Cathodic Protection for AST’s

Presented by:

James T. Lary

Corrpro Companies, inc.

1055 West Smith Road

Medina, Ohio 44256

[email protected]

330-241-6615

Page 2: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

• Preserve Assets

• Avoid Disruption of Service

• Enhance Safety

• Prevent Leaks

• Governmental Regulations

• Reduce Maintenance

Costs

Why is Cathodic Protection Important?

Page 3: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Terminal Tankage

Main Line

M

Valve

OPS

Inspection

MeterM

No OPS

Inspection

OPS Inspection Stops

(Enforcement Policy)

Loading

TerminalProduct

Tank

(Terminal)

Product

Tank

(Terminal)

Page 4: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Breakout Tank

M

Main Line

Valve

OPS

Inspection

MeterM

Product

Tank

(Breakout)

M

Page 5: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Charleston, WV Spill

The investigation found that two small

holes ranging in size from about 0.4-inch

to 0.75-inch in the bottom of the 48,000-

gallon tank 396 were caused by corrosion,

likely resulting from water leaking through

holes in the roof and settling on the tank

floor. Furthermore, the CSB inspection

found a similar hole penetrating the

bottom of nearby tank 397, containing the

same chemical at the facility, located in

Charleston. Other tanks also showed

multiple signs of pitting and metallurgical

damage, investigators said. The growing

corrosion in these tanks went unnoticed

until the bottom of 396 was breached and

up to an estimated 10,000 gallons of

product made their way through the

underlying mixture of soil and gravel

under the facility and into the Elk River on

January 9, 2014.

Page 6: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

- Causes of Corrosion

- Cathodic Protection Applications

- Installation & Maintenance

- Rectifier Monitoring

What we will cover….

Page 7: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Early Oil Tanks & Piping

did not Employ CP

Page 8: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

IRON OXIDE REFINING MILLING

STEEL CORROSION IRON OXIDE

THE PROBLEM…..

Page 9: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Anodic Area

-600mVCathodic Area

-550mV

SAND

CURRENT FLOW

External Corrosion of

Tank Bottom

Page 10: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

MFL Floor

Inspection

Page 11: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for
Page 12: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

SANDCURRENT FLOW

Corrosion Cell Caused

by Foreign Material in

Sand Cushion

CLAY

Steel Tank Floor

Page 13: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

DRY

SAND

MOIST SAND

WATER

Corrosion Caused by

Poor Water Drainage

Page 14: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

New Bottom (Anode)

CURRENT FLOW

SAND

SAND

New Steel Coupled to Old Steel

Old Bottom (Cathode)

Page 15: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Leak detection grove

under under bottom

Tank bottom required

30% floor

replacement

after 5 years in

service

Concrete Slab

Page 16: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Types of Cathodic Protection

Galvanic: Current obtained from a metal

with a higher energy level.

Impressed Current: Requires external

power source (transformer

rectifier).

Page 17: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

System Characteristics

Galvanic Impressed

No external power External power required

Fixed driving voltage Voltage can be varied

Limited current Current can be varied

Small current requirements High current requirements

Used in lower resistivity Used in almost any

environment resistivity environment

Usually negligible Must consider interference

interference with other structures

Page 18: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Above Ground Storage Tank With Galvanic Anodes

Anodes

Tank

Anodes

Page 19: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Above Ground Storage Tank With Galvanic Anodes

Is Protection Being Achieved?

Anode

Tank

Uncoated Tank Bottom

Tank Grounded to Other

Structures

Page 20: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Test

Box

Anode

Cells

Tank

Galvanic Anodes

Page 21: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

• With the advent of secondary containment

liners for AST’s, some oil companies initially

installed galvanic (zinc or magnesium) anode

cathodic protection systems. Many of these

same companies have now abandoned this

approach due to the inability to obtain effective

levels of cathodic protection or limited system

design life.

• The industry preference for cathodic protection

for large AST’s is now impressed current.

Page 22: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Galvanic Anode Installation on AST. Note that anode life and current output are dependent upon sand / backfill conditions. Reference cells were rarely installed to monitor performance.

Galvanic

Anode

(Many galvanic systems installed by tank contractor)

Page 23: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Recommended Practices

API-651 - Cathodic Protection of Aboveground Petroleum

Storage Tanks:

“Galvanic anodes method is not practical for

protection of large bare structures.”

NACE RP0193-2001 - External Cathodic Protection of On-

Grade Carbon Steel Storage Tank Bottoms:

“Galvanic protection systems can be applied to tank

bottoms where the metallic surface area exposed to

the electrolyte can be minimized through the

application of a dielectric coating or the area is small

due to the tank size or configuration.”

Page 24: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

(+)(-)

Return

Rectifier

Anode

CURRENT FLOW

Impressed Current Cathodic Protection

Page 25: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Impressed Current

Cathodic Protection System

Anodes

Rectifier

Wiring

Page 26: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Tanks & Piping

Page 27: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Above Ground Storage Tank Vertical Impressed

Current Anodes - Existing Tanks

Sand

Anodes

Rectifier

Negative

Connection

+

-

Concrete

Ringwall

Tank

AnodesRectifier

-

+

Negative

Connection

Tank

Page 28: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for
Page 29: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Anodes

Junction

Box

Rectifier

-+

Page 30: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Deep Anode

Tank

(+)

(-)

RectifierTank

Tank Tank

Page 31: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Computer Guided Horizontally

Bored Anode System

Tank

Rectifier

(+)

(-)

Anode

Splice Box

Anode

Pipe

Monitoring

Pipe

Anode Pipe

Page 32: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for
Page 33: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

ABOVEGROUND STORAGE TANK

CATHODIC PROTECTION

3” PVC 20%

Exposure

Anode Material

Anode Tube

10’

Typical

Test/Access

Station

Grade

Aboveground

Storage Tank

Page 34: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for
Page 35: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Rectifier Units

Explosion or Non Explosion Proof ?

AC Input ?

AC Availability ?

Page 36: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

CP Applications for Re-bottomed or

New Tanks

Page 37: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

CP Installation on Rebottomed Tank

Page 38: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Above Ground

Storage Tank Bottoms

with Secondary Containment

Page 39: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Liner

Floor

AnodeConduit

CP Installation on Double Bottom Tank

Page 40: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

New Tank Construction with Liner

Page 41: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Anode

Reference

Cells

Tank

Impressed Current

Junction

Box

(-)

(+)

Rectifier

Page 42: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Anode & Reference Cell Placement

in High Resistance Sand

Page 43: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for
Page 44: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Installation of CP System on

Lifted AST

Page 45: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Cathodic Protection Survey (When Tank is Full)

Page 46: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Tank

Rim Potential Measurements

Portable Reference Cell

Soil

(+)

??

-850mV

Page 47: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Soil Access Station (Thru Liner or Asphalt)

Page 48: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Reference Cell Placement Under Tank Bottom

(Note obtain and store native readings)

Page 49: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Reference Cell Monitoring Conduit

Tank

Monitoring

Conduit

Page 50: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Cathodic Protection Monitoring

• Read rectifiers every

30 days.

• Conduct annual

inspection (obtain

potentials) by NACE

certified individuals.

Page 51: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Hot Asphalt Tank Bottoms

Page 52: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Stray Current ?

Page 53: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Pipeline Integrity Inspections

Page 54: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Qualifications

of the corrosion engineer

• Certified by N.A.C.E.

(National Association of Corrosion Engineers)

• Experienced in Cathodic Protection

• Experienced in Cathodic Protection of Fuel

Storage Systems

Page 55: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Internal Corrosion

Page 56: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Anode Cathode

Water / Sediment

Fuel Product

Internal Corrosion

Page 57: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for
Page 58: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

CoatingAnode

Bolt

Tank Bottom

Page 59: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Recommended Practices

API-651 - Cathodic Protection of Aboveground Petroleum

Storage Tanks:

NACE RP0193-2001 - External Cathodic Protection of On-

Grade Carbon Steel Tank Bottoms:

Page 60: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for

Iron Water Fire Water

Piping

Pitting (concentrated)

corrosion attack on ductile iron

pipe.

Page 61: Cathodic Protection for AST’s - AUCSC CP for ASTs _2018.pdf · levels of cathodic protection or limited system design life. •The industry preference for cathodic protection for