Air Technology Systems, Inc.
CEILAiR
Air Technology Systems, Inc.
Ceiling MountedFull line of DX & CW Systems
Precision Air Conditioning1 to 10 Tons(60 Hz Data)
Engineering Manual
Air Technology Systems, Inc.
Air Technology Systems, Inc.1-1
COMFORT ConferenceRooms GeneralOfficeSpaces ModularOffices
CRITICAL / PRECISION TelecommunicationsRooms TelephoneSwitch-GearRooms Computer/LANRooms Copier/FaxRooms ATMBankCenters ElevatorEquipmentRooms CATSCAN/MRIFacilities HospitalOperating&IsolationRooms CleanRooms Laboratories
PERFECT FOR TENANT RENOVATIONS!
Stulz Air Technology Systems, Inc.
SATS is dedicated to providing innovative solu-tions for critical temperature and humidity control needs. SATS designs and manufactures specialized environmental control equipment for commercial, industrial and custom military applications. SATS serves a diverse marketplace - including telecom-munications, information technology, medical, financial, educational, industrial process and gov-ernment contracts - utilizing world-class island manufacturing processes in a modern, 150,000 ft2 facility. The addition of SATS to the STULZ family of companies solidifies STULZ as a global leader in the precision air conditioning marketplace. SATS combines a global network of sales and service companies with an extensive factory engineering staff and highly flexible manufacturing resources dedicated to providing world-class quality, innova-tion and customer service.
ISO-9001:2001Quality RegisteredStulz-ATS is committed to satisfying customer expectations by meeting and exceeding require-ments. Our Quality Policy ensures that every Employee is committed to Customer Satisfaction, Teamwork and utilizing Continuous Process Im-provement methods in order to deliver an excep-tional product. We will continually measure our performance to improve the effectiveness of our quality management system
Precision A/C ApplicationsStulz-ATS is dedicated to the manufacturing of supplemental and precision air conditioning prod-ucts. With an extensive installation base, SATS has earned a solid reputation as a quality supplier and leader in its field.
CeilAiR ceiling mounted air conditioning units provide temperature and/or humidity control for those hot spot areas in the building which exceed the central system capacity. They are an economical solu-tion to such demands which may, in fact, be temporary until the next offices are carved out of an existing plant area, another laboratory added to a school or new medical equipment installed at a hospital. No floor space is required by the CeilAiR ceiling mounted units. The units are designed with a wide range of options to handle both comfort and precision cooling applica-tions. Typical applications include:
Air Technology Systems, Inc.
SECTION - 5
ELECTRICAL DATA: (FLA / MCA / MFS)
ElectricalDataIndex............................................................ 5-1
DX - Compressorized Systems:
AirCooled,Self-ContainedSystems..................................... 5-2
AirCooled,SplitSystems.................................................. 5-2/4
WaterCooledSystems...................................................... 5-2/4
GlycolCooledSystems..................................................... 5-2/4
DX - Air Handling & Remote Condensing Units:
DX-AirHandlingUnits.................................................... 5-5/6
Free-Cooling & Alternate Water Source:
DXwithFree-Cooling....................................................... 5-7/8
DXwithAlternateWaterSource....................................... 5-7/8
Chilled Water Air Handling Systems:
ChilledWaterSystems......................................................... 5-9
SECTION - 6
DIMENSIONAL / INSTALLATION DRAWINGS:
DimensionalDrawing"QuickFind"Index............................ 6-1
PhysicalData-UnitWeights(lbs)......................................... 6-2
ConnectionSizes-DXRefrigerant....................................... 6-3
AirCooledSystems.......................................................... 6-4/9
Water/GlycolCooledSystems..................................... 6-10/13
ChilledWaterSystems.................................................. 6-14/15
1-2
SECTION - 1
IntroductiontoStulz-ATS..................................................... 1-1
TableofContents................................................................ 1-2
SECTION - 2
CeilAiR SYSTEMS:
OutstandingAdvantages..................................................... 2-1
UserOrientedFeatures&Options........................................ 2-2
AvailableConfigurations.................................................. 2-3/4
MODEL NOMENCLATURE:
NomenclatureChart............................................................ 2-5
ModelNomenclatureSpecifications..................................... 2-6
SECTION - 3
GUIDE SPECIFICATIONS:
StandardFeaturesIndex...................................................... 3-1
StandardGuideSpecifications.......................................... 3-2/4
OptionalFeaturesIndex....................................................... 3-5
OptionalFeaturesGuideSpecifications........................... 3-6/14
SECTION - 4
PERFORMANCE / CAPACITY SPECIFICATIONS:
PerformanceDataIndex...................................................... 4-1
DX-AirCooledSystems................................................... 4-2/6
DX-WaterCooledSystems.............................................. 4-7/8
DX-GlycolCooledSystems............................................ 4-9/10
ChilledWaterSystems.................................................. 4-11/16
Free-Cooling&AlternateWaterSourceSystems........... 4-17/28
Table of Contents
Table of Contents
Air Technology Systems, Inc.
Air Technology Systems, Inc.
CeilAiR Systems
2-1
CeilAiRceilingA/C'saredesignedastheultimatespacesaver.Theyeasilymountinastandard2'x4'gridofadroppedceilingple-numandareavailablewithhighstaticblow-ers(upto2.0"e.s.p.available)forconnectiontoceilingplenumducts.CeilAiRunitsarees-peciallyusefulwherethereisnofloororwallspaceavailableforcoolingunitsorwhereaestheticsdemandout-of-sightinstallation.
{
CeilAiR Systems Offer Outstanding Advantages
FlexibilityAwidevarietyoftypesareavailabletomeetyouruniquerequirements.
DX-AirCooled DX-WaterCooled DX-GlycolCooled(w/RemoteDrycoolers& PumpPackages DX-AirHandlingUnits ChilledWaterAirHandlingUnits
Versatility SpotCooling&Ductedsystems Self-Contained&Splitsystems
Space Saving DesignCompact,in-the-ceilingdesignsavesvaluablefloorspace.
Wide Size Range 1to10tonscapacityinelevenincrementalsizesmeetsanysupplementalcoolingrequirement.
Non-Proprietary PartsAllCeilAiRsystemsincorporatenon-proprietarycompo-nentswherepossible.MostmajorHVAC,refrigerationandelectricaldistributorsstockanexactmodelcrossreferenceoranalternatetomostfactoryprovidedcomponents.
Microprocessor ControlsPrecisiontemperatureand/orhumiditycontrolwithunri-valed,user-friendlycontrols,offerawiderangeoffunc-tionsandalarms.
A-Tech-1.1/.2 C-Tech-10 A-Tech-20
Complete Temperature & Humidity Control SteamCanisterHumidification(Optional) DehumidificationMode(Optional)with -ElectricReheat/Heat -HotGasReheat(Energy$aver) -HotWater&SteamReheat/Heat
Capacity Modulation Options Single&DualCompressorSystems HotGasBypassSystems MultistageReheat/Heat
Code Conformance
Listing E112043
R
NRTL LISTED Complies With
CSA C22.2 No. 236Heating & Cooling Equipment
UL 1995C
- NYCMEAApproved(MEA-163-88-E)- ChicagoCodeApproved- MET-CrecognizedbyStandardsCouncilofCanada
Air Technology Systems, Inc.
User Oriented Features & Options
2-2
Scroll CompressorsCeilAiRDXairconditionersincorpo-rateScrollCompressorTechnology(unlessspecifiedotherwise).ScrollCompressorsprovidehigheref-ficiency,higherreliabilityandlowersoundpowerthanothercompressortechnologies.
Year Round OperationOptionofferingsavailablewithCeil-AiRairconditionersallowforyear-round,24/7continuouson-linesystemoperationinanyenvironmentintheworld:
Low Ambient Control (DX - Air Cooled) 0FFanCycling/FanSpeed -20FVariableFanSpeed -30FFloodedHeadPressure
Quiet OperationLowsoundpowerScrollcompressorscoupledwithlowRPMblowers,acousticallylinedcabinetsandlowvelocitygrillesprovidetheoptimuminquietoperation.
Fast Delivery Stock unitscompleteandreadyforshipment "Rapid-Fire",5dayShipProgram
Warranty - 2YearPartsStandard - Optional5YearCompressor
Spot Cooler
Ducted
Other Available Options - CondensatePumps - ElectricalServiceSwitches - Firestats - SmokeDetectors - WaterLeakDetectors - SpecialHighEfficiencyFiltration (2"&4"Filtersup-to60%DustSpot) - HighPressureDX-Water/GlycolCooled CondenserRegulatingValves - Free-Cooling&AlternateWaterSourceUnits - Many more options available (see page 3-5)!
Variety of Air Patterns
CeilAiR Ceiling AC Systems(ModelOHS-()-ASShown)
Selected Standard Features: Acoustical / Thermal Insulation Aluminum Fin / Copper Tube Coils Thermal Expansion Valve Refrigerant Sight Glass Filter / Drier Strainer Liquid Refrigerant Reclaim Valves Insulated SS or Polymer Drain Pans Condensate Overflow Safety Switch High / Low Pressure Switches
Light weight ALL ALUMINUM cabinet and chassis prevents rust & corrosion
Straight-Thru
EVAPORATORAIR OUT
EVAPORATORAIR IN
EVAPORATORAIR OUT
EVAPORATORAIR IN
90 / Right-Angle
EVAPORATORAIR IN
EVAPORATORAIR OUT
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Space Saving Configuration Choices
2-3
OHS-012/040-AS(Self-Contained,DuctedEvaporator)
OHS-012/040-AS(Self-Contained,"Ductless"SpotCooler)
SELF-CONTAINED AIR COOLED - withINTEGRALAirCooledCondenserAIR COOLED SYSTEMS
{{
OHS-012/040-AR(SplitEvaporator,"Ductless"SpotCooler)
{
{{
{ {
{
SATSRemoteOutdoorPropellerCondenser
SATSRemoteIndoorCentrifugalCondenser
SPLIT AIR COOLED - withREMOTEOUTDOORorINDOORAirCooledCondenser (compressorlocatedwithEvaporatorSection) SATSRemoteOutdoor
PropellerCondenser
SATSRemoteIndoorCentrifugalCondenser
SATSRemoteOutdoorPropellerCondenser
SATSRemoteIndoorCentrifugalCondenser
OHS-012/032-AR(SplitEvaporator,DuctedEvaporator)
SATSRemoteOutdoorPropellerCondenser
OHS-012/040-HAR & OHS-048/060-AR(SingleCompressor-SplitEvaporator)
(DuctedOnly)
SATSRemoteIndoorCentrifugalCondenser
OHS-040/120-(D)AR(DualCompressors-SplitEvaporator)
(DuctedOnly)
OHS-012/040-AHU(Split,DX-AirHandlingUnit)
("Ductless"SpotCooler)
SATSOutdoorPropellerRemoteCondensingUnit
SATSIndoorCentrifugalRemoteCondensingUnit
SPLIT AIR COOLED - AIRHANDLINGUNITw/INDOORorOUTDOORREMOTECONDENSINGUNIT (compressorlocatedwithCondensingSection)
OHS-012/040-AHU & HAHU
(Split,DX-AirHandlingUnit)(DuctedEvaporator)
SATSIndoorCentrifugalRemoteCondensingUnit
SATSOutdoorPropellerRemoteCondensingUnit
SATSOutdoorPropellerRemoteCondensingUnit
OHS-048/120-DAHU(DualCircuit,Split,DX-AirHandlingUnit)
(DuctedOnly)
OHS-048/060-AHU(Split,DX-AirHandlingUnit)
(DuctedOnly)
SATSIndoorCentrifugalRemoteCondensingUnit
SATSIndoorCentrifugalRemoteCondensingUnit
SATSOutdoorPropellerRemoteCondensingUnit
Please refer to the SATS Heat Rejection
Engineering Manual for specification and per-
formance data on SATS Remote Condensers &
Condensing Units
Air Technology Systems, Inc.
More Space Saving Configuration Choices
2-4
WATER COOLED SYSTEMSSELF-CONTAINED WATER COOLED SYSTEMS
OHS-012/040-W(Self-Contained,"Ductless"SpotCooler)
OHS-012/032-W(Self-Contained,DuctedEvaporator)
GLYCOL COOLED SYSTEMSSELF-CONTAINED GLYCOL COOLED SYSTEMS
CHILLED WATER SYSTEMS
OHS-048/120-DW(DualCompressors,Self-Contained,DuctedOnly)
OHS-012/040-HW & OHS-048/060-W(SingleCompressor,Self-Contained,DuctedOnly)
OHS-012/040-G with SATS DRYCOOLER & PUMP PACKAGE
(Self-Contained,"Ductless"SpotCoolerwithOutdoorPropellerDrycooler&PumpPackage)
OHS-012/040-HG&
OHS-048/060-G with SATS DRYCOOLER & PUMP PACKAGE(SingleCompressor,Self-Contained,DuctedOnlywith
OutdoorPropellerDrycooler&PumpPackage)
OHS-048/120-DG with SATS DRYCOOLER & PUMP PACKAGE(DualCompressors,Self-Contained,DuctedOnlywith
OutdoorPropellerDrycooler&PumpPackage)
OHS-012/040-G with SATS DRYCOOLER & PUMP PACKAGE
(Self-Contained,DuctedEvaporatorwithOutdoorPropellerDrycooler&PumpPackage)
Remote Water Source(supplied by others)
OHS-012/040-C(Self-ContainedAirHandler)
("Ductless"SpotCoolerEvaporator)
OHS-012/040-C(Self-ContainedAirHandler)
(DuctedEvaporator)
Remote Liquid Chiller(supplied by others)
OHS-048/120-C(Self-ContainedAirHandler)
(DuctedOnly)
Remote Water Source(supplied by others)
Remote Water Source(supplied by others)
Remote Water Source(supplied by others)
Remote Liquid Chiller(supplied by others)
Remote Liquid Chiller(supplied by others)
Please refer to the SATS Glycol Systems Engi-
neering Manual for specification and performance data on
SATS Glycol Pump Pack-ages and Drycoolers
Air Technology Systems, Inc.
Air Technology Systems, Inc.
No
men
clature - C
eilAiR
Systems
Model Nomenclature-"OHS" Systems
2-5
OHS = OverHead SystemCOS =CyberONESystemMCS =ModularCyberSystemVFS=VerticalFloorSystemFCS=FloorConsoleSystemSCS=STULZCondensingSection*GPS=GlycolPumpSystem*
Nominal Capacity in 1,000's of BTU/H
AHU = AirHandlingUnitAR = Remote(Split)AirCooledAS = Self-ContainedAirCooledC = ChilledWaterSystemCAA = IndoorCentrifugalCondenser*D() = Dual(Two)CircuitSystemG = Glycol CooledH() = HorizontalDischarge,"H-Series" Configuration(e.g.:HAHU,HAR,HW,HG,&HC)()AA = OutdoorPropFanCondenserfor0F*()SA = OutdoorPropFanCondenserfor-20F*()AA = OutdoorPropFanCondenserfor-30F*EC = OutdoorPropFanCondenserfor-20F* w/ECFansRCU-I = IndoorCentrifugalRemoteCondensing Unit*RCU-O = OutdoorRemoteCondensingUnit*W = WaterCooled
AWS = "AlternateWaterSource"FC = "Free-Cooling"LP = "LowProfileConfiguration"OA = "OutsideAir"*SF = "Same-Face"AirPatternSP = "SpecialConfiguration"
OHS-040-G-FC
CeilAiR - Ceiling Mounted A/C's
* SATS Condensers & Condensing Units can be found in our "Heat Rejection" engineering manual.
* SATS OHS Oustide Air Units can be found in our "CeilAiR Outide Air" engineering manual.
* SATS Pump Packages and Drycoolers can be found in our "Glycol Systems" engineering manual.
Air Technology Systems, Inc.
No
men
clature - C
eilAiR
Systems
Model Nomenclature Specifications
2-6
"CeilAiR"Model NomenclatureGuide Specifications
AIR COOLED SELF-CONTAINED
Integral Self-Contained(ModelsOHS-012/040-AS)
Thesystemshallbeaself-con-tained,ceilingmountedsupple-mentalairconditionerwithfactorymountedintegralaircooledcondenserwithcentrifugalblower.
Thecondensershallbesizedtoprovidethetotalheatofrejectionofthesystemata95FDBambi-enttemperature.
Thesystemshallrequireonlysinglepointsupplypowercon-nectionandthesystemshallshipfromtheSATSfactorywithafulloperatingrefrigerantcharge.
DX - EVAPORATOR SECTIONS
Air Cooled Remote Evaporator(ModelsOHS-()-()AR)
Thesystemshallbearemote(split)aircooled,ceilingmountedsupplementalairconditionerevaporator.Theevaporatorsec-tionshallhouse,asaminimum,theevaporatorcoil,expansionvalve,compressor,evaporatorblower/motorandassociatedelectricalandrefrigerationcompo-nents.
TheOHS-()-()ARevaporatorsectionshallbelocatedatsomedistancefromitscorrespond-ingCeilAiRmodelHES-()-()CAAindoororWCS-()outdooraircooledcondenser.
TheevaporatorsystemshallrequireonlysinglepointmainpowersupplyconnectionandtheystemshallshipfromtheSATSfactorywithadrynitrogenhold-ingchargereadyforfieldrefriger-ant(R-22)charging.
(Note: SATS Condensers & Condensing Units can be found in our "Heat Rejec-tion" engineering manual.)
DX - WATER COOLED SYSTEMS
Integral Self-Contained(ModelsOHS-()-W/DW)
Thesystemshallbeaself-con-tained,ceilingmountedsupple-mentalairconditionertoincludeintegralwatercooled,coaxialcondenserwithfactoryinstalledheadpressurewaterregulat-ingcontrolvalve(s).Condenser(source)watershallbeprovidedbyacoolingtowerorsomeotherremotewatersource.
Thesystemshallrequireonlysinglepointsupplypowercon-nectionandshallshipfromtheSATSfactorywithafulloperatingrefrigerantcharge.
Water Regulating Valves:
Headpressureshallbeauto-maticallycontrolledbyafactoryinstalled2-waywaterregulatingvalveratedfor150psigw.w.p.
(Note: 3-way and high pressure 300 to 400 psig rated valves are available as op-tions, page 3-9.)
DX - GLYCOL COOLED SYSTEMS
Integral Self-Contained(ModelsOHS-()-G/DG)
Thesystemshallbeaself-con-tained,ceilingmountedsupple-
mentalairconditionertoincludeintegralglycolcooled,coaxialcon-denserwithfactoryinstalledheadpressureglycolregulatingcontrolvalve(s).Condenser(source)gly-colsolutionshallbeprovidedviaaCeilAiRmodelGPS-()-()/HES-()-LGAremoteglycolpumppack-ageanddrycoolersystem.
Thesystemshallrequireonlysinglepointsupplypowercon-nectionandshallshipfromtheSATSfactorywithafulloperatingrefrigerantcharge.
Glycol Regulating Valves:
Headpressureshallbeauto-maticallycontrolledbyafactoryinstalled2-wayglycolregulatingvalveratedfor150psigw.w.p.
(Note: 3-way and high pressure 300 to 450 psig rated valves are available as op-tions, page 3-9.)
CHILLED WATER AIR HANDLERS
CHILLED WATER SYSTEM(ModelsOHS-()-C)
Thesystemshallbeaceilingmountedchilledwatersupple-mentalairconditionertoin-cludechilledwatercoolingcoil,evaporatorblowerandmotorandchilledwatercontrolvalve.Chilledwatershallbeprovidedbyaremoteliquidchillersystem.
Chilled Water Control Valve:
Coolingcapacityshallbecon-trolledwithaslowlyopeningandslowlyclosing2-waymotorizedcontrolvalveratedfor300psigw.w.p.
(Note: 3-way 300 psig motorized valves and 2 or 3-way modulating valves are available as options .)
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Gu
ide Sp
ec's - Stand
ard Featu
res "Qu
ick-Referen
ce" Table
Selected Standard Features - "OHS" Series
3-1
"OHS" Model 012/040-( ) 012/040-H( ) 048/060-( ) 048/120-D( )
SELECTED STANDARD FEATURES:
TEMPERATURE CONTROL CoolingOnly Std Std Std Std Heating/ReheatingControl Opt Opt Opt Opt
HUMIDITY CONTROL ElectrodeCanisterSteamHumidifier Opt Opt Opt Opt DehumidificationModewithReheat Opt Opt Opt Opt
CONTROLS A-Tech-1.1singlestagecontrols Std Std Std N/A A-Tech-1.2twostagecontrols Opt Opt Opt Std C-Tech-10,A-Tech-20,C6000T/HMicroprocessorControls Opt Opt Opt Opt
CABINET AllAluminumConstruction Std Std Std Std InsulatedSSorPolymerCondensateDrainPan Std Std Std Std 1/2",2lbDensityThermal&SoundInsulation Std Std Std Std RubberHangingVibrationIsolators Std Std Std Std
FILTERS / GRILLES SpotCoolerswithbottomsupply/returnfiltergrille Std N/A N/A N/A DuctedUnitswithflangedductedconnections Opt Std Std Std
DX-REFRIGERATION CIRCUIT R22Refrigerant Std Std Std Std R407CRefrigerant Opt Opt Opt Opt ScrollTypeCompressor(s),(unlessotherwisenoted) Std Std Std Std HighEfficiency,AluminumFin/CopperTubeCoils Std Std Std Std ThermalExpansionValve Std Std Std Std RefrigerantSightGlass&Filter/DrierStrainer Std Std Std Std RefrigerantServiceValves Std Std Std Std
BLOWERS / MOTORS Direct-DriveEvaporatorMotors Std N/A N/A N/A Belt-DriveEvaporatorMotors N/A Std Std Std
ELECTRICAL PowerSupply -------------------------SeeElectricalTablesSection5------------------------- Multi-VoltageControlTransformer(24VClassII) Std Std Std Std IndividualMotorStarter(s)/Contactor(s) Std Std Std Std
SAFETY FEATURES CondensatePanOverflowSafetySwitch(es) Std Std Std Std High/LowRefrigerantPressureSwitches(DXunits) Std Std Std Std MotorOvercurrentandOverloadProtectionPerUL1995 Std Std Std Std
SPECIFIC MODEL STANDARD FEATURES:AIR COOLED LowAmbientHeadPressureControl -------------------Threetypesavailable0F,-20For-30F------------------- Integral(modelOHS-()-AS)orRemoteAirCooledCondenser Std Std Std Std
WATER / GLYCOL COOLED 2-way,150psigWater/GlycolRegulatingValves Std Std Std Std HighPressure&3-wayValves Opt Opt Opt Opt Coaxial,Tube-in-TubeHeatExchanger Std Std Std Std
ALL SPLIT DX SYSTEMS LiquidLineSolenoidValvetoPreventLiquidSlugging Std Std Std Std
DUAL CIRCUIT DX SYSTEMS Two(2)IndependentRefrigerantCircuits N/A N/A N/A Std Two(2)EqualHorsepowerScrollCompressors(1percircuit) N/A N/A N/A Std A-Tech-1.2twostagecontrols N/A N/A N/A Std
CHILLED WATER SYSTEMS 2-way,300psigMotorizedValve Std Std Std Std Modulating,HighPressure&3-wayValves Opt Opt Opt OptCODE CONFORMANCE NRTLConformanceCompliancetoUL1995Standard Std Std Std Std NYCMEA-163-88-E/ChicagoCodeApproval Std Std Std Std
Air Technology Systems, Inc.
Gu
ide Sp
ec's - Stand
ard Eq
uip
men
t
Guide Specifications - Standard Equipment
3-2
QUALITY ASSURANCE(ISO-9001:2001 Registered)SATSoperatesinanISO-9001:2001registeredqualitycontrolenviron-ment.EachSATSemployeeiscommittedtosatisfyinghisorhercustomerexpectationswiththehighestlevelofconsistent,mea-surableandcontinuousqualityimprovement.
GENERAL GUIDE SPECIFICATION
General Description
Thesystemshallbeaceilingmountedsupplementalairconditionerde-signedandbuilttothehighestofindustrystandards.Thesystemshallbecompleteandfactoryrun-testedbeforeshipment.ThesystemshallbelistedandlabeledincompliancewithUL1995(#SATS-1995)byanap-provedNationallyRecognizedTestingLaboratory(NRTL).ThesystemshallbeMEANYC(MEA-163-88-E)andChicagoCodeapproved.
ThesystemshallbemanufacturedbyISO-9001QualityRegisteredStulzAirTechnologySystems,Inc.inFrederick,Maryland,USA.
Component AccessTheairconditionershallbefullyaccessiblein-placethrougheasilyremovablesideaccesspanels.
Cabinet ConstructionThecabinetandaccesspanelsshallbefabricatedfromaluminumforcor-rosionprotectionandtominimizethesystemsweight.Thepanelsshallbelinedwith2lb/ft2highdensitysoundandthermalinsulationandsealedwithself-extinguishinggasketingcon-formingtoNFPA90Aand90B.
Electrical System
Thesystemshallincorporateovercur-rentandoverloadprotectioninac-cordancewithUL1995requirements.Eachblowermotor,compressor,electricheaterstageandhumidifier(ifapplicable)shallbeprovidedwithafactorymountedandwiredstarter/contactor.
Thecontrolcircuitshallbea24VACClass2lowvoltagecircuitincludingacircuitbreakerforprotection.Lowvoltage,highvoltageandgroundingwiresshallbecolorcodedandshallbeindividuallynumberedateachendforeaseofservicetracing.AllwiringshallbeinaccordancewiththeNationalElectricCode(NEC).
Overflow Safety Float SwitchAcondensatepanwaterlevelswitchshallbeincorporatedtoshutthesys-temdownifacondensateoverflowconditionissensed.
Remote Stop / StartIncludedinthesystem'selectricalcontrolcircuitshallbea2-pintermi-nalconnectionforremotestop/startoftheCeilAiRairconditionerbyaremotesource.
CoilsEvaporatorsystemsshallbecon-figuredforadraw-thruairpatterntoprovideuniformairdistributionovertheevaporatorcoilface.Thecoilsshallbeseamlessdrawncoppertubes,mechanicallybondedtotem-
peredaluminumfinswitharaised-lancedfindesignformaximumheattransfer.Coilendplatesshallbehotdippedgalvanized.
Theevaporatorcoilshallbemountedinaninsulatedstainlesssteelconden-satepan.
DX- Refrigeration System
Allrefrigerationpipingshallberefrig-erantgradetubing.Eachrefrigerantcircuitshallinclude,asaminimum,refrigerantdrier/strainer,sightglasswithmoisturedetector,thermalexpansionvalvewithrapidbleedportfeatureandexternalequalizer,evapo-ratorcoil,compressor,highpressureswitchwithmanualresetandalowpressureswitchwithautomaticreset.
Split/Remotesystemsshallhavealiquidlinesolenoidforrefriger-antisolationtopreventliquidslug-ging.Allhighpressurejointsshallbebrazed,andtheentiresystemshallbepressuretestedatthefactorywithdrynitrogen,evacuatedtoatleast50micronsandfullychargedwithrefrigerant.
Note: All split / remote DX systems ship with a dry nitrogen holding charge. All self-contained DX systems ship with a full refrigerant (R-22) operating charge.
Scroll Compressors
Eachcompressorshallbeahighef-ficiency,highreliabilityandlowsoundScrollCompressor,unlessspecificallynotedotherwise.
Thermal Expansion Valves
Sight Glasses
Filter Drier/Strainers
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Gu
ide Sp
ec's - Stand
ard Eq
uip
men
t
Guide Specifications - Standard Equipment
3-3
Thecompressorshallbecompletewithchargingandserviceschraederports,internalvibrationisolation,internalthermaloverloads,internalpressurereliefvalve,internaldis-chargegasvibrationeliminatorandexternalvibrationmountingisolation.
Chilled Water Systems(Models OHS-()-C)
Cooling Coil:
Thechilledwatercoilshallbecon-structedofseamlessdrawncoppertubes,mechanicallybondedtotem-peredaluminumfinsformaximumheattransfer.Coilendplatesshallbehotdippedgalvanized.
Thecoolingcoilshallbemountedinaninsulatedstainlesssteelconden-satedrainpan.
Control Valve:
Coolingcapacityshallbecontrolledbyafactoryinstalledslowlyopeningandslowlyclosing2-waymotorizedcontrolvalveratedforamaximum300psigw.w.p.
(Note: Please refer to page 3-10 for ad-ditional chilled water valve options.)
Blowers / MotorsDirect Drive Systems
Theblower(s)shallbedirectdrivenwithdoublewidth,doubleinlethous-ingandforwardcurvedblades.Theblower(s)shallbedynamicallyandstaticallybalancedtominimizevibra-tionandoperateintheClassIrange.Theblower(s)shallbecorrosionprotectedwithapaintedhousingandimpellerwheel.
Thethreespeed(208V)evaporator
motorshallbefactorywiredforthecorrectspeedtoproducethespeci-fiedairquantity.Themotor(s)shallhaveinternaloverloadprotection.
(277V & 460V direct-drive motors shall be 2-speed.)
Belt Driven Systems
Theblower(s)shallbebeltdrivenwithdoublewidth,doubleinlethous-ingandforwardcurvedbladesandpermanentlylubricatedballbearingssizedforanaverage100,000hoursofservicelife.TheblowersshallbedynamicallyandstaticallybalancedtominimizevibrationandoperateintheClassIrange.
Theblower(s)shallhaveanadjust-ablebaseforbelttensioningandalockingsystemtopreventthemo-torsfrommoving.Themotorsdrivesheavesshallhaveanadjustablepitchtochangethespeedoftheblowers.Themotor(s)shallbe1725RPMandshallhaveoverloadprotectionandaminimumNEMAservicefactorof1.15.
Temp & Humid Control
ThestandardCeilAiRsystemiscon-figuredasa"coolingonly"system.Heating,reheatingand/orhumiditycontrolcanbeoptionallyaddedtoprovidetotalspacetemperatureandhumiditycontrol.(Please see pages 3-5 thru 3-7 for more details.)
A-Tech-1.1StandardsinglestageDXandnon-proportionalCWHeat/Coolprogrammabledigitalthermo-stat.
A-Tech-1.2StandarddualstageDXHeat/Coolprogram-mabledigitalthermostat.
C-Tech-10OptionalsingleordualstageDXornon-propor-tionalCWTemperatureandHumidityMicro-processorControllerwithalarms.
A-Tech-20 & C6000Optionalallpur-poseAdvancedTemperatureandHumidityMicroprocessorControllerswithalarmsandop-tionalremoteBMScom-municationsconnections.
(NOTE: Please refer to pages 3-6 & 3-7 for additional specification details on all CeilAiR ceiling AC control options.)
Air Technology Systems, Inc.
Gu
ide Sp
ec's - Stand
ard Eq
uip
men
t
Guide Specifications - Standard Equipment
3-4
Evaporator Air Patterns & Filtration"Ductless" Spot Cooler (Models OHS-012 thru 040-( ) only.)
Theairconditionershallbedesignedforinstallationinastandard2'x4'ceilinggridforductlesssupplyandreturnevaporatorairthroughafac-toryprovidedbottomsupply&returnfiltergrille.
Theairconditioningunitshallhaveadropout,1"deep,class2(perU.L.Standard900)filtereasilyaccessedthroughthehingedreturngrille.Thefiltershallhavearatingofatleast80%averagearrestanceasmeasuredbyASHRAEStandard52-76testmethod.
Ducted Evaporator(Available on all model sizes)
Theairconditionershallbeprovidedwithevaporatorsupplyandreturnairductconnections.
EVAPORATORAIR OUT
EVAPORATORAIR IN
EVAPORATORAIR OUT
EVAPORATORAIR IN
Theunitshallhaveslideout,1"deepClass2(perU.L.Standard900)filter(s)easilyaccessedthroughasideaccesspanel.Thefiltershallhavearatingofatleast80%averagearrestanceasmeasuredbyASHRAEStandard52-76testmethod.
(Note: Please refer to Section 6 for standard CeilAiR cabinet configurations. Consult your local SATS sales representa-tive for special applications.)
DX - Heat Rejection
AIR COOLED
PleaserefertotheSATSHeatRejec-tionEngineeringManualforspecifica-tiondetailsofaircooledcondensersandcondensingunits.
WATER / GLYCOL COOLED
Water/Glycol CooledCondensers
Coaxial Tube-In-Tube:(Models OHS-012/120-()W/G)
Eachevaporatorrefrigerantcircuitshallbeprovidedwithafactoryinstalledsinglepass,counterflowconfigured,tube-in-tubecoaxialcondenser;designedandtestedfora450psig.w.w.p.
2-Way, 150 psig Regulating Valve(Standard on all OHS-( )-()W/G)
Eachrefrigerantcircuit'sheadpres-sureshallbecontrolledbyafactoryinstalled2-waywater/glycolregulat-ingvalveratedfor150psig.w.w.p.
(Note: 3-way and high pressure water/glycol regulating valves are optionally available, page 3-9.)
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Op
tion
al Features - In
dex
Optional Features - Guide Specifications
3-5
Optional Features IndexOPTION .............................................. page
Free Cooling - Valve Combinations 150psigRatedSystem:(standard)...................... 3-11 - 3-way,150psig,DXCondenserValve(s) - 3-way,300/400psig,FCCoilValve 300psigRatedSystem:(optional)....................... 3-11 - 3-way,350psig,DXCondenserValve(s) - 3-way,300/400psig,FCCoilValve 400psigRatedSystem:(optional)....................... 3-11 - 3-way,450psig,DXCondenserValves - 3-way,400psig,FCCoilValve
Capacity Modulation Options
Snap-Acting,HotGasBypass................................. 3-11Full-Floating,HotGasBypass................................. 3-12DualCompressor/2-StageSystems....................... 3-12
ModulatingChilledWaterControlValves............... 3-12
ACCESSORIES
3-PhasePowerSupply............................................ 3-12
277/1/60PowerSupply.......................................... 3-12
CondensatePump............................................ 3-12/13
SmokeDetector..................................................... 3-13
Firestat .......................................................... 3-13
RemoteWater/LeakDetector............................... 3-13
AcousticalCompressorSoundJackets.................... 3-13
LowEnteringCondenserWater............................. 3-14
MainPower-Non-FusedServiceSwitch................. 3-14
RefrigerantLineswith QuickDisconnectCouplings.................................. 3-14
Energy $aving Cooling Options
Free-CoolingCycle................................................. 3-14AlternateWaterSourceCycle................................ 3-14
Microprocessor Controls
A-Tech-1.1 (DigitalThermostat,1-stage)................ 3-6A-Tech-1.2 (DigitalThermostat,2-stage)................ 3-6C-Tech-10 (MicroTemp/Humidw/Alarms)............ 3-6A-Tech-20 AdvancedMicroprocessor.................... 3-7A-Tech-20 RemoteCommunications..................... 3-7C6000 AdvancedMicroprocessor.................... 3-8C6000 RemoteCommunications..................... 3-9
Humidity Control Options
SteamHumidifier................................................... 3-10
DehumidificationCycle
- ElectricReheat/Heat...................................... 3-10 - HotGasReheat............................................... 3-10 - HotWaterReheat/Heat................................. 3-10 - SteamReheat/Heat....................................... 3-10 - SCRFired(0-10Vdc)ElectricReheat................ 3-10
High Static Pressure Blowers
HighStaticBelt-DriveBlowerUpgrade.............. 3-10/11 (Upto2.0"ext.staticpressure)
High Efficiency Filtration (IAQ)
IAQHighEfficiencyFilters..................................... 3-11
Head Pressure Control Options
Air Cooled - Low Ambient Control 0FAmbient.................................................... 3-11 -20FAmbient................................................ 3-11 -30FAmbient................................................ 3-11Water/Glycol Cooled - Regulating Valves 2-way,150psig(Standard).............................. 3-11 2-way,350psig............................................... 3-11 2-way,450psig............................................... 3-11
3-way,150psig............................................... 3-11 3-way,350psig............................................... 3-11 3-way,450psig............................................... 3-11
Air Technology Systems, Inc.
Op
tion
al Features - M
icrop
rocesso
r Co
ntro
l Op
tion
s
Optional Features - Microprocessor Control Options
3-6
A-Tech-1.1
TheCeilAiRceilingairconditionershallbeprovidedwithSATS'"slimline",ultra-thinprofile,1-stagecool/1-stageheat,remotewallmountedprogrammabledigitalmicroprocessorbasedcon-troller.
Note: The A-Tech-1.1 thermostat is stan-dard on all single stage DX and non-pro-portional chilled water systems.
A-Tech-1.2
TheCeilAiRceilingairconditionershallbeprovidedwithSATS'"slimline",ultra-thinprofile,2-stagecool/2-stageheat,re-motewallmountedprogramma-bledigitalmicroprocessorbasedcontroller.
Note: The A-Tech-1.2 thermostat is stan-dard on all dual stage DX systems.
Common A-Tech-1.1/1.2 Features:
Autochangeover forHeat/CoolModes SelectableFordegreesCdisplay Fanselectorforcontinuousfan operation Built-inshortcycleprotection Internalswitchtolock-outthekeypad topreventunauthorizedtampering Electroniccalibration 45secondfanpurgeafterheating andcoolingcall Day/Nightbuttonforuserselectable alternatesetpointmanualsetback
12houror24hourclock DaylightSavingsTimebuttonto adjusttheclock+/-1hour Copybuttontoallowoneprogramto becopiedtosubsequentdays Overridefeature Doesnotrequireabattery Solidstateelectronicoutput
C-Tech-10
Temperature & HumidityMicroprocessor Controller
TheCeilAiRceilingmountedairconditionershallbeprovidedwithSATS'C-Tech-10MicroprocessorbasedTemperatureandHumid-itycontrollerwithAlarms.Thecontrollershallincorporateauser-friendlyoperatingenvironmentwithbacklitgraphicLCDdisplay.
Standard Features:
Display/Keypad: BacklitLCDgraphicdisplaywithcharacterstoshowtheoperat-ingmode,time,setpointsandactualreadings
InternalTemperatureandHu-miditySensor
3SetPointProgrammable (Normal,Temporary,Night)per day,7daysperweek SummaryAlarmContact
Visual/Audible Alarm Indication:
HighTemp(HIT) DirtyFilter(EFL)LowTemp(LOT) SensorFailureHighHumid(HIH) Comm.FailureLowHumid(LOH) Summary(EID)
SummaryAlarm(EID):condensate overflow/waterdetection;smokedetec- tion;firestat(ifapplicable)
MaintenaceAlarms:basedonuser definedcomponentrun-timesschedules (compressor1(HR1)&2(HR2);evap blower(HRF).
CeilAiR ControlOptions
5-Levelsofmicroprocessorcontroloffer-ingsallowyoutheflexibilityofselectingthebestcontrolschemefortheiruniquerequirements:
A-Tech-1.1StandardsinglestageDXandnon-proportionalCWHeat/Coolprogrammabledigitalthermo-stat.
A-Tech-1.2StandarddualstageDXHeat/Coolprogram-mabledigitalthermostat.
C-Tech-10OptionalsingleordualstageDXornon-pro-portionalCWTemperatureandHumidityMicroprocessorControllerwithalarms.
A-Tech-20Optionalallpur-poseAdvancedTemperatureandHumidityMicroproces-sorControllerwithalarmsandoptionalremoteBMScommuni-cationsconnections.
C6000OptionalallpurposeAdvancedTemperatureandHumidityMicroprocessorControllerwithalarmsandoptionalremoteBMScommunicationsconnections.
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Op
tion
al Features - M
icrop
rocesso
r Co
ntro
l Op
tion
s
Optional Features - Microprocessor Control Options
3-7
SystemOperation: FanContinuousoronDemand Auto-RestartUponPowerLoss RemoteStop/StartConnection ShortCycleProtection ColdStartTimeDelay Pump-DownCycle
Optional Features:
RemoteTemp/HumidSensor:Optionalremotewallmounted temperatureandhumiditysensorRemoteSensorCableOptions:75ft.cablelength(standardoption)150ft.cablelength
A-Tech-20
Advanced MicroprocessorTemperature & HumidityController with Alarms
TheCeilAiRceilingmountedairconditionershallbeprovidedwithSATS'A-Tech-20AdvancedMicro-processorbasedTemperatureandHumiditycontrollerwithAlarms.Thecontrollershallincorporatea"user-friendly"operatingenviron-ment,toalloweasysystemsetupandoperation.
Standard Features:
4x20characterliquid-crystal alpha-numericaldisplay FieldConfigurable 30Ft.RemoteDisplayCable UnitMountedT/HSensor CurrentUnitStatus ComponentRun-TimeHistory Visual&AudibleAlarm Indication SummaryAlarmContacts AlarmHistory
RemoteStop/StartConnection SelectableAutomaticorManual RestartUponPowerLoss SequentialLoadActivationUpon PowerLossRestart AlarmDelay forSpaceT/HRecov- eryUponPowerLossRestart Multi-LevelPasswordSecurity Protection ShortCycleProtection ColdStartTimeDelay Pump-DownCycle ServiceMode Time-ClockwithOverride Night-SetbackwithOverride
Display/Sensor Options:
RemoteDisplayCableOptions: 30ft.cablelength(standard) 75ft.cablelength 150ft.cablelength
RemoteSensorCableOptions:
75ft.cablelength(standardoption) 150ft.cablelength
ALARM CONDITIONS:
TheA-Tech-20alertstothefollowingalarmconditions(ifapplicable):
HighTemperature DirtyFilterLowTemperature SmokeDetectionHighHumidity FirestatLowHumidity LeakDetectionHighHeadPress GCPumpFailureLowSuctionPress SensorFailureLossofAirFlow Comm.FailureLossofPower
Theoperatormayselectwhichalarmsareactiveorinactive.
CyberLAN Networking Options:
Multi-Unit Sequencing:MultipleCyberAiRairconditionersincorporatingA-Tech-20controlscanbeconfiguredingroupsofupto6(six)unitstoallowfor"N+1"redundancy/backupcriticalappli-cationoperation.
TheA-Tech-20isprogrammedtoautomaticallychangefromcurrentprimaryunitoperationtosecond-arystandbyunitoperationvia
threemethods:
1) ManualChangeOver2) AutomaticTimed(1-30days)3) AutomaticChangeOveronUnit Failure(ifapplicable):
InterconnectCableOptions:
75ft.cablelength(standardoption) 150ft.cablelength
Capacity Assist-Mode: (Additionally Optional)
Inadditiontoswitchoverviamanual,automatictimedorfailure,theCyberLANMulti-UnitSequencingCapacityAssist-Modecaninitiateswitchovertostandbyunitoperationtoassistinthetemperatureand/orhumiditycontrolofthespace.
CapacityAssistSensorCableOpts:
75ft.cablelength(standardoption) 150ft.cablelength
CyberLAN w/ A-Tech 20 Remote Communications
(Optional)
REMOTEBMSCONNECTION(ModBusGateway)
A-Tech-20Inputs&Outputscanberemotelymonitored(addressreadable)andremotelycontrolled(addresswritable)viaanybuild-ingmanagementsystem(BMS)/localareanetwork(LAN)controlsystemthatcancommunicateviaaModBusprotocol.
16UnitsPerCyberLANModBus:EachModBusGatewaycanac-commodateupto16(sixteen)A/Cunitsinagroup.
Air Technology Systems, Inc.
Op
tion
al Features - M
icrop
rocesso
r Co
ntro
l Op
tion
s
Optional Features - Microprocessor Control Options
3-8
C6000
TheCeilAiR ceiling-mounted airconditionershallbeprovidedwithSATSC6000MicroprocessorbasedTemperatureandHumiditycontrol-lerwithAlarms.Thecontrollershallincorporateauser-friendlyoper-ating environment, to allow easysystemsetupandoperation.
TheC6000 is a completemicro-processor based control systemdesignedforoperating,controllingandmonitoring the precision airconditioningunit.
TheC6000controllershallincludeafull-featuredLEDdisplayforvisualindication of the units operatingconditions.
Thecontrollershallbemountedinanindoorratedsteelbox.Theboxshall bepowder coated tomatchthe environmental control unit.Theboxshallcontainthecontrollerboard,theIOboard,andallneces-sarytransformersandinternalwir-ing.Thecontrolboxshallbewallmounted and fieldwired to theenvironmentalcontrolunit.
Display Key Pad
TheDisplayKeyPadshallfeatureaneasytoread,liquid-crystalalpha-nu-mericaldisplay.Thekeypad/displayallowstheoperatortovisuallymoni-tor and customize unit functionsandsettings.Theself-explanatory,keypad nomenclature shall aid intheeaseoflocationofsystempro-grammingfeatures.
Field ConfigurableTheC6000 controller is fieldpro-gramconfigurableandcapableofmatchingtheuniqueneedsofanydatacenter,telecommunicationorothercriticalarea.
Sensor Location OptionsAsastandard,theC6000tempera-tureandhumidity sensor shall befactoryunitmountedinthereturnairstreamofthePrecisionACunit,afterthereturnairfilter(s).
System Setup & AdjustmentsThe C6000 shall be completelyfactorypreprogrammed,andthere-fore,mostapplicationswillrequirenofieldsetup.However,thede-fault setpointsand their rangesare easily adjusted from C6000keypad/display.
Unit Status DisplayTheC6000keypaddisplays currentunitfunctionsandroomstatus:CurrentDryBulbTempSetPointCurrentRelativeHumiditySet Point
Current Unit StatusSystemON/OFFCoolingHeatingHumidifyingDehumidifyingStandbyModeReheatingManualModeActualRoomDBTemperatureActualRoomRelativeHumidity
Run TimesThehistoricalrun-timeinhoursofthe followingmajor componentsshall be available directly fromtheC6000 keypad/display: (if ap-plicable)BlowerMotor(s)Humidifier
ChilledWaterValve
Alarm ConditionsAlarm conditions activate an au-dibleandvisualindicator.Analarmshall beacknowledged throughaResetbuttonlocatedonthekeypaddisplay.
TheC6000alertstothefollowingalarmconditions(ifapplicable):HighTemperatureLowTemperatureHighHumidityLowHumiditySmokeDetectionFirestatLeakDetectionSensorFailureDirtyFilterLossofAirFlow
Summary Alarm ContactAsummaryalarmdry-contact(n/o)connection shall be available forremote annunciation of an alarmcondition. Anadditionaluser-de-fined custom alarm dry-contactshall also be available onmostsystemconfigurations.
Alarm HistoryTheC6000controllerprovidesuserswitharecordedhistoryofthelast80alarms,includingthetimeanddateofthealarmoccurance.
Control Inputs/OutputsThe C6000 is capable of bothdigital (on/off) and analog inputandoutputdevicecontrol.Priortoshipment,eachPrecisionACunitsC6000 is factoryprogramconfig-ured tomatch the units systemoperationalrequirements.
Temperature AnticipationThe C6000 shall incorporate aself-calibrating and self-adjustingcontrol logic that adjusts the re-
Air Technology Systems, Inc.
Air Technology Systems, Inc.
sponseoftheSATSairconditionerto changes in temperature andhumidity.Thesystemshallprovidepremium setpoint accuracywhilecontrolling the room conditionsrate of change, minimizing theequipmentenergyconsumptionandmaximizing the systems operatinglifeandreliability.
Power Loss RestartIn theeventofa lossofpower tothesystem,theC6000canbecon-figured for Automatic orManualRestart. TheC6000s non-volatilememory enables the system to re-startwhenpowerisrestored,with-outthelossofthelaststoredsetpointsandothersystemconfigura-tionsettings.
Sequential Load ActivationTominimizethetotalinrushcurrentloadsduringsystemstartup/restart,theC6000controller shallbecon-figured for time-delay sequencestartup. The user can designatespecificunit restart time-delays, aswellas,eachunitsrespectiveelectricheaterand/orhumidifier.Unitrestartdelaycanbeadjustedfrom0to10minutes.
Recovery DelayAfter a power loss, the C6000sRecoveryDelay feature allows thesystemtooperatewithoutinitiatinganyhighorlowtemperatureorhu-midityalarmsforadelayedperiod.This featureallows time (15 to60minutes adj.) to pull-down theconditioned spaces loadwithoutnuisancealarmsduringinitialstartuporpowerlossrestart.
SecurityMultiple security levels preventunauthorizedadjustmentofcriticalsystemcontrolparameters.
Diagnostic & Service ModeThe C6000 shall incorporate aunique self-diagnostics algorithmthatcontinuallytestssystemsfunc-tions and hardware operation. Intheeventofsuchafailure,theuserwillbealertedtotheconditionviaavisualandaudiblealarm.
Control BoardTheControl Board shall initiate aself-testofthecontrolsystem.
Input DiagnosticsAllsysteminputsandoutputdevicesshallbecontinuouslymonitoredforproperoperation.
Night Set-backTheC6000shallincludeNightSet-Backoccupied/non-occupiedenergysavingmodes.Thisfeatureenablesthe user to customize each unitsdaily5-day/weeklyand2-day/week-endoperationalschedule.
Remote BMS Connection
MIB GATEWAY (Optional)C-6000Inputs&Outputsshallberemotelymonitored(addressreadable)andremotelycontrolled(addresswrit-able)viaanybuildingmanagementsystem(BMS)/localareanetwork(LAN)controlsystemthatcancommunicateviaaModBusprotocol.EachC-6000configuredforBMScommunicationshallincorporateanRS-485Se-rialCommunicationPortthatisfieldconnectedtoafactoryprovidedwallmountedMIBGateway.MIB-FS GATEWAY (Optional)C-6000Inputs&Outputsshallberemotelymonitored(addressread-able)andremotelycontrolled(addresswritable)viaabuildingmanagementsystem(BMS)/localareanetwork(LAN)controlsystem.AvailableProtocols,ModbusRTU,ModbusTCP/IP,BacnetIP,BacnetMSTP,BacnetEthernet,MetasysN-2,andLonworks.
EachC-6000configuredforBMScom-municationshallincorporateanRS-485SerialCommunicationPortthatisfieldconnectedtoafactoryprovidedwallmountedMIBGateway.TheMIB-FSrequiresfieldconfiguration.Numberofunits,typeofprotocolemployed,andindividualdata-pointsmonitoredmustbeconfiguredintheMIB-FSpriortouse.
Op
tion
al Features - M
icrop
rocesso
r Co
ntro
l Op
tion
s
Optional Features - Microprocessor Control Options
3-9
Air Technology Systems, Inc.
Op
tion
al Features - G
uid
e Specifi
cation
s
Optional Features - Guide Specifications
3-10
SELECTED OPTIONS
Humidity Control
Canister Steam Humidification
Thehumidifiershallbeanelectrodesteamcanistertypeandshallhaveanadjustablehumidityoutputsettingfrom25to100%ofthefullratedhumidifiercapacity,anautomaticflushcyclethatsensesthecurrentconsumptionofthehumidifierandcontrolsmineralconcentrationofthewater.AChangeCylinderlightshallnotifyservicepersonnelwhenthehumidificationoutputisbelowratedrequirementsandwhenmainte-nanceisdue.
Dehumidification Cycle
Theceilingairconditionershallbeprovidedwitharefrigerationbaseddehumidificationmode.Moistureshallbecondensedonthecoolingcoilanddischargedthroughthecondensatedrain.
Reheat(electric,hotgas,hotwaterorsteam)shallbeprovidedtooffsetsensiblecoolingduringthedehumidi-ficationcycle.
Electric Reheat/Heat
Afactorymountedandwiredelectricresistanceheatershallbeincludedtoprovideautomaticsensiblereheatingmodeduringthedehumidificationcycleandautomaticheatingmodeasrequired.Electricheatersshallbeprovidedwiththermal/magneticcircuitbreakerswhichshallprotecteachconductor.Theheaterelementsshallbehousedwithinastainlesssteelframewithmountedsupports.Includedshallbeoneautomaticresettingover-temperaturesafetydevice(pilotduty),andanon-reset-tableover-temperaturesafetydevice(locatedinmainpowerline).
Heatersshallusefastreactingni-chromewireheaterelementswhichcoolquicklywhenturnedoffelimi-natingresidualheatproblems.
Hot Gas Reheat:(ModelsOHS-()-AS,AR,W&Gonly)
HP LP
FloodedHead PressureControl Valve
Equ
aliz
erLi
ne
SolenoidValve
RefrigerantReclaim Port
Liquid RefrigerantReceiver
ReliefValve Sight
Glass
RefrigerantDrier / Strainer
Thermal ExpansionValve
ScrollCompressor
Remote AirCooled Condenser
EvaporatorCooling Coil
FeelerBulb
Hot GasReheat Coil
AirFlow
Hot GasReheat Valve
Equ
aliz
erLi
ne
Afactoryinstalledcoppertube,alumninumfinhotgasreheatcoilandvalveshallbeprovidedforautomaticsensiblereheatingmodeduringdehumidificationcycle.Hotcompressordischargegasshallbedivertedfromthecondensertothehotgasreheatcoilprovidingenergyfreesensiblereheating.
(Note: Hot Gas Reheat is not available on systems incorporating Free-Cooling or Alternate Water Source, because no method of reheat would be available during non-compressorized FC or AWS operation.)
Hot Water Reheat/Heat
Afactoryinstalledcoppertube,aluminumfinheat/reheatcoiland2-waycontrolvalveshallbeprovidedtocontroltheflowofhotwaterforautomaticsensiblereheatingmodeduringthedehumidificationcycleandautomaticheatingmodeasrequired.
Steam Reheat/Heat
Afactoryinstalledcoppertube,alu-minumfinheat/reheatcoiland2-waycontrolvalveshallbeprovidedtocontroltheflowofsteamforautomaticsensiblereheatingmodeduringthedehumidificationcycleandautomaticheatingmodeasrequired.
(Note: Steam trap and steam piping specialities shall be provided by others not SATS.)
SCR Fired Reheat/Heat
Theelectricheat/reheatshallbecontrolledthroughaZeroFiringSiliconControlledRectifier(SCR)withanextrudedaluminumheatsinkandsolidstatelogicsystemtoprovideclosedrybulbtemperaturecontroloftheconditionedair.
A-Tech-20proportional(0-10Vdc)microprocessorcontrolsshallbeprovidedwiththeSCRFiredElectricReheatoption.
High Static Pressure Belt-Drive Blowers
TheCeilAiRceilingairconditionershallbeprovidedwithahighstaticpressurebelt-drivenevaporatorblowertoprovidestandardunitCFM@____"e.s.p.
(Note:DuetotheprobablechangeinstandardunitblowermotorhorsepowerfortheHighStaticBelt-DriveBlower
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Op
tion
al Features - G
uid
e Specifi
cation
s
Optional Features - Guide Specifications
3-11
} 3-wayvalvesshiplooseforfieldinstallation.
option,pleaseconsultyourlocalSATSsalesrepresentativeforthefollowingunitspecificationchanges:
BlowerMotorHorsepower NetCoolingCapacity ElectricalData DischargeBlowerData
Unit AIr Flow Rate (CFM) will match the standard data as shown in Section 4 of this manual for each respective unit model.)
Filtration
CeilAiRceilingA/C'sareavailablewiththefollowingstandard(F1)andoptional(F2,F3&F4)highefficiencyIAQconsciousfiltration:
F1: 1",20%Eff.Filters(standard)F2: 2",30%Eff.FiltersF3: 4",60%Eff.FiltersF4: 2",30%Pre/4",60%Eff.FinalFilters
AirPatternType FiltersAvail.
DirectDrive012/040: w/SpotCooler: F1 w/DuctedReturn: F1,F2(n/a024)
Belt-DriveUnits: w/DuctedReturn: F1,F2,F3&F4
Filterratingsarebasedondustspotef-ficiencyratingsperASHRAETestStandard52-76.
(Note: F2, F3 & F4 optional filters create additional static pressure and may require the High Static Pressure Belt-Drive Option. Please consult your local Sales Represen-tative for details.)
Head Pressure Control
AIR COOLED - Low Ambient
0F, Fan Cycling / Fan Speed
Theaircooledsystemshallincor-poratealowambientfancycling/
fanspeedheadpressurecontrolforyear-roundairconditioningsystemoperationdownto0FDBminimumambientairtemperature.
(Note: 0F fan cycling head pressure con-trol is a standard feature for all CeilAiR air cooled condensers and condensing units incorporating direct drive condenser fans.)
-20F, Variable Speed Control(ModelWCS-()Condensers)
Theaircooledsystemshallincorpo-ratealowambientvariablespeedfanheadpressurecontrolforyear-roundsystemoperationdownto-20FDBminimumambientairtemperature.
-30F, Flooded Control
HP LP
FloodedHead PressureControl Valve
Equa
lizer
Line
Liquid LineSolenoid Valve
RefrigerantReclaim Port
Liquid RefrigerantReceiver
ReliefValve Sight
Glass
RefrigerantDrier / Strainer Thermal Expansion
Valve
LowPressureSwitch
ScrollCompressor
Remote AirCooled Condenser
(Optional)
EvaporatorCooling Coil
FeelerBulb
HighPressure
Switch
Theaircooledsystemshallincor-poratealowambientfloodedheadpressurecontrolforyear-roundsystemoperationdownto-30FDBminimumambientairtemperature.
Thisoptionshallincludeafactoryinstalledcrankcaseheater,cold-startrelay,liquidrefrigerantreceiverwithreceiverliquidlevelsightglassandheadpressureregulatingvalveforfloodedcondenseroperation.
DXWaterCooledandGlycolCooledsystemsareavailablewithfollowingstandard(V1)andoptional(V2-V6)headpressureregulatingcontrolvalves:
V1: 2-way,150psig(standard)V2: 2-way,350psigV3: 2-way,450psig
V4: 3-way,150psigV5: 3-way,350psigV6: 3-way,450psig
Eachrefrigerantcircuit'sheadpres-sureshallbecontrolledbyafactory(orfield)installed____-waywater/glycolregulatingvalveratedfor____psig.w.w.p.
FREE-COOLING SYSTEMS
DXWater/GlycolCooledsystemswithFree-CoolingareavailablewiththefollowingstandardandoptionalDXheadpressureandFree-Coolingvalvecombinations:
150psigRatedSystem:(standard)
DXValves = 3-way,150psigFCValve = 3-way,300/400psig
300psigRatedSystem:(optional)
DXValves = 3-way,350psigFCValve = 3-way,300/400psig
400psigRatedSystem:(optional)
DXValves = 3-way,450psigFCValve = 3-way,400psig
Eachrefrigerantcircuit'sheadpres-sureshallbecontrolledbyafieldinstalled3-waywater/glycolregulat-ingvalveratedfor____psigw.w.p.Free-Coolingmodecoolingshallbecontrolledbyafactoryinstalled3-waymotorized(on/off)controlvalveratedfor____psig.w.w.p.
Note: Modulating (0-10 Vdc) Free-Cool-ing mode cooling control is optionally available via A-Tech-20 controls and modulating 3-way FC control valve.
DX - Capacity Modulation /Freeze-Protection
SNAP-ACTING, Hot Gas Bypass(ModelsOHS-()-AS,AR,W&Gonly)
TheCeilAiRceilingA/Cshallincor-porateasnapactinghotgasbypasssystemtoprovidemodulationoftheunitscoolingcapacityandevaporatorcoilfreezeprotectionunderlowloadconditions.
Air Technology Systems, Inc.
Op
tion
al Features - G
uid
e Specifi
cation
s
Optional Features - Guide Specifications
3-12
HP
LP
FloodedHead PressureControl Valve
Equ
aliz
erLi
ne
Liquid LineSolenoid Valve
RefrigerantReclaim PortLiquid Refrigerant
Receiver
ReliefValve Sight
Glass
RefrigerantDrier / Strainer Thermal Expansion
Valve
LowPressureSwitch
ScrollCompressor
Remote AirCooled Condenser
(Optional)
EvaporatorCooling Coil
FeelerBulb
HighPressure
Switch
Hot GasRegulator Valve
(Optional)
FULL-FLOATING, Hot Gas Bypass(ModelsOHS-()-()AHU/SCOonly)
TheCeilAiRceilingA/Cshallincor-porateafullfloatinghotgasbypasssystemtoprovidemodulationoftheunitscoolingcapacityandevaporatorcoilfreezeprotectionunderlowloadconditions.
DUAL COMPRESSOR SYSTEMS(ModelsOHS-()-D())
Theairconditionershallbeadualscrollcompressorsystemwithtwoindependentrefrigerationcircuitstoprovide50%capacityunloading,aswellascomponentredundancy.
Theairconditionershallbeprovidedwitha2-Stagetemperaturecontrol-lerwithmicroprocessorbasedcontrollogicforautomaticstaging.
Chilled Water & AWSControl Valves
ChilledWaterandAlternateWaterSourcecoolingshallbecontrolledbythefollowingstandardandoptionalcontrolvalves:
ModelsOHS-012/060-C/AWS:
V1: 2-way,300psig(standard)V2: 2-way,400psigV3: 3-way,300psigV4: 3-way,400psig
ModelsOHS-072/120-C/AWS:
V5: 2-way,400psig(standard)
V6: 3-way,400psig
Standard (On/Off) Valve Control :A____-waymotorized(On/Off)CWorAWScoolingcontrolvalveratedforamaximum____psigw.w.p.shallbefactoryunitinstalled.Precisioncoolingcontrolshallbeaccomplishedviaaspringreturnslowopenandclosevalvedesign.
Optional (0-10 Vdc) Valve Control:A____-waymodulatingCWorAWScoolingcontrolvalveratedforamaximum____psigw.w.p.shallbefactoryinstalled.Precisioncoolingcontrolshallbeaccomplishedviaa0-10VdcA-Tech-20analogcontrolsignaltotheproportionalactuatingcontrolvalve.
ACCESSORIES
3 Phase Power Supply
HP LP
FloodedHead PressureControl Valve
Equ
aliz
erLi
ne
Liquid LineSolenoid Valve
RefrigerantReclaim Port
Liquid RefrigerantReceiver
ReliefValve Sight
Glass
RefrigerantDrier / Strainer Thermal Expansion
Valve
LowPressureSwitch
ScrollCompressor
Remote AirCooled Condenser
(Optional)
EvaporatorCooling Coil
FeelerBulb
HighPressure
Switch
Three phase power supply is avail-able, as an option, on OHS-024, 032 & 040-() units.
Compressor,(belt-driveblowermotor(s)andelectricheat/reheatifapplicable)shallbethreephaseinlieuofstandardsinglephase.Allothercomponents(5/10lbhumidifieranddirectdrivemotor(s))shallbesinglephase,witheachlegofpowersupplybalancedascloselyaspossible.
(Note: Three phase power supply is a standard feature on models OHS-048 and larger units.)
277/1/60 Power Supply(ModelsOHS-012thru-040)
Amainpowerdistributionblockshallbelocatedintheairconditioner'selectricboxforsinglepointpowerconnectiontoa277/1/60powersup-plysource.Allsystemcomponents(motor,heater&humidifier,ifap-plicable)shallberatedforoperationwitha277/1/60powersupply.277Vto208Vmainpowerstep-downtransformersshallnotberequired.
Note-1: Fast delivery orders some-times require that the OHS system be shipped from stock as 208/1/60. In those cases, 277/1/60 applications are provided with a field installed 277 to 208 step-down transformer.
Condensate Pump
ALow-Profilecondensatepumpdesignedforlimitedheightceilingplenuminstallationshallbefactoryprovidedforautomaticremovalofcondensateandhumidifierflushwater(ifapplicable).Thecondensatepumpshallbefieldinstalledasastandard.
AheavydutyAll-Metalcondensatepumpshallbeprovidedforautomaticremovalofcondensateandhumidi-fierflushwater(ifapplicable).Thepumpshallbeconstructedwithacastaluminumreservoirandimpeller;aluminumreservoircoverandimpel-lerchambercover;stainlesssteelfastenersandastainlesssteelmotorshaft.Thecondensatepumpmeetsmostlocalcodesforcertificationasa"plenumrated"pump.Theconden-satepumpshallbefieldinstalledonly.
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Op
tion
al Features - G
uid
e Specifi
cation
s
Optional Features - Guide Specifications
3-13
1to3TonModels:OHS-012/040-HAS,HAR,HAHU,HW,HG&HC
4to10TonModels:OHS-048/120-()AR,AHU,W,G&C
Factory Installed In-PanCondensate Pump
(Not Available w/ Humidifier)
Smoke Detector
Aphoto-electricsmokedetectorshallbefactoryinstalledintheCeilAiRevaporatorsectiononthesuctionsideoftheevaporatorblower.
Thesmokedetectorshallberatedforhighairvelocityapplications,andshallshutdowntheairconditioneruponsensingsmokeinthereturnairstream.
Firestat
Theairconditionershallbeprovidedwithafactorywiredandmountedfirestat.Thefirestatshallshutdowntheairconditioneruponsensingahighreturnairtemperature.
Remote Water DetectorsSingle (one) - Spot Type Detector:
Quantity1(one)remotespottype
water/leakdetectorperCeilAiRA/Cunitshallbefactoryprovidedforremotefieldinstallation.Uponsens-ingawaterleak,thenormallyclosedwaterdetectorcontrolcircuitshallopen,therebyshuttingdowntheairconditioner'swaterproducingopera-tions.
Dual (two) - Spot Type Detectors:Quantity2(two)remotespottypewater/leakdetectorsperCeilAiRA/Cunitshallbefactoryprovidedforremotefieldinstallation.Uponsensingawaterleak,thenormallyclosedwaterdetectorcontrolcircuitshallopen,therebyshuttingdowntheairconditioner'swaterproducingoperations.20 Ft. - Strip/Cable Type Detector:
A20Ft.inlengthremotestrip/cabletypewater/leakdetectorshallbefactoryprovidedforremotefieldinstallation.Inadditiontothe20ft.cable,a24Vpowerwaterdetec-torpowermoduleshallrequirefieldmountingandwiringtofactoryprovidedterminalconnection.Uponsensingawaterleak,thenormallyclosedwaterdetectorcontrolcircuitshallopen,therebyshuttingdowntheairconditioner'swaterproducingoperations.
Compressor Sound Jackets(AirCooled0FOHS-()-AS,andWater/GlycolCooledOnly!)
Eachcompressorshallbeprovidedwithafactoryinstalledacousticalsoundjacket.Eachsoundjacketshallhaveasnapclosuresystemforeaseofremovingandreinstallationduring
Thecondensatepumpshallbespecificallydesignedtooperatewiththehighercondensatetemperaturescausedbytheflushanddraincycleoftheelectrodecanisterhumidifiers.
DualOverflowSafetySwitches:Inadditiontothestandardconden-satepanoverflowsafetyfloat(s),thecondensatepumpshallincludeaninternaloverflowsafetyfloatswitchwhich,whenwiredtotheA/C'sre-motestop/startterminals,shallopentheA/C'scontrolcircuit,therebyshuttingtheA/Cdownintheeventofacondensateoverflow.
Factory Installed - Optional
Low-Profile Condensate PumpTheCeilAiRLow-Profilecondensatepumpcanbefactoryinstalledasanoptiononthefollowingmodels:
OHS-012/040-AS,AHU,AR,W,G&C
Factory Installed Low-ProfileCondensate Pump
In-PanCondensatePumpTheCeilAiRIn-Pancondensatepumpcanbefactoryinstalledasanoptioninthefollowingmodels:
Air Technology Systems, Inc.
Op
tion
al Features - G
uid
e Specifi
cation
s
Optional Features - Guide Specifications
3-14
maintenance.EachsoundjacketshallhaveaNoiseReductionCoefficientNRCof85perASTMC-423andaSoundTransmissionLossSTCof11perASTME-90.
Low Entering Condenser Water KitForWater/Glycolsystemsthatrequireenteringcondenserwatertempera-turesfrom65Fto45F,thesystemshallbeprovidedwithafactoryinstalledin-lineliquidrefrigerantreceivertohelpreducethenegativeeffectthelowcondensersourcecanhaveontheevaporator.Acompres-sorcrankcaseheatershallalsobeprovidedstandardwiththisoption.(CompressorSoundJacketsarenotavailablewiththisoptionduetothecrankcaseheater).
Main Power - ElectricNon-Fused Service SwitchThemainpowerserviceswitchshallbetheNEMA3RorNEMA-12non-fusedtype,dependingontheOHSmodelselected.Thedisconnectswitchshallhavealockablehandle.
(Note: Field installed main power service switches shall be the standard option, however, switches can be optionally fac-tory mounted on select CeilAiR systems. Factory mounting of disconnect switches is not available on models OHS-012, 018, 024 & 032-AS incorporating the "Ducted" Evaporator Connection option.)
Refrigerant Lines w/ Quick Disconnects(AHU/RCU-OSystemsOnly!)
Eachrefrigerantcircuitshallbesuppliedwithfactoryassembled,soft-copperrefrigerantlineset50ft.inlengthcompletewithquickdiscon-nectcouplingsandschraederserviceports.Thequickdisconnectcouplesshallbeindustrialgrade,self-sealing,reusabletypecouplings.Suctionlinesshallbeinsulated,liquidlinesshallbeuninsulated.
ENERGY $AVING COOLING OPTIONS
Free-Cooling Option(Water/Glycol Economizer Coil)
AFree-Coolingcycleshallbeprovidedtotakeadvantageoflowambientairtemperatureconditionstoprovidecompressor-lesscooling.
Whenoutdoortemperaturesaresufficientlylow(setpointadjustable),sourcecoolantshallbedivertedfromtheDX-WaterorGlycolCooledrefrigerantcondensertoachilledwater/glycolcoil(free-coolingcoil&controlvalve).Thedrycoolercapac-ityshallbeincreasedbyreversingthetypicaldrycoolerfan(s)cyclingsequenceofoperationtoprovidethemaximumcoolingeffectforthecool-antsolution.Thefree-coolingcoilshallbecloselysizedtomatchthere-frigerantcoolingcapacitytoincreasethenumberofhoursthatthesystemcanoperateinthefree-coolingmode,therebyincreasingtheoperatingsav-ingsoftheinstallation.
Alternate Water Source(Chilled Water by "Day"
and DX-Backup by "Night")
AnAlternateWaterSourcecool-ingcycleshallbeprovidedtoutilizebuildingchilledwatersupplywhenavailableastheprimarycoolingcyclewithDX-AirCooledrefrigerantcool-ingasabackup.
Theairconditionershallhavetwocoolingsystems:
1) Achilledwater/glycolcircuit (AWScoil&controlvalve);
2) AbackupDXcompressorized refrigerantcircuit.
Equ
aliz
erLi
ne
RefrigerantReclaim Port
SightGlass
RefrigerantDrier / Strainer
ExpansionValve
ScrollCompressor DX - Cooling
Coil
Alternate WaterSource Cooling Coil
AWSControl
Valve
Remote Liquid Chiller(by others)
Pump(by others)
Alternate WaterSource Aqua-Stat
FeelerBulbHP LP
SolenoidValve
ReliefValve
Receiver
Remote Air CooledCondenser
T
FSFlow
Switch
FloodedHead Pressure Control Valve
Whenchilledwaterisavailable,thesystemshalloperateasachilledwaterunit,withoutthecompressoroperating.Whenthewatertempera-tureistoohigh,orthewaterflowrateisnotsufficient,theaircondi-tionershallautomaticallyswitchtotheDXcompressorizedrefrigerantoperation.
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Perform
ance D
ata - Ind
ex
Performance Data - Equipment Schedule Data
4-1
Performance Data Index
DX - Air Cooled
Self-Contained Air Cooled:
1-3Ton,modelsOHS-012/040-AS................................... 4-2/3
Split Air Cooled Remote w/ Condenser:
1-5Ton,modelsOHS-012/060-AR................................... 4-2/3 4-10Ton,modelsOHS-048/120-DAR................................. 4-4
Split Air Cooled Air Handling w/ Condensing Unit:
1-5Ton,modelsOHS-012/060-AHU................................... 4-5 4-10Ton,modelsOHS-048/120-DAHU............................... 4-6
DX - Water Cooled
Self-Contained Water Cooled:
1-5Ton,modelsOHS-012/060-W....................................... 4-7 4-10Ton,modelsOHS-048/120-DW.................................. 4-8
DX - Glycol Cooled
Self-Contained Glycol Cooled:
1-5Ton,modelsOHS-012/060-G........................................ 4-9 4-10Ton,modelsOHS-048/120-DG................................. 4-10
Chilled Water
Chilled Water Air Handlers:
1-3Ton,modelsOHS-012/040-C................................. 4-11/12 4-10Ton,modelsOHS-048/120-C............................... 4-13/14
42FEWTPerformanceData............................................ 4-15 50FEWTPerformanceData............................................ 4-16
MODEL TYPE ...........................................page
DX with Free-Cooling
Self-Contained Glycol Cooled w/ FC:
1-5Ton,modelsOHS-012/060-G-FC........................... 4-17/19 4-10Ton,modelsOHS-048/120-DG-FC....................... 4-20/21
Self-Contained Water Cooled w/ FC:
1-5Ton,modelsOHS-012/060-W-FC........................... 4-22/23 4-10Ton,modelsOHS-048/120-DW-FC...................... 4-24/25
DX with Alternate Water Source
Alternate Water Source:
1-5Ton,modelsOHS-012/060-()-AWS............................ 4-26 4-10Ton,modelsOHS-048/120-D()-AWS......................... 4-27 42F/50FEWTPerformanceData.................................. 4-28
Air Technology Systems, Inc.
Perform
ance D
ata - Air C
oo
led (1 to
5 ton
Systems)
Air Cooled - 1 to 5 Ton "OHS" (Single Compressor), Self-Contained & Split
4-2
OHS Model 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-ARNET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB,50%RH
Total 13,985 19,465 25,740 32,770 35,800 59,970 65,975
Sensible 10,585 15,235 19,470 23,430 27,950 47,685 52,435
75FDB/62.5FWB,50%RH
Total 12,710 18,000 23,600 30,000 32,650 55,010 60,470
Sensible 10,645 15,400 19,025 22,920 27,430 46,960 51,630
72FDB/60FWB,50%RH
Total 12,000 17,160 22,465 28,500 31,050 52,400 57,580
Sensible 10,405 15,100 18,580 22,400 26,690 46,020 50,590
80FDB/65FWB,45%RH
Total 13,425 18,860 24,600 31,320 34,700 57,680 63,350
Sensible 11,840 16,990 20,900 24,905 30,900 52,080 57,325
75FDB/61FWB,45%RH
Total 12,270 17,490 23,030 28,895 32,080 53,415 58,620
Sensible 11,385 16,400 20,500 23,940 29,650 50,250 55,285
72FDB/58.5FWB,45%RH
Total 11,585 16,665 22,000 27,400 30,530 50,875 55,790
Sensible 11,110 16,065 20,060 23,600 28,990 49,180 54,080
Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)
ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@208V 17,135(5.0) 17,135(5.0) 17,135(5.0) 17,425(5.1) 17,955(5.3) 37,350(10.9) 38,900(11.4)
@230V 18,840(5.5) 18,840(5.5) 18,840(5.5) 19,130(5.6) 19,660(5.8) 43,140(12.6) 44,690(13.1)
@460V 17,355(5.1) 17,355(5.1) 17,355(5.1) 17,645(5.2) 18,175(5.3) 37,350(10.9) 38,900(11.4)
@277/480V 18,065(5.3) 18,065(5.3) 18,065(5.3) 18,355(5.4) 18,885(5.5) 38,835(11.4) 40,385(11.8)
HOT GAS REHEAT
BTU/H 11,390 17,030 21,190 25,650 30,920 49,310 54,210
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H 20,690 32,420 34,880 50,360 55,320 97,140 111,220
GPM 1 2 2 3 3 4 5
PressureDrop,ft.wg 0.1 0.3 0.3 0.3 0.3 0.4 0.6
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H(nominal) 12,000 18,000 24,000 32,000 40,000 48,000 60,000
Condensate(lb/hr) 13 19 25 34 42 50 63
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)
Lbs/Hr,(KwInput) 2-5,(1.7) 2-5,(1.7) 2-5,(1.7) 2-5,(1.7) 2-5,(1.7) 4-10,(3.4) 4-10,(3.4)
StdControl Cycling Cycling Cycling Cycling Cycling Cycling Cycling
EvaporatorBlower/Motor-DWDICentrifugal
Horsepower 1/4Hp 1/4Hp 1/4Hp 1/3Hp 1/2Hp 1Hp 1-1/2Hp
[email protected]. [email protected]" [email protected]" [email protected]" 1,[email protected]" 1,[email protected]" 2,[email protected]" 2,[email protected]"
Std.DriveMethod DirectDriven DirectDriven DirectDriven DirectDriven DirectDriven BeltDriven BeltDriven
Continued on next page
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Air Cooled - 1 to 5 Ton "OHS" (Single Compressor), Self-Contained & Split
Perform
ance D
ata - Air C
oo
led (1 to
5 ton
Systems)
OHS Model 012-AS/AR 018-AS/AR 024-AS/AR 032-AS/AR 040-AS/AR 048-AR 060-ARNET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/FaceArea(Ft2) 3/2.1 3/2.1 3/2.1 3/2.8 3/2.8 4/5.0 4/5.0
Compressor - Heat pump duty rated, HCFC Ozone Safe R-22
Type,(Qty.) Recip.,(1) Scroll,(1) Scroll,(1) Scroll,(1) Scroll,(1) Scroll,(1) Scroll,(1)
Watts-Input 1,405 1,614 2,092 2,711 2,842 4,415 4,959
Tot.HeatofRej.(BTU/H) 17,595 24,260 31,480 40,500 43,830 70,080 77,395
Filters - 1" deep throwaway
Nom.Size(in.),(Qty.) 20x20,(1) 20x20,(1) 20x20,(1) 20x20,(1) 20x20,(1) 20x16,(2) 20x16,(2)
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant: (OHS-012/060-()AR only)
LiquidLine,(Qty.) 3/8"OD,(1) 3/8"OD,(1) 3/8"OD,(1) 1/2"OD(1) 1/2"OD(1) 1/2"OD(1) 1/2"OD(1)
HotGasLine,(Qty.) 1/2"OD,(1) 1/2"OD,(1) 5/8"OD,(1) 5/8"OD(1) 7/8"OD(1) 7/8"OD(1) 7/8"OD(1)
CondensateDrain 7/8"OD 7/8"OD 7/8"OD 7/8"OD 7/8"OD 3/4"FPT 3/4"FPT
HumidifierInlet 1/4"OD 1/4"OD 1/4"OD 1/4"OD 1/4"OD 1/4"OD 1/4"OD
Physical Size - (Please refer to Section 6 for detailed dimensional data.)
Approx.Wt.(OHS-()-AS) 210lbs 215lbs 220lbs 255lbs 265lbs N/A N/A
Approx.Wt.(OHS-()-AR) 160lbs 165lbs 170lbs 205lbs 215lbs 370lbs 380lbs
Air Cooled Condenser Data - (Self Contained)OHS Model @ 95F Amb. 012-AS 018-AS 024-AS 032-AS 040-AS 048 060Integral Centrifugal Blower, Air Cooled Condenser Data for Self-Contained Model OHS-( )-AS
Condenser Blower Data
CFM @ e.s.p 750 @ 0.3" 1,400 @ 0.3" 1,400 @ 0.3" 2,000 @ 0.3" 2,000 @ 0.3" N/A N/A
Motor Horsepower 1/3 Hp. 1/2 Hp. 1/2 Hp. 1/2 Hp. 1/2 Hp. N/A N/A
Drive Method Direct Direct Direct Direct Direct N/A N/A
Condenser Coil
Rows/Face Area (ft2) 4 / 2.1 4 / 2.1 4 / 2.1 4 / 2.8 4 / 2.8 N/A N/A
Low Ambient Control
Std. Minimum Op. Amb. 0F 0F 0F 0F 0F N/A N/A
Head Pressure Method MotorSpeed MotorSpeed MotorSpeed MotorSpeed MotorSpeed N/A N/A
Note:
CompressorisintegraltotheOHS-()-ASSelf-ContainedUnit.
PleaserefertotheSATSHeat Rejection Engineering ManualforspecificationandperformancedataonRemoteOutdoorandIndoorAirCooledCondensersusedwithOHS-()-()ARSplitSystems.
4-3
Air Technology Systems, Inc.
OHS Model ( )-048-DAR ( )-072-DAR ( )-084-DAR ( )-120-DARNET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB,50%RH
Total 53,740 73,870 92,065 130,435
Sensible 40,860 62,110 71,070 98,030
75FDB/62.5FWB,50%RH
Total 49,250 67,550 83,980 119,590
Sensible 40,290 61,525 70,840 96,230
72FDB/60FWB,50%RH
Total 46,950 64,275 79,760 113,380
Sensible 39,480 60,215 69,565 94,580
80FDB/65FWB,45%RH
Total 51,610 70,730 87,660 124,890
Sensible 44,310 68,085 79,060 106,480
75FDB/61FWB,45%RH
Total 47,860 65,590 80,770 115,540
Sensible 42,830 64,070 76,215 102,850
72FDB/58.5FWB,45%RH
Total 45,620 62,750 76,660 109,955
Sensible 42,040 61,910 73,710 100,920
Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)
ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@208V/460V 36,810(10.9) 38,900(11.4) 40,510(11.9) 43,580(12.8)
@230V 42,600(12.5) 44,690(13.1) 46,300(13.6) 49,370(14.5)
@480V 38,295(11.2) 40,385(11.8) 41,995(12.3) 45,065(13.2)
HOT GAS REHEAT
BTU/H 21,150 32,300 37,190 50,520
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H 50,360 97,880 99,830 130,500
GPM 3 3 3 10
PressureDrop,ft.wg 0.3 0.3 0.3 2.2
Control Motorized Motorized Motorized Motorized
STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H(nominal) 48,000 72,000 90,000 120,000
Condensate(lbs/hr) 50 75 94 125
Control Motorized Motorized Motorized Motorized
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)
Lbs/Hr,(KwInput) 4-10,(3.4) 4-15,(5.1) 4-15,(5.1) 4-15,(5.1)
StdControl Cycling Cycling Cycling Cycling
EvaporatorBlower/Motor-DWDICentrifugal-BeltDriven,VariablePitchPulleys
Horsepower 3/4Hp 1-1/2Hp 2Hp 3Hp
[email protected]. 1,[email protected]" 3,[email protected]" 3,[email protected]" 4,[email protected]"
DriveMethod BeltDriven BeltDriven BeltDriven BeltDriven
Evaporator Coil - Aluminum Fin, Copper Tube
Rows 3 4 4 4
FaceArea(Ft2) 4.1 6.7 6.7 10
Compressor - Heat pump duty rated, HCFC Ozone Safe R-22
Type,(Qty.) Scroll,(2) Scroll,(2) Scroll,(2) Scroll,(2)
WattsInput(percompressor) 2,054 2,797 3,848 4,959
TotalHeatofRejection,(BTU/H) 63,270 86,645 110,250 153,440
Filters - 1" deep throwaway
NominalSize(in.),(Qty.) 16x20,(2) 20x20,(2) 20x20,(2) 24x24,(2)
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant:
LiquidLine,(Qty.) 3/8"OD,(2) 1/2"OD,(2) 1/2"OD,(2) 1/2"OD,(2)
HotGasLine,(Qty.) 5/8"OD,(2) 5/8"OD,(2) 7/8"OD,(2) 7/8"OD,(2)
CondensateDrain,(w/In-PanPump) 3/4"FPT,(1/2"OD) 3/4"FPT,(1/2"OD) 3/4"FPT,(1/2"OD) 3/4"FPT,(1/2"OD)
HumidifierInlet 1/4"OD 1/4"OD 1/4"OD 1/4"OD
Physical Size - (Please refer to Section 6 for detailed dimensional data.)
Approx.Weight 420lbs 450lbs 510lbs 580lbs
Air Cooled - 4 to 10 Ton "OHS" (Dual Compressors)Perfo
rman
ce Data - A
ir Co
oled
(4 to 10 To
n, D
UA
L Co
mp
ressor)
4-4
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensers
4-5
Perform
ance D
ata - Air C
oo
led A
HU
/RC
U (1 to
5 ton
Systems)
Air Cooled AHU/RCU - 1 to 5 Ton "OHS"OHS Model 012-AHU 018-AHU 024-AHU 032-AHU 040-AHU 048-AHU 060-AHU
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total 13,985 19,465 25,740 32,940 36,505 59,970 65,975
Sensible 10,585 15,235 19,470 24,595 30,065 47,685 52,435
75FDB/62.5FWB, 50% RH
Total 12,710 18,000 23,600 30,355 33,750 55,010 60,470
Sensible 10,645 15,400 19,025 24,235 29,300 46,960 51,630
72FDB/60FWB, 50% RH
Total 12,000 17,160 22,465 29,035 32,320 52,400 57,580
Sensible 10,405 15,100 18,580 23,680 28,500 46,020 50,590
80FDB/65FWB, 45% RH
Total 13,425 18,860 24,600 31,670 35,120 57,680 63,350
Sensible 11,840 16,990 20,900 27,560 33,385 52,080 57,325
75FDB/61FWB, 45% RH
Total 12,270 17,490 23,030 29,500 32,790 53,415 58,620
Sensible 11,385 16,400 20,500 26,251 31,530 50,250 55,285
72FDB/58.5FWB, 45% RH
Total 11,585 16,665 22,000 28,220 31,410 50,875 55,790
Sensible 11,110 16,065 20,060 25,570 30,525 49,180 54,080
Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)
ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@208V 17,135(5.0) 17,135(5.0) 17,135(5.0) 17,425(5.1) 17,955(5.3) 37,350(10.9) 38,900(11.4)
@230V 18,840(5.5) 18,840(5.5) 18,840(5.5) 19,130(5.6) 19,660(5.8) 43,140(12.6) 44,690(13.1)
@460V 17,355(5.1) 17,355(5.1) 17,355(5.1) 17,645(5.2) 18,175(5.3) 37,350(10.9) 38,900(11.4)
@277/480V 18,065(5.3) 18,065(5.3) 18,065(5.3) 18,355(5.4) 18,885(5.5) 38,835(11.4) 40,385(11.8)
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H 20,690 32,420 34,880 50,360 55,320 97,140 111,220
GPM 1 2 2 3 3 4 5
PressureDrop,ft.wg 0.1 0.3 0.3 0.3 0.3 0.4 0.6
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H(nominal) 12,000 18,000 24,000 32,000 40,000 48,000 60,000
Condensate(lb/hr) 13 19 25 34 42 50 63
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Humidification-ElectrodeSteamCanisterHumidifierwithAdjustableOutput,(Optional)
Lbs/Hr,(KwInput) 2-5,(1.7) 2-5,(1.7) 2-5,(1.7) 2-5,(1.7) 2-5,(1.7) 4-10,(3.4) 4-10,(3.4)
StdControl Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Horsepower 1/4Hp 1/4Hp 1/4Hp 1/3Hp 1/2Hp 1Hp 1-1/2Hp
[email protected]. [email protected]" [email protected]" [email protected]" 1,[email protected]" 1,[email protected]" 2,[email protected]" 2,[email protected]"
Std.DriveMethod DirectDriven DirectDriven DirectDriven DirectDriven DirectDriven BeltDriven BeltDriven
Opt.DriveMethod Belt-Driven Belt-Driven Belt-Driven Belt-Driven Belt-Driven N/A N/A
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/FaceArea(Ft2) 3/2.1 3/2.1 3/2.1 3/2.8 3/2.8 4/5.0 4/5.0
Filters-1"deepthrowaway
Nom.Size(in.),(Qty.) 20x20,(1) 20x20,(1) 20x20,(1) 20x20,(1) 20x20,(1) 20x16,(2) 20x16,(2)
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant:
Suction,(Qty.) 5/8"OD,(1) 3/4"OD,(1) 3/4"OD,(1) 3/4"OD(1) 7/8"OD(1) 7/8"OD(1) 7/8"OD(1)
LiquidLine,(Qty.) 3/8"OD,(1) 3/8"OD,(1) 3/8"OD,(1) 1/2"OD(1) 1/2"OD(1) 1/2"OD(1) 1/2"OD(1)
CondensateDrain 7/8"OD 7/8"OD 7/8"OD 7/8"OD 7/8"OD 3/4"FPT 3/4"FPT
HumidifierInlet 1/4"OD 1/4"OD 1/4"OD 1/4"OD 1/4"OD 1/4"OD 1/4"OD
Physical Size - (Please refer to Section 6 for detailed dimensional data.)
Approx.Wt. 120lbs 120lbs 120lbs 155lbs 165lbs 270lbs 280lbs
Air Technology Systems, Inc.
Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensing Units
4-6
Air Cooled DAHU/DRCU - 4 to 10 Ton "OHS" (Dual)
OHS Model ( )-048-DAHU ( )-072-DAHU ( )-084-DAHU ( )-120-DAHU
NET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total 53,740 73,870 92,065 130,435
Sensible 40,860 62,110 71,070 98,030
75FDB/62.5FWB, 50% RH
Total 49,250 67,550 83,980 119,590
Sensible 40,290 61,525 70,840 96,230
72FDB/60FWB, 50% RH
Total 46,950 64,275 79,760 113,380
Sensible 39,480 60,215 69,565 94,580
80FDB/65FWB, 45% RH
Total 51,610 70,730 87,660 124,890
Sensible 44,310 68,085 79,060 106,480
75FDB/61FWB, 45% RH
Total 47,860 65,590 80,770 115,540
Sensible 42,830 64,070 76,215 102,850
72FDB/58.5FWB, 45% RH
Total 45,620 62,750 76,660 109,955
Sensible 42,040 61,910 73,710 100,920
Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)
ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@208V/460V 36,810(10.9) 38,900(11.4) 40,510(11.9) 43,580(12.8)
@230V 42,600(12.5) 44,690(13.1) 46,300(13.6) 49,370(14.5)
@480V 38,295(11.2) 40,385(11.8) 41,995(12.3) 45,065(13.2)
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H 50,360 97,880 99,830 130,500
GPM 3 3 3 10
PressureDrop,ft.wg 0.3 0.3 0.3 2.2
Control Motorized Motorized Motorized Motorized
STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H(nominal) 48,000 72,000 90,000 120,000
Condensate(lbs/hr) 50 75 94 125
Control Motorized Motorized Motorized Motorized
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)
Lbs/Hr,(KwInput) 4-10,(3.4) 4-15,(5.1) 4-15,(5.1) 4-15,(5.1)
StdControl Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch Pulleys
Horsepower 3/4Hp 1-1/2Hp 2Hp 3Hp
[email protected]. 1,[email protected]" 3,[email protected]" 3,[email protected]" 4,[email protected]"
DriveMethod BeltDriven BeltDriven BeltDriven BeltDriven
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/FaceArea(Ft2) 3/4.1 4/6.7 4/6.7 4/10.0
Filters - 1" deep throwaway
NominalSize(in.),(Qty.) 16x20,(2) 20x20,(2) 20x20,(2) 24x24,(2)
Connection Sizes - Copper, (Please refer to CeilAiR IOM Manual for proper interconnecting refrigerant line sizing.)
Refrigerant:
SuctionLine,(Qty.) 3/4"OD,(2) 7/8"OD,(2) 7/8"OD,(2) 7/8"OD,(2)
LiquidLine,(Qty.) 3/8"OD,(2) 1/2"OD,(2) 1/2"OD,(2) 1/2"OD,(2)
CondensateDrain,(w/In-PanPump) 3/4"FPT,(1/2"OD) 3/4"FPT,(1/2"OD) 3/4"FPT,(1/2"OD) 3/4"FPT,(1/2"OD)
HumidifierInlet 1/4"OD 1/4"OD 1/4"OD 1/4"OD
Physical Size - (Please refer to Section 6 for detailed dimensional data.)
Approx.Weight 320lbs 350lbs 410lbs 480lbs
Perform
ance D
ata - Air C
oo
led D
AH
U/D
RC
U (4-10 To
n, D
UA
L Co
mp
ressor)
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Please refer to the SATS Heat Rejection Engineering Manual for specification and performance data on Remote Outdoor and Indoor Air Cooled Condensing Units
4-7
Perform
ance D
ata - Water C
oo
led (1 to
5 Ton
Systems)
Water Cooled - 1 to 5 Ton "OHS"OHS Model ( )-012-W ( )-018-W ( )-024-W ( )-032-W ( )-040-W ( )-048-W ( )-060-WNET DX COOLING CAPACITY - BTU/H, (includes standard DX evaporator motor heat @ std CFM & e.s.p. ratings)
80FDB/67FWB, 50% RH
Total 16,394 21,125 27,990 35,550 39,115 64,250 70,665
Sensible 11,675 16,000 20,455 24,575 29,500 49,240 54,100
75FDB/62.5FWB, 50% RH
Total 14,850 19,345 25,750 32,700 35,830 58,820 64,690
Sensible 11,340 15,625 20,100 24,265 28,800 48,580 53,445
72FDB/60FWB, 50% RH
Total 14,000 18,380 24,560 31,150 34,109 56,070 61,650
Sensible 11,050 16,400 19,680 23,775 28,093 47,600 52,345
80FDB/65FWB, 45% RH
Total 15,570 20,430 26,840 34,170 37,355 61,635 67,730
Sensible 12,440 17,645 21,825 26,300 31,600 53,560 58,955
75FDB/61FWB, 45% RH
Total 14,380 18,950 24,920 31,600 35,120 57,130 62,760
Sensible 12,250 17,040 21,075 25,360 30,560 51,780 56,975
72FDB/58.5FWB, 45% RH
Total 13,620 18,065 23,685 30,060 33,460 54,460 59,795
Sensible 12,010 16,710 20,700 24,820 30,470 50,820 55,910
Reheat/Heat - Performance Capacities Include Motor Heat, (Optional)
ELECTRIC REHEAT / HEAT - BTU/H (Kw)
@208V 17,135(5.0) 17,135(5.0) 17,135(5.0) 17,425(5.1) 17,955(5.3) 37,350(10.9) 38,900(11.4)
@230V 18,840(5.5) 18,840(5.5) 18,840(5.5) 19,130(5.6) 19,660(5.8) 43,140(12.6) 44,690(13.1)
@460V 17,355(5.1) 17,355(5.1) 17,355(5.1) 17,645(5.2) 18,175(5.3) 37,350(10.9) 38,900(11.4)
@277/480V 18,065(5.3) 18,065(5.3) 18,065(5.3) 18,355(5.4) 18,885(5.5) 38,835(11.4) 40,385(11.8)
HOT GAS REHEAT
BTU/H 12,440 17,690 22,150 27,045 32,425 51,010 56,120
HOT WATER REHEAT / HEAT - Reheat rated @ 180F Entering Water Temperature, EAT = 72F DB
BTU/H 20,690 32,420 34,880 50,360 55,320 97,140 111,220
GPM 1 2 2 3 3 4 5
PressureDrop,ft.wg 0.1 0.3 0.3 0.3 0.3 0.4 0.6
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
STEAM REHEAT / HEAT - nominally Reheat rated @ 5 psig Steam, EAT = 72F DB
BTU/H(nominal) 12,000 18,000 24,000 32,000 40,000 48,000 60,000
Condensate(lb/hr) 13 19 25 34 42 50 63
Control Motorized Motorized Motorized Motorized Motorized Motorized Motorized
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Optional)
Lbs/Hr,(KwInput) 2-5,(1.7) 2-5,(1.7) 2-5,(1.7) 2-5,(1.7) 2-5,(1.7) 4-10,(3.4) 4-10,(3.4)
StdControl Cycling Cycling Cycling Cycling Cycling Cycling Cycling
Evaporator Blower / Motor - DWDI Centrifugal
Horsepower 1/4Hp 1/4Hp 1/4Hp 1/3Hp 1/2Hp 1Hp 1-1/2Hp
[email protected]. [email protected]" [email protected]" [email protected]" 1,[email protected]" 1,[email protected]" 2,[email protected]" 2,[email protected]"
Std.DriveMethod DirectDriven DirectDriven DirectDriven DirectDriven DirectDriven BeltDriven BeltDriven
Opt.DriveMethod Belt-Driven Belt-Driven Belt-Driven Belt-Driven Belt-Driven N/A N/A
Evaporator Coil - Aluminum Fin, Copper Tube
Rows/FaceArea(Ft2) 3/2.1 3/2.1 3/2.1 3/2.8 3/2.8 4/5.0 4/5.0
Compressor - Heat pump duty rated, HCFC Ozone Safe R-22
Type,(Qty.) Recip.,(1) Scroll,(1) Scroll,(1) Scroll,(1) Scroll,(1) Scroll,(1) Scroll,(1)
WattsInput 1,245 1,239 1,633 2,118 2,222 3,451 3,867
Water Cooled Condenser Data - Based on 0% glycol solution
TotHeatofReject. 18,900Btu/h 24,350Btu/h 32,145Btu/h 41,325Btu/h 44,865Btu/h 70,600Btu/h 77,890Btu/h
GPM@85FEWT 3.8GPM 4.9GPM 6.4GPM 8.3GPM 9.0GPM 14.1GPM 15.6GPM
TotalUnitPD(Ft.ofH2O) 10.0Ft. 6.5Ft. 11.0Ft. 11.7Ft. 13.9Ft. 16.5Ft. 22.7Ft.
Type Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial Coaxial
Head Pressure Control
StandardControl-2-way,150psigWaterRegulatingValve,(