40
1. DISTRIBUTION SYSTEM a) Gravity system b) Pumping system c) Combination of gravity and pump system 2. PIPING MATERIAL a) Selection of piping material b) Advantages and disadvantages of multiple pipe material c) Selection of pipe size 3. COMPONENTS IN DISTRIBUTION SYSTEM a) Valves b) Storage reservoirs i. Storage reservoir construction ii. Main component in storage reservoir 4. NON REVENUE WATER a) Leakage factors b) Leakage procedure measurements i. Direct leakage measurements ii. Indirect leakage measurements c) Methods to control leakage d) Methods to detect leakage e) Piping design with Hazen Williams formula TOPIC 4 :WATER DISTRIBUTION SYSTEM 6 HOURS of LECTURE = 3 WEEKS COURSE OUTLINE

CC607 T4 Water Distribution System New 2

Embed Size (px)

Citation preview

1. DISTRIBUTION SYSTEMa) Gravity systemb) Pumping systemc) Combination of gravity and pump system

2. PIPING MATERIALa) Selection of piping materialb) Advantages and disadvantages of multiple pipe materialc) Selection of pipe size

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valvesb) Storage reservoirs

i. Storage reservoir constructionii. Main component in storage reservoir

4. NON REVENUE WATERa) Leakage factorsb) Leakage procedure measurements

i. Direct leakage measurementsii. Indirect leakage measurements

c) Methods to control leakaged) Methods to detect leakagee) Piping design with Hazen Williams formula

TOPIC 4 :WATER DISTRIBUTION SYSTEM

6 HOURS of LECTURE = 3 WEEKS

COURSE OUTLINE

1. DISTRIBUTION SYSTEM

A good water supply can be considered water distribution system is considered good if it comply with following requirements

i. have good water quality by meeting local needs, such as colorless, not turbid, not hard and does not contain suspended solids

ii. quantity and pressure of water supplied is adequate for all uses, including for fire prevention

iii. Non revenue water occurs at the minimum rate of 15%

iv. cheap, durable and easily maintained

TOPIC 4 :WATER DISTRIBUTION SYSTEM

1. DISTRIBUTION SYSTEMa) Gravity system

• Water is supplied from a higher place to a lower place

• Treatment plant is located at a higher ground from user

• Friction in piping can cause energy loss, i.e distance

• Energy loss eventually can cause static head

• This will make end user experience slow water from tap.

• Advantages o Reliableo Low operation costo Suitable for community at the lower

ground• Disadvantages

o Static head will cause a drop in pressure, and cause end user angry

TOPIC 4 :WATER DISTRIBUTION SYSTEM

1. DISTRIBUTION SYSTEM

b) Pump system• Used for low pressure end user• located on lower ground than end user• Water is directly pumped to delivery pipe • Advantages

o Pressure and flow of water can be adjusted for demand

• Disadvantages o water supply cut off if there is no

electricity or pump defectiveo different water flow rates cause pressure

to changeo pump operate at different speeds

according to the rate of flow, causing the pump can damage quickly

TOPIC 4 :WATER DISTRIBUTION SYSTEM

1. DISTRIBUTION SYSTEM

c) Combined gravity and pump system• Water is pumped up and stored on high

level ground in tank or reservoir • Water id distributed by gravity to end user.• Pressure head must be elevated to allow

next water flow• Advantages

o Effectiveo Low operation costo Able to supply water if pump fail or no

electricityo Need moderate and flat rate capacity

pump• Disadvantages

o Operation and maintenance pump ------ related problem

TOPIC 4 :WATER DISTRIBUTION SYSTEM

2. PIPING MATERIALa)Selection factors

i. Pressure of work and test

ii. Strength

iii. Durability

iv. Workability at site

v. Cost – capital, operation and maintenance

vi.Leakage possibility

TOPIC 4 :WATER DISTRIBUTION SYSTEM

2. PIPING MATERIALb) Advantages and disadvantages of multiple pipe material

TOPIC 4 :WATER DISTRIBUTION SYSTEM

Material Adv Disadv

Cast iron Corrosion resistantLow costMultiple joints available

Weak against impactHeavy

Ductile iron Corrosion resistantAble to strong impact

HeavyHigh cost

Asbestos cement Low costElectrolisys freeLight and easy workability

Weak against bendingeasily leak if exposed to excavatorsFragileeasily leak at the connection

steel strong against bending and tensile impactLong No leak problem

Weak to corrosionPipe Connection need to be welded

HDPE ( high density polyethylene)

FlexibleLightStrong against impactLow Internal friction

High costNeed special tool to connectNeed adjustable socket for other pipe connection

2. PIPING MATERIALc) Selection of pipe size

• For gravity system, it depend on differences in level of source and end user

• For pump system, it depend on the need of power cost

• Pipe diameter also depend on the major loss due to the friction in distribution pipe , delivery pipe and reticulation

• Minor losses caused by valves and connection usually minimum and can be can be neglected

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

i. Stop/gate valve• Use to control flowrate,

pressure and stop flow rate• Stop cock - small size (d <

100mm)• Sluice valve – big size (d >

100mm)

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

ii. Butterfly valve• Use to control flow rate• Pipe size, d > 450mm

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

iii. Scour valve• Stop valve - Use for cleaning

works scouring works• About 1/3 of the main pipe

size

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

iv. Air release valve• Single orifice type – to

release air in the pipe• Double orifice type – to

release air in the pipe and allow air into the pipe

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

v. Check valve• Semi auto valve – allow only

one way flow rate• Open when water flow• Closed when water stop flow

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

vi. Ball valve• Use to control flow level at a

certain level

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

vii. Altitude valve/one way flow (tank fill)• Provides automatic filling of

elevated tanks or reservoirs. • When the altitude control

senses a drop in level below the predetermined set point, the valve opens to fill tank.

• When the level again reaches the set point, the valve will close.

• Discharge of the tank is by a separate line.

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

viii. altitude valve / two way flow (tank fill & discharge) • Controls both the fill and

discharge cycles of a tank or reservoir.

• When valve inlet (system) pressure falls below tank head pressure, the altitude valve opens to feed the system.

• When system pressure recovers above tank head, the tank begins to refill.

• When the high level set point is reached, the valve will close.

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

ix. (a) Pressure reducing valve – pilot operating • automatically reduces the

pressure from the water supply main to a lower, more sensible pressure.

• to boost water supply pressures in supply mains to be able to supply water for fire fighting, high rise buildings to overcome loss of pressure as the elevation increases, and to maintain water supply in water towers and supply tanks

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

x. Pressure sustaining/relief valve• The valve instantly opens

when the pressure in the pipeline exceeds the preset safe level, thus relieving excessive pressure from the pipeline.

• When the pressure returns to normal, the valve closes.

• The valve also can be used to sustain upstream pressure to a preset pressure value

• Use to control pressure

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMa) Valves

xi. Constant flow valve• To provide an accurate way of

controlling flow configuration.• Use to set flow rate

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMb) Storage reservoirs

• Main functiono To provide treated water for emergency use like power

shortage, pump malfunction, fire fightingo To act as a break pressure tank o To equalize flow rate because of changing in demand

rate and supply rate

• Two typesi. Balancing tank

o To distribute water to the service tank o To provide adequate pressure and flow to the

service tanko Design must fulfill the water inlet (from

main/plant) and the water outlet (to the service tank)

o Built near water treatment plant

ii. Service tanko To supply treated water to the reticulation pipeo Normally can supply for one day use

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMb) Storage reservoirs

i. Storage reservoir construction

• Selection factors of material construction

1. Lifespan of material and its advantages2. Volume needed3. Strength of material4. Location and surrounding condition5. resistance to internal and external

corrosion and abrasion

• Materials are :1. Reinforced concrete2. Prestressed concrete3. Galvanized pressed steel4. Fibreglass reinforced plastic5. Steel fused with glass

TOPIC 4 :WATER DISTRIBUTION SYSTEM

3. COMPONENTS IN DISTRIBUTION SYSTEMb) Storage reservoirs

i. Storage reservoir construction

• Materials are :1. Reinforced concrete

• Low cost maintenance and longer lifespan• Grounded or elevated• Volume less than 13,500 m3 – round shape ( rectangle

also does)• But high construction cost • Must meet BS 5337, 1976 ( code of practice for

structural use of aqueous liquid

3. COMPONENTS IN DISTRIBUTION SYSTEMb) Storage reservoirs

i. Storage reservoir construction

• Materials are :2. Prestressed concrete

• More than 13,500m3• Grounded or elevated• Round or rectangle

3. COMPONENTS IN DISTRIBUTION SYSTEMb) Storage reservoirs

i. Storage reservoir construction

• Materials are :3. Galvanized pressed steel

• As storage tank• Fast construction• Low cost construction but high cost

maintenance• Avoid rusting surrounding such as

beach/coast• Grounded or elevated

3. COMPONENTS IN DISTRIBUTION SYSTEMb) Storage reservoirs

i. Storage reservoir construction

• Materials are :4. Fiber glass reinforced plastic

• Low cost construction• Fast and easy installation• Minimum maintenance• Light weight – can customize for order

3. COMPONENTS IN DISTRIBUTION SYSTEMb) Storage reservoirs

i. Storage reservoir construction

5. Steel fused with glass• Smooth, low friction, hard and water

tight• Minimum maintenance• Grounded or elevated• Modular size

3. COMPONENTS IN DISTRIBUTION SYSTEMb) Storage reservoirs

ii. Main component in storage reservoir

1. Inlet pipe 2. Outlet pipe3. Overflow pipe4. Scouring pipe5. Ventilator6. Manhole7. Ladder8. Water level

indicator9. Float valve

4.NON REVENUE WATER

a)Leakage factors

b)Leakage procedure measurementsi. Direct leakage measurementsii. Indirect leakage measurements

c) Methods to control leakage

d)Methods to detect leakage

e) Piping design with Hazen Williams formula

TOPIC 4 :WATER DISTRIBUTION SYSTEM

4. NON REVENUE WATER

• Definition - water that has been produced and is “lost” before it reaches the customer

• Why we have to deal with it :o Almost distribution pipes experiencing leakageo it is not worthy to install “water tight” systemo It makes cost for water treatment escalateso Minimizing NRW – not only good for companies, but less

microorganism penetration thru crack

• Methods of Reducing NRWo Control system to reduce pressure at the very beginning of

distributiono New and comprehensive water distribution systemo Specific department for NRW related problem – solvingo Strict punishment for illegal connection and water leeching

4. NON REVENUE WATERa) Leakage factors

i. Pressure• Pressure surge - main, danger, cause pipe to burst when

the pump stops or the valve closes suddenly

• pressure changes – minor , neglected

ii. Ground movement • expansion and contraction of the soil will cause metal

(pipe) fatigue

iii. Rusting in pipe from electrolysis ---process internal ( high chlorine and acidic )

---process external ( different water characteristic) _ iron and copper – volt (potential different)

iv. Soil condition• Leakage water in the soil tend to appear on the soil

surface because of capillary rise. wet soil causes the plants look and green indicating enough water even in the drought season

4. NON REVENUE WATERa) Leakage factors

v. Traffic load• Vibration will cause tiny crack to the pipe if the bedding is

not strengthened and improper depth

vi. Material and work -> poor quality• Fitting material such as valves and joints are not

suitable/poor quality• Also installation, fixing, setting up are not a good

workmanship

vii. Pipe lifespan• Depend on material property like durability,

internal/external corrosion resistant , impact load, tensile/bending due to the weak bedding

4. NON REVENUE WATERb) Leakage procedure measurements

i. Direct leakage measurements1) Leakage at water tank/reservoir

• Test to water tank valves for not leak• Using depth sensor to measure drop of in water level• 12 hours duration test• Easy to detect leaking• Small and neglected.

2) Leakage at main/delivery pipe.• For each pipeline (vessel), end to end valves are

closed.• Leaking = Final reading (water out) – early reading

(water in)• Sometimes, slightly significant leak and need fixing

3) Leakage at distribution pipe• This is significant leak and need to be concerned• Measure Q night where most possible minimum flow

rate• Must be separated from other supplied area• Leaking = reading (dist. pipe) – reading (user)• Factors > piping system, meter, illegal connection……

4. NON REVENUE WATERb) Leakage procedure measurements

ii. Indirect leakage measurements

Leaking = Water in ---- water out ---

M – metered reading (billed usage)

+ U -- Under recording ( meter inaccuracies)

+D -- Domestic use such as firefighting, scouring work,

I -- Illegal > theft, unauthorized use, leeching

4. NON REVENUE WATERc) Methods to control leakage

i. Pressure control

• Used in the area ---that is have high pressure changes

• Small reducing pressure will reduce leakage significantly

• But most of the old piping material like metal made, pressure reducing will could become a problem due to the internal pipe crusting.

• Typical method used are: Pressure reducing valves Reducing pumping head Pressure break tank

4. NON REVENUE WATERc) Methods to control leakage

ii. Passive control• Leakage will be fixed based on report from concerned

community• Fixing based on complaint/report• Sometime considering the new piping in old area

iii. Listening

4. NON REVENUE WATERc) Methods to control leakage

iv. Waste and combined metering • A waste meter measures the total flow into a waste area by

isolating the area into a few area. And it is called waste meter area, WMA.

• The waste meter area is valved in for the test so that it is only supplied by the waste meter.

• In district metering, a single DMA may be divided into several WMA, sometimes using the same meter revalved into different areas.

• Waste meters are used specifically to record the minimum night flow rate, this measurement being used to judge whether there is significant level of leakage by comparison with previous readings.

• Alternatively, when used with district metering, they are run

only when the district meters indicate a significant level of leak.

• If it is judged that action is required, waste meters can be used to perform further tests to locate the leakage within a still smaller area

4. NON REVENUE WATERd) Methods to detect leakage

i. Visual inspection – using clues to detect leak like• Wet soil surface• Green grass when drought season• There is a clean water flow into drain – detect using

chlorine test

ii. Sounding• Same as listening

4. NON REVENUE WATERd) Methods to detect leakage

iii. Leak noise conductor• More efficient/accurate in iron pipe, not

plastic• Measuring at two suspected point by

vibration/sound• Vibration are transmitted from sensor to the

conductors

4. NON REVENUE WATERd) Methods to detect leakage

iv. Tracer gas – a portable gas sensor is used to detect nontoxic gas as it escaped thru leaks in pipe and rises thru the surrounding soil to the ground surface

4. NON REVENUE WATERe) Piping design with Hazen Williams formula

Factors affecting the design• Flow velocity - normal 2.5 m/s, in pump station must

below 1.2 m/s to cope cavitations problem• Peak demand - because of difference in hourly

demand• Fire fighting flow• Recommended pressure residue - to balance the

demand and supply• Minimum diameter - 150mm for housing area

Easy to use for pressured pipe because of simple calculation

only use scientific calculator and need no graph chart However, it has range of accuracy because limitation

factor Not suitable in diameter less than 50mm and velocity 3

m/s