Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett, Jamie Thompson, Brian Vinci, and Norman McCowan

Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 2: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Conflicting Goals

• 25 to 35 mg/L CO2 concentration begins to reduce rainbow trout

• CO2 removal requires contacting large volumes of air with cascading water

• Heating & cooling costs increase with increased cascade column ventilation

Page 3: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Air Ventilation Considerations %

CO

2 Str

ippi

ng P

er P

ass

Inlet Stripping Gas CO2 (ppm)

0

10

20

30

40

50

60

70

0 2000 4000 6000

G:L=1G:L=5G:L=10

Page 4: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

125 Tonne/yr WRAS Module

Page 5: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Design of Bell Aquaculture Growout WRAS for Yellow Perch

• 26 m3/min (6,900 gpm) total water recirculating flow rate in each WRAS – 85 HP energy for water recirculation

• Pumping, aeration, drum filtration, oxygenation

– 30 minute culture tank retention time – 2,300 gpm/tank – 20 to 40 gpm makeup flow per WRAS

Page 6: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Trout & Salmon Production Tanks (10.7 m ɸ x 3.05 tall; 260 m3 culture volume)

24-hr light and feeding every 2 hrs

Page 7: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

CO2 Production & Removal • CO2 produced in culture tank & biofilter • CO2 removed during plunge into sidewall box

Page 8: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

CO2 Stripping Across Gas Balancing Unit

Page 9: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

CO2 Stripping Depends on Packing Height and Air:Water (G:L) %

CO

2 Rem

oval

Packing Height (m)

0102030405060708090

100

0.0 0.5 1.0 1.5 2.0 2.5

G/ L=1

G/ L=5

G/ L=10

Design Target

Page 10: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Ventilation Fan on CO2 Stripping Column

• Variable Frequency Drive (VFD) used to adjust fan motor speed and air flow ventilated through stripping columns in each RAS

• Observational data collected from all tanks in two identical RAS modules – fan speed adjusted using VFD to three set-points

• 20, 30, & 50 hz – 15.5˚C water temp – 1300 to 1500 ppm CO2 in room air

Page 11: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Culture Tank CO2 Depends on Daily Feed Load and Fan Speed

0

5

10

15

20

25

30

35

40

45

0.0 100.0 200.0 300.0 400.0

Diss

olve

d CO

2, m

g/L

Daily Feed Rate in a Culture Tank, kg/d

50 hz

30 hz

20 hz

Page 12: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Culture Tank CO2 Depends on Tank Specific Feed Load and Fan Speed

• Feed and Fan Speed significantly affect CO2 in the culture tank (ANCOVA, P < 0.01) – CO2 stripping across cascade aeration column

• 45±1% at 50 hz • 24±1% at 30 hz • Not measured at 20 hz (but very little stripping)

– 15± 6% CO2 stripped across sidewall box plunge

Fan - 50 hz Fan - 30 hz Fan - 20 hz

Feed, kg/d CO2, mg/L CO2, mg/L CO2, mg/L 150 22 28 38 200 25 31 NA

Page 13: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Culture Tank CO2 Depends on Daily Feed Load and ∆O2 across Culture Tank

RAS #1 Fan - 50 hz

RAS #4 Fan - 30 hz

Tank - Heavy Feed, kg/d 292 299 CO2, mg/L 31.3 35.8 ∆O2, mg/L 16.0 13.9

Tank - Medium Feed, kg/d 210 230 CO2, mg/L 24.8 32.8 ∆O2, mg/L 11.2 11.5 Tank - Light Feed, kg/d 96 115 CO2, mg/L 20.0 26.5 ∆O2, mg/L 6.8 7.7

Page 14: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Air Ventilated out the Stripping Column Requires Energy

Control Strategy: Set VFD on CO2 stripper exhaust fans to achieve target CO2 removal. The associated makeup air units are ran from a building pressure controller. Maintain building pressure neutral to slightly negative.

Page 15: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Air Ventilated out the Stripping Column Significantly Affects Energy

• CO2 Exhaust fan energy in Row 3* Full Capacity-81,000 cfm (60hz)= $29,025 Yr 85% Capacity-68,850 cfm (51hz)= $17,760 Yr 55% Capacity-45,000 cfm (33hz)= $6,450 Yr

• Associated Makeup Air Cost in Row 3* 100% 69,000 cfm= $226,500 Yr 85% 58,522 cfm= $192,000 Yr 55% 38,250 cfm= $125,000 Yr • Based on ASHRAE weather bin data for Fort Wayne, IN.; $0.07 kWh electric rate; $0.90 therm NG rate;

water set point 15 C; Room set point 15.56 C

Page 16: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Design Conclusions • Ventilation fans must operate near full-speed to

control CO2 at 25 mg/L in culture tanks when a tank is operated at ≈ 200 kg/d feed – Reduced air flow creates problems at high feed load – Air flow can be reduced to save energy when tank

CO2 levels are below 25 mg/L • Real time monitoring of pump sump CO2 concentration

could be used in a feed-back control loop to adjust ventilation rate to minimize building air exchange

Page 17: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,

Design Conclusions-Energy • Even small reductions in exhaust rates can have

significant influence on operational costs. – VFD’s are essential on the CO2 stripper exhaust fans

and on the makeup air units.

Page 18: Case Study: CO2 Removal and Stripping Column Ventilation ...€¦ · Case Study: CO 2 Removal and Stripping Column Ventilation at Bell Aquaculture Steven Summerfelt, Jacob Bartlett,