Power Transmission and Distribution
Catalog HA 41.11 · 2007
Switchgear Type 8DH10up to 24 kV, Gas-Insulated, Extendable
Medium-Voltage Switchgear
2 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
FeaturesPage
8DH10 switchgear is a factory-assembled, type-tested, three-pole,metal-enclosed, metal-clad single-busbar switchgear for in-door in-stallation:
• Up to 24 kV
• Feeder currents up to 630 A
• Busbar currents up to 1250 A
Typical uses
8DH10 switchgear is used – evenunder severe environmental con-ditions – for power distribution insecondary distribution systems,such as
Substations, customer transfersubstations, distribution sub-stations and switching substa-tions of power supply andpublic utilities
Industrial plants, such as:
• Wind power stations
• High-rise buildings
• Airports
• Lignite open-cast mines
• Underground railway stations
• Sewage treatment plants
• Port facilities
• Traction power supply systems
• Automobile industry
• Petroleum industry
• Chemical industry
• Cement industry
• Unit-type heating power stations
• Textile, paper and foodindustry
• Emergency power supplyinstallations
Modular design
• Individual panels and panelblocks can be freely combinedand extended – without gas workon site
• Low-voltage compartments canbe supplied in two overall heightsand are wired to the panel bymeans of plug-in connections
Reliability
• Type and routine-tested
• Standardized and manufacturedusing numerically controlledmachines
• More than 430,000 8DJ/8DHpanels in operation worldwidefor many years
Quality and environment
Quality and environmentalmanagement system acc. toDIN EN ISO 9001 andDIN EN ISO 14001
Personal safety
• Safe-to-touch and hermeticallysealed primary enclosure
• HV HRC fuses and cable sealingends are only accessible whenoutgoing feeders are earthed
• Operation only possible whenenclosure is closed
• Logical mechanical interlocking
• Capacitive voltage detecting sys-tem to verify safe isolation fromsupply
• Feeder earthing by means ofmake-proof earthing switches
Security of operation
• Hermetically sealed primaryenclosure independent ofenvironmental effects (such aspollution, humidity and small ani-mals) – sealed for life:
– Welded switchgear vessel– Welded-in bushings and operating
mechanism
• Operating mechanism partsmaintenance-free(IEC 60 694 / VDE 0670-1000)
• Operating mechanisms of switch-ing devices located outside theswitchgear vessel (primary enclo-sure)
• Switchgear interlocking systemwith logical mechanical interlocks
• Mechanical switch-positionindicators integrated in themimic diagram
Cost-efficiency
Extremely low “life-cycle costs”throughout the entire productservice life as a result of:
• Maintenance-free concept
• Climatic independence
• Minimum space requirements
• Maximum availability
Security of investment
Innovative developments, such as:
• Modular design
• Switchgear extension without gaswork on site
• Maintenance-free 3AH vacuumcircuit-breaker
• SIPROTEC protection device family
Application, Requirements
Features, typical uses 2 and 3
Technical Data
Electrical data, filling pressure,temperature 4 and 5
Switchgear installation, shipping data 6 and 7
Product Range
Product range overview 8 to 15
Design
Panel design 16 and 17
Components
3AH vacuum circuit-breaker 18 and 19
Three-position switch-disconnector 20
Busbars 21
Transformers 22 to 27
Cable connection 28
Low-voltage equipment 29
Dimensions
Individual panels, panel blocks 30 to 34
Metering panel combinations 33 and 35
Floor openings and fixing points 36 to 39
Cable connection examples 40
Standards, Transport, Notes
Standards, specifications, guidelines 41
Transport data, classification 42
Notes 43
For further information, please refer to
• Catalog HA 40.1: (Switchgear Type 8DJ and 8DH,General Part)
• Supplements to Catalogs HA 45.31/41.11
Invalid: Catalog HA 41.11 · 2006
Application, RequirementsContents
© Siemens AG 2007
The products and systems described in this catalog aremanufactured and sold according to certified qualityand enviromental management system (acc. ISO 9001and ISO 14001).(DQS Certificate Reg. No. DQS 003473 QM UM).The certificate is accepted in all IQNet countries.
Siemens HA 41.11 · 2007 3
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Technology
• Maintenance-free
• Climate-independent
• Partition class: Class PM(metallic partition)
• Three-pole primary enclosure,metal-enclosed
• Insulating gas SF6
• Welded switchgear vessel withoutseals, made of stainless steel,with welded-in bushings for elec-trical connections and mechanicalcomponents
• Three-position switch-discon-nector with load-break andmake-proof earthing function
• Cable connection for bushingswith outside cone
• Connection with cable plugs– In ring-main feeders and
circuit-breaker feeders withbolted contact (M16)
– In transformer feeders withplug-in contact
• Option: Connection with conven-tional cable sealing ends
– For thermoplastic-insulatedcables via elbow adapterAKE 20 / 630 (make Siemens)
– For paper-insulated mass-impregnated cables via commer-cially available adapter systems
• Easy installation
• Option: Pressure absorber system– Maintenance-free– For rated short-time withstand
current Ik � 20 kA– For single and multi-panel
combinations of 700 mm to2000 mm width (for panel typeME1 with max. 1 adjacent panel)
– With 300 mm high pressure ab-sorber duct below the switchgearand
– With 115 mm deep pressureabsorber duct for pressure reliefupwards
– With screwed-on cablecompartment cover
– Possible for switchgear with stand-ard cable compartment coverOption: Deeper cable compart-ment cover: 105 or 300 mm
– For overall height of switchgear,see page 6
– Option: Free-standing arrange-ment, for overall height ofswitchgear 2300 mm and withrear cover
For further information concerningthe pressure absorber system,please refer to page 39and to Catalog HA 40.1
Standards
See page 41
ExampleCustomer transfer switchgear
ApplicationCustomer transfer substation in anaccessible switchgear building(transformers, medium-voltage andlow-voltage in a factory-assembledbuilding)
ApplicationPower supply of high-rise buildings
R-H
A4
1-0
15
ep
s
R-H
A4
1-0
14
ep
s
R-H
A4
1-0
13
ae
ps
Application
Typical uses
4 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Technical Data
Electrical data
Commonelectrical data
Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24
Rated short-dur. power-freq. withstand voltage Ud:– phase-to-phase, phase-to-earth, open contact gap kV– across the isolating distance kV
2023
28 1)
32 1)3639
3845
5060
Rated lightning impulse withstand voltage Up:– phase-to-phase, phase-to-earth, open contact gap kV– across the isolating distance kV
6070
75 1)
85 1)95110
95110
125145
Rated frequency fr 50/60 Hz
Rated normal current Ir2) for busbar (standard) up to A 630 630 630 630 630
for busbar (option) *) A 1250 1250 1250 1250 1250
Filling pressure,temperature,partition classandclassification
Rated filling level pre for insulation 150 kPa (absolute) at 20 °C
Min. functional level pme for insulation 130 kPa (absolute) at 20 °C
Ambient air temperature T 3) Panels without secondary equipment Class “Minus 25 indoor” (-25 to +70 °C 4))
Panels with secondary equipment, Classcircuit-breaker panels
“Minus 5 indoor” (-5 to +55 °C 4))
Partition class Class PM (metallic partition)
Loss of servicecontinuity category 5)
LSC (loss of service continuity) LSC 2
Panel data
Ring-main paneltype RK,bus sectionalizerpanel type LT2,cable paneltype K
Rated normal current Ir2) for feeder (for panel types RK ... and K ...) A 400, 630 400, 630 400, 630 400, 630 400, 630
for bus sectionalizer panel type LT2 A 400, 630 400, 630 400, 630 400, 630 400, 630
Rated short-timewithstand current Ik
for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
for switchgear with tk = 3 s (option) up to kA – – 20 – 20 – 20 – 20
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
Transformerpanel type TR
Rated normal current Ir2) for feeder 6) A 200 200 200 200 200
Rated short-timewithstand current Ik
for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
for switchgear with tk = 3 s up to kA – – 20 – 20 – 20 – 20
Rated peak withstand current Ip6) up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima6) up to kA 25 25 25 25 25 25 25 25 25
Reference dimension “e“ of the HV HRC fuse links mm 292 7) 292 442 442 442
Circuit-breakerpanel type LS,bus sectionalizertype LK/LT1
Rated normal current Ir2) for feeder (for panel types LS ...) A 400, 630 400, 630 400, 630 400, 630 400, 630
for bus sectionalizer panel type LT1 A 400, 630 400, 630 400, 630 400, 630 400, 630
Rated short-timewithstand current Ik
for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
for switchgear with tk = 3 s up to kA – – 20 – 20 – 20 – 20
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit breaking current Isc8) up to kA 20 25 20 25 20 25 20 25 20
Electrical service life of3AH vacuum circuit-breakers
at rated normal current 10 000 operating cycles
at rated short-circuit breaking current 50 breaking operations
*) Not for billing meteringpanels type ME1
1) According to some national require-ments, higher values of the ratedshort-duration power-frequencywithstand voltage available forIk = 20 kA with:� 42 kV for phase-to-phase,
phase-to-earth and open contactgap as well as
� 48 kV across the isolating distanceHigher values of the rated lightingimpulse withstand voltage(for IK = 20 kA) :� 95 kV for phase-to-phase,
phase-to-earth and open contactgap as well as
� 110 kV across the isolatingdistance
2) The rated normal currents applyto ambient air temperatures ofmax. 40 °C. The 24-hour meanvalue is max. 35 °C (according toIEC 60 694 / VDE 0670-1000)
3) Operating conditions according toIEC 62 271-200.For application, see also pages2 and 41 (climate and ambientconditions)
4) Temperature range, reducednormal currents at ambient airtemperatures > +40 °C
5) Classification according toIEC 62 271-200 (see also page 42)
6) Depending on the HV HRC fuse link,observe the max. let-throughcurrent of the HV HRC fuse links
7) Extension tube (150 mm long)required additionally for fusemounting 442 mm
8) For the 3AH vacuum circuit-breaker
Siemens HA 41.11 · 2007 5
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Electrical data
*) Not for billing meteringpanels type ME1
1) According to some national require-ments, higher values of the ratedshort-duration power-frequencywithstand voltage available forIk = 20 kA with:� 42 kV for phase-to-phase,
phase-to-earth and open contactgap as well as
� 48 kV across the isolating distanceHigher values of the ratedlighting impulse withstandvoltage (for Ik = 20 kA):� 95 kV for phase-to-phase,
phase-to-earth and open contactgap as well as
� 110 kV across the isolatingdistance
2) The rated normal currents applyto ambient air temperatures ofmax. 40 °C. The 24-hour meanvalue is max. 35 °C (according toIEC 60 694 / VDE 0670-1000)
3) Operating conditions according toIEC 62 271-200.For application, see also pages2 and 41 (climate and ambientconditions)
4) Temperature range, reducednormal currents at ambient airtemperatures > +40 °C
5) Classification according toIEC 62 271-200 (see also page 42)
Commonelectrical data
Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24
Rated short-dur. power-freq. withstand voltage Ud:– phase-to-phase, phase-to-earth, open contact gap kV– across the isolating distance kV
2023
28 1)
32 1)3639
3845
5060
Rated lightning impulse withstand voltage Up:– phase-to-phase, phase-to-earth, open contact gap kV– across the isolating distance kV
6070
75 1)
85 1)95110
95110
125145
Rated frequency fr 50/60 Hz
Rated normal current Ir2) for busbar (standard) up to A 630 630 630 630 630
for busbar (option) *) A 1250 1250 1250 1250 1250
Filling pressure,temperature,partition classandclassification
Rated filling level pre for insulation 150 kPa (absolute) at 20 °C
Min. functional level pme for insulation 130 kPa (absolute) at 20 °C
Ambient air temperature T 3) Panels without secondary equipment Class “Minus 25 indoor” (-25 to +70 °C 4))
Panels with secondary equipment, Classcircuit-breaker panels
“Minus 5 indoor” (-5 to +55 °C 4))
Partition class Class PM (metallic partition)
Loss of servicecontinuity category 5)
LSC (loss of service continuity) LSC 2
Panel data
Busbar earthingpaneltype SE,busbar voltagemetering paneltype MS1V/ME3
Rated short-timewithstand current Ik
for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
for switchgear with tk = 3 s (option) up to kA – – 20 – 20 – 20 – 20
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
Billing meteringpanelstypes ME1and ME2
Rated normal current Ir2) for transfer up to A 630 630 630 630 630
for feeder (T with cable panel as type ME1-K) up to A 630 630 630 630 630
for busbar metering up to A 630 630 630 630 630
Rated short-timewithstand current Ik
for switchgear with tk = 1 s up to kA – 25 20 25 20 25 20 25 20
for switchgear with tk = 3 s up to kA 20 – 20 – 20 – 20 – 20
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Technical Data
6 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Switchgear installation
Room planning
Switchgear installation
Wall-standing arrangement– Single row– Double row (for face-to-face
arrangement)Option: Free-standingarrangement
For room planning andswitchgear installation, pleasenote:– Floor openings: Dimensions
see pages 36 to 39– Direction of pressure relief
acc. to serial no. 13– Respective pressure relief
rooms
Room dimensions see oppositedimension drawings
Door dimensions
The door dimensions dependon the– Number of panels in a
transport unit– Design with or without
low-voltage compartment
Switchgear fastening
• For floor openings and fixingpoints of the switchgear,see pages 36 to 39
• Foundations:– Steel structure– Steel-reinforced concrete
Panel dimensions see p. 30 to 34
Weight
For details, please refer to page 7.
����
����
��
�
��������
���������
���
����
�� ���
���
�� ���
�����
���
����
�
��
�
�
�
�
�
��
�
���
�
��
�
��
��
��
Top view Top view
Side view Side view
����
�
�
���
����
����
����
�
���
���
���
������
���
���
����
�����
����
��
��
��
��
��
��
��
��
��
Cable basement
Switchgear room Switchgear room
Technical Data
Switchgear installation withstandard panels
Switchgear installation with rear-sidepressure absorber duct (option)
1 Relief opening
2 Opening (e.g. for ventilationas option)
3 Room height
4 Panel depth of the standardpanel (may be 15 mm deeperfor free-standing arrangement,depending on the panel design)
5 Control aisle �
6 Panel depth of panels withdeep cable compartmentcover
7 Deep cable compartmentcover
8 Standard cable compartmentcover
17 Depth of the pressure absorberduct behind the panel
18 Wall distance
19 End wall
20 Panel width
21 Width of the pressure absorber duct– 700 mm for panel combinations– Approx. 850 mm for metering
panels type ME1
22 Standard:Low-voltage compartmentfor circuit-breaker panels
Option:– Low-voltage compartment
for all other panel types or– Front cover
23 Relief outlet
9 Foundation
10 2nd cable for connection withof double T-plugs in conjunc-tion with larger floor openingand design with deep cablecompartment cover
11 Height of the cablebasement corresponding tothe cable bending radius
12 Cable
13 Direction of pressure relief
14 Floor openings:Dimensions see pages 34 to 37
15 Option:Pressure absorber duct
16 Base height of the pressureabsorber duct beneath thepanel
* Switchgear height for version withpressure absorber duct:– For wall-standing arrangement
W 1950 mm (panel combinationwithout metering panel ME1)W 2300 mm (for combinationwith metering panel ME1)
– For free-standing arrangementW 2300 mm (high end walls, rearwall and front covers, optionallow-voltage compartment)
** Installation conditions for internalarc classification acc. toIEC 62 271-200
*** Height of pressure absorber duct2100 mm with:– Wall-standing arrangement with
metering panel ME1– Free-standing arrangement for all
panel types
B Depending on nationalspecifications:– For extension/panel replacement:
Control aisle W 1000 mmrecommended (for GermanyW 800 mm)
Cable basement
Siemens HA 41.11 · 2007 7
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Technical Data
Shipping data
Transport units for shipping (top view)
With individual panelor panel block
With combinations of different individualpanels and/or panel blocks(option: Panels bolted together and busbars mounted)
1 T1 = Depth of individualpanel or of panel block
2 Individual panel or panelblock, dimension B1 x T1
3 Transport unit,dimension B2 x T2
4 B3 = Overall width ofcombination of differentindividual panelsor panel blocks
5 B2 = Width of thetransport unit
1) The net weight and the grossweight depend on the extent towhich they are equipped (e.g. withcurrent transformers, motor oper-ating mechanism, deep cablecompartment cover) and aretherefore given as mean value
2) Sum of the net weights of indi-vidual panels and / or panel blocks
* Low-voltage compartment,600 mm high, weight approx.60 kg depending on the paneltype and on the extentto which it is equipped
** The weights depend on theweights of the mountedtransformers
*** Packing weight
Individual panel, panel blockor combinations thereoffor standard switchgear(without pressure relief duct)
TypeShort iden-tification B
current infuture
Panel or panel combination Transport unit (including packing) for standard panels (withoutpressure absorber system)
Width B1mm
Net weight 1)
approx. kgwithout / withLVC */ LVC*
Width B2m
Heightmwithout /withLVC */ LVC*
DepthT2 m
Volumem3
without /withLVC */ LVC*
Gross weight 1)
approx. kgwithout /withLVC */ LVC*
Transport of individual panels
Ring-main panel (standard) RK RK
RK1 RK1
350
500
150 / 210
180 / 240
0.70
0.70
1.60 / 2.20
1.60 / 2.20
1.10
1.10
1.23 / 1.69
1.23 / 1.69
210 / 270
240 / 300
RK2 RK1V 500 200 / 260 0.70 1.60 / 2.20 1.10 1.23 / 1.69 260 / 320
Cable panel (standard) K K 350 145 / 205 0.70 1.60 / 2.20 1.10 1.23 / 1.69 205 / 265
Transformer panel TR TR1 500 180 / 240 0.70 1.60 / 2.20 1.10 1.23 / 1.69 240 / 300
Circuit-breaker panel (standard) LS1 LS1
LS2 LS1V
500
500
– / 260
– / 380
0.70
0.70
– / 2.20
– / 2.20
1.10
1.10
– / 1.69
– / 1.69
– / 320
– / 440
Circuit-breaker panel BB LST1 LST1 500 280 / 340 0.70 1.60 / 2.20 1.10 1.23 / 1.69 320 / 380
Bus sectionalizer panel with circuit-breaker LT1 LK
LT1-V LKV
500
500
– / 280
– / 380
0.70
0.70
– / 2.20
– / 2.20
1.10
1.10
– / 1.69
– / 1.69
– / 340
– / 440
Bus sectionalizer panel with switch-disconnector LT2 LT 500 150 / 210 0.70 1.60 / 2.20 1.10 1.23 / 1.69 210 / 270
Busbar earthing panel
withvoltagetransformer
SE1 SE
SE2 SE1V
350
500
150 / 210
250 / 310
0.70
0.70
1.60 / 2.20
1.60 / 2.20
1.10
1.10
1.23 / 1.69
1.23 / 1.69
210 / 270
310 / 370
Busbar voltage metering panel ME3 MS1V 500 250 / 310 0.70 1.60 / 2.20 1.10 1.23 / 1.69 310 / 370
Billing metering with cast-resinpanels, insulated transformersair-insulated **
with combinedtransformers
ME1 ME1 850 250 / 310 1.08 1.60 / 2.20 1.10 1.90 / 2.61 310 / 370
ME2 ME2 600 390 / 450 1.08 1.60 / 2.20 1.10 1.90 / 2.61 450 / 510
Transport of panel blocks
Ring-main panel block R-B2
R-B3
700
1050
280 / 400
400 / 580
1.08
1.40
1.60 / 2.20
1.60 / 2.20
1.10
1.10
1.90 / 2.61
2.46 / 3.40
340 / 460
470 / 650
Transformer panel block T-B2
T-B3
1000
1500
320 / 440
480 / 660
1.40
2.03
1.60 / 2.20
1.60 / 2.20
1.10
1.10
2.46 / 3.40
3.57 / 4.91
390 / 510
560 / 740
Ring-main/transformer panel block RT-B2
2RT-B3
3RT-B4
700
1050
1400
300 / 420
450 / 630
580 / 820
1.08
1.40
2.03
1.60 / 2.20
1.60 / 2.20
1.60 / 2.20
1.10
1.10
1.10
1.90 / 2.61
2.46 / 3.40
3.57 / 4.91
360 / 480
520 / 700
660 / 900
Cable connection/transformer panel block KT-B2 700 300 / 420 1.08 1.60 / 2.20 1.10 1.90 / 2.61 360 / 480
Transport of combinations of different individual panels or panel blocks
Comprising– a number of individual panels or– 1 panel block or– a number of panel blocks or– individual panels with panel blocks
Overall width B3
� 850 mm
B2
1.08 1.60 / 2.20
T2
1.10 1.90 / 2.61 2) + 60***� 1200 mm 1.40 1.60 / 2.20 1.10 2.46 / 3.39 2) + 70***� 1800 mm 2.03 1.60 / 2.20 1.10 3.57 / 4.91 2) + 85***� 2350 mm 2.53 1.60 / 2.20 1.10 4.49 / 6.17 2) +100***
B Short identifications of the panels have been harmonized
BB Panel type LST1: Please refer to separate Catalog HA 45.31/41.11, Supplements to Catalogs HA 45.31/41.11
8 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Technical Data
Product range overview
Legend for pages 8 and 9
* Short identifications of the panelshave been harmonized
** LV terminals as an option in the LVcompartment (compartment to beordered as an option)
� Three-position switch asthree-position switch-disconnector(switch-disconnectorCLOSED-OPEN-EARTHED)
BB Three-position switch asthree-position circuit-breaker(disconnecting circuit-breakerCLOSED-OPEN-EARTHED), seeSupplements to CatalogsHA 45.31/41.11-2007
1) The equipment applies to the entirepanel block, but it is located in thefirst feeder panel from the left
2) Low-voltage terminals arranged inthe low-voltage niche of thering-main or cable feeder
Product Range
Short identifications *
current in future
Individual panels
Panel blocks
Designation of theindividual panelsand panel blocks
Panelwidth
Type
Column no.
Ring-main panel 350 RK RK
500 RK1 RK1
500 RK2 RK1V
350 RK-U RK-U
500 RK1-U RK1-U
500 RK2-U RK1V-U
Cable panel without earthing switch 350 K K
350 K-U K-U
Cable panel with make-proof earthing switch 350 K K
350 K-U K-U
Transformer panel 500 TR TR1
500 TR-U TR1-U
Transformer panel with plug-in voltage transformers 500 TR-V TR1-V
500 TR/V TR1/V
Circuit-breaker panel 500 LS1 LS1
500 LS1-U LS1-U
Circuit-breaker panel with plug-in busbar voltage transformers 500 LS2 LS1V
500 LS2-U LS1V-U
Circuit-breaker panel (with disconnecting circuit-breaker) �� 500 LST1 LST1
Bus sectionalizer (with vacuum circuit-breaker) 500 LT1 LK
500 LT1-V LKV
Bus sectionalizer (with switch-disconnector) 500 LT2 LT
Busbar earthing panel 350 SE1 SE
500 SE2 SE1V
Busbar voltage metering panel 500 ME3 MS1V
Billing metering panel 850 ME1 ME1
850 ME1-K ME1-K
Billing metering panel for busbar connection 850 ME1-S ME1-S
cable connection 850 ME1-KS ME1-K
Billing metering panel with combined transformers 600 ME2 ME2
Ring-main panel block 700 R-B2
1050 R-B3
Transformer panel block 1000 T-B2
1500 T-B3
Ring-main/transformer panel block700 RT-B2
RK
T
1050 2RT-B3RK
T
1400 3RT-B4RK
T
Cable connection/transformer panel block(cable panel without make-proof earthing switch) 700 KT-B2
K
T
Cable connection/transformer panel block(cable panel with make-proof earthing switch) 700 KT-B2
K
T
Column no.
Siemens HA 41.11 · 2007 9
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Ausstattungsmerkmale
Switchgear Type 8DH10 up to 24 kV, Gas-Insulated, Extendable
Product Range
Equipment features
Man
ualoper
atin
gm
echan
ismfo
r thre
e-posit
ion
switc
hB
)
Man
ualoper
atin
gm
echan
ismfo
r thre
e-posit
ion
circu
it-bre
aker
BB
)
Inte
rlock
for ca
bleco
mpar
tmen
t cove
r
Cable
com
partm
ent co
ver lo
cked
inpla
ce/sc
rew
edon
C-rail a
s cable
brack
et
Low
-volta
genich
eas
term
inal
com
p. above
the
operat
ing
mec
hanism
box
Low
-volta
gete
rmin
als in
the
operat
ing
mec
hanism
box **
Separ
ate
low
-volta
genich
eas
term
inal
com
partm
ent
Relea
seas
shunt re
leas
efo
r thre
e-posit
ion
switc
hB
) andB
B)
Mec
han. r
eady-
for-s
ervic
e indica
tor (e
.g. f
or switc
hing
device
s)
Signal
ling
switc
h(1
NO) for re
mote
elec
trica
l rea
dy-fo
r-ser
vice
indica
tion
Aux.sw
itch
for t
hree-
positio
nsw
itchB
) andB
B) : S
witc
h-disc
onnecto
r CLO
SED/
OPEN: 2
NO+
2NC, EART
HING
CLOSE
D/OPE
N: 2NO
+2NC; c
ircuit-
break
er
type LS
T CLOSE
D/OPE
N: 2NO
+2NC, E
ARTHIN
GCLO
SED/O
PEN: 2
NO+
2NC
Moto
r-ope
rat.
mec
han. f
. thre
e-po
s.sw
itchB
) and
BB
) (f.CLO
SED
and
OPEN)
Inte
rlock
incir
cuit-
break
erpan
elbet
wee
nth
ree-
positio
nsw
itchB
) and
vacu
umcir
cuit-
break
er
De-ea
rthin
glo
ck-o
ut for m
ake-
proof ea
rthin
gsw
itch
of thre
e-posit
ion
switc
hB
) and
BB
)
Closin
glo
ck-o
ut for th
ree-
positio
nsw
itchB
) and
BB
)
Lock
ing
device
for th
ree-
positio
nsw
itchB
) and
BB
)
Short-
circu
itor ea
rth-fa
ultin
dicato
r
Moto
r operat
ing
mec
hanism
for 3AH
vacu
umcir
cuit-
break
er
Relea
seas
curre
nt-tra
nsform
eroper
ated
rele
ase
Low
-volta
geco
mpar
tmen
t **)
Low
-volta
geco
ver
Mounte
dca
blecla
mps
Seco
ndary
equip
men
t
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
• Basic equipment
° Additional equipment(option), further additionalequipment on request
– Not available
• – • – • • – – – • ° ° ° – – ° ° ° – – ° ° ° °• – • – • • – – – • ° ° ° – – ° ° ° – – ° ° ° °• – • – • • – – – • ° ° ° – – ° ° ° – – ° ° ° °• – • – – • – – – • ° ° ° – – ° ° – – – ° ° – °• – • – – • – – – • ° ° ° – – ° ° – – – ° ° – °• – • – – • – – – • ° ° ° – – ° ° ° – – ° ° – °– – – • • • – – – • ° – – – – – – ° – – ° ° ° °– – – • – • – – – • ° – – – – – – – – – ° ° – °• – • – • • – – – • ° ° – – – – ° ° – – ° ° ° °• – • – – • – – – • ° ° – – – – ° – – – ° ° – °• – • – • – • – ° • ° ° ° – ° – ° – – – ° ° ° °• – • – – – • – ° • ° ° ° – ° – ° – – – ° ° – °• – • – • – • – ° • ° ° ° – ° – ° – – – ° ° ° °• – • – – – • – ° • ° ° ° – ° – ° – – – ° ° – °• – • – • – – – ° • ° ° ° ° – ° ° ° ° ° • – ° °• – • – – – – – ° • ° ° ° ° – ° ° – ° ° • – – °• – • – • – – – ° • ° ° ° ° – ° ° ° ° ° • – ° °• – • – – – – – ° • ° ° ° ° – ° ° – ° ° • – – °– • • – • • • – ° • ° • ° – ° ° ° ° – ° ° ° ° °• – – • – – – – ° • ° ° ° ° – – • – ° ° • – – °• – – • – – – – ° • ° ° ° ° – – • – ° ° • – – °• – – • – • – – – • ° ° ° – – – • – – – ° ° – °• – • – – • – – – • ° ° – – – – • – – – ° ° – °• – • – – • – – – • ° ° – – – – • – – – ° ° – °• – – • – • – – – • ° ° ° – – – ° – – – ° ° – °– – – • – – – • – – – – – – – – – – – – ° ° – °– – – • • – – • – – – – – – – – – – – – ° ° ° °– – – • – – – • – – – – – – – – – – – – ° ° – °– – – • • – – • – – – – – – – – – – – – ° ° ° °– – – • – – – – – – – – – – – – – – – – ° ° – °1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
• – • – • • – – – •1)
°1)
° ° – – – ° ° – – ° ° ° °• – • – • • – – – •1)
°1)
° ° – – – ° ° – – ° ° ° °• – • – • – – – ° •1)
°1)
° ° – ° – ° – – – ° ° ° °• – • – • – – – ° •1)
°1)
° ° – ° – ° – – – ° ° ° °• – • – • • – – – •1)
°1)
° ° – – ° ° ° – – ° ° ° °• – • – • 2) – – °
1) 1)
° ° – ° – ° – – – ° ° ° °• – • – • • – – – •1)
°1)
° ° – – ° ° ° – – ° ° ° °• – • – • 2) – – °
1) 1)
° ° – ° – ° – – – ° ° ° °• – • – • • – – – •1)
°1)
° ° – – ° ° ° – – ° ° ° °• – • – • 2) – – °
1) 1)
° ° – ° – ° – – – ° ° ° °– – – • • • – – – •1)
°1) – – – – – – ° – – ° ° ° °
• – – – • 2) – – ° 1)
1)
° ° – ° – ° – – – ° ° ° °• – • – • • – – – •1)
°1) ° – – – – ° ° – – ° ° ° °• – • – • 2) – – °
1) 1)
° ° – ° – ° – – – ° ° ° °
10 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Ring-main panels
as feeder panels
Cable panels
as feeder panels
Transformer panels
as feeder panels
as transfer panels as transfer panels as transfer panels
����
����
����
�� �
����
����
���
�� �
����
����
����
�� �
����
����
����
�� �
����
����
���
�� �
Type RK-U350 mm wide
for transferto the right
����
����
����
�� �
Type RK *350 mm wide
with plug-insurgearresters *
����
����
����
�� �
��
Type RK *350 mm wide
for 2nd cable*
����
����
����
�� �
Type RK-U350 mm wide
for transferto the left
����
����
����
�� �
��
Type K *350 mm wide
for 2nd cable *
����
����
����
�� �
option
option
option
option
option
option
option
option
Type RK350 mm wide
����
����
����
�� �
Type K350 mm wide
����
����
����
�� �
Type K *350 mm wide
with plug-insurgearresters *
����
����
����
�� �
Type K-U350 mm wide
for transferto the right
����
����
����
�� �
Type K-U350 mm wide
for transferto the left
option
option
option
option
option
option
option
option
����
����
����
�� �
option
option
option
option
option
option
option
Type TR1-V B
500 mm wide
with plug-involtage trans-formers
Type TR1-U500 mm wide
for transferto the left
Type TR1500 mm wide
Type TR-V B
500 mm wide(105 mm deepercable compart-ment cover)
with plug-involtage trans-formers in-stead of cableconnection
Type TR1-U500 mm wide
for transferto the right
Product Range
Type RK1 1) 3)
500 mm wide HV HRC fuse
Capacitivevoltage detectingsystem
Cable (notincluded in thescope of supply)
2nd cable (notincluded in thescope of supply)
Plug-insurge arrester
Make-proofearthing switch
4MT8 plug-in voltagetransformer at thecable connection
Cable-type currenttransformer
��
Three-positionswitch-disconnector
4MT8 plug-in voltagetransformer at theconnection
Ring-main, cable and transformer panels as individual panels
HA
41
-22
78
ee
ps
Option:Type RK1 V 1) 2) 3)
500 mm wide
Option:Type RK1-U3)
Type RK1V-U2) 3)
500 mm wide
Option:Type RK1-U3)
Type RK1V-U2) 3)
500 mm wide
Footnotessee page 11
Siemens HA 41.11 · 2007 11
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Ring-main, cable and transformer panels in panel blocks ��
Ring-main panel blocks
Designs and options for each panel, see page 10
Type R-B2700 mm wide
consisting of2 ring-main panels
RK RK
RK RK
����
����
���
��� Type R-B3
1050 mm wide
consisting of3 ring-main panels
Transformer panel blocks
Designs and options for each panel, see page 10
Type T-B21000 mm wide
consisting of2 transformer panels
TR TR
TR TRType T-B31500 mm wide
consisting of3 transformerpanels
Ring-main/transformer panel blocks
Designs and options for each panel, see page 10
Type RT-B2700 mm wide
consisting of1 ring-main panel and1 transformer panel
RK TR c
RK TR c
����
���
��
���
����
����
����
�� �
Type 2RT-B31050 mm wide
consisting of2 ring-main panels and1 transformer panel
Cable connection/transformer panel block
Designs and options for each panel, see page 10
Designs
• Busbar connection system for connection of individualpanels or panel blocks: Arranged in the left-hand panel of thepanel block (therefore extendable at a later date)
• Only either the left-hand or the right-hand panel of the panel blockcan be designed as a transfer panel with busbar connection
• Panel blocks are also available without a busbar connectionsystem (extendable at a later date only via the cable feeder)
TR
RK
RK RK
����
���
���
���
RK TR c
Type 3RT-B41400 mm wide
consisting of3 ring-main panelsand1 transformerpanel
Type KT-B2700 mm wide
consisting of1 cable connection panel1 transformer panel
K TR c
����
����
����
�� �
c A plug-in voltage transformer cannot be provided at the connection
Three-positionswitch-disconnector
HV HRC fuse
Capacitivevoltage detectingsystem
Cable (notincluded in thescope of supply)
����
����
����
�� �
����
���
���
���
RK
����
���
���
���
Product Range
Designs
• Busbar connection system for connection of individualpanels or panel blocks: Arranged in the left-hand panel of thepanel block (therefore extendable at a later date)
• Only either the left-hand or the right-hand panel of the panel blockcan be designed as a transfer panel with busbar connection
• Panel blocks are also available without a busbar connectionsystem (extendable at a later date only via the cable feeder)
HA
41
-22
78
ee
ps
B Deep cablecompartmentcover required
* Depending onthe make/type ofthe cableplug or arrester:Deep cablecompartmentcover required
** Cable-typecurrent trans-former on the2nd cable:For 300 mmdeeper cablecompartmentcover
1) Suitable forvoltagetransformertype 4MT8
2) Suitable forvoltagetransformertype 4MT3
3) Suitable forthree-phasecurrent trans-formers
Footnotesfrom page 10
BB Capacitive voltagedetecting system atthe busbar of thepanel blocks: Onlylocated once in thefirst panel of theblock!
12 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
����
����
����
�� �
��
����
����
����
�� �
��
����
����
���
�� �
��
����
����
����
�� �
��
����
����
����
�� �
��
��
����
����
����
���
�
��
��
����
����
����
�� �
��
��
����
����
����
�� �
��
��
����
����
����
�� �
��
��
��
����
����
����
�� �
��
��
����
����
����
�� �
��
��
��
Circuit-breaker panels as individual panels ��
Circuit-breaker panels
as feeder panels
����
����
���
�� �
��
��
Type LS1500 mm wide
Basic panel
Type LS1 *500 mm wide
for 2nd cable *
Type LS1 *500 mm wide
with plug-insurge arresters orlimiters *
Type LS1 B
500 mm wide
with plug-involtage trans-formers �
as transfer panels
Type LS1-U500 mm wide
for transferto the right
option
option
option
option
option
option
option
option
Type LS1-U500 mm wide
for transferto the left
option
option
option
option
Circuit-breaker panels with plug-inbusbar voltage transformers
as feeder panels
Type LS1V/LS2500 mm wide
Basic panel
Type LS2 *500 mm wide
for 2nd cable *
Type LS1V/LS2 *500 mm wide
with plug-insurge arrestersor limiters *
Type LS1V/LS2 B
500 mm wide
with plug-involtage trans-formers B
as transfer panels
Type LS1V-U/LS2-U500 mm wide
for transferto the right
Type LS1V-U/LS2-U500 mm wide
for transferto the left
option
option
option
option
option
option
option
option option
option
option
option
Three-positionswitch-disconnector
Capacitivevoltage detectingsystem
Cable (notincluded in thescope of supply)
Vacuumcircuit-breaker
Cable-type currenttransformeron the cable
2nd cable (notincluded in thescope of supply)
Plug-insurge arresteror limiter
4MT3 plug-involtagetransformerat the busbar
4MT8 plug-in voltagetransformer at thecable connection
Product Range
HA
41
-22
78
ee
ps
option option option option
option option option option
Footnotessee page 13
4MC63... three-phase currenttransformer
��
��
Siemens HA 41.11 · 2007 13
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
����
����
��
���
����
����
����
�� �
����
����
����
�� �
����
����
���
���
����
����
����
�� �
����
����
����
�� �
Bus sectionalizer with circuit-breaker, bus sectionalizer with switch-disconnector, busbar earthing panels andbusbar voltage metering panel as individual panels ��
option
option
Bus sectionalizerwith circuit-breaker
Type LK/LT1500 mm wide
with vacuumcircuit-breaker
option
option
Type LKV/LT1-V500 mm wide
with vacuumcircuit-breaker andplug-in voltagetransformers
option
option
Type LT2500 mm wide
Busbar earthingpanels
Type SE350 mm wide
Type SE1V/SE2500 mm wide
with plug-involtagetransformers
Busbar voltage meteringpanel
Type MS1V/ME3500 mm wide
Three-positionswitch-disconnector
Vacuumcircuit-breaker
4MT3 plug-involtagetransformerat the busbar
Cable-typecurrent trans-former on thescreened busbar
Make-proofearthing switch
Capacitivevoltage detec-ting system
4MT8 plug-involtagetransformerat the connection
Product Range
HA
41
-22
78
ee
ps
B Deep cablecompartmentcover required
BB Short identi-fications of thepanels havebeen harmo-nized
* Depending onthe make/type ofthe cableplug or arrester:Deep cablecompartmentcover required
** Cable-typecurrent trans-former on the2nd cable:For 300 mmdeeper cablecompartment
Footnotes frompage 12 and 13
Bus sectionalizerwith switch-disconnector
14 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable��
����
����
����
�
��
��
��
option
Type ME1, 850 mm wide
for transfer to the right,transformer terminalsinterchanged
Billing metering panels(standard)
Billing metering panels as endpanels, for cable connection
Billing metering panels forbusbar connection
Cable (notincluded in thescope of supply)
Voltage trans-former, cast-resininsulated
Fixed earthingpoints for busbarearthing
Current trans-former, cast-resininsulated
Type ME1, 850 mm wide
for transfer to the right
����
����
����
�� �
��
�� ��
option
Type ME1-K, 850 mm wide
for transfer to the right
����
���
����
�� �
��
��
option
Type ME1-S, 850 mm wide
for busbar metering
����
���
����
�� �
��
��
��
option
Type ME1, 850 mm wide
for transfer to the right
Type ME1, 850 mm wide
for transfer to the right,transformer terminalsinterchanged
����
���
����
�� �
��
�� ��
option
Type ME1-K, 850 mm wide
for transfer to the right,transformer terminalsinterchanged
����
���
����
�� �
��
��
option
Type ME1-K, 850 mm wide
for transfer to the right
����
���
����
�� �
��
��
option
Type ME1-K, 850 mm wide
for transfer to the right,transformer terminalsinterchanged
����
���
����
�� �
��
��
option
Type ME1-S, 850 mm wide
for busbar metering,transformer terminalsinterchanged
����
���
����
�� �
����option
����
���
���
�� �
����option
Air-insulated metering panels as transfer panels
����
����
���
�� �
����
����
����
����
�� �
����
Type ME1-S, 850 mm wide
for busbar metering,transformer terminalsinterchanged
Type ME1-S, 850 mm wide
for busbar metering,transformer terminalsinterchanged
Scheme 1 Scheme 1 Scheme 1
Scheme 2Scheme 2Scheme 2
Scheme 3Scheme 3Scheme 3
Scheme 4Scheme 4Scheme 4
Note
Schemes 1 to 4 also feasiblefor transfer to the left
Note
Schemes 1 to 4 also feasiblefor transfer to the left
option
option
Voltage transformer,cast-resin insulatedor on request:
Voltage transformer,cast-resin insulated,with HV HRC fuse
P1 and P2are terminaldesignationsof the currenttransformer
Product Range
HA
41
-22
78
de
ps
1)
Siemens HA 41.11 · 2007 15
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable��
����
���
����
�
��
��
��
Air-insulated metering panels as transfer panels
Billing metering panels as endpanels, for cable connection
Billing metering panelsas individual panels, for cableconnection
Type ME1-KS, 850 mm wide
for transfer to the right
option
Type ME1-KK, 850 mm wide
for cable connection
����
���
����
�� �
��
��
��
option
Type ME1-KS, 850 mm wide
for transfer to the right
����
����
����
�� �
��
��
��
option
Type ME1-KS, 850 mm wide
for transfer to the right,transformer terminalsinterchanged
����
����
����
�� �
��
��
��
option
Type ME1-KK, 850 mm wide
for cable connection,transformer terminalsinterchanged Cable (not
included in thescope of supply)
Fixed earthingpoints for busbarearthing
Current trans-former, cast-resininsulated
4MK plug-incombined voltagetransformer,metal-enclosed
Type ME1-KS, 850 mm wide
for transfer to the right,transformer terminalsinterchanged
4MK plug-incombined currenttransformer,metal-enclosed
Note
Schemes 1 to 4 also feasibleas left-hand end panelfor transfer to the left
Scheme 1
Scheme 2
Scheme 3
Scheme 4
Voltage transformer,cast-resin insulatedor on request:
Voltage transformer,cast-resin insulated,with HV HRC fuses
Type ME1-KK, 850 mm wide
for cable connection
Type ME1-KK, 850 mm wide
for cable connection,transformer terminalsinterchanged
P1 and P2are terminaldesignationsof the currenttransformer
Product Range
����
����
���
���
��
��
����
����
����
���
��� ����
��
��
����
���
���
���
����
��
��
����
���
���
���
����
��
��
����
����
����
���
��
��
����
����
����
�
��
��
��
����
����
����
�
��
��
��
����
����
���
�
��
��
��
Type ME2, 600 mm wide
for transfer to the right
Type ME2, 600 mm wide
for transfer to the right,transformer terminalsinterchanged
Type ME2, 600 mm wide
for transfer to the left
Type ME2, 600 mm wide
for transfer to the left,transformer terminalsinterchanged
* Mainly for connection tobus sectionalizer with switch-disconnectorLT1, LT1-V and LT2
option
option
option
option
Billing metering panels *with metal-enclosedcombined transformers
Scheme 1
Scheme 2
Scheme 3
Scheme 4
Scheme 1
Scheme 2
Scheme 3
Scheme 4
HA
41
-22
78
ee
ps
1)
��
16 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Panel design (examples)
����
����
����
�
�
�
�
�
�
�
�
��
��
��
��
��
��
��
��
�
�
��
��
��
��
�
��
��
��
��
��
�
�
��
��
Ring-main panel Section Transformer panel Section
Billing metering panel, air-insulated Section
����
����
����
�
�
�����
��
��
��
��
��
��
��
��
�
�
��
��
��
��
��
��
��
��
��
��
��
��
��
�
�
��
��
����
����
����
�
�
�
��
�
�
�
��
��
��
�
�
��
��
��
��
��
��
Type RK Type TR
Type ME1
Design
Legend for pages 16 and 17
1 Option: Low-voltage compartment
2 Niche for customer-side low-voltage equipment,with hinged cover
3 Switch-position indicator for load-breakfunction “CLOSED – OPEN”
4 Switch-position indicator for earthingfunction “OPEN – EARTHED”
5 Ready-for-service indicator
6 Rating and type plate
7 Mimic diagram
8 Option: Short-circuit / earth-fault indicator
9 Sockets for voltage detecting system
10 Arrangement of the busbars
11 Feeder designation label
12 Option: Locking device for three-positionswitch-disconnector
13 Manual operation for the mechanism ofthe earthing function
14 Manual operation for the mechanism ofthe load-break function
15 Interlock of the cable compartment cover
16 Arrangement of the cable connections
17 Busbar system
18 Switchgear vessel filled with gas
19 Busbar connection
20 Pressure relief device
Siemens HA 41.11 · 2007 17
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Panel design (examples)
Circuit-breaker panel Section
����
����
����
�
����
��� ����
��
�
��
��
��
��
�
�
��
��
��
��
��
��
��
���������
�
��
��
��
��
��
��
��
��
��
�
�
��
��
��
��
Type LS1 (without voltage transformers)
����
����
����
��
��
��
��
��
��
Type LS2-V (with voltage transformers)
Design
21 Partition for busbar
22 Earthing busbar with earthing connection
23 Three-position switch-disconnector
24 Spring-operated mechanism
25 Bushing for cable plug with bolted contact (M16)
26 Option: Cable T-plug
27 Cable compartment cover
28 Cable compartment
29 Cable bracket
30 Earthing connection for earthing accessories
31 HV HRC fuse assembly, cover removed
32 Handle for replacing HV HRC fuse links
33 Interlock for HV HRC fuse assembly
34 Cover of the HV HRC fuse compartment
35 Spring-operated / stored-energy mechanism
36 Bushing for cable plug with plug-in contact
37 Cable elbow plug with plug-in contact
38 Switch-position indicator for load-break function“CLOSED – OPEN” and, if applicable,“HV HRC fuse tripped” or “shunt release tripped”
39 Cover for access to the busbar connection and tothe instrument transformers, screwed on
40 4MR voltage transformer
41 4MA7 current transformer
42 Cover to busbar connectioncompartment, screwed on
43 Option: SIPROTEC bay control unit
44 Low-voltage compartment (standard)
Vacuum circuit-breaker:
45 Opening for the hand crank– for closing with manual operating mechanism– for emergency operation with motor operating
mechanism
46 Operating mechanism box
47 Mechanical “ON” pushbutton (not supplied withspring-operated mechanism)
48 Mechanical “OFF” pushbutton
49 Operating cycle counter
50 “Spring charged” indicator
51 Vacuum interrupter
52 Switch-position indicator
53 Option: Interlock between vacuum circuit-breakerand three-position switch-disconnector
54 Option: Three-phase current transformer(protection transformer)
55 Cable-type current transformer
56 4MT3 plug-in voltage transformer at the busbar
57 Bushing for connection of plug-in voltage transformers
58 Plug-in connection according to EN 50181 /DIN EN 50181 as interface type “A”
59 Option: 4MT8 plug-in voltage transformer at the connection
60 Deep cable compartment cover
61 Wiring duct, removable, for control cables and/or bus wires
62 Cover screwed on
63 Option: Interlock between three-positionswitch-disconnector and circuit-breaker
18 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Features
• According to IEC 62 271/VDE 0671-100(standards see page 41)
• Application of all 8DH10switchgear in hermeticallysealed vessel in conformitywith the system
• Climate-independent vacuuminterrupter poles in thegas-filled switchgear vessel
• Maintenance-free for indoorinstallation according toIEC 60 694/ VDE 0670-1000(standards see page 41)
• Individual secondary equipment
• A metal bellows is used forgasketless separation of theSF6-insulation and the operat-ing mechanism – as alreadyused with success for over100000 vacuum interrupters
Switching duties andoperating mechanisms
The switching duties of thevacuum circuit-breaker are de-pendent, among other factors, onits type of operating mechanism.Three operating mechanism ver-sions are available:
• Motor operating stored-energymechanism
– For auto-reclosing (K),– For synchronization and
rapid load transfer (U)
• Manual operating stored-energy mechanism
– For auto-reclosing (K)
• Manual spring-operated me-chanism (= spring CLOSED,stored-energy OPEN)
– Not for auto-reclosing (K)– For normal closing and– For storage of one opening
operation
Further operating mechanismfeatures
• Located outside the switch-gear vessel in the operatingmechanism box and behindthe control board
• Stored-energy springmechanism for 10000operating cycles
3AH vacuum circuit-breaker
Operating mechanismfunctions
Motor operating mechanism 1)
(M1 *)
In the case of the motor oper-ating mechanism, the closingspring is charged by means ofa motor and latched in thecharged position (the “springcharged” indication is visible).Closing is effected either bymeans of an ON pushbutton ora closing solenoid. The closingspring is recharged automati-cally (for auto-reclosing).
Manual operating stored-energy mechanism
The closing spring is chargedby means of the hand crank sup-plied until latching of the closinglatch is indicated(= “spring charged” indication).
Subsequently the vacuumcircuit-breaker can be closedeither manually or electricallyand the closing spring can berecharged manually. The “possi-bility to close” is thus storedonce more (for auto-reclosing).
Manual spring-operatedmechanism(= spring CLOSED, stored-energyOPEN)
The closing spring of the vacuumcircuit-breaker is charged bymeans of the hand crank sup-plied until the vacuum circuit-breaker closes. Subsequentlyeither manual or electrical open-ing is possible.
Vacuum circuit-breakers withspring-operated mechanism arenot suitable for auto-reclosing.
Trip-free mechanism
The vacuum circuit-breakeris fitted with a trip-freemechanism.
1) Motor rating at24 V to 220 V DC: 350 W110 V and 230 V AC:400 VA
2) With closing solenoid
* Item designation
For further technical data and description of typical applications,please refer also to Catalog HG 11.11 “3AH Vacuum Circuit-Breakers”
Components
CO = CLOSE operation with subsequentOPEN operation at the shortestinternal close-open time of thevacuum circuit-breaker
t = Dead time 0.3 s
t ‘ = Dead time 3 min
Abbreviations for switchingduties and applications:
U = Synchronization andrapid load transfer(make time � 90 ms)
K = Auto-reclosing
O = OPEN operation
Differentiation features between the vacuum circuit-breakersdepending on the operating mechanism version
Operatingmechanismversion
Motor operatingstored-energymechanism
Manualoperatingstored-energymechanism
Manual spring-operatedmechanism
Typical uses Utilitysubstationsand industrialplants
Classic transfersubstations andsubstationswithout auxiliaryvoltage supply
Simple utilitysubstations(circuit-breakeremployed astransformerswitch)
Mechanismfunction
Stored-energyCLOSED,stored-energyOPEN
Stored-energyCLOSED,stored-energyOPEN
SpringCLOSED,stored-energyOPEN
Mechanismoperation
With motor 1),manual (emer-gency) opera-tion at the panelincluding anti-pumping
With handcrank
With handcrank
Closing thevacuumcircuit-breaker
Electrically 2) ormechanically atthe panel withpushbutton
Mechanicallyat the panelwith push-button, option:electrically 2)
Mechanicallyat the panelwith handcrank (chargingprocess)
Closingsolenoid, e.g.for remoteelectricalclosing
Always provid-ed, with elec-trical signal“closing springcharged”
Option Without
Ratedoperatingsequence
O-t-COorO-t-CO-t’-CO
O-t-CO O or CO
Auto-reclosing (K)
Suitable (multi-ple auto-reclos-ing possible)
Suitable (onlywith closingsolenoid)
–
R-H
A4
1-0
16
ep
s
1
2
3
4
5
7
10
6
8
11
13
15
Operating mechanism of the vacuum circuit-breaker(for the legend, see page 19)
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 19
Secondary equipment of the 3AH vacuum circuit-breaker
Circuit-breaker tripping signal(standard)
• For electrical signalling (as pulse> 10 ms), e.g. to remote controlsystems, in the case of automatictripping (e.g. protection)
• Via limit switch (S6 *) andcut-out switch (S7 *)
Varistor module
• To limit overvoltages to approx.500 V for protection devices(when inductive devices aremounted in the vacuum circuit-breaker)
• For auxiliary voltages W 60 V DC
Auxiliary switch
• Type 3SV9 (S1 *)
• Standard: 6 NO+6 NC, of which2 NO+2 NC+2 changeovercontacts are free 1)
• Option: 12 NO+12 NC, of which7 NO+4 NC+2 changeovercontacts are free 1)
Position switch
• Type 3SE4 (S4 *)
• For signalling “closing springcharged”
• Only in conjunction with stored-energy mechanisms
Mechanical interlocking
• Dependent on the type ofoperating mechanism
• Option: Switchgear interlockingwith the three-position switch-disconnector (option: Closinglock-out for the three-positionswitch-disconnector in circuit-breaker panels type LS and LT1)
• Option: Operating mechanismwith mechanical interlocking as
– Spring-operated mechanism:Hand crank opening is blocked
– Stored-energy mechanism withclosing solenoid (Y9 *) andpushbutton (S12 *): The push-button (S12 *) operated by themechanical interlock prevents acontinuous command to theclosing solenoid
• During operation of the three-position switch-disconnectorfrom CLOSED to OPEN:Vacuum circuit-breakercannot be closed.
����
����
�����
��
��
��
�
�
����
����
�����
��
�
�
�
�
��
��
�
�
��
��
��
The scope of the 3AH vacuumcircuit-breaker secondary equip-ment depends on the type of appli-cation and offers a wide range ofoptions, thus allowing even thehighest requirements to be satis-fied.
Closing solenoid
• Type 3AY15 10 (Y9 *)
• For electrical closing
Shunt releases
• Types:– Standard: 3AY15 10 (Y1 *)– Option: 3AX11 01 (Y2 *),
with energy store
• Tripping by protection device orelectrical operation
Current-transformeroperated release
• Type 3AX11 04 (Y6 *) for trip-ping pulse W 0.1 Ws in con-junction with suitable protec-tion systems, e.g. 7SJ4 protec-tion system, 4MC6.. transformerprotection system, SEG relay(other designs on request)
• Used where no externalauxiliary voltage is available,tripping by protection device
Undervoltage release
• Type 3AX11 03 (Y7 *)
• Comprising:– Energy store and unlatching
mechanism– Electromagnetic system which is
permanently connected to voltagewhile the vacuum circuit-breakeris closed; tripping is initiatedwhen this voltage drops
• Connection to voltage trans-formers possible
Anti-pumping (standard)(mechanical and electrical)
• Function: If constant CLOSE andOPEN commands are present atthe vacuum circuit-breaker atthe same time, the vacuum cir-cuit-breaker will return to theopen position after closing. Itremains in this position until anew CLOSE command is given.In this manner, continuous clos-ing and opening (= pumping) isavoided.
Basic equipment with manual spring-operated mechanism
Maximum equipment with motor operating stored-energy mechanism
Secondary equipment (view into the operating mechanism box)
1 Gear
2 Position switch (S4 *)
3 Closing spring
4 Motor (M1 *)
5 Operating cycle counter
6 “Closing spring charged” indicator
7 Closing solenoid (Y9 *)
8 Option: Auxiliary switch12 NO+12 NC
9 Auxiliary switch6 NO+6 NC (S1 *)
10 Circuit-breaker “CLOSED”
11 Circuit-breaker “OPEN”
12 Option: 2nd release
13 1st release (Y1 *)
14 Option: Mechanical inter-locking with interrogationof the three-positionswitch-disconnector
15 Operating rod with contactpressure springs
16 Interlocking to the three-position switch-disconnector
17 Actuation for closing thevacuum circuit-breaker
Abbreviations:NO = normally-open contactNC = normally-closed contact
1) For utilizationby thecustomer
* Itemdesignation
For further technical data and description of typical applications,please refer also to Catalog HG 11.11 “3AH Vacuum Circuit-Breakers”
Components
20 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Three-position switch-disconnector
Features
• Switch positions: CLOSED –OPEN – EARTHED
• Switching functions asgeneral-purpose switch-disconnector (class E3)according to
– IEC 60 265-1/ VDE 0670-301– IEC 62 271-102/ VDE 0671-102
(standards see page 41)
• Designed as a multi-chamberswitch with the functions
– Switch-disconnector and– Make-proof earthing switch
• Operation via gas-tight welded-inmetal bellows at the front of theswitchgear vessel
Three-position switch-disconnector
1 Three-position switch-disconnector
2 Coupling linkage
3 Switchgear vessel
4 Operating mechanism rocker
5 Detachable lever mechanism
6 Operating lever inserted
����
����
�����
� � � �
Switch positions
Detachable lever mechanismwith three-position switch-disconnector
SF6 insulation
For further details, please refer toCatalog HA 40.1 “SwitchgearTypes 8DJ and 8DH for SecondaryDistribution Systems up to 24 kV,Gas-Insulated (General Part)”
R-H
A4
1-0
12
ep
s
EARTHED
OPEN
CLOSED
Components
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 21
Busbars
Features
• Safe-to-touch as a result ofuse of metal covers
• Plug-in type
• Consisting of round-barcopper, insulated by means ofsilicone rubber
• Busbar joints with cross andend adapters, insulated bymeans of silicone rubber
• Insensitive to pollution andcondensation
• Switchgear extension orpanel replacement is possi-ble without gas work
• Special busbar connectionsto metering panels type ME1are possible. Connection tothe
– Cable connection bushingsof the adjacent panelor to the
– Busbar bushings
• Busbar arrangement in panelblocks within the switchgearvessel filled with gas
• Option screened busbar:– Field control by means of
electrically conductive layerson the silicone-rubberinsulation
– Installation of 4MC70 32current transformers is thuspossible
– Independent of the sitealtitude
• Option: Capacitive voltagedetecting system for thebusbar, refer also to theproduct range, pages 10to 15
����
����
�����
�
�
�
�
�
��
�
�
Insulated plug-in type busbarunscreened design
Top view
Busbar compartments over 2 panelswith busbar connections, busbar covers removed
R-H
A4
1-0
17
ae
ps
3
82
7
Busbar system
1 End adapter
2 Cross adapter
3 Busbar insulation of silicone rubber
4 Threaded bolt M12 / M16
5 Busbar, Cu, diameter 32 mm
6 Stopper
Switchgear vessel
7 Primary enclosure panel 1
8 Primary enclosure panel 2
9 Bushing
10 Capacitive tap at the bushings,earthed (standard)
Components
22 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
4MT3 * and 4MT8 * plug-in voltage transformers for panel types LS, TR, SE and ME3
Common features
• According to IEC 60 044-2/ VDE 0414-2
• Designed as single-pole voltage trans-formers, plug-in type
• Inductive type
• Climate-independent
• Secondary connection by means ofplugs inside the panel
• Connection with plug-in contact
• Installation behind metallic cover
Features type 4MT3
• Inside-cone system, metal-coated
Features type 4MT8
• Outside-cone system, metal-enclosed
• For deep cable compartment cover
Installation
• Safe-to-touch arrangement due tometallic cover
• Arrangement on the switchgearvessel for busbar metering:
– 4MT3 voltage transformer for paneltypes LS1V/LS2, SE1V/SE2, MS1V/ME3and LKV/LT1
• Arrangement at the cable connection:– 4MT8 voltage transformer, pluggable
on screened cable T-plug, for paneltypes LS1-V, LS2-V and TR-V (deepcable compartment cover required)
– 4MT8 voltage transformer, directlypluggable via adapter on the bushingwith plug-in contact (interface type “A”),for panel type TR-V (deep cable com-partment cover required)
����
����
�����
�
R-H
A4
1-0
20
ep
sR
-HA
41
-01
9e
ps
R-H
A4
1-0
18
ae
ps
Panel sectiontype LS2-V
1 4MT3 * for the busbar
2 4MT8 * at the cable connection
4MT8 plug-in voltage transformermounted on cable T-plug (in panel type LS1-V)
4MT3 plug-involtagetransformer(for the busbar)
4MT8 plug-involtagetransformer(at the cableconnection)
Technical data4MT3 * and 4MT8 * voltage transformers
Primary data
Max. equipment operatingvoltage Um (= 1.2 x UN)
12 kV
Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud
3.3/ 3 kV at 10 kV
3.6� 3 kV at 20 kV4.8/ 3 kV at 20 kV5.0� 3 kV at 20 kV6.0/ 3 kV at 20 kV6.6/ 3 kV at 20 kV
7.2/ 3 kV at 28 kV10.0/ 3 kV at 28 kV11.0/ 3 kV at 28 kV
Rated lightning impulsewithstand voltage Up
3.6 kV / 20 kV7.2 kV / 60 kV12 kV / 75 kV
Rated voltage factor (8 h) 1.9 x UN
Max. equipment operatingvoltage Um (= 1.2 x UN)
24 kV
Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud
13.8/ 3 kV at 38 kV15.0/ 3 kV at 38 kV
17.5/ 3 kV at 50 kV20.0/ 3 kV at 50 kV22.0/ 3 kV at 50 kV
Rated lightning impulsewithstand voltage Up
17.5 kv / 95 kV24 kV / 125 kV
Rated voltage factor (8 h) 1.9 x UN
* Disassembly is necessary in order to perform voltage tests on the switchgear on site (max. 80 % Ud)
Make Type Combination
Euromold (K) 400 TB/G(K) 440 TB, AGT 10/20
yes
nkt cables ASTS 10/630,ASTS 20/630
yes
PrysmianKabel undSysteme
FMCTs-400, FMCTg-400 yes
Make Type Combination
Südkabel SEHDT (13/23) yes
Südkabel SET (12/24) on request
Cooper DT 400 P yes
Tyco Electronics RSTI�L56xx for:
• 35-300 mm2
(M12)
• > 300 mm2
(M16)
on request(add.measures)
on request
Combination of 4MT8 * voltage transformers with cable T-plugs (screened, without metal housing)
Components
Secondary data for 4MT3 voltage transformers
Rated voltage 100/ 3 V110/ 3 V (option)
Rated voltage forauxiliary winding (option)
100/3 V110/3 V (option)
Rated thermallimit current(measuring winding)
6 A
Rated long-time thermalcurrent (8 h)
4 A
Rating VA 25 15 60 100 150
Class 0.2 0.5 0.5 1 1
Secondary data for 4MT8 voltage transformers
Rated voltage 100/ 3 V110/ 3 V (option)
Rated voltage forauxiliary winding (option)
100/3 V110/3 V (option)
Rated thermallimit current(measuring winding)
4 A
Rated long-time thermalcurrent (8 h)
4 A
Rating VA 15 15 30 30 100
Class 0.2 0.5 0.5 1 3
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 23
4MC63 three-phase current transformer for panel type LS
Features
• According to IEC 60 044-1/VDE 0414-1
• Designed as three-polering-core current transformer
• Free of dielectricallystressed cast-resin parts(due to design)
• Insulation class E
• Inductive type
• Climate-independent
• Secondary connection bymeans of a terminal stripinside the panel
Installation
• Arranged outside the switch-gear vessel on the bushingsof the cable connection
• Mounted at the factory
Other designs(option)
Three-phase current trans-former for protection equip-ment based on the current-transformer operation principle:
• 7SJ4x protection systemas definite-time overcurrentprotection
• Definite-time overcurrent pro-tection relay make SEG, typeWIP 1 or type WIC
Other values on request Other values on request
����
����
�����
�
R-H
A4
1-0
21
be
ps
R-H
A4
1-0
22
ep
s
4MC63 three-phasecurrent transformer
4MC63 three-phase current transformeron the bushings of the cable connection
Panel sectiontype LS1
1 4MC63 three-phasecurrent transformer
Technical data4MC63 10 three-phase current transformerfor IN � 150 A and ID = 630 A
Primary data
Max. equipment operatingvoltage Um
0.72 kV
Rated current IN A 150 100 75 50
Rated short-durationpower-frequency with-stand voltage (winding test)
3 kV
Rated thermal short-timewithstand current Ith
25 kA
Rated continuousthermal current ID
630 A
Transient overloadcurrent
1.5 x ID / 1 h
Rated peak withstandcurrent Idyn
unlimited
Secondary data
Rated current A 1 0.67 0.5 0.33
Rating VA 2.5 1.7 1.25 0.8
Rated current (option) 5 A
Current at ID 4.2 A
Protec- Classtion Overcurrent factorcore
10 P
10
4MC63 11 three-phase current transformerfor IN � 400 A and ID = 630 A
Primary data
Max. equipment operatingvoltage Um
0.72 kV
Rated current IN A 400 300 200
Rated short-durationpower-frequency with-stand voltage (winding test)
3 kV
Rated thermal short-timewithstand current Ith
25 kA
Rated continuousthermal current ID
630 A
Transient overloadcurrent
2 x ID / 0.5 h
Rated peak withstandcurrent Idyn
unlimited
Secondary data
Rated current A 1 0.75 0.5
Rating VA 4 3 2
Rated current (option) 5 A
Current at ID 1.575 A
Protec- Classtion Overcurrent factorcore
10 P
10
Components
24 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
4MC70 33 and 4MC70 31 cable-type current transformers for panel types LS, RK and TR
Features
• According to IEC 60 044-1/VDE 0414-1
• Designed as single-pole ring-core current transformers
• Free of dielectrically stressedcast-resin parts (due to design)
• Insulation class E
• Inductive type
• Climate-independent
• Secondary connection bymeans of a terminal stripinside the panel
• Only for shielded cables
Installation
• 4MC70 33 cable-type currenttransformer for panel type LS
• 4MC70 31 cable-type currenttransformer for panel typesRK and TR
• Arranged outside the switch-gear vessel around the cableat the panel connection
• Transformers mounted on asupporting plate at the fac-tory; final assembly aroundthe cables on site
• For double cable: 300 mmdeeper cable compartmentcover
Other values on request
* Max. 230 mm, depending onthe core data of the 4MC70 33cable-type current transformer,overall heights 170 and 285 mm(observe floor openings on page 36)
����
����
�����
�
�
�
R-H
A4
1-0
23
ae
ps
R-H
A4
1-0
25
ep
s
4MC70 31 cable-typecurrent transformer
4MC70 33 cable-type current transformerfor the cables at the panel connection
Other values on request
Panel sectiontype LS1
Frontview
1 Cable-type current transformer2 Cable shield
Technical data4MC70 33 cable-type current transformer
Primary data
Max. equipment operatingvoltage Um
0.72 kV
Rated current IN 30 A to 600 A
Rated short-durationpower-frequency with-stand voltage (winding test)
3 kV
Rated thermal short-timewithstand current Ith
25 kA
Rated continuousthermal current ID
1.0 x IN
option: 1.2 x IN
Transient overloadcurrent
1.5 x ID / 1 h or2 x ID / 0.5 h
Rated peak withstandcurrent Idyn
unlimited
Secondary data
Rated current 1 A (option: 5 A)
Meas- Classuring Overcurrent factorcore
Rating
0.2 0.5 1
FS10 (option: FS5)
2.5 VA to 10 VA
Pro- Classtection Overcurrent factorcore
Rating
10 P 5 P
10 10
2.5 VA to 10 VA
Option: Secondary tap 1 : 2(e.g.150 A – 300 A)
Dimensions
Overall height H, mmdependent on thecore data
50 100 170 285
Outside diameter 145 mm
Inside diameter 55 mm
For cable diameter 50 mm
4MC70 31 cable-type current transformer
Primary data
Max. equipment operatingvoltage Um
0.72 kV
Rated current IN 50 A to 600 A
Rated short-durationpower-frequency with-stand voltage (winding test)
3 kV
Rated thermal short-timewithstand current Ith
25 kA
Rated continuousthermal current ID
1.0 x IN
option: 1.2 x IN
Transient overloadcurrent
1.5 x ID / 1 h or2 x ID / 0.5 h
Rated peak withstandcurrent Idyn
unlimited
Secondary data
Rated current 1 A (option: 5 A)
Meas- Classuring Overcurrent factorcore
Rating
1
FS5 (option: FS10)
2.5 VA to 10 VA
Option: Secondary tap 1 : 2
Dimensions
Overall height H 89 mm
Width x depth 85 mm x 114 mm
Inside diameter 40 mm
For cable diameter 36 mm
Components
4MC70 33 cable-typecurrent transformers,4 different overall heights
R-H
A4
1-0
24
ae
ps
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 25
Features
• Used exclusively forscreened busbars
• Preferably in combinationwith panel type ME2
• According to IEC 60 044-1/VDE 0414-1
• Designed as single-polering-core current trans-formers
• Free of dielectricallystressed cast-resin parts (dueto design)
• Insulation class E
• Inductive type
• Climate-independent
• Secondary connection bymeans of a terminal stripinside the panel
Installation
• Arranged outside theswitchgear vessel only onthe screened busbars
• Installation of the bus-typecurrent transformers eitherbetween the panels or alter-natively
• Supplied loosely (includingthe busbar connections), ifthe mounting position of thebus-type current transformerslies at the joint of a transportunit
4MC70 32 bus-type current transformer,mounted on screened busbars, in some casesbetween the panels
����
����
����
�
R-H
A4
1-0
26
ae
ps
R-H
A4
1-0
27
ep
s
4MC70 32 bus-typecurrent transformer
Other values on request * On request
4MC70 32 bus-type current transformers for panel type LT (for screened busbars only)
Panel sectiontype LT1
1 4MC70 32 bus-typecurrent transformer
Technical data4MC70 32 bus-type current transformer
Primary data
Max. equipment operatingvoltage Um
0.72 kV
Rated current IN 200 A to 600 A
Rated short-durationpower-frequency with-stand voltage (winding test)
3 kV
Rated thermal short-timewithstand current Ith
25 kA
Rated continuousthermal current ID
1.0 x IN
option: 1.2 x IN
Transient overloadcurrent
1.5 x ID / 1 h or2 x ID / 0.5 h
Rated peak withstandcurrent Idyn
unlimited
Secondary data
Rated current 1 A (option: 5 A)
Meas- Classuring Overcurrent factorcore
Rating
0.2 0.5 1
FS10 (option: FS5)
2.5 VA to 10 VA
Pro- Classtection Overcurrent factorcore
Rating
10 P 5 P *
10 10
2.5 VA to 15 VA
Option: Secondary tap 1 : 2(e.g. 150 A – 300 A)
Dimensions
Overall width B,dependent on thecore data
80 mm 150 mm
Outside diameter 125 mm
Inside diameter 55 mm
Components
26 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
4MA7 current transformers and 4MR voltage transformersfor air-insulated billing metering panels type ME1
Features
4MA7 current transformer
• According to IEC 60 044-1/VDE 0414-1
• Dimensions according toDIN 42600-8 (small design)
• Designed as single-poleindoor block-type currenttransformers
• Cast-resin insulated
• Insulation class E
• Secondary connection bymeans of screw-typeterminals
4MR voltage transformer
• According to IEC 60 044-2/VDE 0414-2
• Dimensions according toDIN 42600-9 (small design)
• Designed as indoorvoltage transformers:
– Type 4MR, single-pole– Option: Type 4MR, two-pole
• Cast-resin insulated
• Insulation class E
• Secondary connection bymeans of screw-typeterminals
Other values on request Other values on request
����
����
�����
�
R-H
A4
1-0
28
ep
s
4MR14 voltagetransformer
4MA7 currenttransformer
4MR voltage transformers and4MA7 current transformers installed inbilling metering panel type ME1
R-H
A4
1-0
29
ae
ps
R-H
A4
1-0
30
ae
ps
1 4MR voltage transformer2 4MA7 current transformer
Panel section type ME1
Technical data4MA7 single-pole current transformer
Primary data
Max. equipment operatingvoltage Um
12/ 24 kV17.5 kV
Rated short-durationpower-frequencywithstand voltage Ud
28/ 50 kV38 kV
Rated lightning impulsewithstand voltage Up
75/ 125 kV95 kV
Rated current IN 25 A to 600 A
Rated thermal short-timewithstand current Ith
up to 25 kA
Rated continuousthermal current ID
1.0 x IN
option: 1.2 x IN
Rated peak withstandcurrent Idyn
max. 2.5 x Ith
Secondary data
Rated current 1 A or 5 A
Meas- Classuring Overcurrent factorcore
Rating
0.2 0.5 1
FS5 or FS10
10 VA to 15 VA
Pro- Classtection Overcurrent factorcore
Rating
5 P or 10 P
10
5 VA to 15 VA
4MR single-pole voltage transformer
Primary data
Max. equipment operatingvoltage Um (= 1.2 x UN)
12 kV
Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud
3.3/ 3 kV at 10 kV
3.6/ 3 kV at 20 kV4.8/ 3 kV at 20 kV5.0/ 3 kV at 20 kV6.0/ 3 kV at 20 kV6.6/ 3 kV at 20 kV
7.2/ 3 kV at 28 kV10.0/ 3 kV at 28 kV11.0/ 3 kV at 28 kV
Rated lightning impulsewithstand voltage Up
3.6 kV / 20 kV7.2 kV / 60 kV
12 kV / 75 kV
Rated voltagefactor (8 h)
1.9 x UN
Max. equipment operatingvoltage Um (= 1.2 x UN)
24 kV
Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud
13.8/ 3 kV at 38 kV15.0/ 3 kV at 38 kV
17.5/ 3 kV at 50 kV20.0/ 3 kV at 50 kV22.0/ 3 kV at 50 kV
Rated lightning impulsewithstand voltage Up
17.5 kV / 95 kV24 kV / 125 kV
Rated voltagefactor (8 h)
1.9 x UN
Secondary data
Rated voltage 100/ 3 V110/ 3 V (option)120/ 3 V (option)
Rated voltage for auxiliarywinding (option)
100/3 V110/3 V (option)120/3 V (option)
Rating 20 VA 50 VA 100 VA
Class 0.2 0.5 1
Components
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 27
4MK * metal-enclosed combined transformersfor billing metering panels type ME2
Features
• 4MK * combinedtransformer, comprising
– 4MK1 combined currenttransformer
– 4MK3 combined voltagetransformer
• According to IEC 60 044-3/VDE 0414-5
• Designed as indoor trans-formers, single-polecombination
• Metal-enclosed
• Insulation class E
• Inductive type
• Secondary connection bymeans of screw-typeterminals
Panel type ME2
• For combination withleft-hand panels
– As individual panels or– As panel blocks (on request)
• For combination withright-hand panels as endpanels or panel blocks
Other values on request Other values on request
����
����
�����
�
4MK combined transformers installed inbilling metering panel type ME2
R-H
A4
1-0
31
ae
ps
R-H
A4
1-0
32
ep
s
4MK combinedtransformer
1 4MK3combinedvoltagetransformer
2 4MK1combinedcurrenttransformer
1
2
Panel section type ME2
1 4MK3 combined voltagetransformer
2 4MK1 combined currenttransformer
* Available only as a combination ofcurrent and voltage transformers
Technical data4MK1 combined current transformer
Primary data
Max. equipmen+toperating voltage Um
12 kV 24 kV
Rated short-durationpower-frequencywithstand voltage Ud
28 kV 50 kV
Rated lightning impulsewithstand voltage Up
75 kV 125 kV
Rated current IN 50 A to 600 A
Rated thermal short-timewithstand current Ith
up to 25 kA
Rated continuousthermal current ID
1.0 x IN
option: 1.2 x IN
Rated peak withstandcurrent Idyn
max. 2.5 x Ith
Secondary data
Rated current 1 A or 5 A
Meas- Classuring Overcurrent factorcore
Rating
0.2 0.5 1
FS5 or FS10
10 VA to 15 VA
Pro- Classtection Overcurrent factorcore
Rating
10 P
10
5 VA or 15 VA
Secondary multiratio option
4MK3 combined voltage transformer
Primary data
Max. equipment operatingvoltage Um (= 1.2 x UN)
12 kV
Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud
3.3/ 3 kV at 10 kV
3.6/ 3 kV at 20 kV4.8/ 3 kV at 20 kV5.0/ 3 kV at 20 kV6.0/ 3 kV at 20 kV6.6/ 3 kV at 20 kV
7.2/ 3 kV at 28 kV10.0/ 3 kV at 28 kV11.0/ 3 kV at 28 kV
Rated lightning impulsewithstand voltage Up
3.6 kV / 20 kV7.2 kV / 60 kV12 kV / 75 kV
Rated voltagefactor (8 h)
1.9 x UN
Max. equipment operatingvoltage Um (= 1.2 x UN)
24 kV
Rated voltage UN at max.rated short-durationpower-frequencywithstand voltage Ud
13.8/ 3 kV at 38 kV15.0/ 3 kV at 38 kV
17.5/ 3 kV at 50 kV20.0/ 3 kV at 50 kV22.0/ 3 kV at 50 kV
Rated lightning impulsewithstand voltage Up
17.5 kV / 95 kV24 kV / 125 kV
Rated voltagefactor (8 h)
1.9 x UN
Secondary data
Rated voltage 100/ 3 V110/ 3 V (option)
Rated voltage for auxiliarywinding (option)
100/3 V110/3 V (option)
Rating 30 VA 75 VA 150 VA
Class 0.2 0.5 1
Components
28 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Cable connection
Features
• Bushings with outside cone
• Uniform cable connectionheight 575 mm
• With cable bracket, e.g.type C40 according toDIN EN 50 024
• Access to the cable compart-ment only if the feeder hasbeen isolated and earthed
Special features
– In ring-main panels– In circuit-breaker panels– In cable panels:
• With bolted contact (M16)as interface type “C”according to EN 50181/DIN EN 50181
• For thermoplastic-insulated cables
• For paper-insulatedmass-impregnated cableswith adapter systems
• For conventional cablesealing ends via elbowadapter AKE 20/630(make Siemens)
• For cable T-plugs or cableelbow plugs with bolted con-tact (M 16)
• For connection cross-sections up to 300 mm²(standard)
• Cable routing downwards,cable connection at front
• For rated normal currents of400/630 A
– In transformer panels:
• With plug-in contact asinterface type “A”according to EN 50 181/DIN EN 50 181
• For cable elbow plugswith plug-in contact
• For thermoplastic-insulated cables
• For connection cross-sections up to 120 mm²
• For rated normal currentsof 200 A
Options
See figures on the right
* Cable plugs, cable sealing endsand cable clamps are notincluded in the scope of supply
Cable connections inring-main panels
1 Prepared for cableplugs with boltedcontact (M16)
2 Phase L1:Make Euromold,type K400 LB ascable elbow plug
3 Phase L2:Make Euromold,type K400 TB ascable T-plug
4 Phase L3:Make Euromold,type AGT 20/630 ascable T-plug
For options A, B, Cand E, see below
Cable connection · Examples
Cable plugs withbolted contact (M16)
Cable compartment, as-deliveredcondition *
L1 L2 L3 L3L2L1
Cable compartment,as-delivered condition *
Cable plugs withbolted contact (M16)
Cable connections incircuit-breaker panels
5 Prepared for cableplugs with boltedcontact (M16)
6 Phase L1:Elbow adapter,make Siemens,type AKE 20/630
7 Phase L2:Make Euromold,type K400 TB ascable T-plug
8 Phase L3:Make Euromold,type AGT 20/630 ascable T-plug
For options A, B, C,E and F, see below
L2L1L3L2L1
R-H
A4
1-0
33
ep
s
R-H
A4
1-0
34
ep
s
R-H
A4
1-0
35
ep
s
R-H
A4
1-0
36
ep
s
R-H
A4
1-0
37
ep
s
R-H
A4
1-0
38
ep
s
L3L2L1 L3L2L1
Cable elbow plugs withplug-in contact
Cable compartment,as-delivered condition *
Cable connections intransformer panels
9 Prepared for cableelbow plugs with plug-incontact
10 Phase L1:Make Euromold,type AWGL
11 Phase L2:Make Euromold,type K158 LR
12 Phase L3:Make Euromold,type AGW 20/250(with metal housing)
For options A, D and F,see below
Options
A Mounted cable clamps
B Short-circuit / earth-fault indicator
C Double cable connection withcorresponding cable plugs anddeep cable compartment cover
D Bushings as interface type “C” according toEN 50 181 / DIN EN 50 181 for cable plugs with bolted contact (M16)
E Suitable for connection of plug-in surge arresters in conjunction withcorresponding cable T-plugs
F Suitable for connection of 4MT8 metal-enclosed voltagetransformers in conjunction with corresponding cable T-plugs;deep cable compartment cover is required
L3
1
3
4
5
7
8
6
109
11
12
2
Components
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 29
Low-voltage equipment
Low-voltage compartment *
• Overall height– Standard 600 mm– Option 900 mm
• Partitioned safe-to-touch fromthe high-voltage part of thepanel
• Installation on the panel:– Standard for circuit-breaker
panel type LS and bus section-alizer with switch-disconnectortype LT1
– Option for all other paneltypes, depending on thescope of the secondaryequipment
• For accommodation of protec-tion, control, measuring andmetering equipment, e. g.suitable for multifunction pro-tection device SIPROTEC 47SJ63
• Electronic control boardof the multifunction protec-tion device SIPROTEC 4 7SJ63with the following features:
1 User-programmable LEDswith application-specific label,for displaying any desiredprocess and equipment data
2 LCD for process andequipment data, e.g. for
– Measuring and meteringvalues
– Binary information on status ofswitchgear and switchingdevice
– Protection data– General indications– Alarms
3 Keys for navigation in themenus and for entering values
4 Four user-programmablefunction keys for frequentlyperformed actions
Low-voltage niche
• Only inside billing meteringpanels type ME1
• Option: For accommodation,e.g. of voltage transformer,m.c.b.s
Low-voltage cables
• Control cables of the panel tothe low-voltage compartmentare connected via multi-pole,coded module plug connectors
• Option: Plug-in bus wires frompanel to panel are routed inthe separate wiring duct onthe panel
* Door hinge on the left (standard)
Low-voltage compartment
Low-voltage compartmentof a circuit-breaker paneltype LS
Electronic control board withmultifunction protection deviceSIPROTEC 4 7SJ63
R-H
A4
1-0
41
ae
ps
R-H
A4
1-0
39
ae
ps
R-H
A4
1-0
40
ep
s
Open low-voltage compartmentwith (optional) equipment
Low-voltage niche
R-H
A4
1-0
42
ep
s
Low-voltage niche of abilling metering panel type ME1with open cover
1 Low-voltageniche
2 Equipment(option)
1 LEDs
2 LCD
3 Navigation keys
4 Function keys
1
2
3
1
4
2
Components
30 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Ring-main, cable, transformer and circuit-breaker panels as individual panels
Cable panel type K:
1 Option: Earthing function
2 Interlock of cable compartment coverif earthing function is available
3 Cable compartment cover screwed on (without earthing function)
4 Cover screwed on
* Option:With low-voltage compartment
** Dependent on the type ofcable plug
*** Available mounting depthfor low-voltage equipment
**** Option: With highlow-voltage compartment 900 mm
Dimensions
����
����
����
�
�����������
���
���
���
���
���
���
�����
����
���
����
�����
����
��
���
����
����
�
���
��
�
Circuit-breaker paneltype LS1
����
����
����
�
����
��� �����������
���
���
���
���
���
���
�����
���
����
����
�
��
����
�����
����
��
���
�
Circuit-breaker paneltype LS1 V/LS2
����
����
���
�
����
���
����
��
��� �����������
���
���
���
���
���
���
����
�����
���
���
���
�
Ring-main paneltype RK
����
����
���
�
����
��� ��������
���
���
���
���
���
���
�
�
����
�����
���
���
����
��
���
��
�
�
�
���Cable paneltype K
����
����
� ��
�
����
��� ������������
���
���
���
���
���
���
���
����
��
���
��
����
�����
���
�
�
Transformer paneltype TR 1
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 31
Ring-main, cable and transformer panels in panel blocks
Ring-mainpanel block type R-B2
Ring-mainpanel block type R-B3
Transformerpanel block type T-B2
Transformerpanel block type T-B3
Ring-main/transformerpanel block type RT-B2
Ring-main/transformerpanel block type 2RT-B3
Ring-main/transformerpanel block type 3RT-B4
Cable connection/transformerpanel block type KT-B2
Cable panel type K:
1 Option: Earthing function
2 Interlock of cable compartment coverif earthing function is available
3 Cable compartment cover screwed on(without earthing function)
4 Cover screwed on
* Option:With low-voltage compartment
Dimensions
����
����
����
���
��
���
����
�����
���
�� ��
�
�
����
����
����
���
������
����
�����
���
�� �� ��
�
�
����
����
����
���
��
����
����
�����
���
�� ��
���
����
���
�� �
����
����
����
�����
���
�� �� ��
�
����
����
����
���
��
���
����
�����
���
����
�
�
����
����
����
���
��
����
����
�����
���
�� �� ��
�
�
����
����
����
���
��
����
����
�����
���
�� �� �� ��
�
�
����
����
����
���
��
���
����
�����
���
���
�
�
�
�
�
32 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
����
����
����
�
���
����
��
��
����
���
����
�����
���
������
���
���
���
���
���
�
�
�
����
����
����
�
������
���
���
���
���
���
����
���
����
��
���
��
����
�����
���
�
�
�
Bus sectionalizers with circuit-breakers, bus sectionalizers with switch-disconnectors andbusbar voltage metering panel as individual panels
1 Cover screwed on
* Option: With low-voltage compartment
*** Available mounting depth forlow-voltage equipment
**** Option: With highlow-voltage compartment 900 mm
Dimensions
Voltage meteringpanel type MS1V/ME3
Bus sectionalizer withswitch-disconnector type LT2
����
����
����
�
����
���
����
����
�
��� ������
���
���
���
���
���
�����
��
����
�����
����
��
�
�
Bus sectionalizer withcircuit-breaker type LK/LT1
����
����
����
�
������
���
���
���
���
���
�����
����
���
����
����
�
���
��
����
�����
����
��
�
�
Bus sectionalizer withcircuit-breaker type LKV/LT1
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 33
����
����
���
�
������
���
���
���
���
���
���
����
��
��
����
���
����
�����
���
�
�
�
����
����
����
�
���
����
��
��
����
���
����
�����
���
������
���
���
���
���
���
�
�
�
����
����
� ��
�
������
��� ���
���
���
���
��
���
����
��
������
�
����
��
����
�����
���
�
�
Earthing paneltype SE
Earthing paneltype SE1V/SE2
Billing meteringpanel type ME2
Dimensions
* Option:With low-voltage compartment
1 Cover screwed on
* Option:With low-voltage compartment
*** Available mounting depthfor low-voltage equipment
1) Panel block on request
Metering panel combination
Billing metering panel type ME2 withindividual panel attached on the leftand panel block attached on the right(example)
Busbar earthing panelsas individual panels
Billing metering panel ME2 as individual panel andmetering panel combin. with billing metering panel
����
��
����
����
����
�
Only individualpanel or panel block, 1)
on the left
Billing meteringpanel
type ME2
Individual panelor panel block,on the right
Connectionat the busbar
Connectionat the busbar
34 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
����
����
� ��
�
����
���
����
��
���
��
����
�����
���
������
���
���
���
���
���
��� ���
��
����
�
�
�
�
����
����
� ��
�
����
���
����
��
���
��
����
�����
���
������
���
��� ���
��
����
������
�
�
�
�
����
����
���
�
����
���
����
�����
���
��� ���
���
����
��
��
���
���
���
��� �
���
��
������
��� ���
�
�
�
�
����
����
� ��
�
����
���
����
��
���
��
����
�����
���
������
���
���
���
���
���
��� ����
���
��
�
�
�
�
Billing metering panels type ME1... as individual panels
Dimensions
1 Cover/cable compartment cover screwed on
* Option:With low-voltage compartment
** Dimension for cable routing: 323 mm for combination ofpanel type ME1-K with pressure absorber duct
Billing metering paneltype ME1
Billing metering paneltype ME1-K
Billing metering paneltype ME1-KS
Billing metering paneltype ME1-S
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 35
Billing metering panels with individual panelsor panel blocks attached on the left and right (examples)
Connection inside the panel block:
* Only possible in the right-hand feeder
** Only possible in the left-hand feeder
Possible panel arrangements
The following types of individual panelsor panel blocks can be attached to billingmetering panels – on the right or left:
Possibility 1
• Types attached on the leftwith connection at the feeder
– Individual panel typeRK-U, K-U, TR-U, LS1-U or LS2-U
– Panel block typeR-B2 or R-B3 (in RK-U panel),T-B2 or T-B3 (in TR-U panel),RT-B2, 2RT-B3 or 3RT-B4 (in TR-U panel)or KT-B2 (in TR-U panel)
• Types attached on the rightwith connection at the busbar
– Individual panel typeRK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
– Panel block typeR-B2, R-B3, T-B2, T-B3, RT-B2, 2RT-B3, 3RT-B4or KT-B2
Possibility 2
• Types attached on the leftwith connection at the busbar
– Individual panel typeRK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
– Panel blocks cannot be attached
• Types attached on the rightwith connection at the feeder
– Individual panel typeRK-U, K-U, TR-U, LS1-U or LS2-U
– Panel block typeR-B2 or R-B3 (in RK-U panel),T-B2 or T-B3 (in TR-U panel),RT-B2, 2RT-B3 or 3RT-B4 (in RK-U panel)or KT-B2 (in K-U panel)
Possibility 3
• Types attached on the leftwith connection at the busbar
– Individual panel typeRK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
– Panel blocks cannot be attached
• Types attached on the rightwith connection at the busbar
– Individual panel typeRK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
– Panel block typeR-B2, R-B3, T-B2, T-B3, RT-B2, 2RT-B3, 3RT-B4or KT-B2
Metering panel combinations with billing metering panels type ME1...
Possiblity 1
Possiblity 2
Possiblity 3
���
����
!�
!�
!�!� !� !�
����
����
����
�
Billing meteringpanel
type ME1-S
Individual panelor panel block,on the right
Connectionat the busbar
Connectionat the busbar
Onlyindividual panel,
on the left
Dimensions
����
���
����
����
����
�
Individual panelor panel block,
on the left
Billing meteringpanel
type ME1
Individual panelor panel block,on the right
Connectionat the feeder *
Connectionat the busbar
����
���
!�
!�
!�!� !� !�
����
����
����
�
Onlyindividual panel,
on the left
Billing meteringpanel
type ME1
Individual panelor panel block,on the right
Connectionat the busbar
Connectionat the feeder **
36 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Floor openings (dimensions in red) and fixing points
• For billing meteringpanels
– Type ME1– Type ME1-K– Type ME1-S– Type ME1-KS– Type ME1-KK
• For transformerpanel blocktype T-B2
• For ring-mainpanel blocktype R-B2
• For ring-main/transformerpanel blocktype RT-B2
• For cable connection/transformerpanel blocktype KT-B2
1 Wall distance
2 Fixing frame (base) of an individual panel or panel block
3 Floor opening for high-voltage cables (and, if applicable,control cables)
4 Fixing points
5 For 4MC70 33 cable-type current transformer with outside diameter145 mm for arrangement beneath the panel
6 Position of the incoming cables for metering panels type ME1...
7 Position of the incoming cables for the feeder
8 Overall panel depth
B Cutout in the fixing frame for extended floor opening forpanel with cable-type current transformers
Dimensions
• For billing meteringpanelstype ME2
• For circuit-breakerpanel types LS1 and LS2each with cable-typecurrent transformers
• For circuit-breaker panel typesLS1 and LS2 for ring-main pan-els type RK1 each without ca-ble-type current transformers
• For transformerpanels type TR1
• For bus sectionalizer with cir-cuit-breaker type LK and bussectionalizer with switch-dis-connector type LT
• For busbar earthingpanel type SE2
• For busbar voltagemetering panel type ME3
• For ring-main panelstype RK
• For cable panelstype K
• For busbar earthingpaneltype SE
Standard (for special versions, see pages 38 and 39)
����
����
����
�
���
�
����
���
���
��
���
��
��
���
���
���
���
���
����
�
��
��
�
���
���
���
���"���
���"��� �
�
�
�
�
����
�����
For individual panels
����
���
���
� �������
���
��
���
��
��
����
���
���
���
�����
���
���
��
��
���
�����
��
���
������������
���
���"���
���"��� �
�
�
�
�
��
��
���
���
�
���
For panel blocks
�������
����
��
���
��
��
���
���
���
���
���
����
�
��
��
�
���
���
����
����
����
�
���
�����
��
��
������������
���
���"���
���"��� �
�
�
�
�
��
��
���
���
�
���
For panel block
�����
��
��
���
��
��
���
���
���
���
����
�
��
��
�
������
����
����
����
�
���"���
���"��� �
�
�
�
�
���
For individual panels
�������
���
���
��
���
��
��
���
���
���
���
���
����
�
��
���
�
���
���
���
��
��
����
����
����
�
���
���
���
�� ���
���"���
���"��� �
�
�
�
�
�
�
���
For individual panels
�������
���
���
��
���
��
��
���
���
���
���
���
����
�
��
��
�
������
����
����
���
�
���
���"���
���"��� �
�
�
�
�
�
��
���
���
���
For individual panels
�������
���
���
��
���
��
��
���
���
���
���
���
����
�
�� ���
����
����
����
�
���
���"���
�
�
�
�
���"���
��
��
���
��� ��
���
�
For individual panels
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 37
Floor openings (dimensions in red) and fixing points
• For trans-formerpanel blocktype T-B3
• For ring-main/transformerpanel blocktype 3RT-B4
• For ring-mainpanel blocktype R-B3
• For ring-main/transformerpanel blocktype 2RT-B3
Dimensions
1 Wall distance
2 Fixing frame (base) of an individual panel or panel block
3 Floor opening for high-voltage cables (and, if applicable, control cables)
4 Fixing points
7 Position of the incoming cables for the feeder
8 Overall panel depth (including cable compartment cover)
9 Fixing support
B Cutout in the fixing frame for extended floor opening forpanel with cable-type current transformers
� ��� ��� ���� ���
���
����
���
����
#��
�
� $%"&���
Example for fixingpanels on the floor
� ��� ��� ���� ���
����
���
����
�
�
�
����"���
Detail “A”
���
�
�������
����
��
���
��
��
���
���
���
���
���
����
�
��
��
�
����
���
����
����
����
�
���
�����
�����
��
������������
���
������
���
���"���
���"��� �
�
�
�
�
���� ����
���
��� ��
For panel block
���
�
����
���
���
� �������
����
��
���
��
��
���
���
���
���
���
����
�
��
��
�
����
���
�����
��� ��� ����� ��
������������
���
������
���
������
���
���"���
���"��� �
�
�
�
�
��������
���
��� ��
����
For panel block
���
�
���
���
����
���
���
� �������
����
��
���
����
���
���
���
���
���
����
�
��
��
�
���
���
�����
�����
���
������������
���
������
���
���"���
���"��� �
�
�
�
�
��������
��
For panel blocks
38 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Floor openings (dimensions in red) and fixing points
Dimensions
• For ring-main panelstype RK
• For cable panelstype K
Legends and footnotes see page 39Special versions
• For ring-main panelstype RK
• For cable panelstype K
• For ring-main panelstype RK1
• For circuit-breaker panelstype LS1 and LS2
• For ring-main panelstype RK
• For cable panelstype K
• For ring-main panelstype RK1
• For circuit-breaker panelstype LS1 and LS2
• For ring-main panelstype RK
• For cable panelstype K
For individual panels with double cable connection (panel depth 1075 mm), 300 mm deeper cable compartment cover
• For ring-main panelstype RK1
• For circuit-breaker panelstype LS1 and LS2
�������
���
���
��
���
��
��
���
���
���
���
���
����
�
�
���
����
����
����
�
���
���
��
��
�����
���
���
�����
���"���
�
�
�
�
���"���
��� ��
�
���
�
For individual panels with cable-type current transformersor surge arresters
��
���
���
��
���
��
��
���
���
���
�
���
����
�
�� ���
����
����
����
�
���
���"���
�
�
�
���"���
�
��
�
��� ��
����
�
���
���
���
���
�
���
�������
���
���
���
���
��
��
���
���
���
���
���
����
�
�� �������
����
����
�
���
���"���
�
�
�
�
���"���
�
���
�
���
��
����
�
��
���
���
�
For individual panels with double cable connection (panel depth 880 mm), 105 mm deeper cable compartment cover
�������
���
���
���
����
��
��
���
���
���
��
���
����
�
�
���
����
����
����
�
���
��
���
���
����
�
���
���"���
�
�
���"���
�
�
�
��
��
���
���
�
����
���
��
���
���
��
���
��
��
���
���
���
����
����
�
�� �������
����
����
�
���
���"���
�
�
�
�
���"���
�
��
�
��� ��
����
���
���
���
�
For individual panels with double cable connection or surge arresters make Tyco Electronics, type RDA 24(panel depth 775 mm), standard or 25 mm deeper cable compartment cover
���
��
���
���
�������
���
���
���
���
��
��
���
���
���
���
���
����
�
�� �������
����
����
�
���
���"���
�
�
���"���
�
���
�
���
��
���
����
�
�
�
�
�������
���
���
���
����
��
��
���
���
���
��
���
����
�
�
���
����
����
����
�
���
��
���
���
���
���
����
�
���"���
�
�
���"���
��
�
�
�
��
���
���
����
�
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 39
Special versions in combination with pressure absorber system
• For ring-main panelstype RK and RK1
• For cable panelstype K
• For circuit-breaker panelstype LS1 and LS2
• For transformer panelstype TR
• For ring-main panelstype RK and RK1
• For cable panelstype K
• For circuit-breaker panelstype LS1 and LS2
• For ring-main panelstype RK and RK1
• For cable panelstype K
• For circuit-breaker panelstype LS1 and LS2
• For ring-main panelstype RK and RK1
• For cable panelstype K
• For circuit-breaker panelstype LS1 and LS2
• For transformer panelstype TR, however connec-tion with bolted contact(M16)
Dimensions
Floor openings (dimensions in red) and fixing points
1 Wall distance
2 Fixing frame (base) of an individual panel orpanel block
3 Floor opening for high-voltage cables (and, ifapplicable, control cables)
4 Fixing points
7 Position of the incoming cables for the feeder
8 Overall panel depth (including cable compartment cover)
10 Position of 2nd cable
11 For surge arrester
12 For cable-type currenttransformers with outsidediameter up to 90 mm
13 Pressure absorber duct
14 Front edge of base of the pressure absorber system
15 Front edge of panel without cable compartment cover
* Dependent on the type of cable plug employed
** For panel types RK, K and LS
*** For panel types TR, connection with plug-in contact
� Cutout in the fixing frame for extended floor openingfor panel with cable-type current transformers
��
�����
�
���
���
��
���
���
���
����
����
����
�
��� �
����
���
���
���"��� �
�
�
�
����
�
���
���
���
����
��
���
����� ���
For individual panels with single cable connection
��
���
���
���
���"��� �
�
�
�
���
��
��
���
���
������
����
���
�
���
����
�
��
���
���
���
���
���
����
�
���
����� ���
For individual panels with double cable connectionstandard or 25 mm deepercable compartment cover
����
���
����
���
���
��
���
���
�������
����
����
�
��� �
����
���"��� �
�
���
�
���
����
�
���
��� ��
��
�
��
���
����
����� ���
For individual panels with double cable connection300 mm deeper cable compartment cover
��
���
���
���
���"��� �
�
�
�
���
��
����
���
�
��
����
����
����
�
���
���
�
��
���
���
���
���
���
� ���
�
��
���
����� ���
For individual panels with double cable connection105 mm deeper cable compartment cover
40 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
1 Elbow adapter, make Siemens,type AKE 20/630 withconventional cable sealing end,make Lovink Enertech, type IAE 20
2 Cable T-plug, make Euromold,type (K)400 TB/G
3 Cable T-plug, make Euromold,type (K)400 TB/G
4 Cable T-plug, make Euromold,type (K)400 TB/G as 2nd cable(option: Cable elbow plugtype (K)400 LB/G);always same make required
5 Surge arrester,make Euromold,type 300 SA-5 or 300 SA-10
6 Cable plug,make Euromold,type 430 TB
7 Cable plug,make Tyco Electronics,type RICS 5139
8 Surge arrester,make Tyco Electronics,type RDA 21 (for type RDA 24,a floor opening of 635 mminstead of 610 mm is required)
9 Cable T-plug,make Südkabel,type SET (12/24)
and
10 Surge arrester,make Südkabel,type MUT (13/23)
or:
9 Cable connector,make nkt cables, type AB 24-630
and
10 Surge arrester,make nkt cables, type ASA 24-5
11 Cable T-plug, make Euromold,type (K)400 TB/G
12 Surge arrester, e.g.make Euromold,type 400 Pbor similar designs
13 Busbar systemfor billing metering paneltype ME1
14 Cable T-plug,make nkt cables, type CB 24-630
15 Coupling connector,make nkt cables, type CC 24-630
16 Cable T-plug,make Euromold, type (K)400 TB/G
17 4MT8 plug-in voltage transformer
18 Cable T-plug,make Südkabel,type SET 24
19 Coupling insert,make Südkabel,type KU 23.2
Cable connection examples in ring-main, cable and circuit-breaker panels(non-binding examples, for further examples see Catalog HA 40.1)
Dimensions
����
����
����
�
������ �
���
�����
������
���
����
�� �
����
�� ���
������
�
���
������
������
���� ��
����
����
����
�
���
�����
���
�������
������
����
����
����
�
�
���
������
�����
������
���
����
����
���
�
��
���
�� ���
������
����������
������
����
����
����
���
�
��
��
���
���
������
����
����
����
�
���
��������
����
���
���������
���
��
����
����
����
�
��
���
������
�����
������
�����
����
�� �
�����
�� ���
������
�
���
������
������������
����
�� �
�����
�� ��� ��
���
�
������
���� ������
Cable connection withsurge arresters
Connection incircuit-breaker panel
Cable connection inring-main panel
Standard cable compartment coverStandard cable compartment cover
Standard cable compartment coverStandard cable compartment cover Standard cable compartment cover
25 mm deepercable compartment cover
105 mm deepercable compartment cover
150 mm deepercable compartment cover
150 mm deepercable compartment cover
300 mm deeper cable compartmentcover for double cable connection
* Max. mounting spacefor cable plugs
** Dependent on the typeof cable plug
*** Dimension for bushing asinterface type “C” withbolted contact (M16)
**** Mounting depth forcombination of cable T-plugand surge arrester
����
���
���
�
������
������
� ��
�����
���
�
�����
Standard cable compartment cover
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 41
Overview of standards (July 2007)
Standards
Standards, specifications, guidelines
IEC standard VDE standard EN standard
Switchgear 8DH10 IEC 60 694 VDE 0670-1000 EN 60 694
IEC 62 271-200 VDE 0671-200 EN 62 271-200
Switching devices Circuit-breaker IEC 62 271-100 VDE 0671-100 EN 62 271-100
Disconnector andearthing switch
IEC 62 271-102 VDE 0671-102 EN 62 271-102
Switch-disconnector IEC 60 265-1 VDE 0670-301 EN 60 265-1
Switch-disconnector /fuse combination
IEC 62 271-105 VDE 0671-105 EN 62 271-105
HV HRC fuses IEC 60 282-1 VDE 0670-4 EN 60 282
Voltage detecting systems IEC 61 243-5 VDE 0682-415 EN 61 243-5
Degree of protection – IEC 60 529 VDE 0470-1 EN 60 529
Insulation – IEC 60 071 VDE 0111 EN 60 071
Instrument transformers Current transformers IEC 60 044-1 VDE 0414-1 EN 60 044-1
Voltage transformers IEC 60 044-2 VDE 0414-2 EN 60 044-2
Combined transformers IEC 60 044-3 VDE 0414-5 EN 60 044-3
Installation – IEC 61 936-1 VDE 0101 –
Standards
The 8DH10 switchgearcomplies with the relevantstandards and specificationsapplicable at the time oftype tests.
In accordance with theharmonization agreementreached by the countries of theEuropean Community, theirnational specificationsconform to the IEC standard.
Dielectric strength
See also Catalog HA 40.1“Standards”.
Terms
“Make-proof earthing switches”are earthing switches withshort-circuit making capacityaccording to IEC 62 271-102/VDE 0671-102.
Protection against solid for-eign objects, electric shockand ingress of water
The switchgear types 8DH10fulfill acc. to the standards
the following degrees of pro-tection (for explanations re-garding the degrees of protec-tion, please refer to Catalog HA40.1, page 38)
Climate and ambientconditions
8DH10 switchgear types arefully enclosed and insensitive toclimatic conditions.
• Climatic tests fulfilled inaccordance with IEC 60 932(report)
• All medium-voltage devices(except for HV HRC fuses)are installed in a gas-tight,welded stainless steelswitchgear vessel which isfilled with SF6 gas
• Live parts outside the switch-gear vessel are provided withsingle-pole enclosure
• At no point can creepagecurrents flow from high-voltage potentials to earth
• Operating mechanism partswhich are functionally impor-tant are made of corrosion-proof materials
• Bearings in operating mech-anisms are designed as dry-type bearings and do notrequire lubrication
• Suitable instrument trans-former designs
• Plug-in busbar system,insulated or screened
• Operating conditions accord-ing to IEC 62 271-200,among other, relative airhumility: 95 %(24-hour mean value)
• Metering panel ME1(air-insulated) according toIEC 60 694: “Normal operat-ing conditions”
Type of service location
8DH10 switchgear can beused as indoor installations inaccordance with IEC 61 936(Power installations exceeding1 kV AC) and VDE 0101:
• Outside lockable electricalservice locations at placeswhich are not accessible tothe public. Enclosures ofswitchgear can only beremoved with tools.
• Inside lockable electricalservice locations. A lockableelectrical service location is aplace outdoors or indoors thatis reserved exclusively forhousing electrical equipmentand which is kept under lockand key. Access is restrictedto authorized personnel andpersons who have been prop-erly instructed in electricalengineering. Untrained orunskilled persons may onlyenter under the supervision ofauthorized personnel or prop-erly instructed persons.
Internal arc classification(option)
The possibility of arc faults ingas-insulated switchgear type8DH is improbable and a merefraction of that typical of earlierswitchgear types, due to:
• Use of gas-filled switchgearcompartments
• Use of suitable switchingdevices such as three-position switches with make-proof earthing switch
• Logical mechanical interlocks
• Use of metal-coated voltagetransformers and three-phasering-core current transformers.
Optionally, switchgear type8DH can be designed with in-ternal arc classification:
• Internal arc classification IAC
• Type of accessibility A(for authorized personnelonly)
• Accessible sides– Side F (front)– Side L (lateral)– Side R (rear) as an option for
switchgear with pressureabsorber
• Arc test current up to 21 kA /1 s
IEC 60 694 VDE 0670-1000DIN EN 60 694
IEC 62 271-200
VDE 0671-200
IEC 60 529 DIN EN 60 529
Degree ofprotection
Type ofprotection
IP 2X(standard)
Live parts under highvoltage in switchgearwith HV HRC fuses
Degree ofprotection
Type ofprotection
IP 3X(option)
Enclosure of live partsunder high voltage inswitchgear withlocking device
IP 3XD(on request)
Live parts under highvoltage in switchgearwith locking device
IP 65 Live parts under highvoltage in switchgearwithout HV HRC fuses
42 Siemens HA 41.11 · 2007
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Standards, Transport
Transport
8DH10 switchgear is deliveredin transport units containingindividual panels or severalpanels.
The following must be noted:
• Transport facilities on site
• Transport dimensions andweights
• Size of door openings inbuilding
Packing
Place of destination insideGermany or other Europeancountries
• Means of transport:Rail and truck
• Type of packing:– Panels on open pallets– Open packing with PE
protective foil
Place of destination overseas
• Means of transport:Ship
• Type of packing:– Panels on open pallets– In closed crates with sealed
upper and lower PE protectivefoil
– With desiccant bags– With sealed wooden base– Max. storage time: 6 months
Transport data, classification
Classification of 8DH10 switchgear according to IEC 62 271-200
Design and construction
Partition class PM (metallic partition)
Loss of service continuity category 1)
Panels– With HV HRC fuses– Without HV HRC fuses
LSC 2ALSC 2B
Accessibility to compartments(enclosure)
– Busbar compartment– Switching-device compartment– Low-voltage compartment– Cable compartment 2)
– Panel without HV HRC fuses– Panel with HV HRC fuses (TR…)– Panel type K– Panel without cable connection
(e.g. type RK-U, LS1-U)
Access option
– Tool-based– Non-accessible– Tool-based
– Interlock-controlled– Interlock-controlled– Tool-based– Interlock-controlled and tool-based
Internal arc classification (option)
Designation ofinternal arc classification IACfor
– Wall-standing arrangement (standard)– Free-standing arrangement (option)
Rated voltage 7.2 kV to 24 kV
IAC A FL 21 kA, 1 sIAC A FLR 21 kA, 1 s
Type of accessibility A
– F– L– R
Switchgear in closed electrical service location,access “for authorized personnel only“ (acc. to IEC 62 271-200)FrontLateralRear (for free-standing arrangement)
Arc test current Up to 21 kA
Test duration 1 s
1) The loss of service continuitycategory is always refered to thecomplete switchgear, i.e. the panelwith the lowest category definesthe loss of service continuitycategory of the completeswitchgear.
2) For 8DH10 switchgear withpressure absorber:Access to cable compartment istool-based and interlock-controlled.For metering panels type ME1... :Access to cable compartment istool-based.
Switchgear Type 8DH10, up to 24 kV, Gas-Insulated, Extendable
Siemens HA 41.11 · 2007 43
Responsible for
Technical contents:Christoph MaulSiemens AG, Dept. PTD M 2 PPMErlangen
General editing:Gabriele PollokSiemens AG, Dept. PTD CC MErlangen
Notes
If not stated otherwise on theindividual pages of this catalog,we reserve the right to includemodifications, especiallyregarding the stated values,dimensions and weights.
Drawings are not binding.
All product designations usedare trademarks or productnames of Siemens AG or othersuppliers.
If not stated otherwise, alldimensions in this catalog aregiven in mm.
For questions concerning
Power Transmission and Distribution:
You can contact our Customer Support
Center 24 hours a day, 365 days a year.
Tel.: +49 180/524 70 00
Fax: +49 180/524 24 71
(Charges depending on provider)
E-Mail: [email protected]
www.siemens.com/energy-support
Siemens AG
Power Transmission and Distribution
Medium Voltage Division
Postfach 32 40
91050 Erlangen
Germany
www.siemens.com/
medium-voltage-switchgear
Subject to change without noticeOrder No.: E50001-K1441-A101-A7-7600Printed in GermanyDispo 31606KG 10.07 7.0 40 En102773 6101/6487
The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.
The required features should therefore be specified in each individual case at the time of closing the contract.