The Centric uPS from 25kw to 1.6MwGamatronic is proud to present the Centric, an innovative UPS, available in many configurations (25, 50, 75, 100, 175, 200, 400, 600, 800, 1000, 1200, 1400, 1600kW).
The Centric provides reliable, clean, regulated AC power at an attractive price. For users with greater power requirements, up to five Centric units can be operated in a parallel configuration for five times the power.
The Centric’s double conversion topology provides high quality power regulation in accordance with IEC 62040 VFI-SS-111, and AC/AC efficiency up to 96%.
The Centric battery is true online as per IEC 62040, guaranteeing instant availability of backup power in the event of mains failure, and provides high unique DC/AC efficiency of up to 98%.
The Centric’s vertical and horizontal modularity reduce the down time thus providing a fault tolerant power source to critical loads and applications.
The Centric’s reliability, flexibility, intelligent features and design make it a great choice for your data center.
features• Advanced colorful LCD touch screen
• True on-line battery
• Up to 96% efficiency
• High power output
• Small footprint
• Lightweight
• Optional manual maintenance bypass switch
• Hot swappable power modules
• Hot swappable system controller
CENTRIC
Power usage Effectiveness (PuE)
Centric is an ideal efficient UPS for Tier 3 and 4 data centers with a low load. The Centric can achieve 96% efficiency in a load between 20% to 60%.
2N+1 (Tier 4) Application
25% LOAD CENTRIC 2 x 200kW
25% LOAD CENTRIC 2 x 200kW
100% IT LOAD
Efficiency vs. load
Load 200kW(%)
Efficiency
The PC-based centric controller enhances data centre management systems with its unique abilities:
• Built-in flexible connectivity
• Intelligent interface
• Fail-safe (non-critical for UPS operation)
• Hot swappable
Additional features include:
• RS232
• Modbus RS485
• Modbus TCP/IP
• USB
• SNMP
• Configurable web interface
• Unlimited servers shutdown
• Unlimited email notifications
• Data-rich system log
• Multi-language interface
footprint Power: 49w / cm2 ׀ Power density: 0.4w / cm3
CENTRIC Power density
76 cm
120 cm
202 cm
120 cm
76 cm54 cm
Vertical modularity in a basic unit is 25kW per power module; the vertical stack is scalable to up to 8 power modules (200kW). Horizontal modularity of a basic unit is up to 200kW, the horizontal scalability is up to 8 units (1600kW).
Modularity and Scalability
front view202 cm
350 cm
Vertical and Horizontal Redundancy with Decentralized or Centralized Redundancy Battery
Solutions
Up to 175kW Vertical & Horizontal
Redundancy
Up to 200kW Horizontal
Redundancy
Up to 350kWVertical
Redundancy
Up to 75kW Vertical & Horizontal Redundancy
Up to 100kW Horizontal
Redundancy
Up to 150kW VerticalRedundancy
Up to 150kW Vertical & Horizontal
Redundancy
Up to 200kW Horizontal
Redundancy
Up to 225kWVertical
Redundancy
Up to 225kW Vertical & Horizontal
Redundancy
Up to 300kW Horizontal
Redundancy
Up to 300kW Vertical
Redundancy
Up to 350kW Vertical & Horizontal
Redundancy
Up to 400kW Horizontal
Redundancy
Up to 525kWVertical
Redundancy
Up to 525kW Vertical & Horizontal
Redundancy
Up to 600kW Horizontal
Redundancy
Up to 700kWVertical
Redundancy
Up to 700kW Vertical & Horizontal
Redundancy
Up to 800kW Horizontal
Redundancy
Up to 875kWVertical
Redundancy
* All specifications are subject to change without prior notice.
CENTRIC uPS System SpecificationsTopology Modular, hot swappable, double-conversion, VFI, online battery
Operation Continuous
INPUT
Voltage (V) 3x400 (4 wires + Gnd)
Voltage range (%)-20 / +15 (360 ~ 460 Vac: full power; 320 ~ 360 Vac: derated 20 %)
Current (A) 3 × 42 per module – no inrush current at startup
Rectifier frequency (Hz) 40 ~ 70
Power walk-in (sec) >60
Power factor correction >0.99
THDI (%) <3
Inrush current None
OUTPUT
Rated Power kW) 25 ~ 1600
Nominal frequency (Hz) 50/60
Frequency tracking range (Hz) ±(0.5, 1, 2, 3, 4), selectable
Frequency tracking slew rate (Hz/sec) 1
Frequency (in free-running mode) (Hz) 50/60 ±0.1 %
Nominal voltage (Vac) 3x380, 3x400, 3x415 (4 wires + Gnd)
Static voltage regulation (%) ±1
Regulation for 100 % unbalanced load (%) ±1
Dynamic response to 100 % load step (%) ±2
Overload withstandInverter mode 110 % : 10 min, 125 % : 60 s, 150 % : 30 s
Bypass mode 125 % : 10 min, 1000 % : 1 cycle
Waveform Sinusoidal
THD (%) Linear load: <2; non-linear load: <6
Load CF (max) 6:1
Power factor Any
AC/AC efficiency (nominal) (%) Up to 96
BATTERIES
DC-link voltage (Vdc) +/-405V (405 floating, accuracy to ±1 %)
Quantity 60 × 12 Vdc
Type Sealed, lead-acid. Lithium-ion batteries also supported
GENERAL
Maximum power dissipation (Po=25 kW) N*1041 W (N*3552 BTU/h), where N = # modules
Ambient temperature (°C) -10 to +40 (operating), -20 to +60 (storage)
Relative humidity (%) 95 maximum, non-condensing
Altitude (m) 1500 without derating
Enclosure IP20
Cooling system Multi-fan with speed control (forced)
DESIGN & MANUFACTURING STANDARDS
Safety IEC 62040-1
EMC IEC 62040-2
Design classification IEC 62040-3
Low magnetic field radiation EMF as per ICNIRP
DIMENSIONS
UPS MODEL 50 kW 100 kW 200 kW
# OF POWER MODULES 1 2 3 4 4 5 6 7 8
POWER OUTPUT (kW/kVA) 25 50 75 100 100 125 150 175 200
Height (mm) 932 1200
Width (mm) 540
Depth (mm) 757
Weight (kg) w/o batt. box 82.6 102.4 122.2 142 149.3 169.1 188.9 208.7 228.5
CENTRIC
Technical Specifications for the System Controller
Display LCD flat panel, touch-sensitive
Other indicators Audible alarm
Analog input channels 4 input dry contacts (N.O. / N.C.)
Real-time clock (RTC) Yes, with backup
Power meter kVA, kW, PF
Volt-free outputs (dry contacts) 6 outputs, rated 48 V / 1 A
Output dry contacts
AC failureDC failureUPS module(s) failureLoad on bypassBattery test failureOver/under temperatureOverload(Each system alarm type can be routed to the dry contact of your choice)
Communication ports Serial, Ethernet, USB
Communication protocols RS232, RS485, TCP/IP, SNMP, Modbus
Communications with system modules Serial, isolated
Events log 500 events
System operation without controller Unchanged
On-screen parameters
Load bar-graph3-phase voltages3-phase currentsBattery voltageStatus of each UPS moduleStatic-switch parameters and statusBattery sensor temperature
RTC operation without power Indefinitely
Power requirements 3 × 400 Vac and 405 Vdc
Remote indication panel capability Yes
* All specifications are subject to change without prior notice.
Technical Specifications for the System Controller
Choose the Centric and enjoy a reliable, clean, regulated AC power UPS.
This is the kind of feedback we continually receive from our customers:
“We are very satisfied with the Centric’s performance and back up of the critical load in the data center.”
With Regards,
Jacob Shaaltiel
Business Manager, Data Center Consulting
Technology Consulting
Hewlett-Packard (Israel) Ltd.
February 2017
GAMATRoNIC ElECTRoNIC INduSTRIES lTd.
ISRAEl (HEAdquARTERS)17 Hartum St. P.O. Box 45029, Jerusalem 9777517, Israel Tel: +972 2 588 8222 | Fax: +972 2 582 8875 [email protected] | www.gamatronic.com
GAMATRoNIC uk ltd. 15 Chester Road, Colmworth Business Park, Eaton Socon, Cambridgeshire, PE19 8YT, United Kingdom Tel: +44 (0)1480 479889/ 472665 | Fax: +44(0)1480 407865 [email protected] | www.gamatronic.co.uk
GAMATRoNIC SouTH AfRICA 377 Rivonia Boulevard, Rivonia 2128, Gauteng, South Africa Office: +27 11 593 2403 | Fax: +27 86 682 2468 [email protected] | www.gamatronic.co.za
GAMATRoNIC CHINA RM2001, No 1, Alley 100. East Tiyuhui Rd, Shanghai 200081, China Tel: +86 21 6587 2583 | [email protected] | www.gamatronic.cn