I M Catawba Nuclear Station Polyethylene Piping Use for Safety Related Buried Water Piping Service ATTACHMENT 2

Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

I M

Catawba Nuclear Station

Polyethylene Piping Use forSafety Related Buried

Water PipingService

ATTACHMENT 2

Page 2: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Agenda

* Meeting Purpose and Expectations* Polyethylene Piping Use by Catawba* Polyethylene Materials* Joining Polyethylene* Seismic Analysis* NDE Technique Evaluation* Relief Request* Overall Strategy for Service Water System* Questions (questions encouraged during

presentation)

Page 3: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Meeting Purpose

*Nuclear service water systems havebeen designed using codes thatspecify only metallic materials.

*Polyethylene (HDPE) material hasdemonstrated superior corrosion andfouling resistance in non safety relatedcooling water system service.

Page 4: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Meeting Purpose*Provide information on use ofPolyethylene Piping in non safetyrelated service water system atCatawba Nuclear Station

*Provide information on developmentof relief request for replacement ofsafety related piping with high densitypolyethylene (HDPE) in buried servicewater applications

Page 5: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Meeting Expectations

Information presented in the 6-27-05meeting is expected to be useful forfuture review of Duke Relief Request.

*NRC comments and questions duringthe 6-27-05 meeting will be used tofocus efforts to develop and preparethe Duke Relief Request.

Page 6: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Catawba Nuclear StationPolyethylene Pipe Use

* ', Iw-uItr

T

4

Page 7: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Catawba Nuclear Station

* Located 19 miles southwest of Charlotte, NCon the shores of Lake Wylie

* Two Unit 1208 MW Westinghouse PWR

* Main condenser cooling provided by closedloop cooling tower system

* Commercial operation in 1985 &1986respectively

Page 8: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Water Systems

* Nuclear Service Water System coonuclear safety related components.material: SAl 55, Class 1, KC 70 &plain carbon steels

ling toPiping

SAl 06 CS

* Low Pressure Service Water Systemsecondary cooling and cooling towermakeup. Piping material: A1 06 CS & AP15Lcarbon steel

* Both systems combined total approximately45,000-50,000 feet of piping

Page 9: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

LEGEND

LA s y tIE

* RC CONDENSER CIRCULATING WATER

RL CONVENTIONAL LOW PRESSURESERVICE WATER

* RN NUCLEAR SERVICE WATER ANDSTANDBY NUCLEAR SERVICE WATER

* RY EXTERIOR FIRE PROTECTIONSERVICE WATER

4

RI INtAKE'���:�ZZ7STRUITURE

.R1 WACE4TERW ') eJ[>.

0 M. ,.'.. ant: pv ... -I

PhDukae 41_VPowerB

CATAWBA NUCLEAR STATIONSERVICE WATER PROJECT

FIGURE D-1LbWG Li~ N ~RETumR N

SITE PLANFIGURE Q-1

,_ _,,._ _.,I

Page 10: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

~[Qp ertion

'ten'

Page 11: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Service Water Problems

* Potential loss of adequate cooling due toflow restrictions

* Concern for Foreign Material Exclusion(FME) from the corrosion products,sedimentation, biological growth, andclams fouling components within thesystem

* Localized through wall pitting

Page 12: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Problems Addressedby System Monitoring

* UT corrosion rate monitoring to addressstructural integrity issues

* Systems Engineers trend flows,temperatures, equipment performance,and set maintenance equipment PMfrequencies

Page 13: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Problems Addressedby System Cleaning

* In 2000, CNS cleaned and inspected over 8,000feet of Nuclear Service Water System piping.

* The primary methods used for this operationwere "Pigging" and Hydrolazing (High PressureWash) with Turbo Vacuum Trucks to remove thedebris.

* Chemical treatment was added to the safetyrelated service water system after the cleaningto help control the biological growth. Currentlymonitoring actual results of treatment

Page 14: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Polyethylene

* 1985 CNS began experimenting withPolyethylene piping materials as a replacementfor Polybutylene

* Further testing of the Polyethylene piping beganin 1991 -1 992

* The test proved conclusively that Polyethylenewas very compatible with the system designparameters and water chemistry

Page 15: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Polyethylene Piping Replacement

* After six years of actual in service application,there was no corrosion or biological materialbuildup on the inside of the pipe walls

* In 1998, the existing A-1 06 carbon steel supplyand return piping to the Unit 2 generatorhydrogen coolers was replaced with 500-600feet of 6" & 8" HDPE, SDR-1 1, polyethylenepiping

* Inspection results and performance of this pipingsince installation have been flawless (Nodegradation and no measurable fouling)

Page 16: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

, jj. I-"'ImII-p1 Ii)

A 2

F-- �-----���

F.,

A--

I - I4iF -Qd-e j

*: -

"- - .-

-a-woto

$t , __ _ _ _ _ _ _ '_ X

~~~~n~~. j '.2a>A.,.,

4j* - - **

._

Page 17: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

�N¶I

t

Page 18: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

.. . - - -1 ' . s

- - I

.Nx-11

-. . . . .

S: i - - -I. ; ,, '.- - . I .. I

,: -

,;. _

I .,-, & -,R � --. ,

bilk<..'.! I

ir. : - t T .'

j, - - -1 i

.a,. z 11k - -=

i-I

/

4a� -�

S~~ . .; X .

*, ati. -;. -- h I'

- . ., .) nS x.Ify4-'.'

Page 19: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

(I'- 7�.lpt, I

X�MA�L

w: -. -kt t , ~

C t w - r t x x

-c*�2

- a

;Ž �.. c�xI 7

4'xIt-.

Page 20: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

I*.I *1r- 7Sin ai

, -: -4s v/

.:-" * ,

I.I ~. Ia~I'.

-:L

-, i l '

1.dI-

(E. Ki e -A - 4 .

11

-

K

F'� I

I ,Hire

Page 21: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

w 7 r

*.. r.I

I1

Page 22: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

K f 1 --- ���>

=&NW'M

'. - 41.W --

;MIOW7

-, r:

Page 23: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

W- ? .I hi

I ;i hb ,_

,. .. . .

. ..

.

.

..

. .

:

, . 4. , .I: , .,

:'I - - :

X of, S ''' as.,,'w 4-" ' ''.'9F ,

.- 4'11 11 11 1'1 L1

Page 24: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Conclu USions - Non Safety RelatedService Water Piping Experience

HDPE Piping has not exhibited anycorrosion or degradation or significantfouling in over 1 0 years of service atCatawba Nuclear Station.

Page 25: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

HDPE USE by British Energy

* Coordinated efforts with British EnergySizewell B Plant to use HDPE Piping

* Monthly teleconference meetings* PE Training organized in September/2004* HDPE Piping installed by Sizewell B in

Spring 2005 in the ASME Section III Class3 emergency service water system.

Page 26: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

HDPE USE by British Energy__cKFsWTTTZ

Page 27: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

HDPE USE by British Energy

Page 28: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Polyethylene Piping Materials

ASTM Material Specifications Used:* ASTM D-3350 Standard Specification for PE

Plastic Pipe & Fittings Material* ASTM D-3035 Standard Specification for PE

Plastic Pipe based on controlled outsidediameter

* ASTM D-2837 Standard Method for ObtainingHydrostatic Design Basis for ThermoplasticPipe Material or Pressure Design Basis forThermoplastic Pipe Products

Page 29: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

HDPE Butt Fusion

«.7

Page 30: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

HDPE Butt Fusion

Joints made by trained and qualifiedoperators in accordance with a qualifiedprocedures

Essential parameters by data logger as apermanent record

Page 31: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

HDPE Butt Fusion

2 H Minimum1/2 H Maximum

2-1/2 H Maximum

_ , H

Uniform Bead Size & Shape

Bead Rolled to Pipe Surface

PE Pipe (Cross Section View)

Page 32: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

McElroy Joint Report

. Nlt, Q , .. tz.- ,, ,- Xw, T

:' I, t: raot-~

4 :Car~fyll U!¢3

t r;Uchm ,Y [-t INi'dilme ,

t:I 0 .4, _f tJ ,

r 'pof kv,-r i^A~; t"F1*>

JM: f f

f . X, -. -~' t .. i~ .t

I.,9 t, ^''i; Ip-i,,

41 $ rA

r~ t4

;^ ,~~ 414 rA ii*e. tr!4. !.r* Prqax"uttQ, 4V PA4

SlS' ti, i:,v 4i: 1'l -

'1 . rntr -A it ;vsta . r

HDPE Butt Fusion , !;f 4 r ! fl,� !a! 11 f c� ,, � � �

1 114 � .

, 1, , �,I �.

I; 1 .4�

1 � �� '. " I

Data Logger Report Datat i. rAnutw

COz-

Page 33: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

f Polyethylene Replacement Pipe, Project

Seismic Analysis

Jack SpannerEPRI NDE CenterJune 27, 2005USNRC Offices-White Flint

Page 34: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Objectives

This project will provide a seismic analysismethodology for the technical justification toaccompany the relief request and a Code Case toallow utilities to repair or replace safety relatedpiping with polyethylene

Contract deliverables.*Task 1-Develop a general methodology for buried

HDPE pipe*Task 2-Analyze a buried system at Catawba NPP

- Piping to diesel heat exchanger*Task 3-Prepare Code case for Section III/XI

Page 35: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Status

*Seismic analysis scheduled for completion byAugust 1, 2005

*Obtained HDPE and seismic performance datafrom Gas Technology Institute

*Catawba staff will also provide informationnecessary for seismic analysis-soil type, groundaccelerations, drawings, etc.

*Contractor provided analysis for buried HDPEpipe at a DOE facility

Page 36: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

,.�

-�U

-� I

-� I

Polyethylene Replacement Pipex-A Project

NDE Technique Evaluation

Jack SpannerEPRI NDE CenterJune 27, 2005USNRC Offices-White Flint

Page 37: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Objectives of EPRI PE Pipe Project

This project will develop a technical justification toaccompany a Code Case to allow utilities to repair orreplace safety related piping that has degraded, usuallydue to corrosion. It was decided to also evaluate NDEtechniques for qualifying joining procedures.

* Task 1 - Evaluate NDE techniques for HDPE joints.* Task 2-Develop and publish a technical report that

provides the technical justification for the Code case andRelief Request

* Task 3-Submit a Code case to the Code forimplementation.- Buried pipe Code case first- Above ground Code case later

Page 38: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

NDE Techniques to Evaluate

*Visual Inspection of joint and bead* Microwave Inspection-Evisive*Ultrasonic Phased Array* Ultrasonic Time of Flight Diffraction (TOFD)9 Radiography

Page 39: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Microwave Inspection atCatawba NPP

Waveguide

Evisive Manual Scanner,IA

PScanner

Page 40: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Microwave Inspection of EF Coupling JointRG&E Mockup

Evisive Microwave NDT FileSaturday, May 1, 2004 13:55:33

Right Circular Cylinder - Sample Rate (Hz): 240

Ca)

-a

N. 03 0315

~0406 3039

3432 0127

3 4022- 02

3302 02 1

030097335 W ires30 43 0 0473

03424 0 05243

033334 0 04348

_003302

32940 0

3282 -0-449Pipe End0327337 01633

032507 .02926

02407 4 04022

0323404 005237

02109

3 1307 31187 5 -N nonFusb

End

on

Nameplates

Wires

Coupler EndCircumference

C D3

Page 41: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Phased Array UT of EFCoupling Joint

i* Assumed Signals in Linear Array Ultrasonic Inspection for PE Coupler Joining

UltrasonicArray Sensor \

K'-00- \A/irga

End Cold _ 1,Zone

Coupler Wall

Pipe Wall oPipe

Electro-Fusion JInterface Z Center Cold

C(C*

Page 42: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Time of Flight Diffraction (TOFD) UTTechnique-Cold fusion in butt joint

* Stage 3 - correlation UT-TOFD vs.destructive examination* Lab test spools. Field welds

Field Sample &Scan"

* Results* Strong positive

correlation ofNDE indicationsto actual flaws

FLUOR.

coS5

Page 43: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Status

*Evaluating NDE techniques* RG&E, Duke and EPRI mockups* Microwave system interfaced with UT pipe scanner

and used at Catawba and on mockups* Ultrasonic time of flight demonstrations in progress* Tried phosphor plate RT techniques-not successful

- NE Gas Assoc. had better success

*Collaborating with others like British Energy(Sizewell), NorthEast Gas Assoc., RG&E,etc.

Page 44: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Relief Request - Scope

* Catawba Nuclear Service Water System -Buried Piping (ASME Section Ill

* Buried Supply Piping to the heatClass 3)

exchangers that reject heat for the mainemergency diesel generators

* Existing 10 inch Carbon Steel NPS Pipingto be replaced with HDPE

* Approximately 1700 feet of piping forCatawba Units 1 and 2

Page 45: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Relief Request - Development

* EPRI Project for code case development beganin 2004.

* Code case concept introduced at ASME SectionXl Committee in February, 2004.

* Code case and relief request work complimentone another.

* Duke Power made decision to pursue reliefrequest since piping replacement will berequired before code case is approved.

* Target date to submit relief request is2Fall, 20052

Page 46: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Relief Request - Development

* Relief Request will address:DesignInstallationI nspectionTestingProcurement

Page 47: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Service Water PipingRefurbishment Plan

NSW Plan (2006-2010)

* Replace portions of auxiliary building piping* Install NSW pump house header crossover* Install NSW auxiliary building header crossover* Replace EDG cooling supply headers* Remove selective cooling loads from NSW* Move isolation valves to reduce lake water

exposure* Submit LAR for single header operation

12

Page 48: Catawba Nuclear StationMeeting Purpose *Provide information on use of Polyethylene Piping in non safety related service water system at Catawba Nuclear Station *Provide information

Contacts:

Larry Rudy, Regulatory Compliance, [email protected], 803-831-3084Steve Lefler Engineering, [email protected], 704 382 0138Ernie McElroy, Engineering, ewmcelro~duke-enerqv.com, 803 831 4174Dave Ward, Engineering, [email protected]' 803 831 4190Mel Arey Engineering, miareyl @duke-energy.com, 704 382 8619Joel Reeves CNS Service Water Project, [email protected], 803 831 3835Terry Edwards CNS Service Water Project, [email protected] 803 831 4153Jack Spanner (EPRI), [email protected], 704 547 6065