PLFY-1 PLFY-P-NCMU-E/NBMU-E (Feb. 2009) PLFY-P-NCMU-E PLFY-P-NBMU-E PLFY-P-NCMU-E/PLFY-P-NBMU-E 1. SPECIFICATIONS.................................................................................................................................................. PLFY-3 2. EXTERNAL DIMENSIONS..................................................................................................................................... PLFY-6 3. CENTER OF GRAVITY .......................................................................................................................................... PLFY-8 4. ELECTRICAL WIRING DIAGRAMS....................................................................................................................... PLFY-9 5 SOUND PRESSURE LEVELS ............................................................................................................................. PLFY-11 5-1. Sound Pressure Levels .............................................................................................................................. PLFY-11 5-2. NC Curves.................................................................................................................................................. PLFY-11 6. TEMPERATURE/AIRFLOW DISTRIBUTIONS .................................................................................................... PLFY-12 6-1. Temperature Distributions .......................................................................................................................... PLFY-12 6-2. Airflow Distributions.................................................................................................................................... PLFY-13 6-3. Branch Duct Capacities.............................................................................................................................. PLFY-14 7. VENTILATION AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS......................................... PLFY-20 7-1. PLFY-P-NCMU-E ....................................................................................................................................... PLFY-20 7-2. PLFY-P-NBMU-E with Multi-function Casement and Filters....................................................................... PLFY-20 8. OPTIONAL PARTS............................................................................................................................................... PLFY-22 8-1. Air Outlet Shutter Plate PAC-SH51SP-E for PLFY-P-NBMU-E.................................................................. PLFY-22 8-2. High Efficiency Filter Element PAC-SH59KF-E for PLFY-P-NBMU-E........................................................ PLFY-23 8-3. Multi-function Casement PAC-SH53TM-E for PLFY-P-NBMU-E ............................................................... PLFY-23 8-4. i-see Sensor Corner Panel PAC-SA1ME-E for PLFY-P-NBMU-E.............................................................. PLFY-24 8-5. Wireless Signal Receiver PAR-SF9FA-E for for PLFY-P-NBMU-E ........................................................... PLFY-24 7-1. External Heater Adapter CN24RELAY-KIT-CM3 ........................................................................................ PLFY-25 CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW)

CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-1PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

PLFY-P-NCMU-E/PLFY-P-NBMU-E

1. SPECIFICATIONS .................................................................................................................................................. PLFY-3

2. EXTERNAL DIMENSIONS ..................................................................................................................................... PLFY-6

3. CENTER OF GRAVITY .......................................................................................................................................... PLFY-8

4. ELECTRICAL WIRING DIAGRAMS ....................................................................................................................... PLFY-9

5 SOUND PRESSURE LEVELS ............................................................................................................................. PLFY-115-1. Sound Pressure Levels .............................................................................................................................. PLFY-115-2. NC Curves .................................................................................................................................................. PLFY-11

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS .................................................................................................... PLFY-126-1. Temperature Distributions .......................................................................................................................... PLFY-126-2. AirflowDistributions .................................................................................................................................... PLFY-136-3. Branch Duct Capacities .............................................................................................................................. PLFY-14

7. VENTILATION AIR INTAKE AMOUNT & STATIC PRESSURE CHARACTERISTICS ......................................... PLFY-207-1. PLFY-P-NCMU-E ....................................................................................................................................... PLFY-207-2. PLFY-P-NBMU-EwithMulti-functionCasementandFilters....................................................................... PLFY-20

8. OPTIONAL PARTS ............................................................................................................................................... PLFY-228-1. AirOutletShutterPlatePAC-SH51SP-EforPLFY-P-NBMU-E .................................................................. PLFY-228-2. HighEfficiencyFilterElementPAC-SH59KF-EforPLFY-P-NBMU-E ........................................................ PLFY-238-3. Multi-functionCasementPAC-SH53TM-EforPLFY-P-NBMU-E ............................................................... PLFY-238-4. i-seeSensorCornerPanelPAC-SA1ME-EforPLFY-P-NBMU-E .............................................................. PLFY-248-5. WirelessSignalReceiverPAR-SF9FA-EforforPLFY-P-NBMU-E ........................................................... PLFY-247-1. External Heater Adapter CN24RELAY-KIT-CM3 ........................................................................................ PLFY-25

CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW)

Page 2: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-2 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW)

PLFY-P-NCMU-EPLFY-P-NBMU-E

Various airflow pattern to meet your needs, strong airflow power, suitable for ceiling of max.13 -9" height

4-, 3-, or 2-way outlet selection

Fixed airflow direction per vane

Motorfor the vane

72 airflow patterns

850mm(33-1/2in.)

Fixed

Fixed Fixed

Fixed

Refrigerated showcase not affected by air conditioning

Top or bottom airflow setting via remote controller

1

23

Outside Inside

Grille Vane

Example (Convenient chain store)Airflow doesn't disturb the cooled air in show-casehelps energy saving.

1 Uniformly distribute the air onto the louver.2 3 Avoid airflow rising up.2 3 Avoid dust attachment.

Allowing long piping and versatility.

The PLFY not only brings outside air into your space, but the PLFY-P-NBMU-Ecan also branch over to air-condition an adjacent room.

Drain water lifted to 33” (PLFY-P-NBMU-E) or 19-7/16” (PLFY-P-NCMU-E)Precise airflow pattern on PLFY-P-NBMU-E

(on PLFY-P-NBMU-E)

PLFY-P-NBMU-E

PLFY-P-NBMU-EPLFY-P-NCMU-E

PLFY-P-NBMU-E

PLFY-P-NCMU-E

3.2HP 8.0HP4.0HP 5.0HPP08 P12 P15 P18 P30 P36 P48P06 P24 P27 P54 P72

10.0HPP96

0.8HP 1.0HP 1.3HP 1.6HP 2.0HP 2.5HP 2.8HP 5.6HPCassette ceiling

48,0006,700

Nominal cooling cap.*1Nominal heating cap.*2

6,000 8,000 12,000 15,000 18,000 24,000 27,000 30,000 36,000 54,000 72,000 96,00060,000 80,000 108,00027,000 30,000 34,000 40,000 54,0009,000 13,500 17,000 20,000

BTU/hBTU/h

* Nominal conditions *1, *2 are referred to in the Specification sheet.

Page 3: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-3PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

Model PLFY-P08NCMU-E PLFY-P12NCMU-E PLFY-P15NCMU-EPowersource 1-phase 208-230 V 60HzCoolingcapacity*1 (Nominal)

BTU / h 8,000 12,000 15,000 kW 2.3 3.5 4.4

Powerinput kW 0.05 0.06 0.06 Current input A 0.23 0.28 0.28

Heatingcapacity*2 (Nominal)

BTU / h 9,000 13,500 17,000 kW 2.6 4.0 5.0

Powerinput kW 0.05 0.06 0.06 Current input A 0.23 0.28 0.28

Externalfinish Galvanized Steel Sheet

External dimension H x W x Din. 9-1/4 x 22-7/16 x 22-7/16 9-1/4 x 22-7/16 x 22-7/16 9-1/4 x 22-7/16 x 22-7/16mm 235 x 570 x 570 235 x 570 x 570 235 x 570 x 570

Netweight lbs (kg) 34 (15.5) 37 (17) 37 (17)

Decoration panel

Model SLP-15AAUW SLP-15AAUW SLP-15AAUWExternalfinish Munsell No. 6.4Y 8.9/0.4Dimension in. 25/32 x 25-19/32 x 25-19/32 25/32 x 25-19/32 x 25-19/32 25/32 x 25-19/32 x 25-19/32H x W x D mm 20 x 650 x 650 20 x 650 x 650 20 x 650 x 650Net Weight lbs (kg) 7(3) 7(3) 7(3)

Heat exchanger Crossfin

Fan

TypexQuantity Turbofanx1 Turbofanx1 Turbofanx1

External static pressure

in.WG 0.000 (208V) 0.000 (208V) 0.000 (208V)Pa 0 0 0in.WG 0.000 (230V) 0.000 (230V) 0.000 (230V)Pa 0 0 0

Motortype 1-phase induction motorMotor output kW 0.015 0.020 0.020 Driving mechanism Direct-driven

Airflowrate (Low-Mid-High)

cfm 280-320-350 320-350-390 320-350-390m3 / min 8.0-9.0-10.0 9.0-10.0-11.0 9.0-10.0-11.0L / s 133-150-167 150-167-183 150-167-183

Soundpressurelevel(Low-Mid-High) (measured in anechoic room) dB <A> 29-32-38 (208-230V) 30-34-39 (208-230V) 31-35-40(208-230V)

Insulation material PolyethylenefoamAirfilter PolypropylenehoneycombfabricProtection device FuseRefrigerantcontroldevice LEVConnectable outdoor unit R410A,R22 CITY MULTI

Diameterofrefrigerantpipe(O.D.)

Liquid (R410A) (R22) in. (mm)

1/4 (6.35) Flare 1/4 (6.35) Flare 1/4 (6.35) Flare1/4 (6.35) Flare 1/4 (6.35) Flare 3/8 (9.52) Flare

Gas (R410A) (R22) in. (mm)

1/2 (12.7) Flare 1/2 (12.7) Flare 1/2 (12.7) Flare1/2 (12.7) Flare 1/2 (12.7) Flare 5/8 (15.88) Flare

Field drain pipe size in. (mm) O.D. 1-1/4(32) O.D. 1-1/4(32) O.D. 1-1/4(32)DrainLiftMechanism in. (mm) 19-11/16 (500) 19-11/16 (500) 19-11/16 (500)

DrawingExternal RG01N654Wiring RG79V389

Refrigerantcycle -

Standard attachment Document Accessory

Installation Manual,Installation Book Drain hose<1-1/4in.(32mm)>

Optional parts Decoration panel SLP-15AAUW SLP-15AAUW SLP-15AAUW

Remark

*PLFY-P-NCMU-EshouldusedtogetherwithSLP-15AAUW.

Installation Detailsonfoundationwork,ductwork,insulationwork,electricalwiring,powersourceswitch,andotheritemsshallbereferredtotheInstallationManual.

VentilationAir:Providingsufficientventilationairisanimportantpartofeverybuildingdesign.ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

1. SPECIFICATIONS

Note: *1Nominalcoolingconditions *2Nominalheatingconditions Unit converter

Indoor: 80degF D.B. / 67degF W.B. (26.7degC D.B. / 19.4degC W.B.) 70degF D.B. (21.1degC D.B.)

kcal/h = kW x 860 BTU/h = kW x 3,412

Outdoor: 95degF D.B. (35degC D.B.) 47degF D.B. / 43degF W.B. (8.3degC D.B. / 6.1degC W.B.)

cfm=m3/minx35.31

lbs = kg / 0.4536

Pipe length: 25ft.(7.6m) 25ft.(7.6m) *Abovespecificationdataissubjecttorounding variation. Leveldifference: 0ft.(0m) 0ft.(0m)

*Duetocontinuingimprovement,abovespecificationmaybesubjecttochangewithoutnotice.

Page 4: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-4 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

Model PLFY-P12NBMU-E PLFY-P15NBMU-E PLFY-P18NBMU-EPowersource 1-phase 208-230 V 60HzCoolingcapacity*1 (Nominal)

BTU / h 12,000 15,000 18,000 kW 3.5 4.4 5.3

Powerinput kW 0.03 0.04 0.05 Current input A 0.22 0.29 0.36

Heatingcapacity*2 (Nominal)

BTU / h 13,500 17,000 20,000 kW 4.0 5.0 5.9

Powerinput kW 0.02 0.03 0.04 Current input A 0.14 0.22 0.29

Externalfinish Galvanized steel sheet

External dimension H x W x Din. 10-3/16 x 33-3/32 x 33-3/32 10-3/16 x 33-3/32 x 33-3/32 10-3/16 x 33-3/32 x 33-3/32mm 258 x 840 x 840 258 x 840 x 840 258 x 840 x 840

Netweight lbs (kg) 49 (22) 49 (22) 51 (23)

Decoration panel

Model PLP-40BAU PLP-40BAU PLP-40BAUExternalfinish Munsell No. (6.4Y 8.9/0.4)Dimension H x W x D

in. 1-3/8 x 37-13/32 x 37-13/32 1-3/8 x 37-13/32 x 37-13/32 1-3/8 x 37-13/32 x 37-13/32mm 35 x 950 x 950 35 x 950 x 950 35 x 950 x 950

Net Weight lbs (kg) 13 (6) 13 (6) 13 (6)Heat exchanger Crossfin

FAN

TypexQuantity Turbofanx1 Turbofanx1 Turbofanx1

External static pressure

in.WG 0.000 (208V) 0.000 (208V) 0.000 (208V)Pa 0 0 0in.WG 0.000 (230V) 0.000 (230V) 0.000 (230V)Pa 0 0 0

Motortype DC motorMotor output kW 0.050 0.050 0.050 Driving mechanism Direct-driven

Airflowrate(Low-Mid2-Mid1-High)

cfm 388 - 424 - 459 - 494 424 - 459 - 494 - 565 494 - 530 - 565 - 636m3 / min 11.0 - 12.0 - 13.0 - 14.0 12.0 - 13.0 - 14.0 - 16.0 14.0 - 15.0 - 16.0 - 18.0L / s 183 - 200 - 217 - 233 200 - 217 - 233 - 267 233 - 250 - 267 - 300

Soundpressurelevel(Low-Mid2-Mid1-High) (measured in anechoic room) dB <A> 27 - 28 - 29 - 31(208-230V) 27 - 28 - 30 - 31(208-230V) 28 - 29 - 30- 32(208-230V)

Insulation material PSAirfilter PPhoneycomb(longlifefilter,anti-bacterialtype)Protection device FuseRefrigerantcontroldevice LEV

Connectable outdoor unit R410A,R22 CITY MULTI

Diameterofrefrigerantpipe(O.D.)

Liquid (R410A) (R22) in. (mm)

1/4 (6.35) Flare 1/4 (6.35) Flare 1/4 (6.35) Flare1/4 (6.35) Flare 1/4 (6.35) Flare 3/8 (9.52) Flare

Gas (R410A) (R22) in. (mm)

1/2 (12.7) Flare 1/2 (12.7) Flare 1/2 (12.7) Flare1/2 (12.7) Flare 1/2 (12.7) Flare 5/8 (15.88) Flare

Field drain pipe size in. (mm) O.D. 1-1/4(32) O.D. 1-1/4(32) O.D. 1-1/4(32)Drainliftmechanism in. (mm) 33-1/2 (851) 33-1/2 (851) 33-1/2 (851)Standard attachment

Document Accessory Installation Manual, Instruction Book

Optional parts

Air outlet shutter plate PAC-SH51SP-E PAC-SH51SP-E PAC-SH51SP-EHighefficiencyfilterelement(MERV10) PAC-SH59KF-E PAC-SH59KF-E PAC-SH59KF-EMulti-functioncasement PAC-SH53TM-E PAC-SH53TM-E PAC-SH53TM-Ei-see sensor corner panel PAC-SA1ME-E PAC-SA1ME-E PAC-SA1ME-EFlangeforfreshairintake PAC-SH65OF-E PAC-SH65OF-E PAC-SH65OF-EWireless signal receiver PAR-SA9FA-E PAR-SA9FA-E PAR-SA9FA-E

Remark

Installation Detailsonfoundationwork,ductwork,insulationwork,electricalwiring,powersourceswitch,andotheritemsshallbereferredtotheInstallationManual.

VentilationAir:Providingsufficientventilationairisanimportantpartofeverybuildingdesign.ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

1. SPECIFICATIONS

Note: *1Nominalcoolingconditions *2Nominalheatingconditions Unit converter

Indoor: 80degF D.B. / 67degF W.B. (26.7degC D.B. / 19.4degC W.B.) 70degF D.B. (21.1degC D.B.)

kcal/h = kW x 860 BTU/h = kW x 3,412

Outdoor: 95degF D.B. (35degC D.B.) 47degF D.B. / 43degF W.B. (8.3degC D.B. / 6.1degC W.B.)

cfm=m3/minx35.31

lbs = kg / 0.4536

Pipe length: 25ft.(7.6m) 25ft.(7.6m) *Abovespecificationdataissubjecttorounding variation. Leveldifference: 0ft.(0m) 0ft.(0m)

*Duetocontinuingimprovement,abovespecificationmaybesubjecttochangewithoutnotice.

Page 5: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-5PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

Model PLFY-P24NBMU-E PLFY-P30NBMU-E PLFY-P36NBMU-EPowersource 1-phase 208-230 V 60HzCoolingcapacity*1 (Nominal)

BTU / h 24,000 30,000 36,000 kW 7.0 8.8 10.5

Powerinput kW 0.06 0.07 0.16 Current input A 0.43 0.51 1.07

Heatingcapacity*2 (Nominal)

BTU / h 27,000 34,000 40,000 kW 7.9 10.0 11.7

Powerinput kW 0.05 0.06 0.15

Current input A 0.36 0.43 1.00

Externalfinish Galvanized steel sheet

External dimension H x W x Din. 10-3/16 x 33-3/32 x 33-3/32 10-3/16 x 33-3/32 x 33-3/32 11-3/4 x 33-3/32 x 33-3/32mm 258 x 840 x 840 258 x 840 x 840 298 x 840 x 840

Netweight lbs (kg) 51 (23) 51 (23) 60 (27)

Decoration panel

Model PLP-40BAU PLP-40BAU PLP-40BAUExternalfinish Munsell No. (6.4Y 8.9/0.4)

Dimension H x W x D

in. 1-3/8 x 37-13/32 x 37-13/32 1-3/8 x 37-13/32 x 37-13/32 1-3/8 x 37-13/32 x 37-13/32

mm 35 x 950 x 950 35 x 950 x 950 35 x 950 x 950Net Weight lbs (kg) 13 (6) 13 (6) 13 (6)

Heat exchanger Crossfin

Fan

TypexQuantity Turbofanx1 Turbofanx1 Turbofanx1

External static pressure

in.WG 0.000 (208V) 0.000 (208V) 0.000 (208V)Pa 0 0 0in.WG 0.000 (230V) 0.000 (230V) 0.000 (230V)Pa 0 0 0

Motortype DC motorMotor output kW 0.050 0.050 0.120 Driving mechanism Direct-driven

Airflowrate (Low-Mid2-Mid1-High)

cfm 530 - 565 - 636 - 706 565 - 636 - 706 - 777 777 - 883 - 989 - 1,059m3 / min 15.0 - 16.0 - 18.0 -20.0 16.0 - 18.0 - 20.0 - 22.0 22.0 - 25.0 - 28.0 - 30.0L / s 250 - 267 - 300 - 333 267 - 300 - 333 - 367 367 - 417 - 467 - 500

Soundpressurelevel(Low-Mid2-Mid1-High) (measured in anechoic room) dB <A> 28 - 30 - 32 - 34(208-230V) 30 - 32 - 35 - 37(208-230V) 35 - 38 - 41 - 43(208-230V)

Insulation material PSAirfilter PPhoneycomb(longlifefilter,anti-bacterialtype)Protection device FuseRefrigerantcontroldevice LEVConnectable outdoor unit R410A,R22 CITY MULTI

Diameterofrefrigerantpipe(O.D.)

Liquid (R410A) (R22) in. (mm)

3/8 (9.52) Flare 3/8 (9.52) Flare 3/8 (9.52) Flare3/8 (9.52) Flare 3/8 (9.52) Flare 3/8 (9.52) Flare

Gas (R410A) (R22) in. (mm)

5/8 (15.88) Flare 5/8 (15.88) Flare 5/8 (15.88) Flare5/8 (15.88) Flare 5/8 (15.88) Flare 3/4 (19.05) Flare

Field drain pipe size in. (mm) O.D. 1-1/4(32) O.D. 1-1/4(32) O.D. 1-1/4(32)Drainliftmechanism in. (mm) 33-1/2 (851) 33-1/2 (851) 33-1/2 (851)Standard attachment

Document Accessory Installation Manual, Instruction Book

Optional parts

Air outlet shutter plate PAC-SH51SP-E PAC-SH51SP-E PAC-SH51SP-EHighefficiencyfilterelement(MERV10) PAC-SH59KF-E PAC-SH59KF-E PAC-SH59KF-EMulti-functioncasement PAC-SH53TM-E PAC-SH53TM-E PAC-SH53TM-Ei-see sensor corner panel PAC-SA1ME-E PAC-SA1ME-E PAC-SA1ME-EFlangeforfreshairintake PAC-SH65OF-E PAC-SH65OF-E PAC-SH65OF-EWireless signal receiver PAR-SA9FA-E PAR-SA9FA-E PAR-SA9FA-E

Remark

Installation Detailsonfoundationwork,ductwork,insulationwork,electricalwiring,powersourceswitch,andotheritemsshallbereferredtotheInstallationManual.

VentilationAir:Providingsufficientventilationairisanimportantpartofeverybuildingdesign.ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes.

1. SPECIFICATIONS

Note: *1Nominalcoolingconditions *2Nominalheatingconditions Unit converter

Indoor: 80degF D.B. / 67degF W.B. (26.7degC D.B. / 19.4degC W.B.) 70degF D.B. (21.1degC D.B.)

kcal/h = kW x 860 BTU/h = kW x 3,412

Outdoor: 95degF D.B. (35degC D.B.) 47degF D.B. / 43degF W.B. (8.3degC D.B. / 6.1degC W.B.)

cfm=m3/minx35.31

lbs = kg / 0.4536

Pipe length: 25ft.(7.6m) 25ft.(7.6m) *Abovespecificationdataissubjecttorounding variation. Leveldifference: 0ft.(0m) 0ft.(0m)

*Duetocontinuingimprovement,abovespecificationmaybesubjecttochangewithoutnotice.

Page 6: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-6 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

PLFY-P08,12,15 NCMU-E

PLFY-P15NCMU-EPLFY-P12NCMU-EPLFY-P08NCMU-E

Brand label

(1/2 (12.7) dia.)

1/2Fflared connection

Refrigerant pipe

flared connection1/4F

Refrigerant pipe(1/4 (6.35) dia.)

1

Detail drawing of ventilation air intake

Ceiling surface

Cut out hole2-7/8( 73.4)

Burring hole3- 1/8( 2.8)

3-15/16( 100)

4-21

/32(

118)

1(25)

120°

120°

+ 0(2

7 )

+3/1

6

01-

1/16

Unit : in.(mm)

19/32~1-15/32(15~37) 19/32~1-15/32(15~37)22-11/16~24-13/32(576~620)

22-7/16(570)

20-7/8(530)

1

2

2

Grille

Ventilation air intake

DrainpipeVP-25 connection(O.D. 1-1/4( 32))

Vane motor

Drain hole

Models

Air intake grille

2-5/

32(5

5)1-

3/8(

35)

1-3/8(35) 2-5/32(55)

Auto vane

Grille

Air intake hole

Air

inta

ke h

ole

Air

outle

t hol

e

Air outlet hole11-27/32(301)

11-2

7/32

(301

)

14-2

7/32

(377

)

14-27/32(377)

25-1

9/32

(650

)

Suspension bolt M10 or W3/89-1/16(230)

7-5/

32(1

82)

1-7/

8(48

)

Wiring entry

Terminal block Ceiling surface

9-1/

4(23

5)8-

3/16

(208

)

7-19

/32(

193)

25/3

2(20

)

3-21

/32(

93)

1-1/

2~2-

9/32

(38~

58)

2-19

/32(

66)

4-3/

4(12

1)

7-15/16(202)

2-7/

32(5

6)

2-1/

14(5

7) 3-7/16

(87)1-

7/32

(31)

Cei

ling

hole

Sus

pens

ion

bolt

pitc

h

19/3

2~1-

15/3

2(15

~37)

19/3

2~1-

15/3

2(15

~37)

22-1

1/16

~24-

13/3

2(57

6~62

0)

16-1

7/32

(420

)

22-7

/16(

570)

13-3

/16(

335)

7-27/32(199)

13-27/32(352)13-3/16(335)

Suspension bolt pitch

Ceiling hole

25-19/32(650)

Ref. : PLFY-NCMU-E_EXD_USDB_P08-15Unit : in.(mm)

2. EXTERNAL DIMENSIONS

Serv

ice

Acc

ess

Req

uire

d

Page 7: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-7PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

PLFY-P12,15,18,24,30,36 NBMU-E Unit : in. (mm)

14-27/3211-3/162-3/8

+5 0

+35

-5

(187.5) (160)

(160)

(7.5

)

(950

)

(500

)

Keep 25/64(10) to 19/32(15)between unit ceiling and ceiling slab.

Grille

Indoor unit

Ceiling

Floor

Min.94-1/2(2400)from floor

Min.19-11/16(500)

Entireperiphery

(36)

(83)

(36)

(83)

(500)

(950)

(597

)

(597)

(w15

8)

(ø175)(350)

(130

)(1

00)

(90)(100)

(90)

(100)

(77)3-1/32

(85)3-11/32

(298)11-3/411-1/16

(281)

(74)(80)(258)(241)2-29/323-5/3210-3/16

PLFY-P36NBMU-E

PLFY-P24NBMU-EPLFY-P30NBMU-E

(35)

(17

)

+3/1

6

0

(190

)

(156

)

(50~

70)

(140

)

(170

)

(377)(284)(60)(2

4)(840)

(160

)

(20~

45)

to 1

-25/

32

(620

)

(605

)

-3/1

6+1

-3/8

(90)

(150

)(1

60)

(7.5

)

(20~

45)

1-25

/32

Corner pocket

In case of wireless remote controllerIn case of standard grille

9-1/2

Drain holeDrain pump clean holeand Drain emergency drainage hole

For MA-Remote controllerterminal block

Emergency operation switch<Cooling>

Emergency operation switch<Heating>

Ceiling

Cut out hole

Burring hole pitch3-ø1/8(3-ø2.8)Burring hole

Detail drawing of ventilation air intake hole

Burring hole14-ø1/8(14-ø2.8)

Cut out hole

Burring hole pitch

Cut out hole

Detail connecting of branch duct(Both aspects)

Refrigerant pipe ø15.88 / ø19.05Flared connection 5/8 / 3/4(compatible)

DCBA

Refrigerant pipe ø12.7 / ø15.88Flared connection 1/2 / 5/8(compatible)

Refrigerant pipe ···ø15.88Flared connection ···5/8

Refrigerant pipe ···ø12.7Flared connection ···1/2

Refrigerant pipe···ø6.35Flared connection···1/4Refrigerant pipeø6.35 / ø9.52Flared connection1/4 / 3/8(compatible)

PLFY-P18NBMU-E

Refrigerant pipe···ø9.52Flared connection···3/8

ModelsPLFY-P12NBMU-EPLFY-P15NBMU-E

Suspension bolt lower edge

Vane motor

Air intakegrille

Air outlet hole

Air

outle

t hol

e

Auto vane(Air outlet)

Air

inta

ke h

ole

Air intake hole

Grille

Ceiling

)(Connected the attachedflexible pipe or socket.

Drain pipeconnected to VP-25

Suspension bolt M10 or W3/8

Branch duct hole

Ventilation air intake hole

Branchduct hole

Cei

ling

hole

Sus

pens

ion

bolt

pitc

h

Suspension bolt pitch

Ceiling hole

(5/1

6)(5

/16)

23-1

3/16

24-1

3/32

DEFROST/STAND BY lamp

Receiver

Operation lamp

6-5/16

6-16/5

1

2

3-15

/16

5-1/

8

13-25/32

3-17/32

3-15/16 3-15/16

3-17/32

70°

w6-

9/16

(167

)

w6-

3/32

(155

)

ø5-29/32(ø150)

6-7/8

19-11/16

19-1

1/16

23-1/2

M

M

M

M

3-17/64

1-27/64

37-3/8

3-17

/64

1-27

/64

37-3

/8

23-1

/2

1-31

/32

to 2

-3/4

w5-

1/2

w6-

11/1

6

1-3/

8

11/1

6

w4-

1/8(

105)

w6-9

/64

w7-1

5/32 A B

6-5/

16

33-1

/16(

840)

5-29

/32

3-17

/32

C D

33-1/16

7-3/8

25/32~1-25/32(20~45) 33-27/32 to 35-13/16(860~910) 25/32 to 1-25/32(20~45)

31-7/8(810)

25/3

2 to

33-2

7/32

to 3

5-13

/16(

860~

910)

25/3

2

15/1

6

6-5/

16

Indoor unit/Outdoor unit connecting terminal block

ø4-29/32(ø125)

ø3-15/16(ø100)

6-7/

32

120°

120°

1 2

Note:1. As for drain pipe, please use VP-25 O.D. 1-1/4(32) PVC TUBE. Drain pump is included. Max. lifting height is 33-1/2 (850mm) from the ceiling.2. As for suspension bolt, please use M10 or W3/8. (Procured at local site)3. Electrical box may be removed for the service purpose. Make sure to slack the electrical wire little bit for control/power wires connection.4. The height of the indoor unit is able to be adjusted with the grille attached.5. For the installation of the optional high efficiency filter or optional multi-functional casement. 1 Add 5-5/16"(135mm) to the dimensions Wmarked on the figure. 2 The optional high efficiency filter becomes optional multi-functional casement and concomitant use.6. When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.) As for necessary installation / service space, please refer to the left figure.Accessory···Drain socket(I.D.1-1/4)

Flare nut 3/8 (For P18)Flare nut 5/8 (For P18)Flare nut 3/4 (For P36)

2. EXTERNAL DIMENSIONS

Page 8: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-8 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

3. CENTER OF GRAVITY

PLFY-P08,12,15NCMU-E

PLFY-P12,15,18,24,30,36NBMU-E

Ref.: PLFY_NCMU_COG_USDB_ALL

150 [5-29/32] 260 [10-1/4] 105 [4-5/32]150 [5-29/32] 260 [10-1/4] 105 [4-5/32]150 [5-29/32] 260 [10-1/4] 105 [4-5/32]

PLFY-P08NCMU-EPLFY-P12NCMU-EPLFY-P15NCMU-E

X Y Z(mm)[in]

Model name

280 [11-1/32] 400 [15-3/4] 105 [4-5/32]280 [11-1/32] 400 [15-3/4] 105 [4-5/32]280 [11-1/32]280 [11-1/32]280 [11-1/32]280 [11-1/32]

400 [15-3/4]400 [15-3/4]400 [15-3/4]400 [15-3/4]

105 [4-5/32]105 [4-5/32]105 [4-5/32]125 [4-15/16]

PLFY-P12NBMU-EPLFY-P15NBMU-EPLFY-P18NBMU-EPLFY-P24NBMU-EPLFY-P30NBMU-EPLFY-P36NBMU-E

X Y Z(mm)[in]

Model name

Refrigerant pipe

Refrigerant pipe side

Refrigerant pipe side

Refrigerant pipe

Page 9: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-9PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

Ref. : PLFY-NCMU-E_EWD_USDB_P08-15PLFY-P08,12,15 NCMU-E

DP

WHT(DRAIN)

WHT

FAN(FAN)

See fig: 1

MODELS

P08

P12

P15

<fig: 1>

ONOFF

1 2 3 4 5 6

ONOFF

1 2 3 4 5 6

ONOFF

1 2 3 4 5 6

SW2

Power supply for MA-Remote controller on lamp is lit

Main power supply(Indoor unit:208-230V) power on lamp is litMain power supply

Power supply forMA-Remote controllerLED2

LED1

Mark MeaningLED on indoor controller board for service

Function

CN32(REM

OTE SWITCH)

WHT

32

1

DC24-30VCONTROLLER

TO NEXT INDOOR UNIT

PULL BOX

FUSE(15A)

BREAKER (15A)

60Hz

HA

1234

WHT

CN41 CN51

WHT(CENTRALLY CONTROL)

5 4 3 2 1

CN52

(REMOTE INDICATION)

GRN

12345

REMOTE SWITCHCN32

X7 FAN MOTOR (Me)X6 FAN MOTOR (Hi)X5 FAN MOTOR (Lo)

SW1 SWITCH MODE SELECTION

CONNECTION No.SW14SW12SW11 ADDRESS SETTING 1ST DIGIT

ADDRESS SETTING 2ND DIGIT

MODEL SELECTIONMODE SELECTIONCAPACITY CODE

SW4SW3SW2

(32°F/15kΩ 77°F/5.4kΩ)

(32°F/15kΩ 77°F/5.4kΩ)

DP DRAIN PUMPDS DRAIN SENSORH2 DEW PREVENTION HEATER

FAN MOTOR (LL)DRAIN PUMP/DEW PREVENTION HEATERX1 AUX. RELAY

SYMBOL NAME

VARISTOR

INDOOR POWER BOARDP.B

ZNR

X4

I.B

CN41CN51CN52FUSE FUSE (6.3A/250V)

REMOTE INDICATIONCENTRALLY CONTROLHA TERMINAL-A

CONNECTORINDOOR CONTROLLER BOARD

[LEGEND]NAMESYMBOL

PIPE TEMPERATURE DETECTION/GASTH23

TRANSMISSIONTERMINALBLOCK

POWER SUPPLYTB5TB15

TB2

(32°F/15kΩ 77°F/5.4kΩ)THERMISTOR ROOM TEMPERATURE DETECTION

TH22

TH21

LEV LINEAR EXPANSION VALVE

MVMF

VANE MOTORFAN MOTOR (WITH THERMAL FUSE)

CAPACITOR (FAN MOTOR)C1

PIPE TEMPERATURE DETECTION/LIQUID

MA-REMOTE CONTROLLER

LED2

LED1

31 1 3CND

(POWER)

YLW21

YLW

1 3 BLU

(D+U+M)CNC

(D+HEATER) RED ORN

FUSE

ZNR

CNP

X1

RED

ORN

GRILLE

BLU

5WHTBLU

REDORNYLW

REDRED

1

10

7

236

45

89

3

5

5

5

5

C1

1 5

BLK

YLW WHTBR

N

7 9

X6 X5 X4 X7

X4 X7X5X6

MF

I.B

CN20

CN31

123

BLU

WHT

ORN

RED

YLW 6

6 5 4 3 2 1

(VANE)CN6V

GRN

RED

ORN

BLU

6 5 4 3 2 1

(LEV)CN60

WHT

WHT

YLWBRN

BLK

2 2 11

(LIQUID)(INTAKE)CN21

RED WHT

2 1

(GAS)CN29

(REM

OCON

)

WHT

13RE

D

P.B

RED

CNDK

(POWER BORD)

123

AC208-230VCNSK(RED)

TB2 L1L2GR

REDBLU

GRN/YLW

~/N 208-230V POWER SUPPLY

TRANSDC13.1VCN2S(WHT)

21

21

(POW

ER

BO

RD)

CN2D

WHT WHT

BLK

M1

12 CONTROLLER

DC8.7-13V

TO MA-REMOTE

CN2M

(M-N

ET) 1

23

1CN

3A

BLU

BLU

M2

TB15S(SHIELD)

M-NET REMOTE

TO OUTDOOR UNITBC CONTROLLERTB5

X1

TH23TH22TH21DSLEV

5

3RDDIGIT

0O

0

0N0FF

SW1

1 2 3 4 5 6 7 8 9 10

SW12 SW11

1STDIGIT

0

2NDDIGIT

SW14

CONNECTIONNo.

1 2 3 4 50FF0N

SW4SW2

654321 109876543210FF0N

SW3

MV

H2

MV

MV

MV

Notes:1.At servicing for outdoor unit,always follow the wiring diagram of outdoor unit.2.In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)3.In case of using M-NET, please connect to TB5. (Transmisson line is non-polar.)4.Symbol[S] of TB5 is the shield wire connection.5.Symbols used in wiring diagram above are, :terminal block, :connecter.6.The setting of the SW2 dip switches differs in the capacity for the detail,refer to the fig: 1.7.Use copper supply wire.

4. ELECTRICAL WIRING DIAGRAMS

Page 10: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-10 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

PLFY-P12,15,18,24,30,36 NBMU-E

CN27CN32CN51CN52

SW2SW3SW4SWE

ZNR01,02

DSAFUSE

X1

LED1LED2

MFMV

DPFS

TB2TB5TB15TH21

TH22

TH23

LEV

SW1SW11SW12SW14

SWASWB

SWC

W.B

RU

BZLED1LED2

SW1SW2

POWER SUPPLYTRANSMISSIONMA-REMOTE CONTROLLERROOM TEMP. DETECTION(0: / 15kΩ, 25:/ 5.4kΩ)PIPE TEMP. DETECTION / LIQUID(0:/ 15kΩ, 25:/ 5.4kΩ)PIPE TEMP. DETECTION / GAS(0:/ 15kΩ, 25:/ 5.4kΩ)

FAN MOTORVANE MOTOR

DRAIN-UP MACHINEDRAIN FLOAT SWITCH

TERMINALBLOCK

THERMISTOR

LINEAR EXPANSION VALVE

I. B

Mark

LED1 Main power supply

Power supply forMA-Remote controller

Main Power supply (Indoor unit:208-230V)power on Lamp is lit.Power supply for MA-Remote controlleron Lamp is lit.LED2

Meaning Function

INDOOR CONTROLLER BOARDCONNECTOR DAMPER

REMOTE SWITCHCENTRALLY CONTROLREMOTE INDICATION

CAPACITY CODEMODE SELECTIONMODEL SELECTIONDRAIN-UP MACHINE (TEST MODE)

SWITCH

VARISTOR

SURGE ABSORBERFUSE (T6.3AL250V)

AUX. RELAY

POWER SUPPLY (I. B)POWER SUPPLY (I. B)

DRAIN WATER LIFTING-UP MACH.

SYMBOL

A. B

OPTION PART

ADDRESS BOARDSWITCH

MODE SELECTIONADDRESS SETTING 1ST DIGITADDRESS SETTING 2ND DIGITCONNECTION NO.

CEILING HEIGHT SELECTORDISCHARGE OUTLET NUMBERSELECTOROPTION SELECTOR

PCB FOR WIRELESS REMOTE CONTROLLER

RECEIVING UNIT

BUZZERLED (OPERATION INDICATION : GREEN)LED (PREPARATION FOR HEATING : ORANGE)

EMERGENCY OPERATION (HEAT / DOWN)EMERGENCY OPERATION (COOL / UP)

SYMBOLNAME SYMBOL NAME NAME

NOTES:1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.2.In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)4.Symbol [S] of TB5 is the shield wire connection.5.Symbols used in wiring diagram above are, : terminal block, : connecter.6.The setting of the SW2 dip switches differs in the capacity. For the detail, refer to fig<w1>.

[LEGEND]

LED on indoor board for service

w2.Use copper supply wires.

w2

ADDRESSCN81(RED)

ADDRESSCN42(RED)

BZ

WH

TY

LWO

RN

BLU

RE

DB

RN

LEV

LED2SW1

CNB54

MT

I-SEE SENSOR CORNER PANEL(OPTION PART)

I-SEESENSOR

TO MA-REMOTECONTROLLERDC8.7-13V

TB151BLU

BLU 2

SW2 LED1

RUW.B

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

VANE CNV(WHT)

5

0

555

MMMMMVMVMVMV

GRILLE

Pair No.

J41J42

1 3

CN32(WHT)

1

1 6

3

LED2

81 41

4

1 8

8

1

0 0

A.B

I.B

4

(RED)ADDRESS

CN43

(RED)ADDRESS

CN82

SWBSWA

SWC

3RD.DIGIT 2ND.DIGIT 1ST.DIGIT

SW14

CONNECTIONNo.

1

2

3211 2 3 4 5 6 7 8 910

234

0SW12 SW11

SW1ON

OFF

91

WIRELESSCN90(WHT)

19

4

LIQUID/PIPECN44(WHT)

TH23TH22

t°t°

1 4

FS

1 2

INTAKECN20(RED)

1 2

FLOAT SWCN4F(WHT)

CN27(RED)

1 2 1 21 3

LED1

CN25(WHT)

CN24(YLW)

CN3G(BLK)

7 14

FANCNMF(WHT)

MF

MS3~

3 1

DP

M1~

M

M

D.U.MCNP(BLU)

3 1

CNAC(WHT)

U

U

ZNR02

ZNR01

DSA

1 3 5

FUSE

CND

DC311~339VRECTIFICATION

X1

2 1M-NETCN2M(BLU)

BLUBLU

M1M2

TB5

(SHIELD)

TO OUTDOOR UNITBC CONTROLLERREMOTE CONTROLLERDC24-30VS

L1L2GR

TB2REDBLU

GRN/YLW TO NEXT INDOOR UNIT

PULL BOX

FUSE(16A)

BREAKER(16A)

POWER SUPPLY~/N 208-230V 60Hz

wBe sure to turn off the power source and then disconnect fan motor connector. (Failure to do so will cause trouble in Fan motor.)TH21

SW3 SW4

SWE

SW2ON

OFFONOFF

ONOFF

1 2 34 5 67 8 910 1 2 34 5 61 2 3 4 5

See fig:w1

1 6

6

1 4

1 41 5 1 5

LEVCN60(WHT)

MA REMOCONCN3A(BLU)

I-SEE SENSORCN4Y(WHT)

CN41(WHT)

CN51(WHT)

CN52(GRN)

I-SEE SENSOR MOTORCN6Y(RED)

ONOFF

1 2 3 4 5 6

ONOFF

1 2 3 4 5 6

ONOFF

1 2 3 4 5 6

ONOFF

1 2 3 4 5 6

ONOFF

1 2 3 4 5 6

ONOFF

1 2 3 4 5 6

P12

MODELS MODELS<w1>

SW2 SW2

P15

P18

P24

P30

P36

4. ELECTRICAL WIRING DIAGRAMS

Page 11: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-11PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

5-1. Sound Pressure Levels

35-38-41-43

30-32-35-37

28-30-32-3428-29-30-32

27-28-30-3127-28-29-31

31-35-4030-34-3929-32-38

Operating sound levels(Low-Middle2-Middle1-High)

PLFY-P12NBMU-E

PLFY-P12NCMU-EPLFY-P08NCMU-E

PLFY-P18NBMU-E

PLFY-P15NBMU-E

PLFY-P24NBMU-E

PLFY-P30NBMU-E

Sound level (A weighted)Model

Unit : dB(A)Cassette ceiling series

UNIT

MICROPHONE

CEILING

Measurement location

(1.5m)4- 7/8ft

PLFY-P36NBMU-E

PLFY-P15NCMU-E

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

63 125 250 500 1k 2k 4k 8k

NC-60

NC-50

Approximate minimumaudible limit oncontinuous noise

NC-40

NC-30

NC-20

Octave band center frequencies (Hz)

HighMiddle 60HzLow 60Hz

60Hz

PLFY-P08NCMU-EExternal Static Pressure: 0PaPower Source: 208-230V 60Hz

Ref.:PLFY-NCMU-E_NCC_USDB_P08

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

63 125 250 500 1k 2k 4k 8k

NC-60

NC-50

Approximate minimumaudible limit oncontinuous noise

NC-40

NC-30

NC-20

Octave band center frequencies (Hz)

HighMiddle 60HzLow 60Hz

60Hz

PLFY-P12NCMU-EExternal Static Pressure: 0PaPower Source: 208-230V 60Hz

Ref.:PLFY-NCMU-E_NCC_USDB_P12

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

63 125 250 500 1k 2k 4k 8k

NC-60

NC-50

Approximate minimumaudible limit oncontinuous noise

NC-40

NC-30

NC-20

Octave band center frequencies (Hz)

HighMiddle 60HzLow 60Hz

60Hz

PLFY-P15NCMU-EExternal Static Pressure: 0PaPower Source: 208-230V 60Hz

Ref.:PLFY-NCMU-E_NCC_USDB_P15

PLFY-P12NBMU-EExternal static pressure : 0PaPower source : 208,230V, 60Hz

Middle2 60HzHigh 60HzLow 60Hz

Middle1 60Hz

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

63 125 250 500 1k 2k 4k 8k

NC-60

NC-50

NC-40

NC-20

NC-30

Oct

ave

band

pre

ssur

e le

vel (

dB)

0dB

=20µP

a

Octave band center frequencies (Hz)

Approximate minimumaudible limit oncontinuous noise

Power source : 208,230V, 60Hz

PLFY-P15NBMU-EExternal static pressure : 0Pa

Middle2 60HzHigh 60HzLow 60Hz

Middle1 60Hz

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

63 125 250 500 1k 2k 4k 8k

NC-60

NC-50

NC-40

NC-20

NC-30

Oct

ave

band

pre

ssur

e le

vel (

dB)

0dB

=20µP

a

Octave band center frequencies (Hz)

Approximate minimumaudible limit oncontinuous noise

Power source : 208,230V, 60Hz

PLFY-P18NBMU-EExternal static pressure : 0Pa

Middle2 60HzHigh 60HzLow 60Hz

Middle1 60Hz

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.070.0

63 125 250 500 1k 2k 4k 8k

NC-60

NC-50

NC-40

NC-20

NC-30

Oct

ave

band

pre

ssur

e le

vel (

dB)

0dB

=20µP

a

Octave band center frequencies (Hz)

Approximate minimumaudible limit oncontinuous noise

PLFY-P30NBMU-EExternal static pressure : 0PaPower source : 208,230V, 60Hz

Middle2 60HzHigh 60HzLow 60Hz

Middle1 60Hz

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

63 125 250 500 1k 2k 4k 8k

NC-60

NC-50

NC-40

NC-20

NC-30

Oct

ave

band

pre

ssur

e le

vel (

dB)

0dB

=20µP

a

Octave band center frequencies (Hz)

Approximate minimumaudible limit oncontinuous noise

Power source : 208,230V, 60Hz

PLFY-P36NBMU-EExternal static pressure : 0Pa

Middle2 60HzHigh 60HzLow 60Hz

Middle1 60Hz

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

63 125 250 500 1k 2k 4k 8k

NC-60

NC-50

NC-40

NC-20

NC-30

Oct

ave

band

pre

ssur

e le

vel (

dB)

0dB

=20µP

a

Octave band center frequencies (Hz)

Approximate minimumaudible limit oncontinuous noise

Power source : 208,230V, 60Hz

PLFY-P24NBMU-EExternal static pressure : 0Pa

Middle2 60HzHigh 60HzLow 60Hz

Middle1 60Hz

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

55.0

60.0

65.0

70.0

63 125 250 500 1k 2k 4k 8k

NC-60

NC-50

NC-40

NC-20

NC-30

Oct

ave

band

pre

ssur

e le

vel (

dB)

0dB

=20µP

a

Octave band center frequencies (Hz)

Approximate minimumaudible limit oncontinuous noise

5-2. NC Curves

5. SOUND PRESSURE LEVELS

Page 12: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-12 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

6-1. Temperature Distributions

PLFY-P-NBMU-E

Note : These figures show typical temperature distributions in the conditions above. In the actual installation, they may differfrom these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

• PLFY-P12,15,18,24,30NBMU-E<Cooling mode> StandardFlow angle : 30° 4-way flowceiling height : 2.7 m(8.8ft)

0

1

2

2.7

4 3 2 1 0

He

igh

t <

m(f

t)>

Floor distance <m(ft)>

Floor distance <m(ft)>

27(81)

27(81)

25(77)

23(73)

• PLFY-P12,15,18,24,30NBMU-E<Heating mode> StandardFlow angle : 60° 4-way flowceiling height : 2.7 m(8.8ft)

1

04 3 2 1 0

2

2.7

He

igh

t <

m(f

t)>

Floor distance <m(ft)>

Floor distance <m(ft)>

32(90)

26(79)

23(73)

29(84)

23(73)

20(68)20

(68)

• PLFY-P36NBMU-E<Cooling mode> StandardFlow angle : 30° 4-way flowceiling height : 3.2 m(10.4ft)

• PLFY-P36NBMU-E<Heating mode> StandardFlow angle : 60° 4-way flowceiling height : 3.2 m(10.4ft)

0

1

2

3.2

5 4 3 2 1 0

He

igh

t <

m(f

t)>

He

igh

t <

m(f

t)>27(81)

27(81)

25(77)

0

1

2

3.2

5 4 3 2 1 0

23(73)

32(90)

23(73)

26(79)

29(84)

20(68)

20(68)

(8.8)

(6.6)

(3.3)

(10.5) (10.5)

(6.6)

(3.3)

(13.1) (9.8) (6.6) (3.3)

(9.8)(13.1)(16.4) (6.6) (3.3)

(6.6)

(3.3)

(9.8)(13.1)(16.4) (6.6) (3.3)

(13.1) (9.8) (6.6) (3.3)

(8.8)

(6.6)

(3.3)

23(73)

<˚C(˚F)> <˚C(˚F)>

<˚C(˚F)> <˚C(˚F)>

PLFY-P08,12,15 NCMU-E

2.7(8.8)

Hei

ght <

m(f

t)>

Floor distance <m(ft)>

2(6.6)

1(3.3)

3(9.8)

2(6.6)

1(3.3)

00

21(70)

23(73)25(77)

25(77)

Floor distance <m(ft)>

00

35(95)

27(81)23(73)

23(73)

31(88)

19(66)

<˚C(˚F)> <˚C(˚F)>

3(9.8)

2(6.6)

1(3.3)

2.7(8.8)

Hei

ght <

m(f

t)> 2

(6.6)

1(3.3)

<Heating mode>Flow angle 70˚

<Cooling mode>Flow angle 30˚

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

Page 13: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-13PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

6-2. Airflow Distributions

2.7

2 1 00

1

2

3 4

Floor distance <m(ft)>

Hei

ght <

m(f

t)>

3.0(9.8)

0.5(1.6)

2.0(6.6)

1.0(3.3)

2.7

2 1 00

1

2

3 4

Floor distance <m(ft)>

Hei

ght <

m(f

t)>

0.5(1.6)

2.0(6.6)

1.0(3.3)

3.0(9.8)

3.2

2 1 00

1

2

3 4 5

Floor distance <m(ft)>

Hei

ght <

m(f

t)>

0.5(1.6)

3.0(9.8)

1.0(3.3)

2.0(6.6)

4.0(13.1)

3.2

2 1 00

1

2

3 4 5

Floor distance <m(ft)>

Hei

ght <

m(f

t)>

0.5(1.6)

3.0(9.8)

1.0(3.3)

2.0(6.6)

4.0(13.1)

(8.8)

(6.6)

(3.3)

(13.1) (9.8) (6.6) (3.3)

(10.5) (10.5)

(6.6)

(3.3)

(13.1)(16.4) (9.8) (6.6) (3.3)

(6.6)

(3.3)

(13.1)(16.4) (9.8) (6.6) (3.3)

(8.8)

(6.6)

(3.3)

(13.1) (9.8) (6.6) (3.3)

<Cooling mode>Flow angle 30˚

<Heating mode>Flow angle 60˚

<Cooling mode>Flow angle 30˚

<Heating mode>Flow angle 60˚

<m/s(ft/s)> <m/s(ft/s)>

<m/s(ft/s)> <m/s(ft/s)>

PLFY-P12,15,18,24,30NBMU-E

PLFY-P36NBMU-E

Note : These figures show typical airflow distributions in the conditions above. In the actual installation, they may differ from these figures under the influence of air temperature conditions, ceiling height, cooling/heating load,obstacles,etc.

<Fan mode>Flow angle 30˚

<Fan mode>Flow angle 70˚

Hei

ght <

m(f

t)>

Floor distance <m(ft)> Floor distance <m(ft)>

00

<m/s(ft/s)> <m/s(ft/s)>

Hei

ght <

m(f

t)>

00

PLFY-P08,12,15 NCMU-E

2.7

2

1

2.7(8.8)

(6.6)

(3.3)

(8.8)

(6.6)

(3.3)

2

1

34 2 1

3.0(3.3)2.0(6.6)

1.0(3.3)

0.5(1.6)

2.0(6.6)

3.0(9.8)

1.0(3.3)

0.5(1.6)

34(13.1) (9.8) (6.6) (3.3) (13.1) (9.8) (6.6) (3.3)

2 1

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

Page 14: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-14 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

6-3. Branch Duct Capacities

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

Page 15: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-15PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

Page 16: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-16 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

Page 17: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-17PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

Page 18: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-18 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

Page 19: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-19PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

6. TEMPERATURE/AIRFLOW DISTRIBUTIONS

Page 20: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-20 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

Static pressure : P [in.W.G.]Air flow : Q [CFM]20

20

40

60

80

100

120

0 20 40 60 80 100 120

Taking air into the unit

NOTE: Ventilation air intake amount should be 20% or less oftotal air amount to prevent condensate dripping.

Refrigerant pipeDrain pipeElectrical Box

Ventilation air intakeVentilation air intake hole diagram (Unit : inch)

3 - 1/8Burring hole

3-15/16Burring hole pitch

2-7/8(Cut out hole)

Ceiling surface

120_

120_

4-21

/32

By mounting the optional multi-function casement (PAC-SH53TM-E) to the indoor unit main body, increased ventilation air intake can be accomplished. (The mounting of the multi-function casement increase the height of the ceiling plenum by 5-5/16 [135mm].)

Knockout hole for ventilation air intake

Direct ventilation air intake into the main body is also possible.

with Multi-function Casement and Filters

7. VENTILATION AIR INTAKE AMOUNT AND STATIC PRESSURE

7-1. PLFY-P08, 12, 15NCMU-E

7-2. PLFY-P12, 15, 18, 24, 30, 36NBMU-E with Multi-function Casement and Filters

Page 21: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-21PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

2 - inlet

1 - inlet

2 - inlet

1 - inlet

2 - inlet

1 - inlet

200(0.80)

150(0.60)

100(0.40)

50(0.20)

0

0 1 2

50 100 150 200 [CFM]

3 4 5 6[CMM]

2 - inlet

1 - inlet

Airflow rate Airflow rate

Sta

tic p

ress

ure

[Pa(

in.W

.G.]

200(0.80)

150(0.60)

100(0.40)

50(0.20)

0

0 1 2

50 100 150 200 [CFM]

3 4 5 6[CMM]

Sta

tic p

ress

ure

[Pa(

in.W

.G.]

200(0.80)

150(0.60)

100(0.40)

50(0.20)

0

0 1 2

50 100 150 200 [CFM]

3 4 5 6[CMM]

Airflow rate

Sta

tic p

ress

ure

[Pa(

in.W

.G.]

200(0.80)

150(0.60)

100(0.40)

50(0.20)

0

0 2

50 100 150 200 250 [CFM]

4 8 [CMM]6

Airflow rate

Sta

tic p

ress

ure

[Pa(

in.W

.G.]

200(0.80)

150(0.60)

100(0.40)

50(0.20)

0 0

0 2

50 100 150 200 250 [CFM]

4 8 [CMM]6

Airflow rate

Sta

tic p

ress

ure

[Pa(

in.W

.G.]

200(0.80)

150(0.60)

100(0.40)

50(0.20)

0 2

50 100 150 200 250 [CFM]

4 8 [CMM]6

Airflow rate

Sta

tic p

ress

ure

[Pa(

in.W

.G.]

connection only

7. VENTILATION AIR INTAKE AMOUNT AND STATIC PRESSURE

Note:Anauxillaryfanisrequiredtobringoutsideair into the unit.

Note:Anauxillaryfanisrequiredtobringoutsideair into the unit.

Note:Topreventsoundissues,theairflowrateshouldbelessthan75CFM/inlet.

Page 22: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-22 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

PLFY-P-NBMU-E

Multi-function casementPAC-SH53TM-E

Air outlet shutter platePAC-SH51SP-E

High efficiency filter element PAC-SH59KF-E (MERV 10) PAC-SH53TM-E is necessary to use with filter PAC-SH59KF-E.

PLFY-P-NBMU-E

8-1. Air Outlet Shutter Plate PAC-SH51SP-E for PLFY-P-NBMU-EUsing the air outlet shutter plate to block the air outlet to modify the air-way from 4 to 3 or 2.With 1 PAC-SH51SP-E, 4 air-ways can be changed to 3;With 2 PAC-SH51SP-E, 4 air-ways can be changed to 2;Changing to 1 way is not allowed. Material: Foamed polyethylene + foamed urethane, color: Black

Item 1. Shutter plate

Quantity 2

Shape

2. Insulator

1

Detailed installation information should be referred to its Installation Manual.

8. OPTIONAL PARTS

8-1. Air Outlet Shutter Plate PAC-SH51SP-E for PLFY-P-NBMU-E

Page 23: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-23PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

8-2. High Efficiency Filter Element PAC-SH59KF-E (MERV 10) for PLFY-P-NBMU-ELife span: 2,500 hr (Dust concentration 0.15mg/m ); Colorimetric method 65% (JIS 11 class)); No re-production.3

*.The actual dust situation affects the filter life span, which should be considered at the applying site.Material: Electrostatic polyolefin fiberHigh efficiency filter element PAC-SH59KF-E must be used together with the Multi-function casement PAC-SH53TM-E. When using PAC-SH59KF-E, switching on SWC of the Indoor unit address board is needed. Details should be referred to its Installation Manual.

Quantity 1

Shape

Detailed installation information is referred in its Installation Manual.

8-3. Multi-function Casement PAC-SH53TM-E for PLFY-P-NBMU-EMulti-function casement is used for High efficiency filter element and/or ventilation air intake from outdoor.It should be used with High efficiency filter element PAC-SH59KF-E (Colorimetric method 65%).ventilation air intake on the Multi-function casement is possible from any 2 or less corners among the 4 ones.But duct and flange on the casement should be prepare locally.

Item 1. Multi-functional casement

5. Insulator A for Decorative panel 6. Insulator B for Decorative panel

2. Screw with washer (black) 3. Screw

Quantity 1 4 8

4

Shape

M5X0.8X25 M5X0.8X12

Decorative panel securing bracket

With insulator

Item

Quantity 1 1

Shape

Detailed installation information should be referred to its Installation Manual.

4.

8-2. High Efficiency Filter Element PAC-SH59KF-E (MERV 10) for PLFY-P-NBMU

8. OPTIONAL PARTS

8-3. Multi-function Casement PAC-SH53TM-E for PLFY-P-NBMU-E

Page 24: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-24 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E

8-4. i-see Sensor Corner Panel PAC-SA1ME-E for PLFY-P-NBMU-Ei-see sensor provides comfortable space as it detects the floor temperature to prevent spotty temperature.It also enables the unit to save energy.AttentionMake sure that there are no gaps between the unit and the grille, and the grille and ceiling.It may cause condensate dripping.

Item 1. i-see sensor corner panel

Quantity 1

Shape

2. Plastic fastener

2

Detailed installation information should be referred to its Installation Manual.

8-5. Wireless Signal Receiver PAR-SF9FA-E for PLFY-P-NBMU-EUsing the wireless signal receiver to use wireles remote controller.The corner panel(the other side of refrigerant piping) is changed for the wireless signal receiver.

Item 1. Wireless signal receiver

Quantity 1

Shape

Detailed installation information should be referred to its Installation Manual.

8-4. i-see Sensor Corner Panel PAC-SA1ME-E for PLFY-P-NBMU-E

8. OPTIONAL PARTS

8-5. Wireless Signal Receiver PAR-SA9FA-E for PLFY-P-NBMU-E

Page 25: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-25PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY-P-NCMU-E PLFY-P-NBMU-E

8-6. External Heater Adapter CN24RELAY-KIT-CM3

8. OPTIONAL PARTS

External heater adaptor CN24RELAY-KIT-CM3 is a set of special wiring parts for controlling the electric heater* with the air conditioner system.*The electric heater should be designed and prepared at the site.

A basic connection method is shown as follows:(For details, refer to its Installation Manual.)

Item External output cable Fan speed setting cablewith resistance

Quantity 2 2

Shape

Refer to the Installation Manual for wiring and installation details.

For relay X use the specifications given below Operation coilRated voltage : 12VDCPower consumption : 0.9W or less

The length of the electrical wiring for the CN24RELAY-KIT-CM3 is 2 meters (6-1/2 ft)To extend this length, use sheathed 2-core cable.

Control cable type : CVV, CVS, CPEV or equivalent.Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 AWG)Don't extend the cable more than 10 meters (32ft)

Recommended circuit

CN24

XX

Remote control Board Relay circuit AdapterIndoor unitcontrol board

Outdoor unitcontrol board

Ele

ctric

Hea

ter

pow

er s

ourc

e

ElectricHeater

Red 1

White 2

Preparations in the field Maximum cable lengthis 10 m (32ft)

Whi

te

FS1

FS2FS1

FS2

RS

RS

CN24

H288H

H188H

26H88H

Wiring diagram

1-phase powersupply208V, 230V/60Hz

Control board

FS1, 2 ----- Thermal fuseH1, H2 ----- Heater26H --------- Overheat protection

thermostat88H --------- Electromagnetic contactor

PUHY,PURY-P-TGMUSW5-2 "ON"

PUHY,PURY-P-T/YHMUSW5-10 "ON"

PUMY seriesSW4-4 "ON"

PUHY,PURY-P-T/YJMUSW5-10 "ON"PUHY,PURY-HP-TJMUSW5-10 "ON"

Page 26: CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P … · 2014. 3. 5. · CEILING-RECESSED CASSETTE (FOUR-WAY AIRFLOW) PLFY-P-NCMU-E PLFY-P-NBMU-E Various airflow pattern to meet

PLFY-26 PLFY-P-NCMU-E/NBMU-E (Feb. 2009)

PLFY

-P-NC

MU-E

PLFY

-P-NB

MU-E