Cascaded Two-Level Inverter-Based Multilevel

Embed Size (px)

Citation preview

  • 7/23/2019 Cascaded Two-Level Inverter-Based Multilevel

    1/9

    IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 3, JUNE 2014 993

    Cascaded Two-Level Inverter-Based Multilevel

    STATCOM for High-Power ApplicationsN. N. V. Surendra Babu, Member, IEEE, and B. G. Fernandes, Member, IEEE

    AbstractIn this paper, a simple static var compensating

    scheme using a cascaded two-level inverter-based multilevel in-verter is proposed. The topology consists of two standard two-levelinverters connected in cascade through open-end windings of athree-phase transformer. The dc-link voltages of the inverters areregulated at different levels to obtain four-level operation. The

    simulation study is carried out in MATLAB/SIMULINK to pre-

    dict the performance of the proposed scheme under balanced andunbalanced supply-voltage conditions. A laboratory prototype isdeveloped to validate the simulation results. The control schemeis implemented using the TMS320F28335 digital signal processor.

    Further, stability behavior of the topology is investigated. Thedynamic model is developed and transfer functions are derived.

    The system behavior is analyzed for various operating conditions.

    Index TermsDC-link voltage balance, multilevel inverter,

    power quality (PQ), static compensator (STATCOM).

    I. INTRODUCTION

    T HE application of flexible ac transmission systems(FACTS) controllers, such as static compensator(STATCOM) and static synchronous series compensator

    (SSSC), is increasing in power systems. This is due to their

    ability to stabilize the transmission systems and to improve

    power quality (PQ) in distribution systems. STATCOM is pop-ularly accepted as a reliable reactive power controller replacing

    conventional var compensators, such as the thyristor-switched

    capacitor (TSC) and thyristor-controlled reactor (TCR). This

    device provides reactive power compensation, active power

    oscillation damping, flicker attenuation, voltage regulation, etc.

    [1].

    Generally, in high-power applications, var compensation is

    achieved using multilevel inverters [2]. These inverters consist

    of a large number of dc sources which are usually realized by

    capacitors. Hence, the converters draw a small amount of active

    power to maintain dc voltage of capacitors and to compensate

    the losses in the converter. However, due to mismatch in con-duction and switching losses of the switching devices, the ca-

    pacitors voltages are unbalanced. Balancing these voltages is a

    major research challenge in multilevel inverters. Various con-

    trol schemes using different topologies are reported in [3][7].

    Among the three conventional multilevel inverter topologies,

    Manuscriptreceived February 07,2012; revisedJune 27, 2012, June19, 2013,and October 02, 2013; accepted February 04, 2014. Date of publication March

    04, 2014; dateof current versionMay 20, 2014. Paper no. TPWRD-00127-2012.The authors are with the Electrical Engineering Department, Indian Institute

    of Technology Bombay, Mumbai, Maharashtra 400076, India (e-mail: suren-

    [email protected]; [email protected]).

    Digital Object Identifier 10.1109/TPWRD.2014.2305692

    cascade H-bridge is the most popular for static var compensa-

    tion [5], [6]. However, the aforementioned topology requires a

    large number of dc capacitors. The control of individual dc-link

    voltage of the capacitors is difficult.

    Static var compensation by cascading conventional multi-

    level/two level inverters is an attractive solution for high-power

    applications. The topology consists of standard multilevel/two-

    level inverters connected in cascade through open-end wind-

    ings of a three-phase transformer. Such topologies are popular

    in high-power drives [8]. One of the advantages of this topology

    is that by maintaining asymmetric voltages at the dc links of the

    inverters, the number of levels in the output voltage waveformcan be increased. This improves PQ [8]. Therefore, overall con-

    trol is simple compared to conventional multilevel inverters.

    Various var compensation schemes based on this topology are

    reported in [10][12]. In [10], a three-level inverter and two-

    level inverter are connected on either side of the transformer

    low-voltage winding. The dc-link voltages are maintained by

    separate converters. In [11], three-level operation is obtained by

    using standard two-level inverters. The dc-link voltage balance

    between the inverters is affected by the reactive power supplied

    to the grid.

    In this paper, a static var compensation scheme is proposed

    for a cascaded two-level inverter-based multilevel inverter. Thetopology uses standard two-level inverters to achieve multilevel

    operation. The dc-link voltages of the inverters are regulated at

    asymmetrical levels to obtain four-level operation. To verify the

    efficacy of theproposed control strategy, the simulation study is

    carried out for balanced and unbalanced supply-voltage condi-

    tions. A laboratory prototype is also developed to validate the

    simulation results.

    From the detailed simulation and experimentation by the au-

    thors, it isfound that the dc-link voltages of two inverters col-

    lapse for certain operating conditions when there is a sudden

    change inreference current. In order to investigate the behavior

    of the converter, the complete dynamic model of the system isdeveloped from the equivalent circuit. The model is linearized

    and transfer functions are derived. Using the transfer functions,

    systembehavior is analyzed for different operating conditions.

    This paper is organized as follows: The proposed control

    schemeis presented in Section II. Stability analysis of the con-

    verter is discussed in Section III. Simulation and experimental

    results are presented in Sections IV and V, respectively.

    II. CASCADED TWO-LEVEL INVERTER-BASED

    MULTILEVELSTATCOM

    Fig. 1 shows the power system model considered in this paper

    [13]. Fig. 2 shows the circuit topology of the cascaded two-level

    0885-8977 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.

    See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

  • 7/23/2019 Cascaded Two-Level Inverter-Based Multilevel

    2/9

    994 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 3, JUNE 2014

    inverter-based multilevel STATCOM using standard two-level

    inverters. The inverters are connected on the low-voltage (LV)

    side of the transformer and the high-voltage (HV) side is con-

    nected to thegrid. The dc-linkvoltages of the inverters are main-

    tained constant and modulation indices are controlled to achieve

    the required objective. The proposed control scheme is derived

    from the ac side of the equivalent circuit which is shown in

    Fig. 3. In the figure, and are the source voltages re-

    ferred to LV side of the transformer, and are the re-

    sistances which represent the losses in the transformer and two

    inverters, and are leakage inductances of transformer

    windings, and and are the output volt-

    ages of inverters 1 and 2, respectively. are the leakage

    resistances of dc-link capacitors and , respectively. As-

    suming and applying

    KVL on the ac side, the dynamic model can be derived using

    [14] as

    (1)

    Equation (1) represents the mathematical model of the cas-

    caded two-level inverter-based multilevel STATCOM in the

    stationary reference frame. This model is transformed to the

    synchronously rotating reference frame [14]. The - axes

    reference voltage components of the converter and are

    controlled as

    (2)

    (3)

    where is the -axis voltage component of the ac source and

    are - axes current components of the cascaded inverter,

    respectively. The synchronously rotating frame is aligned with

    source voltage vector so that the -component of the source

    voltage is made zero. The control parameters and are

    controlled as follows:

    (4)

    (5)

    The -axis reference current is obtained as

    (6)

    where and are the reference and actual

    dc-link voltages of inverters 1 and 2, respectively. The -axis

    reference current is obtained either from an outer voltage

    regulation loop when the converter is used in transmission-line

    voltage support [5] or from the load in case of load compensa-

    tion [16].

    Fig. 1. Power system and the STATCOM model.

    Fig. 2. Cascaded two-level inverter-based multilevel STATCOM.

    Fig. 3. Equivalent circuit of the cascaded two-level inverter-based multilevel

    STATCOM.

    A. Control Strategy

    The control block diagram is shown in Fig. 4. The unitsignals and are generated from the phase-locked

    loop (PLL) using three-phase supply voltages [14].

    The converter currents are transformed to the syn-

    chronous rotating reference frame using the unit signals. The

    switching frequency ripple in the converter current components

    is eliminated using a low-pass filter (LPF). From

    and loops, the controller generates axes reference volt-

    ages, and for the cascaded inverter. With these reference

    voltages, the inverter supplies the desired reactive current

    and draws required active current to regulate total

    dc-link voltage . However, this will not ensure that

    individual dc-link voltages are controlled at their respective

    reference values. Hence, additional control is required to regu-

    late individual dc-link voltages of the inverters.

  • 7/23/2019 Cascaded Two-Level Inverter-Based Multilevel

    3/9

    SURENDRA BABU AND FERNANDES: CASCADED TWO-LEVEL INVERTER-BASED MULTILEVEL STATCOM 995

    Fig. 4. Control block diagram.

    B. DC-Link Balance Controller

    The resulting voltage of the cascaded converter can be given

    as , where and .

    The active power transfer between the source and inverter de-

    pends on and is usually small in the inverters supplying var to

    the grid [1]. Hence, can be assumed to be proportional to .

    Therefore, the -axis reference voltage component of inverter-2

    is derived to control the dc-link voltage of inverter-2 as

    (7)

    The -axis reference voltage component of inverter-1 is ob-

    tained as

    (8)

    The dc-link voltage of inverter-2 is controlled at 0.366

    times the dc-link voltage of inverter-1 [9]. It results in

    four-level operation in the output voltage and improves the har-

    monic spectrum. Expressing dc-link voltages of inverter-1 and

    inverter-2 in terms of total dc-link voltage, as

    (9)

    (10)

    Since the dc-link voltages of the two inverters are regulated, the

    reference -axis voltage component is divided in between the

    two inverters in proportion to their respective dc-link voltage as

    (11)

    (12)

    For a given power, if

    increases and

    decreases. Therefore, power transfer to inverter-2 increases,

    while it decreases for inverter-1. The power transfer to

    inverter-2 is directly controlled, while for inverter-1, it is

    controlled indirectly. Therefore, during disturbances, the

    dc-link voltage of inverter-2 is restored to its reference quickly

    compared to that of inverter-1. Using and , the reference

    voltages are generated in stationary reference frame for

    inverter-1 and using and for inverter-2. The reference

    voltages generated for inverter-2 are in phase opposition to

    that of inverter-1. From the reference voltages, gate signals are

    generated using the sinusoidal pulse-width modulation (PWM)

    technique [15]. Since the two inverters reference voltages

    are in phase opposition, the predominant harmonic appears at

    double the switching frequency.

    C. Unbalanced Conditions

    Network voltages are unbalanced due to asymmetric faults or

    unbalanced loads [16]. As a result, negative-sequence voltage

    appears in the supply voltage. This causes a double supply fre-

    quency component in the dc-link voltage of the inverter. This

    double frequency component injects the third harmonic com-ponent in the ac side [17]. Moreover, due to negative-sequence

    voltage, large negative-sequence current flows through the in-

    verter which may cause the STATCOM to trip [16]. Therefore,

    during unbalance, the inverter voltages are controlled in such

    a way that either negative-sequence current flowing into the in-

    verter is eliminated or reduces the unbalance in the grid voltage.

    In the latter case, STATCOM needs to supply large currents

    since the interfacing impedance is small. This may lead to trip-

    ping of the converter.

    The negative-sequence reference voltage components of the

    inverter and are controlled similar to positive-sequence

    components in the negative synchronous rotating frame as [18]

    (13)

    (14)

    where are - axes negative-sequence voltage compo-

    nents of the supply and are - axes negative-sequence

    current components of the inverter, respectively. The control pa-

    rameters and are controlled as follows:

    (15)

    (16)

    The reference values for negative-sequence current components

    and are set at zero to block negative-sequence current

    from flowing through the inverter.

    III. STABILITYANALYSIS

    Considering the dc side of the two inverters in Fig. 3, the

    complete dynamics of the system are derived in the Appendix.

    The transfer function is as follows:

    (17)

  • 7/23/2019 Cascaded Two-Level Inverter-Based Multilevel

    4/9

    996 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 3, JUNE 2014

    and the transfer function is

    (18)

    where and are given in the

    Appendix.

    From the transfer functions (26) and (27), it can be observed

    that the denominator is a function of resistances ,

    reactances , and modulation indices

    and . Although the denominator includes an op-

    erating condition term , the product

    is always positive. Hence, the poles of transfer function always

    lie on the left half of the -plane. However, numerators of the

    transfer functions are functions of the operating conditions

    of and . The positions of zeros primarily de-

    pend on and . The sign of these variables changes

    according to the mode of operation. Therefore, zeros of the

    transfer functions shift to the right half of the -plane for certain

    operating conditions. This system is said to be nonminimum

    phase and there is a limit onachievable dynamic response[19].

    The system may exhibit oscillatory instability when there is a

    step change in reference for high controller gains. Therefore,

    the controller gains should be designed suitably to avoid the

    instability. This behavior is similar to that of the two-level

    inverter-based STATCOM [20], [21].

    The transfer function for 1.02 p.u.,

    (capacitive mode) is given in (19), shown at the bottom of the

    page. From (19), it can be observed that all poles as well as all

    zeros lie on the left half of the -plane for this operating condi-

    tion. Fig. 5 shows the frequency response of the transfer func-tion for the same operating condition. From

    the figure, it can be observed that the system has sufficient gain

    and phase margins for this operating condition. Fig. 6 shows an

    enlarged root locus of the transfer function

    when STATCOM is in inductive mode of operation. The reac-

    tive component is set at 0.75 p.u. and proportional gain

    is varied from 0 to 10. It can be seen that all poles lie on the

    left half of the -plane for this case as well. However, one zero

    shift to the right half and three zeros lie on the left half of the

    -plane. Moreover, it can be seen that closed-loop poles of the

    system shift to the right half of the -plane for high controller

    gains.

    IV. SIMULATION RESULTS

    The system configuration shown in Fig. 1 is considered for

    simulation. The simulation study is carried out using MATLAB/

    SIMULINK. The system parameters are given in Table I.

    Fig. 5. Frequency response at 1.02 p.u.,

    80 p.u., 60 p.u.

    Fig. 6. Root locus of the transfer function at 0.75p.u., 80 p.u., 60 p.u.

    TABLE ISIMULATIONSYSTEM PARAMETERS

    A. Reactive Power Control

    In this case, reactive power is directly injected into the gridby setting the reference reactive current component at a par-

    ticular value. Initially, is set at 0.5 p.u. At 2.0 s, is

    changed to 0.5 p.u. Fig. 7(a) shows the source voltage and

    converter current of the phase. Fig. 7(b) shows the dc-link

    voltages of two inverters. From the figure, it can be seen that the

    dc-link voltages of the inverters are regulated at their respective

    (19)

  • 7/23/2019 Cascaded Two-Level Inverter-Based Multilevel

    5/9

    SURENDRA BABU AND FERNANDES: CASCADED TWO-LEVEL INVERTER-BASED MULTILEVEL STATCOM 997

    Fig. 7. Reactive power control. (a) Source voltage and inverter current.

    (b) DC-link voltages of two inverters.

    reference values when the STATCOM mode is changed from ca-

    pacitive to inductive. Moreover, the dc-link voltage of inverter

    2 attains its reference value faster compared to that of inverter

    1 as discussed in Section II.

    B. Load Compensation

    In this case, the STATCOM compensates the reactive power

    of the load. Initially, STATCOM is supplying a current of 0.5

    p.u. At 2.0 s, the load current is increased so that STATCOM

    supplies its rated current of 1 p.u. Fig. 8(a) shows source voltage

    and converter current, while Fig. 8(b) shows the dc-link voltages

    of two inverters. The dc-link voltages are maintained at their

    respective reference values when the operating conditions are

    changed.

    C. Operation During the Fault Condition

    In this case, a single-phase-to-ground fault is created at

    1.2 s,on the phase ofthe HVside ofthe 33/11-kVtransformer.

    The faultis cleared after 200 ms. Fig. 9(a) shows voltages across

    the LV side of the 33/11-kV transformer. Fig. 9(b) and (c) shows

    the - axes components of negative-sequence current of the

    converter. These currents are regulated at zero during the fault

    condition.

    V. EXPERIMENTALRESULTS

    A scaled down laboratory prototype is developed for the val-

    idation of the proposed var compensation scheme. The exper-

    imental setup consists of two insulated-gate bipolar transistor

    (IGBT)-based two-level inverters connected in cascade on the

    LV side of the 6-kVA, 200/400-V, three-phase transformer. The

    Fig. 8. Load compensation. (a) Source voltage and inverter current.

    (b) DC-link voltages of two inverters.

    HV side of the transformer is connected to supply lines. The

    transformer has resistance and leakage reactance of 5.1% and

    3.6%, respectively. The control strategy is implemented using

    TMS320F28335. The switching frequency is set at 1.2 kHz. The

    dc-link voltages of inverters 1 and 2 are regulated at 88 V and

    32 V, respectively. The source voltage is kept at 70 V(rms). The

    reactive power is directly injected into the source by keeping

    the reference current at a particular value.

    A. Operation Under Balanced Voltage Conditions

    a) Capacitive Mode of Operation: Initially, STATCOM is

    set ina capacitive modeof operationby keeping at 7 A.The

    waveforms for this operating condition are shown in Fig. 10.

    Fig. 10(a) shows the source voltage and STATCOM current,

    while Fig. 10(b) shows dc-link voltages of the two inverters.

    Fig. 10(c) shows the harmonic spectrum of the STATCOM cur-

    rent. From the harmonic spectrum, it can be seen that the pre-

    dominant harmonic appears at double the switching frequency.

    b) Inductive Mode of Operation: In this case, the dynamic

    performance of the controller is verified by changing from 7

    A to 7 A. Fig. 11(a) shows the variation of dc-link voltages of

    two inverters. These voltages are maintained at their respective

    reference values and the experimental result resembles the sim-

    ulation result presented in the previous section. Fig. 11(b) shows

    the response of STATCOM current during this disturbance.

    B. Operation Under Unbalanced Voltage Conditions

    a) Without Negative-Sequence Controller: In this case,

    output of the STATCOM has only the positive-sequence volt-

    ages. Unbalance in the supply voltages is created by connecting

  • 7/23/2019 Cascaded Two-Level Inverter-Based Multilevel

    6/9

    998 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 3, JUNE 2014

    Fig. 9. Operation during fault. (a) Grid voltages on the LV side of the trans-

    former. (b) -axis negative-sequence current component . (c) -axis nega-

    tive-sequence current component .

    an inductor in the phase. The reference current is set at

    A. Fig. 12(a) shows the source voltages and converter currents.

    From the figure, it can be seen that the converter currents are un-

    balanced. Fig. 12(b) shows the dc-link voltages of the inverters.The waveforms pulsate at twice the supply frequency.

    b) With Negative-Sequence Controller: In this case, the

    negative-sequence controller represented by (13) and (14) is

    enabled along with the positive-sequence controller. The ref-

    erences for inverter negative-sequence current components

    and are set at zero. Therefore, the inverter supplies balanced

    currents as shown in Fig. 13(a). Fig. 13(b) shows the dc-link

    voltages of two inverters. The oscillations in the dc-link voltages

    of two inverters are reduced compared to those in Fig. 12(b).

    VI. CONCLUSION

    DC-link voltage balance is one of the major issues in cas-

    caded inverter-based STATCOMs. In this paper, a simple var

    Fig. 10. Experimental result: Capacitive mode of operation. (a) Source voltage(50 V/div) and STATCOM current (5 A/div). (b) DC-link voltages of inverter-1

    and inverter-2 (20 V/div). Time scale: 5 ms/div. (c) Harmonic spectrum ofcurrent.

    compensating scheme is proposed for a cascaded two-level in-

    verter-based multilevel inverter. The scheme ensures regulationof dc-link voltages of inverters at asymmetrical levels and reac-

    tive power compensation. The performance of the scheme is val-

    idated by simulation and experimentations under balanced and

    unbalanced voltage conditions. Further, the cause for instability

    when there is a change in reference current is investigated. The

    dynamic model is developed and transfer functions are derived.

    System behavior is analyzed for various operating conditions.

    From the analysis, it is inferred that the system is a nonmin-

    imum phase type, that is, poles of the transfer function always

    lie on the left half of the -plane. However, zeros shift to the

    right half of the -plane for certain operating conditions. For

    such a system, oscillatory instability for high controller gains

    exists.

  • 7/23/2019 Cascaded Two-Level Inverter-Based Multilevel

    7/9

    SURENDRA BABU AND FERNANDES: CASCADED TWO-LEVEL INVERTER-BASED MULTILEVEL STATCOM 999

    Fig. 11. Experimental result: Mode change from capacitive to inductive.

    (a) DC-link voltages of inverter-1 and inverter-2 (20 V/div). Time scale:100 ms/div. (b) Source voltage (100 V/div) and STATCOM current (5 A/div)

    in steady state. Time scale: 100 ms/div.

    APPENDIX

    From Fig. 3, the ac-side dynamics are derived as

    (20)

    where

    (21)

    where are modulation indices, are phase angles

    between inverters voltage and source voltage, and is the

    supply frequency in radians per second. Substituting (21) in

    (20), expressed in per unit

    (22)

    (23)

    Fig. 12. Operation under unbalanced voltage conditions and without the neg-

    ative-sequence controller: (a) Source voltages (20 V/div) and inverter currents(5 A/div). (b) DC-link voltages of inverter-1 and inverter-2 (20 V/div). Time

    scale: 5 ms/div.

    Fig. 13. Operation with a negative-sequence controller in capacitive mode of

    operation. (a) Source voltages (20 V/div) and inverter currents(5 A/div). (b) DClink voltages of inverter-1 and inverter-2 (20 V/div). Time scale: 5 ms/div.

  • 7/23/2019 Cascaded Two-Level Inverter-Based Multilevel

    8/9

    1000 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 3, JUNE 2014

    Equating power on both sides of the inverter, the dc-side dy-

    namics of two inverters in per unit, are derived as

    (24)

    (25)

    In the equations, (22)(25), , and rep-

    resent the per-unit quantities of , and

    , respectively. The dynamic equations (22)(25) are

    linearized, and transfer functions are derived. The transfer func-

    tion is as follows:

    (26)

    where

    The transfer function is

    (27)

    where and represent steady-state

    values.

    REFERENCES

    [1] N. G. Hingorani and L. Gyugyi, Understanding FACTS. Delhi, India:

    IEEE, 2001, Standard publishers distributors.[2] B. Singh, R. Saha, A. Chandra,and K. Al-Haddad, Staticsynchronous

    compensators (STATCOM): A review, IET Power Electron., vol. 2,

    no. 4, pp. 297324, 2009.[3] H. Akagi, H. Fujita, S. Yonetani, and Y. Kondo, A 6.6-kV trans-

    formerless STATCOM based on a five-level diode-clamped PWM con-verter: System design and experimentation of a 200-V 10-kVA labo-

    ratory model, IEEE Trans. Ind. Appl., vol. 44, no. 2, pp. 672680,Mar./Apr. 2008.

    [4] A. Shukla, A. Ghosh, and A. Joshi, Hysteresis current control opera-tion offlying capacitor multilevel inverter and its application in shunt

    compensation of distribution systems, IEEE Trans. Power Del., vol.22, no. 1, pp. 396405, Jan. 2007.

    [5] H. Akagi, S. Inoue, and T. Yoshii, Controland performance of a trans-

    formerless cascaded PWM STATCOM with star configuration, IEEETrans. Ind. Appl., vol. 43, no. 4, pp. 10411049, Jul./Aug. 2007.

    [6] Y. Liu, A. Q. Huang, W. Song, S. Bhattacharya, and G. Tan, Small-signal model-based control strategy for balancing individual dc capac-

    itor voltages in cascade multilevel inverter-based STATCOM, IEEE

    Trans. Ind. Electron., vol. 56, no. 6, pp. 22592269, Jun. 2009.[7] H. P. Mohammadi and M. T. Bina, A transformerlessmedium-voltage

    STATCOM topology based on extended modular multilevel con-verters, IEEE Trans. Power Electron., vol. 26, no. 5, pp. 15341545,

    May 2011.[8] X. Kou, K. A. Corzine, and M. W. Wielebski, Overdistention opera-

    tion of cascaded multilevel inverters, IEEE Trans. Ind. Appl., vol. 42,

    no. 3, pp. 817824, May/Jun. 2006.

    [9] K. K. Mohaptra, K. Gopakumar, and V. T. Somasekhar, A harmonicelimination and suppression scheme for an open-endwinding inductionmotor drive,IEEE Trans. Ind. Electron., vol. 50,no. 6,pp. 11871198,

    Dec. 2003.[10] Y. Kawabata, N. Yahata, M. Horii, E. Egiogu, and T. Kawabata, SVG

    using open winding transformer and two inverters, inProc., 35th An-

    nual IEEE Power Electron. Specialists Conf., 2004, pp. 30393044.

    [11] S. Ponnaluri, J. K. Steinke, P. Steimer, S. Reichert, and B. Buchmann,

    Design comparison and control of medum voltage STATCOM withnovel twin converter topology, inProc., 35th Annu. IEEE Power Elec-

    tron. Specialists Conf., 2004, pp. 25462550.[12] N. N. V. Surendra Babu, D. Apparao, and B. G. Fernandes, Asym-

    metrical dc link voltage balance of a cascaded two level inverter basedSTATCOM, inProc., IEEE TENCON, 2010, pp. 483488.

    [13] IEEE Criteria for Class IE Electric Systems, IEEE Standard 141-1993.

    [14] C. Schauder and H. Mehta, Vector analysis and control of advancedstatic VAr compensators, inProc. Inst. Elect. Eng. C., Jul. 1993, vol.

    140, no. 4, pp. 299305.[15] D. G. Holmes and T. A. Lipo, IEEE series on power engineering, in

    Pulse Width M odulation for Power Converters: Principles and Prac-tice. Piscataway, NJ, USA: IEEE, 2003.

    [16] B. Blazic and I. Papic, Improved D-statcom control for operation with

    unbalanced currents and voltages,IEEE Trans. Power Del., vol. 21,no. 1, pp. 225233, Jan. 2006.

    [17] A. Leon, J. M. Mauricio, J. A. Solsona,and A. Gomez-Exposito, Soft-ware sensor-based STATCOM control under unbalanced conditions,

    IEEE Trans. Power Del., vol. 24, no. 3, pp. 16231632, Jul. 2009.[18] Y. Suh, Y. Go, and D. Rho, A comparative study on control algorithm

    for active front-end rectifier of large motor drives under unbalanced

    input, IEEE Trans. Ind. Appl., vol. 47, no. 3, pp. 825835, May/Jun.2011.

    [19] K. Ogata, Modern Control Engineering, 4th ed. Delhi, India:Pearson, 2004.

    [20] K. R. Padiyar and A. M. Kulkarni, Design of reactive current andvoltage controller of static condenser, Elect. Power Energy Syst., vol.

    19, no. 6, pp. 397410, 1997.

  • 7/23/2019 Cascaded Two-Level Inverter-Based Multilevel

    9/9

    SURENDRA BABU AND FERNANDES: CASCADED TWO-LEVEL INVERTER-BASED MULTILEVEL STATCOM 1001

    [21] A. K. Jain, A. Behal, X. T. Zhang, D. M. Dawson, and N. Mohan,Nonlinear controllers for fast voltage regulation using STATCOMs,

    IEEE Trans. Power Del., vol. 21, no. 2, pp. 726735, Apr. 2006.

    N. N. V. Surendra Babu (S10M14) received theB.E. degree in electrical and electronics engineering

    from Andhra University, Visakhapatnam India, in

    1998, the M.Tech. degree in power and energysystems from Mangalore University, Mangalore,

    Karnataka, in 2000, and the Ph.D. degree in powerelectronics from the Indian Institute of Technology

    Bombay, Mumbai, India in 2013.His technical interests include power electronics,

    machines, and power-electronicinterfaces for renew-

    able energy sources.

    B. G. Fernandes (M13) received the B.Tech.degree in electrical engineering from Mysore Uni-

    versity, Mangalore, Karnataka, India, in 1984, the

    M.Tech. degree in power electronics and machinedrives from the Indian Instiute of Technology (IIT)

    Kharagpur in 1989, and the Ph.D. degree in powerelectronics and machine drives from the Indian

    Institute of Technology Bombay, Mumbai, in 1993.He then joined IIT Kanpur as an Assistant Pro-

    fessor. In 1997, he joined IIT Bombay where he iscurrently a Professor in the Department of Electrical

    Engineering. His current research interests are high-performance ac drives, mo-

    tors for electric vehicles, and power-electronic interfaces for nonconventionalenergy sources.