Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201026
Indicating and measuring equipment
Short-circuit/earth-faultindicators (option)
All ring-main feeders can beoptionally equipped with a 3-phaseshort-circuit or earth-fault indicator.
Characteristics
Use depends on network conditions
Optical signal when a preselectedpickup value is exceeded
Depending on the type, reset Manually Automatically after a preset time
(e.g. 2 hours)
With ring-type sensors
Display panel, withdrawable housing,depending on the type
Response values settable(depending on the type of device)
Options:Remote electrical indication viacontact (1 NO + 1 NC) dependingon the type of device settable aspassing contact (W) or maintainedcontact (D).
Short-circuit indicator ALPHA M Short-circuit indicator ALPHA E
Short-circuit /earth-fault indicator EKA-3
R-HA
40-0
96ep
s
R-HA
40-0
97ep
s
R-HA
40-0
98ep
s
R-HA
40-0
95ep
s Red indication:Short-circuit indicatorhas picked up
Selection of short-circuit and earth-fault indicators
Indicator type 1) Reset
Ma- Automaticalnual after
Remote reset:A:by aux. voltageB:via NO contact(floating)
Automatical resetafter return ofpower supply
Response values
Short-circuit currentIK (A)Standard, othervalues on request
Response values
Earth-fault currentIE (A)Standard, othervalues on request
Opt.: Remote indicat. as
W (passing contact= standard)
D (maintained contact= option)
Short-circuit indicator
ALPHA M 5) x 400, 600, 800, 1000 W, D
ALPHA E 5) x 2 h or 4 h A (12-60 V AC/DC) 400, 600, 800, 1000 W, D
GAMMA 5.0 2)5) x 4 s after returnof power supply
2 h or 4 h
x (230 V AC, 50 Hz) 400, 600, 800, 1000 W, D
ALPHA automatic 5)
x 3 h A (12-60 V AC/DC) self-adjusting,change of current with150 A w D i w 300 A,response time: t w 20 ms
W, D
KA-Opto F 3) 5)with 3 LEDindications
x after 2 h or 4 h B (1NO) 400, 600, 800, 1000 W, D
IKI-10 V2 SP 6) x after 2 h or 4 h B (1NO) 400, 600, 800, 1000 W, D
IKI-10 V2 L 6) x after 2 h or 4 h B (1NO) x (110-230 V AC, 50/60 Hz) 400, 600, 800, 1000 W, D
Earth-fault/short-circuit indicator
EKA-3 4) 5) x (230 V AC, 50 Hz) 450 40, 80, 160 W, D
DELTA M 5) x 400, 600, 800, 1000 200 W, D
DELTA E 5) x after 2 h or 4 h A (12-60 V AC/DC) 400, 600, 800, 1000 200 W, D
KA-Opto F+E 5) x after 2 h or 4 h B (1NO) 400, 600, 800, 1000 40, 60, 80 W, D
IKI-10 V2 SP/ES 6) 7) x after 2 h or 4 h B (1NO) 400, 600, 800, 1000 10% or 25% of IK W, D
IKI-10 V2 L/ES 6) 7) x after 2 h or 4 h B (1NO) x (110-230 V AC, 50/60 Hz) 400, 600, 800, 1000 10% or 25% of IK W, D
Earth-fault indicator
EKA-3/1 4) 5) x (230 V AC, 50 Hz) 40, 80, 160 W, D
IKI-10 V2 L/ES 6) 7) x after 2 h or 4 h B (1NO) x (110-230 V AC, 50/60 Hz) 30, 55, 80, 100 W, D
Short-circuit/earth-fault indicators(examples)
Earth-fault indicator EKA-3/1
R-HA
40-0
94a
eps
Short-circuit indicator IKI-10 V2 SPR-
HA40
-100
eps
R-HA
40-0
99ep
s
Short-circuit indicator Opto F
1) Further types and other makesavailable on request
2) External auxiliary voltage required(120 V AC or 240 V AC)
3) Power supply required for the LED indications(indication by means of an integrated batteryor 12 V AC to 60 V AC voltage)
4) External auxiliary voltage required(230 V AC, 50 Hz), device with integrated battery
5) Make: Horstmann
6) Make: Kries Energietechnik
7) Ring-type sensor: d = 110 mm
Components
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 27
Ready-for-service indicator
Characteristics
Self-monitoring; easy to read
Independent of temperatureand pressure variations
Independent of site altitude
Only responds to changes ingas density
Option: Alarm switch1 NO contact for remoteelectrical indication
Mode of operation
For the ready-for-service indica-tor, a gas-tight measurementbox is installed on the inside ofthe switchgear vessel.
A coupling magnet, which isfitted to the bottom end of themeasurement box, transmitsits position to an outside arma-ture through the stainless steelswitchgear vessel. This arma-ture moves the ready-for-ser-vice indicator of the switchgear.
While changes in the gasdensity during the loss of gas,which are decisive for theinsulating capacity, are dis-played, temperature-depen-dent changes in the gaspressure are not. The gas inthe measurement box has thesame temperature as that inthe switchgear.
The temperature effect iscompensated via the samepressure change in both gasvolumes.
Verification of correctterminal-phase connections
Possible by means of aphase comparison test unit(can be ordered separately)
Safe-to-touch handling of thephase comparison test unit byinserting it into the capacitivetaps (socket pairs) of theswitchgear or the feeders.
3 Measurement box
4 Magnetic coupling5 Red indication:
Not ready for service6 Green indication:
Ready for service
Principle of operationof gas monitoringwith ready-for-service indicator
Stainless-steel vesselfilled with SF6 gas,gauge pressure500 hPa at 20 C
Ready-for-serviceindicator
Ready-for-service indicator
Gas monitoring
Indicating and measuring equipment
Phase comparison test units
R-HA
40-0
59ep
s
Make: Pfisterer, type EPV For plug-in voltage detection systems For integrated voltage detection systems
(CAPDIS-S1+, -S2+)
R-HA
40-0
89ep
s
Make: Horstmann, type ORION 3.0combined test unit for Phase comparison Interface testing at switchgear Voltage detection for
HR and LRM systems andCAPDIS-S1+, -S2+
R-HA
35-1
24ep
s
Make: Kries, type CAP-Phaseas combined test unit (HR and LRM)for: Voltage detection Repeat test Phase comparison Phase sequence test Self-testThe unit doesnt require any battery
or other makes
R-HA
41-1
14ep
s
Control board of a ring-main panel (example)
1
Indicator on control board:Ready for service
1 Ready-for-serviceindicator (option)
2 Indicator green:Ready for service(indicator red:Not ready forservice)
R-HA
41-1
13ep
s
2
Components
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201028
Interlocking systems and locking devices
Interlocking of connectioncompartment
Ring-main andcircuit-breaker panel
Access to the cable con-nection compartment(e.g. for cable testing) isonly possible providedthat the feeder is isolatedand earthed (three-posi-tion switch-disconnectorin EARTHED position)
Option: Closing lock-outThis prevents the three-position switch-discon-nector from beingswitched from OPEN toCLOSED position,when the cable compart-ment cover is removed
Transformer panel
Access to the cable con-nection compartment andto the HV HRC fuse com-partment (e.g. for replace-ment of HV HRC fuselinks) is only possible pro-vided that the feeder isisolated and earthed(three-position switch-disconnector inEARTHED position)
Option: De-earthinglock-outThis prevents thethree-position switch-disconnector from beingswitched from positionEARTHED to OPEN.
Switchgear interlocking
Dependent on the va-cuum circuit-breaker oper-ating mechanism with
Spring-operated or Stored-energy mechanism
Option: Switchgear-sidemechanical interlockingwith three-positionswitch-disconnector
Vacuum circuit-breakercannot be closed whenthree-position switch-disconnector is in theOPEN position:
Spring-operated mecha-nism: Hand crank openingis blocked
Stored-energy mechanismwith closing solenoid3AY15 10: Pushbutton(S12) operated by mecha-nical interlock preventscontinuous command toclosing solenoid
Interlocking in circuit-breaker panel types LS1,LS1-U and LT10 (with 3AH5fixed-mounted vacuumcircuit-breaker)
Option: Logical mechanicalinterlocking with three-po-sition switch-disconnector
Earthing of feeder viathree-position switch-disconnector inEARTHED position
Interlocking in circuit-breaker panels (with 3AH6removable vacuum circuit-breaker)
Option: For 630 A paneltypes LS11, LS11-U andLT11: Logical mechanicalinterlocking with three-po-sition switch-disconnector
Standard: For 1250 Apanel types LS31, LS31-U,LS32 and LT31: Logicalmechanical interlockingwith three-positiondisconnector
Logical mechan. interlock-ing of cable compartmentcover: Opening of cablecompartment cover onlypossible provided that thefeeder is earthed
Feeder earthing
Standard: For panel typesLS11, LS11-U, LT11, LS31,LS31-U and LS32:Earthing by switching ofvacuum circuit-breaker3AH6 1) in positionCLOSED and of three-position switch 2) inposition EARTHED
Option: For circuit-breakerpanel types LS11, LS31and LS32: Earthing bymeans of an additionalmake-proof earthingswitch at the feeder withinspection window in thecable compartment cover
Locking devices
The three-position switch-disconnector can be lockedon the operating mechanismside in any position (option).
Interlocking systems
Locking device (option)
R-HA
41-0
64ce
psR-
HA41
-081
eps
Interlocking for cable compartment cover
Removed cable compartment coverwith earthed bus sectionalizer panel
Locking device of the detachable lever mechanisme.g. for padlock
1) With additional locking device optionally with signalling switch forsecuring the CLOSED position ofthe vacuum circuit-breaker for feederEARTHED
2) Three-position switch as Switch-disconnector in panel
types LS11, LS11-U and LT11 Disconnector in panel types
LS31, LS31-U, LS32 and LT31
Components
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 29
4MC63 three-phase current transformers for panel types LS ... and LT ...
Application
For circuit-breaker panelstype LS ...
For bus sectionalizer panelstype LT ...
Option: For ring-main panelstype RK ...
Features
According to IEC 60044-1/VDE 0414-1
Designed as a three-polering-core currenttransformer
Free of dielectricallystressed cast-resin parts (dueto design)
Insulation class E
Inductive type
Climate-independent
Secondary connection bymeans of a terminal stripinside the panel
Installation
Arranged outside the switch-gear vessel on the bushings
Factory-assembled
Other designs(option)
Three-phase current transfor-mers for protection equipmentbased on c.t. operation:
7SJ45 protection relay asdefinite-time overcurrentprotection
Definite-time overcurrentprotection relay,make SEG, type WIP 1,WIC 1
Technical data 4MC63 53 three-phase current transformerfor IN < 150 Afor ID = 630 A
for IN < 400 Afor ID = 630 A
for IN < 1000 Afor ID = 1250 A
Primary data
Max. equipment operatingvoltage Um
0.72 kV 0.72 kV 0.72 kV
Rated current IN A 150 100 75 50 400 300 200 1000 750 600 500
Rated short-durationpower-frequencywithstand voltage(winding test)
3 kV 3 kV 3 kV
Rated thermal short-timewithstand current Ith
25 kA 25 kA 25 kA
Rated continuous thermalcurrent ID
630 A 630 A 1250 A
Transient overloadcurrent
1.5 x ID / 1 h 2 x ID / 0.5 h 1.5 x ID / 1 h
Rated peak withstandcurrent Idyn
unlimited unlimited unlimited
Secondary data
Rated current A 1 0.67 0.5 0.33 1 0.75 0.5 1 0.75 0.6 0.5
Rating VA 5 3.33 2.5 1.67 5 3.75 2.5 5 3.75 3 2.5
Rated current (option) 5 A 5 A 5 A
Current at ID 4.2 A 1.575 A 1.25 A
Protec-tioncore
Class 10 P 10 P 10 P
Overcurrent factor 10 10 10
Other values available on request
R-HA
41-0
48ep
s
4MC63 53 three-phasecurrent transformer
4MC63 53 three-phase current transformeron the bushings of the three-positionswitch-disconnector
R-HA
41-0
44ep
s
Components
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201030
4MC70 33 cable-type current transformerson the cable at the panel connection
Application
For circuit-breaker panelstype LS ...
For ring-main panelstype RK ...
For transformer panelstype TR ...
Features
According to IEC 60044-1/VDE 0414-1
Designed as a single-polering-core current transformer
Only for shielded cables
Climate-independent
Free of dielectricallystressed cast-resin parts (dueto design)
Insulation class E
Inductive type
Secondary connection bymeans of a terminal stripinside the panel
Installation
4MC70 33 cable-type currenttransformer for panel typesLS ...
4MC70 31 cable-type currenttransformer: e.g. for paneltypes RK ..., K ... and TR ...
Arranged on the cable atthe panel connection
Transformers mounted on asupporting plate at ourfactory; final assembly onthe cables on site
* Depending on the core data** Available installation height
inside panel types RK or RK1:Approx. 285 mm, depending onmake, type and cross-section ofsealing end Other values available on request
R-HA
41-0
49a
eps
R-HA
41-0
25ep
s
4MC70 31 cable-typecurrent transformerH
4MC70 33 cable-typecurrent transformer,4 different overall heights
4MC70 33 and 4MC70 31 cable-type current transformers
Technical data 4MC70 33 cable-typecurrent transformer
4MC70 31 cable-typecurrent transformer
Primary data
Max. equipment operatingvoltage Um
0.72 kV 0.72 kV
Rated current IN 30 A to 600 A 50 A to 600 A
Rated short-durationpower-frequencywithstand voltage(winding test)
3 kV 3 kV
Rated thermal short-timewithstand current Ith
25 kA 25 kA
Rated continuous thermalcurrent ID
1.0 x INoption: 1.2 x IN
1.0 x INoption: 1.2 x IN
Transient overloadcurrent
1.5 x ID / 1 h or 2 x ID / 0.5 h 1.5 x ID / 1 h or 2 x ID / 0.5 h
Rated peak withstandcurrent Idyn
unlimited unlimited
Secondary data
Rated current 1 A (option: 5 A) 1 A (option: 5 A)
Meas-uringcore
Class 0.2 0.5 1 1
Overcurrent factor FS10 (option: FS5) FS5 (option: FS10)
Rating 2.5 VA to 10 VA 2.5 VA to 10 VA
Pro-tectioncore
Class 10 P 5 P
Overcurrent factor 10 10
Rating 2.5 VA to 10 VA
Option: Secondary tap 1 : 2 (e.g. 150 A 300 A) 1 : 2
Dimensions
Overall height H ** mm 50* 100* 170* 285* 89Outside diameter 145 mm 85 mm x 114 mm
Inside diameter 55 mm 40 mm
For cable diameter 50 mm 36 mm
H
RHA4
1-02
4aep
s
Components
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 31
4MA7 block-type current transformers and 4MR voltage transformers
Application
For billing metering panelstype ME1 ...
For bus riser paneltype HF
For mounting at thefeeder
Features
4MA7 current transformer
According to IEC 60044-1/VDE 0414-1
Dimensions according toDIN 42600-8
Designed as a single-poleindoor block-type currenttransformer
Cast-resin insulated
Insulation class E
Secondary connection bymeans of screw-typeterminals
4MR voltage transformer
According to IEC 60044-2/VDE 0414-2
Dimensions according toDIN 42600-9 (smallmodel)
Designed as an indoorvoltage transformer:
Type 4MR, single-pole Option: Type 4MR, two-pole
Cast-resin insulated
Insulation class E
Secondary connection bymeans of screw-typeterminals
R-HA
41-0
60a
eps
4MA7 block-type currenttransformer,single-pole
4MR14 voltagetransformer,single-pole
4MR voltage transformer and4MA7 block-type current transformer installed inbilling metering panel type ME1
R-HA
41-0
29a
eps
R-HA
41-0
30a
eps
Technical data
4MA7 single-pole block-type current transformer (other values on request)Primary data
Max. equipment operating voltage Um kV 3.6 7.2 12 17.5 24Rated short-durat. power-freq. withstand volt. Ud kV 10 20 28 38 50Rated lightning impulse withstand voltage Up kV 20 60 75 95 125Rated current IN A 20 to 1250Rated thermal short-time withstand current Ith kA up to 25Rated continuous thermal current ID up to 1.0 x In (option: 1.2 x In)Rated peak withstand current Idyn max. 2.5 x Ith
Secondary data
Rated current A 1 or 5Measuring Class 0.2; 0.5; 1core Overcurrent factor FS5 or FS10
Rating VA 10 to 15Protection Class 5 P or 10 Pcore Overcurrent factor 10
Rating VA 5 to 15
4MR single-pole voltage transformer (other values on request)Primary data
Max. equipment operating voltage Um (= 1.2 x UN) kV 3.6 7.2 12 17.5 24Rated short-durat. power-freq. withstand volt. Ud kV 10 20 28 38 50Rated lightning impulse withstand voltage Up kV 20 60 75 95 125Rated voltage UN kV 3.3/ 3 3.6/ 3
4.8/ 35.0/ 36.0/ 36.6/ 3
7.2/ 310.0/ 311.0/ 3
13.8/ 315.0/ 3
17.5/ 320.0/ 322.0/ 3
Rated voltage factor (8h) 1.9 x UN
Secondary data
Rated voltage V 100/ 3110/ 3 (option)120/ 3 (option)
Rated voltage for auxiliary winding (option) V 100/3110/3 (option)120/3 (option)
Rating VA 20 50 100Class 0.2 0.5 1.0
Components
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201032
Cable connection
General features
Connecting lugs for sealing endsarranged one behind the other
Uniform cable connection heightfor the respective panel types
With cable bracket, e.g. type C40according to DIN EN 50024
Access to the cable connectioncompartment only if feeder hasbeen isolated and earthed
Special features
In ring-main panels In circuit-breaker panels In cable panels
For thermoplastic-insulated cables
For paper-insulated mass-impregnated cables withadapter systems
For connection cross-sections up to 300 mm2
Cable routing downwards
In transformer panels:
For thermoplastic-insulated cables
For connection cross-sections up to 120 mm2:Cable lug max. 32 mm wide
For rated normal currentsof 200 A
For options see figures
Cable cross-sections
Note
Cable sealing ends and cable clampsare not included in the scope of supply
Cable connection (examples)
Cable connection compartment with cablesealing ends (options: A, B, C 1) and D 1), see below)
Ring-main panel type RKCable connection compartment as delivered
L3 L2 L1 L1L2L3
Transformer panel type TRCable connection compartment as delivered
Cable connection compartment with cablesealing ends (option: A 2), see below)
L3L2L1
R-HA
41-0
50ep
s
R-HA
41-0
51ep
s
R-HA
41-0
53ep
s
R-HA
41-0
52ep
s
R-HA
41-0
55ep
s
R-HA
41-0
67ep
s
L3L2L1
Cable connection compartment with cablesealing ends (options: A, B, C and D, see below)
Circuit-breaker panel type LS11Cable connection compartment as delivered
Options A Mounted cable clamps 2)
B Short-circuit / earth-fault indicator
C Double cable connection
D Suitable for connection of surge arresters 3)
5
1
4
3
7
8
14
10 13
12
2
6
L1L2 L3
9
11
1) Only with ring-main panel type RK1
2) Cable clamps with transformerpanels type TR ... partly mountedunderneath the panel in the cablebasement
3) Make Siemens, type 3EK7,other makes on request
Panel type Connectable cables xconnection cross-section
No. x mm2
for rated voltage
12 kV 17.5 kV 24 kV
K Standard
On request
1x 300 1x 300 1x 300
2x 300
K1 2x 400 2x 400 2x 400
RK, Standard 1x 300 1x 300 1x 300K-E
On request 2x 300
RK1, K1-E 2x 300 2x 300 2x 300
LS1 2x 300 2x 300 2x 300
LS11, LS31 2x 400 2x 400 2x 300
LS32 Standard
Option
On request
3x 400 3x 400 3x 300
4x 300 4x 300
4x 300
ME1-K, ME1-KS 3x 400 3x 400 3x 300
Components
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 33
1) Transformer panel types TR ...: Lower edge of sealing end below panel Cable lugs of sealing ends up to 32 mm width Owing to the various sealing end lengths, some of
the mounted cable clamps are underneath the panel
2) Circuit-breaker panel types LS11, LS31 and LS32: Lower edge of sealing end below panel
Selection data for various cable sealing ends
1 As-delivered condition,e.g. for Up w 95 kV, preparedfor cable sealing end
2 As-delivered condition,e.g. for Up > 95 kV, additionally withinsulating sleeve, preparedfor cable sealing end
3 Phase L1:Make Lovink-EnertechType IAEM 20, 240 mm2 (20 kV)
4 Phase L2:Make Tyco Electronics RaychemType EPKT 24 C / 1X,185 mm2 (24 kV),as shrink-on sealing end,for severe ambient conditions
5 Phase L3:Make Prysmian Kabel und Systeme(Pirelli Elektrik)Type ELTI mb-1C-2h-C-T3,240 mm2 (24 kV)
6 As-delivered condition, preparedfor cable sealing end
7 Phase L1:Make Lovink-EnertechType IAEM 20,95 mm2 (20 kV)
8 Phase L2:Make Tyco Electronics RaychemType TFTI/5131,95 mm2 (24 kV),as push-on sealing end
9 Phase L3:Make EuromoldType AIN, 95 mm2 (24 kV)
10 As-delivered condition,e.g. for Up < 95 kV, preparedfor cable sealing end
11 As-delivered condition,e.g. for Up W 95 kV, additionally withinsulating cap, prepared forcable sealing end
12 Phase L1:Make Lovink-EnertechType IAES 20,240 mm2 (20 kV)
13 Phase L2:Make Prysmian Kabel und Systeme(Pirelli Elektrik)Type ELTI 1C-24-D-T3,240 mm2 (24 kV),as indoor sealing end,for severe ambient conditions
14 Phase L3:Make EuromoldType AIN 20,240 mm2 (24 kV)
Connection height **of cables abovefloor or abovelower edge of panel:
Cable sealing ends(examples)
Note
Depending on make andtype, the termination of thecable sealing end (= shieldearth) for the 3-core thermo-plastic-insulated cable andthe fitted cable clamp (option)may be located underneath thepanel in the cable basement.This must be taken intoaccount in panels withfloor cover (option).
3) Cable sealingend type withinsulation shields
* On request:Max. connectioncross-section ofcable sealing endtypes
**Due to the installation of4MA cast-resin insulatedblock-type current trans-formers in panels RK1and LS1, the connectionheight of the cables isreduced to 380 mm
Panel type TR
Dimension a~ 530 mm at 12 kV~ 380 mm at 24 kV
!
!
Panel type LS1 ...
Panel type RK ...
Panel type LS11 ...
Single-core thermoplastic-insulated cables for < 12 kV (6/10 kV)
Euromold AIN 10 25300 (500*)35 MSC35 MSC (option 3))
16300 (500*)25300 (500*)
ITK-212 50300 (400*)Prysmian Kabel undSysteme (Pirelli Elektrik)
ELTI mb-1C-12 35240ELTI-1C-12 25300
Tyco Electronics Raychem IXSU-F 16300 (500*)TFTI 25300 (400*)EPKT 1) 16300
Lovink-Enertech IAEM 10 25300IAES 10 25300 (500*)
3M Germany 92-EB 6x-1 35300 (400*)Sdkabel SEHDI 10.2 35300 (500*)
SEI 12 70300nkt cables TI 12 25240
AV 10 C 25300 (500*)AV 10 E 25300 (500*)
Single-core thermoplastic-insulated cables for > 12 kV to < 24 kV (12/20 kV)
Euromold AIN 20 25300 (630*)35 MSC35 MSC (option 3))
257025185
36 MSC 2)36 MSC (option 3))
95300 (500*)95300 (500*)
ITK-224 25240Prysmian Kabel undSysteme (Pirelli Elektrik)
ELTI mb-1C-24 35240ELTI-1C-24 25300
Tyco Electronics Raychem IXSU-F 25300 (500*)TFTI 25300 (400*)EPKT 16300 (500*)
Lovink-Enertech IAEM 20 25300IAES 20 25300 (500*)
3M Germany 93-EB 6x-1 50300 (400*)Sdkabel SEHDI 20.2 35300 (500*)
SEI 24 25240nkt cables TI 24 25240
AV 20 E 25300 (500*)AV 10 E 25300 (500*)
Three-core thermoplastic-insulated cables for < 12 kV (6/10 kV)
Euromold AIN 10 25300 (500*)SR-DI 12 35300 (500*)
Prysmian Kabel undSysteme (Pirelli Elektrik)
ELTI-3C-12 25300
Tyco Electronics Raychem IXSU-F 16300 (500*)Lovink-Enertech IAES 10 25300
GHKI 16300 (400*)
Three-core thermoplastic-insulated cables for > 12 kV to < 24 kV (12/10 kV)
Euromold SR-DI 24 2) 35300 (500*)Lovink-Enertech GHKI 25300 (500*)
Cable sealing end, e.g. for panel types RK..., LS1..., LS11..., LS31..., LS32and TR ...1) (for connection heights of cables see opposite dimension drawings)
Make Type Cross-section in mm2
Components
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201034
Low-voltage equipment
Low-voltage niche(standard)
Screwed-on cover as Cover (available mounting
depth behind ofapprox. 184 mm)
Frame cover, approx.46 mm deeper version(available mountingdepth behind ofapprox. 230 mm)
For accommodation ofterminals and standardprotection devices, e.g.in circuit-breaker panelscombined with framecover for panels
Type LS1: Protectionrelays (with max. 75 mmwide mounting frame), e.g. Type 7SJ45, 7SJ46 Make SEG, type WICOn request: 7SJ60 Make SEG, WIP1
Type LS11, LS31 and LS32:Protection relays (withmax. 75 mm widemounting frame), e.g.type 7SJ45, 7SJ46,7SJ60.On request: 7SJ61/62 (150 mm wide) Make SEG, WIP1
For bus wires and/or con-trol cables; niche open atthe side to the adjacentpanel
Safe-to-touch, separatedfrom high-voltage part ofthe panel
Degree of protectionIP 3X (standard)
Low-voltage compartment(option)
Overall heights:350 mm, 550 mm
Available mounting depth:442 mm
Overall widths:375 mm, 500 mm, 750 mm
For mounting on the panel
Dependent on the panel-specific scope of thesecondary equipment
For accommodation ofprotection, control, mea-suring and meteringequipment, e.g. multi-function protection relaySIPROTEC 4 7SJ61/62/63or other makes of protec-tion relays
Compartment 750 mmwide for panel type LS32
1 LED indications
2 LCD
3 Navigation keys
4 Function keys
5 Option:Short-circuit/earth-faultindicator
6 Frame cover oflow-voltage niche(can be unscrewed)
7 Momentary-contactrotary control switchON-OFF for motoroperating mechanismof the three-positionswitch-disconnector
8 Local-remote switchfor three-positionswitch-disconnector
9 Control board
10 Low-voltage nicheopen
11 Option:Installed equipment
12 Panel front
13 Option:Multifunctionprotection relaySIPROTEC 4 7SJ61on swing-out frame
14 Option:Protection devicemake SEG,type WIC
Electronic functions
Multifunction protectionrelay SIPROTEC 4 7SJ62or 7SJ63 with the followingfeatures:
1 User-programmable LEDswith application-specificlabel, for displaying anydesired process andequipment data
2 LCD for process andequipment data, e.g. for:
Measuring and meteringvalues
Binary information on thestatus of switching pointand device
Protection data General indications Alarms
3 Keys for navigation inmenus and for enteringvalues
4 Four user-programmablefunction keys forfrequently performedactions
Low-voltage cables
Control cables of thepanel to the low-voltagecompartment are con-nected via multi-pole,coded module plugconnectors
Option: Plug-in bus wiresfrom panel to panel insidethe low-voltage niches,optionally in separatecable duct on the panel
Low-voltage niche (examples)
SIPROTEC 47SJ61:
1 LED indications
2 LCD
3 Navigation keys
4 Function keys
Low-voltage compartment (option)
R-HA
41-0
62a
eps
R-HA
41-0
83ep
sR-
HA41
-059
aep
s
In bus sectionalizer panel type LT11(low-voltage niche closed)
In circuit-breaker panel type LS1(low-voltage niche open)
In billing metering panel type ME1(low-voltage niche open)
On circuit-breaker panel type LS1for additional low-voltage equipment
6
5
7
8
9
3
2
2
1
4
3
10
R-HA
41-0
58ep
s
11
9
10
11
12
1
4
14
13
Components
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 35
Ring-main panels, transformer panels
*
+
+
*
*
*
+
+
1) Location of voltage transformerin left-hand panel,e.g. in panel typeLT10 or LT11
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
*** For panel type RK1 the cableconnection height is reducedto approx. 380 mm for panelversion with 4MA block-typecurrent transformer
Ring-mainpanels
Ring-main panelfor panel combinations
Transformerpanels
Type RK Type RK1
Type RK-U
Type TR1Type TR
Dimensions
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201036
Cable panels
*
+
+
*
+
+
Type K Type K1
Type K1-EType K-E
Cable panels
Cable panels(with additional make-proofearthing switch)
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
Dimensions
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 37
Circuit-breaker panels
*
+
*
"
*
*
1) Type designation of thevacuum circuit-breaker
2) Option: Inspection window
3) Option: With make-proofearthing switch
* Option: Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment Approx. 184 mm with cover Approx. 230 mm with extended
frame cover
*** The cable connection height isreduced to approx. 380 mm forpanel version with 4MA block-typecurrent transformer
Circuit-breaker panel630 Awith 3AH5 1)
Type LS1
Type LS11 (with make-proof earthing switch)
Circuit-breaker panels630 Awith 3AH6 1)
Type LS11 (withoutearthing switch)
*
*
Type LS31 3) (for connectionof max. 2 cables)
Type LS32 3) (for connectionof 3 cables)
Circuit-breaker panels1250 Awith 3AH6 1)
Dimensions
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201038
Bus sectionalizer panels with bus riser panel
*
*
*
*
Type LT10 + type HF
Type LT11 + type HF
Bus sectionalizer panel630 Awith 3AH5 1)
Bus sectionalizer panel630 Awith 3AH6 1)
1) Type designation of thevacuum circuit-breaker
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment Approx. 184 mm
with cover Approx. 230 mm
with extended frame cover
Bus sectionalizer panel1250 Awith 3AH6 1)
!
*
*
Type LT31 + type HF
Dimensions
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 39
Bus sectionalizer panels
*
*
Type LT2( type RK-U with type HF)
Type LT2-W
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
Bus sectionalizer panelswithout transformers
Bus sectionalizer panelswith transformers
Type LT22( type RK-U with type RK-U)
Type LT22-W
Dimensions
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201040
Billing metering panels
*
*
*
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
Billing metering panel(standard)
Billing metering panelsfor busbar and cableconnection
Billing meteringpanel for2nd current transformer set
Type ME1
Type ME1-S(for busbar connection)
Type ME1-H
*
Type ME1-K(for cable connection)
Dimensions
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 41
Busbar voltage metering panels, busbar earthing panels, bus riser panels
*
*
Busbarvoltage meteringpanels
Type ME3 Type ME31-Fwith fuses
1) Location of voltagetransformer inleft-hand panel
* Option:Low-voltage compartmentavailable in two heights:350 mm or 550 mm
** Available mounting depthfor low-voltage equipment
*
Busbarearthingpanels
Type SE1without transformers
*
Type SE2with voltage transformers
*
Busriserpanels
Type HFwithout transformers
*
Type HFwith transformers
Dimensions
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201042
Floor openings (dimensions in red) and fixing points
For
pane
lwid
th37
5m
m
+
+
,
,
+
+
+
,
,
,
,
+
,
,
+
+
,
,
!
!
With cable connection
1 Wall distance
2 Fixing frame (base)of an individual panel or panel block
3 Floor opening for high-voltage cables and,where applicable, control cables; in paneltypes LS11, LS31 and LS31-K: floor openingalso possible below floor cover
4 Position of the led-in cables for the feeder
5 Fixing points
6 Floor opening if required for panelswithout cable connection
+
+
,
,
Without cable connection
For
pane
lwid
th50
0m
m
Without cable connectionWith cable connection
For
pane
lwid
th75
0m
m
With double cable connection
For dimensions not shownsee illustration on the left
Without cable connection
For pa-nel type
RKKK-ETR
For pa-nel type
RK-UME3HFSE1
For pa-nel type
RK1K1+K1-ETR1
For pa-nel type
RK1-UME31-FSE2
For pa-nel type
LS1(Dim. a= 562.5)
ME1-K(Dim. a= 375)
ME1-KS(Dim. a= 375)
For pa-nel type
LS1-ULS11-ULT10LT11LT2LT2-WLT22LT22-WME1ME1-SME1-H
LS31-ULT31
For pa-nel type
LS11
LS31
For pa-nel type
LS32
With cable connection
For
pane
lwid
th87
5m
m
With cable connection
+
+
!
,
,
Dimensions
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 43
Altitude correction factor Ka
For site altitudesabove 1000 m, thealtitude correctionfactor Ka is recom-mended, depend-ing on the actualsite altitude abovesea level.
Rated short-dur. power-freq. withstand volt. for site altitudes > 1000 m to be selected
W Rated short-duration power-frequency withstand voltage up to w 1000 m Ka
Rated lightning impulse withstand voltage for site altitudes > 1000 m to be selected
W Rated lightning impulse withstand voltage up to w 1000 m Ka
Example:
3000 m site altitude above sea level17.5 kV switchgear rated voltage95.0 kV rated lightning impulse withstand voltage
Rated lightning impulse95 kV 1.28 = 122 kVwithstand volt. to be selected
Standards, specifications, guidelines, classification
Standards
The SIMOSEC switchgearcomplies with the relevantstandards and specificationsapplicable at the time oftype tests.
In accordance with the harmo-nization agreement reached bythe countries of the EuropeanCommunity, their nationalspecifications conform to theIEC standard.
-
Alti
tude
corr
ectio
nfa
ctor
Site altitude in m above sea level
Type of service location
SIMOSEC switchgear can beused as an indoor installation inaccordance with IEC 61936(Power installations exceeding1 kV AC) and VDE 0101
Outside lockable electricalservice locations at placeswhich are not accessible tothe public. Enclosures ofswitchgear can only beremoved with tools.
Inside lockable electricalservice locations. A lockableelectrical service location isa place outdoors or indoorsthat is reserved exclusively forhousing electrical equipmentand which is kept under lockand key. Access is restrictedto authorized personnel andpersons who have beenproperly instructed in electri-cal engineering.Untrained or unskilled per-sons may only enter underthe supervision of authorizedpersonnel or properly instruc-ted persons.
Terms
Make-proof earthing switchesare earthing switches withshort-circuit making capacityaccording to IEC 62271-102
and VDE 0671-102
Colour of panel front
Siemens standard (SN)47 030 G1,colour no. 700 / light basic(similar to RAL 7047 / grey)
Insulating capacity
The insulating capacity is veri-fied by testing the switchgearwith rated values of short-duration power-frequencywithstand voltage and light-ning impulse withstand volt-age according to IEC 62271-1/VDE 0671-1 (see tableInsulating capacity).
The rated values are referredto sea level and to normalatmospheric conditions(1013 hPa, 20 C, 11 g/m3humidity in accordance withIEC 60071 and VDE 0111).
The insulating capacitydecreases with increasingaltitude.For site altitudes above1000 m (above sea level)the standards do not provideany guidelines for the insula-tion rating. Instead, specialregulations apply to thesealtitudes.
Site altitude As the altitude increases, the
insulating capacity of insula-tion in air decreases due tothe decreasing air density.This reduction is permitted upto a site altitude of 1000 maccording to IEC and VDE.
For site altitudes above1000 m a higher insulationlevel must be selected. Itresults from the multiplica-tion of the rated insulationlevel for 0 to 1000 m with thealtitude correction factor Ka.
Result:
According to the abovetable, a switchgear for arated voltage of 24 kV witha rated lightning impulsewithstand voltage of125 kV is to be selected.
Table Insulating capacity
Rated voltage (rms value) kV 7.2 12 15 17.5 24
Rated short-duration power-frequency withstand voltage (rms value)
Across isolating distances kV 23 32 39 45 60
Between phases and to earth kV 20 28 36 38 50
Rated lightning impulse withstand voltage (peak value)
Across isolating distances kV 70 85 105 110 145
Between phases and to earth kV 60 75 95 95 125
Overview of standards (May 2008)
IEC standard VDE standard EN standard
Switchgear SIMOSEC IEC 62271-1 VDE 0671-1 EN 62271-1
IEC 62271-200 VDE 0671-200 EN 62271-200
Devices Circuit-breaker IEC 62271-100 VDE 0671-100 EN 62271-100
Disconnector and earthingswitch
IEC 62271-102 VDE 0671-102 EN 62271-102
Switch-disconnector IEC 60265-1 VDE 0670-301 EN 60265-1
Switch-disconnector /fuse combination
IEC 62271-105 VDE 0671-105 EN 62271-105
HV HRC fuses IEC 60282-1 VDE 0670-4 EN 60282
Voltage detection system IEC 61243-5 VDE 0682-415 EN 61243-5
Degree ofprotection
IEC 60529 VDE 0470-1 EN 60529
Insulation IEC 60071 VDE 0111 EN 60071
Transformers Current transformer IEC 60044-1 VDE 0414-1 EN 60044-1
Voltage transformer IEC 60044-2 VDE 0414-2 EN 60044-2
Installation IEC 61936-1 VDE 0101
Standards
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201044
Standards, specifications, guidelines, classification
Internal arc classification(option)
Safety of operating personnelensured by tests to verify in-ternal arc classification
The possibility of arc faultsin SIMOSEC switchgear ismuch less due to:
Metal-enclosed and gas-insulated switching functions(e.g. of three-position switch-disconnector and 3AH5vacuum circuit-breaker)
Logical arrangement ofoperating mechanismelements and mechanicalinterlocks
Short-circuit-proof feederearthing by means of thethree-position switch-disconnector
The internal arc fault testsmust be performed in accord-ance with IEC 62271-200/VDE 0671-200 *
Criteria for internal arc faults
Criteria according toIEC 62271-200/VDE 0671-200 * with respectto the behaviour in case ofinternal arc faults
Definitions of criteria: Acceptance criterion 1
Covers and doors remainclosed. Limited deformationsare accepted.
Acceptance criterion 2No fragmentation of theenclosure. No projection ofsmall parts above 60 gweight.
Acceptance criterion 3No holes in the accessiblesides up to a height of 2 m.
Acceptance criterion 4Indicators do not ignite dueto the effect of hot gases.
Acceptance criterion 5The enclosure remainsconnected to its earthingparts.
For cable testing the installation and
operating instructions ofthe switchgear
the standardsIEC 62271-200/VDE 0671-200Section 5.105 *
the information on manu-facturer-dependent cablesealing ends
the cable version(e.g. paper-insulated mass-impregnated cables, PVCcables or XLPE cables)
must be observed.
1) VLF = very low frequency
2) Referred to: U0 /U (Um = 6.35/11 (12) kV)
* Standards see page 43
Cable testing
For circuit-breaker andswitch-disconnector feeders
DC voltage test
before the test:
Remove or disconnect anyvoltage transformers at thecable connection inSIMOSEC switchgear.
SIMOSEC switchgear forrated voltages up to 24 kVcan be subjected to cabletests at a max. DC testvoltage of 72 kV or accordingto VDE at 70 kV, 15 min.The voltage at the busbarmay be 24 kV in this case.
Test voltages:
Ratedvoltage
U0 /U (Um) Max. test voltageapplied to cable
VLF 1), 0.1 Hz acc. to IEC VDE 0278
3 x U0 6 x U0, 15 min.ULF U = max. U =
Ur (kV) (kV) AC (kV) DC (kV) DC (kV)
12 6 / 10 (12) 19 24 38 2)
24 12 / 20 (24) 38 48 70
Climate and ambientconditions
SIMOSEC switchgear may beused, subject to possible addi-tional measures e.g. panelheaters or floor covers under the following ambientconditions and climate classes:
Ambient conditions Natural foreign materials Chemically active pollutants Small animals
Climate classesThe climate classes areclassified according toIEC 60721-3-3
SIMOSEC switchgear is largelyinsensitive to climate andambient conditions by virtue ofthe following features:
No cross insulation forisolating distances betweenphases
Metal enclosure of switchingdevices (e.g. three-positionswitch) in gas-filled stainless-steel switchgear vessel
Dry-type bearings inoperating mechanism
Essential parts of the operat-ing mechanism made ofcorrosion-proof materials
Use of climate-independentthree-phase current trans-formers
Standards
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 2010 45
Standards, specifications, guidelines, classification
Classification of the SIMOSEC switchgear according to IEC 62271-200
Construction and design
Partition class PM (metallic partition)
Loss of service continuity category 1)Panels
With HV HRC fuses, and for panel typeswith removable circuit-breakers type 3AH6
Without HV HRC fuses, and for panel typeswithout removable circuit-breakers type 3AH6
In a SIMOSEC switchgear, panel types ME1 orHF are also part of the busbar. According toIEC 62271-200 a category is not applicable
LSC 2A
LSC 2B
Accessibility to compartments Busbar compartment Switching-device compartment Switching-device compartment with
circuit-breakers type 3AH6 (removable) Low-voltage compartment Cable connection compartment
Without HV HRC fuses With HV HRC fuses
Tool-basedNot accessibleAccessible and interlock-based
Tool-based
Tool-basedInterlock-based and tool-based
Internal arc classification (option)
Class Free-standing arrangement Wall-standing arrangement
7.2 kV to 24 kVIAC A FLR 20 kA, 1 sIAC A FL 20 kA, 1 s
Degree of accessibility A
F L R
Switchgear in closed electrical service location, access only forproperly instructed personnelFrontLateralRear (for free-standing arrangement)
Test current 20 kA
Test duration 1 s
1) The loss of service continuity cate-gory always refers to the completeswitchgear, i.e. the panel with thelowest category determines theloss of service continuity categoryof the complete switchgear.
Standards
Switchgear Type SIMOSEC up to 24 kV, Air-insulated, Extendable Siemens HA 41.21 201046
Standards, specifications, guidelines, classification
IEC 60 529 and EN 60529:
* Standards see page 43** For explanations
see adjacent table
Type of protection Degree of protection
I P 2Xss
Protection against solid foreign bodiesProtected against the penetrationof solid foreign bodies, diameter W 12.5 mm
Protection against electric shockProtected against access to dangerous partsby means of a finger (the distance betweena test finger with a diameter of 12 mmto dangerous parts must be sufficient)
Protection against the ingress of waterNo definition
I P 3Xss
Protection against solid foreign bodiesProtected against the penetrationof solid foreign bodies, diameter W 2.5 mm
Protection against electric shockProtected against access to dangerous partsby means of a wire (the distance between a testrod with a diameter of 2.5 mm and a length of100 mm to dangerous parts must be sufficient)
Protection against the ingress of waterNo definition
I P 3 X Dsss
Protection against solid foreign bodiesProtected against the penetrationof solid foreign bodies, diameter W 2.5 mm
Protection against the ingress of waterNo definition
Protection against electric shockProtected against access to dangerous partsby means of a wire (the distance between a testrod with a diameter of 1 mm and a length of100 mm to dangerous parts must be sufficient)
I P 6 5ss
Protection against solid foreign bodiesDust-proof: no penetration of dust
Protection against electric shockProtected against access to dangerous partsby means of a wire (test probe with a diameter of 1 mmmay not penetrate)
Protection against the ingress of waterProtected against water jets,water which is directed towardsthe enclosure from any directionmay not have a damaging effect
Protection against solidforeign bodies, electric shockand ingress of water
SIMOSEC switchgear fulfillsacc. to the standards *
the following degrees ofprotection **:
Degree ofprotection
Type ofprotection
IP 2X(standard)
Enclosure of liveparts underhigh-voltage
Compartments
IP 3X(option)
Enclosure of liveparts under high-voltage inswitchgear withlocking device
IP 3XD(onrequest)
Enclosure of liveparts under high-voltage inswitchgear withlocking device
IP 65 Metal enclosureof gas-filledswitchgear vessels
IEC 62271-1 VDE 0671-1EN 62271-1
IEC 62271-200 VDE 0671-200
IEC 60529 EN 60529
Standards
www.siemens.com/energy
Published by and copyright 2010:Siemens AGEnergy SectorFreyeslebenstrasse 191058 Erlangen, Germany
Siemens AGEnergy SectorPower Distribution DivisionMedium VoltagePostfach 324091050 Erlangen, Germanywww.siemens.com/medium-voltage-switchgear
For more information, please contact ourCustomer Support Center.Phone: +49 180 524 70 00Fax: +49 180 524 24 71(Charges depending on provider)E-Mail: [email protected]
Order No. E50001-K1441-A211-A6-7600Printed in GermanyDispo 30403, c4bs 7475KG 11.10 2.0 48 En3600/31293
Printed on elementary chlorine-free bleached paper.
All rights reserved.If not stated otherwise on the individual pages of thiscatalog, we reserve the right to include modifications,especially regarding the stated values, dimensions and weights.Drawings are not binding.All product designations used are trademarks or productnames of Siemens AG or other suppliers.If not stated otherwise, all dimensions in thiscatalog are given in mm.
Subject to change without prior notice.The information in this document contains generaldescriptions of the technical options available, whichmay not apply in all cases. The required technicaloptions should therefore be specified in the contract.