Fault Analysis and Removal
EATS1 - 63 - A / P
Pole:3P 4P
Circuit Breaker Rated Current
Design Number
Fame Grading
Shanghai EBASEE Electric Co., Ltd.
CB class MIN CIRCUIT BREAKER SERIES A.T.S
260316
112
145
Indicate status
AUTO MANU
Total height: 123mm
NA NB NC NN
A
BCN
ATSF1N3F2
RA RB RC RN
F1
N3
F2
XF1
XF2
CO
M
NC
NO
NA NB NC NN
ABCN
EATS1 type ATS
RA RB RC RN
AC220V0.15A
CB class EATS1Series Dual-power Automatic Transfer Switch
CB class EATS1Series Dual-power Automatic Transfer Switch
Products feature and characterEATS1 Series intelligent dual power automatic swithes is made up of two units in 3 pole and 4 pole ofMCCB and (auxiliary contacl,alarm contact),the mechani cal interlo cking transmission,intelligent controllerand other components. It has the integral style and split type with two kinds mechanism. Integral controlleris equipped with a base and executing agencies ; Split type is intelligent controll er installe d in the panemUser take the base by implementing agencies to install into the cabinet controller with about 2m cables.
Reliable mechanical interlock between the two circuit breakers and electrical in terlock dev ice .Eelimin-ate the two devices closing completely at the same time.SCM intelligent controller used to control the core hardware is simple and powerful, expansion of conv-enience, high reliability.It has a short circuit, over load protection functions, over voltage,under voltage, loss phase automatictransfer function andintelligent alarm function.Automatic switching external parameters can be set free.Operation of Intelligent motor protectionThe control circuit devices with fire, fire control cente r to a cont rol signal into intell igent controller. Twosets circuit breaker will enter a stating of breaking .There is a computer network interface for achieving remote control four remote telemetry functions
The feature and character of EATS1 series ATS
EATS1 series ( terminal type ) (economic type ) - Automatic Transfer Switches, is used to the terminals tothe dual electrical power switching devices;Small in volume,simple in constitution;There is provide 2P,3P,4P.Easy to operation and long to use;Transfer switch driving by single motor, a smooth, no noise, the impact is small;With mechanical interlocking and electrical interlock , change over credibility , could be supply by man-ual or automatic operation;Common, spare circuit breaker rated current can be different;A.T.S contain connector for users wiring can rdflect Breaker (open or closed) state;A.T.S panel show various instructions: separations instruction manual, automatic and wiring diagramand so on.
Model and Meaning
EATS1- 63X, EATS1- 63Yautomatic transfer switch Overall and installation dimensions
EATS1-63X, EATS1-63Yseries wiring diagram
Loadoutput
main power
main power closed transitioninstruction (AC220V150mA)
standby power closed transitioninstruction(AC220V150mA)
start the generatorFire Signalno power
inputno power
output
Standby power
main power
Loadoutput
Standby power
stan
dby
pow
ercl
osed
trans
ition
inst
ruct
ion
Mai
npo
wer
clos
edtra
nsiti
onin
stru
ctio
n
Note: this wiring diagram is only fit for 4 pole ATS, when choose 3 pole ATS, zero line of Main power (NN) must be connected to the 3 pole zero line terminal.
Use of Operates and supportsWhether main power or backup power with voltage or not, all can be by manual mode ope rated.Undermanual,put the auto- manual but ton to manu al position, pull the handle by clockwise to end,Backuppower implementation circuit breaker Qr i s OFF, implementation of MAIN power supply circuit breakerQn ONg; When pull handle counterclockwise to the end, the implementation of Backup power sourceQr is ON,implementation of MAIN power supply circuit breaker Qn is OFF;Set the auto position, if the MAIN power is normally,ATS will transfer to MAIN power working.The MAINPOWER indiacation will bright on panel;If the MAIN power is unusually,ATS will t ransfer to Backup Powerworking.The Backup indication will be bright on the panel.ATS has 1A of two units fuses and a elec tric connector, fuse as short-circuit protection in automaticcontroller.Electric connecto as dry contact in In dication light to panel of controller box,v oltage of 220VAC, l50mA , the detail please reference to instruction.
When ATS under automatic control state,the POWER condition was changed,but the operation mecha-nism no action. Such as MCB can't closed-transition or open - transition then should be checked:1.whether the power grid are failured;2.whether the wiring shedding;3.the fuse itself whether burning. If the front point of one circuit breaker with ele ctricity, and th e conne- ction are botht wiring well, fuses are intact, but yet can not closed-transition or open-transition.You should be asked to professionals or contact manufactory.
Notice to users in ordersWhen User place the order need to notice the identifying device model s, spe cifica tions, dis pensedbreaker models, speci fications, pole number. Such as : Automatic Transfer Switch device, Self-inputandSelf-recovertype, rated current of 50 A,4 pole, which is written EATS1-63L/4P (50A).For users special requirements, please contact with factories and to explain well in orders indicate.
EATS1-63X
Connecting
terminal
Fire control portGenerator port Exterior indication port
EATS1-63X wiring diagram
EATS1-63Y wiring diagram
Power supply Main power ON Backup power ON
DUAL-BREAK
EATS1-63(Economic type)
112
165
285260
Connectterminal
Standby powerneutral line(NR)
Normal powerneutral line(NN)
³ £ Ó Ã µ ç Ô ´
N R
± ¸ Ó Ã µ ç Ô ´
1 2 3
N on R on Power
N-Fuse-R
AUTO
EATS1-63/ PStandard IEC60947-6-1 GB/T14048.11 Rated Frequency 50HzRated Working Voltage 400V/230V Rated current ANumber of out factory Date
Normalpower
OFFON
N R
Total height 120mm
Main power
Type: YEQ1-63 N/4 PStandard: GB/T14048.11-2002Rated current: 50ARated voltage: AC400V50/60HzCerious No .
CCC
N2
UR
ON
N1
UN RUNRUN
ON
N4N3
NON
O
R ON
170
320
125352
210
4- 6
EATS1-63N
EATS1-63L307
325
85 110
14115
Status indication
R N ON R ON PowerN
EATS1 63L/ PStandard IEC60947-6-1 GB/T14048.11 Rated Frequency 50HzRated voltage 400V/230V Rated current A
4- 7
3P
4P380V
6, 10, 16, 20, 25, 32, 40, 50, 63
50/60 220V 1.5 3S 10000
Rated CurrentIn(A)AC
Frequency(Hz)
Control voltage(V)
Transfer time Mechanical life (times)
F1
N3
F2
AC220VAC220V
Un- -main power
Qn- -main circuit breaker
Qn Qr
Un Ur
Qn Qr
Un Ur
1
4
2
5
3
6
AC220V
AC220V
QnQrN
AC220V
Qn Qr
Un Ur
EATS1-63 (Economic type) wiring diagram by users
EATS1-63N wiring diagram by users
EATS1-63L wiring diagram by users
4- 7
CB class EATS1Series Dual-power Automatic Transfer Switch
CB class EATS1Series Dual-power Automatic Transfer Switch
[EATS1-63](Economic Type) A.T.S
[EATS1-63](Terminal Type) A.T.S
[EATS1-63L] A.T.S
[EATS1] Technical Parameter of EATS1 tye A.T.s
Poles Rated voltageUe(V)AC
Working principleWhen common source is n ormal, the functional key is at position "auto", reserve breaker is open andcommon breaker is closed to protect common source for connecting with load,the common power voltageindicator is light.When the common source failures (the voltage is lower than 60% of rated voltage), thecommon source will transfer to reserve source automatically, the reserved source voltage indicator is ON,the reserved source working indicator is ON. After removing the failure of the common source,this swi tchwill transfer to the common source automatically again.
EATS1 Series ATS wiring diagram
Ur- -standby power
Qr- -standby circuit breaker
Controller
Shunt switch
main power closed transition instruction
standby power closed transition instruction
main power instruction
standby power instructionController
Un- -main power
Qn- -main circuit breaker
Ur- -standby power
Qr- -standby circuit breaker
main power instruction
standby power instruction
Shunt switch
Un- -main power
Qn- -main circuit breaker
Ur- -standby power
Qr- -standby circuit breaker
Controller
main power closed transition instruction
standby power closed transition instruction
Shunt switch
Note: Use correct wire size for input elec tric connector of 2 units MCB well.Putting into the line-phase seq- uence to be unanimous. Three phase MCB add the neutral to be used to swich nuetral N as well.
Connectterminal
Normalinsurance
Standbyinsurance
MANUAL
Status IndicatorDual-power
Automatic Transfer Switch
Reservepower
CQC
Backup power
Dual-power Automatic Transfer SwitchOFF
Auto Manual
Dual-power Automatic Transfer Switch
Main power Backup powerONOFF
Auto Manual Fuse
S
A039101
EATS 2 C D 100 - 63 / 3 R
R=Auto transfer and auto retransfer (network..network)
S=Auto transfer and non-auto retransfer (network..network)
F=netork..generator
Poles:2P,3P,4P
Circuit breaker rated interruption current
Frame class
Chosen controller
A: (Standard type) only supplied with self transfer/retransfer
(for integral type ATS)
B: (Intelligent type) display source voltages, starts generators,
fire protection actuation (for integral type ATS)
C: (Intelligent type) same functions as type B controller, (for split
type ATS)
D: (Intelligent type) same function as type B controller, with liquid
crystal Chinese language display (for split type ATS)
Circuit breaker type:
C--Chinese make circuit breaker (CM1, C45)
N--Schneider make circuit breaker (NS, C65)
P--ABB make circuit breaker
Design No .
1--mini circuit breaker
2--Moulded case circuit breaker
Shanghai EBASEE Electric Co., Ltd.
CB class ATS EATS1 -1250CB
EATS1 CB EATS1 PB
EATS1 NBEATS1 CB
C type controller D type controller
CB class EATS1Series Dual-power Automatic Transfer Switch
CB class EATS1Series Dual-power Automatic Transfer Switch
General introductionEATS1 series automatic transfer switch is the best development of the company generation products.Mostly used to monitor the power supply circuits. When main power failured,it will change over to backuppower by automatically,thus completing the transformation of power system . At present, in particularsuited for the important electricity power places where disallow to failure, in order to meet the needs ofthe scene.Automatic switch has self-input and self-recover,self-input without self-recover, utility to utility,utility-generators work with a variety functions,the product applied in 220V,AC 50Hz,rated cu rrent from10A to 1250A (CB class) automatically switch products.
Structure and features
EATS1 Series intelligent dual power automatic swit hes is made up of two units in 3 pol e and 4 pole ofMCCB and(auxiliary contacl,alarm contact),the mechanical interlocking transmissi on,intellige nt contro llerand other components. It has the integral style and split type with two kinds mechanism. Integral controlleris equipped with a base and executing agencies ; Split type is intelligent control ler install ed in the p anemUser take the base by implementing agencies to install into the cabinet controller with about 2m cables.
Reliable mechanical in terlock between the two circuit breakers and electrical interlock device. Eeliminatethe two devices closing completely at the same time.SCM intelligent controller used to control the core hardware is simple and powerful, expansion of conv-enience, high reliability.It has a short circuit, over load protection functions, over voltage,under voltage, loss phase automatictransfer function andintelligent alarm function.Automatic switching external parameters can be set free.Operation of Intelligent motor protectionThe control circuit devices with fire, fire control center to a control signal into intelligent controller. Twosets circuit breaker will enter a stating of breaking .There is a computer network interface for achieving remote control four remote telemetry functions
Product Model and Meaning
Beauty in appearance, reliable in quality, long life and easy in operation
EATS1 CA
EATS1CB
CB class EATS1Series Dual-power Automatic Transfer Switch
CB class EATS1Series Dual-power Automatic Transfer Switch
A new intelligent modular design
Implement varioustypes of devices tobe choose , the ins-tallation reasonable,convenient replace-ment
Enclosed manual handle, convenient alternative byautomatic manual control
Basefloor
Provide a variety of functionsas a controller,you could ch-oose to meet the needs ofdifferent occasions
Function of the controller
A type controller
A controller (basic type) and switch body ins tall together, as per working vo ltage are normally or not decide
how to work conversion
A type controller
Function
Alternative work by automatic and manual operation;
Monitoring the two sources,whether is loss phase, under voltage, loss voltage and such abnormal conditions,
the indication show whether in located normal voltage;
Conversion type is Self-input and self-recover;
Electric Performance
Rated working voltage: AC220V / 50Hz;
Transfer delay time: 0.5s;
B type controllerB type controller adopting microprocessor programmed control; linking with switches body together
cleverly, easy to operate ,function is powerful, and increased C controller and D type LCD display fission
controller on the basis of the B model controller .
B type controller
Function
Accurately shows two ways three phase voltage, frequency and switch state capacity in two sources;
Allow user allows to monitor the scene,the control center to amend the parameter of working status and
transfer delay time;
Set arbitrarily self-input and self-revover self-input without self-recover, utility-generator models
Fire Alarm linkage- conversion to 0;
Manual and automatic conversion mode alternative function;
Under the utility-generator model with a send off signal to generator;
Conversion and delay time can be set arbitrarily;
With a strong anti-jamming capability, suitable for the strong electromagnetic interference using in a compl-
exa environment
Electric PerformanceWorking voltage: AC220V / 50Hz;
Transfer delay time: 0.5s-90s continuous adjustabled;
Return delay time: 0.5s-90s continuous adjustabled;
Lack voltage transfer value:145V-210V continuous adjustabled;
Over voltage transfer value:230V-300V continuous adjustabled
Transfer time: not more than 4s
MOULDED CASE CIRCUIT BREAKER
Rated working voltage
Rated insulating voltage
Rated Frequency
Rated current
Current Instant-trip
Rated temp
Short-circuitBreaking Capacity
Icu/Ics(kA)Ratedshort
-circuit level
L
M
H
AC400V AC690V
35/22
50/35
85/50
20/10
Date:2010-9
Standard
C
D
EATS1CC
EATS1CD
TestWork
Automatic transfer switch
YEQ2 - /
GB/T14048.11-2002
Date
ClassCB
Ie A
UeAC400V 5060Hz
IEC 60947-6-1
L1
L2
L3
V
SNormal Emergency
OFFON
ATS Control Module
AUTOMANUAL
Hz
ON
AutoTest
Manual
ATS switch body dimensions
EATS1C- 63
EATS1N- 63
EATS1P- 63
EATS2C- 63
EATS2C- 100
EATS2C- 225
EATS2C- 400
EATS2C- 630
EATS2C- 800
EATS2C- 1250
EATS2N- 250
EATS2N- 630
EATS2P- 125
EATS2P- 160
285
285
285
305
335
365
491
524
580
580
355
497
305
335
320
320
320
355
395
435
587
640
720
720
425
587
355
395
245
245
245
265
295
325
431
464
520
520
315
437
265
295
280
280
280
315
355
395
527
580
660
660
385
527
315
355
255
255
255
255
255
255
330
330
340
415
255
355
255
255
230
230
230
230
230
230
300
300
310
385
230
325
230
230
141
141
141
141
141
155
215
215
215
290
148
215
155
155
HA
B
DCO
ON
A B C NNormal
A B C NEmergency
Load
O
ON
Specification
Dimensions A
3P 4P
B
3P 4PC D H
8, 400A 44 10
YEQ2
CB class EATS1Series Dual-power Automatic Transfer Switch
CB class EATS1Series Dual-power Automatic Transfer Switch
C Type and D Type ControllerIf the user requiring to conducting separated controller, choosing C or D model controller install tocabinet panel, through 2m serial data cable linked. B model controller on Switch body, all operationsand display functions are all forbiding state (switch body display switches off automatically), externalcontroller starting work, users could observed the ATS control of the switch running stat us through theexternal controller to operate when they can't open the cabinet.
Adopt digital and indicator t show status,two state orads supply voltage and frequency.
Through button to choose the manual transfer mode and set parameters
C Type Controller Character and Function
Using the dot-matrix LCD screen display and show the voltage¡ ¢ frequency of two sources;
Press the key to operate by manual and set the parameters
D Type Controller Character and Function
Appearance and installation dimensionsThe appearance of ATS switch body
MOULDED CASE CIRCUIT BREAKER
Rated working voltage
Rated insulating voltage
Rated Frequency
Rated current
Current Instant-trip
Rated temp
Short-circuitBreaking Capacity
Icu/Ics(kA)Ratedshort
-circuit level
L
M
H
AC400V AC690V
35/22
50/35
85/50
20/10
Date:2010-9
Standard
Normal
ON
Emergency
ONAUTO
L1
L2
L3
V
S
Hz
AutoTest
Manual
OFF
ATS ControlM odule
MANUAL
MENU
Normal
ON
Emergency
ATS ControlM odule
ON
140
83
72
120
323
140
83
76
122
Perforation Diagram of split Type Controller
Perforation Diagram of split Type Controller
CB class EATS1Series Dual-power Automatic Transfer Switch
CB class EATS1Series Dual-power Automatic Transfer Switch