Upload
nabil160874
View
215
Download
0
Embed Size (px)
Citation preview
8/20/2019 Ch 9 - l Controls Excitation
1/40
GENERATOR CONTROL AND PROTECTION
Supplemental Controls
8/20/2019 Ch 9 - l Controls Excitation
2/40
GENERATOR CONTROL AND PROTECTION
Outline• Basic Control Functions
• Supplemental Control Functions
– Take Over (HV/LV Gates)– Summing Point
• Reactive current compensators
• var/power factor controllers
• Limiter functions– Over / under excitation
– V/Hz
– Stator current– Field temperature limiters
8/20/2019 Ch 9 - l Controls Excitation
3/40
GENERATOR CONTROL AND PROTECTION
Basic Control Functions• Basic control functions “Manual” or
“Automatic”• Manual: operator control of field excitation
directly
• Automatic: maintaining generator terminal
voltage at a predetermined level without
operator action
8/20/2019 Ch 9 - l Controls Excitation
4/40
GENERATOR CONTROL AND PROTECTION
Supplemental Control Functions• Reactive current compensators
• var/power factor controllers• Limiter functions
– Over / under excitation– V/Hz
– Stator current
– Field temperature limiters
8/20/2019 Ch 9 - l Controls Excitation
5/40
GENERATOR CONTROL AND PROTECTION
Supplemental Control Functions• There are two basic ways a supplemental
control function can interface with theAVR, take over and summing point
• Take over utilizes either a “High Value” or
a “Low Value” gate
8/20/2019 Ch 9 - l Controls Excitation
6/40
GENERATOR CONTROL AND PROTECTION
Supplemental Control Functions• The HV (LV) gate selects one of two
inputs, based on which signal is higher(lower), and provides it to the output of the
gate.
IN 1
IN 2
HV
GATE
LV
GATE
IN 1
IN 2
OUT OUT
8/20/2019 Ch 9 - l Controls Excitation
7/40
GENERATOR CONTROL AND PROTECTION
Supplemental Control Functions
• A summing point implementation adds the
supplemental control signal into the AVRssumming junction or at some other point in
the AVR control path
ΣΣΣΣ
Vsupplemental input
Vsense
Vref error signal
output
+
-
+
8/20/2019 Ch 9 - l Controls Excitation
8/40
GENERATOR CONTROL AND PROTECTION
Static Exciter showing both Summing
Point and Take Over Style SupplementalControl Functions
Voel
HVGATE
LVGATECONTROLLERHVGATEVref
Vuel
Vsense
Vpss
Vuel
Voel
ΣΣΣΣΣΣΣΣ
+
+
Vpss
-
Vuel
+
-
OUTPUT+
+
8/20/2019 Ch 9 - l Controls Excitation
9/40
GENERATOR CONTROL AND PROTECTION
Reactive Current Compensators
• Reactive droop compensation is used to
facilitate reactive current sharing betweenmachines tied in parallel
VC = | V
T +/- I
T (R
C + jX
C) |
VT
VC
IT
8/20/2019 Ch 9 - l Controls Excitation
10/40
GENERATOR CONTROL AND PROTECTION
Var/PF Controllers
• Supervisory controls that act to modify the
reference to the AVR in order to maintainreactive power or power factor at a
predetermined value.
• Some implementations interface to the
AVR through the reference adjuster (IEEE
type 1)• Others feed a continuous signal into the
summing junction (IEEE type 2)
8/20/2019 Ch 9 - l Controls Excitation
11/40
GENERATOR CONTROL AND PROTECTION
Var/PF Controllers
• Reference adjuster: A device or control
function that modifies the Vref input to theAVR via raise and lower command inputs
• Older excitation systems - motor operated
control (MOC) or motor operated
potentiometer (MOP)
• Modern digital excitation systemsimplement this functionality in software
8/20/2019 Ch 9 - l Controls Excitation
12/40
GENERATOR CONTROL AND PROTECTION
Var/PF Controllers
• A type 1 var / power factor controller
implements the control in much the sameway as the operator would, implementing a
“dead band” where no control action
occurs, and an intermittent or continuousraise / lower command.
8/20/2019 Ch 9 - l Controls Excitation
13/40
GENERATOR CONTROL AND PROTECTION
Type 1 - Var/PF Controllers
8/20/2019 Ch 9 - l Controls Excitation
14/40
GENERATOR CONTROL AND PROTECTION
Var/PF Controllers
• A type 2 var / power factor controller adds
a signal into the AVRs summing point,providing continuous correction signals.
The PI style of control is normally adjusted
for slow response so it won’t impact theAVRs ability to control excitation during
system fault conditions.
8/20/2019 Ch 9 - l Controls Excitation
15/40
GENERATOR CONTROL AND PROTECTION
Type 2 - Var/PF Controllers
KIs
ΣΣΣΣ
Q
VVAR
+
+
To AVRsumming
pointVCLMT
VCLMT
-VCLMT
-VCLMT
QREF KP
ΣΣΣΣ+
-
EXLON
0
8/20/2019 Ch 9 - l Controls Excitation
16/40
GENERATOR CONTROL AND PROTECTION
Limiters
Limiters are used to limit generator operation
to the area bounded by the capability curve of
the machine. Q
P
StatorCurrent
Limit
Over
ExcitationLimit
Under
ExcitationLimit
8/20/2019 Ch 9 - l Controls Excitation
17/40
GENERATOR CONTROL AND PROTECTION
Over Excitation Limiter
A control function that limits the field
current of a synchronous machine or
excitation equipment to permissible
values with regard to thermal overload.
Action may be immediate or timedelayed. See field current/voltage limiter.
Also called a maximum excitation limiter.
(IEEE421.1)
8/20/2019 Ch 9 - l Controls Excitation
18/40
GENERATOR CONTROL AND PROTECTION
OEL
• Designed to protect the field from damage due toexcessive heating
• Field thermal limits defined in ANSI/IEEE C50.13• Allowable field voltage versus time
– 208% for 10 seconds
– 146% for 30 seconds– 125% for 60 seconds
– 112% for 120 seconds
• New standard will be defined with equation
8/20/2019 Ch 9 - l Controls Excitation
19/40
GENERATOR CONTROL AND PROTECTION
Rotor Heating Curve
0 10 20 30 40 50 60 70 80 90 100 110 120 100
110
120
130
140
150
160
170
180
190
200
210
Time (sec.)
E x c i t a t i o n
l e v e l % o f
r a t e d
8/20/2019 Ch 9 - l Controls Excitation
20/40
GENERATOR CONTROL AND PROTECTION
OEL
• Steady state limit value can be a function of
cooling air temperature, hydrogen pressure
or other parameter
• Field current measurement techniques
– Field shunt– Saturating field current transducer
– Hall Effect device
C bili C f S h
8/20/2019 Ch 9 - l Controls Excitation
21/40
GENERATOR CONTROL AND PROTECTION
ARMATUREWINDING
HEATING
LIMITATION
Capability Curve of a Synchronous
Generator+1.0
-1.0
1.0 1.2 1.4
+0.8
-0.8
0.8
+0.6
-0.6
0.6
+0.4
-0.4
0.4
+0.2
-0.2
0.2
0
0
KILOWATTS PER UNIT
L E A
D I N G
L A G G I N
G
R E A C T I V
E P O W E R
P E R
U N I T
FIELD WINDING
HEAT LIMITATION
-3V t2/X
s
8/20/2019 Ch 9 - l Controls Excitation
22/40
GENERATOR CONTROL AND PROTECTION
Summing Point OEL Model
KI
s
ΣΣΣΣ
IOEL_REF
0.00833 KG
VREF
IFD
VOEL
ΣΣΣΣ +
+
+
-
ΣΣΣΣ
VREF
VC
To PIDController
0
0
VREF
-
+
-
8/20/2019 Ch 9 - l Controls Excitation
23/40
GENERATOR CONTROL AND PROTECTION
Under Excitation Limiter
A function that either overrides the voltageregulator action (takeover type) or adds to
terminal voltage setpoint (summing type), tomaintain synchronous machine excitation suchthat synchronous machine output remains abovea preset level. Various terms have been applied,
often descriptive of the measured variable;minimum excitation limiter, underexcitedreactive limit, and rotor angle limiter.
(IEEE421.1)
8/20/2019 Ch 9 - l Controls Excitation
24/40
GENERATOR CONTROL AND PROTECTION
UEL
• Prevents operation which jeopardizes
stability or could lead to loss of synchronism
• Designed to protect the armature core end
iron from damage due to excessive heating
• Prevents loss-of-excitation relays fromoperating
8/20/2019 Ch 9 - l Controls Excitation
25/40
GENERATOR CONTROL AND PROTECTION
UEL
• Two styles, Summing Point or Take Over
– Summing point works through the AVR by
adding a signal into the summing junction
– Take over style uses a high value (HV) gate to
select the higher of the two control functions,
either the AVR or the limiter. The limiter acts
to override the normal action of the AVR
8/20/2019 Ch 9 - l Controls Excitation
26/40
GENERATOR CONTROL AND PROTECTION
UEL
• Summing Point
– Summing point adds a signal into the summing
junction of an AVR
– Provides smooth transition in and out of limiter
– Does not cause integrator windup– Does not provide direct control of field current
– Coordinates with PSS
8/20/2019 Ch 9 - l Controls Excitation
27/40
GENERATOR CONTROL AND PROTECTION
UEL
• Take Over
– Provide signal to high value gate
– The higher of two signals is passed to output– Transition in and out of limiter can cause
discontinuities in excitation
– Can cause integrator windup
– Can cause system instabilities due to removal ofPSS stabilizing signal when in limit
– Provides direct control of field current
Capability Curve of a Synchronous
8/20/2019 Ch 9 - l Controls Excitation
28/40
GENERATOR CONTROL AND PROTECTION
Capability Curve of a Synchronous
Generator
ARMATURE
WINDING
HEATING
LIMITATION
+1.0
-1.0
1.0 1.2 1.4
+0.8
-0.8
0.8
+0.6
-0.6
0.6
+0.4
-0.4
0.4
+0.2
-0.2
0.2
0
0
KILOWATTS PER UNIT
L E A D I N G
L A G G I N G
R E A C
T I V E P O W E R
P
E R U N I T
ARMATURE CORE
END IRON
HEATING LIMITATION
8/20/2019 Ch 9 - l Controls Excitation
29/40
GENERATOR CONTROL AND PROTECTION
Circular UEL Implementation
VUC
= |KUC
VT - jI
T| VUELΣΣΣΣ
+-
KUL
+ KUI
/ s
VUR
= |KUR
VT |
VT
IT
8/20/2019 Ch 9 - l Controls Excitation
30/40
GENERATOR CONTROL AND PROTECTION
Circular UEL Characteristic
Q
P
Under Excitation Limit
KUC KUR
8/20/2019 Ch 9 - l Controls Excitation
31/40
GENERATOR CONTROL AND PROTECTION
Volts per Hertz Limiter
A function that acts to prevent the ratio of
terminal voltage to frequency from
exceeding a preset level. The purpose isto prevent excessive magnetic flux in the
synchronous machine and connectedtransformers. (IEEE421.1)
8/20/2019 Ch 9 - l Controls Excitation
32/40
GENERATOR CONTROL AND PROTECTION
Regulator Volts/Hertz Characteristic
1 pu V/Hz
VT
f
VNOM
fCORNER
=fNOM
1.05 pu V/Hz
8/20/2019 Ch 9 - l Controls Excitation
33/40
GENERATOR CONTROL AND PROTECTION
Volts per Hertz Limiter
+
-K
VHZ Σ
-
Corner
frequency
generatorfrequency
AVRSumming
PointΣ+
-
0
1.0
VREF
VC
8/20/2019 Ch 9 - l Controls Excitation
34/40
GENERATOR CONTROL AND PROTECTION
Stator Current Limiter
A function that acts to prevent the stator
current from exceeding a preset value. If
the generator is operating overexcited, thelimiter will decrease excitation, while in
underexcited operation the limiterincreases excitation. (IEEE421.1)
8/20/2019 Ch 9 - l Controls Excitation
35/40
GENERATOR CONTROL AND PROTECTION
SCL
• Designed to protect the armature from damage
due to excessive heating
• Armature thermal limits defined in ANSI/IEEEC50.13
• Allowable armature current versus time
– 226% for 10 seconds
– 154% for 30 seconds
– 130% for 60 seconds– 116% for 120 seconds
Capability Curve of a Synchronous
8/20/2019 Ch 9 - l Controls Excitation
36/40
GENERATOR CONTROL AND PROTECTION
ARMATUREWINDING
HEATING
LIMITATION
Capability Curve of a Synchronous
Generator+1.0
-1.0
1.0 1.2 1.4
+0.8
-0.8
0.8
+0.6
-0.6
0.6
+0.4
-0.4
0.4
+0.2
-0.2
0.2
0
0
KILOWATTS PER UNIT
L E A D I N G
L A G G I N
G
R E A C T I V
E P O W E R
P E R
U N I T
RATED PF
LAGGING
0.95 PF
LEADING
8/20/2019 Ch 9 - l Controls Excitation
37/40
GENERATOR CONTROL AND PROTECTION
Field Temperature Limiter• The temperature of the stationary winding of a generator
may be measured with some form of a temperature-measuring device, like a thermocouple or a Resistance
Temperature Detector (RTD).• The temperature of the field winding, on the other hand,
is much more difficult to measure because it is revolvingon the shaft.
• One method of calculating the field temperature is tomeasure the effective “dc” resistance of the field andcomparing it to the value at a known temperature
(normally 25°C).
8/20/2019 Ch 9 - l Controls Excitation
38/40
GENERATOR CONTROL AND PROTECTION
Field Temperature Limiter
• Using the following formula, you can
calculate the field temperature.
( ) 5.2345.234 −+= COLDCOLD
HOT
HOT T R
R
T
8/20/2019 Ch 9 - l Controls Excitation
39/40
GENERATOR CONTROL AND PROTECTION
Summary• Basic Control Functions
• Supplemental Control Functions– Take Over (HV/LV Gates)
– Summing Point
• Reactive current compensators
• var/power factor controllers
• Limiter functions– Over / under excitation
– V/Hz
– Stator current
– Field temperature limiters
8/20/2019 Ch 9 - l Controls Excitation
40/40
GENERATOR CONTROL AND PROTECTION
QUESTIONS?