating (A) Handle colour Handle type References

125 … 200 Black Single lever 4199 5012250 … 630 Black Single lever 2799 7052800 … 1600 Black Double lever 2799 7012

External operation handles

acce

s_15

0_a_

1_ca

tac

ces_

151_

a_1_

cat

ReferencesSIRCOVER

Rating (A)

Changeoveroperation

typeExternal

IP(1) Handle type References

125 … 630 I - 0 - II IP55 S2 1421 2113125 … 630 I - 0 - II IP65 S2 1423 2113125 … 630 I - I+II - II IP65 S2 1423 2114800 … 1800 I - 0 - II IP65 S3 1433 3113800 … 1800 I - I+II - II IP65 S3 1433 31142000 … 3150 I - 0 - II IP65 2799 7146(1)

UseThe door interlocked externaloperation includes one lockablehandle, one escutcheon andmust be associated with a shaftextension.

SIRCOVER by-pass

Rating (A)

Changeoveroperation

typeExternal

IP Handle type References

125 … 200 I - 0 - II IP65 S2 1423 2113250 … 630 I - 0 - II IP65 S3 1433 3113800 … 1600 I - 0 - II IP65 4199 7146

125 … 200 I - 0 - II IP55 S2 1421 2113

S type handle adapter

acce

s_18

7_a_

2_ca

t

ReferenceHandle colour ReferenceExternal IP Pack qty

Black 1493 0000IP65 10

UseEnables new S type handles to be mounted using old fixingholes for replacement or retrofitapplications.DimensionsAdds 12 mm to the depth.

Alternative S type handle cover colours

acce

s_19

8_a_

2_ca

t

ReferencesHandle colour Pack qty References

Light grey 50 1401 0001Dark grey 50 1401 0011

UseFor single lever handles type S1,S2 and S3.Others colours: please consult us.

Page 7: Change Over

SIRCOVER

Rating (A) Shaft length (mm) Dimension X (mm) References

125 … 400 200 210 … 310 1400 1020125 … 400 320 210 … 430 1400 1032500 … 630 200 280 … 390 1400 1020500 … 630 320 280 … 510 1400 1032800 … 1800 200 425 … 577 1401 1520800 … 1800 320 425 … 697 1401 15322000 … 3150 320 653 … 923 2799 3018

SIRCOVER by-pass

Rating (A) Dimension X (mm) References

125 … 200 200 320 … 450 1400 1020125 … 200 320 320 … 570 1400 1032250 … 400 200 298 … 420 1401 1520250 … 400 320 298 … 540 1401 1532500 … 630 200 417 … 539 1401 1520500 … 630 320 417 … 659 1401 1532800 … 1600 200 550 … 680 2799 3015800 … 1600 450 550 … 800 2799 3019

UseFor standard lenghts externaloperation: - 200 mm- 320 mm- 450 mmOther lengths: please consult us.

Bridging bars

acce

s_20

5_a_

1_ca

tac

ces_

041_

a_1_

cat

ReferencesRating (A) No. of poles Section (mm) Assembly References

125 … 200 1 20 x 2.5 customer 4109 0019250 1 25 x 2.5 customer 4109 0025400 1 32 x 5 customer 4109 0039500 1 32 x 5 customer 4109 0050630 1 50 x 5 customer 4109 0063800 1 50 x 6 customer 4109 00801250 1 60 x 8 customer 4109 01201600 ... 1800 1 90 x 10 customer 4109 01602000 ... 3150 1 factory consult us

UseCreation of a common link, on the top or bottom side of the switch, in order to feedload with either power supply I or/and II.For a by-pass SIRCOVER, twosets of bridging bars are neededas the switch is composed ofthree basic switch framesPosition I: 6 or 8 polesPosition II: 3 or 4 poles

A. 118 This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

FunctionsReferencesAccessoriesCharacteristicsDimensions

AccessoriesShaft extension for external front operation

acce

s_14

3_a_

1_ca

t

Xacce

s_03

4_a_

1_x_

cat

References

Changeover switches

SIRCOVER andSIRCOVER by-pass125 to 3150 A

SOCOMEC general catalogue

Shaft length (mm)

acce

s_20

8_a_

1_ca

t

SIRCOVER by-pass

SIRCOVER

SIRCOVER

svr_

068_

a_1_

x_ca

t

svr_

124_

a

SIRCOVER by-passSIRCOVER

Page 8: Change Over

References

2694 3014(1)(2)

2694 4014(1)(2)

2694 3021(1)(2)

2694 4021(1)(2)

2694 3051(1)(2)

2694 4051(1)(2)

A. 119

Changeover switches

SIRCOVER and SIRCOVER by-pass

Accessories

Auxiliary contacts

acce

s_06

5_a_

1_ca

tsv

r_05

8_a_

1_ca

t

ReferencesNO/NC auxiliary contact

Rating (A) Contact(s) References

125 … 1800 1st / 2nd 4109 00212000 … 3150 1st 4409 00212000 … 3150 2nd 4409 0022

SOCOMEC general catalogue This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

Characteristics

Rating (A) Nominal

current (A)

Operating current Ie (A)

250 VAC 400 VAC 24 VDC 48 VDCAC-13 AC-13 DC-13 DC-13

125 … 3150 16 12 8 14 6

UsePre breaking and positions I and II signalling: 1 or 2 NO/NCauxiliary contacts in eachposition.Low level auxiliary contacts and more auxiliary contactsrequirement: please, consult us.

Connection to control circuitVia 6,35 mm fast-on tags.

Electrical characteristics30 000 operations.

Terminal shrouds

acce

s_20

6_a_

1_ca

t

References

Rating (A) No. of poles Position

125 … 200 3 top / bottom / front (I) / rear (II)125 … 200 4 top / bottom / front (I) / rear (II)250 … 400 3 top / bottom / front (I) / rear (II)250 … 400 4 top / bottom / front (I) / rear (II)500 … 630 3 top / bottom / front (I) / rear (II)500 … 630 4 top / bottom / front (I) / rear (II)

(1) To shroud front switch top and bottom 2 references requiredfor SIRCOVER and 3 references required for SIRCOVER by-pass.

(2) To fully shroud front and rear / top and bottom 4 references requiredfor SIRCOVER and 6 references required for SIRCOVER by-pass.

UseProtection against directcontacts with terminals or connecting parts.Supplied as pair.

Advantage of terminalshroudsHoles enable remote thermalchecking without removing.

Terminal screens

acce

s_20

7_a_

1_ca

t

ReferencesRating (A) No. of poles Position Pack qty References

125 … 200 3 top / bottom 2 1509 3012125 … 200 4 top / bottom 2 1509 4012250 … 400 3 top / bottom 2 1509 3025250 … 400 4 top / bottom 2 1509 4025500 … 630 3 top / bottom 2 1509 3063500 … 630 4 top / bottom 2 1509 4063800 … 1250 3 top / bottom 2 1509 3080800 … 1250 4 top / bottom 2 1509 40801600 ... 1800 3 top / bottom 2 1509 31601600 ... 1800 4 top / bottom 2 1509 41602000 … 3150 3/4 top / bottom 2 standard

UseTop or bottom protectionagainst direct contacts withterminals or connecting parts.Top and bottom pair.

Other specific accessories

bd_0

1_01

_03

• Special protection screens (for specific dimensions orhigh ambiant temperatures).

• Phase barrier shields betweenterminals.

• Connection accessories.• Low level auxiliary contacts.

Page 9: Change Over

Accessories

A. 120 This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

��

FunctionsReferencesAccessoriesCharacteristicsDimensions

Handle key interlocking accessories

Changeover switches

SIRCOVER andSIRCOVER by-pass125 to 3150 A

SOCOMEC general catalogue

(1) Specific handle included.(2) This locking facility can be configured by the user in the 3 positions.

3

3125 … 630 direct

800 … 1800 direct2000 … 3150 direct

external

125 … 200

800 … 1600direct250 … 630

800 … 1600external125 … 630

2000 … 3150125 … 1800

800 … 1600125 … 630

acce

s_06

1_a_

1_x_

cat

Fig. 1

acce

s_00

1_a_

1_x_

cat

Fig. 2

acce

s_13

2_a_

1_x_

cat

Fig. 3

acce

s_15

8_a_

1_x_

cat

Fig. 4

RéférencesLockable in position I, 0 or II

Rating (A) SIRCOVER Operation Figure Reference

125 … 630 external 1 4199 5015

Locking using RONIS EL11AP lock in position 0 (not included)

Rating (A) SIRCOVER Operation Figure References

125 … 630 direct 2 4109 1006(1)

800 … 1800 direct 3 4109 1004(2)

2000 …3150 direct 3 4409 2007

external 4 1499 7701

external 2799 7002(2)

Locking using RONIS EL11AP lock in positions I, 0, II (not included)

Rating (A) SIRCOVER Operation Figure References

2 4109 1002(1)

3 4109 1004(2)

3 4409 2003

2799 7002(2)

UseCan be locked inposition 0 or in positions I, 0 or IIof front operation: • using padlock (not

supplied) (Fig.1). Thisdevice is factorymounted in the director external operationhandle. The lock escutcheoncontains sections tobe pushed outaccording to lockingposition required.However, locking inthe 3 positions forexternal operation onthe range requiresspecial orhandle.

• using a lock (notincluded) for directoperation using: - a special handle

which receives thelock bolt onSIRCOVER 125 to 630 A (Fig. 2)

- a locking disk forSIRCOVER 800 to 3150 A (Fig. 3)

• using a lock (notincluded) fordetachable externaloperation using: - a device which lifts

the lock inside thecabinet door forSIRCOVER 125 to 630 A (Fig. 4)

- a locking disk forSIRCOVER 800 to3150 A

• using undervoltagecoil for SIRCOVER800 to 3150 A.Operation onSIRCOVER is onlypossible when coil isunder voltage.

Locking using 230 VAC undervoltage coil in position 0 (factory fitted)

Rating (A) SIRCOVER Operation Figure References

direct 3 consult us

2000 … 3150 direct 3 4409 9161

Locking using CASTELL type K lock (not included)

Rating (A) SIRCOVER Operation Figure References

125 … 1800 external 4 1499 7702

2000 … 3150 external 4 2799 7003

800 … 1800

Rating (A)SIRCOVER by-pass

125 … 200

Rating (A) SIRCOVER by-pass

125 … 200

800 … 1600direct consult us250 … 630

Rating (A) SIRCOVER by-pass

consult us

Rating (A) SIRCOVER by-pass

Rating (A)SIRCOVER by-pass

125 … 630800 … 1600

4 1499 7701

800 … 1600

Page 10: Change Over

A. 121

Changeover switches

SIRCOVER and SIRCOVER by-pass

SOCOMEC general catalogue This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

Characteristics (according to IEC 60947-3)

Rated operation currents Ie (A) Rated voltage Load duty category A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1)

400 VAC AC-21 A / AC-21 B 125/125 160/160 200/200 250/250 400/400 500/500 630/630AC-22 A / AC-22 B 125/125 160/160 200/200 250/250 400/400 500/500 630/630AC-23 A / AC-23 B 125/125 160/160 160/160 250/250 250/250 500/500 500/500

690 VAC(2) AC-20 A / AC-20 B 125/125 160/160 200/200 250/250 400/400 500/500 630/630AC-21 A / AC-21 B 125/125 160/160 160/160 200/250 200/250 400/400 500/500AC-22 A / AC-22 B 125/125 125/125 125/125 125/160 125/160 250/315 315/315AC-23 A / AC-23 B 63/80 63/80 63/80 100/125 100/125 160/200 160/200

220 VDC DC-20 A / DC-20 B 125/125 160/160 200/200 250/250 400/400 500/500 630/630DC-21 A / DC-21 B 125/125 160/160 160/160 250/250 250/250 500/500 630/630DC-22 A / DC-22 B 125/125 160/160 160/160 250/250 250/250 400/500 500/500DC-23 A / DC-23 B 125/125 125/125 125/125 200/200 200/200 400/400 500/500

440 VDC DC-20 A / DC-20 B 125/125 160/160 200/200 250/250 400/400 500/500 630/630DC-21 A / DC-21 B 125(3)/125(3) 125(3)/125(3) 125(3)/125(3) 200(3)/200(3) 200(3)/200(3) 400(3)/400(3) 500(3)/500(3)

DC-22 A / DC-22 B 125(3)/125(3) 125(3)/125(3) 125(3)/125(3) 200(3)/200(3) 200(3)/200(3) 315(3)/400(3) 500(3)/500(3)

DC-23 A / DC-23 B 125(4)/125(4) 125(4)/125(4) 125(4)/125(4) 200(4)/200(4) 200(4)/200(4) 400(4)/400(4) 500(4)/500(4)

(1) A/B: Category with index A = frequent operation - Category with index B = infrequent operation.(2) With terminal shrouds or phase barrier.(3) 3-pole device with 2 pole in series for the + and 1 pole for the -.(4) 4-pole device with 2 pole in series by polarity.(5) The power value is given for information only, the current values vary from one manufacturer to another.(6) For a rated operating voltage Ue = 400 VAC.(7) Increased endurances: please consult us.

Thermal current Ith (40°C) Rated insulation voltage Ui (V) 800 800 800 800 800 1000 1000Rated impulse withstand voltage Uimp (kV) 8 8 8 8 8 12 12

Operational power in AC-23 (kW)(1)(5)

At 400 VAC without pre-break AC 63/63 80/80 80/80 132/132 132/132 280/280 280/280At 690 VAC without pre-break AC 55/75 55/75 55/75 90/110 90/110 150/185 150/185

Reactive power (kvar)(5)

At 400 VAC 55 75 90 115 185 230 290

Fuse protected short-circuit withstand (kA rms prospective)(6)

Prospective short-circuit current (kA rms) 100 100 50 50 18 100 70Associated fuse rating (A) 125 160 200 250 400 500 630

Overload capacityRated short-time withstand current 1 s. Icw (kA rms) 7 7 7 9 9 13 13Short-circuit making capacity (kA peak)(6) 20 20 20 30 30 45 45

630 A500 A125 A 160 A 200 A 250 A 400 A

ConnectionMinimum Cu cable section (mm2) 35 50 50 95 185 240 2 x 150Minimum Cu busbar section (mm2) - - - - - - 2 x 30 x 5Maximum Cu cable section (mm2) 50 95 95 150 240 240 2 x 300Maximum Cu busbar width (mm) 25 25 25 32 32 40 50Min. tightening torque (Nm) 9 9 9 20 20 20 20

Mechanical characteristicsEndurance (number of operating cycles)(7) 10 000 10 000 10 000 10 000 10 000 5 000 5 000Weight of 3 p switch (kg) 1.5 1.6 1.8 2 3 3.5 3.5Weight of 4 p switch (kg) 1.6 1.7 1.9 2.1 3.5 4 4

Page 11: Change Over

A. 122 This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

��

FunctionsReferencesAccessoriesCharacteristicsDimensions

Changeover switches

SIRCOVER andSIRCOVER by-pass125 to 3150 A

SOCOMEC general catalogue

Characteristics (according to IEC 60947-3)

Rated operation currents Ie (A) Rated voltage Load duty category A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1) A/B(1)

400 VAC AC-21 A / AC-21 B 800/800 1250/1250 1600/1600 1800/1800 2000/2000 2500/2500 3150/3150AC-22 A / AC-22 B 800/800 1250/1250 1600/1600 1800/1800 2000/2000 2000/2500 2500/2500AC-23 A / AC-23 B 800/800 1250/1250 1250/1250 1250/1250 1250/1250 1250/1250 1250/1250

690 VAC(2) AC-20 A / AC-20 B 800/800 1250/1250 1600/1600 1800/1800 2000/2000 2500/2500 3150/3150AC-21 A / AC-21 B 800/800 800/800 1000/1000 1000/1000 2000/2000 2000/2500 2000/2500AC-22 A / AC-22 B 800/800 800/800 1000/1000 1000/1000 1000/1000 1000/1000 1000/1000AC-23 A / AC-23 B 200/250 200/250 500/500 500/500 800/800 800/800 800/800

220 VDC DC-20 A / DC-20 B 800/800 1250/1250 1600/1600 1800/1800 2000/2000 2500/2500 3150/3150DC-21 A / DC-21 B 800/800 1250/1250 1250/1250 1250/1250 2000/2000 2000/2500 2000/2500DC-22 A / DC-22 B 800/800 1250/1250 1250/1250 1250/1250 1250/1600 1250/1600 1250/1600DC-23 A / DC-23 B 800/800 1250/1250 1250/1250 1250/1250 1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3)

440 VDC DC-20 A / DC-20 B 800/800 1250/1250 1600/1600 1800/1800 2000/2000 2500/2500 3150/3150DC-21 A / DC-21 B 800(3)/800(3) 1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3) 1250/1250 1250/1250 1250/1250DC-22 A / DC-22 B 800(3)/800(3) 1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3)

DC-23 A / DC-23 B 800(3)/800(3) 1250(3)/1250(3) 1250(3)/1250(3) 1250(3)/1250(3) 1000(3)/1000(3) 1000(3)/1000(3) 1000(3)/1000(3)

(1) A/B: Category with index A = frequent operation - Category with index B = infrequent operation.(2) With terminal shrouds or phase barrier.(3) 4-pole device with 2 pole in series by polarity.(4) The power value is given for information only, the current values vary from one manufacturer to another.(5) For a rated operating voltage Ue = 400 VAC.(6) Increased endurances: please consult us.

Thermal current Ith (40°C) Rated insulation voltage Ui (V) 1000 1000 1000 1000 1000 1000 1000Rated impulse withstand voltage Uimp (kV) 12 12 12 12 12 12 12

Operational power in AC-23 (kW)(1)(4)

At 400 VAC without pre-break AC 450/450 710/710 710/710 710/710 710/710 710/710 710/710At 690 VAC without pre-break AC 185/220 185/220 475/475 475/475 750/750 750/750 750/750

3150 A2500 A800 A 1250 A 1600 A 1800 A 2000 A

Reactive power (kvar)(4)

At 400 VAC 365 575 - - - - -

Fuse protected short-circuit withstand (kA rms prospective)(5)

Prospective short-circuit current (kA rms) 50 100 100 100 100 100 -Associated fuse rating (A) 800 1250 2 x 800 2 x 800 2 x 1000 2 x 1250 -

Overload capacityRated short-time withstand current 1 s. Icw (kA rms) 26 35 50 50 50 50 55Short-circuit making capacity (kA peak) (5) 55 80 110 110 110 110 120

ConnectionMinimum Cu cable section (mm2) 2 x 185 - - - - - -Minimum Cu busbar section (mm2) 2 x 40 x 5 2 x 60 x 5 2 x 80 x 5 2 x 80 x 5 3 x 100 x 5 4 x 100 x 5 4 x 100 x 5Maximum Cu cable section (mm2) 2 x 300 4 x 185 6 x 185 6 x 185 - - -Maximum Cu busbar width (mm) 63 63 100 100 125 125 125Min. tightening torque (Nm) - 20 40 40 40 40 40

Mechanical characteristicsEndurance (number of operating cycles)(6) 3 000 3 000 4 000 4000 3 000 2 500 2 500Weight of 3 p switch (kg) 17.5 22.5 34 34 70 72 98Weight of 4 p switch (kg) 21 27.5 42 42 85 88 110

Page 12: Change Over

A. 123

Changeover switches

SIRCOVER and SIRCOVER by-pass

SOCOMEC general catalogue This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

Dimensions• SIRCOVER 125 to 1800 ADirect front operation External front operation

BA

CA

CA

AA

AC

M10A

XJ

T T T

N

U W

O

III

ZY

C 18H

L1

V

Y

Z1

II I

H

E min.

HA

8.5 1

40

4 Ø 7Ø 37

28

A

B

45

125

61

210

0

II

I

90°

90°2

svr_

072_

f_1_

x_ca

t

• SIRCOVER 2000 to 3150 A

Direct front operation External front operation

610518

4’-8’2’-6’ 4-8 2-6

1’-5’

Z3Z2

Z1Z Y Y

3’-7’ 1-5 3-7

60.5 12012.5 120 120 46.5 51.5

561

350

AA

11

7 - 7’ 5 - 5’ 3 - 3’ 1 - 1’

8 - 8’ 6 - 6’ 4 - 4’ 2 - 2’

M 88F

A

1

590 110

545

50

50

4 ø 4.5ø 31

65

2

545

svr_

095_

b_1_

x_ca

t

1. Terminal screen. 2. Minimum length with shaft extension: 650.

Rating(A)

Overall dimensions Switch body Switch mounting Connection terminalsA 3p. A 4p. F 3p. F 4p. M 3p. M 4p. Y Z Z1 Z2 Z3 AA

2000 576 696 447.5 567.5 347 467 10 78.5 225.5 309.5 456.5 4552500 576 696 447.5 567.5 347 467 10 78.5 225.5 309.5 456.5 4553150 576 696 447.5 567.5 347 467 15 78.5 230.5 309.5 461.5 505

A. External operation handle S2 type: 125 to 630 A.

B. External operation handle S3 type: 800 to 1800 A.

1. Terminal shrouds.

2. Direct operation handle:

- 125 to 630 A: L1 = 140 mm.- 800 to 1800 A: L1 = 210 mm.

Rating(A)

Overall dimensions Switch body Switch mounting Connection terminalsA 3p. A 4p. C E min AC H HA J 3p. J 4p. M 3p. M 4p. N T U V W X 3p. X 4p. Y Z Z1 AA BA CA

125 221 251 218 210 235 148 25 182 212 156 186 101 36 20 25 8.5 56 50 3.5 28 124 135 115 10160 221 251 218 210 235 148 25 182 212 156 186 101 36 20 25 8.5 56 50 3.5 28 124 135 115 10200 221 251 218 210 235 148 25 182 212 156 186 101 36 20 25 8.5 56 50 3.5 28 124 135 115 10250 262 312 218 210 280 148 25 223 273 196 246 116 50 25 30 11 61 61 3.5 30 124 160 130 10400 262 312 218 210 280 148 25 223 273 196 246 116 50 35 35 11 61 61 3.5 30 124 170 140 15500 319 379 295 280 401 225 25 272 332 246 306 176 65 32 37 13 70.5 65.5 5 43 180 235 205 15630 319 379 295 280 400 225 25 272 332 246 306 176 65 45 50 13 70.5 65.5 5 43 180 260 220 20800 386 466 375 425 459 298 29 306.5 336 336 250 80 50 60,5 15 48 48 7 66.5 253.5 321 26.51250 386 466 375 425 459 298 29 306.5 336 336 250 80 60 65 48 48 7 66.5 255.5 330 29.51600 478 598 375 425 461 298 29 388.5 347 467 250 120 90 43.5 54 54 8 66.5 255.5 288 151800 478 598 375 425 461 298 29 388.5 347 467 250 120 90 43.5 54 54 8 66.5 255.5 288 15

386.5386.5518.5518.5

16x1112.5x512.5x5

Terminalshrouds

Page 13: Change Over

BA

CA

CA

AA

AC

M10A

X T TJ

T

N

U W8.5

O

III

H

Y Y YZ

Z1Z2

C 18

V

L1

I III

1

40

4 Ø 7Ø 37

28

HE min.

HA 45

125

61

210

B

A

504 Ø 4.5

Ø 31

50

0

II

I

90°

90°

HE min.

HA

103

330

==

C

0

II

I

90°

90°

2

svr_

070_

g_1_

x_ca

t

A. 124 This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

FunctionsReferencesAccessoriesCharacteristicsDimensions

Changeover switches

SIRCOVER andSIRCOVER by-pass125 to 3150 A

SOCOMEC general catalogue

Dimensions• SIRCOVER by-pass 125 to 1600 A

Direct front operation

A. External operation handle S2 type: 125 to 200 A.

B. External operation handle S3 type: 250 to 630 A.

C. External operation handle: 800 to 1600 A.

1. Terminal shrouds.2. Direct operation handle:

- 125 to 200 A: L1 = 140 mm.- 250 to 630 A: L1 = 210 mm.- 800 to 1600 A: L1 = Ø 330 mm.

Rating(A)

Overalldimensions

Terminalshrouds

Switchbody

Switchmounting Connection terminals

A 3+6 p

A 4+8 p

C Emin.

AC H HA J 3+6 p

J 4+8 p

M 3+6 p

M 4+8 p

N T U V W X 3+6 p

X 4+8 p

Y Z Z1 Z2 AA BA CA

125 221 251 313 320 235 243 25 182 212 156 186 101 36 20 25 8.5 56 50 3.5 28 124 219 135 115 10160 221 251 313 320 235 243 25 182 212 156 186 101 36 20 25 8.5 56 50 3.5 28 124 219 135 115 10200 221 251 313 320 235 243 25 182 212 156 186 101 36 20 25 8.5 56 50 3.5 28 124 219 135 115 10250 262 312 313 298 280 243 25 223 273 196 246 116 50 25 30 11 61 61 3.5 30 124 219 160 130 10400 262 312 313 298 280 243 25 223 273 196 246 116 50 35 35 11 61 61 3.5 30 124 219 170 140 15500 319 379 432 417 401 362 25 272 332 246 306 176 65 32 37 13 70.5 65.5 5 43 180 317 235 205 15630 319 379 432 417 400 362 25 272 332 246 306 176 65 45 50 13 70.5 65.5 5 43 180 317 260 220 20800 386 466 560 550 459 479 29 306.5 386.5 255 335 250 80 50 60.5 15 48 48 7 66.5 253.5 439.5 321 26.51250 386 466 560 550 459 479 29 306.5 386.5 255 335 250 80 60 65 48 48 7 66.5 253.5 439.5 320 29.251600 478 598 560 550 461 479 29 388.5 518.5 347 467 250 120 90 54 54 8 66.5 253.5 439.5 288 15

16 x 1143.5

External front operation

12.5 x 5

Page 14: Change Over

A. 125

Changeover switches

SIRCOVER and SIRCOVER by-pass

SOCOMEC general catalogue This document is not a contract. SOCOMEC reserves the right to modify featureswithout prior notice in view of continued improvement. 2006-2007

Dimensions

• SIRCOVER 2000 to 2500 A

ø 13

4020

4020 20

80

svr_

079_

a_1_

x_ca

t

9650

50 25

28

4 x Ø 6.5 3 x Ø 6.5Ø 31

sirc

o_22

4_b_

1_x_

cat

• SIRCOVER 3150 A50

25

5035 35120

ø 13

100

svr_

080_

b_1_

x_ca

t

Connection terminals

Door drilling with CASTELL K lock

Door drilling with RONIS EL11AP lock

20 20

Ø 37

Ø 37

2 Ø 6.5

4 Ø 7

1414

7922

45°

28.5

svr_

101_

a_1_

x_ca

t

• SIRCOVER 125 to 1800 A SIRCOVER by-pass 125 to 630 A

33 8.58.5

50

3310

ø 9

ø 15

svr_

077_

a_1_

x_ca

t

16 x 11

60

28.5 15.7515.75

28.5

15

svr_

078_

b_1_

x_ca

t55

12.5

3025

90

ø12.5

453025

45

15

sirc

o_27

1_a_

1_x_

cat

20

4 Ø 5.5Ø 26

20

Ø 37

4 Ø 7

1414

73.5

2624

45° 3.5

28

svr_

102_

a_1_

x_ca

t

• SIRCOVER 2000 to 3150 A andSIRCOVER by-pass 800 to 1600 A

• SIRCOVER and SIRCOVER by-pass 800 A

• SIRCOVER and SIRCOVER by-pass 1250 A

• SIRCOVER 1600 to 1800 ASIRCOVER by-pass 1600 A

• SIRCOVER 125 to 1800 ASIRCOVER by-pass 125 to 630 A