1

CATALOGUEELECTRIC ENERGY METERS

Page 2: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

CATALOGUEELECTRIC ENERGY METERS

Page 3: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

4 5

СЕ101 ........................................................................................................ 6

СЕ200 ........................................................................................................ 7

СЕ102 R5.1 ............................................................................................... 8

СЕ102 М ...................................................................................................10

СЕ201 .......................................................................................................12

СЕ208 R5 ..................................................................................................14

СЕ208 С2 ..................................................................................................16

СЕ208 S7 DLMS ...................................................................................... 18

СЕ208 S7 ................................................................................................. 20

СЕ300, СЕ302 .......................................................................................... 22

СЕ301 R33 ............................................................................................... 23

СЕ301 S31 ............................................................................................... 25

СЕ303 R33 ............................................................................................... 27

СЕ303 S31 ............................................................................................... 29

СЕ303 S34 ............................................................................................... 31

СЕ304 ...................................................................................................... 33

СЕ307 R33 ............................................................................................... 35

СЕ308 C36 ............................................................................................... 37

СЕ308 R32, R33 DLMS ........................................................................... 39

СЕ308 S31, S34 DLMS ............................................................................ 41

Cases’ dimensional drawings ................................................................. 43

SINGLE PHASE

single-tariff

multi-tariff

THREE PHASE

single-tariff

multi-tariff

CONTENT

The history of the Concern Energomera has started in 1994 from the small company with an R&D bureau. The company has been growing and now the Concern has reached the level it can be proud of:

· Energomera is the pioneer in the electricity meters manufacturing in Russia.· Totally domestic production from project development to complete devices manufacturing.· 5 generations of meters have been presented. Each of them has become a technological breakthrough.· About 5 000 of employees. More than 180 specialties and professions.· High-tech factories in Russia, Ukraine and Belarus.· Own Corporate Institute of Electrotechnical Instrument Engineering.

Own factory in Nevinnomyssk (Stavropol region) produces electricity meters over the time of MORE THAN 20 YEARS

APPENdIx

LEAdERSHIPQUALITYINNOVATIONS

ABOUT THE COMPANY

Page 4: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

6 7

SpEcificATiONSActive energy measurement accuracy class Network frequencyNominal voltageBase (max.) currentStarting current (sensitivity)Operating temperature range Operating phase voltage range Overall dimensions:for the case type R5.1 for the case type R5 for the case type S6

SIN

GLE-

PHAS

E SI

NGL

E-TA

RIFF

CE101

R5.1 R5.1R5 S6

SINGLE-PHASE SINGLE-TARIFFACTIVE ENERGY METERS

1 50±2,5 Hz230 V5 (60); 10 (100) А10; 20 mАfrom 40 to 70 °С(0,75 … 1,15) Unom

105 х 59 х 89,5 mm110 х 89 х 72,5 mm170 х 115 х 53 mm

CE101 S6 145CE101 S6 145 M6CE101 S6 148CE101 S6 148 M6

CE101 R5 145CE101 R5 145 M6CE101 R5 148CE101 R5 148 M6

CE101 R5.1 145CE101 R5.1 145 M6

BASicMOdificATiONS

dESigNATiON STRucTuRE

CE 101 X X X X XReadout unit:М6 – six-digits mechanical(no symbol) – LCD

Base (max.) current:5 – 5 (60) А8 – 10 (100) А

Nominal voltage:4 – 230 V

Accuracy class:1 – 1

Case type:S6 – for three screws mounting R5 – for DIN-rail mountingR5.1 – for universal mounting

REliABiliTY ANd wARRANTYAverage time to failurVerification interval Warranty periodAverage service life

220 000 hours16 years5 years30 years

case types:

SIN

GLE-

PHAS

E SI

NGL

E-TA

RIFF

SpEcificATiONSActive energy measurement accuracy classNetwork frequencyNominal voltageBase (max.) currentStarting current (sensitivity)Operating temperature range Operating phase voltage range Overall dimensions:for the case type R5.1for the case type R5for the case type S6

1 50±2,5 Hz230 V5 (60); 10 (100) А20; 40 mАfrom - 40 to +70 °С(0,75 … 1,15) Unom

105 х 59 х 89,5 mm110 х 89 х 72,5 mm170 х 115 х 53 mm

CE200

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)

case types: R5

CE 200 R5 145 М6CE 200 S6 145 M6CE 200 R5.1 145

BASicMOdificATiONS

dESigNATiON STRucTuRE

СЕ 200 X X X X XReadout unit:М6 – six-digit mechanical(no symbol) – LCD

Base (maximum) current:5 – 5 (60) А8 – 10 (100) А

Nominal voltage:4 – 230 V

Accuracy class:1 – 1

Case type:S6 – for 3 screws mountingR5 – for DIN-rail mountingR5.1 – for universal mounting

REliABiliTY ANd wARRANTY

Average time to failure Verification interval Warranty period Average service life

160 000 hours16 years5 years30 years

SINGLE-PHASE SINGLE-TARIFFACTIVE ENERGY METERS

S6R5.1

ApplicATiONDirect connection meter is designed for single-tariff active electric energy metering in single-phase AC circuits.

RANgE Of uSE· Meter is designed for local operating.

fuNcTiONAl cApABiliTiES· The R5.1 case type is designed for universal mounting – DIN-rail and flat surface.· Modification with LCD ensures maximum protection from the magnet influence.· Mechanical readout unit has a magnetic shield and a reverse stopper.· Shunt used as the measuring unit makes the meter resistant for an electromagnetic influence.· Shockproof cases made of incombustible plastic.· Low starting current provides a high sensitivity of the meter.

ApplicATiONDirect connection meter is designed for single-tariff active electric energy metering in single-phase AC circuits.

RANgE Of uSE· Meter is designed for independent (local) operating, out of AMR system.

fuNcTiONAl cApABiliTiES· R5.1 case type is designed for universal mounting – DIN-rail and flat surface.· Two measuring units prevent theft by phase reversal.· Modification with LCD provides maximum protection from the magnet influence.· Mechanical readout unit has a magnetic shield and a reverse stopper.· Shunt used as the measuring unit makes the meter electromagnetic influence resistant.· Shockproof cases made of incombustible plastic.· Low starting current provides a high sensitivity of meter.

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)

For overall dimensions see the Appendix

Page 5: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

8 9

CE102

R5.1

SINGLE-PHASE MULTI-TARIFF ACTIVE ENERGY METERS

case types:

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)

SpEcificATiONSAccuracy class Number of tariffs Network frequencyNominal voltageBase (max.) currentStarting currentStoring depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariff Operating temperature rangeOperating phase voltage range Overall dimensions

1 4+1 (emergency)50±2,5 Hz230 V5 (60) А10 mА36 days12 monthsfrom - 45 to +70 °С(0,7…1,15) Unom105 x 60,5 x 105 mm

CE102 R5.1 145-JCE102 R5.1 145-JAN

BASic MOdificATiONSdESigNATiON STRucTuRE

CE 102 X XXX XXX

Interfaces:N – external power supply for RS485 interfaceA – RS485J – optical port

Base (maximum) current, A:5 – 5 (60) А

Nominal voltage:4 – 230 V

Accuracy class:1 – 1

Case type:R5.1 – for DIN-rail mounting

REliABiliTY ANd wARRANTY

Average time to failure Verification interval Warranty periodAverage service life

220 000 hours16 years5 years30 years

MOdificATiONS wiTH iNTERfAcES

RS485OPTICAL PORT

ApplicATiONMeter is designed for active energy measurement in single-phase AC circuits, organization of multi-tariff electric energy metering, network parameters measuring.

RANgE Of uSE· Meter is designed for local operating.· Meter is able to operated as a part of AMR system for the measured parameters transmission to control, metering and electric power distribution center via RS485 wired communication interface.

fuNcTiONAl cApABiliTiES· Measurement and indication of:– active energy consumption in total and separately on 4+1 tariffs at the end of the month and for 12 previous months;– active energy consumption in total and separately on 4+1 tariffs at the end of the day and for 36 previous days.· Metering and indication of:– current;– voltage rate;– network frequency; – active power value.· Event log recording of:– time correction;– device settings change.

For overall dimensions see the Appendix

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

Page 6: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

10 11

CE102 М

R5S7

SINGLE-PHASE MULTI-TARIFF ACTIVE ENERGY METERS

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)

Case type :

SpEcificATiONAccuracy class Number of tariffs Network frequencyNominal voltage Base (max.) currentStarting currentStoring depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariffOperating temperature rangeOperating phase voltage range Overall dimensions:S7 case typeR5 case type

1 4 50±2,5 Hz230 V5 (60); 10 (100) А10; 20 mА44 days 13 monthsfrom – 45 to +70 °С(0,75 … 1,15) Unom

213,3 х 122 х 73 mm110 х 89 х 72,5 mm

CE102M S7 145-JVCE102M S7 145-AVCE102M S7 148-JVCE102M S7 148-AV

CE102M R5 145-JCE102M R5 145-ACE102M R5 148-JCE102M R5 148-A

BASic MOdificATiONS

Meters for local operating

dESigNATiON STRucTuRE

СЕ 102 M X X X X X X

Additional options:V – Electronic seal of terminal block cover

Interfaces:J – optical portA – RS485

Base (maximum) current:5 – 5 (60) А8 – 10 (100) А

Nominal voltage:4 – 230 V

Accuracy class:1 – 1

Case type:S7 – for 3 screws mountingR5 – for DIN-rail mounting

REliABiliTY ANd wARRANTY

Average time to failure Verification interval: for the case type S7for the case type R5Warranty periodAverage service life

220 000 hours

16 years10 years5 years30 years

MOdificATiONS wiTH iNTERfAcES

ApplicATiONMeter is designed for active energy measurement in single-phase AC circuits and organization of multi-tariff electricity metering, network parameters measurement.

RANgE Of uSE· Meter is designed for local operating· Meter can be used as a part of AMR system for transmission of collected parameters via RS485 wired interface.

fuNcTiONAl cApABiliTiES · Electronic seal of terminal block cover (S7 case type)· Battery replacement without case opening and unscheduled verification (S7 case)· Metering and indication of:– active electric energy consumption in total and separately on 4 tariffs for the end of month and for 12 previous months;– active electric energy consumption in total and separately on 4 tariffs for the end of day and for 44 previous days;· Memory protection against unauthorized modifications with buttons’ pressing or via interfaces (two passwords for two access levels).· Metering and indication of:– current;– voltage;– network frequency;– active power;– active power factor.· Event log recording of:– time correction;– device settings change;– electronic seal state.

RS485OPTICAL PORT

For overall dimensions see the Appendix

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

Page 7: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

12 13

СЕ201

S7

SINGLE-PHASE MULTI-TARIFF ACTIVE ENERGY METER

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)

Case type :

MOdificATiONS wiTH iNTERfAcES

RS485OPTICAL PORT RF433 MHz PLC ЕTHERNETApplicATiONMeter is designed for active energy metering in single-phase AC circuits, organization of multi-tariff electricity metering, single phase network parameters measurement.

RANgE Of uSE· Meter can be used as a part of AMR system for the measured or calculated parameters transmission to control, metering and electric power distribution center.· Meter can be used locally, out of AMR system.

fuNcTiONAl cApABiliTiES · Modifications with single and double current sensors.· Load profiles (60 minutes interval) registration and storage for the period of 96 days.· Electronic seal of terminal block cover.· Modification with signalization relay (for external switching device control).· Metering and displaying of current parameters of: current, voltage, network frequency, power.· Manual time correction or via a communication interface (the daily limit is 30 seconds).· Battery replacement without case opening and unscheduled verification.· Built-in relay switching on/off in following modes:– relay switching on/off by the dispatcher’s remote command;– power relay automatic switching off with the further switching on after a specified time period if the customer has exceeded power limit;– if network voltage limits have been exceeded;– access attempt to the terminal block.· Measurement and indication of:– Active energy consumption in total and separately on 4 tariffs at the end of the month and for 12 previous months;– Active energy consumption in total and separately on 4 tariffs at the end of the day and for 45 previous days.· Memory protection against unauthorized modifications with buttons’ pressing or via interfaces (two passwords for two access levels).· Event log recording of:– 60 corrections of date/time; – 60 device settings changes;– 60 electronic seal states;– 60 voltage limits exceeds.

SpEcificATiONSActive energy accuracy class Number of tariffs Network frequencyNominal voltageBase (max.) current Starting currentStoring depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariffLoad profiles averaging timeStoring depth for every load profileOperating temperature rangeOperating phase voltage range Overall dimensions

1 4 50±2,5 Hz230 V5 (60); 10 (100) А10; 20 mА45 days 12 months 3; 5; 10; 15; 30; 60 min.96 days (at the 60 minutes averaging time) from – 45 to +70 °С(0,75 … 1,15) Unom 213,3 х 122 х 73 mm

CE201.1 S7 145-JAVZCE201.1 S7 148-JAVZCE201 S7 145 JAVZCE201 S7 148 JAVZCE201 S7 145-JАQ2VZCE201.1 S7 145-JАQ2VZ

BASic MOdificATiONS

Meters for local operating

dESigNATiON STRucTuRE

СЕ 201 X X X X XX X...X

Additional options:Designation of built-in communication module in accordance with normative and technical documentation (for P, R1, R2 modifications).Z – extended parameters setV – electronic seal of terminal block coverQ2 – load control relay, 60 A

Interfaces:J – optical portА – RS485P – PLC-interfaceR1 – RF433 – interface with built-in antennaR2 – RF433 – interface with external antennaТ – Ethernet

Base (maximum) current:5 – 5 (60) А8 – 10 (100) А

Nominal voltage:4 – 230 V

Accuracy class:1 – 1

Case type:S7 – for board mounting – two current sensors modification.1 – one current sensors modification

REliABiliTY ANd wARRANTYAverage time to failure Verification interval Warranty periodAverage service life

220 000 hours16 years5 years30 years

CE201 S7 145 JPVZ ССМЕ-0002CE201 S7 148 JPVZ ССМЕ-0002CE201.1 S7 148 JPVZ ССМЕ-0002CE201.1 S7 145 JTVZ CE835.01CE201 S7 145-JPQ2VZ ССМЕ-0002CE201.1 S7 145-JPQ2VZ ССМЕ-0002

Meters with communication modules

For overall dimensions see the Appendix

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

Page 8: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

14 15

MOdificATiONS wiTH iNTERfAcES

R5Case type:

CE208 SINGLE-PHASE MULTI-TARIFF ACTIVE ANd REACTIVE ENERGY METER

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)

PLC

fuNcTiONAl cApABiliTiES· Data exchange via PLC interface· Built-in relay switching on and off in following modes:– relay switching on/off by dispatcher’s remote command;– if the power limits have been exceeded (the consumption limit mode);– if network voltage limits have been exceeded;– access attempt to the terminal block.· Metering of:– by four tariffs with an ability to set up to eight tariff zones per day (for one daily schedule) with one minute of discreteness – individually for each day of the week in season program;– up to 36 different daily schedules of tariff switching and up to 12 season programs (season program defines the constant tariffing for the period from one day to one calendar year); – up to 32 exclusion days (holidays and postponed days) the tariffing on these days is different from the daily tariffing used in season program.· Ability for meter reading without network supply.· Network quality and operating network parameters measurement.· Registration and storage of load profiles for the previous 256 days.· Archive logging of 4 tariffs and total measured active energy:– progressive total (total from reset);– for the current month and previous 35 months;– for the end of a month and previous 36 months;– for the current day and previous 127 days;– for the end of the day and previous 128 days.· Logs recording of:– programming;

RANgE Of uSEMeter is designed to use it as a part of AMR system for measured or calculated parameters transmission to control center, and for consumer’s load remote control.

ApplicATiONMeter is designed for direct active energy measurement and bidirectional measurement of reactive energy in single-phase AC circuits, of multi-tariff electric energy metering organization.

SpEcificATiONSActive / Reactive energy measurement Accuracy class Number of tariffs Network frequencyNominal voltageBase (max.) currentStarting current (sensitivity)Storing depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariffNumber of load profiles Load profiles averaging timeEvery load profile storing depthOperating temperature range Operating phase voltage range Overall dimensions

1/2450±2,5 Hz230 V5 (60) А10 mА128 days36 months3 (P+; Q+; Q-) 3; 5; 10; 15; 30, 60 minutes12; 21; 42; 64; 128; 256 daysfrom – 45 to +70 °С(0,75 … 1,15) Unom110 х 89 х 72,5 mm

CE208 R5.845.1.OP.Q PL01

REliABiliTY ANd wARRANTY

Basic modifications

dESigNATiON STRucTuRE

СЕ 208 R5 X X Х. X. XXX. Х. ХXXX

Built-in communication interface designation

Additional options:Q – built-in switching relay (load opening switch)

Interfaces: O – optical portP – PLC-interface

Number of measuring elements:1 – meter with one current sensor

Base (maximum) current:5 – 5 (60) А

Nominal voltage:4 – 230 V

Active/ Reactive energy measurement accuracy class:8 – 1/2

Case type:R5 – for rail mounting

REliABiliTY ANd wARRANTYAverage time to failure Verification interval Warranty periodAverage service life

220 000 hours16 years5 years30 years

– voltage state;– current circuits state.· 100 events storing depth for the event logs.

OPTICAL PORT

For overall dimensions see the Appendix

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

Page 9: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

16 17

MOdificATiONS wiTH iNTERfAcES

customer interface unit (CIU)

CE208 C2SINGLE-PHASE MULTI-TARIFF ACTIVE ANd REACTIVE ENERGY METER

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)

measuring unit

RF433 MHz PLC+

fuNcTiONAl cApABiliTiESBy design the meter is divided into two parts: measuring unit and CIU.

MEASURING UNIT· DLP data exchange protocol support.· Outdoor mounting on the leading to consumer power lines.· Data exchange with data concentrator unit (DCU) via 433 MHz RF-interface.· Data transmission to the CIU via PLC without DCU engaging. · Active and reactive energy metering.· The design of measuring unit prevents electricity thefts.· Provides the customers’ load control with the built-in relay for the maximum current value up to 80A.· Totally integrated design (no way to disassemble).· Four-tariff electricity metering. · Allows to:– adjust up to 8 different daily schedules;– adjust up to 8 season programs;– adjust up to 20 exclusion days (holidays and postponed days) the tariffing on these days is different from the seasonal and weekly programs;– adjust up to 2 tariffing tables (main and backup) and date of switching to the backup table;– register tariffing archive logs by four tariffs of total measured energy for 36 previous months and 180 previous days.

RANgE Of uSE· Meter is designed to use it as a part of AMR system for measured and calculated parameters transmission to a control center, and for the remote consumers’ load control.· Meter has a split design and is dedicated for the mounting in the residential sector directly on the power lines.

· Registration of 60/30 minutes interval load profiles with the storage depth of 360/180 days.· Allows to control power limit or electricity consumption limit and send notifications if limits have been exceeded or switch the meter off after limit exceeding.· Power relay switching on and off:– relay switching on/off by the dispatcher’s remote command;– power relay automatic switching off with the further switching on after a specified time period if the customer has exceeded power limit.

CIU· Indoor mounting. Plug in to any socket in home. · Measuring unit data reading by PLC channel.· Two buttons for displayed information control.· Indicating of:– active energy measured in total and per tariff;– network voltage;– current in phase- and zero-wires;– active power;– network frequency;– date and time;– monthly stored energy for previous 13 months;– daily stored energy for previous 45 days;– measuring unit service information (MAC-address; identification number etc.).

ApplicATiONMeter is designed for active and reactive energy measurement in single-phase AC circuits, organization of multi-tariff electric energy metering in residential sector with the maximum anti-theft protection.

For overall dimensions see the Appendix

SpEcificATiONSActive/ Reactive energy measurement accuracy class Number of tariffs Measuring Network frequency Nominal voltage Base (max.) current Starting current (sensitivity)Storing depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariff Number of load profiles Load profiles averaging timeEvery load profile storing depthOperating temperature range: measuring unit CIUOperating phase voltage range Overall dimensions: measuring unitindicating deviceIngress Protection class:measuring unitCIU

1/24 50±2,5 Hz230 V5 (80) А10 mА180 days36 months2 30; 60 minutes180; 360 days

from – 40 to +70 °Сfrom – 20 to +70 °С(0,55 – 1,15) Unom 200 х 125 х 53 mm155 х 95 х 49 mm

IP 64IP 51

CE208 С2.849.2.OPR1.QD

BASic MOdificATiONSdESigNATiON STRucTuRE

СЕ 208 СX XXX. X. X...X. XX

Additional options:Q – load control relayD – with the CIU

Interface:O – optical portР – PLC-interfaceR1 – RF433 with the built-in antenna

Number of measuring elements:.2 – two current sensors

Base (maximum) current:9 – 5 (80) А

Nominal voltage:4 – 230 V

Active/ Reactive energy measurement Accuracy class:8 – 1/2 for active/reactive energy

Case type for the power line mounting:2 – with line breakthrough

REliABiliTY ANd wARRANTYAverage time to failureVerification interval Warranty periodAverage service life

220 000 hours16 years5 years16 years

OPTICAL PORT

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

Page 10: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

18 19

MOdificATiONS wiTH iNTERfAcES

S7Case type:

CE208 DLMSSINGLE-PHASE MULTI-TARIFF ACTIVE ANd REACTIVE ENERGY METER

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)

fuNcTiONAl cApABiliTiES · Multi-tariff metering of electric energy with a wide range of tariff schedules settings.· Bidirectional active and reactive energy metering.· Support of GOST IEC 61107-2011 and DLMS / COSEM data exchange protocols.· Measurement of electric energy quality parameters.· Flexible settings of reactions to the events appearing in the meter.· Measurement of electric energy quality:voltage deviation; – network frequency declination;– voltage failure duration and depth;– overvoltage duration and maximum value;– blackouts.· Recording of load profiles, with an ability to set the type of saved parameters and averaging period.· Network parameters measurement:– voltage frequency;– current;– voltage;– angle between current ant voltage;– power factor;– reactive power;– apparent power.· Active power consumption control.

RANgE Of uSEMeter is designed to use it as a part of AMR system for the measured parameters transition to the control center and remote control of consumers load.

· «Instantaneous power» consumption control.· Active energy consumption control.· Power supply voltage control.· Network frequency control.· Signalization relay.· Protection against unauthorized case opening (electronic seals).· Magnetic field sensor.· Data archive logging for:– active and reactive energy measurement data registration (total and per tariff) after a change of a day;– active and reactive energy measurement data registration (total and per tariff) after a change of a month (with a programmable date of billing period end);– active and reactive energy measurement data registration (total and per tariff) after a change of a year;– active and reactive energy measurement data registration (total and per tariff) by a command or event.· Sound signal.· Self-testing.· Displaying of information accompanied supported by OBIS codes.

ApplicATiONMeter is designed for active and reactive bidirectional energy measurement in single-phase AC circuits and organization of multi-tariff electric energy metering with the maximum anti-theft protection.

RS485 PLC GSM/GPRS

SpEcificATiONSActive/ Reactive energy Accuracy classNumber of tariffs Network frequencyNominal voltageBase (max.) currentStarting currentStoring depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariff Load profile averaging periodEvery profile storing depthOperating temperature rangeOperating phase voltage range Overall dimensions

1/2до 850±2,5 Hz230 V5 (60); 5 (100) А10 mА128 days40 months1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 minutes128 daysfrom – 45 to +70 °С(0,55…1,15) Unom200 x 122 x 73 mm

dESigNATiON STRucTuRE

CE 208 X 84X.X.XXXXX.XXXX

Designation of built-in communication module in accordance with normative and technical documentation (for P, R1, R2 modifications), and protocol designationAdditional options:Q – load control relay Y – bidirectional energy metering U – electric network quality parameters V – electronic seals L – LCD backlight F – magnetic-field sensor N – communication interface external power supply Z – extended parameters set Integrated communication interfaces: O – optical port A – RS485 P – PLC G – GSMNumber of measuring elements:1 – meter with one current sensor2 – meter with two current sensors (in the phase and neutral circuit)Base (maximum) current:5 – 5 (60) А6 – 5 (100) АActive/ Reactive energy measurement Accuracy class:8 – 1/2 active/reactive energyNominal voltage:4 – 230 VCase type and number:S7 – for board mounting

REliABiliTY ANd wARRANTYAverage time to failure Verification interval Warranty periodAverage service life

220 000 hours16 years5 years30 years

OPTICAL PORT

For overall dimensions see the Appendix

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

Page 11: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

20 21

MOdificATiONS wiTH iNTERfAcES

S7Case type:

CE208 SINGLE-PHASE MULTI-TARIFF ACTIVE ANd REACTIVE ENERGY METER

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)

fuNcTiONAl cApABiliTiES · Support of GOST IEC 61107–2011 and Smart Metering data exchange protocols. · Multi-tariff energy metering with a wide range of tariff schedules settings.· Two independent communication channels.· Bidirectional active and reactive energy measurement.· Two current sensors.· Measurement of electric energy quality parameters:– voltage failure duration and depth;– overvoltage duration and value.· Load profile storing, with an ability to set the type of saved parameters and averaging time. · Measurement of network parameters:– voltage frequency;– current;– voltage;– power factors;– active power;– reactive power;– apparent power.· Сontrol of active power consumption. · Сontrol of active energy consumption. · Сontrol of power supply voltage. · Сontrol of network frequency.

RANgE Of uSEMeter is designed for operating locally and as a part of AMR system for the measured parameters transmission to the control center and for the remote control of consumers load.

· Load control relay.· Protection against unauthorized case opening (electronic seals).· Magnetic field sensor.· Recording of measurement history. · Displaying of information supported by OBIS codes. · LCD backlight.· Self-testing.

ApplicATiONMeter is designed for active and reactive energy bidirectional measurement in single-phase AC circuits, organization of multi-tariff electric energy metering and array of single phase network parameters measuring and logging. Meter is designed for board mounting.

RF433 MHzPLC

SpEcificATiONSActive/ Reactive energy measurement accuracy class Number of tariffs Network frequencyNominal voltageBase (max.) currentStarting current Storing depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariff Load profile averaging periodOperating temperature rangeOverall dimensions

1/2до 850±2,5 Hz230 V5 (80) А20 mА128 days36 monthsfrom 1 to 60 minutes with 1 minute step of changefrom – 45 to +70 °С200 x 122 x 73 mm

dESigNATiON STRucTuRE

CE 208 X XXX XXX Х SMP

Designation of built-in communication module, and protocol designation

Additional options:Q – load control relayY – bidirectional energy meteringU – network parameters V – electronic seals F – magnetic-field sensorL – LCD backlightZ – extended parameters set

Integrated interfaces: O – optical port P – PLC R1 – RF433-interface with built-in antenna

Number of measuring elements:1 – meter with one current sensor2 – meter with two current sensors (phase and neutral circuit)

Base (maximum) current, A:9 – 5 (80) А

Nominal voltage:4 – 230 V

Active/ Reactive energy measurement Accuracy class:8 – 1/2

Case type and number:S7 – for board mounting

REliABiliTY ANd wARRANTYAverage time to failure Verification interval Warranty periodAverage service life

220 000 hours16 years5 years16 years

CE208 S7.849.2.OPR1.QYUVFLZ RP01

ВАРИАНТЫ БАЗОВЫХ ИСПОЛНЕНИЙ

OPTICAL PORT

For overall dimensions see the Appendix

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

SIN

GLE-

PHAS

E M

ULTI

-TAR

IFF

Page 12: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

22 23TH

REE-

PHAS

E SI

NGL

E-TA

RIFF

CЕ300, CE302

R31 S33

THREE-PHASE SINGLE-TARIFFACTIVE ANd REACTIVE ENERGY METERS

СЕ300GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)

СЕ302GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)GOST 31819.22-2012 (IEC 62053-22:2003)

Case type:

SpEcificATiONSActive energy measurement accuracy class Reactive energy measurement accuracy class (for CE302 only) Network frequencyNominal voltageBase (max.) currentStarting current (sensitivity):for direct connection metersfor transformer connection metersOperating temperature rangeOperating phase voltage range Overall dimensions:S33 case typeR31 case type

REliABiliTY ANd wARRANTYAverage time to failure Verification interval Warranty periodAverage service life

0,5S; 10,5; 1

50±2,5 Hz3х57,7/100 V; 3х230/400 V5 (10); 5 (60); 5 (100) А

20 mА5 mАfrom – 40 to +60 °С(0,75 … 1,15) Unom

235 х 169 х 70 mm143 х 113 х 72,5 mm

160 000 hours16 years4 years30 years

CE300 R31 043-JYCE300 R31 043-JCE300 R31 145-JCE300 R31 146-JCE300 S33 043-JYCE300 S33 003-JCE300 S33 003-JYCE300 S33 043-JCE300 S33 145-JCE300 S33 146-J

BASic MOdificATiONS

dESigNATiON STRucTuRE

СЕ 30Х Х Х Х Х Х

Interfaces and additional options:Y – bidirectional energy meteringJ – optical portNominal, base (maximum) curren:3 – 5 (10) А5 – 5 (60) А6 – 5 (100) АNominal voltage:0 – 3х57,7/100 V4 – 3х230/400 VActive/ Reactive energy measurement Accuracy class:0 – 0,5S1 – 15 – 0,5S/0,5 for СЕ3027 – 1/1 for СЕ302Case type and number:S33 – for 3-screws mountingR31 – for DIN-rail mountingElectric energy:0 – active2 – active and reactive

CE302 R31 543-JYCE302 R31 543-JCE302 R31 745-JCE302 R31 746-JCE302 S33 503-JCE302 S33 503-JYCE302 S33 543-JCE302 S33 543-JYCE302 S33 745-JCE302 S33 746-J

MOdificATiONS wiTH iNTERfAcES

ApplicATiONThree-phase meters is designed for direct or transformer connection, single-tariff metering of active and reactive electric energy in three-phase AC circuits.

RANgE Of uSE· Meter is designed for local operating.· CE300 meter is designed for active energy measurement.· CE302 meter is designed for active and reactive energy measurement.

fuNcTiONAl cApABiliTiES· Bidirectional energy metering.· LCD as a reading unit ensures reliable protection against any magnetic field influence.· Low values of starting current ensure high sensitivity of the meter.

OPTICAL PORT

MOdificATiONS wiTH iNTERfAcES

R33Case types:

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.22-2012 (IEC 62053-22:2003)

CE301THREE-PHASE MULTI-TARIFFACTIVE ENERGY METER

The meter is additionally replenished with a smaller terminal block cover

RS485

fuNcTiONAl cApABiliTiES· Two terminal block covers allow to mount meter as on a flat surface so on a DIN-rail.· Registration and storage of load profiles (60 minutes interval) for 255 days.· Modification with signalization relay (for control of external switching device).· Measurement and displaying of current value of current, voltage, frequency, power.· Power supply from both-phase (presence of one phase) and linear (zero wire breakthrough) voltage.· Power and consumption limit exceeding alarm, registration of the maximal power value per each tariff through the month and limit exceeding control with external relay switch by meter’s command. · Metering and indication of:– active electric energy consumption in total and separately for 4 tariffs at the end of a month and for 12 previous months;– active electric energy consumption in total and separately for 4 tariffs at the end of a day and for 129 previous days;– Memory protection against unauthorized modifications with buttons’ pressing or via interfaces (two passwords for two access levels).

RANgE Of uSE· Meter is designed for local operating.· Meter can be used as a part of AMR system for transition of collected parameters via wired RS485 interface.

· Metering by each phase separately:– active energy;– instant value of current;– instant of voltage;– instant value of network frequency;– instant value of power;– angle of phase displacement;– angle between current vector and phase voltage vector;– phase active power factor.· Event log recording of:– 100 corrections of time;– 100 changes of device settings;– 50 states of electronic seal;– 100 relay states;– 200 excesses of phase voltage operating values.

ApplicATiONThree-phase direct or transformer connection meter is designed for measurement of active electric energy, power, frequency, angle between vectors of phase voltages and vectors of phase current, RMS voltage value, current.

THRE

E-PH

ASE

MUL

TI-T

ARIF

FOPTICAL PORT

For overall dimensions see the Appendix

Page 13: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

24 25

SpEcificATiONSActive energy measurement Accuracy class Number of tariffs Network frequency Nominal voltageBase (max.) currentStarting current (sensitivity):for direct connection metersfor transformer connection metersStoring depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariffNumber of load profiles Load profile averaging time Every profile storing depthOperating temperature rangeOperating phase voltage range Overall dimensions

0,5S; 1 4 50±2,5 Hz3х230/400 V5 (10); 5 (60); 5 (100) А

20 mА5 mА129 days 37 monthsup to 2 (P+, P-) 1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 minutes255 days (averaging time – 60 minutes) from – 40 to +60 °С(0,75 … 1,15) Unom151,5 х 143 х 72,5 mm113 х 143 х 72,5 mm – with the smaller terminal cover

CE301 R33 043 JAZCE301 R33 043 JAQZCE301 R33 145 JAZCE301 R33 145 JAQZCE301 R33 146 JAZCE301 R33 146 JAQZ

BASic MOdificATiONS

For local operating

dESigNATiON STRucTuRE

СЕ 301 X X X X X...X

Additional options:J – optical portA – RS485Q – AC relay to control external commutation switchY – bidirectional energy meteringZ – extended parameters set

Nominal, base (maximum) current:3 – 5 (10) А5 – 5 (60) А6 – 5 (100) А

Nominal voltage:4 – 3х230/400 V

Active energy measurement accuracy class:0 – 0,5S1 – 1

Case type:R33 – for DIN-rail mounting

REliABiliTY ANd wARRANTYAverage time to failure Verification interval Warranty periodAverage service life

220 000 hours10 years4 years30 years

MOdificATiONS wiTH iNTERfAcES

S31Case types:

CE301THREE-PHASE MULTI-TARIFFACTIVE ENERGY METER

RS485 RF433 MHz PLC

fuNcTiONAl cApABiliTiES· Bidirectional electric energy measurement.· Registration and storage of load profiles (60 minutes interval) for 255 days.· Electronic seal of terminal block cover.· Metering and displaying of current, voltage frequency and power values.· Battery replacement without case opening and unscheduled verification of device.· Power supply from both - phase (presence of one phase) and linear (zero wire breakthrough) voltage.· Power and consumption limit exceeding alarm, registration of the maximal power value per each tariff through the month and limit exceeding control with external relay switch by meter’s command. · Metering and indication of:– active electric energy consumption in total and separately for 4 tariffs at the end of a month and for 12 previous months;– active electric energy consumption in total and separately for 4 tariffs at the end of a day and for 129 previous days.· Memory protection against unauthorized modifications with buttons’ pressing or via interfaces (two passwords for two access levels).

RANgE Of uSE· Meter can be used as a part of AMR system for measured or calculated parameters transmission to the control, metering and electric energy distribution center.· Meter can be used independently (locally) out of AMR system.

· Metering by each phase separately:– active energy;– instant value of current;– instant of voltage;– instant value of network frequency;– instant value of power;– angle of phase displacement;– angle between current vector and phase voltage vector;– phase active power factor.· Event log recording of:– 100 corrections of time ;– 100 changes of device settings;– 50 states of electronic seal;– 100 relay states;– 200 excesses of phase voltage operating values.

ApplicATiONThree-phase direct or transformer connection meter is designed for measurement of active electric energy, power, frequency, angle between vectors of phase voltages and vectors of phase current, RMS voltage value, current.

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.22-2012 (IEC 62053-22:2003)

OPTICAL PORT

For overall dimensions see the Appendix

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 14: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

26 27

CE301 S31 146 JAVZCE301 S31 146 JAVZ(12)

BASic MOdificATiONS

For local operating

dESigNATiON STRucTuRE

СЕ 301 X X X X X...X

Additional options:J – optical portA – RS485P – PLC-interfaceR1 – RF433 interface with built-in antennaR2 – RF433 interface with external antennaQ – external commutation switch controlY – bidirectional energy meteringV – electronic seal of terminal block coverQ – external commutation switch controlY – bidirectional energy meteringZ (12) – backup power supply and indicator backlight

Nominal, base (maximum) current:3 – 5 (10) А5 – 5 (60) А6 – 5 (100) А

Nominal voltage:0 – 3х57,7/100 V4 – 3х230/400 V

Active energy measurement accuracy class:0 – 0,5S1 – 1

Case type:S31 – for 3 screw mounting

Modifications with communication modulesCE301 S31 145 JPVZCE301 S31 146 JPVZCE301 S31 145 JPQVZ

SpEcificATiONSActive energy measurement accuracy class Number of tariffs Network frequency Nominal voltage Base (max.) currentStarting current (sensitivity):for direct connection metersfor transformer connection metersStoring depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariffNumber of load profiles Load profile averaging time Every profile storing depthOperating temperature rangeOperating phase voltage range Overall dimensions

0,5S; 1 4 50±2,5 Hz3х57,7/100; 3х230/400 V5 (10); 5 (60); 5 (100) А

20 mА5 mА129 days 37 monthsup to 2 (P+, P-) 1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 minutes255 days (averaging time – 60 minutes) from – 40 to +60 °С(0,75 … 1,15) Unom 212 х 177 х 73 mm

REliABiliTY ANd wARRANTYAverage time to failure Verification interval Warranty periodAverage service life

220 000 hours10 years4 years30 years

MOdificATiONS wiTH iNTERfAcES

Case type:

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)GOST 31819.22-2012 (IEC 62053-22:2003)

CE303THREE-PHASE MULTI-TARIFFACTIVE ANd REACTIVE ENERGY METER

The meter is additionally replenished with a smaller terminal block cover

RS485

fuNcTiONAl cApABiliTiES· Two terminal block covers allow to mount meter as on a flat surface so on a DIN-rail.· Registration and storage of load profiles (60 minutes interval) for 255 days.· Modification with signalization relay (for control of external switching device).· Measurement and displaying of current value of current, voltage, frequency, power.· Power supply from both – phase (presence of one phase) and linear (zero wire breakthrough) voltage· Power and consumption limit exceeding alarm, registration of the maximal power value per each tariff through the month and limit exceeding control with external relay switch by meter’s command · Metering and indication of:– active electric energy consumption in total and separately for 4 tariffs at the end of a month and for 12 previous months;– active electric energy consumption in total and separately for 4 tariffs at the end of a day and for 129 previous days;· Memory protection against unauthorized modifications with buttons’ pressing or via interfaces (two passwords for two access levels).

RANgE Of uSE· Meter is designed for local operating· Meter can be used as a part of AMR system for collected data transmission via RS485 wired interface.

· Metering by each phase separately:– active energy;– reactive energy;– instant value of current;– instant of voltage;– instant value of network frequency;– instant value of power;– angle of phase displacement;– angle between current vector and phase voltage vector;– phase active power factor.· Event log recording of:– 100 corrections of time; – 100 changes of device settings;– 50 states of electronic seal;– 100 relay states;– 200 excesses of phase voltage operating values.

ApplicATiONThree-phase direct or transformer connection meter is designed for measurement of active and reactive electric energy, power, frequency, active and reactive power factors, angle between vectors of phase voltages and vectors of phase current, RMS voltage value, current.

OPTICAL PORT

R33

For overall dimensions see the Appendix

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 15: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

28 29

SpEcificATiONSActive/reactive energy measurement accuracy classNumber of tariffs Network frequency Nominal voltageBase (max.) current Starting current (sensitivity):for direct connection metersfor transformer connection meters Storing depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariffNumber of load profiles Load profile averaging time Every profile storing depth Operating temperature rangeOperating phase voltage range Overall dimensions

0,5S/0,5; 1/1 4 50±2,5 Hz3х230 / 400 V5 (10); 5 (60); 5 (100) А

20 mА5 mА129 days 37 minutesup to 4 (P+, P-, Q+, Q-) 1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 minutes255 days (averaging interval – 60 minutes) from – 40 to +60 °С(0,75 … 1,15) Unom 151,5 х 143 х 72,5 mm113 х 143 х 72,5 mm – with the smaller terminal cover

CE303 R33 543 JAZCE303 R33 543 JAQZCE303 R33 745 JAZCE303 R33 745 JAZCE303 R33 746 JAQZ

BASic MOdificATiONS

For local operating

dESigNATiON STRucTuRE

СЕ 303 X X X X X...X

Additional options:J – optical portA – RS485Q – AC relay to control external commutation switchY – bidirectional energy meteringZ – extended parameters set

Nominal, Base (maximum) current, A:3 – 5 (10) А5 – 5 (60) А6 – 5 (100) А Nominal voltage:4 – 3х230/400 V Active energy measurement accuracy class:5 – 0,5S/0,57 – 1/1 Case type: R33 – for DIN-rail mounting

REliABiliTY ANd wARRANTYAverage time to failure Verification interval Warranty periodAverage service life

220 000 hours10 years4 years30 years

MOdificATiONS wiTH iNTERfAcES

S31Case type:

RS485 RF433 MHz PLC GSM/GPRS ЕTHERNET

fuNcTiONAl cApABiliTiES· Bidirectional electric energy metering.· Registration and storage of load profiles (60 minutes interval) for 255 days.· Electronic seal of terminal block cover.· Modification with signalization relay (for control of external switching device).· Measuring and displaying of current, voltage frequency and power values Power supply from both phase (1 phase) and phase-to-phase (zero wire disconnection) voltage.· Battery replacement without case opening and unscheduled verification of device.· Power and consumption limit exceeding alarm, registration of the maximal power value per each tariff through the month and limit exceeding control with external relay switch by meter’s command. · Metering and indication of:– active electric energy consumption in total and separately for 4 tariffs at the end of a month and for 12 previous months;– active electric energy consumption in total and separately for 4 tariffs at the end of a day and for 129 previous days.· Memory protection against unauthorized modifications with buttons’ pressing or via interfaces (two passwords for two access levels).

RANgE Of uSE· Meter can be used as a part of AMR system for measured or calculated parameters transmission to the control, metering and electric energy distribution center· The meter can be used independently (locally) out of AMR system.

· Metering by each phase separately:– active energy;– reactive energy;– instant value of current;– instant of voltage;– instant value of network frequency;– instant value of power;– angle of phase displacement;– angle between current vector and phase voltage vector;– phase active power factor;– reactive power phase index.· Event log recording of:– 100 corrections of time; – 100 changes of device settings;– 50 states of electronic seal;– 100 relay states;– 200 excesses of phase voltage operating values.

ApplicATiONThree-phase direct and transformer connection meter is designed for metering of active and reactive electric energy, power, voltage frequency, active and reactive power factor, angle between vectors of phase voltages and vectors of phase current, RMS voltage value, curren.

CE303THREE-PHASE MULTI-TARIFFACTIVE ANd REACTIVE ENERGY METER

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)GOST 31819.22-2012 (IEC 62053-22:2003)

OPTICAL PORT

For overall dimensions see the Appendix

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 16: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

30 31

SpEcificATiONSActive/ reactive energy measurement accuracy class Number of tariffs Network frequencyNominal voltageBase (max.) current Starting current (sensitivity):for direct connection meters for transformer connection metersStoring depth of daily energy, collected per tariffStoring depth of monthly energy, collected per tariffNumber of load profiles Load profile averaging time Every profile storing depth Operating temperature range Operating phase voltage range Overall dimensions

0,5S/0,5; 1/1 4 50±2,5 Hz3х57,7/100; 3х230/400 V5 (10); 5 (60); 5 (100) А

20 mА5 mА 129 days 37 monthsup to 4 (P+, P-, Q+, Q-) 1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 minutes255 days (averaging interval – 60 minutes)from – 40 to +60 °С(0,75 … 1,15) Unom 212 х 177 х 73 mm

dESigNATiON STRucTuRE

СЕ 303 Х X X X X...Х Х...Х

Designation of built-in communication module in accordance with normative and technical documentation (for P, R1, R2 modifications) Additional options:J – optical portA – RS485Р – PLCR1 – RF-interface with built-in antennaR2 – RF-interface with external antennaG – GSM/GPRS-modemT – EthernetQ – external commutation switch controlY – bidirectional energy meteringV – electronic seal of terminal blockZ (12) – backup power supply and indicator backlight

Nominal, base (maximum) current:3 – 5 (10) А5 – 5 (60) А6 – 5 (100) А

Nominal voltage:0 – 3 х 57,7/100 V4 – 3 х 230/400 V

Active energy measurement accuracy class:5 – 0,5S/0,57 – 1/1

Case type:S31 – for 3 screws mounting

REliABiliTY ANd wARRANTYAverage time to failureVerification intervalWarranty periodAverage service life

220 000 hours16 years4 years30 years

CE303 S31 503 JAQVZ CE303 S31 543 JAVZ(12) CE303 S31 503 JAQYVZ CE303 S31 543 JAYVZCE303 S31 503 JAVZ CE303 S31 745 JAQVZCE303 S31 503 JAVZ(12) CE303 S31 745 JAVZCE303 S31 503 JAYVZ

BASic MOdificATiONS

For local operating

Meters with communication modulesCE303 S31 503 JGVZ GS01CE303 S31 503 JGYQVZ GS01CE303 S31 503 JGYQVZ(12) GS01CE303 S31 543 JGQVZ(12) GS01CE303 S31 543 JGVZ GS01CE303 S31 543 JGVZ(12) GS01CE303 S31 543 JPQVZCE303 S31 543 JPVZCE303 S31 543 JPVZ(12)CE303 S31 543 JR1QVZ CE831M01.03CE303 S31 543 JR1VZ CE831M01.03CE303 S31 543 JR1VZ CE831M01.03 с CE901CE303 S31 543 JR2VZ CE831M02.03CE303 S31 543 JR2VZ CE831M02.03 с CE901CE303 S31 543-JTQVZ(12)CE303 S31 543 JR1VZ(12) CE831M01.03CE303 S31 543 JR2QVZ CE831M02.03CE303 S31 745 JGQVZ GS01CE303 S31 745 JGVZ GS01CE303 S31 745 JPVZCE303 S31 745 JR1VZ CE831M01.03CE303 S31 746 JGQVZ GS01CE303 S31 746 JGVZ GS01CE303 S31 746 JR1QVZ CE831M01.03CE303 S31 746 JR1QVZ CE831M01.03 сCE901CE303 S31 746 JR1QVZ(12) CE831M01.03CE303 S31 746 JR1VZ CE831M01.03CE303 S31 746 JR2QVZ CE831M02.03CE303 S31 746 JR2VZ CE831M02.03

CE303 S31 745 JAVZ(12)CE303 S31 503 JAYVZ(12) CE303 S31 746 JAQVZCE303 S31 543 JAQVZ CE303 S31 746 JAVZCE303 S31 543 JAQYVZ(12) CE303 S31 746 -JAVZ(12)CE303 S31 543 JAVZ

MOdificATiONS wiTH iNTERfAcES

S34Case type:

RS485 RF433 MHz PLC GSM/GPRS

fuNcTiONAl cApABiliTiES· Three-phase load control relay.· Registration and storage of load profiles (60 minutes interval) for 255 days.· Electronic seal of terminal block cover.· Measuring and display of current value of current, voltage, frequency, power.· Power supply from both-phase (presence of one phase) and linear (zero wire breakthrough) voltage.· Battery replacement without case opening and unscheduled verification of device.· Power and consumption limit exceeding alarm, registration of the maximal power value per each tariff through the month and limit exceeding control with external relay switch by meter’s command. · Metering and indication of:– active electric energy consumption in total and separately for 4 tariffs at the end of a month and for 12 previous months;– active electric energy consumption in total and separately for 4 tariffs at the end of a day and for 129 previous days.· Memory protection against unauthorized modifications with buttons’ pressing or via interfaces (two passwords for two access levels).· Metering by each phase separately:– active energy;– reactive energy;

RANgE Of uSEThe meter is designed for use as a part of AMR system for measured or calculated parameters transmission to the control center and remote control of consumer’s load

– instant value of current;– instant of voltage;– instant value of network frequency;– instant value of power;– angle of phase displacement;– angle between current vector and phase voltage vector;– phase active power factor;– phase reactive power factor.· Event log recording of:– 100 corrections of time; – 100 changes of device settings;– 50 states of electronic seal;– 100 relay states;– 200 excesses of phase voltage operating values.

ApplicATiONThree-phase direct connection meter is designed for measurement of active and reactive electric energy, power, frequency, angle between vectors of phase voltages and vectors of phase current, RMS voltage value, current.

ЕTHERNET

For overall dimensions see the Appendix

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)GOST 31819.22-2012 (IEC 62053-22:2003)

CE303THREE-PHASE MULTI-TARIFFACTIVE ANd REACTIVE ENERGY METER

OPTICAL PORT

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 17: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

32 33

SpEcificATiONSActive/reactive energy measurement accuracy class Number of tariffs Network frequency Nominal voltage Base (max.) current, Starting current (sensitivity) Storing depth of daily energy, collected per tariff Storing depth of monthly energy, collected per tariffNumber of load profiles Load profile averaging time Every profile storing depthOperating temperature rangeOperating phase voltage rangeOverall dimensions

1/1 4 50±2,5 Hz 3х230/400 V 5 (60) А; 5 (100) А20 mА129 days 37 monthsup to 4 (P+, P-, Q+, Q-) 1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 minutes255 days (averaging interval – 60 minutes) from – 40 to +60 °С(0,75 … 1,15) Unom280 х 175 х 85 mm

CE303 S34 745 JAQ2VZCE303 S34 745 JAQ2VZ(12)CE303 S34 746 JAQ2VZCE303 S34 746 JAQ2VZ(12)

CE303 S34 745 JGQ2VZ GS01CE303 S34 745 JGQ2VZ(12) GS01CE303 S34 745 JPQ2VZ PLC 1111CE303 S34 745 JR1Q2VZ CE831M01.03CE303 S34 745 JR1Q2VZ CE831M01.03 CЕ901CE303 S34 745 JR2Q2VZ CE831M02.03 CE901CE303 S34 745-JTQ2VZ(12)CE303 S34 745 JPQ2VZCE303 S34 745 JPQ2VZ(12)CE303 S34 746 JGQ2VZ GS01CE303 S34 746 JPQ2VZCE303 S34 746 JPQ2VZ PLC 1111CE303 S34 746 JR1Q2VZ CE831M01.03 CЕ901CE303 S34 746-JR1Q2VZ CE831M01.03

BASic MOdificATiONS

Meters for local operating

Meters with communication modules

dESigNATiON STRucTuRE

СЕ 303 X X X X X...X

Additional options:J – optical portA – RS485Р – PLCR1 – RF-interface with built-in antennaR2 – RF-interface with external antenna plugG – GSM/GPRST – EthernetQ2 – load control relayV – electronic seal of terminal blockZ (12) – backup power supply and indicator backlight

Nominal, base (maximum) current:5 – 5 (60) А6 – 5 (100) А

Nominal voltage:4 – 3х230/400 V

Active energy measurement accuracy class:7 – 1/1

Case type: S34 – for 3 screws mounting

REliABiliTY ANd wARRANTYAverage time to failureVerification intervalWarranty periodAverage service life

220 000 hours16 years4 years30 years

* СЕ901 – external indicating device

MOdificATiONS wiTH iNTERfAcES

S32Case type:

fuNcTiONAl cApABiliTiES· Bidirectional electric energy measurement.· Registration and storage of load profiles (60 minutes interval) for 512 days.· Two independent communication interfaces.· Self-testing of meter, clock, programs’ memory, data memory, power supply and informing about errors and bugs on the LCD or via communication interfaces.· Switching device control relay.· Meters provides the following programmable load control criteria: per tariff, by power limit and consumed energy, by a phase state, by time, by command via interface.· Metering of loses in the power lines of every electric energy direction with a glance to current transformation factor. · Ability to connect a backup battery.· Measurement and display of current value of current, voltage, frequency, power.· Metering and indication of:– apparent, active and reactive power consumption in total and separately for each phase; – RMS phase voltages per phase in voltage circuits;– RMS currents per phase in current circuits;– phase angle between phase voltages and currents fundamental harmonics;– phase angle between phase voltages fundamental harmonics;– active and reactive power factors per each phase (with aт off-the-ratio accuracy).

RANgE Of uSE· Meter can be used as a part of AMR system for measured or calculated parameters transmission to the control, metering and electric energy distribution center· Meter can be used independently (locally) out of AMR system.

· Metering of:– consumed and supplied active and reactive electric energy on a cumulative total or separately by 4 tariffs;– consumed and supplied active and reactive electric energy on a cumulative total if tariffing schedules have not been done or have been done incorrectly;– consumed and supplied active and reactive electric energy for the last 24 months;– consumed and supplied active and reactive electric energy for the last 45 days;– monthly maximal values of power by 4 tariffs with storage depth of 24 months.· Data memory and program memory protection against an unautho-rized modifications (password and sealed button).· Zeroing of all energetic parameters if the authorized access have been granted.· Event log recording of:– 40 last devices parameters corrections;– 40 last phase voltage changes with recording of parameters changing characteristic;– 40 last negative results of meter’s tests.· Summing up of impulses from 4 external devices (energy, water, gas meters, safety sensors or fire alarms) considering programmable transformation ratio for each input and metering on a cumulative total according to the tariff schedule;· 2 outputs for load control (if load control module is available).

ApplicATiONMeter is designed for measurement of active and reactive electric energy, active, reactive and apparent power, power factor, frequency, RMS voltage value and current in three-phase AC circuits and organization of multi-tariff electric energy metering.

СЕ304THREE-PHASE MULTI-TARIFFACTIVE ANd REACTIVE ENERGY METER

RS232 RS485 GSM/GPRS2хRS485 2хRS232

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)GOST 31819.22-2012 (IEC 62053-22:2003)

OPTICAL PORT

For overall dimensions see the Appendix

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 18: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

34 35

SpEcificATiONSActive/reactive energy measurement accuracy class Number of tariffsNetwork frequency Nominal voltageBase (max.) currentStarting current (sensitivity) For direct connection metersFor transformer connection metersStoring depth of daily energy, collected per tariffNumber of load profilesLoad profile averaging timeEvery profile storing depthOperating temperature range Operating phase voltage range Overall dimensions

0,2S /0,5; 0,5S/1; 1/24 50±2,5 Hz3х57,7/100 V; 3х220/380 V1 (1,5); 5 (7,5); 5 (50); 10 (100) А

20 mА5 mА45 days up to 4 (P+, P-, Q+, Q-) 1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 minutes512 days (averaging time – 60 minutes) from – 40 to +60 °С(0,7 … 1,15) Unom 277,5 х 173 х 89 mm

CE304 S32 402-JAAQ2HYCE304 S32 402-JAEQ2HYCE304 S32 602-JAAQ2HYCE304 S32 602-JAEQ2HYCE304 S32 632-JAAQ2HYCE304 S32 834-JAAQ2HYCE304 S32 834-JAEQ2HYCE304 S32 838-JAAQ2HYCE304 S32 838-JAEQ2HYCE304 S32 432-JAAQ2HY

BASic MOdificATiONSdESigNATiON STRucTuRE

СЕ 304 Х Х Х Х - Х...Х Х...Х

Additional options:Q2 – external commutation switch control relay H – pulse inputsY – bidirectional energy metering

Interfaces:J – оптопорт A – RS485E – RS232G – GSM/GPRS

Nominal, base (maximum) current:0 – 1 (1,5) А2 – 5 (7,5) А4 – 5 (50) А8 – 10 (100) А

Nominal voltage:0 – 3х57,7/100 V3 – 3х220/380 V

Active/reactive energy measurement accuracy class:4 – 0,2S/0,56 – 0,5S/18 – 1/2

Case type:S32 – for 3 screws mounting

MOdificATiONS wiTH iNTERfAcES

R33Case type:

CE307THREE-PHASE MULTI-TARIFFACTIVE ENERGY METER

RS485

fuNcTiONAl cApABiliTiES· Electric energy measurement by 4+1 (emergency) tariffs with an ability to set up to sixteen tariff zones per one day with discreteness of one minute individually for each day of the week inside the season program.· Modifications as with optical port only so with optical port and RS485-interface.· Ability to mount on a flat surface.· Total modifications list for connection current of 5-10 A, 5-60 A, 10-100 A.· Additional 5th emergency tariff.· Power control function.· Logging of active energy consumption data per 4+1 tariffs in total and on a cumulative total.· State/event logs recording, parameters programming log recording. Registration of events and date/time when events occurred.· Unauthorized modifications password protection.

· Metering and indication of:– active energy consumption on a cumulative total and separately on 4+1 tariffs for the end of the month and for12 previous month;– active energy consumption on a cumulative total and separately on 4+1 tariffs for the end of the day and for 36 previous days.· The meter allows to set the following parameters:– up to 12 season programs;– up to 32 exclusion days (days in which tariffing is different and is set by user);– up to 36 daily schedules.· Manual time correction up to 29 seconds per day.· Information storage duration without power supply – up to 30 years.

ApplicATiONThree-phase, transformer or direct connection meter is designed for active electric energy measurement.

RANgE Of uSE· Meter is designed for local operating.· Meter can be used as a part of AMR system for measured or calculated parameters transmission via RS485 interface.

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)

REliABiliTY ANd wARRANTYAverage time to failureVerification intervalWarranty periodAverage service life

220 000 hours8 years4 years30 years

For overall dimensions see the Appendix

OPTICAL PORT

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 19: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

36 37

SpEcificATiONSAccuracy class Number of tariffs Network frequency Nominal voltage Base (max.) current, Starting current (sensitivity) For direct connection meters For transformer connection meters Operating temperature range Operating phase voltage range Overall dimensions

0,5s, 14+1 (emergency)50±2,5 Hz3*230/400 V5 (10); 5 (60); 5 (100) А

10, 20 mА5 mАfrom – 40 to +70 °С(0,7…1,15) Unom 151,5 x 143 x 72,5 mm

dESigNATiON STRucTuRE

CE307 R33. XXX.0X.X

Interfaces and additional options:N – interface external power supplyА – RS485О – optical port

Nominal, base (maximum) current:3 – 5 (10) – transformer connection5 – 5 (60) – direct connection6 – 5 (100) – direct connection

Nominal voltage:4 – 230/400 V

Accuracy class:0 – 0,5 S1 – 1

Case type:R33 – for DIN-rail mounting

220 000 hours16 years4 years30 years

CE307 R33.043.OCE307 R33.043.ОA.NCE307 R33.145.ОCE307 R33.145.ОA.NCE307 R33.146.ОCE307 R33.146.ОA.N

BASic MOdificATiONS

REliABiliTY ANd wARRANTYAverage time to failureVerification intervalWarranty periodAverage service life

MOdificATiONS wiTH iNTERfAcES

C36Case type:

RS485 RF433 MHz

fuNcTiONAl cApABiliTiES· DLP data exchange protocol support.· Multi-tariff electric energy measurement.· Power line pole mounting without additional protection.· Three communication channels:– 434 MHz RF-interface is designed for meter operating as a part of AMR system;– 868 MHz RF-interface is designed for data exchange with CE901 RUP-02 meter reading device (MRD);– PLC interface is designed for data exchange with CE901 RUP-02 meter reading device (MRD).· Consumer’s load control relay.· Lithium element exchange without case opening and doesn’t require to record date and time.· CE901 RUP-02 meter reading device (MRD).· Terminal cover opening control.· Magnetic field influence control.· Network parameters measurement:– frequency;– phase currents;– phase voltages;– angle between current and voltage by phases;

– active power per phase and in total;– reactive power per phase and in total;– apparent power per phase and in total.· «Instantaneous power» consumption control.· Archive logging by the end of a billing period (day, month, year) for all phases in total and for the end of the day separately per each phase.· Recording of active and reactive energy profiles, with an ability to set the averaging time.· Apparent, active and reactive power control.· Phase voltages control.· Phase currents control.· Network frequency control.· Phase interlacing control.· Phase wire breakthrough control.· Zero wire breakthrough control.· Self-testing.· Information protection. · Load switching off in case of: network frequency deviation, voltage per each phase deviation, each phase current limit exceeding, active power consumption limit exceeding; or direct switching off via communication interface.

ApplicATiONThe meter is designed for active and reactive energy measurement, organization of single- or multi-tariff electric energy metering.

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)

RF868 MHz

RANgE Of uSE· Meter is designed for use as a part of AMR system for measured or calculated parameters transmission to control center, and for the remote control of consumer’s load.· Meter has a split design and is dedicated for the mounting in the industrial objects, sub-stations, etc.· The meter can be used independently (out of AMR system).

CE308THREE-PHASE MULTI-TARIFFACTIVE ANd REACTIVE ENERGY METER

For overall dimensions see the Appendix

OPTICAL PORT

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 20: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

38 39

SpEcificATiONSActive/reactive energy accuracy class Number of tariffs Network frequency Nominal voltage Base (max.) current Starting current (sensitivity) Storing depth of daily energy, collected per tariff Storing depth of monthly energy, collected per tariff Load profile averaging time Operating temperature range Overall dimensions, do not exceeOperating phase voltage range Ingress protection class

1/1450±2,5 Hz3*230/400 V5 (100) А10 mА128 days36 months1; 3; 5; 10; 15; 30; 60 minutesfrom – 40 to +70 °С270 x 189 x 76 mm(0,55…1,15) UnomIP64

CE308 C36.746.OPR1.QYVF RP03 DLPCE901 RUP-02 – indicating device

BASic MOdificATiONSdESigNATiON STRucTuRE

CE 308 C36 XXX XXX XXX X

Designation of communication modules:RP03 – Combined module

Additional options:Q – switching off relayY – bidirectional energy meteringD – CE901 RUP-02 meter reading device includedV – Terminal cover opening controlF – magnetic field sensor

Interfaces:O – optical portP – PLC-интерфейсR1 – RF-interface with built-in antenna

Nominal, Base (maximum) current: 6 – 5 (100) A

Nominal voltage:4 – 230/400 V

Accuracy class: 7 – 1/1

Case type: C36 – for outdoor mounting

REliABiliTY ANd wARRANTYAverage time to failureVerification intervalWarranty periodAverage service life

220 000 hours16 years4 years30 years

MOdificATiONS wiTH iNTERfAcES

R33Case type:

CE308 DLMS THREE-PHASE MULTI-TARIFFACTIVE ANd REACTIVE ENERGY METER

fuNcTiONAl cApABiliTiES· Multi-tariff electric energy measurement with a wide range of tariff schedule settings.· Bidirectional active and reactive energy metering.· Support of GOST IEC 61107-2011 and DLMS/COSEM data exchange protocols.· Flexible adjustment of reaction to the events occurring in the meter.· Electric energy quality measurement:– voltage deviation;– network frequency deviation;– duration and depth of power failure;– duration and maximal value of overvoltage;– blackouts.· Load profile logging, with an ability to set the type of parameters to save and averaging time for registration.· Network parameters metering:– voltage frequency;– currents;– voltages;– angles between current and voltage;– power factor;– active power;– reactive power;– apparent power.

· Active power consumption control.· «Instantaneous power» consumption control.· Active energy consumption control.· Voltage of power supply control.· Network frequency control.· Signalization relay.· Unauthorized opening protection (electronic seals).· Magnetic field sensor.· Control of phase interlacing succession.· Phase breakthrough control.· Data logging for:– measured data registration (total and per tariff) for active and reactive energy by day changing;– measured data registration (total and per tariff) for active and reactive energy by month changing (with programmable date when the billing period ends);– measured data registration (total and per tariff) for active and reactive energy by year changing;– measured data registration (total and per tariff) for active and reactive energy per event or command.· Load control by external switching unit.· Sound alarm.· Self-testing.· Displaying of data supported by OBIS codes.

ApplicATiONThree-phase transformer or direct connection meter is designed for active and reactive electric energy measurement and organization of multi-tariff electric energy metering.

RANgE Of uSE· Meter can be used as a part of AMR system for measured parameters transition to the control, metering and electric energy distribution center· Meter can be used independently (out of AMR system).

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)GOST 31819.23-2012 (IEC 62053-23:2003)

R32

For overall dimensions see the Appendix

RS485OPTICAL PORT

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 21: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

40 41

SpEcificATiONSActive/reactive energy accuracy class Number of tariffs Network frequency Nominal voltage Base (max.) current Starting current -for direct connection meters -for transformer connection metersStoring depth of daily energy, collected per tariff Storing depth of monthly energy, collected per tariff Load profile averaging timeOperating temperature range Operating phase voltage range (min. - max.)

Overall dimensions, do not exceed

0,5s/0,5; 1/1up to 8 50±2,5 Hz3*57,7/100; 3*230/400 V5 (10); 5 (60); 5 (100) А

10 mА5 mА128 days40 months1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 minutesfrom – 40 to +70 °C 34,5…66,4 V172...264,5 V170 x 141,5 x 52,5 mm – for R32 case151,5 x 143 x 72,5 mm – for R33 case

dESigNATiON STRucTuRE

CE308 X XXX XXX XXX X

Designation of built-in communication module (if any) in accordance with normative and technical documentation (for P, R1, R2 modifications), and protocol designation

Additional options:S – signalization relayY – bidirectional energy meteringU – network quality parametersL – LCD backlightF – magnetic field sensorN – interface external power supplyZ – extended parameters set

Interfaces:O – optical portА – RS485

Nominal, base (maximum) current:3 – 5 (10) А5 – 5 (60) А6 – 5 (100) А

Nominal voltage:0 – 3x57,7/100 V4 – 3x230/400 V

Accuracy class:5 – 0,5S/0,57 – 1/1

Case type and number:R32, R33 – for DIN-rail mounting

MOdificATiONS wiTH iNTERfAcES

S34

fuNcTiONAl cApABiliTiES· Multi-tariff electric energy measurement with a wide range of tariff schedule settings.· Bidirectional active and reactive energy measurement.· Support of GOST IEC 61107-2011 and DLMS/COSEM data exchange protocols.· Flexible adjustment of reaction to the events occurring in the meter.· Electric energy quality measurement:– voltage deviation;– network frequency deviation;– duration and depth of power failure;– duration and maximal value of overvoltage;– blackouts.· Load profile logging, with an ability to set the type of parameters to save and averaging time for registration.· Network parameters metering:– voltage frequency;– currents;– voltages;– angles between current and voltage;– power index;– active power;– reactive power;– apparent power.

· Active power consumption control.· «Instantaneous power» consumption control.· Active energy consumption control.· Voltage of power supply control.· Network frequency control.· Signalization relay.· Unauthorized opening protection (electronic seals).· Magnetic field sensor.· Data logging for:– measured data registration (total and per tariff) for active and reactive energy by day changing;– measured data registration (total and per tariff) for active and reactive energy by month changing (with programmable date when the billing period ends);– measured data registration (total and per tariff) for active and reactive energy by year changing;– measured data registration (total and per tariff) for active and reactive energy per event or command.· Load control by external switching unit.· Sound alarm.· Self-testing.· Displaying of data supported by OBIS codes.

ApplicATiONThree-phase transformer or direct connection meter is designed for active and reactive electric energy measurement and organization of single- and multi-tariff electric energy metering.

GOST 31818.11-2012 (IEC 62058-11-2012)GOST 31819.21-2012 (IEC 62058-21-2012)

RANgE Of uSE· Meter can be used as a part of AMR system for measured parameters transition to the control, metering and electric energy distribution center.· Case type is designed for the installation on the mounting surface.

RS485 PLC GSM/GPRS ЕTHERNET

S31

REliABiliTY ANd wARRANTYAverage time to failureVerification intervalWarranty periodAverage service life

220 000 hours16 years4 years30 years

For overall dimensions see the Appendix

Case type:

CE308 DLMS THREE-PHASE MULTI-TARIFFACTIVE ANd REACTIVE ENERGY METER

OPTICAL PORT

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 22: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

42 43

dESigNATiON STRucTuRE

CE308 X X X X XXX XXX XXX

Designation of built-in communication module (if any) in accordancewith normative and technical documentationAdditional options:Q – consumption load control relayS – signalization relayY – bidirectional energy meteringD – external displayU – network quality parametersV – electronic seals J – ability to connect a backup power supply L – LCD backlightF – magnetic field sensorZ – extended parameters setInterfaces:O – optical portA – RS485P – PLCG – GSMN – EthernetNominal, Base (maximum) current:3 – 5 (10) А5 – 5 (60) А6 – 5 (100) АNominal voltage:0 – 3x57,7/100 V4 – 3x230/400 VAccuracy class for active/reactive energy:5 – 0,5S/0,57 – 1/1Case type and number:S31, S34 – for board mounting

SpEcificATiONSActive/reactive energy metering accuracy class Number of tariffs Network frequency Nominal voltage Base (max.) current Starting current – for direct connection meters – for transformer connection metersStoring depth of daily energy, collected per tariff Storing depth of monthly energy, collected per tariff Load profile averaging timeOperating temperature range Operating phase voltage range (min.-max.)

Overall dimensions, do not exceed

0,5s/0,5; 1/18 50±2,5 Hz3*57,7/100; 3*230/400 V5 (10); 5 (60); 5 (100) А

10 mА5 mА128 days40 months1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 minutesfrom – 40 to + 70 °C 34,5…66,4 V172...264,5 V215 x 175 x 72 mm – for S31 case280 x 175 x 85 mm – for S34 case

CASES’ dIMENSIONAL dRAwINGS

Appendix

95

89...103115

170

53

125.

..140

210,

5 147.

..215

145...159

7

71,5175

95173 89

100

144...156

210.

..221

277,

5

9227

61

7

145

169

143...155

150

– 23

0

623

5

70

175 85

154

6

220-

235

280

12

89,5 44659

4510

,510

5

36

104 ± 2

15,5

185

124

110

1114

0.. 1

55

103 ± 5

62

APPE

NDI

x

REliABiliTY ANd wARRANTYAverage time to failureVerification intervalWarranty periodAverage service life

220 000 hours16 years4 years30 years

For overall dimensions see the Appendix

Case type S6 Case type S7 Case type S8

Case type S31 (Ш31) Case type S10 Case type R5.1

Case type S33 (Ш33) Case type S34 Case type S32

THRE

E-PH

ASE

MUL

TI-T

ARIF

F

Page 23: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

44

Case type R33

140

6449

50

9095

30

200

155

110

55

4466,572,5

89

143

89

110

55

6 66,542,2

Case type R31

141 52

34

170

Case type R32 (P32)

Case type C2

Case type R5

Case type C36

280

188,8

98,5*

76,3

APPE

NDI

x

CASES’ dIMENSIONAL dRAwINGS

Page 24: CATALOGUE - torgpredstvo.rstorgpredstvo.rs/kontent/kom_326/1.pdf · 6 7 SpEcificATiONS Active energy measurement accuracy class Network frequency Nominal voltage Base (max.) current

+7 (800) [email protected]

vk.com/energomera.ru facebook.com/energomera.ru twitter.com/energomera_ru youtube.com/user/energomera.ru

Designed and manufactured by Energomera in Russia