ErP Ecodesign for RVUs CASE STUDY
I t is not just about efficiency
CASE STUDY | ECODESIGN RVUs
+ other benefits:
The heat exchanger is very important part of the calculation.
There are two main parameters of the heat exchanger:
Efficiency combined with balanced pressure drop. Both
parameters are important. Pressure drop even more.
Why?
Case: Residential unit RVU 250
New legislation, ErP VU 1235/2014 Ecodesign for residential units (RVUs) brings ranking of these
units into the energy class according to the SEC calculation.
In the first RVU 250, there is used RSP+10 plastic counter flow heat exchanger with spacing 3.2 mm (81.5 %/70 Pa). In the second one, there is the Competitor plastic counter flow heat exchanger with lower spacing (83.3 %/115 Pa).
• In some cases smaller fans can be used or higher static pressure is available• Larger spacing means approx. 10 % less used pre-heating power• Lower risk of freezing• Higher year efficiency (depends on climatite used)• Easier condensate drain
Conclusion: In this case the � rst RVU 250 with the lower e� ciency heat exchanger achieves the noise level lower by -1 dB (A) compared to the second one and slightly better SEC level (If this would be on the edge between two classes this can decide).
RVU with Competitor´s HEXRVU with RSP+10...-32
[m3/h]
0 50 100 150 200 250 300
RVU 250 – characteristic with di� erent heat exchangers
Stat
ic p
ress
ure
avai
labl
e [P
a]
200
100
400
500
300
0
[m3/h]
0 50 100 150 200 250 300
RVU 250 – consumption with di� erent heat exchangers
[W]
40
20
80
100
120
140
60
0
AV = 200 m3/hLWA = 35 dB(A)P = 92 WEff. = 81.5 %SEC = -38.64 kWh/(m2a) *A
AV = 200 m3/hLWA = 36 dB(A)P = 108 WEff. = 83.3 %SEC = -37.95 kWh/(m2a) *A
RSP+10-300-32
Competitor´s HEX
PRE-10 %